Cooling/Heat Pump Convertible Air Handlers

2/4TEC3F18-60A1000A
1 5 Ton

PUB. NO. 22-1774-01-0905 (EN)

Features and Benefits


13.0 SEER Ships horizontal converts to vertical by standing unit on end. Six-way convertibility horizontal (left and right), front and rear access; upflow, downflow 1-man installation opportunity Electrical, refrigerant, condensate and blower access convertible to either side Compact 21" depth for easy installation Corrosion resistant galvanized metal with attractive finish Superior condensate performance Factory installed non-bleed TXV Enhanced internally finned coil tubes Direct drive motor Multi-speed blower Versatile duct flange allows flush fit 3/4", 1" or 1.5" duct insulation Filter panel stamped with word filter 200/230 volt primary and 24 volt secondary transformer Low voltage wire nut connections Insulated cabinet Uses 1400 series heaters External access to heater circuit breakers Polarized plugs for making electrical connections from air handler control box to heaters Approved for modular or manufactured homes

Selection Procedure
Model Number Nomenclature 1 2 2 T 3 E 4 C 5 3 6 F 7 1 8 8 9 A 10 1 11 0 12 0 13 0 14 A 15 A

SYSTEM TYPE 2 = R-22 4 = R-410 APPLICATION TE = Fully Convertible TG = Semi Convertible TF = Front Return TV = Vertical PRODUCT FAMILY E = Leadership Variable Speed P = Leadership C = Replacement/Retail B = Basic FLOW CONTROL 3 = Non-Bleed TXV 4 = FCCV FEATURE IDENTIFIER 0 = Standard Unit F = Air-Tite

UNIT PARTS IDENTIFIER MINOR DESIGN MODIFICATION FUTURE OPTION Factory Installed Heater Nominal KW Value ELECTRICAL CONNECTION 0 = Pig Tails B = Circuit Breaker D = Pull Disconnect POWER SUPPLY 1 = Single Phase MAJOR DESIGN MODIFICATION NOMINAL NET COOLING CAPACITY (MBTUH)

2005 American Standard Inc. All Rights Reserved

22-1774-01-0905 (EN)

Contents

Features and Benefits Selection Procedure


Model Number Nomenclature

2 2
2

General Data
2/4TEC3F18A1000A 2/4TEC3F24A1000A 2/4TEC3F30A1000A 2/4TEC3F36A1000A 2/4TEC3F42A1000A 2/4TEC3F48A1000A 2/4TEC3F60A1000A

4
4 4 4 4 4 5 5

Performance Data Electrical Data Field Wiring 2/4TEC3F18-60A1000A Convertibility Dimensions Mechanical Specification Options

6 11 16 18 19 20

22-1774-01-0905 (EN)

General Data

MODEL RATED VOLTS/PH/HZ. RATINGS 1 INDOOR COIL Type Rows F.P.I. Face Area (sq. ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.) 2 INDOOR FAN Type Diameter Width (in.) No. Used Drive No. Speeds CFM vs. in w.g. No. Motors H.P. Motor Speed R.P.M. Volts/Ph/Hz F.L. Amps L.R. Amps FILTER Vertical Applications Filter Furnished? Type Recommended No.-Size-Thickness Horizontal Applications Filter Furnished? Recommended Size 3 REFRIGERANT Ref. Line Connections Coupling or Conn. Size in. Gas Coupling or Conn. Size in Liq. DIMENSIONS Crated (in.) Uncrated WEIGHT Shipping (Lbs.) / Net (Lbs.) MODEL RATED VOLTS/PH/HZ. RATINGS 1 INDOOR COIL Type Rows F.P.I. Face Area (sq. ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.) 2 INDOOR FAN Type Diameter Width (in.) No. Used Drive No. Speeds CFM vs. in w.g. No. Motors H.P. Motor Speed R.P.M. Volts/Ph/Hz F.L. Amps L.R. Amps FILTER Vertical Applications Filter Furnished? Type Recommended No.-Size-Thickness Horizontal Applications Filter Furnished? Recommended Size 3 REFRIGERANT Ref. Line Connections Coupling or Conn. Size in. Gas Coupling or Conn. Size in Liq. DIMENSIONS Crated (in.) Uncrated WEIGHT Shipping (Lbs.) / Net (Lbs.)

