This instruction manual describes the control boards F5-Compact/General with special programming for split-cage blowers.
It is only valid together with the Instruction Manuals Part 1 and Part 2. Both Instruction Manuals must be made available
to the user. Prior to performing any work on the unit the user familiarize himself with the unit. This includes especially the
knowledge and observance of the safety and warning directions of Part 1. The pictographs used in this instruction manual
have following meaning:
Danger
Is used, if life or health of the user are endangered or substantial damage to pro-
Warning
perty can occur.
Caution
Attention
observe at Is used, if a measure is necessary for safe and trouble-free operation.
all costs
Information
Help Is used, if a measure simplifies the handling or operation of the unit.
Tip
The information contained in the technical documentation, as well as any user-specific advice in
spoken and written and through tests, are made to best of our knowledge and information about the
application. However, they are considered for information only without responsibility. This also applies
to any violation of industrial property rights of a third-party.
Inspection of our units in view of their suitability for the intended use must be done generally by the
user. Inspections are particulary necessary, if changes are executed, which serve for the further
development or adaption of our products to the applications (hardware, software or download lists).
Inspections must be repeated completely, even if only parts of hardware, software or download lists
are modified.
Application and use of our units in the target products is outside of our control and therefore
lies exclusively in the area of responsibility of the user.
Table Of Contents
4 Certifications................................................. 18
4.1 CE-Marking .................................................................18
4.2 Manufacturer´s Declaration ......................................18
4.3 UL / CUL - Marking .....................................................18
5. Passwords..................................................... 19
GB - 3
Installation and Connection
X2A
X2A
1. Control board F5-C/-G X2A
1.1 Assignment of 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
Terminal Strip
X2A
PIN Function Name Description
Analog inputs
1 + Setpoint input AN1+ Differential voltage input
0…10 VDC, 0…20 mA, 4…20 mA. Resolution / scan time
2 - Setpoint input AN1-
Active, if no fixed frequency is selected. General: 12 Bit / 1 ms
3 reserved AN2+ Compact: 11 Bit / 2 ms
No function
4 reserved AN1-
Analog outputs
Analog output of the output frequency
5 Analog output 1 ANOUT1 5 mA; Ri=100 Ω
0…10 V DC ^ 0…fmax (dep. on blower)
Resolution 12 Bit
Analog output of the apparent current
6 Analog output 2 ANOUT2
0…10 V DC ^ 0…2 x rated current
Voltage supply
7 +10 V Output CRF Reference voltage for setpoint potentiometer +10 VDC +5% / max. 4 mA
8
Analog ground COM Ground for analog in- and output
9
Digital inputs
10 I1 Terminals for the direction of rotation and blo-
Direction of rotation/blo-
11 I2 wer type selection. Assignment see „Digital in-
wer type
12 I3 puts“.
13…30 V DC ±0 % stabili-
Anti-pressure hunting
13 I4 Electronic anti-pressure hunting function zed
function
Ri=2,1 kΩ
14 Fixed frequency 1 F I1+I2 = fixed frequency 3
Scan time 1 ms
15 Fixed frequency 2 R no input = analog set value
16 Control release / Reset ST Power modules are enabled
17 Reset RST Reset; only when an error occurs
Transistor outputs
18 Overload protection O1 Transistor output switches on releasing of the electronic anti-pressure hun-
ting function.
19 Stall protection O2 Transistor output switches, if the mototr is overload or minimum frequency is
not reached (blower blocked).
Voltage supply
20 24 V-Output Uout Supply voltage for digital inputs/outputs (max. 100 mA)
21 20...30 V-Input Uin Voltage input for external supply
22
Digital ground 0V Reference potential for digital inputs/outputs
23
Relay outputs
GB - 4
Installation and Connection
GB - 5
Installation and Connection
1.3 Operator
As an accessory to the local or external (option: cable 00.F5.0C0-1xxx) operation an operator is necessary. To
prevent malfunctions, the inverter must be brought into nOP status before connecting / disconnecting the operator
(open control release). When starting the inverter, it is started with the last stored values or factory setting.
ENTER FUNC.
F/R SPEED
COMBIVERT
X6C X6D
Use only the operator interface for the serial data transfer according to RS232/485.
The direct connection, PC to the inverter is only valid with a special cable (part
number 00.F5.0C0-0001), otherwise, it would lead to the destruction of the PC-in-
terface !
