SION Vacuum Circuit-Breakers 3AE5 and 3AE1


Medium-Voltage Equipment Catalog HG 11.02 2013

Answers for infrastructure and cities.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Siemens HG 11.02 2013

R-HG11-172.tif

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Contents

Contents

Page

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Description 5
General Construction and mode of operation Ambient conditions, current carrying capacity and dielectric strength Basic equipment, product range overview 6 8 Standards, maintenance-free design and interlocking 11 12 13

Medium-Voltage Equipment Catalog HG 11.02 2013


Invalid: Catalog HG 11.02 2011

Equipment Selection
Order number structure Configuration example Circuit-breaker and equipment package Secondary equipment Additional equipment Accessories and spare parts

15
16 17 18 31 37 38

Technical Data
Electrical data, dimensions and weights Dimension drawings Operating times and internal times, short-circuit protection of motors Consumption data of releases Circuit diagrams

43
44 64 72 72 74

Annex 81
Inquiry form Configuration instructions Configuration aid 82 83 Foldout page

The products and systems described in this catalog are manufactured and sold according to a certified management system (acc. to ISO 9001, ISO 14001 and BS OHSAS 18001).

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Siemens HG 11.02 2013

R-HG11-357.tif

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Description
Contents

Contents

Page

Description 5
General Construction and mode of operation Switching medium Pole assemblies Operating mechanism Trip-free mechanism Releases Closing and anti-pumping Closing spring charged indication Circuit-breaker tripping signal Interlocking Low-voltage interface
R-HG11-174.tif

8 8 8 8 9 9 9 9 9 9 10 10 10 11 11 11

Withdrawable module Withdrawable module with make-proof earthing switch Circuit-breaker on truck for retrofitting 8B switchgear Standards Maintenance-free design Interlocking Ambient and operating conditions Ambient conditions Current carrying capacity Dielectric strength Basic equipment Product range overview

Industrial application: Refinery

12 12 12 13 13

Siemens HG 11.02 2013

Description
General

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

SION Vakuum Circuit-Breakers 3AE5 and 3AE1 from 7.2 kV to 24 kV The Modulars

SION vacuum circuit-breakers control all switching duties in medium-voltage distribution systems and are suitable for installation in all customary, new, air-insulated medium-voltage switchgear types as well as for retrofitting existing switchgear. They are applicable for operation of e.g. overhead lines, cables, transformers, capacitors and motors. The comprehensive installation accessories enable easy integration in the panel, and form maximally equipped as a withdrawable module with earthing switch almost the complete circuit-breaker compartment inside the switchgear. SION vacuum circuit-breaker for fixed mounting

Our comprehensive circuit-breaker product range offers a wide selection for pole-center distances and widths across flats as well as various equipment options for voltage levels from 7.2 kV to 24 kV. The withdrawable part, contact arms, contacts and bushings enable easy integration in all customary mediumvoltage switchgear types. Identical dimensions and connection dimensions across several voltage levels reduce planning costs and the diversity of panel versions. High reliability and availability are just as much a matter of course as 10,000 maintenance-free operating cycles.

SION vacuum circuit-breaker on withdrawable part

The SION vacuum circuit-breaker can be adjusted to your requirements by means of various equipment options. This switching device can be mounted on a withdrawable part. Furthermore, mountable contact arms, contacts and bushings allow easy integration in your switchgear.

The circuit-breaker mounted on a withdrawable part can be supplied both with and without contact arms and contacts.

Siemens HG 11.02 2013

R-HG11-381.eps

R-HG11-373.tif

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Description
General

SION vacuum circuit-breaker on withdrawable part with contacts

Withdrawable module with 3AE5 vacuum circuit-breaker

The SION vacuum circuit-breakers can be supplied with contact arms and contacts.

The withdrawable module contains all components required for the circuit-breaker compartment of a switchgear panel. It consists of the circuit-breaker mounted on a withdrawable part, with contact arms, fitted in a cartridge with side and rear walls. The withdrawable module is equipped with bushings, fixed contacts, shutters and the shutter mechanism. The side and rear walls form the tested connection compartment. Circuit-breaker on truck for retrofitting 8B swichgear (only for SION 3AE1 vacuum circuit-breaker)

Withdrawable module with earthing switch

R-HG11-362.tif

The withdrawable module is also available with earthing switch. It contains all components required for the circuitbreaker compartment of a switchgear panel. It consists of the circuit-breaker mounted on a withdrawable part, with contact arms, fitted in a cartridge with side and rear walls. The withdrawable module is equipped with bushings, fixed contacts, shutters and the shutter mechanism, as well as with a make-proof earthing switch. The side and rear walls form the tested connection compartment.

Our retrofit solutions allow for considerable cost savings. With the consequent design of a simple plug & play principle, replacing the circuit-breaker requires extremely short operational interruptions. The retrofit solution for 8B switchgear is available up to 17.5 kV, 2500 A and 31.5 kA; for 24 kV, up to 2000 A and 25 kA. Other retrofit solutions are available on request.

Siemens HG 11.02 2013

R-HG11-363.eps

R-HG11-376.eps

R-HG11-375.tif

Description
Construction and mode of operation

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Switching medium The vacuum switching technology, proven and fully developed for more than 30 years, serves as arc-quenching principle by using vacuum interrupters.
3AE1 3AE5

Pole assemblies The pole assemblies consist of the vacuum interrupters and the pole shells. The vacuum interrupters are air-insulated and freely accessible. The pole assemblies are fixed on the mounting plate of the operating mechanism and supported by means of the pole shell (6). The vacuum interrupter (5) is mounted rigidly to the upper interrupter support. The lower part of the interrupter is guided in the lower interrupter support, allowing axial movement. The pole shell (6) absorbs the external forces resulting from switching operations and the contact pressure. Operating mechanism The whole operating mechanism with motor (13), releases (11), indicators and actuating devices is mounted on the mechanism mounting plate (9). This compact design enables very fast operating times. The circuit-breaker operating mechanism is a stored-energy spring mechanism. The force is transmitted from the operating mechanism to the pole assemblies via operating levers. The closing spring (15) can be charged either electrically or manually, and latches automatically in when charging is complete. The closing spring (15) acts as a stored-energy mechanism. To close the breaker, the closing spring (15) can be unlatched either mechanically at the device (ON pushbutton), or electrically by remote control. The closing spring (15) charges the opening or contact-pressure springs (17) as the breaker closes. The now discharged closing spring (15) will be charged again automatically by the motor (13). In this way, the stored-energy mechanism stores the OPEN CLOSE OPEN operating sequence that is required for an auto-reclosing operation on the system side. All stored-energy mechanisms transmit the switching duties of synchronising, rapid load transfer, and auto-reclosing. Trip-free mechanism SION vacuum circuit-breakers have a trip-free mechanism. In the event of an opening command being given after a closing operation has been initiated, the moving contacts return to the open position and remain there even if the closing command is sustained. This means that the contacts of the vacuum circuit-breakers are momentarily in the closed position, which is permissible. For charging the closing spring (15), the motor (13) operates in short-time duty. Therefore the voltage and power consumption might differ from the data of the motor rating plate.
HG11-2500a eps

HG11-2838 eps

HG11-2501 eps

Front view 1 Cover of low-voltage interface 2 Central control board

3 4 5
Pole structure

6 7 8

3 Separating shell to the operating mechanism 4 Upper connection 5 Vacuum interrupter 6 Pole shell 7 Lower connection 8 Insulator

Operating mechanism 3AE1 without cover 9 Mechanism mounting plate 10 Auxiliary switch 11 1st release

10

11
HG11-2502b eps

12 Terminal strip 13 Motor 14 Closing solenoid 15 Closing spring 16 Gear 17 Opening spring

9 12 10 11 13 14 15
HG11-2839a eps

Operating mechanism 3AE5 without cover 9 Mechanism mounting plate 10 Auxiliary switch 11 1st release 12 Terminal strip 13 Motor 14 Closing solenoid 15 Closing spring 16 Gear 17 Opening spring

16 17

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Description
Construction and mode of operation

Releases A release is a device which transfers electrical commands from an external source, such as a control room, to the latching mechanism of the vacuum circuit-breaker so that it can be opened or closed. The releases are designed for shorttime duty up to 1 minute and are reset internally. The various types of releases available are described in detail below: Closing solenoid The closing solenoid unlatches the charged closing spring of the vacuum circuit-breaker, closing it by electrical means. Shunt releases Shunt releases are used for automatic tripping of the circuitbreaker by suitable protection relays and for deliberate tripping by electrical means. They are intended for connection to an external power supply (DC or AC voltage). Current-transformer operated releases Current-transformer operated releases comprise a storedenergy mechanism, an unlatching mechanism, and an electromagnetic system. They are used when there is no external source of auxiliary power (e.g. a battery). Tripping is effected by means of a protection relay (e.g. overcurrent-time protection) acting on the current-transformer operated release. Undervoltage releases Undervoltage releases comprise a stored-energy mechanism, an unlatching mechanism and an electromagnetic system which is permanently connected to the secondary or auxiliary voltage while the circuit-breaker is closed. If the voltage falls below a predetermined value, unlatching of the release is enabled and the circuit-breaker is opened via the storedenergy mechanism. The maximum possible equipment are two releases according to page 32. The consumption data of the releases is listed on pages 70/71. Closing and anti-pumping In the standard version, the circuit-breakers can be remoteclosed electrically. In addition, they can be mechanically closed locally by direct unlatching of the closing spring. If constant electrical signals for CLOSE and OPEN commands are present at the circuit-breaker at the same time, the circuit- breaker will carry out an OPEN-CLOSE-OPEN or a CLOSE-OPEN operating sequence. A new CLOSE command is given only following a short-time interruption of the closing signal. In this manner, continuous closing and opening (= pumping) is prevented.

Closing spring charged indication The circuit-breaker has a mechanically operated spring charged indication. The charging status of the closing spring can also be interrogated electrically by means of an integrated position switch. Circuit-breaker tripping signal During electrical opening, the NO contact S6 makes brief contact. This is often used to operate a hazard warning system which should respond to automatic tripping of the circuit-breaker. In case of local control, the NO contact S6 does not close. For the corresponding circuit diagrams, refer to page 58. Interlocking Mechanical interlocking At the interface of the mechanical interlocking of the circuitbreaker, sensors on the switchgear side can check the switch position and prevent the associated disconnector from being operated while the circuit-breaker is closed. The system also prevents the circuit-breaker from being closed while the associated disconnector is in a faulty position. Circuit-breakers mounted on withdrawable parts are mechanically interlocked, with the result that the handle for racking the withdrawable part can only be inserted in the OPEN position. The lock of the withdrawable part can only be released in the disconnected position by operating the pushing handles. If the circuit-breaker on the withdrawable part is in an intermediate position (neither in the service nor in the disconnected position), operation is not possible due to the mechanical interlocking. Electrical interlocking The auxiliary and signalling contacts which show the switch position of the circuit-breaker or the position of the withdrawable part can be integrated in the switchgear interlocking concept in order to exclude impermissible switching sequences. Low-voltage interface The removable cover of the SION 3AE1 and 3AE5 vacuum circuit-breakers enables easy access to the low-voltage interface. All possible customer-side control and signalling connections are concentrated here.

Siemens HG 11.02 2013

Description
Construction and mode of operation

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Withdrawable module The withdrawable module contains all necessary components for the circuit-breaker compartment of a switchgear panel. It consists of the circuit-breaker mounted on a withdrawable part, with contact arms, fitted in a cartridge with side and rear walls. The withdrawable module is equipped with bushings, fixed contacts, shutters and shutter mechanism. The side and rear walls form the tested connection compartment. The vacuum circuit-breaker on the withdrawable part is racked into the cartridge with the associated handle by the rotary movement of the spindle. The shutter mechanism is controlled by lateral gates, and the shutters are opened for contacting. Signals for the service and disconnected positions are transmitted to the module connector at the low-voltage interface of the vacuum circuit-breaker via the position switches of the withdrawable part. Withdrawable module with make-proof earthing switch The make-proof earthing switch at the cartridge has a defined making capacity up to the values stated on the circuitbreaker rating plate. It features a compact design with spring-operated mechanism and a switching angle of 90, low torques for closing and opening, as well as low maintenance. The make-proof earthing switch has been tested in the withdrawable module and fulfills the relevant standards for the withdrawable module.
HG11-2840 eps

Withdrawable module 3AE1


1 2 3 4 5

1 Fixed contact 2 Bushing 3 Shutter 4 Contact 5 Contact arm

HG11-2815 eps

Withdrawable module 3AE5


1 2 3 4 5

6 Cartridge 7 Low-voltage interface 8 Circuit-breaker 9 Withdrawable part

Retrofit Circuit-breaker on truck for retrofitting 8B swichgear (only for SION 3AE1 vacuum circuit-breaker) With our retrofit solution it is possible to replace only the components that have been stressed the most in long years of reliable operation, instead of the complete switchgear panel. As a rule, these are the circuit-breaker truck and the circuit-breaker itself. To do this, the new truck with the circuit-breaker including contact arms with contacts, secondary equipment, interlocking, wiring and low-voltage plug connector is adjusted at Siemens in such a way that replacement in the switchgear can take place based on a plug & play principle. Solutions for other ratings or other switchgear types such as Reyrolle LMT are available on request. The switchgear documentation, e.g. circuit diagrams, must be provided by the customer. Special equipment like instrument transformers must be ordered separately. Dimension drawings for 8B retrofit are available on request.
R-HG11-364.eps

10

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Description
Standards, maintenance-free design and interlocking

Standards The circuit-breakers conform to the following standards: IEC 62271-1 IEC 62271-100 All circuit-breakers fulfil the endurance classes C2, E2 and M2 according to IEC 62271-100. The withdrawable modules have been tested according to IEC 62271-200, 62271-1 and 62271-102 regarding Dielectric strength Temperature rise Switching capacity. Maintenance-free design The circuit-breakers are maintenance-free: Under normal ambient conditions according to IEC 62271-1 Up to 10,000 operating cycles, no regreasing no readjusting The ratings are independent within their tolerances of the switching rate or standing times without switching. Interlocking
Interlocking of Interlocking of Interlocking of vacuum circuitracking the withdrawable part breaker against in the switchgear withdrawable part closing (optionally panel (latching of (between with key-operated locking handles) disconnected, interlock) test and service in disconnected position) position Interlockable Service position Switching state of vacuum circuit-breaker Switching state of earthing switch Disconnected position Interlocking of earthing switch against closing

Vacuum circuit-breaker Fixed-mounted

Racking

n n

OPEN CLOSED CLOSED OPEN

Disconnecting on withdrawable part and in withdrawable module Disconnecting on withdrawable part, in withdrawable module and with earthing switch Earthing on withdrawable part, in withdrawable module and with earthing switch

n n n n n n n n n n

Active Active Active Active Active Active Active Active Active Active OPEN OPEN OPEN OPEN OPEN Active OPEN Active Active

OPEN CLOSED CLOSED OPEN OPEN CLOSED CLOSED or OPEN CLOSED or OPEN

Siemens HG 11.02 2013

11

Description
Ambient conditions, current carrying capacity and dielectric strength

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Ambient conditions The circuit-breakers are designed for the normal operating conditions defined in IEC 62271-100. Condensation can occasionally occur under the ambient conditions shown opposite. The circuit-breakers are suitable for use in the following climatic classes according to IEC 60721, Part 3-3: Climatic ambient conditions: Biological ambient conditions: Mechanical ambient conditions: Chemically-active substances: Mechanically-active substances: Class 3K41) Class 3B1 Class 3M2 Class 3C2 Class 3S22)

1) Low temperature limit: 5 C (with order code A40 up to 25 C) 2) Restriction: Clean insulation parts

Current carrying capacity The rated normal currents specified in the diagram have been defined according to IEC 62271-100 for an ambient air temperature of +40 C and apply to open switchgear. For enclosed switchgear the data of the switchgear manufacturer applies. At ambient air temperatures below +40 C, higher normal currents can be carried (see diagram): Characteristics curve 1 = Rated normal current 800 A Characteristics curve 2 = Rated normal current 1250 A Characteristics curve 3 = Rated normal current 2000 A Characteristics curve 4 = Rated normal current 2500 A Characteristics curve 5 = Rated normal current 3150 A Dielectric strength
50 60 C 70 40 Ambient air temperature

Rated normal current

2600 2200 1800 1400 2 1000 600 1 10 20 30 4 3

HG11-2516a_en eps

3400 A 3000

1.50 Altitude correction factor

The dielectric strength of air insulation decreases with increasing altitude due to low air density. According to IEC 62271-1, the values of the rated lightning impulse withstand voltage and the rated short-duration power-frequency withstand voltage specified in the chapter Technical Data apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite diagram. The characteristic shown applies to both rated withstand voltages. To select the devices, the following applies: U U0 x Ka
U Rated withstand voltage under reference atmosphere U0 Rated withstand voltage requested for the place of installation Ka Altitude correction factor according to the opposite diagram

1.40

1.30

1.20
HG11-2517c_en eps

1.10

Example For a requested rated lightning impulse withstand voltage of 75 kV at an altitude of 2500 m, an insulation level of 90 kV under reference atmosphere is required as a minimum: 90 kV 75 kV x 1.2

1.00 1000

1500

2000

2500

3000 3500 m 4000 Site altitude

12

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Description
Basic equipment, product range overview

Basic equipment
Equipment Operating mechanism Closing 1st release 2nd release Minimum equipment Electrical operating mechanism Closing solenoid and mechanical manual closing Shunt release Without Alternative equipment None None Remarks Also for manual operation

Varistor circuit Auxiliary switch Plug connection Anti-pumping Circuit-breaker tripping signal Operations counter Position switches for withdrawable part Mechanical interlocking Installation accessories

Standard for SION 3AE1 Installed with 60 V DC f. SION 3AE5 6 NO + 6 NC 27-pole terminal strip f. SION 3AE1 20-pole plug connector f. SION 3AE5 Available Without Available 5 momentary-contact position switches per position Available for withdrawable module Fixed-mounted

Undervoltage release, c.t.-operated release For SION 3AE5, only shunt releases are possible Shunt release, undervoltage release, Combination of 2 undervoltage releases or 2 c.t.c.t.-operated release operated releases is not possible. For SION 3AE5, the combination of undervoltage and c.t.-operated releases is not possible either None For limiting switching overvoltages 12 NO + 12 NC 24-pole plug, 64-pole plug None Possible None None 12 NO + 12 NC not available with 24-pole plug

Mechanical interlocking for circuit-breaker Required for withdrawable module With withdrawable part, contact arms and contact, fixed contacts and bushings, complete withdrawable module with and without make-proof earthing switch

Product range overview: Circuit-breaker without installation accessories


Rated normal current Rated shortcircuit breaking current Pole-center distance (in mm) 150 160 Width across flats (in mm) 205 n n n n 275 n n n n 310 n n n n 205 n n n n 275 n n n n 310 n n n n 205 n n n n 275 n n n n 310 n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n 310 210 275

Type 3AE10 / 3AE50

Rated voltage kV 7.2

kA 16 20 25 25 31.5 31.5 40 40 16 20 25 25 31.5 31.5 40 40 12.5 16 25 25 31.5 31.5 40 40 12.5 16 20 20 25 25

A 800/1250 800/1250 800/1250 2000 800/1250 2000/2500 1250/2000 2500/3150 800/1250 800/1250 800/1250 2000 800/1250 2000/2500 1250/2000 2500/3150 800/1250 800/1250 800/1250 2000/2500 800/1250 2000/2500 1250/2000 2500/3150 800/1250 800/1250/2000 800/1250 2000/2500 800/1250 2000/2500

3AE10

7.2

3AE11/ 3AE51

12

n n n n

n n n n

n n n n

n n n n

n n n n

n n n n

n n n n

n n n n

3AE11

12

3AE12

17.5

n n n n

n n n n

n n n n

n n n n

n n n n

n n n n

n n n n

n n n n

3AE13

24

Note: The circuit-breaker is available with various installation accessories: These versions can be configured from page 18.