2/4TEC3F18A1000A 208-230/1/60 See O.D. Specifications Plate Fin 3 - 14 3.21 3/8 - Copper TXV-NB 3/4 NPT Centrifugal 9x8 1 Direct - 3 See Fan Performance Table 1 - 1/4 1075 200-230/1/60 1.5 - 3.1

2/4TEC3F24A1000A 208-230/1/60 See O.D. Specifications Plate Fin 3 - 14 3.21 3/8 - Copper TXV-NB 3/4 NPT Centrifugal 9x8 1 Direct - 3 See Fan Performance Table 1 - 1/4 1075 200-230/1/60 1.7 - 3.6

2/4TEC3F30A1000A 200-230/1/60 See O.D. Specifications Plate Fin 3 - 14 3.67 3/8 - Copper TXV-NB 3/4 NPT Centrifugal 9x8 1 Direct - 3 See Fan Performance Table 1 - 1/3 1075 200-230/1/60 2.1 - 4.6

Yes Throwaway 1 - 20 x 20 x 1 in. No See Note 3 R-22 R-410A Brazed Brazed 5/8 1/2 1/4 1/4 HxWxD 44 1/2 x 24 x 23-1/2 See Outline Drawing 121/111 2/4TEC3F36A1000A 200-230/1/60 See O.D. Specifications Plate Fin 3 - 14.0 3.67 3/8 - Copper TXV-NB 3/4 NPT Centrifugal 10 x 7 1 Direct - 3 See Fan Performance Table 1 - 1/3 1080 200-230/1/60 2.2 - 5.3

Yes Throwaway 1 - 20 x 20 x 1 in. No See Note 3 R-22 R-410A Brazed Brazed 3/4 5/8 5/16 5/16 HxWxD 44 1/2 x 24 x 23-1/2 See Outline Drawing 121/111 2/4TEC3F42A1000A 200-230/1/60 See O.D. Specifications Plate Fin 3 - 14 5.04 3/8 - Copper TXV-NB 3/4 NPT Centrifugal 10 x 10 1 Direct - 3 See Fan Performance Table 1 - 1/2 1075 200-230/1/60 3.3 - 7.8

Yes Throwaway 1 - 20 x 20 x 1 in. No See Note 3 R-22 R-410A Brazed Brazed 3/4 3/4 5/16 5/16 HxWxD 46-1/2 x 24 x 23-1/2 See Outline Drawing 135/125
1 These Air Handlers are ARI certified with various Split System Air Conditioners and Heat Pumps (ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data. 2 3/4" Male Plastic Pipe (Ref.: ASTM 1785-76) 3 Minimum filter size for horizontal applications will be based on airflow selection and will be calculated as follows: Low Velocity Filter: Face area (Sq. Ft.) = CFM / 300 High Velocity Filter: Face area (Sq. Ft.) = CFM / 500

Yes Throwaway 1 - 20 x 20 x 1 in. No See Note 3 R-22 R-410A Brazed Brazed 7/8 3/4 3/8 3/8 HxWxD 46-1/2 x 24 x 23-1/2 See Outline Drawing 135/125 4

Yes Throwaway 1 - 20 x 20 x 1 in. No See Note 3 R-22 R-410A Brazed Brazed 7/8 3/4 3/8 3/8 HxWxD 53-1/4 x 26 x 23-1/2 See Outline Drawing 165/150 22-1774-01-0905 (EN) 2/4TEC3F36A1000A 2/4TEC3F42A1000A

General Data

MODEL RATED VOLTS/PH/HZ. RATINGS 1 INDOOR COIL Type Rows F.P.I. Face Area (sq. ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.) 2 INDOOR FAN Type Diameter Width (in.) No. Used Drive No. Speeds CFM vs. in w.g. No. Motors H.P. Motor Speed R.P.M. Volts/Ph/Hz F.L. Amps L.R. Amps FILTER Vertical Applications Filter Furnished? Type Recommended No.-Size-Thickness Horizontal Applications Filter Furnished? Recommended Size 3 REFRIGERANT Ref. Line Connections Coupling or Conn. Size in. Gas Coupling or Conn. Size in Liq. DIMENSIONS Crated (in.) Uncrated WEIGHT Shipping (Lbs.) / Net (Lbs.)

2/4TEC3F48A1000A 200-230/1/60 See O.D. Specifications Plate Fin 3 - 14 6.19 3/8 - Copper TXV-NB 3/4 NPT Centrifugal 11 x 10 1 Direct - 3 See Fan Performance Table 1 - 1/2 1000 200-230/1/60 2.7 - 4.5

2/4TEC3F60A1000A 200-230/1/60 See O.D. Specifications Plate Fin 3 - 14 (3-16, 4TEC) 6.19 3/8 - Copper TXV-NB 3/4 NPT Centrifugal 11 x 10 1 Direct - 4 See Fan Performance Table 1-1 1050 200-230/1/60 7.2

Yes Throwaway 1 - 20 x 20 x 1 in. No See Note 3 R-22 R-410A Brazed Brazed 1-1/8 7/8 3/8 3/8 HxWxD 53-1/2 x 26 x 23-1/2 See Outline Drawing 166/151