RS 232 cable
Part number PC Operator
00.58.025-001D
Length 3 m
Housing (PE)
GB - 6
Operation of the Unit
Principally during a change, parameter values are immediately accepted and stored non-volatile. However, with
some parameters it is not useful that the adjusted value is accepted immediately. With these parameters (see
parameter overview) the adjusted value is accepted and stored non-volatile by pressing the ENTER key.
If a malfunction occurs during operation, the actual display is overwritten by the alarm message. The alarm mes-
sage in the display is reset by ENTER.
ENTER
With ENTER only the error message in the display is reset. The present error is displayed in the sta-
tus display (CP. 3). In order to reset the error itself, the cause must be removed or a power-on reset
must be made.
GB - 7
Parameter Description
GB - 8
Parameter Description
ENTER
Password
FUNC
ENTER
Password
FUNC
Co-domain Description
0…±400 Hz Display of the actual output frequency in Hz. Additionally the operator display "noP" and
"LS", even if the control release or direction of rotation are not switched (see CP.3). The
rotation of the inverter is indicated by the sign. Examples:
18.3 Output frequency 18,3 Hz, rotation forward
-18.3 Output frequency 18,3 Hz, rotation reverse
Co-domain Description
0…±400 Hz Display of actually set value. For control reasons the set speed is displayed, even if the
control release or direction of rotation are not switched. If no direction of rotation is set,
the set speed for clockwise rotation (forward) is displayed.
GB - 9
Parameter Description
Display Status
rAcc "Reverse Acceleration" drive accelerates with direction of rotation reverse.
rdEc "Reverse Deceleration" drive decelerates with direction of rotation reverse.
Fcon "Forward Constant" drive runs with a constant speed and direction of rotation forward.
rcon "Reverse Constant" drive runs with constant speed and direction of rotation reverse.
Other status messages are described at the parameters, where they occur (see chapter 4 „Error diagnosis“).
Co-domain Description
0…±6553.5 A Display of the actual apparent current in ampere.
Co-domain Description
0…±6553.5 A CP.5 makes is possible to recognize the max. apparent current. For that the highest value
of CP.4 is stored in CP.5 . The peak value memory can be cleared by pressing the UP,
DOWN or ENTER key or over bus by writing any value you like to the address of CP.5.
The switch off of the inverter also clears the memory.
Co-domain Description
0.0…200.00 % Display of the actual inverter rate of utilization in percent. 100% rate of utilization is equal
to the inverter rated current. Only positive values are displayed, meaning there is no dif-
ferentiation between motor and generatoric operation.
Display Description
0…1000 V Display of actual DC-link voltage in volt. Typical values:
V-class Normal operation Overvoltage (E.OP) Undervoltage (E.UP)
230 V 300…330 V DC approx. 400 V DC approx. 216 V DC
400 V 530…620 V DC approx. 800 V DC approx. 240 V DC
Display Description
0…1000 V CP.8 makes it possible to recognize short-time voltage rises within an operating cycle. For
that the highest value of CP.7 is stored in CP.8. The peak value memory can be cleared
by pressing the UP, DOWN or ENTER key or over bus by writing any value you like to the
address of CP.8. The switch off of the inverter also clears the memory.
Co-domain Description
0…778 V Display of the actual output voltage in volt.
GB - 10
Parameter Description
Co-domain Description
0…100 % This parameter displays the value of the analog signal in percent AN1 (X2A.1 / X2A.2). A
value of 0…±100 % corresponds to the setpoint selection (CP.26) 0…±10 V, 0…±20 mA
or 4…20 mA.
Co-domain Description
0…100 % The output voltage is load-adapted. Energy is saved by reduced voltage and an overhe-
ating of the motor is prevent.
This parameter displays the value in percent on which the current output voltage is redu-
ced referring to the output voltage in accordance with V/f characteristic.