Siemens HG 11.02 2013

13

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

14

Siemens HG 11.02 2013

R-HG11-377.tif

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Contents

Contents

Page

Equipment Selection
Order number structure Configuration example Circuit-breaker and equipment package Voltage level 7.2 kV Voltage level 12 kV Voltage level 17.5 kV Voltage level 24 kV Secondary equipment Release combination Operating voltage of the closing solenoid
R-HG11-378.tif

15
16 17

18 22 27 30

31 31 32 32 33 34 35 36 37

Operating voltage of the 1st release Operating voltage of the 2nd release Circuit-breaker installation accessories Operating voltage of the motor operating mechanism Interlocking, auxiliary switch, circuit-breaker tripping signal and secondary connection Languages of operating instructions and rating plate; AC frequency of operating voltages Additional equipment Accessories and spare parts Rating plate Accessories catalog

3AE5 vacuum circuit-breaker as fixed-mounted version

38 38

3AE1 vacuum circuit-breaker as fixed-mounted version

R-HG11-176.eps

Siemens HG 11.02 2013

15

Equipment Selection
Order number structure

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Order number structure The circuit-breakers consist of a primary and a secondary part. The relevant data make up the 16-digit order number. The primary part covers the main electrical data of the circuit-breaker poles. The secondary part covers the auxiliary devices which are necessary for operating and controlling the vacuum circuit-breaker. Order codes Individual equipment versions, marked with 9 or Z in the 9th to 16th position, are explained more in detail by a 3-digit order code. Several order codes can be added to the order number in succession and in any sequence.

Special versions () In case of special versions, -Z is added to the order number and a descriptive order code follows. If several special versions are required, the suffix -Z is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation. The agreement hereto is made directly between your responsible sales partner and the order processing department at Siemens.

2
Position:

a: alphabetical n: numerical
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes

Order No.: Primary part Superior group Switching devices Main group Circuit-breaker Subgroup Circuit-breaker type series Circuit-breaker version Rated voltage from 7.2 kV to 24 kV Pole-center distance / Width across flats Rated short-circuit breaking current from16 kA to 40 kA Rated normal current from 800 A to 3150 A Secondary part Secondary equipment, operating mechanism, releases, operating voltages and further auxiliary equipment Order codes Groups of 3 after the Order No. Format: a n a Special versions () Initiated with -Z Groups of 3 after the Order No. Format: a n n

3 A

n n n

1st position 2nd position 3rd position 4th position 5th position 6th position 7th position

8th position

9th to 16th position

16

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Configuration example

Configuration example In order to simplify the selection of the correct order number for the requested circuit-breaker type, you will find two configuration examples below. Two complete circuit-breakers have been configured as an example. On the foldout page you can enter the Order No. determined for your circuit-breaker. Based on the Order No. you can request an offer from your Siemens partner.

Configuration example 1: SION 3AE5 vacuum withdrawable module (vacuum circuit-breaker on withdrawable part in cartridge)
Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes

Order No.: Configuration example SION vacuum circuit-breaker Rated voltage Ur = 12 kV, 50 / 60 Hz Rated lightning impulse withstand voltage Up = 75 kV Rated short-circuit breaking current ISC = 25 kA Rated normal current Ir = 1250 A Pole-center distance = 150 mm Width across flats = 310 mm 1st shunt release (only one shunt release) Operating voltage of the closing solenoid 48 V DC Operating voltage of the 1st release 32 V DC Without 2nd release Circuit-breaker on withdrawable part, with cartridge, contact arm, contact, fixed contacts, bushing, shutters, make-proof earthing switch Operating voltage of the motor operating mechanism 230 V AC

3 A 3 A

E E

5 n n n n n n n n n n n n 5

n n n

2 A C 9 0 L 1 B

2
6 K N 2 Z Z F 3 0

With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug Frequency of the operating voltage 50 Hz and DC, operating instructions and rating plate in english Hand crank Example for Order No.: Order codes: 3 L A 1 E B 5 + 1 F 2 3 4 0 2 A C 9 0 6

K N 2

Configuration example 2: SION vacuum circuit-breaker for 8B retrofit


Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Order codes

Order No.: Configuration example SION vacuum circuit-breaker Rated voltage Ur = 17.5 kV, 50 / 60 Hz Rated lightning impulse withstand voltage Up = 95 kV Rated short-circuit breaking current ISC = 25 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm Width across flats = 310 mm 1st shunt release (only one shunt release) Operating voltage of the closing solenoid 48 V DC Operating voltage of the 1st release 32 V DC Without 2nd release 8B retrofit: Circuit-breaker up to 17.5 kV, 25 kA, 1250 A, contact arm type C Operating voltage of the motor operating mechanism 230 V AC

3 A 3 A

E E

1 n n n n n n n n n n n n 1

n n n

2 A C 9 0 7 K N 2 Z Z F 3 0 Z R 2 1 L 1 B

With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug Frequency of the operating voltage 50 Hz and DC, operating instructions and rating plate in english Hand crank Example for Order No.: Order codes: 3 L A 1 E B 1 + 2 R 8 2 4 1 + 2 A C F 3 0 9 0 7

K N 2

Siemens HG 11.02 2013

17

Equipment Selection
Circuit-breaker and equipment package

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

7.2 kV
Rated short-circuit breaking current at 50 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

5 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 7.2

Up kV 60

Ud kV 20

ISC kA 16

Ima kA 40/42 mm 210 mm 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

7.2

60

20

20

50/52

210

310 310 275 275 205 205

160

310 310 275 275 205 205

150

310 310 275 275 205 205

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

Retrofit

Special version Ud = 32 kV Legend: V With contact system n Without contact system see page 33, 13th position

See page 37 E

*) Can also be ordered without withdrawable part,

18

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Circuit-breaker and equipment package

7.2 kV
Rated short-circuit breaking current at 50 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

5 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 7.2

Up kV 60

Ud kV 20

Isc kA 25

Ima kA 63/65 mm 210 mm 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2

160

150

n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n

V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V

V V V V

V V V V

Retrofit

See page 37

V V V V

V V V V

Special version Ud = 32 kV Isc = 26.3 kA Legend: V With contact system n Without contact system see page 33, 13th position

Z Z

E E

1 4

6 6

*) Can also be ordered without withdrawable part,

Siemens HG 11.02 2013

19

Equipment Selection
Circuit-breaker and equipment package

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

7.2 kV
Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

1 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 7.2

Up kV 60

Ud kV 20

ISC kA 16

Ima kA 40/42 mm 210 mm 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

7.2

60

20

20

50/52

210

310 310 275 275 205 205

160

310 310 275 275 205 205

150

310 310 275 275 205 205

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

Retrofit

Special version Ud = 32 kV Legend: V With contact system n Without contact system see page 33, 13th position

See page 37 E

*) Can also be ordered without withdrawable part,

20

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Circuit-breaker and equipment package

7.2 kV
Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

1 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 7.2

Up kV 60

Ud kV 20

ISC kA 25

Ima kA 63/65 mm 210 mm 310 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310

Ir A 800 1250 2000 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 1250 2000 2500 3150 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 6 6 1 2 4 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 2 4 6 7

160

150

7.2

60

20

31.5

80/82

210

160

150

7.2

60

20

40

100/104

210

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V

V V V V V

Retrofit

See page 37

V V V V V V V V V V

V V V V V V V V V V

V V V V V V V V

V V V V V V V V
Z E 1 6

Special version Ud = 32 kV Legend: V With contact system n Without contact system see page 33, 13th position

*) Can also be ordered without withdrawable part,

Siemens HG 11.02 2013

21

Equipment Selection
Circuit-breaker and equipment package

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

12 kV
Rated short-circuit breaking current at 50 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

5 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 12

Up kV 75

Ud kV 28

Isc kA 16

Ima kA 40/42 mm 210 mm 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

12

75

28

20

50/52

210

310 310 275 275 205 205

160

310 310 275 275 205 205

150

310 310 275 275 205 205

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

Retrofit

Special version Ud = 42 kV Up = 95 kV Legend: V With contact system n Without contact system see page 33, 13th position

Z Z

See page 37 E E

1 9

3 5

*) Can also be ordered without withdrawable part,

22

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Circuit-breaker and equipment package

12 kV
Rated short-circuit breaking current at 50 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

5 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 12

Up kV 75

Ud kV 28

Isc kA 25

Ima kA 63/65 mm 210 mm 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A E E E E E E E E E E E E E E E E E E 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2

n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n

V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V

V V V V

V V V V

Retrofit

See page 37

V V V V

V V V V

Special version Ud = 42 kV Isc = 26.3 kA Up = 95 kV Circuit-breaker for installation in NXAIR World 1) 12 75 28 25 63/65 160 275 275 Special version Ud = 42 kV Isc = 26.3 kA Ud = 95 kV 1) W63 is absolutely necessary as order code Legend: V With contact system n Without contact system s Retrofit contact system see page 33, 13th position 800 1250 3 A 3 A E E 5 5 5 5 5 5 4 1 4 2 n n

Z Z Z Z Z Z Z Z

E E E

1 4 9

3 6 5 3 3 3 6 5

W 6 W 6 E E E 1 4 9

*) Can also be ordered without withdrawable part,

Siemens HG 11.02 2013

23

Equipment Selection
Circuit-breaker and equipment package

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

12 kV
Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

1 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 12

Up kV 75

Ud kV 28

ISC kA 16

Ima kA 40/42 mm 210 mm 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2 3 1 3 2

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

12

75

28

20

50/52

210

310 310 275 275 205 205

160

310 310 275 275 205 205

150

310 310 275 275 205 205

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

Retrofit

Special version Ud = 42 kV Up = 95 kV Legend: V With contact system n Without contact system see page 33, 13th position

Z Z

See page 37 E E

1 9

3 5

*) Can also be ordered without withdrawable part,

24

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Circuit-breaker and equipment package

12 kV
Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

1 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 12

Up kV 75

Ud kV 28

ISC kA 25

Ima kA 63/65 mm 210 mm 310 310 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205

Ir A 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 4 1 4 2 4 4 4 6 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 5 1 5 2 5 4 5 6 5 1 5 2 5 1 5 2 5 1 5 2 5 1 5 2 5 1 5 2 5 1 5 2 5 1 5 2 5 1 5 2

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

12

75

28

31.5

80/82

210

310 310 310 310 275 275 205 205

160

310 310 275 275 205 205

150

310 310 275 275 205 205

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V

V V V V V V

Retrofit

s s s

See page 37

V V V V

V V V V

V V V V V V

V V V V V V

s s s

V V V V

V V V V

Special version Ud = 42 kV Up = 95 kV Legend: V With contact system n Without contact system s Retrofit contact system see page 33, 13th position

Z Z

E E

1 9

3 5

*) Can also be ordered without withdrawable part,

Siemens HG 11.02 2013

25

Equipment Selection
Circuit-breaker and equipment package

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

12 kV
Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

1 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 12

Up kV 75

Ud kV 28

ISC kA 40

Ima kA mm mm 310 310 310 310 100/104 210

Ir A 1250 2000 2500 3150 3 A 3 A 3 A 3 A E E E E 1 1 1 1 1 1 1 1 8 8 8 8 6 2 6 4 6 6 6 7

n n n n

n n n n

V V V V

V V V V

V V V V

V V V V
Z Z E E 1 9 3 5 3 3 3 3 3 3 3 3 3 3 5

Circuit-breaker for installation in NXAIR World 1) Special version Ud = 42 kV Up = 95 kV 12 75 28 25 63/65 160 160 210 40 100/104 210 275 275 31.5 80/81.9 275 275 275 275 275 275 275 Special version Ud = 42 kV Up = 95 kV 1) W63 is absolutely necessary as order code Legend: V With contact system n Without contact system 800 1250 800 1250 1250 2500 1250 2500 3150 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A E E E E E E E E E 1 1 1 1 1 1 1 1 1 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 6 6 6 4 1 4 2 5 1 5 2 5 2 5 6 6 2 6 6 6 7 n n n n n n n n n

Retrofit

Z Z Z Z Z Z Z Z Z Z Z see page 33, 13th position

See page 37 W 6 W 6 W 6 W 6 W 6 W 6 W 6 W 6 W 6 E E 1 9

*) Can also be ordered without withdrawable part,

26

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Circuit-breaker and equipment package

17.5 kV
Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

1 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 17.5

Up kV 95

Ud kV 38

ISC kA 12.5

Ima kA 31/33 mm 210 mm 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 1 1 1 2 1 1 1 2 1 1 1 2 1 1 1 2 1 1 1 2 1 1 1 2 1 1 1 2 1 1 1 2 1 1 1 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 4 1 4 2 4 4 4 6

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

17.5

95

38

16

40/42

210

310 310 275 275 205 205

160

310 310 275 275 205 205

150

310 310 275 275 205 205

17.5

95

38

25

63/65

210

310 310 310 310

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V

V V V V

Retrofit

See page 37

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

V V V V

s s s

Legend: V With contact system n Without contact system s Retrofit contact system

*) Can also be ordered without withdrawable part,


see page 33, 13th position

Siemens HG 11.02 2013

27

Equipment Selection
Circuit-breaker and equipment package

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

17.5 kV
Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

1 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 17.5

Up kV 95

Ud kV 38

ISC kA 25

Ima kA 63/65 mm 210 mm 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 1250 2000 2500 3150 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 4 1 4 2 5 1 5 2 5 4 5 6 5 1 5 2 5 1 5 2 5 1 5 2 5 1 5 2 5 1 5 2 5 1 5 2 5 1 5 2 5 1 5 2 6 2 6 4 6 6 6 7

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

17.5

95

38

31.5

80/82

210

310 310 310 310 275 275 205 205

160

310 310 275 275 205 205

150

310 310 275 275 205 205

17.5

95

38

40

100/104 210

310 310 310 310

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V

V V V V

V V V V

V V V V

V V V V V V

V V V V V V

V V V V

V V V V

V V V V

V V V V

Legend: V With contact system n Without contact system s Retrofit contact system

*) Can also be ordered without withdrawable part,


see page 33, 13th position

28

Siemens HG 11.02 2013

Retrofit

See page 37

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Circuit-breaker and equipment package

17.5 kV
Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

1 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 17.5

Up kV 95

Ud kV 38

ISC kA 25

Ima kA 63/65 mm 160 mm 275 275 275 275 210 275 275 275 275 275

Ir A 800 1250 800 1250 1250 2500 1250 2500 3150 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A E E E E E E E E E 1 1 1 1 1 1 1 1 1 6 6 6 6 6 6 6 6 6 2 2 2 2 6 6 6 6 6 4 1 4 2 5 1 5 2 5 2 5 6 6 2 6 6 6 7

Circuit-breaker for installation in NXAIR World 1)

Retrofit

n n n n n n n n n n see page 33, 13th position

Z Z Z Z Z Z Z Z Z Z

See page 37 W 6 W 6 W 6 W 6 W 6 W 6 W 6 W 6 W 6 W 6

3 3 3 3 3 3 3 3 3 3

31.5 80/81.9 160

40

100/104 210

1) W63 is absolutely necessary as order code Legend: n Without contact system

*) Can also be ordered without withdrawable part,

Siemens HG 11.02 2013

29

Equipment Selection
Circuit-breaker and equipment package

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

24 kV
Rated short-circuit breaking current at 36 % DC component Rated short-circuit making current (at 50 / 60 Hz)

Position:

8 9 12

13th position Equipment package

14 16

Order codes

Order No.:

3 A

1 n n n n

Circuit-breaker for fixed mounting, without circuit-breaker installation accessories

n Orderable versions Withdrawable module without earthing switch Withdrawable module with earthing switch

n n n

On withdrawable part with complete contact system and bushings *

Rated short-duration power- frequency withstand voltage

On withdrawable part with complete contact system *

Rated lightning impulse withstand voltage

Rated normal current

See pages 31 and 32

Pole-center distance

On withdrawable part

See pages 34 to 36

Width across flats

Rated voltage for 50 / 60 Hz

Ur kV 24

Up kV 125 125

Ud kV 50 50

ISC kA 12.5 16

Ima kA 31/33 40/42 mm 210 210 mm 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310

Ir A 800 1250 800 1250 2000 800 1250 2000 800 1250 2000 2500 800 1250 2000 2500 800 1250 2000 2500 800 1250 2000 2500 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 2 2 2 2 2 5 5 5 2 2 2 2 5 5 5 5 2 2 2 2 5 5 5 5 1 1 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 1 2 1 2 4 1 2 4 1 2 4 6 1 2 4 6 1 2 4 6 1 2 4 6

24

275

24

125

50

20

50/52

210

275

24

125

50

25

63/65

210

275

n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n n n n n n n n n n n n n n n n n

V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V

V V V V V V V V V V V V V V V V V V V V V V V V

Retrofit

s s

s s

See page 37

Special version Ud = 55 kV Special version Ud = 65 kV Circuit-breaker for installation in NXAIR 3) 24 125 50 25 63/65 210 275 Special version Ud = 55 kV 1) With special version E55 (selection is possible if 13th position 0, 1, 2, 3 and 5) 2) With special version E65 (selection is possible if 13th position 0 and 1) 3) W63 is absolutely necessary as order code Legend: V With contact system n Without contact system s Retrofit contact system see page 33, 13th position 320 320 320 1250 2000 2500 3 A 3 A 3 A E E E 1 1 1 7 7 7 1 4 4 4 2 4 4 4 6 n n n

Z Z

E E

5 6

5 5

1) 2)

Z Z Z Z

W 6 W 6 W 6 E 5

3 3 3 5 1)

*) Can also be ordered without withdrawable part,

30

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Secondary equipment

9th position Release combination 1)


Undervoltage release C.t.-operated release with tripping pulse 0.1 Ws (10 )

Position:

10 11 12

13 14 15 16

Order codes

Order No.: C.t.-operated release with tripping pulse 0.1 Ws (20 )