Yes Throwaway 1 - 20 x 22 x 1 in. No See Note 3 R-22 R-410A Brazed Brazed 1-1/8 7/8 3/8 3/8 HxWxD 59-1/2 x 26 x 23-1/2 See Outline Drawing 170/155

1 These Air Handlers are ARI certified with various Split System Air Conditioners and Heat Pumps (ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data. 2 3/4" Male Plastic Pipe (Ref.: ASTM 1785-76) 3 Minimum filter size for horizontal applications will be based on airflow selection and will be calculated as follows: Low Velocity Filter: Face area (Sq. Ft.) = CFM / 300 High Velocity Filter: Face area (Sq. Ft.) = CFM / 500

22-1774-01-0905 (EN)

Performance Data

Airflow Performance 2/4TEC3F18A: Wet Coil, No Heaters AIRFLOW (CFM) EXTERNAL STATIC PRESSURE (in.w.g.) HI 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 NOTES: 1032 993 949 901 849 788 711 608 467 VERTICAL 230 VOLTS MED 673 662 639 609 574 532 475 391 266 LO 473 443 413 382 347 303 245 167 HI 973 941 901 856 805 745 670 569 429 208 VOLTS MED 567 563 544 518 485 444 388 307 187 LO 372 371 340 299 258 219 170 93 HI 1003 962 922 876 820 752 670 575 472 230 VOLTS MED 676 661 642 616 578 528 465 388 301 LO 458 443 418 387 350 304 245 163 HI 958 919 880 834 778 711 632 546 457 HORIZONTAL 208 VOLTS MED 579 564 550 527 489 436 373 311 266 LO 396 372 341 303 259 214 173 146 -

With filter, no horizontal drip tray Small apex baffle Subtract 0.06" W.G. for downflow

As shipped except without filter Subtract 0.05" W.G. for horizontal left

Airflow Performance 2/4TEC3F24A: Wet Coil, No Heaters AIRFLOW (CFM) EXTERNAL STATIC PRESSURE (in.w.g.) HI 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 NOTES: 1134 1102 1048 984 912 833 738 614 442 197 VERTICAL 230 VOLTS MED 876 839 798 750 694 622 532 416 268 LO 818 789 751 705 649 581 496 385 240 HI 1093 1073 1020 953 880 802 714 599 434 187 208 VOLTS MED 781 751 713 668 614 548 465 358 216 LO 723 696 661 618 567 504 425 321 184 HI 1083 1051 996 930 858 782 693 579 418 184 230 VOLTS MED 870 831 783 728 667 597 512 406 266 LO 813 783 739 687 628 561 479 375 236 HI 1050 1020 967 903 833 758 669 554 391 156 HORIZONTAL 208 VOLTS MED 780 745 703 655 600 533 452 349 217 LO 739 697 657 614 563 499 417 313 182 -

With filter, no horizontal drip tray Small apex baffle Subtract 0.06" W.G. for downflow
6

As shipped except without filter Subtract 0.05" W.G. for horizontal left

22-1774-01-0905 (EN)

Performance Data

Airflow Performance 2/4TEC3F30A: Wet Coil, No Heaters AIRFLOW (CFM) EXTERNAL STATIC PRESSURE (in.w.g.) HI 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 NOTES: 1252 1169 1099 1031 956 869 769 659 542 429 VERTICAL 230 VOLTS MED 998 992 954 896 829 755 672 569 432 239 LO 813 835 822 786 735 670 590 486 342 141 HI 1188 1138 1079 1012 938 857 765 660 536 387 208 VOLTS MED 911 893 855 807 756 698 628 532 390 177 LO 728 718 700 673 635 586 522 440 338 210 HI 1225 1169 1108 1041 966 879 780 666 533 380 230 VOLTS MED 1038 1001 952 896 835 765 682 574 427 223 LO 871 855 823 783 736 680 610 515 382 193 HI 1198 1143 1086 1022 950 865 766 650 517 366 HORIZONTAL 208 VOLTS MED 917 893 861 819 767 705 629 536 421 279 LO 745 724 705 679 641 587 517 433 341 247

With filter, no horizontal drip tray Small apex baffle Subtract 0.06" W.G. for downflow

