Atmosphere : Industries.
Altitude Location B. Battery Charger
System Parameters (Incoming Power Supply) Voltage : 415 V 6% (-20% transient), 3 Phase 3wire Frequency : 50 Hz 5% Neutral : Solidly earthed Symmetrical fault level : 50kA for 1 Sec Miscellaneous Requirements Charger voltage range for Ni-Cd Battery Float Charger voltage per cell : Quick Charger voltage per cell : Mounting : Access : Cable entry : Earth bus : Separate bolted removable undrilled Gland plate for cable entry : g. Cable glands and lugs h. Painting :
1.40-1.42 Volt/Cell. 1.70 Volt/Cell. Free standing, Floor Mounted Front/Rear Bottom 25X6mm2 Copper Provided : Provided RAL 7032
i.
C. ECS Interface Normally open(NO) potential-free contacts wired up to terminal strip for connection to ECS interface, for the following conditions: Charger failure Battery Discharged Battery Isolated
EPCC-4 CPP PANIPAT NAPTHA CRACKER PROJECT, INDIAN OIL CORPORATION LTD. PMC- EIL
Max.: 46.6C, Min.:-0.7C Max.: 45C, Min.:10C (For battery sizing) 88% (Normal); 95% (Maximum) Dusty, tropical and corrosive as found in hydrocarbon Industries. (+) 238M above MSL Panipat
1.0 System Parameters (Incoming Power Supply) Voltage : 415 V 6% (-20% transient), 3 Phase 3wire Frequency : 50 Hz 5% Neutral : Solidly earthed Symmetrical fault level : 50kA for 1 Sec 2.0 Miscellaneous Requirements a. Charger voltage range for Ni-Cd Battery i. Float Charger voltage per cell : 1.40-1.42 Volt/Cell. ii. Quick Charger voltage per cell : 1.70 Volt/Cell. b. Mounting : Free standing, Floor Mounted c. Access : Front/Rear d. Cable entry : Bottom e. Earth bus : 25X6mm2 Copper f. Separate bolted removable undrilled Gland plate for cable entry : Provided g. Cable glands and lugs : Provided h. Painting : RAL 7032 i. Incoming Cable size : 2 Runs of 3C-120 Sq mm Al, Armoured Cable E. ECS Interface Normally open(NO) potential-free contacts wired up to terminal strip for connection to ECS interface, for the following conditions: Charger failure Battery Discharged Battery Isolated
EPCC-4 CPP PANIPAT NAPTHA CRACKER PROJECT, INDIAN OIL CORPORATION LTD. PMC- EIL
52-BC-09705A 52-BC-09705B Caldyne Automatics Limited 220V/403A 220V 403A 220V 1.4v/Cell 1.7v/Cell 1.4v/Cell to 1.42v/Cell 1.7v/cell 60% 80% 0.85 Less than 2% 2% Constant voltage with current limit Constant Current with close loop feedback control Close loop feedback control Close loop feedback control As per spec 1775+1775 900 2300 IP-42
Method of current control in float mode 13 Method of current control in quick mode 14 Safety factor used for selecting components 15 Charger Dimensions 15.1 Width (mm) 15.2 Depth (mm) 15.3 Height(mm) 16 Max heat loss in Watts 17 Degree of protection (IP)
EPCC-4 CPP PANIPAT NAPTHA CRACKER PROJECT, INDIAN OIL CORPORATION LTD. PMC- EIL
: Max.:46.6C, Min.:-0.7C : Max.:45C, Min.:10C(For battery sizing) : 88%(Normal); 95%(Maximum) : Dusty, tropical and corrosive as found in hydrocarbon Industries. : (+)238M above MSL : Panipat
415 V 6% (-20% transient), 3 Phase 3wire 50 Hz 5% Solidly earthed 50kA for 1 Sec
2. Miscellaneous Requirements a. Charger voltage range for Ni-Cd battery i. Float Charger voltage per cell : 1.40-1.42 Volt/Cell ii. Quick Charger voltage per cell : 1.70 Volt/Cell b. Mounting : Free standing, Floor Mounted c. Access : Front/Rear d. Cable entry : Bottom e. Earth bus : 25X6 mm2 Copper f. Separate bolted removable undrilled Gland plate for cable entry : Provided g. Cable glands and lugs : Provided h. Painting : RAL 7032 i. Incoming Cable size cable : 1Run of 3C-25 Sq mm Al, Armoured C. ECS Interface Normally Open (NO) potential-free contacts wired up to terminal strip for connection to ECS interface, for the following conditions: Charger failure Battery Discharged Battery Isolated DATA SHEET-BATTERY CHARGER FOR LIGHTING AND MISCELLANEOUS LOADS PART-II