Decimal
Input Function
value
1 X2A.16
2 X2A.17
4 X2A.14
8 X2A.15
16 X2A.10 Display of the currently controlled digital inputs. The logic levels are indicated at the
32 X2A.11 input terminals or at the internal inputs regardless of the following logic operations. A
64 X2A.12 certain decimal value is output for each digital input. If several inputs are controlled,
128 X2A.13 the sum of the decimal values is indicated.
256 internal A
512 internal B
1024 internal C
2048 internal D
Display Description
0…7 Display of actual blower type. The display is dependent on the wiring of the terminals
X2A.10…12 (see page 5). The values are assigned as follows:
Value Blower type Connection
0 Antrieb stillgesetzt –
170CM-Y, 250CM-Y, 340CM-Y, 500CM-Y, 700CM-Y,
�������������
1 1000CM-Y, 1400CM-Y, 1000CM-C, 1400CM-C, 2000CM-Y,
2800CM-Y, 5500CM-Y, 7500CM-Y, 8000CM-Y, 9500CM-Y
3 reseviert –
2000CM-CS, 2800CM-CS, 5500CM-C, 7500CM-C, 8000CM- �������������
4
C, 9500CM-C
5-7 reserviert –
GB - 11
Parameter Description
Decimal
Output Function
value
1 X2A.18
2 X2A.19
4 X2A.24…26
Display of the external and internal digital output set currently. A certain decimal
8 X2A.27…29
value is output for each digital output. If several outputs are set, the sum of the
16 internal A
decimal values is indicated.
32 internal B
64 internal C
128 internal D
Co-domain Description
0…150 °C This parameter displays the current power module temperature of the inverter.
Co-domain Description
0…255 This parameter stores the last occured error. E.UP is not stored. The error messages are
described in the chapter "Error Diagnosis".
Co-domain Description
0…255 This parameter stores all errors of the type E.OC „overcurrent“. The error messages are
described in the chapter "Error Diagnosis".
Co-domain Description
0…255 This parameter stores all errors of the type E.OL „overload“. The error messages are de-
scribed in the chapter "Error Diagnosis".
Co-domain Description
0…255 This parameter stores all errors of the type E.OP "overvoltage". The error messages are
described in the chapter "Error Diagnosis".
Co-domain Description
0…255 This parameter stores all errors of the type E.OH „overheating power module of the inver-
ter“. The error messages are described in the chapter "Error Diagnosis".
CP.21 Timer 1 display protection function overload or minimal frequency not reached
Co-domain Description
0.00…300.00 s Timer 1 starts as soon as the inverter starts to modulate. The timer is reset as soon as the
minimum frequency (blower dependent) is reached. Depending on the blower type this
can last max. upto. 300 s. E.EF is released on exceeding 300 s. Thus a blockade of the
blower is recognized.
After that timer 1 starts as soon as the rated motor current (blower dependent) is excee-
ded. The rated motor current is reset if the load decreases to the permissible level. E.EF is
released after expiration of timer 1 (300 s), in order to avoid overload and thus overheating
of the motor.
GB - 12
Parameter Description
Co-domain Description
0.00…300.00 s Timer 2 starts when „modulation off“. Timer 2 is reset as soon as load exceeds the level
for the electronic anti-pressure hunting function.
Description
The setpoint input 1 (AN1) can be triggered by various signal levels. In order to correctly evaluate the signal, this
parameter must be adapted to the signal source. The settings must be confirm by „ENTER“.
Value Setting Direction of rotation
0 x 0…±10 V DC / Ri = 56 kΩ
1 0…±20 mA DC / Ri = 250 Ω
2 4…20 mA DC / Ri = 250 Ω
f
�����
�����
UREF
�� ���
���� �����
���� �����
GB - 13
3. Error Assistance
At KEB COMBIVERT error messages are always represented with an "E." and the appropriate error in the
display. Error messages cause the immediate deactivation of the modulation. Restart possible only after reset or
autoreset.
GB - 14
Display COMBIVIS Value Meaning
Load-shunt relay has not picked up. occurs for a short time during the
switch-on phase, but must automatically be reset immediately. If the
error message remains the following causes may be applicable:
load-shunt defective
E.LSF Error ! Load shunt fault 15
input voltage wrong or too low
high losses in the supply cable
braking resistor wrongly connected or damaged
braking module defective
Motor temperature switch or PTC at the terminals T1/T2 is again in the
E.ndOH no ERROR drive overheat 11
normal operating range. The error can be reset now.
Temperature of the heat sink is again in the permissible operating range.
E.nOH no E. over heat pow.mod. 36
The error can be reset.
No longer overheating in the interior E.OHI, interior temperature has
E.nOHI no ERROR overheat int. 7
fallen by at least 3°C
No more overload, OL-counter has reached 0%; after the error E.OL
a cooling phase must elapse. This message appears after the cooling
E.nOL no ERROR overload 17
phase is completed. The error can be reset. The inverter must remain
switched on during the cooling phase.