3 A

1 n n n n n n n n n n n n

n n n

See page 32

See page 32

See page 34

See page 35

See page 36

2nd shunt release

1st shunt release

C.t.-operated release 0.5 A 2)

C.t.-operated release 1.0 A

n n n n n n n n n n n n n n n n 1) Operating voltage is selected at positions 11 + 12 2) Special version with c.t.-operated release 5 A: Can be ordered with order code A49 for all circuit-breakers (except retrofit) with c.t.-operated release 0.5 A (4th column) (not for 3AE5) n n n n n n n n n

A B C D G H F E N P Q J K L M not for 3AE5 not for 3AE5 not for 3AE5 not for 3AE5 not for 3AE5 not for 3AE5 not for 3AE5 not for 3AE5

See page 37

2
Z A 4 9

10th position Operating voltage of the closing solenoid


Standard voltages 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50 / 60 Hz 3) 110 V AC 50 / 60 Hz 3) 230 V AC 50 / 60 Hz 3) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 50 / 60 Hz 3) 125 V AC 50 / 60 Hz 3) 240 V AC 50 / 60 Hz 3) 3) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 36) Special voltages B C D E F H J K M N P Q R S U V W

Siemens HG 11.02 2013

31

Equipment Selection
Secondary equipment

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

11th position Operating voltage of the 1st release

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n See page 34 See page 35 See page 36 See page 37

n n n

Standard voltages

Special voltages

C.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50 / 60 Hz 1) 110 V AC 50 / 60 Hz 1) 230 V AC 50 / 60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 50 / 60 Hz 1) 125 V AC 50 / 60 Hz 1) 240 V AC 50 / 60 Hz 1)

0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9

not for 3AE5

2
12th position Operating voltage of the 2nd release
Standard voltages

L L L L L L L L L

1 1 1 1 1 1 1 1

A B C D E F K L

1 M

Special voltages

without, or c.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50 / 60 Hz 1) 110 V AC 50 / 60 Hz 1) 230 V AC 50 / 60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 50 / 60 Hz 1) 125 V AC 50 / 60 Hz 1) 240 V AC 50 / 60 Hz 1) 1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 36)

0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9 M 1 M 1 M 1 M 1 M 1 M 1 M 1 M 1 A B C D E F K L

M 1 M

32

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Secondary equipment

13th position Circuit-breaker installation accessories

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n See page 34 See page 35 See page 36 See page 37

n n

Options

Circuit-breaker for fixed mounting Without circuit-breaker installation accessories, circuit-breaker for fixed mounting Circuit-breaker prepared for separate mounting of withdrawable part Without withdrawable part, with contact arm, contact 1), wiring of withdrawable part (loose delivery) Without withdrawable part, with contact arm, contact 1), fixed contact, bushing, wiring of withdrawable part (loose delivery) Circuit-breaker on withdrawable part On withdrawable part On withdrawable part, with contact arm, contact 1) On withdrawable part, with contact arm, contact 1), fixed contact, bushing Withdrawable module Circuit-breaker on withdrawable part, with cartridge, contact arm, contact 1), fixed contacts, bushing, shutters Circuit-breaker on withdrawable part, with cartridge, contact arm, contact 1), fixed contacts, bushing, shutters, make-proof earthing switch Retrofit 8B Circuit-breaker on truck for retrofitting 8B switchgear, see next page 1) Special version: Contact with 13 contact fingers (only up to 1250 A and 31.5 kA) can be ordered with order code Z-M13 7 not for 3AE5 5 6 1 2 3 2 Z M 2 2 0

M 2 3

Example: Circuit-breaker for fixed mounting

Example: Circuit-breaker on drawout element with contact arms and contacts

Example: Circuit-breaker with withdrawable module

Example: Circuit-breaker with withdrawable module and earthing switch

Siemens HG 11.02 2013

33

R-HG11-362.eps

R-HG11-379.tif

R-HG11-375.tif

R-HG11-376.tif

Equipment Selection
Secondary equipment

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

13th position Circuit-breaker installation accessories (continued)

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n See page 35 See page 36 See page 37 Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z

n n n

Options

Circuit-breaker on truck for retrofitting 8B switchgear Ratings of your 8B swichgear 7.2 12 kV 7.2 12 kV 7.2 12 kV 7.2 12 kV 12 kV 7.2 12 kV 12 kV 12.5 25 kA 12.5 25 kA 12.5 25 kA 12.5 25 kA 29 (10 kV) 31.5 kA 29 (10 kV) 31.5 kA 12.5 25 kA 8 25 kA 20 25 kA 25 kA 31.5 kA 31.5 kA 8 20 kA 12.5 kA 12.5 kA 20 kA 25 kA 25 kA 630 1250 A 1600 A 2000 A 2500 A 630 1250 A 630 1250 A 1600 A 630 1250 A 630 1250 A 2000 A 2500 A 630 1250 A 630 1250 A 1600 A 1600 A 2000 A 1250 A 2000 A Contact arm type A Contact arm type B Contact arm type D Contact arm type D Contact arm type A Contact arm type D Contact arm type B Contact arm type A Contact arm type C Contact arm type D Contact arm type D Contact arm type D Contact arm type C Contact arm type C Contact arm type D Contact arm type D Contact arm type C Contact arm type D Lower insertion height 665 mm 665 mm 598 mm 598 mm 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A 3 A Order number E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 3 8 8 8 8 8 8 8 8 8 8 8 8 8 8 2 2 2 2 2 2 4 4 4 4 5 5 5 5 4 4 4 4 5 5 3 3 3 3 4 4 2 4 4 6 2 2 4 6 2 2 4 6 2 6 2 4 4 4 2 4 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 R R R R R R R R R R R R R R R R R R R R 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

7.2 12 kV 15 kV 17.5 kV 15 17.5 kV 15 kV 15 kV 15 kV 24 kV 24 kV 24 kV 24 kV 24 kV 24 kV Type A B C D

1600 2500 A Contact arm type D

1600 2500 A Contact arm type D

Contact arm including contact Thickness of fixed contact Fixed contact 10 mm Fixed contact 15 mm Fixed contact 10 mm Fixed contact 15 mm

14. position Operating voltage of the motor operating mechanism


S. page 35 S. page 36 Standard voltages 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50 / 60 Hz 1) 110 V AC 50 / 60 Hz 1) 230 V AC 50 / 60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 50 / 60 Hz 1) 125 V AC 50 / 60 Hz 1) 240 V AC 50 / 60 Hz 1) 1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 36) Special voltages B C D E F H J K M N P Q R S U V W S. page 37

34

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Secondary equipment

15th position Interlocking, auxiliary switch, circuit-breaker tripping signal and secondary connection
Auxiliary switch

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Secondary connection 27-pole for 3AE1 20-pole for 3AE5 terminal strip 1) See page 36 p p n n n n n n n n n n n n n n n n not for 3AE5 p p p n n p p p p p p B D F H K M R Q A C E G J L N P U 3) if 0 is selected at p  the 13th position
3)

Circuit-breaker tripping signal

24-pole plug 1)

If 0 6 is selected at the 13th position: Circuit-breaker / circuit-breaker withdrawable module


n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

64-pole plug 2)

12 NO + 12 NC

6 NO + 6 NC

Mechanical interlocking

See page 37

Same as for N, but with 9 NO + 9 NC 3)

If 7 is selected at the 13th position: Retrofit circuit-breaker


n n n n n n n n n n n n Special versions Auxiliary switch contacts 6 NO + 6 NC and pins of the 24-pole plug connector gold-plated (not for retrofit) Auxiliary switch contacts 12 NO + 12 NC and pins of the 64-pole plug connector gold-plated (not for retrofit) Key-operated interlock (lock at the circuit-breaker) Only for circuit-breakers with mechanical interlocking and without electrical closing lock-out (A47) (not for retrofit) 1) Electrical devices are wired to the lower part of a plug through the terminal strip. The free auxiliary switch connections are not wired. 2) Electrical devices are wired to the lower part of a plug through the terminal strip. The auxiliary switches are wired to the lower part of the plug according to the circuit diagrams. 3) Standard for NXAIR World. not for 3AE5 Z Z A A 2 2 0 1 n n n n n n n n n n n n A B C D E F G H

Siemens HG 11.02 2013

35

Equipment Selection
Secondary equipment

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

16th position Languages of operating instructions and rating plate, as well as AC frequency of operating voltages 1)
Language selection

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Frequency selection

DC or AC 50 Hz

German

Spanish

English

French

60 Hz

n n n n

n n n n n n n n n n n n

0 1 2 3 4 5 6 7 9 9 9 9 R R R R 1 1 1 1 F G H K

2
Special versions Russian, 60 Hz

Italian, DC or AC 50 Hz Russian, DC or AC 50 Hz Polish, DC or AC 50 Hz Other languages on request 1) AC voltage refers to the secondary side and not to the primary part of the circuit-breaker

36

Siemens HG 11.02 2013

See page 37

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Additional equipment

Additional equipment
Circuit-breaker 13th pos. = 0, 1, 2, 3 Withdrawable module 13th position = 5, 6 Retrofit 13th position = 7

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Options

3AE1

3AE5

Wiring cables, halogen-free Protection against condensed water, heating for 230 V AC, 50 W Silicone-free design Circuit-breaker for operation at ambient air temperatures down to 25 C Electrical closing lock-out C.t.-operated release 5 A Additional rating plate, loose delivery Without loose delivery Separating shell towards contact arm side (standard version) Separating shell towards contact arm side (short version, for 24 kV) Rated short-duration power-frequency withstand voltage 32 kV (at 7.2 kV) Rated short-duration power-frequency withstand voltage 42 kV (at 12 kV) Rated short-circuit breaking current Isc = 26.3 kA Rated short-duration power-frequency withstand voltage 55 kV (at 24 kV) Rated short-duration power-frequency withstand voltage 65 kV (at 24 kV) 1) Routine test certificate (enclosed with delivery) Rated lightning impulse withstand voltage 95 kV (at 12 kV) Routine test certificate (with stamp and signature to orderer) Routine test certificate (to orderer) Rated operating sequence O 3 min CO 3 min CO Rated operating sequence O 0.3 s CO 15 s CO Hand crank (for manual charging of the closing spring) (scope of supply: one hand crank per circuit-breaker) Hand crank, long (scope of supply: one hand crank per circuit-breaker) Handle for withdrawable part (for racking the circuitbreaker on the withdrawable part) (scope of supply: one handle per circuit-breaker). Only required when a withdrawable part is ordered Handle for make-proof earthing switch (for operation of the earthing switch at the withdrawable module) (scope of supply: one handle per circuit-breaker). Only required when a withdrawable module with earthing switch is ordered Break time Y1 60 ms at rated voltage Closing time T Close < 55 ms Key-operated interlock (for circuit-breakers with mechanical interlocking and without A47) Contact with 13 contact fingers (up to 1250 A and 31.5 kA) (selection via 13th position / page 29) 30,000 operating cycles for all circuit-breakers: 12 kV, 25 kA, 2000 A and 12 kV, 31.5 kA and 17.5 kV, 31.5 kA Prepared for NXAIR World 1) Only for 0 and 1 at the 13th position

n n n n n n n n n n n n

n n n n

n n

n n n n

n n n n n n n n

Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z

A A A A A A B B D D E E E E E F E F F F F

1 3 3 4 4 4 0 2 9 9 1 1 4 5 6 2 9 2 2 2 2

0 0 1 0 7 9 0 4 0 1 6 3 6 5 5 0 5 1 3 7 8

n n n n

n n n n n n

n n

n n

n n n

n n n

n n

n n n n

n n n n

n n

n n n

n n n n

n n

n n

n n

n n

n n

Z Z

F F

3 3

0 1

n n n n n n n

n n n n n

n n n

Z Z Z Z

F G G J

3 2 2 6

4 2 3 0

n n

M 1

n n

Z Z

M 3 W 6

0 3

Siemens HG 11.02 2013

37

Equipment Selection
Accessories and spare parts

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Note: For any query regarding spare parts, subsequent deliveries, etc., the following 3 details are necessary: Type designation Serial no. Year of manufacture

Position: Designation Description Feature

19

Order No. 3AX15 30-2B 3AX14 30-2B 3AX14 30-2C 3AX14 30-2D 3AX14 30-3D 3AX11 33-3H 3AX11 33-3E 3AX14 33-2L

Handles

Hand crank for circuit-breaker Long hand crank for circuit-breaker Handle for withdrawable part Handle for earthing switch (for modules up to 31.5 kA) Handle for earthing switch (for 40 kA modules)

Lubricant

180 g of Klber-Isoflex Topas L32 1 kg of Klber-Isoflex Topas L32 1 kg of Molykote grease

Operating solenoid

Used as closing solenoid or 1st shunt release For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE5 For 3AE5 For 3AE5 For 3AE5 For 3AE5 For 3AE5 For 3AE5 For 3AE5 For 3AE5 24 V DC 30/32 V DC 48 V DC 60 V DC 100/124 V DC 125/144 V DC 220/250 V DC 100/125 V AC, 50/60 Hz 230/240 V AC, 50/60 Hz 24 V DC 30/32 V DC 48 V DC 60 V DC 100/124 V DC 125/144 V DC 220/250 V DC 100/125 V AC, 50/60 Hz 230/240 V AC, 50/60 Hz 24 32 V DC 48 60 V DC 110 127 V DC 220 240 V DC 100 125 V AC, 50 Hz 230 240 V AC, 50 Hz 100 125 V AC, 60 Hz 230 240 V AC, 60 Hz 3AY15 10-5B 3AY15 10-5M 3AY15 10-5C 3AY15 10-5D 3AY15 10-5E 3AY15 10-5N 3AY15 10-5F 3AY15 10-5E 3AY15 10-5F 3AY14 10-0B 3AY14 10-0M 3AY14 10-0C 3AY14 10-0D 3AY14 10-0E 3AY14 10-0N 3AY14 10-0F 3AY14 10-0E 3AY14 10-0F 3AX11 01-2B 3AX11 01-2C 3AX11 01-2E 3AX11 01-2F 3AX11 01-2G 3AX11 01-2J 3AX11 01-3G 3AX11 01-3J 3AX14 11-2A 3AX14 11-5A

2nd shunt release

For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5

Mounting parts

For 2nd shunt release For 3AE1 For 3AE5

38

Siemens HG 11.02 2013

HG11-2518b_en eps

On request we will be pleased to send you a complete overview of the accessories and spare parts. Please take the following information into account for ordering.

Rating plate

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Accessories and spare parts

Position: Designation Description Feature

19

Order No. 3AX11 02-2A 3AX11 02-2B 3AX11 04-2B 3AX14 11-2A 3AX14 11-5A

Current-transformer operated release Mounting parts Undervoltage release

For rated normal current 0.5 A For rated normal current 1 A For current-transformer operated release

For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 For 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 For 3AE5 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE5 For 3AE5 For 3AE5 For 3AE5 For 3AE5 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 24/30/32 V DC 48 V DC 60 V DC 100/110/125 V DC/AC 220 V DC/230 V AC 24/30/32 V DC 48 V DC 60 V DC 100/110/125 V DC/AC 220 V DC/230 V AC 24 V DC 30/32 V DC 48 V DC 60 V DC 110 V DC 120/127 V DC 220 V DC 240/250 V DC 110 V AC, 50/60 HZ 120 V AC, 50/60 HZ 125 V AC, 50/60 HZ 230 V AC, 50/60 HZ 240 V AC, 50/60 HZ 24 V 60 V 110 V 230 V 24 V DC 30/32 V DC 48 V DC 60 V DC 110 V DC 120/127 V DC 220 V DC 240 V DC 100 V AC, 50 Hz 110/125 V AC, 50 Hz 230 V AC, 50 Hz 240 V AC, 50 Hz 100 V AC, 60 Hz 110/125 V AC, 60 Hz 230 V AC, 60 Hz 240 V AC, 60 Hz

For tripping pulseW0.1Ws, 20 for protection relay 7SJ45 For 3AE1 and 3AE5

3AX11 03-2B 3AX11 03-2L 3AX11 03-2C 3AX11 03-2D 3AX11 03-2E 3AX11 03-2N 3AX11 03-2F 3AX11 03-2P 3AX11 03-2G 3AX11 03-2H 3AX11 03-2J 3AX11 03-2M 3AX11 03-3G 3AX11 03-3H 3AX11 03-3J 3AX11 03-3M 3AX14 13-2A 3AX14 13-5A 3AY17 11-2B 3AY17 11-2C 3AY17 11-2D 3AY17 11-2E 3AY17 11-2F 3AY17 11-0B 3AY17 11-0C 3AY17 11-0C 3AY17 11-0E 3AY17 11-0F SWB: 55656 SWB: 55658 SWB: 55659 SWB: 55660 SWB: 55661 SWB: 55662 SWB: 55663 SWB: 55665 SWB: 55666 SWB: 55667 SWB: 55668 SWB: 55669 SWB: 55670 3AY14 20-0B 3AY14 20-0E

Mounting parts Drive motor

For undervoltage release

Auxiliary contactor

Type 3RH11 22 For anti-pumping

Electronic module

For 3AE5

Siemens HG 11.02 2013

39

Equipment Selection
Accessories and spare parts

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Position: Designation Description Feature

19

Order No.