EPCC-4 CPP PANIPAT NAPTHA CRACKER PROJECT, INDIAN OIL CORPORATION LTD. PMC- EIL
52-BC-09703 Caldyne Automatics Limited 220V/80A 220V 80A 220V 1.4v/Cell 1.7v/Cell 1.4v/Cell to 1.42v/Cell 1.7v/cell 60% 80% 0.85 Less than 2% 2% Constant voltage with current limit Constant Current with close loop feedback control Close loop feedback control Close loop feedback control As per spec 1275 700 1800 IP-42
Method of current control in float mode 13 Method of current control in quick mode 14 Safety factor used for selecting components 15 Charger Dimensions 15.1 Width (mm) 15.2 Depth (mm) 15.3 Height(mm) 16 Max heat loss in Watts 17 Degree of protection (IP)
EPCC-4 CPP PANIPAT NAPTHA CRACKER PROJECT, INDIAN OIL CORPORATION LTD. PMC- EIL
: Max.:46.6C,Min.:-0.7C : Max.:45C,Min.:10C(For battery sizing) : 88%(Normal);95%(Maximum) : Dusty,tropical and corrosive as found in hydrocarbon Industries. : (+)238M above MSL : Panipat
415 V 6% (-20% transient), 3 Phase 3wire 50 Hz 5% Solidly earthed 50kA for 1 Sec
2. Miscellaneous Requirements a. Charger voltage range for Ni-Cd battery i. Float Charger voltage per cell : 1.40-1.42 Volt/Cell. ii. Quick Charger voltage per cell : 1.70 Volt/Cell. b. Mounting : Floor Mounted c. Access : Front/Rear d. Cable entry : Bottom e. Earth bus : 25X6 mm2 Copper f. Separate bolted removable undrilled Gland plate for cable entry : Provided g. Cable glands and lugs : Provided h. Painting : RAL 7032 i. Incoming Cable size : 1 Run of 3C-95 AL, Armoured cable C. ECS Interface Normally open (NO) potential-free contacts wired up to terminal strip for connection to ECS interface, for the following conditions: Charger failure Battery Discharged Battery Isolated
EPCC-4 CPP PANIPAT NAPTHA CRACKER PROJECT, INDIAN OIL CORPORATION LTD. PMC- EIL
DATA SHEET-BATTERY CHARGER FOR SWITCHGEAR LOADS PART-II 1 2 3 4 4.1 4.2 4.3 5 5.1 5.2 6 7 8 8.1 8.2 9 10 10.1 10.2 11 11.1 11.2 12 Item no. as per MR/PR Tag no Manufacturers Name Rating Charging Rating Output Voltage Output Current Nominal Voltage Float Charging Quick Charging Float Charging Voltage Range Quick Charging Voltage Range Minimum efficiency of charger At light load (40%) At Rated load PF at rated voltage and load Max RMS ripple voltage content at rated load With battery connected Without battery connected Method of voltage control In float charging mode In Quick charging mode 52-BC-09702A 52-BC-09702B Caldyne Automatics Limited 220V/187A 220V 187A 220V 1.4v/Cell 1.7v/Cell 1.4v/Cell to 1.42v/Cell 1.7v/cell 60% 80% 0.85 Less than 2% 2% Constant voltage with current limit Constant Current with close loop feedback control Close loop feedback control Close loop feedback control As per spec 1475+1475 800 2000 IP-42
Method of current control in float mode 13 Method of current control in quick mode 14 Safety factor used for selecting components 15 Charger Dimensions 15.1 Width (mm) 15.2 Depth (mm) 15.3 Height(mm) 16 Max heat loss in Watts 17 Degree of protection (IP)
EPCC-4 CPP PANIPAT NAPTHA CRACKER PROJECT, INDIAN OIL CORPORATION LTD. PMC- EIL
: Max.:46.6C, Min.:-0.7C : Max.:45C, Min.:10C (For battery sizing) : 88%(Normal); 95%(Maximum) : Dusty, tropical and corrosive as found in hydrocarbon Industries. : (+)238M above MSL : Panipat
B. Battery Charger 1. System Parameters (Incoming Power Supply) Voltage : 415 V 6% (-20% transient), 3 Phase 3wire Frequency : 50 Hz 5% Neutral : Solidly earthed Symmetrical fault level : 50KA for 1 Sec 2. a. i. ii. b. Miscellaneous Requirements Charger voltage range for Ni-Cd battery Float Charger voltage per cell Quick Charger voltage per cell Mounting : 1.40-1.42 Volt/Cell. : 1.70 Volt/Cell. : Free standing, Floor