Occurs, if the specified peak current is exceeded. Causes:
acceleration ramps too short
the load is too big at turned off acceleration stop and turned off constant
current limit
short-circuit at the output
E. OC Error ! Overcurrent 4
short-circuit at the output
deceleration ramp too short
motor cable too long
EMC
DC brake at high ratings active (see 6.9.3)
Error: Overtemperature of power module. Error can only be reset at
E.nOH. Causes:
E. OH Error ! Overheat pow.mod. 8 insufficient air flow at the heat sink (soiled)
ambient temperature too high
ventilator clogged
E.OH2 Error ! Motor protection 30 Electronic motor protective relay has tripped.
Error: Overheating in the interior: error can only be reset at E.nOHI, if
E.OHI Error ! Overheat internal 6
the interior temperature has dropped by at least 3 °C.
Error: Overload error can only be reset at E.nOL, if OL-counter reaches
0% again. Occurs, if an excessive load is applied longer than for the
permissible time (see technical data). Causes:
poor control adjustment (overshooting)
E. OL Error ! Overload (Ixt) 16
mechanical fault or overload in the application
inverter not correctly dimensioned
motor wrongly wired motor wrongly wired
encoder damaged
further on next side
GB - 15
Display COMBIVIS Value Meaning
Voltage in the DC-link circuit too high. Occurs, if the DC-link voltage
rises above the permissible value. Causes:
poor controller adjustment (overshooting)
E. OP Error ! Overvoltage 1 input voltage too high
interference voltages at the input
deceleration ramp too short
braking resistor defective or too small
E. Pu Error ! Power unit 12 Error: General power circuit fault
Error: During the initialization the power circuit could not be recognized
E.Puci Error ! Unknown power unit 49
or was identified as invalid.
Error: Power circuit identification was changed; with a valid power circuit
this error can be reset by writing to SY.3. If the value displayed in SY.3
E.Puch Error ! Power unit changed 50 is written, only the power-circuit dependent parameters are reinitialized.
If any other value is written, then the default set is loaded. On some
systems after writing Sy.3 a Power-On-Reset is necessary.
Error ! Power unit Error: Parameter value could not be written to the power circuit.
E.PUCO 22
communication Acknowledgement from LT <> OK
Error: Software version for power circuit and control card are different.
E.PUIN Error ! Power unit invalid 14
Error cannot be reset (only at F5-G B-housing)
It has been attempted to select a locked parameter set. Programmed
E.SEt Error ! Set 39
response „Error, restart after reset”.
Error: Undervoltage (DC-link circuit) Occurs, if the DC-link voltage falls
below the permissible value. Causes:
input voltage too low or instable
inverter rating too small
voltage losses through wrong cabling
the supply voltage through generator / transformer breaks down at very
E. UP Error ! Undervoltage 2
short ramps
at F5-G housing B E.UP is also displayed if no communication takes
place between power circuit and control card.
jump factor (Pn.56) too small
if a digital input was programmed as external error input with error
message E.UP (Pn.65).
E.UPh Error ! Phase failure 3 One phase of the input voltage is missing (ripple-detection)
GB - 16
GB - 17
Certifications
4 Certifications
4.1 CE-Marking
CE marked frequency inverter and servo drives were developed and manufactured to comply with the regulations
of the Low-Voltage Directive 73/23/EEC.
The inverter or servo drive must not be started until it is determined that the installation complies with 89/392/EEC
(machine directive) as well as the EMC-directive (89/336/EEC)(note EN 60204).
The frequency inverters and servo drives meet the requirements of the Low-Voltage Directive 73/231/EEC. The
harmonized standards of the series EN 50178 in connection with EN 60439-1 and EN 60146 were used.
This is a product of limited availability in accordance with IEC 61800-3. This product may cause radio interference
in residential areas. In this case the operator may need to take corresponding measures.
• Inverter is suitable for use on a circuit capable of delivering not more than 10 kA rms (symmetrical), 240 V AC
or 480 V AC maximum
• Maximum surrounding air temperature 45°C
• For control cabinet mounting as „Open Type“
• For use in a pollution degree 2 environment
• Motor protection by adjustment of current parameters
• Not incorporated with overspeed protection
• Tightening torques of the power circuit terminals (see documentation part 2)
• Tightening torques of the control circuit terminals 0,5 Nm
• Overload protection at 130 % of inverter output rated current (see type plate)
• Refer to this installation instructions for proper wiring
GB - 18
Passwords
5. Passwords
100 – –