Introduction:
Testing the quality of building material is very necessary at the site before it is ready to be
used as a construction material. The material which is used on site suffers from many
different environmental conditions (moisture conditions and temperature conditions) then the
material tested in the laboratory as compared to the control conditions of laboratory. The
material available near the site for example the water has to be tested for its construction
requirements as it may affect the quality of construction. The water used must not have high
chlorine content.
Since the moisture content of sand varies continuously depending upon different weather
conditions so its moisture content has to be check regularly and necessary correction has to
be implanted and proper quantity of sand and aggregate can be used to achieve the desired
standard of strength.
Admixtures are substances used in small quantity to increase the workability of the concrete
for the given water cement ratio without affecting the strength of the concrete. Admixtures
used at the site are Sikament170PL4.
Water proofing of walls and floors are necessary to prevent them from dampness and
destruction of steel in reinforcement due to rusting and to prevent subsequent leakages and
even in worst cases failure of complete structure.
According to the material available at the site before starting of the construction proper mix
design is done and is estimated that what moisture content will amount to what strength in
concrete and a regular check is made by testing the concrete while construction and proper
correction is made if necessary.
• The grade of concrete used for construction purpose varies from M-25 to M-40 grade
concrete.
• Aggregate are tested for their strength by aggregate crushing and aggregate impact
test on site. Maximum size of aggregate used at site is 20 mm and minimum is 10
mm. The test are made according to IS – 2386 Part (I-VIII).
• Cubes are casted and check for their strength by checking their 7 days and 20 days
compressive strength.
• Non-destructive tests (like ultrasonic test etc.) are done on concrete if the concrete
fails to achieve the desired strength after 28 days to determine the cause of such weak
strength (due to honey-bee structure, etc.)
Test on Aggregate:
• Sieve analyses.
• Flakiness and elongation test.
• Aggregate Impact test.
• Aggregate Crushing test.
Test on Concrete:
• Compressive strength test.
Field Quality Control:
IS/ Job
Sl. Tests to Test conducted
Material Specification Frequency
No. be conducted By
Ref. No.
a. Total IS 2386
deleterious Twice per source Approved Lab
material content Part II
IS 2386
e. Elongation Once initially and then Simplex Field
Index change with source. Lab
Part I
IS 2386
g. Los Angeles Once initially and then once Simplex Field
Abrasion value every month. Lab
Part IV
IS 4031
a. Initial & Final Every 3000 bags and at least Simplex Field
setting time once monthly. Lab
Part V
IS 4031
b. Compressive Every 3000 bags and at least Simplex Field
strength once monthly. Lab
Part VI
4. Cement
a. Each lot a. Manufacturer
c. Chemical IS 4032/ IS Test Certificate
Analysis 4031 Part II b. Once for every type of
cement b. Approved Lab