Chilca Uno Enersur Chilca Uno Power Station ST Code D11 #270T818
Revision Date: 06/14/2012 Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
During starting of the steam turbine or while operating at no-load following loss of load, it is probable that that steam temperature will be high enough to cause excessively high exhaust hood temperatures. To avoid this undesirable condition, spray nozzles are provided in the low-pressure section of the steam turbine. These nozzles are supplied from the discharge of the condensate pump.
Revision Date: 06/14/2012 Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
The components controlling the flow of condensate to the spray nozzles consist of:
Exhaust Hood Water Spray Valve (AOV-WSV), Water Spray Strainer (WSS), Manual Water Spray Calibrating Valve Pressure Instruments PI-210E
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Exhaust Hood Temperature Sensor Flow Limit Valve Condensate Isolation Valve Automatic Water Spray Valve
To Operate System: Condensate available. Automatic Water Spray Control Valve set to: Begin opening at 135oF Fully open at 175oF Set Flow limit valve to maintain 40 psig on water spray supply header with Automatic and full condenser vacuum Allow Automatic WSV to control Exhaust Hood temperature.
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
The operation of the Exhaust Hood Water Spray system is fully automatic. The Mark VIe control system monitors exhaust hood temperature via 3 temperature transmitters (TE-210A/B/C).
High Temperature Trip - 107C (225F). High Temperature Alarm 93C (200F).
Condensate supply pressure is adjusted by means of WSCV. This pressure is set at 2.76 bar (40 psig) which corresponds to required system flow. This is achieved by adjusting WSCV to obtain 40 psig as read on PI-210E with AOV-WSV fully open.
Revision Date: 06/14/2012 Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!
Property of General Electric Energy Learning CenterCenter- Proprietary Information for Training Purposes Only!