Position switch

Type SE4 without installation accessories Used for: Electrical anti-pumping (-S3) Electrical interlocking (-S12) Motor control (-S21, -S22) Closing spring charged (-S4) Circuit-breaker tripping signal (-S6) Electrical closing lock-out (-S5) Withdrawable part (-S1.0 to - S1.9) Nos. 1 1 2 1 2 1 10 3SV92 73-2AA0 3SV92 74-2AA0 For 3AE1 State position indicator of withdrawable part (for conductor cross-section 1.5 mm) Crimp pins (for lower part of plug) Crimp sockets (for upper part of plug) Crimping pliers Disassembly tool Plug connector, complete For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 For 3AE1 For 3AE1 For 3AE5 For 3AE5 For 3AE5 For 3AE1 For 3AE1 7.2 to 17.5 kV to 1250 A 7.2 to 17.5 kV to 3150 A 24 kV to 2500 A 7.2 to 17.5 kV 7.2 to 17.5 kV 7.2 to 17.5 kV 7.2 to 12 kV 7.2 to 12 kV 7.2 to 12 kV 24 kV 24 kV 24-pole 64-pole 24 V DC 30/32 V DC 48 V DC 60 V DC 100/127 V DC 220/240 V DC 100 V AC, 50/60 Hz 100/125 V AC, 50/60 Hz 220/240 V AC, 50/60 Hz 24-pole 64-pole 64-pole 3AX11 34-3A 3AX11 34-4B 3AX11 34-4C 3AX11 34-4D 3AX11 34-4G 3AX11 34-7A 3AX11 34-6A 3AX14 05-2B 3AX14 05-2K 3AX14 05-2C 3AX14 05-2D 3AX14 05-2E 3AX14 05-2F 3AX14 05-2G 3AX14 05-2H 3AX14 05-2J 3AX14 15-2A 3AX14 16-2A 3AX14 51-2A 3AX14 51-2B 3AX14 51-2B 3AX14 38-2A 3AX14 38-2C 3AX14 38-2D 3AX14 38-5A 3AX14 38-5C 3AX14 38-5D 3AX14 38-2B 3AX14 38-3B 3AX14 52-2B For 3AE1 For 3AE1 and 3AE5 3AX14 20-2A 3AX14 37-2A 3AX14 60-2A SWB: 46677

Auxiliary switch (-S1) Mechanical interlocking Key-operated interlocking Module connector Accessories for plug connector

6 NO + 6 NC 12 NO + 12 NC

Electrical closing lock-out

Mounting parts Bushing

For electrical closing lock-out

Separating shell towards contact arm side, for standard circuit-breakers only for additional screening in case of narrow installation conditions Standard version, width across flats 310 mm Standard version, width across flats 275 mm Standard version, width across flats 205 mm Standard version, width across flats 310 mm Standard version, width across flats 275 mm Standard version, width across flats 205 mm Standard version, width across flats 310 mm Short version, width across flats 310 mm Gate for cartridge Short version

40

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Equipment Selection
Accessories and spare parts

Position: Designation Description Feature

19

Order No. 3AX14 42-2A 3AX14 42-2B 3AX14 42-2C 3AX14 42-2D 3AX14 43-2A 3AX14 43-2B 3AX14 43-2C 3AX14 43-2D 3AX14 43-2E 3AX14 43-2F 3AX14 43-2G 3AX14 43-2H 3AX14 43-2J 3AX14 43-2K 3AX14 44-2A 3AX14 44-2B 3AX14 44-2A 3AX14 44-2C 3AX14 55-2A 3AX14 55-2A 3AX14 55-2B 3AX14 55-2C 3AX14 55-2D 3AX14 55-2E 3AX14 55-2F 3AX14 55-2G 3AX14 55-2H 3AX14 19-0A 3AX14 19-0B 3AX14 19-5A

Contact system

For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5 For 3AE1 and 3AE5

7.2/12/24 kV, 800 up to 1250 A 17.5 kV, 800 up to 1250 A 7.2/12/24 kV, up to 3150 A 17.5 kV, up to 3150 A 7.2/12 kV, up to 31.5 kA, up to 1250 A 7.2/12 kV, up to 31.5 kA, up to 2500 A 17.5 kV, up to 31.5 kA, up to 1250 A 17.5 kV, up to 31.5 kA, up to 2500 A 24 kV, up to 25 kA, up to 1250 A 24 kV, up to 25 kA, up to 2500 A 7.2/12 kV, 40 kA, up to 1250 A 7.2/12 kV, 40 kA, up to 3150 A 17.5 kV, 40 kA, up to 1250 A 17.5 kV, 40 kA, up to 3150 A 7.2/12/17.5 kV, up to 31.5 kA, to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, to 2500 A 7.2/12/17.5 kV, 40 kA, up to 3150 A 24 kV, up to 25 kA, up to 2500 A 7.2/12/17.5 kV, up to 31.5 kA, to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, to 2500 A 7.2/12/17.5 kV, 40 kA, up to 3150 A 24 kV, up to 25 kA, up to 2150 A 24 kV, up to 25 kA, up to 2150 A 24 kV, up to 25 kA, up to 2500 A 24 kV, up to 25 kA, up to 2500 A For 3AE5 For 3AE5

Contact arm, complete with contact system

Fixed contact

Conductor bars (1 set each) for earthing switch connection

For 3AE1 and 3AE5 150/210 mm pole-center distance, 275 mm width across flats 150 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 275 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 275 mm pole-center distance, 310 mm width across flats

Protection plate PG cable gland

150/160 mm pole-center distance 210 mm pole-center distance

Siemens HG 11.02 2013

41

Equipment Selection
Accessories and spare parts

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Position: Designation Rated short-circuit breaking current at 36 % DC component Description Travel / feature

19

10 Language code *

Order No.

Ur

ISC kA mm 150 /160 150 /160 210 210 210 210 275 275 150 /160 150 /160 210 210 31.5 31.5 31.5 31.5 31.5 40 25 25 25 25 31.5 31.5 31.5 31.5 31.5 40 25 25 25 25 150 150 210 210 210 210 210 275 210 275 150 150 210 210 210 210 210 275 210 275 275 310 275 310 310 310 310 310 310 310 275 310 275 310 310 310 310 310 310 310 mm

kV Withdrawable part 17.5 17.5 17.5 17.5 24 24 24 24 17.5 17.5 17.5 17.5 Cartridge without earthing switch 17.5 17.5 17.5 17.5 17.5 17.5 24 24 24 24 Cartridge with earthing switch 17.5 17.5 17.5 17.5 17.5 17.5 24 24 24 24 A B C D E F G H Z

Rated normal current Ir A 220 mm (without cable harness) 220 mm (with cable harness) 220 mm (without cable harness) 220 mm (with cable harness) 260 mm (without cable harness) 260 mm (with cable harness) 260 mm (without cable harness) 260 mm (with cable harness) 180 mm (without cable harness) 180 mm (with cable harness) 180 mm (without cable harness) 180 mm (with cable harness) 1250 1250 1250 1250 > 1250 all Ir 1250 1250 > 1250 > 1250 1250 1250 1250 1250 > 1250 all Ir 1250 1250 > 1250 > 1250 with partition with partition without partition without partition without partition without partition with partition with partition without partition without partition 3AX71 12-2A 3AX71 12-3A 3AX71 12-2B 3AX71 12-3B 3AX71 12-2C 3AX71 12-3C 3AX71 12-2D 3AX71 12-3D 3AX71 12-2E 3AX71 12-3E 3AX71 12-2F 3AX71 12-3F 3AX71 11-5A 3AX71 11-5B 3AX71 11-5C 3AX71 11-5D 3AX71 11-5G 3AX71 11-5H 3AX71 11-5E 3AX71 11-5F 3AX71 11-5J 3AX71 11-5K 3AX71 11-6A 3AX71 11-6B 3AX71 11-6C 3AX71 11-6D 3AX71 11-6G 3AX71 11-6H 3AX71 11-6E 3AX71 11-6J 3AX71 11-6F 3AX71 11-6K n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n n

Pole-center distance

*) The language of the rating plate is given in the table. The individual code has to be added to the order number.
German English French Spanish Italian Russian Portuguese Polish Open with Z = ...

42

Siemens HG 11.02 2013

Width across flats

Rated voltage for 50 / 60 Hz

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Contents

Contents

Page

Technical Data
Electrical data, dimensions and weights Voltage level 7.2 kV Operating cycle diagrams for 7.2 kV Voltage level 12 kV Operating cycle diagrams for 12 kV Voltage level 17.5 kV Operating cycle diagrams for 17.5 kV Voltage level 24 kV Operating cycle diagrams for 24 kV Dimension drawings Voltage levels 7.2 to 24 kV
R-HG11-380.tif

43
44 50 51 57 58 61 62 63

64 72 72 72

Operating times and internal times Short-circuit protection of motors Consumption data of releases Circuit diagrams Standard scheme for plug connector for 3AE1 Position switch for withdrawable part for 3AE1 Additional equipment for 3AE1 Additional equipment: Releases for 3AE1 Standard scheme for plug connector for 3AE5 Position switch for withdrawable part for 3AE5 Additional equipment for 3AE5 Additional equipment: Releases for 3AE5

SION vacuum circuit-breaker on withdrawable part, with contacts

74 74 75 76 77 77 78 79

Contact assignment for auxiliary switch for 3AE1 75

Contact assignment for auxiliary switch for 3AE5 78

SION vacuum circuit-breaker on withdrawable part, with contacts

R-HG11-375.tif

Siemens HG 11.02 2013

43

Technical Data
Electrical data, dimensions and weights for 3AE5

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

50 / 60 Hz

Ir A 3AE5 002-1... mm mm n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 16 16 20 20 25 25 16 16 20 20 25 25 16 16 20 20 25 25 % 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 kA

Ima kA

Up kV 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

Ud kV 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 mV 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 mm mm mm mm 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 kg 49/ 49/ 49/ 49/ 49/ 49/ 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/85 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 1 1 2 2 3a 3a 1 1 2 2 3a 3a 1 1 2 2 3a 3a

800 205 150

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 002-2... 1250 205 150 3AE5 003-1... 800 205 150

3AE5 003-2... 1250 205 150 3AE5 004-1... 800 205 150

3AE5 004-2... 1250 205 150 3AE5 012-1... 800 275 150

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 012-2... 1250 275 150

3AE5 013-1...

800 275 150

3AE5 013-2... 1250 275 150 3AE5 014-1... 800 275 150

3AE5 014-2... 1250 275 150 3AE5 022-1... 800 310 150

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 022-2... 1250 310 150 3AE5 023-1... 800 310 150

3AE5 023-2... 1250 310 150 3AE5 024-1... 800 310 150

3AE5 024-2... 1250 310 150

Note: Dimension drawings from page 64

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

44

Siemens HG 11.02 2013

Operating cycle diagram no. (see page 50)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

7.2 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Electrical data, dimensions and weights for 3AE5

50 / 60 Hz

Ir A 3AE5 032-1... mm mm n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 16 16 20 20 25 25 16 16 20 20 25 25 16 16 20 20 25 25 16 16 % kA

Ima kA

Up kV 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

Ud kV 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 mV 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 mm mm mm mm 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 kg 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202022 S_A7E_44202022 1 1 2 2 3a 3a 1 1 2 2 3a 3a 1 1 2 2 3a 3a 1 1

800 205 160

50 17.9 40/42 50 17.9 40/42 50 22.4 50/52 50 22.4 50/52 50 50 28 28 63/65 63/65

3AE5 032-2... 1250 205 160 3AE5 033-1... 800 205 160

3AE5 033-2... 1250 205 160 3AE5 034-1... 800 205 160

3AE5 034-2... 1250 205 160 3AE5 042-1... 800 275 160

50 17.9 40/42 50 17.9 40/42 50 22.4 50/52 50 22.4 50/52 50 50 28 28 63/65 63/65

3AE5 042-2... 1250 275 160 3AE5 043-1... 800 275 160

Operating cycle diagram no. (see page 50)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

7.2 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

3AE5 043-2... 1250 275 160 3AE5 044-1... 800 275 160

3AE5 044-2... 1250 275 160 3AE5 052-1... 800 310 160

50 17.9 40/42 50 17.9 40/42 50 22.4 50/52 50 22.4 50/52 50 50 28 28 63/65 63/65

3AE5 052-2... 1250 310 160 3AE5 053-1... 800 310 160

3AE5 053-2... 1250 310 160 3AE5 054-1... 800 310 160

3AE5 054-2... 1250 310 160 3AE5 062-1... 800 205 210

50 17.9 40/42 50 17.9 40/42

129 51.5/91.5 129 51.5/91.5

3AE5 062-2... 1250 205 210

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the n Standard information on rating plate dimension drawing of the withdrawable part (page 68)  Possible with order suffix Z and order code F28

Siemens HG 11.02 2013

45

Technical Data
Electrical data, dimensions and weights for 3AE5

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

50 / 60 Hz

Ir A 3AE5 063-1... mm mm n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 20 20 25 25 16 16 20 20 25 25 16 16 20 20 25 25 % 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 kA

Ima kA

Up kV 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

Ud kV 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 mV 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 mm mm mm mm 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 129 129 129 129 kg 51.5/ 51.5/ 51.5/ 51.5/ S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 2 2 3a 3a 1 1 2 2 3a 3a 1 1 2 2 3a 3a

800 205 210

22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 063-2... 1250 205 210 3AE5 064-1... 800 205 210

3AE5 064-2... 1250 205 210 3AE5 072-1... 800 275 210

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5

3AE5 072-2... 1250 275 210 3AE5 073-1... 800 275 210

3AE5 073-2... 1250 275 210

3AE5 074-1...

800 275 210

3AE5 074-2... 1250 275 210 3AE5 082-1... 800 310 210

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 082-2... 1250 310 210 3AE5 083-1... 800 310 210

3AE5 083-2... 1250 310 210 3AE5 084-1... 800 310 210

3AE5 084-2... 1250 310 210

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the n Standard information on rating plate dimension drawing of the withdrawable part (page 68)  Possible with order suffix Z and order code F28

46

Siemens HG 11.02 2013

Operating cycle diagram no. (see page 50)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

7.2 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Electrical data, dimensions and weights for 3AE1

50 / 60 Hz

Ir A 3AE1 002-1... mm mm n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

ISC kA 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA

Ima kA

Up kV 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

Ud kV 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 67/ 67/ 67/ 67/ 67/ 67/ 80/ 80/ 67/103 67/103 67/103 67/103 67/103 67/103 80/120 80/120 67/103 67/103 67/103 67/103 67/103 67/103 80/120 80/120 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 1 1 2 2 3a 3a 4 4 1 1 2 2 3a 3a 4 4 1 1 2 2 3a 3a 4 4

800 205 150

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 002-2... 1250 205 150 3AE1 003-1... 800 205 150

3AE1 003-2... 1250 205 150 3AE1 004-1... 800 205 150

3AE1 004-2... 1250 205 150 3AE1 005-1... 800 205 150

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 005-2... 1250 205 150 3AE1 012-1... 800 275 150

Operating cycle diagram no. (see page 50)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

7.2 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

3AE1 012-2... 1250 275 150 3AE1 013-1... 800 275 150

3AE1 013-2... 1250 275 150 3AE1 014-1... 800 275 150

3AE1 014-2... 1250 275 150 3AE1 015-1... 800 275 150

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 015-2... 1250 275 150 3AE1 022-1... 800 310 150

3AE1 022-2... 1250 310 150 3AE1 023-1... 800 310 150

3AE1 023-2... 1250 310 150 3AE1 024-1... 800 310 150

3AE1 024-2... 1250 310 150 3AE1 025-1... 800 310 150

35.4 80/82 35.4 80/82

3AE1 025-2... 1250 310 150 Note: Dimension drawings from page 64

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 69)

Siemens HG 11.02 2013

47

Technical Data
Electrical data, dimensions and weights for 3AE1

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

50 / 60 Hz

Ir A 3AE1 032-1... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

ISC kA 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA

Ima kA

Up kV 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

Ud kV 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 165 129 140 165 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 67/ 67/ 67/ 67/ 67/ 67/ 80/ 80/ 67/ 67/ 67/ 67/ 67/ 67/ 80/ 80/ 67 67 67 67 67 67 80 80 67/ 67/ S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202022 S_A7E_44202022 1 1 2 2 3a 3a 4 4 1 1 2 2 3a 3a 4 4 1 1 2 2 3a 3a 4 4 1 1

800 205 160

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 032-2... 1250 205 160 3AE1 033-1... 800 205 160

3AE1 033-2... 1250 205 160 3AE1 034-1... 800 205 160

3AE1 034-2... 1250 205 160 3AE1 035-1... 800 205 160

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 035-2... 1250 205 160

3AE1 042-1...

800 275 160

3AE1 042-2... 1250 275 160 3AE1 043-1... 800 275 160

3AE1 043-2... 1250 275 160 3AE1 044-1... 800 275 160

3AE1 044-2... 1250 275 160 3AE1 045-1... 800 275 160

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 045-2... 1250 275 160 3AE1 052-1... 800 310 160

3AE1 052-2... 1250 310 160 3AE1 053-1... 800 310 160

3AE1 053-2... 1250 310 160 3AE1 054-1... 800 310 160

3AE1 054-2... 1250 310 160 3AE1 055-1... 800 310 160

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42

3AE1 055-2... 1250 310 160 3AE1 062-1... 800 205 210

3AE1 062-2... 1250 205 210

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

48

Siemens HG 11.02 2013

Operating cycle diagram no. (see page 50)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

7.2 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Electrical data, dimensions and weights for 3AE1

50 / 60 Hz

Ir A 3AE1 063-1... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

ISC kA 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 25 31.5 31.5 31.5 31.5 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA

Ima kA

Up kV 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

Ud kV 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.5 2.1 2.1 1.5 1.5 mm mm mm mm 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 160 129 140 160 129 140 160 129 140 160 129 140 160 129 140 160 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 67/ 67/ 67/ 67/ 90/ 90/ 67/103 67/103 67/103 67/103 67/103 67/103 90/130 90/130 67/103 67/103 67/103 67/103 67/103 67/103 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202028 S_A7E_44202024 S_A7E_44202024 S_A7E_44202028 S_A7E_44202028 2 2 3a 3a 4 4 1 1 2 2 3a 3a 4 4 1 1 2 2 3a 3a 3 4 4 4 4

800 205 210

22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 063-2... 1250 205 210 3AE1 064-1... 800 205 210

3AE1 064-2... 1250 205 210 3AE1 065-1... 800 205 210

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 065-2... 1250 205 210 3AE1 072-1... 800 275 210

3AE1 072-2... 1250 275 210 3AE1 073-1... 800 275 210

Operating cycle diagram no. (see page 50)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

7.2 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

3AE1 073-2... 1250 275 210 3AE1 074-1... 800 275 210

3AE1 074-2... 1250 275 210 3AE1 075-1... 800 275 210

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 28 63/65 63/65 63/65

3AE1 075-2... 1250 275 210 3AE1 082-1... 800 310 210

3AE1 082-2... 1250 310 210 3AE1 083-1... 800 310 210

3AE1 083-2... 1250 310 210 3AE1 084-1... 800 310 210

3AE1 084-2... 1250 310 210 3AE1 084-4... 2000 310 210 3AE1 085-1... 800 310 210

129 265 130 130 110/150 129 140 160 129 140 160 75 75 90/130 90/130

35.4 80/82 35.4 80/82 35.4 80/82 35.4 80/82

3AE1 085-2... 1250 310 210 3AE1 085-4... 2000 310 210 3AE1 085-6... 2500 310 210

129 265 130 130 110/150 129 265 130 130 110/150

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

Siemens HG 11.02 2013

49

Technical Data
Electrical data, dimensions and weights for 3AE1

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Rated lightning impulse withstand voltage

50 / 60 Hz

Ir A mm mm n n n n

tk s 3 3 3 3

ISC kA 40 40 40 40 % 36 36 36 36 kA

Ima kA

Up kV

Ud kV 20 20 20 20 mV 1.7 1.0 1.0 1.0 mm mm mm mm kg S_A7E_44202070 S_A7E_44202071 S_A7E_44202071 S_A7E_44202071 5 5 5 5

3AE1 086-2... 1250 310 210 3AE1 086-4... 2000 310 210 3AE1 086-6... 2500 310 210 3AE1 086-7... 3150 310 210

44.9 100/104 60 44.9 100/104 60 44.9 100/104 60 44.9 100/104 60

145 155 169 140 120/160 145 249 149 140 160/210 145 249 149 140 160/210 145 249 149 140 160/210

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

Operating cycle diagrams for 7.2 kV


20 000 The permissible number of electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape 200 70 46 30 100
HG11-2540c_en eps

20 000

Operating cycles No.