As shipped except without filter Subtract 0.05" W.G. for horizontal left

Airflow Performance 2/4TEC3F36A: Wet coil, No Heaters AIRFLOW (CFM) EXTERNAL STATIC PRESSURE (in.w.g.) HI 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 NOTES: 1484 1412 1344 1277 1209 1139 1065 988 907 823 VERTICAL 230 VOLTS MED 1282 1268 1226 1171 1110 1049 987 916 827 702 LO 1077 1082 1055 1013 965 915 862 799 713 584 HI 1402 1352 1292 1227 1163 1098 1031 957 870 760 208 VOLTS MED 1200 1166 1130 1089 1040 982 915 839 757 671 LO 963 948 924 893 856 814 764 703 624 521 HI 1402 1350 1289 1225 1163 1104 1043 977 894 783 230 VOLTS MED 1265 1228 1180 1127 1073 1019 962 897 815 707 LO 1069 1048 1015 976 933 887 835 771 689 579 HI 1349 1298 1243 1185 1127 1066 1001 929 846 745 HORIZONTAL 208 VOLTS MED 1165 1131 1090 1047 1001 953 898 829 736 609 LO 947 915 890 866 836 795 743 677 599 513

With filter, no horizontal drip tray Small apex baffle Subtract 0.06" W.G. for downflow
7

As shipped except without filter Subtract 0.05" W.G. for horizontal left

22-1774-01-0905 (EN)

Performance Data

Airflow Performance 2/4TEC3F42A: Wet Coil, No Heaters AIRFLOW (CFM) EXTERNAL STATIC PRESSURE (in.w.g.) HI 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 NOTES: 1869 1715 1609 1529 1458 1385 1303 1210 1109 1009 VERTICAL 230 VOLTS MED 1690 1542 1449 1380 1314 1240 1158 1078 1018 1010 LO 1435 1316 1237 1177 1123 1064 1000 932 870 829 HI 1723 1640 1561 1485 1409 1332 1251 1165 1071 968 208 VOLTS MED 1435 1367 1317 1274 1227 1170 1099 1015 921 825 LO 1100 1079 1060 1032 991 939 884 838 820 854 HI 1793 1721 1651 1578 1500 1417 1329 1237 1145 1057 230 VOLTS MED 1533 1522 1471 1400 1322 1245 1170 1092 1000 878 LO 1309 1277 1237 1190 1139 1085 1026 963 895 819 HI 1721 1665 1600 1527 1449 1367 1284 1200 1117 1034 HORIZONTAL 208 VOLTS MED 1400 1389 1350 1294 1231 1164 1094 1019 931 820 LO 1100 1095 1068 1030 987 940 889 826 740 617

With filter, no horizontal drip tray Small apex baffle Subtract 0.06" W.G. for downflow

As shipped except without filter Subtract 0.05" W.G. for horizontal left

Airflow Performance 2/4TEC3F48A: Wet Coil, No Heaters AIRFLOW (CFM) EXTERNAL STATIC PRESSURE (in.w.g.) HI 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 NOTES: 1945 1880 1824 1770 1712 1647 1571 1485 1391 1293 VERTICAL 230 VOLTS MED 1768 1712 1659 1606 1551 1490 1419 1337 1238 1120 LO 1617 1583 1532 1474 1415 1358 1296 1219 1113 955 HI 1810 1762 1710 1654 1595 1532 1462 1383 1291 1180 208 VOLTS MED 1618 1574 1526 1476 1421 1360 1290 1206 1101 970 LO 1478 1428 1382 1333 1278 1212 1134 1044 945 840 HI 1959 1910 1860 1810 1758 1700 1636 1561 1471 1363 230 VOLTS MED 1745 1722 1683 1636 1584 1529 1470 1402 1319 1212 LO 1582 1612 1582 1524 1457 1394 1336 1274 1190 1056 HI 1768 1750 1714 1664 1606 1542 1471 1392 1300 1190 HORIZONTAL 208 VOLTS MED 1562 1606 1577 1511 1436 1365 1300 1228 1127 959 LO 1440 1430 1390 1336 1275 1213 1146 1068 966 821

With filter, no horizontal drip tray Small apex baffle Subtract 0.06" W.G. for downflow
8

As shipped except without filter Subtract 0.05" W.G. for horizontal left

22-1774-01-0905 (EN)

Performance Data

Airflow Performance 2/4TEC3F60A: Wet Coil, No Heaters AIRFLOW (CFM) EXTERNAL STATIC PRESSURE (in.w.g.) HI 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 NOTES: 2163 2132 2088 2044 2004 1972 1941 1902 1841 1735 VERTICAL 230 VOLTS MED-H 2018 1974 1936 1901 1867 1832 1797 1760 1721 1683 M-LO 1901 1852 1811 1775 1741 1707 1672 1635 1594 1549 LOW 1831 1796 1754 1709 1663 1617 1572 1526 1475 1416 HI 2129 2091 2049 2008 1970 1935 1899 1858 1803 1722 208 VOLTS MED-H 1988 1954 1915 1874 1835 1797 1761 1725 1684 1636 M-LO 1893 1833 1790 1756 1723 1687 1646 1602 1556 1516 LOW 1820 1769 1722 1678 1634 1590 1542 1489 1427 1354 HI 2107 2063 2028 1995 1962 1925 1883 1834 1779 1719 230 VOLTS MED-H M-LO 1963 1927 1889 1851 1814 1778 1743 1710 1678 1648 1840 1810 1773 1735 1698 1662 1628 1595 1559 1518 LOW 1774 1743 1706 1663 1617 1569 1520 1473 1429 1389 HI 2085 2049 2011 1973 1934 1896 1855 1812 1761 1699 HORIZONTAL 208 VOLTS MED-H M-LO 1956 1912 1870 1830 1793 1757 1721 1685 1648 1606 1837 1797 1756 1716 1678 1641 1606 1570 1531 1484 LOW 1777 1729 1683 1638 1593 1548 1501 1450 1392 1326