Mounted c. Access : Front/Rear d. Cable entry : Bottom e. Earth bus : 25X6 mm2 Copper f. Separate bolted removable undrilled Gland plate for cable entry : Provided g. Cable glands and lugs : Provided h. Painting : RAL 7032 i. Incoming Cable size : 3 Runs of 3C-120 Sq mm AL, Armoured cable C. ECS Interface Normally open (NO) potential-free contacts wired up to terminal strip for connection to ECS interface, for the following conditions: Charger failure Battery Discharged Battery Isolated
EPCC-4 CPP PANIPAT NAPTHA CRACKER PROJECT, INDIAN OIL CORPORATION LTD. PMC- EIL
52-BC-09701A 52-BC-09701B Caldyne Automatics Limited 220V/630A 220V 630A 220V 1.4v/Cell 1.7v/Cell 1.4v/Cell to 1.42v/Cell 1.7v/cell 60% 80% 0.85 Less than 2% 2% Constant voltage with current limit Constant Current with close loop feedback control Close loop feedback control Close loop feedback control As per spec 1775+1775 900 2300 IP-42
Method of current control in float mode 13 Method of current control in quick mode 14 Safety factor used for selecting components 15 Charger Dimensions 15.1 Width (mm) 15.2 Depth (mm) 15.3 Height(mm) 16 Max heat loss in Watts 17 Degree of protection (IP)
EPCC-4 CPP PANIPAT NAPTHA CRACKER PROJECT, INDIAN OIL CORPORATION LTD. PMC- EIL
: Max.:46.6C, Min.:-0.7C : Max.:45C,Min.:10C (For battery sizing) : 88%(Normal); 95% (Maximum) : Dusty, tropical and corrosive as found in hydrocarbon Industries. : (+)238M above MSL : Panipat
B. Battery Charger 1. System Parameters(Incoming Power Supply) Voltage Frequency Neutral Symmetrical fault level 2. a. : : : : 415 V 6% (-20% transient), 3 Phase 3wire 50 Hz 5% Solidly earthed 50kA for 1 Sec
Miscellaneous Requirements Charger voltage range for Ni-Cd battery i. Float Charger voltage per cell : 1.40-1.42 Volt/Cell. ii. Quick Charger voltage per cell :1.70 Volt/Cell. b. Mounting : Floor Mounted c. Access : Front/Rear d. Cable entry : Bottom e. Earth bus : 25X6 mm2 Copper f. Separate bolted removable undrilled Gland plate for cable entry : Provided g. Cable glands and lugs : Provided h. Painting : RAL 7032 i. Incoming Cable size : 1 Run of 3C-25 Al, Armoured Cable
C. ECS Interface Normally open (NO) potential-free contacts wired up to terminal strip for connection to ECS interface, for the following conditions: Charger failure Battery Discharged Battery Isolated
EPCC-4 CPP PANIPAT NAPTHA CRACKER PROJECT, INDIAN OIL CORPORATION LTD. PMC- EIL
DATA SHEET-BATTERY CHARGER FOR INSTRUMENATION LOADS PART-II 1 2 3 4 4.1 4.2 4.3 5 5.1 5.2 6 7 8 8.1 8.2 9 10 10.1 10.2 11 11.1 11.2 12 Item no. as per MR/PR Tag no Manufacturers Name Rating Charging Rating Output Voltage Output Current Nominal Voltage Float Charging Quick Charging Float Charging Voltage Range Quick Charging Voltage Range Minimum efficiency of charger At light load (40%) At Rated load PF at rated voltage and load Max RMS ripple voltage content at rated load With battery connected Without battery connected Method of voltage control In float charging mode In Quick charging mode 52-BC-09704A 52-BC-09704B Caldyne Automatics Limited 24V/ 407A 24V 407A 24V 1.4v/Cell 1.7v/Cell 1.4v/Cell to 1.42v/Cell 1.7v/cell 60% 80% 0.85 Less than 2% 2% Constant voltage with current limit Constant Current with close loop feedback control Close loop feedback control Close loop feedback control As per spec 1475+1475 800 2000 IP-42
Method of current control in float mode 13 Method of current control in quick mode 14 Safety factor used for selecting components 15 Charger Dimensions 15.1 Width (mm) 15.2 Depth (mm) 15.3 Height(mm) 16 Max heat loss in Watts 17 Degree of protection (IP)