5 000 2 000 1 000 500

Operating cycles No.

10 000

10 000 5 000 2 000 1 000 500 200 80 50 100


HG11-2539c_en eps

beyond the parameters defined in IEC 62271-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.

20 10 0.5 1 2

1 2

3a

20 10 0.5 1 2 5

5 10 16 20 25 kA 50 Breaking current (r.m.s. value)

Breaking current (r.m.s. value)

10 kA 20 25 40 50 31.5

50

Siemens HG 11.02 2013

Operating cycle diagram no. (see below)

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

7.2 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Electrical data, dimensions and weights for 3AE5

50 / 60 Hz

Ir A 3AE5 102-1... mm mm n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 16 16 20 20 25 25 16 16 20 20 25 25 16 16 20 20 25 25 16 16 % 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 kA

Ima kA

Up kV 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75

Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 mV 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 mm mm mm mm 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 kg 49/ 49/ 49/ 49/ 49/ 49/ 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/85 49/ 49/ S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202016 S_A7E_44202016 6 6 7 7 8a 8a 6 6 7 7 8a 8a 6 6 7 7 8a 8a 6 6

800 205 150

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 102-2... 1250 205 150 3AE5 103-1... 800 205 150

3AE5 103-2... 1250 205 150 3AE5 104-1... 800 205 150

3AE5 104-2... 1250 205 150 3AE5 112-1... 800 275 150

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 112-2... 1250 275 150 3AE5 113-1... 800 275 150

Operating cycle diagram no. (see page 57)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

12 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

3AE5 113-2... 1250 275 150 3AE5 114-1... 800 275 150

3AE5 114-2... 1250 275 150 3AE5 122-1... 800 310 150

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 122-2... 1250 310 150 3AE5 123-1... 800 310 150

3AE5 123-2... 1250 310 150 3AE5 124-1... 800 310 150

3AE5 124-2... 1250 310 150 3AE5 132-1... 800 205 160

17.9 40/42 17.9 40/42

3AE5 132-2... 1250 205 160

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

Siemens HG 11.02 2013

51

Technical Data
Electrical data, dimensions and weights for 3AE5

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

50 / 60 Hz

Ir A 3AE5 133-1... mm mm n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 20 20 25 25 16 16 20 20 25 25 16 16 20 20 25 25 16 16 20 20 % 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 kA

Ima kA

Up kV 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75

Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 mV 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 mm mm mm mm 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 129 kg 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 49/ 51.5/ 51.5/ 51.5/ 51.5/ S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 7 7 8a 8a 6 6 7 7 8a 8a 6 6 7 7 8a 8a 6 6 7 7

800 205 160

22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 133-2... 1250 205 160 3AE5 134-1... 800 205 160

3AE5 134-2... 1250 205 160 3AE5 142-1... 800 275 160

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 142-2... 1250 275 160 3AE5 143-1... 800 275 160

3AE5 143-2... 1250 275 160

3AE5 144-1...

800 275 160

3AE5 144-2... 1250 275 160 3AE5 152-1... 800 310 160

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 152-2... 1250 310 160 3AE5 153-1... 800 310 160

3AE5 153-2... 1250 310 160 3AE5 154-1... 800 310 160

3AE5 154-2... 1250 310 160 3AE5 162-1... 800 205 210

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52

3AE5 162-2... 1250 205 210 3AE5 163-1... 800 205 210

3AE5 163-2... 1250 205 210

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

52

Siemens HG 11.02 2013

Operating cycle diagram no. (see page 57)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

12 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Electrical data, dimensions and weights for 3AE5

50 / 60 Hz

Ir A 3AE5 164-1... mm mm n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 25 25 16 16 20 20 25 25 16 16 20 20 25 25 25 25 % 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 kA 28 28

Ima kA 63/65 63/65

Up kV 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75

Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 mV 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 mm mm mm mm 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 245 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 93 129 129 kg 49/ 49/ S_A7E_44202022 S_A7E_44202022 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 8a 8a 6 6 7 7 8a 8a 6 6 7 7 8a 8a 8a 8a

800 205 210

3AE5 164-2... 1250 205 210 3AE5 172-1... 800 275 210

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 51.5/91.5 129 129 49/ 49/

3AE5 172-2... 1250 275 210 3AE5 173-1... 800 275 210

3AE5 173-2... 1250 275 210 3AE5 174-1... 800 275 210

3AE5 174-2... 1250 275 210 3AE5 182-1... 800 310 210

Operating cycle diagram no. (see page 57)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

12 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE5 182-2... 1250 310 210 3AE5 183-1... 800 310 210

3AE5 183-2... 1250 310 210 3AE5 184-1... 800 310 210

3AE5 184-2... 1250 310 210 3AE5 554-1... 800 275 160

44.9 63/65 44.9 63/65

3AE5 554-2... 1250 275 160

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the n Standard information on rating plate dimension drawing of the withdrawable part (page 68)  Possible with order suffix Z and order code F28

Siemens HG 11.02 2013

53

Technical Data
Electrical data, dimensions and weights for 3AE1

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

50 / 60 Hz

Ir A 3AE1 102-1... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

ISC kA 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA

Ima kA

Up kV 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75

Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 115 129 140 115 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 67/ 67/ 67/ 67/ 67/ 67/ 80/ 80/ 67/103 67/103 67/103 67/103 67/103 67/103 80/120 80/120 67/103 67/103 67/103 67/103 67/103 67/103 80/120 80/120 67/ 67/ S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202010 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202011 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202012 S_A7E_44202016 S_A7E_44202016 6 6 7 7 8a 8a 9 9 6 6 7 7 8a 8a 9 9 6 6 7 7 8a 8a 9 9 6 6

800 205 150

17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 102-2... 1250 205 150 3AE1 103-1... 800 205 150

3AE1 103-2... 1250 205 150 3AE1 104-1... 800 205 150

3AE1 104-2... 1250 205 150 3AE1 105-1... 800 205 150

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 105-2... 1250 205 150

3AE1 112-1...

800 275 150

3AE1 112-2... 1250 275 150 3AE1 113-1... 800 275 150

3AE1 113-2... 1250 275 150 3AE1 114-1... 800 275 150

3AE1 114-2... 1250 275 150 3AE1 115-1... 800 275 150

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 115-2... 1250 275 150 3AE1 122-1... 800 310 150

3AE1 122-2... 1250 310 150 3AE1 123-1... 800 310 150

3AE1 123-2... 1250 310 150 3AE1 124-1... 800 310 150

3AE1 124-2... 1250 310 150 3AE1 125-1... 800 310 150

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42

3AE1 125-2... 1250 310 150 3AE1 132-1... 800 205 160

3AE1 132-2... 1250 205 160

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68) Rated operating sequence possible up to ISC = 31.5 kA

54

Siemens HG 11.02 2013

Operating cycle diagram no. (see page 57)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

12 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Electrical data, dimensions and weights for 3AE1

50 / 60 Hz

Ir A 3AE1 133-1... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

ISC kA 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA

Ima kA

Up kV 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75

Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 165 129 140 165 129 140 165 129 140 165 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 67/ 67/ 67/ 67/ 80/ 80/ 67/ 67/ 67/ 67/ 67/ 67/ 80/ 80/ 67/ 67/ 67/ 67/ 67/ 67/ 80/ 80/ 67/ 67/ 67/ 67/ S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202016 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202017 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202018 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 7 7 8a 8a 9 9 6 6 7 7 8a 8a 9 9 6 6 7 7 8a 8a 9 9 6 6 7 7

800 205 160

22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 133-2... 1250 205 160 3AE1 134-1... 800 205 160

3AE1 134-2... 1250 205 160 3AE1 135-1... 800 205 160

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 135-2... 1250 205 160 3AE1 142-1... 800 275 160

3AE1 142-2... 1250 275 160 3AE1 143-1... 800 275 160

Operating cycle diagram no. (see page 57)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

12 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

3AE1 143-2... 1250 275 160 3AE1 144-1... 800 275 160

3AE1 144-2... 1250 275 160 3AE1 145-1... 800 275 160

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 145-2... 1250 275 160 3AE1 152-1... 800 310 160

3AE1 152-2... 1250 310 160 3AE1 153-1... 800 310 160

3AE1 153-2... 1250 310 160 3AE1 154-1... 800 310 160

3AE1 154-2... 1250 310 160 3AE1 155-1... 800 310 160

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52

3AE1 155-2... 1250 310 160 3AE1 162-1... 800 205 210

3AE1 162-2... 1250 205 210 3AE1 163-1... 800 205 210

3AE1 163-2... 1250 205 210

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68) Rated operating sequence possible up to ISC = 31.5 kA

Siemens HG 11.02 2013

55

Technical Data
Electrical data, dimensions and weights for 3AE1

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

50 / 60 Hz

Ir A 3AE1 164-1... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

ISC kA 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 25 25 31.5 31.5 31.5 31.5 40 40 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 28 28

Ima kA 63/65 63/65

Up kV 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75

Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.5 1.5 2.1 2.1 1.5 1.5 1.7 1.0 mm mm mm mm 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 160 129 140 160 129 140 160 129 140 160 129 140 160 129 140 160 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 67/ 67/ 90/ 90/ 67/103 67/103 67/103 67/103 67/103 67/103 90/130 90/130 67/103 67/103 67/103 67/103 67/103 67/103 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 S_A7E_44202022 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202023 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202024 S_A7E_44202028 S_A7E_44202028 S_A7E_44202024 S_A7E_44202024 S_A7E_44202028 S_A7E_44202028 S_A7E_44202070 S_A7E_44202071 8a 8a 9 9 6 6 7 7 8a 8a 9 9 6 6 7 7 8a 8a 8 8 9 9 9 9 10 10

800 205 210

3AE1 164-2... 1250 205 210 3AE1 165-1... 800 205 210

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 63/65 63/65

3AE1 165-2... 1250 205 210 3AE1 172-1... 800 275 210

3AE1 172-2... 1250 275 210 3AE1 173-1... 800 275 210

3AE1 173-2... 1250 275 210

3AE1 174-1...

800 275 210

3AE1 174-2... 1250 275 210 3AE1 175-1... 800 275 210

35.4 80/82 35.4 80/82 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 28 28 28 28 63/65 63/65 63/65 63/65

3AE1 175-2... 1250 275 210 3AE1 182-1... 800 310 210

3AE1 182-2... 1250 310 210 3AE1 183-1... 800 310 210

3AE1 183-2... 1250 310 210 3AE1 184-1... 800 310 210

3AE1 184-2... 1250 310 210 3AE1 184-4... 2000 310 210 3AE1 184-6... 2500 310 210 3AE1 185-1... 800 310 210

129 265 130 130 110/150 129 265 130 130 110/150 129 140 160 129 140 160 75 75 90/130 90/130

35.4 80/82 35.4 80/82 35.4 80/82 35.4 80/82

3AE1 185-2... 1250 310 210 3AE1 185-4... 2000 310 210 3AE1 185-6... 2500 310 210 3AE1 186-2... 1250 310 210 3AE1 186-4... 2000 310 210

129 265 130 130 110/150 129 265 130 130 110/150 145 155 169 140 120/160 145 249 149 140 160/210

44.9 100/104 75 44.9 100/104 75

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68) Rated operating sequence possible up to ISC = 31.5 kA

56

Siemens HG 11.02 2013

Operating cycle diagram no. (see page 57)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

12 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Electrical data, dimensions and weights for 3AE1

Rated lightning impulse withstand voltage

50 / 60 Hz

Ir A mm mm n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3

ISC kA 40 40 25 25 31.5 31.5 31.5 31.5 40 40 40 % 36 36 36 36 36 36 36 36 36 36 36 kA

Ima kA

Up kV

Ud kV 28 28 28 28 28 28 28 28 28 28 28 mV 1.0 1.0 2.1 2.1 2.1 2.1 2.1 1.7 1.0 1.0 mm mm mm mm kg S_A7E_44202071 S_A7E_44202071 10 10 8a 8a 9 9 9 9 10 10 10

3AE1 186-6... 2500 310 210 3AE1 186-7... 3150 310 210 3AE1 554-1... 800 275 160

44.9 100/104 75 44.9 100/104 75 44.9 63/65 44.9 63/65 44.9 80/82 44.9 80/82 44.9 80/82 44.9 80/82 75 75 75 75 75 75

145 249 149 140 160/210 145 249 149 140 160/210 129 140 115 129 140 115 129 140 115 129 140 115 129 140 165 75 75 75 75 75 67/ 67/ 80/ 80/ 90/ 120/ 160/ 160/

3AE1 554-2... 1250 275 160 3AE1 555-1... 800 275 160

3AE1 555-2... 1250 275 160 3AE1 565-2... 1250 275 210 3AE1 565-6... 2500 275 210 3AE1 566-2... 1250 275 210 3AE1 566-6... 2500 275 210 3AE1 566-7... 3150 275 210

Operating cycle diagram no. (see below)

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

12 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

44.9 100/104 75 44.9 100/104 75 44.9 100/104 75

145 155 169 140 145 249 149 140 145 249 149 140

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

Operating cycle diagrams for 12 kV


20 000 The permissible number cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape 200 70 46 30 100
HG11-2735b_en eps

20 000

Operating cycles No.

Operating cycles No.

10 000 5 000 2 000 1 000 500

of electrical operating

10 000 5 000 2 000 1 000 500 200 80 50 100


HG11-2734a_en eps

beyond the parameters defined in IEC 62271-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.

20 10 0.5 1 2

6 7

8a

20 10 0.5 1 2 5

9 8 10

5 10 16 20 25 kA 50 Breaking current (r.m.s. value)

10 kA 20 25 40 50 31.5 Breaking current (r.m.s. value)

Siemens HG 11.02 2013

57

Technical Data
Electrical data, dimensions and weights for 3AE1

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

50 / 60 Hz

Ir A 3AE1 201-1... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

ISC kA 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA

Ima kA

Up kV 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95

Ud kV 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 275 237 150 129 275 237 150 129 275 237 150 129 275 237 150 129 275 237 150 129 275 237 150 129 275 237 150 129 275 237 150 kg 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ S_A7E_44202013 S_A7E_44202013 S_A7E_44202013 S_A7E_44202013 S_A7E_44202013 S_A7E_44202013 S_A7E_44202013 S_A7E_44202013 S_A7E_44202014 S_A7E_44202014 S_A7E_44202014 S_A7E_44202014 S_A7E_44202014 S_A7E_44202014 S_A7E_44202014 S_A7E_44202014 S_A7E_44202015 S_A7E_44202015 S_A7E_44202015 S_A7E_44202015 S_A7E_44202015 S_A7E_44202015 S_A7E_44202015 S_A7E_44202015 S_A7E_44202019 S_A7E_44202019 11 11 12 12 13 13 14 14 11 11 12 12 13 13 14 14 11 11 12 12 13 13 14 14 11 11

800 205 150

14.9 31/33 14.9 31/33 17.9 40/42 17.9 40/42 28 28 63/65 63/65

3AE1 201-2... 1250 205 150 3AE1 202-1... 800 205 150

3AE1 202-2... 1250 205 150 3AE1 204-1... 800 205 150

3AE1 204-2... 1250 205 150 3AE1 205-1... 800 205 150

35.4 80/82 35.4 80/82 14.9 31/33 14.9 31/33 17.9 40/42 17.9 40/42 28 28 63/65 63/65

3AE1 205-2... 1250 205 150

3AE1 211-1...

800 275 150

129 275 214 150 80/120 129 275 214 150 80/120 129 275 214 150 80/120 129 275 214 150 80/120 129 275 214 150 80/120 129 275 214 150 80/120 129 275 214 150 80/120 129 275 214 150 80/120 129 275 190 150 80/120 129 275 190 150 80/120 129 275 190 150 80/120 129 275 190 150 80/120 129 275 190 150 80/120 129 275 190 150 80/120 129 275 190 150 80/120 129 275 190 150 80/120 129 275 247 150 129 275 247 150 80/ 80/

3AE1 211-2... 1250 275 150 3AE1 212-1... 800 275 150

3AE1 212-2... 1250 275 150 3AE1 214-1... 800 275 150

3AE1 214-2... 1250 275 150 3AE1 215-1... 800 275 150

35.4 80/82 35.4 80/82 14.9 31/33 14.9 31/33 17.9 40/42 17.9 40/42 28 28 63/65 63/65

3AE1 215-2... 1250 275 150 3AE1 221-1... 800 310 150

3AE1 221-2... 1250 310 150 3AE1 222-1... 800 310 150

3AE1 222-2... 1250 310 150 3AE1 224-1... 800 310 150

3AE1 224-2... 1250 310 150 3AE1 225-1... 800 310 150

35.4 80/82 35.4 80/82 14.9 31/33 14.9 31/33

3AE1 225-2... 1250 310 150 3AE1 231-1... 800 205 160

3AE1 231-2... 1250 205 160

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68) Rated operating sequence possible up to ISC = 31.5 kA

58

Siemens HG 11.02 2013

Operating cycle diagram no. (see page 61)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

17.5 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Electrical data, dimensions and weights for 3AE1

50 / 60 Hz

Ir A 3AE1 232-1... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

ISC kA 16 16 25 25 31.5 31.5 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 16 16 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA

Ima kA

Up kV 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95

Ud kV 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 275 247 150 129 275 247 150 129 275 247 150 129 275 247 150 129 275 247 150 129 275 247 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 kg 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 90/ 90/ 90/ 90/ S_A7E_44202019 S_A7E_44202019 S_A7E_44202019 S_A7E_44202019 S_A7E_44202019 S_A7E_44202019 S_A7E_44202020 S_A7E_44202020 S_A7E_44202020 S_A7E_44202020 S_A7E_44202020 S_A7E_44202020 S_A7E_44202020 S_A7E_44202020 S_A7E_44202021 S_A7E_44202021 S_A7E_44202021 S_A7E_44202021 S_A7E_44202021 S_A7E_44202021 S_A7E_44202021 S_A7E_44202021 S_A7E_44202025 S_A7E_44202025 S_A7E_44202025 S_A7E_44202025 12 12 13 13 14 14 11 11 12 12 13 13 14 14 11 11 12 12 13 13 14 14 11 11 12 12

800 205 160

17.9 40/42 17.9 40/42 28 28 63/65 63/65

3AE1 232-2... 1250 205 160 3AE1 234-1... 800 205 160

3AE1 234-2... 1250 205 160 3AE1 235-1... 800 205 160

35.4 80/82 35.4 80/82 14.9 31/33 14.9 31/33 17.9 40/42 17.9 40/42 28 28 63/65 63/65

3AE1 235-2... 1250 205 160 3AE1 241-1... 800 275 160

3AE1 241-2... 1250 275 160 3AE1 242-1... 800 275 160

Operating cycle diagram no. (see page 61)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