With filter, no horizontal drip tray Small apex baffle Subtract 0.06" W.G. for downflow

As shipped except without filter Subtract 0.05" W.G. for horizontal left

PRESSURE DROP FOR ELECTRIC HEATERS IN AIR HANDLER MODELS


NUMBER OF RACKS
1 2 3 4 5

HEATER RACKS
HEATER MODEL NO. BAYHTR1405 NO. OF RACKS 1 2 2 2 3 3 4 5
NOTES: 1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters 2. Heater model numbers may have additional suffix digits.

AIRFLOW CFM
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 0.01 0.01 0.02 0.03 0.04 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.13 0.14

AIR PRESSURE DROP INCHES W.G.


0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11 0.13 0.15 0.17 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.12 0.14 0.16 0.18 0.20 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.19 0.21 0.23 0.08 0.09 0.11 0.13 0.15 0.17 0.19 0.21 0.23 0.26

BAYHTR1408 BAYHTR1410 BAYHTR3410 BAYHTR1415 BAYHTR3415 BAYHTR1419 BAYHTR1425

22-1774-01-0905 (EN)

Performance Data
Air Handler/Fan Speed Heater Matrix
HEATER MODEL NUMBER BAYHTR
Air Handler Model Unit Position
Vertical Upflow Vertical Downflow Horizontal Left Horizontal Right Vertical Upflow Vertical Downflow Horizontal Left Horizontal Right Vertical Upflow Vertical Downflow Horizontal Left Horizontal Right Vertical Upflow Vertical Downflow Horizontal Left Horizontal Right Vertical Upflow Vertical Downflow Horizontal Left Horizontal Right Vertical Upflow Vertical Downflow Horizontal Left Horizontal Right Vertical Upflow Vertical Downflow Horizontal Left Horizontal Right

1405 Application
A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump A/C or Elec. Furnace Heat Pump
4.80KW

1408
7.68KW

*410
9.60KW

*415
L M L M L M L M L M L M L M L M L H L H L H L H L M L H L H L H L L L H L L L L L L L ML L ML L ML

1419
L H L H L H L H L H L H L H L H L M N/A N/A L L L L L ML L MH L ML L L

1425

* = 1 or 3

15.36KW 19.20KW 24.96KW

2/4TEC3F18A

L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L

L M L M L M L M L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L

L M L M L M L M L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L

2/4TEC3F24A

2/4TEC3F30A

2/4TEC3F36A

2/4TEC3F42A

2/4TEC3F48A

2/4TEC3F60A

10

22-1774-01-0905 (EN)

Electrical Data

2/4TEC3F18A WIRING DATA (Indoor Blower Motor Powered from Heater Circuit 1) Heater Model No. BAYHTR1405+++ BAYHTR1408 BAYHTR1408+++ BAYHTR1410 +++ BAYHTR3410 000 Number of Circuits/ Phase 1/1 1/1 1/1 1/3 240 VOLT Capacity KW BTUH 4.80 7.68 9.60 9.60 16400 26200 32800 32800 Heater Amps per Circuit 20 32 40 34.6 Minimum Circuit Ampacity 27 42 52 43 Maximum Overload Protection 30 45 60 45 Capacity KW BTUH 3.60 5.76 7.20 7.20 12300 19700 24600 24600 208 VOLT Heater Amps per Circuit 17.3 27.7 34.6 30 Minimum Circuit Ampacity 24 37 45 37 Maximum Overload Protection 25 40 45 40

NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, PDC 000 = pigtails, PDC= contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