17.5 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

3AE1 242-2... 1250 275 160 3AE1 244-1... 800 275 160

3AE1 244-2... 1250 275 160 3AE1 245-1... 800 275 160

35.4 80/82 35.4 80/82 14.9 31/33 14.9 31/33 17.9 40/42 17.9 40/42 28 28 63/65 63/65

3AE1 245-2... 1250 275 160 3AE1 251-1... 800 310 160

3AE1 251-2... 1250 310 160 3AE1 252-1... 800 310 160

3AE1 252-2... 1250 310 160 3AE1 254-1... 800 310 160

3AE1 254-2... 1250 310 160 3AE1 255-1... 800 310 160

35.4 80/82 35.4 80/82 14.9 31/33 14.9 31/33 17.9 40/42 17.9 40/42

3AE1 255-2... 1250 310 160 3AE1 261-1... 800 205 210

3AE1 261-2... 1250 205 210 3AE1 262-1... 800 205 210

3AE1 262-2... 1250 205 210

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

Siemens HG 11.02 2013

59

Technical Data
Electrical data, dimensions and weights 3AE1

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

50 / 60 Hz

Ir A 3AE1 264-1... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

ISC kA 25 25 31.5 31.5 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 16 16 25 25 25 25 31.5 31.5 31.5 31.5 40 40 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 28 28

Ima kA 63/65 63/65

Up kV 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95

Ud kV 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.5 1.5 2.1 2.1 1.5 1.5 1.7 1.0 mm mm mm mm 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 kg 90/ 90/ 90/ 90/ S_A7E_44202025 S_A7E_44202025 S_A7E_44202025 S_A7E_44202025 S_A7E_44202026 S_A7E_44202026 S_A7E_44202026 S_A7E_44202026 S_A7E_44202026 S_A7E_44202026 S_A7E_44202026 S_A7E_44202026 S_A7E_44202027 S_A7E_44202027 S_A7E_44202027 S_A7E_44202027 S_A7E_44202027 S_A7E_44202027 S_A7E_44202029 S_A7E_44202029 S_A7E_44202027 S_A7E_44202027 S_A7E_44202029 S_A7E_44202029 S_A7E_44202070 S_A7E_44202071 13 13 14 14 11 11 12 12 13 13 14 14 11 11 12 12 13 13 13 13 14 14 14 14 15 15

800 205 210

3AE1 264-2... 1250 205 210 3AE1 265-1... 800 205 210

35.4 80/82 35.4 80/82 14.9 31/33 14.9 31/33 17.9 40/42 17.9 40/42 28 28 63/65 63/65

3AE1 265-2... 1250 205 210 3AE1 271-1... 800 275 210

129 275 165 150 90/130 129 275 165 150 90/130 129 275 165 150 90/130 129 275 165 150 90/130 129 275 165 150 90/130 129 275 165 150 90/130 129 275 165 150 90/130 129 275 165 150 90/130 129 275 160 150 90/130 129 275 160 150 90/130 129 275 160 150 90/130 129 275 160 150 90/130 129 275 160 150 90/130 129 275 160 150 90/130 129 265 130 130 110/150 129 265 130 130 110/150 129 275 160 150 90/130 129 275 160 150 90/130 129 265 130 130 110/150 129 265 130 130 110/150 145 249 169 140 120/160 145 249 149 140 160/210

3AE1 271-2... 1250 275 210 3AE1 272-1... 800 275 210

3AE1 272-2... 1250 275 210

3AE1 274-1...

800 275 210

3AE1 274-2... 1250 275 210 3AE1 275-1... 800 275 210

35.4 80/82 35.4 80/82 14.9 31/33 14.9 31/33 17.9 40/42 17.9 40/42 28 28 28 28 63/65 63/65 63/65 63/65

3AE1 275-2... 1250 275 210 3AE1 281-1... 800 310 210

3AE1 281-2... 1250 310 210 3AE1 282-1... 800 310 210

3AE1 282-2... 1250 310 210 3AE1 284-1... 800 310 210

3AE1 284-2... 1250 310 210 3AE1 284-4... 2000 310 210 3AE1 284-6... 2500 310 210 3AE1 285-1... 800 310 210

35.4 80/82 35.4 80/82 35.4 80/82 35.4 80/82

3AE1 285-2... 1250 310 210 3AE1 285-4... 2000 310 210 3AE1 285-6... 2500 310 210 3AE1 286-2... 1250 310 210 3AE1 286-4... 2000 310 210

44.9 100/104 95 44.9 100/104 95

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

60

Siemens HG 11.02 2013

Operating cycle diagram no. (see page 61)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

17.5 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Electrical data, dimensions and weights 3AE1

Rated lightning impulse withstand voltage

50 / 60 Hz

Ir A mm mm n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3

ISC kA 40 40 25 25 31.5 31.5 31.5 31.5 40 40 40 % 36 36 36 36 36 36 36 36 36 36 36 kA

Ima kA

Up kV

Ud kV 38 38 38 38 38 38 38 38 38 38 38 mV 1.0 1.0 2.1 2.1 2.1 2.1 2.1 1.7 1.0 1.0 mm mm mm mm kg S_A7E_44202071 S_A7E_44202071 15 15 13 13 14 14 14 14 15 15 15

3AE1 286-6... 2500 310 210 3AE1 286-7... 3150 310 210 3AE1 624-1... 800 275 160

44.9 100/104 95 44.9 100/104 95 44.9 63/65 44.9 63/65 44.9 80/82 44.9 80/82 44.9 80/82 44.9 80/82 95 95 95 95 95 95

145 249 149 140 160/210 145 249 149 140 160/210 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 165 150 80/ 80/ 80/ 80/ 90/ 120/ 160/ 160/

3AE1 624-2... 1250 275 160 3AE1 625-1... 800 275 160

3AE1 625-2... 1250 275 160 3AE1 665-2... 1250 275 210 3AE1 665-6... 2500 275 210 3AE1 666-2... 1250 275 210 3AE1 666-6... 2500 275 210 3AE1 666-7... 3150 275 210

Operating cycle diagram no. (see below)

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

17.5 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

44.9 100/104 95 44.9 100/104 95 44.9 100/104 95

145 249 169 140 145 249 149 140 145 249 149 140

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

Operating cycle diagrams for 17.5 kV


20 000 The permissible number of electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape beyond the parameters defined in IEC 62271-100 is based on
HG11-2537b_en eps

20 000

Operating cycles No.

Operating cycles No.

10 000 5 000 2 000 1 000 500 180 200 80 50 100

10 000 5 000 2 000 1 000 350 500 200 100


HG11-2541a_en eps

average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.

50 20 10 0.5 1 2

20 10 0.5 1 2

12 13 5 kA 10 16 20 25 Breaking current (r.m.s. value)

15

11

14

40 50

5 kA 10 12.5 20 31.5 50 Breaking current (r.m.s. value)

Siemens HG 11.02 2013

61

Technical Data
Electrical data, dimensions and weights 3AE1

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

50 / 60 Hz

Ir A 3AE1 321-1... mm mm n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

ISC kA 12.5 12.5 16 16 16 20 20 20 20 25 25 25 25 16 16 16 20 20 20 20 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA

Ima kA

Up kV 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125

Ud kV 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 mV 2.6 2.6 2.6 2.6 2.0 2.6 2.6 2.0 2.0 2.6 2.6 2.0 2.0 2.6 2.6 2.0 2.6 2.6 2.0 2.0 mm mm mm mm kg S_A7E_44202050 S_A7E_44202050 S_A7E_44202050 S_A7E_44202050 S_A7E_44202051 S_A7E_44202050 S_A7E_44202050 S_A7E_44202051 S_A7E_44202051 S_A7E_44202050 S_A7E_44202050 S_A7E_44202051 S_A7E_44202051 S_A7E_44202052 S_A7E_44202052 S_A7E_44202053 S_A7E_44202052 S_A7E_44202052 S_A7E_44202053 S_A7E_44202053 16 16 17 17 17 18 18 18 18 19 19 19 19 17 17 17 18 18 18 18

800 310 210

14.9 31/33 14.9 31/33 17.9 40/42 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 22.4 50/52 22.4 50/52 28 28 28 28 63/65 63/65 63/65 63/65

200 350 200 210 120/160 200 350 200 210 120/160 200 350 200 210 120/160 200 350 200 210 120/160 200 340 200 205 140/180 200 350 200 210 120/160 200 350 200 210 120/160 200 340 200 205 140/180 200 340 200 205 140/180 200 350 200 210 120/160 200 350 200 210 120/160 200 340 200 205 140/180 200 340 200 205 140/180 200 350 265 210 130/180 200 350 265 210 130/180 200 340 265 205 150/200 200 350 265 210 130/180 200 350 265 210 130/180 200 340 265 205 150/200 200 340 265 205 150/200

3AE1 321-2... 1250 310 210 3AE1 322-1... 800 310 210

3AE1 322-2... 1250 310 210 3AE1 322-4... 2000 310 210 3AE1 323-1... 800 310 210

3AE1 323-2... 1250 310 210 3AE1 323-4... 2000 310 210

3AE1 323-6... 2500 310 210 3AE1 324-1... 800 310 210

3AE1 324-2... 1250 310 210 3AE1 324-4... 2000 310 210 3AE1 324-6... 2500 310 210 3AE1 352-1... 800 310 275

17.9 40/42 17.9 40/42 17.9 40/42 22.4 50/52 22.4 50/52 22.4 50/52 22.4 50/52

3AE1 352-2... 1250 310 275 3AE1 352-4... 2000 310 275 3AE1 353-1... 800 310 275

3AE1 353-2... 1250 310 275 3AE1 353-4... 2000 310 275 3AE1 353-6... 2500 310 275

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

62

Siemens HG 11.02 2013

Operating cycle diagram no. (see page 63)

Rated lightning impulse withstand voltage

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

24 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Electrical data, dimensions and weights 3AE1

Rated lightning impulse withstand voltage

50 / 60 Hz

Ir A 3AE1 354-1... mm mm n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3

ISC kA 25 25 25 25 25 25 25 25 25 25 % 36 36 36 36 36 36 36 36 36 36 kA 28 28 28 28 28 28

Ima kA 63/65 63/65 63/65 63/65 63/65 63/65

Up kV 125 125 125 125 125 125 125 125 125 125

Ud kV 50 50 50 50 50 50 50 50 50 50 mV 2.6 2.6 2.0 2.0 2.6 2.0 2.0 2.0 mm mm mm mm kg S_A7E_44202052 S_A7E_44202052 S_A7E_44202053 S_A7E_44202053 19 19 19 19 19 19 19 19 19 19

800 310 275

200 350 265 210 130/180 200 350 265 210 130/180 200 340 265 205 150/200 200 340 265 205 150/200 200 350 200 210 200 340 200 205 200 340 200 205 120/ 150/ 150/ 150/

3AE1 354-2... 1250 310 275 3AE1 354-4... 2000 310 275 3AE1 354-6... 2500 310 275 3AE1 714-2... 1250 320 210 3AE1 744-4... 2000 320 275 3AE1 744-6... 2500 320 275 3AE1 724-4... 2000 320 210 3AE1 724-6... 2500 320 210 3AE1 754-6... 2500 320 275

44.9 63/65 44.9 63/65 44.9 63/65 44.9 63/65

Operating cycle diagram no. (see below)

Rated short-duration power-frequency withstand voltage Voltage drop U between connections (according to IEC 62271-1 at DC 100 A) Minimum creepage distance. interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth

24 kV
Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50 / 60 Hz) Asymmetrical breaking current Rated duration of short-circuit O 3 min CO 3 min CO O 0.3 s CO 3 min CO Rated operating sequence:

Weight 1) (fixed-mounted circuit-breaker / withdrawable module)

Detailed dimension drawing (has to be ordered)

O 0.3 s CO 15 s CO

Rated normal current

Pole-center distance

Width across flats

Order No.

200 340 200 205

Possible with order suffix Z and order code F27 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in n Standard information on rating plate the dimension drawing of the withdrawable part  Possible with order suffix Z and order code F28 (page 68)

Operating cycle diagrams for 24 kV


20 000 The permissible number cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape 150 50 20 10 0.5 1 2 200 100
HG11-2538b_en eps

20 000

Operating cycles No.

5 000 2 000 1 000 500

Operating cycles No.

10 000

of electrical operating

10 000 5 000 2 000 1 000 500 200 90 30 20 10 0.5 1 2 17 19 100


HG11-2542a_en eps

beyond the parameters defined in IEC 62271-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.

50

16

18

5 10 12.5 20 kA Breaking current (r.m.s. value)

50

5 10 16 25 kA 50 Breaking current (r.m.s. value)

Siemens HG 11.02 2013

63

Technical Data
Dimensions drawings for voltage levels 7.2 kV to 12 kV for 3AE5

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Dimension drawings for 7.2 to 12 kV Vacuum circuit-breaker without contact arm


q a a
HG11-2834 eps

n i m
o g f p

d e

Voltage level

Pole-center distance a mm 150 150 150 160

Width across flats b mm 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310

c mm 445 445 445 465 465 465 565 565 565 445 445 445 465 465 465 565 565 565

d mm 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540

e mm 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5

f mm 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380

g mm 329 329 329 329 329 329 329 329 329 329 329 329 329 329 329 329 329 329

i mm 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5

l mm 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371

m mm 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540

n mm 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105

o mm 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8

p mm 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288

q mm 169 169 169 169 169 169 169 169 169 169 169 169 169 169 169 169 169 169

7.2 kV

160 160 210 210 210 150 150 150 160

3
12 kV

160 160 210 210 210

Note: Small deviations of the dimensions are permissible

64

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Dimensions drawings for voltage levels 7.2 kV to 24 kV for 3AE1

Dimension drawings for 7.2 to 24 kV Vacuum circuit-breaker without contact arm


q n a a
HG11-2813a eps

d e

g f

Voltage level

Pole-center distance a mm 150 150 150 160

Width across flats b mm 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 310 310

c mm 445 445 445 465 465 465 565 565 565 445 445 445 465 465 465 565 565 565 445 445 445 465 465 465 565 565 565 570 700

d mm 540 5) 540 5) 540 5) 540 5) 540 5) 540 5) 540 5) 540 5) 540 5) 540 5) 540 5) 540
5)

e mm 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 283 283

f mm 380 380 380 380 380 380 380 380 380 1) 380 380 380 380 380 380 380 380 380 1) 380 380 380 380 380 380 380 380 380 1) 469 469

g mm 300 6) 300 6) 300 6) 300 6) 300 6) 300 6) 300 6) 300 6) 300 2) 6) 300 6) 300 6) 300
6)

i mm 523 7) 523 7) 523 7) 523 7) 523 7) 523 7) 523 7) 523 7) 523 7) 523 7) 523
7)

l mm 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 421 421

m mm 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540

n mm 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105

o mm 30 30 30 30 30 30 30 30 30 8) 30 30 30 30 30 30 30 30 30 8) 30 30 30 30 30 30 30 30 30 8) 58 58

p mm 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279

q mm 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165

7.2 kV

160 160 210 210 210 150 150 150 160

523 3) 7) 371 4)

540 5) 540 5) 540 5) 540 5) 540 5) 540 5) 562 562 562 562 562 562 562 562 562 739 739

300 6) 300 6) 300 6) 300 6) 300 6) 310 310 310 310 310 310 310 310 310 2) 360 360

523 7) 523 7) 523 7) 523 7) 523 7) 517.5 517.5 517.5 517.5 517.5 517.5 517.5 517.5 739 739

12 kV

160 160 210 210 210 150 150 150 160

300 2) 6) 523 3) 7) 371 4)

17.5 kV

160 160 210 210 210 210 275

517.5 3) 371 4)

24 kV

Note: Dimension drawings for 8B retrofit (13th position = 7) are available on request. Note: Small deviations of the dimensions are permissible 1) At Isc = 40 kA --> 450 mm 2) At Isc = 40 kA --> 350 mm 3) At Isc = 40 kA --> 610 mm 4) At Isc = 40 kA --> 420 mm 5) At Ir >1250 A or at Isc = 31.5 kA --> 562 mm 6) At Ir >1250 A or at Isc = 31.5 kA --> 310 mm 7) At Ir >1250 A or at Isc = 31.5 kA --> 518 mm 8) At Isc = 40 kA --> 50 mm

Siemens HG 11.02 2013

65

Technical Data
Dimensions drawings for voltage levels 7.2 kV to 12 kV for 3AE5

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Dimension drawings for 7.2 to 12 kV Vacuum circuit-breaker with contact arm


q a a
HG11-2835 eps

n i m
o g f p

Voltage level

Pole-center distance a mm 150 150 150 160

Width across flats b mm 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310

c mm 445 445 445 465 465 465 565 565 565 445 445 445 465 465 465 565 565 565

d mm 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540

e mm 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5 217.5 217.5 237.5

f mm 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380

g mm 329 329 329 329 329 329 329 329 329 329 329 329 329 329 329 329 329 329

i mm 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5 500.5

k mm 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274

l mm 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371

m mm 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540

n mm 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105

o mm 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8

p mm 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288 288

q mm 169 169 169 169 169 169 169 169 169 169 169 169 169 169 169 169 169 169

7.2 kV

160 160 210 210 210 150 150 150 160

3
12 kV

160 160 210 210 210

Note: Small deviations of the dimensions are permissible

66

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Dimensions drawings for voltage levels 7.2 kV to 24 kV for 3AE1

Dimension drawings for 7.2 to 24 kV Vacuum circuit-breaker with contact arm


q n a a
HG11-2812a eps

d e

g f

Voltage level

Pole-center distance a mm 150 150 150 160

Width across flats b mm 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 205 275 310 310 310

c mm

d mm

e mm

f mm

g mm 300 6) 300 6) 300 6) 300 6) 300 6) 300 6) 300 6) 300 6) 300 6) 300 6) 300
6)

i mm 523 7) 523 7) 523 7) 523 7) 523 7) 523 7) 523 7) 523 7) 523 3) 7) 523 7) 523 7) 523
7)

k mm 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 274 324 324

l mm 371 371 371 371 371 371 371 371 371 4) 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 371 421 421

m mm 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540

n mm 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105 105

o mm 30 30 30 30 30 30 30 30 30 8) 30 30 30 30 30 30 30 30 30 8) 30 30 30 30 30 30 30 30 30 8) 58 58

p mm 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279 279

q mm 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165

445 540 5) 217.5 380 445 540 5) 217.5 380 445 540 5) 237.5 380 465 540 5) 217.5 380 465 540 5) 217.5 380 465 540 5) 237.5 380 565 540 5) 217.5 380 565 540 5) 217.5 380 445 540 5) 217.5 380 445 540 5) 217.5 380 445 540
5)

7.2 kV

160 160 210 210 210 150 150 150 160

565 540 5) 237.5 380 1) 300 2) 6)