2/4TEC3F24A WIRING DATA (Indoor Blower Motor Powered from Heater Circuit 1) Heater Model No. BAYHTR1405+++ BAYHTR1408 BAYHTR1408+++ BAYHTR1410 +++ BAYHTR3410 000 BAYHTR1415 BRK BAYHTR3415 000 Number of Circuits/ Phase 1/1 1/1 1/1 1/3 2/1 1/3 240 VOLT Capacity KW BTUH 4.80 7.68 9.60 9.60 15.36 15.36 16400 26200 32800 32800 52400 52400 Heater Amps per Circuit 20 32 40 34.6 40/24 38.2 Minimum Circuit Ampacity 27 42 52 43 52*/30 49 Maximum Overload Protection 30 45 60 45 60*/30 50 Capacity KW BTUH 3.60 5.76 7.20 7.20 11.53 11.53 12300 19700 24600 24600 39300 39300 208 VOLT Heater Amps per Circuit 17.3 27.7 34.6 30 34.6/20.8 33.1 Minimum Circuit Ampacity 24 37 45 37 45*/26 43 Maximum Overload Protection 25 40 45 40 45*/30 45

NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, PDC 000 = pigtails, PDC= contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

2/4TEC3F30A WIRING DATA (Indoor Blower Motor Powered from Heater Circuit 1) Heater Model No. BAYHTR1405+++ BAYHTR1408 BAYHTR1408+++ BAYHTR1410 +++ BAYHTR3410 000 BAYHTR1415 BRK BAYHTR3415 000 Number of Circuits/ Phase 1/1 1/1 1/1 1/3 2/1 1/3 240 VOLT Capacity KW BTUH 4.80 7.68 9.60 9.60 15.36 15.36 16400 26200 32800 32800 52400 52400 Heater Amps per Circuit 20 32 40 34.6 40/24 38.2 Minimum Circuit Ampacity 27 42 52 43 52*/30 49 Maximum Overload Protection 30 45 60 45 60*/30 50 Capacity KW BTUH 3.60 5.76 7.20 7.20 11.53 11.53 12300 19700 24600 24600 39300 39300 208 VOLT Heater Amps per Circuit 17.3 27.7 34.6 30 34.6/20.8 33.1 Minimum Circuit Ampacity 24 37 45 37 45*/26 43 Maximum Overload Protection 25 40 45 40 45*/30 45

NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, PDC 000 = pigtails, PDC= contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

22-1774-01-0905 (EN)

11

Electrical Data

2/4TEC3F36A WIRING DATA (Indoor Blower Motor Powered from Heater Circuit 1) Heater Model No. BAYHTR1405+++ BAYHTR1408 BAYHTR1408+++ BAYHTR1410 +++ BAYHTR3410 000 BAYHTR1415 BRK BAYHTR3415 000 BAYHTR1419 BRK Number of Circuits/ Phase 1/1 1/1 1/1 2/1 1/3 2/1 240 VOLT Capacity KW BTUH 4.80 7.68 9.60 15.36 15.36 19.20 16400 26200 32800 52400 52400 65500 Heater Amps per Circuit 20 32 40 40/24 38.2 32/48 Minimum Circuit Ampacity 27 42 52 52*/30 49 43*/60 Maximum Overload Protection 30 45 60 60*/30 50 45*/60 Capacity KW BTUH 3.60 5.76 7.20 11.53 11.53 14.42 12300 19700 24600 39300 39300 49200 208 VOLT Heater Amps per Circuit 17.3 27.7 34.6 34.6/20.8 33.1 27.7/41.6 Minimum Circuit Ampacity 24 37 45 45*/26 43 37*/52 Maximum Overload Protection 25 40 45 45*/30 45 40*/60

NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, PDC 000 = pigtails, PDC= contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

2/4TEC3F42P WIRING DATA (Indoor Blower Motor Powered from Heater Circuit 1) Heater Model No. BAYHTR1405 +++ BAYHTR1408 +++ BAYHTR141 +++BAYHTR3410 000 BAYHTR1415 BRK BAYHTR3415 000 BAYHTR1419 BRK Number of Circuits/ Phase 1/1 1/1 1/1 1/3 2/1 1/3 2/1 240 VOLT Capacity KW BTUH 4.80 7.68 9.60 9.60 15.36 15.36 19.20 16400 26200 32800 32800 52400 52400 65500 Heater Amps per Circuit 20 32 40 34.6 40/24 38.2 32/48 Minimum Circuit Ampacity 29 44 54 43 54*/30 51 44*/60 Maximum Overload Protection 30 45 60 45 60*/30 60 45*/60 Capacity KW BTUH 3.60 5.76 7.20 7.20 11.53 11.53 14.42 12300 19700 24600 24600 39300 39300 49200 208 VOLT Heater Amps per Circuit 17.3 27.7 34.6 30 34.6/20.8 33.1 27.7/41.6 Minimum Circuit Ampacity 26 39 47 37 47*/26 45 39*/52 Maximum Overload Protection 30 40 50 40 50*/30 45 40*/60

NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

12

22-1774-01-0905 (EN)

Electrical Data

2/4TEC3F48A WIRING DATA (Indoor Blower Motor Powered from Heater Circuit *) Heater Model No. NONE BAYHTR1405 +++ BAYHTR1408 +++ BAYHTR1410 +++ BAYHTR1415 +++ BAYHTR1415 BRK with Single Circuit Power Source Kit BAYSPEK140A BAYHTR3410 000 BAYHTR3415 000 BAYHTR1419 000 BAYHTR1419 BRK with Single Circuit Power Source Kit BAYSPEK140A Number of Circuits/ Phase 1/1 1/1 1/1 1/1 2/1 1/1 1/3 1/3 2/1 1/1 240 VOLT Capacity KW N/A 4.80 7.68 9.60 BTUH N/A 16400 26200 32800 Heater Amps per Circuit N/A 20 32 40 40/24 64 34.6 38.2 32/48 80 Minimum Circuit Ampacity 3.4 28 43 53 53*/30 89 43 51 43*/60 109 Maximum Overload Protection 15 30 45 60 60*/30 90 45 60 45*/60 110 Capacity KW N/A 3.60 5.76 7.20 BTUH N/A 12300 19700 24600 208 VOLT Heater Amps per Circuit N/A 17.3 27.7 34.6 34.6/20.8 55.4 30.0 33.1 17.7/41.6 69.3 Minimum Circuit Ampacity 3.4 25 39 47 47*/26 78 37 44 38*/52 96 Maximum Overload Protection 15 30 40 50 50*/30 80 40 45 40*/60 100

15.36 52400 15.36 52400 9.60 32800

11.53 39300 11.53 39300 7.20 24600

15.36 52400 19.20 65500 19.2 65500

11.53 39300 14.42 49200 14.42 49200

NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

2/4TEC3F60A WIRING DATA (Indoor Blower Motor Powered from Heater Circuit *) Heater Model No. NONE BAYHTR1405 +++ BAYHTR1408 +++ BAYHTR1410 +++ BAYHTR1415 +++ BAYHTR1415 BRK with Single Circuit Power Source Kit BAYSPEK140A BAYHTR3410 000 BAYHTR3415 000 BAYHTR1419 000 BAYHTR1419 BRK with Single Circuit Power Source Kit BAYSPEK140A Number of Circuits/ Phase 1/1 1/1 1/1 1/1 2/1 1/1 1/3 1/3 2/1 1/1 240 VOLT Heater Capacity Amps per KW BTUH Circuit N/A 4.80 7.68 9.60 N/A 16400 26200 32800 N/A 20 32 40 40/24 64 34.6 38.2 32/48 80 Minimum Circuit Ampacity 4.8 30 45 55 55*/30 89 43 52 45*/60 109 Maximum Overload Protection 15 30 45 60 60*/30 90 45 60 45*/60 110 208 VOLT Heater Capacity Amps per KW BTUH Circuit N/A 3.60 5.76 7.20 N/A 12300 19700 24600 N/A 20 27.7 34.6 34.6/20.8 55.4 30.0 33.1 17.7/41.6 69.3 Minimum Circuit Ampacity 4.8 26 39 48 48*/26 78 37 45 39*/52 96 Maximum Overload Protection 15 30 40 50 50*/30 80 40 45 40*/60 100

15.36 52400 15.36 52400 9.60 32800

11.53 39300 11.53 39300 7.20 24600

15.36 52400 19.20 65500 19.2 65500

11.53 39300 14.42 49200 14.42 49200

NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

22-1774-01-0905 (EN)

13

Electrical Data
Unit Wiring Diagram 2/4TEC3F18-48A1000A

MODEL TEC3F18 - 48A

14

22-1774-01-0905 (EN)

Electrical Data
Unit Wiring Diagram 2/4TEC3F60A1000A

NOTE: Motor Speed Tap # 5 must be selected if a time delay function is required.
22-1774-01-0905 (EN) 15

Field Wiring

Air Handler with Single Speed Cooling Unit, 2 Stage Heat

From Dwg. 21B801081 Rev. 1

Air Handlers with Single Speed Cooling Unit, 1 Stage Heat

From Dwg. 21B801083 Rev. 1

16

22-1774-01-0905 (EN)

Field Wiring

Field Wiring Diagrams for Air Handlers with Heat Pump

From Dwg. 21B801082 Rev. 1

Air Handler Subbase


REAR FLANGE

JOISTS HEADER

JOIST
ONE INCH DUCT SPACERS

FIG. 1
A
UNIT

FRONT OF UNIT

SUBBASE
HEADER JOISTS

APPROX. 3/4" FLANGES ON FIELD FABRICATED DUCT OR PLENUM.