237.5 380

465 540 5) 217.5 380 465 540 5) 217.5 380 465 540 5) 237.5 380 565 540 5) 217.5 380 565 540 5) 217.5 380 445 445 445 465 465 465 565 565 565 570 700 562 217.5 380 562 217.5 380 562 237.5 380 562 217.5 380 562 217.5 380 562 237.5 380 562 217.5 380 562 217.5 380 562 237.5 380 1) 739 739 283 283 469 469

300 6) 300 6) 300 6) 300 6) 300 6) 310 310 310 310 310 310 310 310 310 2) 360 360

523 7) 523 7) 523 7) 523 7) 523 7) 517.5 517.5 517.5 517.5 517.5 517.5 517.5 517.5 517.5 3) 739 739

12 kV

160 160 210 210 210 150 150 150 160

565 540 5) 237.5 380 1) 300 2) 6) 523 3) 7)

371 4) 540

17.5 kV

160 160 210 210 210 210 275

371 4) 540

24 kV

Note: Small deviations of the dimensions are permissible 1) At Isc = 40 kA --> 450 mm 2) At Isc = 40 kA --> 350 mm 3) At Isc = 40 kA --> 610 mm 4) At Isc = 40 kA --> 420 mm 5) At Ir >1250 A or at Isc = 31.5 kA --> 562 mm 6) At Ir >1250 A or at Isc = 31.5 kA --> 310 mm 7) At Ir >1250 A or at Isc = 31.5 kA --> 518 mm 8) At Isc = 40 kA --> 50 mm

Siemens HG 11.02 2013

67

Technical Data
Dimensions drawings for voltage levels 7.2 kV to 24 kV for 3AE5

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Dimension drawings for 7.2 to 12 kV Cartridge without earthing switch


l q a a d
HG11-2836 eps

Voltage level

Pole-center distance a mm 150 150 210 210 150 150 210 210

Width across flats b mm 275 310 275 310 275 310 275 310

c mm 594 594 794 794 594 594 794 794

d mm 147 147 187 187 147 147 187 187

e mm 850 905 850 905 850 905 850 905

f mm 266.5 286.5 266.5 286.5 266.5 286.5 266.5 286.5

g mm 710 710 710 710 710 710 710 710

h mm 263 263 263 263 263 263 263 263

i mm 224 224 224 224 224 224 224 224

k mm 476 476 476 476 476 476 476 476

l mm 371 371 371 371 371 371 371 371

m mm 540 540 540 540 540 540 540 540

n mm 105 105 105 105 105 105 105 105

q mm 169 169 169 169 169 169 169 169

7.2 kV

12 kV

Note: Small deviations of the dimensions are permissible

Withdrawable part
HG11-2590a eps

Voltage level

Pole-center distance mm 150 160 210 150

a mm 529 529 679 529 529 679 529 529 679 679 879

b mm 424 424 424 424 424 424 424 424 424 424 424

c mm 500 500 650 500 500 650 500 500 650 650 850

d mm 470 470 620 470 470 620 470 470 620 620 820

e mm 107 107 107 107 107 107 107 107 107 107 107

f mm 42 42 42 42 42 42 42 42 42 42 42

Weight approx. 15 kg approx. 15 kg approx. 20 kg approx. 15 kg approx. 15 kg approx. 20 kg approx. 15 kg approx. 15 kg approx. 20 kg approx. 20 kg approx. 25 kg

7.2 kV

12 kV

160 210 150

17.5 kV

160 210 210 275

24 kV

68

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Dimensions drawings for voltage levels 7.2 kV to 24 kV for 3AE1

Dimension drawings for 7.2 to 24 kV Cartridge without earthing switch


l q a a d
HG11-2782b eps

Voltage level

Pole-center distance a mm 150 150 210 210 150 150 210 210 150 150 210 210 210 275

Width across flats b mm 275 310 275 310 275 310 275 310 275 310 275 310 310 310

c mm 594 594 794 794 594 594 794 794 594 594 794 794 794 994

d mm 147 147 187 187 147 147 187 187 147 147 187 187

e mm 850 905 850 905 850 905 850 905 850 905 850 905

f mm

g mm

h mm 263 263 263 263 263 263 263 263 263 323 323

h mm 323 323 323 323 323

i mm 224 224 224 224 224 224 224 224 224 224 224 224 274 274

i mm 323 323

k mm 476 476 476 476 476 476 476 476 476 537 537

l mm 371 371 371 371 371 371 371 371 371 421 421

m mm 540 540 540 540 540 540 540 540 540 540 540

n mm 105 105 105 105 105 105 105 105 105 105 105 105 105 105

q mm 165 165 165 165 165 165 165 165 165 165 165 165 165 165

266.5 710 266.5 710 286.5 710 266.5 710 266.5 710 286.5 710 266.5 710 266.5 710 286.5 710 810 810

7.2 kV

286.5 710 1) 263

274 476 2) 371 3) 540

12 kV

286.5 710 1) 263

274 476 2) 371 3) 540

17.5 kV

286.5 710 1) 263

274 476 2) 371 3) 540

24 kV

187 1040.5 332 222 1040.5 332

h/i = up to Ir = 1250 A h/i = up to Ir = 2000 A, 2500 A and 3150 A Note: Small deviations of the dimensions are permissible 1) At Isc = 40 kA --> 760 mm 2) At Isc = 40 kA --> 526 mm 3) At Isc = 40 kA --> 420 mm
HG11-2590a eps

Withdrawable part
d

Voltage level

Pole-center distance mm 150 160 210 150

a mm 529 529 679 529 529 679 529 529 679 679 879

b mm 424 424 424 424 424 424 424 424 424 424 424

c mm 500 500 650 500 500 650 500 500 650 650 850

d mm 470 470 620 470 470 620 470 470 620 620 820

e mm 107 107 107 107 107 107 107 107 107 107 107

f mm 42 42 42 42 42 42 42 42 42 42 42

Weight approx. 15 kg approx. 15 kg approx. 20 kg approx. 15 kg approx. 15 kg approx. 20 kg approx. 15 kg approx. 15 kg approx. 20 kg approx. 20 kg approx. 25 kg

7.2 kV

12 kV

160 210 150

17.5 kV
a

160 210 210 275

24 kV

Siemens HG 11.02 2013

69

Technical Data
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV for 3AE5

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Dimension drawings for 7.2 to 24 kV Cartridge with earthing switch


l q a a d
HG11-2837 eps

h r t u

g s

Voltage level

Pole-center distance a mm 150 150 210 210 150 150 210 210

Width across flats b mm 275 310 275 310 275 310 275 310

c mm 594 594 794 794 594 594 794 794

d mm 147 147 187 187 147 147 187 187

e mm 850 905 850 905 850 905 850 905

f mm

g mm

h mm 263 263 263 263 263 263 263 263

i mm 224 224 224 224 224 224 224 224

k mm 476 476 476 476 476 476 476 476

l mm 371 371 371 371 371 371 371 371

m mm 540 540 540 540 540 540 540 540

n mm 105 105 105 105 105 105 105 105

266.5 710 286.5 710 266.5 710 286.5 710 266.5 710 286.5 710 266.5 710 286.5 710

7.2 kV

12 kV

Voltage level

o mm 359 363 359 359 359 363 359 359

p mm 287 287 287 287 287 287 287 287

q mm 169 169 169 169 169 169 169 169

r mm 803 803 803 803 803 803 803 803

s mm 64 64 65 65 64 64 65 65

t mm

u mm

v mm 575 575 575 575 -

w mm 25 25 25 25 -

Note: Small deviations of the dimensions are permissible

1142 1233 1142 1233 1143 1234 1142 1234 1142 1233 1142 1233 1143 1234 1143 1234

7.2 kV

12 kV

70

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV for 3AE1

Dimension drawings for 7.2 to 24 kV Cartridge with earthing switch

Voltage level

Pole-center distance a mm 150 150 210 210 150 150 210 210 150 150 210 210 210 275

Width across flats b mm 275 310 275 310 275 310 275 310 275 310 275 310 310 310

c mm 594 594 794 794 594 594 794 794 594 594 794 794 794 994

d mm 147 147 187 187 147 147 187 187 147 147 187 187

e mm 850 905 850 905 850 905 850 905 850 905 850 905

f mm

g mm

h mm 263 263 263 263 263 263 263 263 263 323 323

h mm 323 323 323 323 323

i mm 224 224 224 224 224 224 224 224 224 224 224 224 274 274

i mm 323 323

k mm 476 476 476 476 476 476 476 476 476 537 537

l mm 371 371 371 371 371 371 371 371 371 421 421

m mm 540 540 540 540 540 540 540 540 540 540 540

n mm 105 105 105 105 105 105 105 105 105 105 105 105 105 105

266.5 710 286.5 710 266.5 710 266.5 710 286.5 710 266.5 710 266.5 710 286.5 710 266.5 710 810 810

7.2 kV

286.5 710 1) 263

274 476 2) 371 3) 540

12 kV

286.5 710 1) 263

274 476 2) 371 3) 540

17.5 kV

286.5 710 1) 263

274 476 2) 371 3) 540

24 kV

187 1040.5 332 222 1040.5 332

Voltage level

o mm 359 359 359 359 359 359 359 359 359 359 359 359 359 359

p mm 287 287 287 287 287 287 287 287 287 287 287 287 287 287

q mm 165 165 165 165 165 165 165 165 165 165 165 165 165 165

r mm 803 803 803 803 803 803 803 803 803 803 803 803 902 902

s mm 64 64 65 65 64 64 65 65 64 64 65 65 64 65

t mm

u mm

v mm 575 575 575 575 575 575 575

w mm 25 25 25 25 25 25 10

h / i = up to Ir = 1250 A h / i = up to Ir = 2000 A, 2500 A and 3150 A Note: Small deviations of the dimensions are permissible 1) At Isc = 40 kA --> 760 mm 2) At Isc = 40 kA --> 526 mm 3) At Isc = 40 kA --> 420 mm

1142 1233 1142 1233 1143 1234 1142 1234 1142 1233 1142 1233 1143 1234 1143 1234 1142 1233 1142 1233 1143 1234 1143 1234 1243 1433 1243 1433

7.2 kV

12 kV

17.5 kV

24 kV

Siemens HG 11.02 2013

71

Technical Data

SION Vacuum Circuit-Breakers 3AE5 and 3AE1 Operating times and internal times, short-circuit protection of motors, consumption data of releases

Operating times and internal times for 3AE5


Operating times at rated voltage of the secondary circuit Closing time Opening time Arcing time Break time Dead time CLOSE / OPEN contact time Minimum command duration Equipment of circuit-breaker 1st shunt release 2nd release 1st shunt release 2nd release 1st shunt release 2nd release Closing solenoid 1st shunt release 2nd release Pulse time for circuit-breaker tripping signal Charging time for electrical operation Synchronism error between the poles 1st shunt release 2nd release Operating time of the circuit-breaker < 60 ms < 60 ms < 45 ms < 15 ms < 75 ms < 60 ms 300 ms < 75 ms < 60 ms 45 ms 40 ms 20 ms > 10 ms > 6 ms < 10 s 2 ms

Short-circuit protection of motors (fuse protection of drive motors) for 3AE5


Rated voltage of the motor Operating voltage Power consumption of the motor Smallest possible rated current 1) of the m.c.b. (miniature circuit-breaker) with C-characteristic

V 24 DC 48 DC 60 DC 110 DC 220 DC 110 AC 230 AC

max. V 26 53 66 121 242 121 244

min. V 20 41 51 93 187 93 187

W 150 W 170 W 170 W 120 W 115 W 200 V A 200 V A

A 6 4 4 2 1.6 2 1.6

1) The current inrush in the drive motor can be neglected due to its very short presence.

Consumption data of releases for 3AE5


Release Power consumption Operation at Closing solenoid 3AY14 10 1st shunt release (without energy store) 3AY14 10 2nd shunt release (with energy store) 3AX11 01 Undervoltage release 3AX11 03 Current-transformer operated release 3AX11 02 (rated normal current 0.5 A or 1 A) Current-transformer operated release 3AX11 04 (tripping pulse 0.1 Ws) DC approx. W 300 300 70 20 AC 50 / 60 Hz approx. VA 300 300 50 20 10 2) Tripping ranges Tripping voltage at DC 85 to 110 % U 70 to 110 % U 70 to 110 % U 35 to 0 % U Tripping voltage or tripping current at AC 50 / 60 Hz 85 to 110 % U 85 to 110 % U 85 to 110 % U 35 to 0 % U 90 to 110 % Ia

2) Consumption at pickup current (90 % of the rated normal current) and open armature.

72

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1 Technical Data Operating times and internal times, short-circuit protection of motors, consumption data of releases

Operating times and internal times for 3AE1


Operating times at rated voltage of the secondary circuit Closing time Opening time Arcing time Break time Dead time CLOSE / OPEN contact time Minimum command duration Equipment of circuit-breaker 1st shunt release 2nd release 1st shunt release 2nd release 1st shunt release 2nd release Closing solenoid 1st shunt release 2nd release Pulse time for circuit-breaker tripping signal Charging time for electrical operation Synchronism error between the poles 1st shunt release 2nd release Operating time of the circuit-breaker < 60 ms < 60 ms < 45 ms < 15 ms < 75 ms < 60 ms 300 ms < 75 ms < 60 ms 45 ms 40 ms 20 ms > 10 ms > 6 ms < 10 s 2 ms

Short-circuit protection of motors (fuse protection of drive motors) for 3AE1


Rated voltage of the motor Operating voltage Power consumption of the motor Smallest possible rated current 1) of the m.c.b. (miniature circuit-breaker) with C-characteristic

V 24 DC 48 DC 60 DC 110 DC 220 DC 110 AC 230 AC

max. V 26 53 66 121 242 121 244

min. V 20 41 51 93 187 93 187

W 400 400 400 400 400 400 400

A 8 6 4 2 1.6 2 1.6

1) The current inrush in the drive motor can be neglected due to its very short presence.

Consumption data of releases for 3AE1


Release Power consumption Operation at Closing solenoid 3AY15 10 1st shunt release (without energy store) 3AY15 10 2nd shunt release (with energy store) 3AX11 01 Undervoltage release 3AX11 03 Current-transformer operated release 3AX11 02 (rated normal current 0.5 A or 1 A) Current-transformer operated release 3AX11 04 (tripping pulse 0.1 Ws) DC approx. W 140 140 70 20 AC 50 / 60 Hz approx. VA 140 140 50 20 10 2) Tripping ranges Tripping voltage at DC 85 to 110 % U 70 to 110 % U 70 to 110 % U 35 to 0 % U Tripping voltage or tripping current at AC 50 / 60 Hz 85 to 110 % U 85 to 110 % U 85 to 110 % U 35 to 0 % U 90 to 110 % Ia

2) Consumption at pickup current (90 % of the rated normal current) and open armature.

Siemens HG 11.02 2013

73

Technical Data
Circuit diagrams for 3AE1

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Standard scheme for plug connector


1. Arbeitsstromauslser 1st shunt release 1st shunt release 2. Arbeitsstromauslser 2nd shunt release 2nd shunt release Energiearmer Low energy Wandlerstromauslser c.t.-operated release Low energy C.T. operated release

1. Wandlerstrom1st c.t.-operated auslser release 1st C.T. operated release

1. Wandlerstrom1st c.t.-operated auslser 5A release 5A 1st C.T. operated release 5A

-Q0 -X0

C2

C3

-Q0 -X0

A3

D3

-Q0 -X0

A4

-Q0 -X0

A4

-Q0 -X0

A4

-Q0 -X0

C5

3)

D5

-Q0 -X0

-Q0 -S1 23
24

-Q0 -S1 33
34 1 L 2 N

-Q0 -S1 43
44

-V4.1
4 3 + 1) 2) 1) 2) U 1) 2) U 1) 2) U 1) 2) U 1) 2) U

-Q0 -Y1

A1 A2

-Q0 -Y2

A1 A2

-Q0 -Y4

A1 A2

-Q0 -Y4.1

A1 A2

-Q0 -Y6

A1 A2

-Q0 -Y7

D1 D2 U

-Q0 -F1

-Q0 -R1

1 2

-Q0 -X0 D2

-Q0 -X0 B3 S_A7E_449_38021_001

-Q0 -X0 B4 S_A7E_449_38024_001

-Q0 -X0 B4 S_A7E_449_38024_004 Order Zusatzcode A49 A49 Order codes A49

-Q0 -X0 B4 S_A7E_449_38023_001

-Q0 -X0 B5 S_A7E_449_38026_001

-Q0 -X0 B1

S_A7E_449_38020_001

S_A7E_449_38030_001 Order code Zusatz A49 A49 Order codes A49

Position switch for withdrawable part


-Q0 -X01
1 3 5 7

-Q0 -X02
1 3 5 7

Withdrawable part

Q1

-S1.0 13 -S1.1 13 -S1.2 13 -S1.3 13 -S1.4 13


14 14 14 14 14

-S1.5 13 -S1.6 13 -S1.7 13 -S1.8 13 -S1.9 13


14 14 14 14 14
HG11-2847 eps

-Q0 -X01 2

-Q0 -X02 2 S_A7E_449_38085_001

-Q0 -X0
A14 A15 A16 B14 B15 B16 C1 C4

-Q0 -X0
C15 C16 D1 D13 D14 D15 C13 C14

-Q0 -X01

-Q0 -X02

S_A7E_449_38085_002

Legend see page 76

74

Siemens HG 11.02 2013

HG11-2848 eps

HG11-2843 eps

Elektrische Electrical closing Einschaltsperre lock-out Electrical Closing lock-out DC


A5 E1 E2

UnterspannungsUndervoltage auslser release Undervoltage

release

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Circuit diagrams for 3AE1

Contact assignment for auxiliary switch


Aus / Off Open Open Aus / Off Open Aus / Off Closed Ein / On Open Aus / Off Closed Ein / On Open Aus / Off Open Aus / Off Closed Ein / On Closed Ein / On Closed Ein / On Closed Ein / On
C12

Aus / Off Open

Aus / Off Open

Aus / Off Open

Aus / Off Open

Aus / Off Open

Open Aus / Off

Ein / On Closed

Ein / On Closed

Ein / On Closed

Ein / On Closed

Closed Ein / On

Closed Ein / On

-Q0 -X0
C7 A8 C8 C8 A10 C10 A11 C11 A12 A13

11

13 14

21 22

23 24

31 32

33 34

41 42

43 44

51 52

53 54

61 62

63 64
HG11-2849 eps

-Q8 -S1

12

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

(-Y9)

(-Y1)

(-Y2)

(-Y7)
81 82 83 91 93 101 103 111 113 121 123 84 92 94 102 104 112 114 122 124 2) 2) 2) 2) 2)

S_A7E_449_38066_001

11 13 21 23 31 33 41 43 51 53 61 63 71 73

-Q0 -S1

12 14 22 24 32 34 42 44 52 54 62 64 72 74 1) 2) 2) 3) 3) 3)

Closed Ein / On

Hilfsschalter 6S/6 Auxiliary switch 6NO/6NC

-Q0 -X0

D7

B8

D8 D9 B9 C9 B10 D10 B11 D11

B12

D12

B13

Additional equipment
Einschaltung und Pumpverhinderung mit mechanischer Closing and und Verriegelung anti-pumping with mit Einschaltsperre mechanical interlocking Closing and anti and closing lock-out pumping with mechanical interlocking and el. closing lock-out

S_A7E_449_38063_001 Auxiliary switch 12NO/12NC Hilfsschalter 12S/12 Auxiliary switch 12NO/12NC

HG11-2846 eps

Motoraufzug Motor charging Motor charging

-Q0 -X0
A1

-Q0 -X0
A2

2)

-Q0 -S1 11
12

-Q0 -S3 21
22 13 14

-Q0 -S21

21 22

-Q0 -K1 21
22

-Q0 -K1 31
A1 1) U 32 1) 2)

-Q0 -M1

M 1=
D2

-Q0 -Y9 -Q0 -S5

A1 A2 13 14

U -Q0 -K1

-Q0 -S22

22 21 2)
HG11-2841 eps

-Q0 -S12 13
HG11-2842 eps

14

-Q0 -X0 D16

-Q0 -X0

B2

S_A7E_449_38001_001

S_A7E_449_38011_504

Legend see page 76

Siemens HG 11.02 2013

75

Technical Data
Circuit diagrams for 3AE1

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Additional equipment: Releases


Meldung: Feder gespannt Signal: Spring charged Signal: Spring charged Schalterfallmeldung Circuit breaker breaker Circuit tipping signal tipping signal

-Q0 -X0

A6

C6

-Q0 -X0

A7

-Q0 -X0

-Q0 -S4 13
14

21 22

-Q0 -S6

21 22

-Q0 -R01 1
2

Heizung Heating Heating


A7

HG11-2844 eps

-Q0 -X0 B6

D6

-Q0 -X0 B7

-Q0 -X0 B7

S_A7E_449_33042_001

S_A7E_449_38043_001 S_A7E_449_38050_001 Order code Zusatz A30 A30 Order codes A30

Legend (for pages 74 to 76) K1 M1 Q0 Q1 R1 S1 S3 Contactor (anti-pumping) Motor operating mechanism Circuit-breaker wiring Wiring of withdrawable part Resistance Auxiliary switch Position switch (anti-pumping) S4 Position switch (for closing spring charged) S5 Electrical closing lock-out S6 Circuit-breaker tripping signal S12 Mechanical interlocking S21 Position switches S22 (to de-energise the motor oper- ating mechanism after charging) X0 X1 Y1 Y2 Y4 Plug connector, 24-pole or 64-pole Terminal strip, 27-pole 1st shunt release 2nd shunt release Current-transformer operated release (rated normal current 0.5 A or 1 A) Y6 Y7 Y9 Current-transformer operated release (tripping pulse W 0.1 Ws) Undervoltage release Closing solenoid

HG11-2845 eps

Abbreviations: NC = Normally closed NO = Normally open

The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring.

76

Siemens HG 11.02 2013

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Circuit diagrams for 3AE5

Standard scheme for plug connector


1. Arbeitsstromauslser 1st shunt release 1st shunt release 2. Arbeitsstromauslser 2nd shunt release 2nd shunt release

1. Wandlerstromauslser 1st c.t.-operated release 1st C.T. operated release

1. Wandlerstromauslser 5A 1st c.t.-operated release 1st C.T.5A operated release 5A

-Q0 -X1.1
4

-Q0 -X0
C3

-Q0 -X1.5.1
4

-Q0 -X1.5.2
3

-Q0 -X1.1
5

-Q0 -X0
D3

-Q0 -X1.1
5

-Q0 -X1.1
5

-Q0 -X1.1
7

Unterspannungsauslser Undervoltage release Undervoltage release -X1.1


5

-Q0 -S1 33
34

-Q0 -S1 43
44 1)

-Q0 -Y7

A1 A2 U

-Q0 -S3 23
24

1)

1) U

-Q0 -Y1

A1 A2

-Q0 -Y2

A1 A2 U

-Q0 -Y4

A1 A2

-Q0 -Y6

A1 A2

-Q0 -X1.5.2 4

-Q0 -X1.5.1 3

-Q0 -X1.1 3

-Q0 -X1.1 6

-Q0 -X1.1 6

-Q0 -X1.1 6

-Q0 -X1.1 6

S_A7E_449_41020_001 S_A7E_449_41020_010 S_A7E_449_41020_002 Teil des Grundleitungssatzes Part of basic wiring Part of basis wiring S_A7E_449_41099_010 S_A7E_449_41099_010

S_A7E_449_41021_001

S_A7E_449_41024_001

S_A7E_449_41023_001

S_A7E_449_41026_001

HG11-2855 eps

3
Position switch for withdrawable part
-Q0 -X01
1 3 5 7

-Q0 -X02
1 3 5 7

Withdrawable part

Q1

14

14

14

14

14

14

14

14

14

14

-Q0 -X01 2

-Q0 -X02 2

S_A7E_449_41085_001

-Q0 -X0
A14 A15 A16 B14 B15 B16 C1 C4

-Q0 -X0
C15 C16 D1 D13 D14 D15 C13 C14

HG11-2858 eps

-S1.0 13 -S1.1 13 -S1.2 13 -S1.3 13 -S1.4 13

-S1.5 13 -S1.6 13 -S1.7 13 -S1.8 13 -S1.9 13

-Q0 -X01

-Q0 -X02

S_A7E_449_41085_002

Legend see page 79

HG11-2859 eps

Siemens HG 11.02 2013

77

Technical Data
Circuit diagrams for 3AE5

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Contact assignment for auxiliary switch


Hilfsschalter 6S/6 Auxiliary switch switch 6NO/6NC 6NO/6NC Auxiliary Aus / Off Open Aus / Off Open Aus / Off Open Aus / Off Open Aus / Off Open Open Aus / Off Ein / On Closed Ein / On Closed Ein / On Closed Ein / On Closed Ein / On Closed Closed Ein / On -Q0 -X0
C7 A8 C8 C8 A10 C10 A11 C11 A12 C12 A13

(-Y9)
11 13 14 21 22 23 24 31 32 33 34 41 42 43 44 51 52 53 54 61 62 63
HG11-2860 eps

(-Y1)

(-Y2)

(-Y7)
81 82 83 91 93 101 103 111 113 121 123 84 92 94 102 104 112 114 122 124 2) 2) 2) 2) 2)

-Q8 -S1

11 13 21 23 31 33 41 43 51 53 61 63 71 73

12

64

-Q0 -S1

12 14 22 24 32 34 42 44 52 54 62 64 72 74 1) 2) 2) 1) 3) 4)

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

-Q0 -X0

D7

B8

D8 D9 B9 C9 B10 D10 B11 D11

B12

D12

B13

S_A7E_449_41063_001

Additional equipment
Closing and Closing and anti anti-pumping device Closing and Closing and anti anti-pumping device Closing and Closing and anti anti-pumping device Closing and Closing and anti anti-pumping device
Pumpverhinderung Closing and anti-pumping device Closing and anti Pumpverhinderung Closing and anti-pumping device Closing and anti Pumpverhinderung Closing and anti-pumping device Closing and anti

Einschaltung und Pumpverhinderung

Einschaltung und Pumpverhinderung

Einschaltung und Pumpverhinderung

Einschaltung und Pumpverhinderung

Einschaltung und

Einschaltung und

Einschaltung und

pumping device

pumping device

pumping device

pumping device

pumping device

pumping device

pumping device

24 V - 32 V 100 V - 127 V -Q0 -X1.2


7

48 V - 60 V 220 V - 240 V -Q0 -X1.2


4

24 V - 32 V 100 V - 127 V -Q0 -X1.2


3

48 V - 60 V 220 V - 240 V -Q0 -X1.2


4

-Q0 -X1.5.2
8

-Q0 -X1.2
3

-Q0 -X1.2
8

-Q0 -X1.5.1
1

1)

-Q0 -Y9

A1 A2 U

Motor charging
M 1=

HG11-2857 eps

S_A7E_449_41066_401

Motor charging
A1 1) U D2
HG11-2851 eps

-Q0 -M1 -Q0 -S3 21


22

-Q0 -S3 11 -Q0 -S3 13


14 12

-Q0 -S12 14
13

-Q0 -X1.2 6

-Q0 -X1.2 5

-Q0 -X1.5.2 7

-Q0 -X1.5.2 7

-Q0 -X1.5.2 9

-Q0 -X1.5.2 9

-Q0 -X1.5.1 7 -Q0 -X1.5.1 9

HG11-2852 eps

-Q0 -X1.5.1 2

S_A7E_449_41012_001 S_A7E_449_41012_002 S_A7E_449_41012_003 S_A7E_449_41012_004 S_A7E_449_41012_005 S_A7E_449_41012_006

S_A7E_449_41012_010 Teil des Grundleitungssatzes Part of basic wiring Part of basis wiring S_A7E_449_41099_010 S_A7E_449_41099_010

S_A7E_449_41001_010 Teil des Grundleitungssatzes Part of basic wiring Part of basis wiring S_A7E_449_41099_010 S_A7E_449_41099_010

Legend see page 79

78

Siemens HG 11.02 2013

Motoraufzug

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Technical Data
Circuit diagrams for 3AE5

Motoraufzug Motor charging Motor charging

Schalterfallmeldung Circuit Circuit breaker breaker tipping tipping signal signal

Additional equipment: Releases


Meldung: Feder gespannt Signal: Spring Signal:charged Spring charged

Heizung -Q0 -X1.5.1 -Q0 -X1.2


5

-Q0 -X1.1
1

-Q0 -X1.5.2
2

-Q0 -X1.1

-Q0 -X1.2
1 0 8

-Q0 -X1.2
1

-Q0 -X1.2
2

-Q0 -S21

21 22

-Q0 -S4 13
14

21 22

-Q0 -S6

21 22

-R01 1
2

HG11-2850 eps

-Q0 -X1.5.2 1

-Q0 -X1.1 2

-Q0 -X1.1 9 -Q0 -X1.1 10

-Q0 -X1.5.2 5

-Q0 -X1.5.2 6

-Q0 -X1.5.1 6

-Q0 -X1.2 9

S_A7E_449_41001_001 Einschaltung und Pumpverhinderung Closing and antipumping device Closing and anti pumping device

S_A7E_449_41042_001

S_A7E_449_41043_001 Einschaltung und Pumpverhinderung Closing and antipumping device Closing and anti pumping device

S_A7E_449_41043_010 Teil des Grundleitungssatzes Part of basic wiring Part of basis wiring S_A7E_449_41099_010 S_A7E_449_41099_010

S_A7E_449_41050_001 Zusatzcode A30 Order Order codes A30

HG11-2856 eps

Heating
8

-Q0 -K1 -Q0 -X1.1 1


2 3 4 5 6 7 8 9 10

-Q0 -X1.1 1
2 3 4 5 6 7 8 9 10

-Q0 -X0

A1 D16 D2 C2

(-M1) (-M1) (-Y1) (-Y1)

-Q0 -K1 -Q0 -X1.1 1


2 3 4 5 6 7 8 9 10

-X1.3

C6 B6 D6

(-S4) (-S4) (-S4) (-S6) (-S6) (-Y9) (-Y9)

1 2 3 4 5 6 7 8 9 10

-Q0 -X0

A1 D16 D2 C2

(-M1) (-M1) (-Y1) (-Y1)

C6 B6 D6 A7 B7 B2 A2

(-S4) (-S4) (-S4) (-S6) (-S6) (-Y9) (-Y9)

-Q0 -X1.2 1

-Q0 -X1.4 1

2 3 (100 - 127 V) 4 (220 - 240 V) 5 6 7 8 9 10


HG11-2853 eps

A7 2 B7 3 (100 - 127 V) 4 (220 - 240 V)B2 5 A2 6 7 8 (-R01) 9 (-R01 ) 10

-Q0 -X1.2 1
2 3 (24 - 32 V) 4 (48 - 60 V) 5 6 7 8 9 10

-Q0 -X1.4 1
2 3 (24 - 32 V) 4 (48 - 60 V) 5 6 7 8 9 10
HG11-2854 eps

(-R01) (-R01 )

S_A7E_449_41012_051

S_A7E_449_41012_053

Legend (for pages 77 to 79) K1 M1 Q0 Q1 R1 S1 S3 Contactor (anti-pumping) Motor operating mechanism Circuit-breaker wiring Wiring of withdrawable part Resistance Auxiliary switch Position switch (anti-pumping) S4 Position switch (for closing spring charged) S5 Electrical closing lock-out S6 Circuit-breaker tripping signal S12 Mechanical interlocking S21 Position switches S22 (to de-energise the motor oper- ating mechanism after charging) X0 X1 Y1 Y2 Y4 Plug connector, 24-pole or 64-pole Terminal strip, 27-pole 1st shunt release 2nd shunt release Current-transformer operated release (rated normal current 0.5 A or 1 A) Y6 Y7 Y9 Current-transformer operated release (tripping pulse W 0.1 Ws) Undervoltage release Closing solenoid

Abbreviations: NC = Normally closed NO = Normally open

The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring.

Siemens HG 11.02 2013

79

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

80

Siemens HG 11.02 2013

R-HG11-181.tif

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Annex
Contents

Contents

Page

Annex 81
Inquiry form Configuration instructions Configuration aid 82 83 Foldout page

Switchgear Factory in Berlin, Germany

R-HG11-180.eps

Siemens HG 11.02 2013

81

Annex
Inquiry form
Please copy, fill in and return to your Siemens partner or you can use our prompted online configurator under www.siemens.com/SION

SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Inquiry concerning

Technical data
Rated voltage Rated lightning impulse withstand voltage

SION vacuum circuit-breaker from 7.2 to 24 kV

7.2 kV 24 kV 60 kV 125 kV

12 kV 75 kV 28 kV 50 kV 16 kA 31.5 kA 1250 A 3150 A 160 mm 275 mm

17.5 kV 95 kV 38 kV 55 kV 20 kA 40 kA 2000 A 210 mm 310 mm

Other values _ _ _ kV _ _ _ kV _ _ _ kV _ _ _ kA ___ A 275 mm

Please

Rated short-duration 20 kV power-frequency withstand voltage 42 kV Rated short-circuit breaking current Rated normal current Pole-center distance Width across flats 12.5 kA 25 kA 800 A 2500 A 150 mm 205 mm

Submit an offer Call us Visit us

Your address
Company Dept. Name Street Postal code / city Country

Secondary equipment
For possible combinations see pages 31 to 36
Circuit-breaker equipment Motor operating mechanism Closing solenoid
st 1 shunt nd

Fixed mounting _ _ _ V DC _ _ _ V DC _ _ _ V DC _ _ _ V DC

Withdrawable part, contact arms Withdrawable part, contact arms, bushings Withdrawable module with earthing switch Withdrawable module without earthing switch Retrofit _ _ _ V AC, _ _ _ H z _ _ _ V AC, _ _ _ H z _ _ _ V AC, _ _ _ H z _ _ _ V AC, _ _ _ H z

release

2 shunt release

Current-transformer operated release Phone Fax E-mail Undervoltage release Auxiliary switch Low-voltage connection Mechanical interlocking Circuit-breaker tripping signal _ _ _ V DC 6 NO + 6 NC

_ _ _ V AC, _ _ _ H z 12 NO + 12 NC 24-pole plug French 64-pole plug Spanish

20- or 27-pole terminal strip German English

Siemens AG
Dept. Name Street

Electrical closing lock-out Operating instructions

Application and other requirements


Postal code / city Country Fax Please check off

_ _ _ Please fill in

82

Siemens HG 11.02 2013

You prefer to configure your SION vacuum circuit-breaker on your own?


Please follow the steps for configuration and enter the order number in the configuration aid. Alternatively you can also use our prompted online configurator under www.siemens.com/SION.

Instruction for configuration of the SION vacuum circuit-breaker


1st step: Definition of the circuit-breaker and equipment package (see pages 18 to 30)
Please specify the following ratings: Rated voltage (Ur) Rated lightning impulse withstand voltage (Up) Rated short-duration power-frequency withstand voltage (Ud) Rated short-circuit breaking current (ISC) Rated normal current (Ir) Pole-center distance Width across flats These ratings define the positions 5 to 8 of the order number. Possible options: Ur: 7.2 kV to 24 kV Up: 60 kV to 125 kV Ud: 20 kV, 28 kV, 32 kV, 42 kV, 55 kV, 65 kV ISC: 16 kA to 40 kA Ir: 800 A and 3150 A 150 mm to 275 mm 205 mm to 310 mm

2nd step: Definition of the secondary equipment (see pages 31 to 36)


Please specify the following equipment features: Release combination (position 9) Closing solenoid (position 10) Operating voltage of the releases (positions 11 / 12) Installation accessories (position 13) Motor operating mechanism (position 14) Number of auxiliary contacts (position 15) Design of the secondary connection (position 15) Mechanical interlocking, circuit-breaker tripping signal (position 15) Language of the documentation (position 16) Frequency of the operating voltage of the secondary equipment at AC (position 16) These equipment features define the positions 9 to 16 of the order number. Possible options: Shunt release, current-transformer operated release and undervoltage release Operating voltages from 24 V DC to 240 V AC Operating voltages from 24 V DC to 240 V AC Fixed mounting, with withdrawable part, with contact, fixed contact, bushing, cartridge, with / without earthing switch, retrofit 8B Operating voltages from 24 V DC to 240 V AC 6 NO + 6 NC, 12 NO + 12 NC 20- or 27-pole terminal strip, 24-pole plug connector 64-pole plug connector With or without English, German, French, Spanish, Russian, further languages on request DC or AC 50 Hz; 60 Hz

3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 37) Should you still need more options than the possible special equipment like halogen-free and flame-retardant or silicone-free design, condensation protection or an additional rating plate, etc., please contact your responsible sales partner.

Siemens HG 11.02 2013

83

For configuration of your SION vacuum circuit-breaker

10 11 12

13 14 15 16

3 A

E n n n n n n n n n n n n n See pages 33+34

See page 18

See page 31

See page 31

See page 32

See page 32

See page 34

See page 35

See page 36

3 A

E + +

+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +

+ + + + + + + + + + + + + + + +

3 A

3 A

3 A

3 A

3 A

3 A

3 A

See page 37

page 30

to

Published by and copyright 2013: Siemens AG Infrastructure & Cities Sector Wittelsbacherplatz 2 80333 Munich, Germany

Siemens AG Infrastructure & Cities Sector Low and Medium Voltage Division Nonnendammallee 104 13629 Berlin, Germany www.siemens.com

All rights reserved. If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights.

Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm.

Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.

For more information, please contact our Customer Support Center. Phone: +49 180 524 84 37 Fax: +49 180 524 24 71

Order No. IC1000-K1511-A021-A3-7600 Printed in Germany KG 03.13 1.0 86 En 7400 / 46651 W Printed on elementary chlorine-free bleached paper.