JOIST

FLOOR

NAILS

NAILS

FLOOR OPENING - SIZE


FIG. 2

MODEL NO. TAYBASE100 TAYBASE101

A 23-3/4 21-3/4

B 14-13/16 14-13/16

HEADER

HEADER

FIG. 3

1"

1"

MIN. SPACING TO ANY COMBUSTIBLE MATERIAL.

22-1774-01-0905 (EN)

17

2/4TEC3F18-60A1000A Convertibility

Six (6) Way Convertibility

One Unit - 4 Applications


(Conversions 1-4)

Easy Conversion to Opposite Side Access


(Conversions 5 & 6) Unit is shipped as Horizontal right
Airflow

(as shipped)

Refrigerant Connections

Primary Condensate

Airflow
Horizontal Drain pan Coil Supports

Airflow

Pull coil out and rotate the coil 180


(as shipped) One-step Conversion Stand unit on end

Airflow

Slide coil back in on supports and roll unit 180 (so primary
Rotate Coil Airflow Airflow condensate is down)

One-step Conversion from Horizontal left

Note connections and access are now on back side of unit

Airflow

6 CONVERSION APPLICATIONS 1. Horizontal Right - (Front Access) 2. Vertical Upflow 3. Horizontal Left - (Front Access) 4. Vertical Downflow 5. Horizontal Right - (Rear Access) 6. Horizontal Left - (Rear Access)

Airflow

18

22-1774-01-0905 (EN)

Dimensions

Outline Drawing for 2/4TEC3F18-60A1000A

Fig. 1 MODEL NO. 2/4TEC3F18, 24, 30, 36 J K 19.22 12.02 21.22 2/4TEC3F48, 60

Fig. 2 J K 18.22 n/a 11.02 20.22 31.15 L

2/4TEC3F42

2/4

From Dwg. 21D800666 Rev. 6

R-22 (2TEC) Model No. *TEC3F18A *TEC3F24A *TEC3F30A *TEC3F36A *TEC3F42A *TEC3F48A, *TEC3F60A
* = 2 or 4

R-410 (4TEC) GAS LINE BRAZE 1/2 5/8 3/4 3/4 3/4 7/8 LIQ. LINE BRAZE 1/4 5/16 5/16 3/8 3/8 3/8

A 43

D 15.57

FLOW CONTROL

GAS LINE BRAZE 5/8

LIQ. LINE BRAZE 1/4 5/16

21.50 45 51.75 57.90 23.50 23.50

19.50 17.57 21.50 21.50 18.33 30.47

3.65

5.77 3.62 1.89 TXV/NB

3/4 7/8

4.65 4.65

6.77 6.77

3/8 1-1/8

22-1774-01-0905 (EN)

19

Mechanical Specification Options


General Blower coil units shall be completely factory assembled including coil, condensate drain pan, fan, motor, filters and controls in an insulated casing that can be applied in horizontal or vertical configuration. The F model indicates an Air-Tite model with 4.2 R value insulation and additional sealing systems. This new line of 2/4TEC-A Air Handlers provides exclusive compact size combined with simple 6-way convertibility in sizes up to 5 Tons. The unit ships in the right-hand horizontal configuration and converts to vertical upflow just by standing the unit on end. No tools required. Simple coil rotation provides downflow and horizontal left applications. The 6-way convertibility provides you inventory benefits and service/ installation flexibility. The simple conversion provides opposite side access for installation and service. These Air Handlers enjoy the best reputation in the industry. Superior airflow, great sound level, reliability and performance are responsible for the industry leadership. We are not about to give up such top performance. Units shall be UL listed. Casing Units shall have a rugged sheet metal and steel frame construction and shall be painted with an enamel finish. Casing shall be insulated and knockouts for electrical power and control wiring. Refrigerant Circuits The 2/4TEC-A units have a single refrigerant circuit. 2/4TEC3F18-60A refrigerant circuit shall be controlled by a factory-installed non-bleed thermal expansion valve. Coil Aluminum fin surface shall be mechanically bonded to 3/8-inch OD copper tubing. Coils are factory pressure and leak tested. Fan Forward curved, dynamically balanced and statically balanced with 3-speed direct drive shall be standard, fan motor bearing shall be permanently lubricated. Controls Low voltage pig tails, fan contactor, and plug-in module for accessory electric heat control shall be included. 2/4TEC models also include check valves. Filters Filters shall be included as standard, one-inch low velocity semi-permanent type (except 5-ton - washable filter). Accessories Electric Heaters Shall be available in a wide range of capacities and voltages with various staging options, and plug-in control wiring. Heaters shall fit inside the internal compartment.

P.I.

Trane A business of American Standard Companies www.trane.com

Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.