SWITCH YARD

No. of bays Generator bays Bhilwara line bays Dausa line bays Kota line bay Spare bay Bus caupler bay Bus transfer section bay Bus switching scheme Double main bus Rated Current Fault Current 12 (Including 1 for future) 4 2 2 1 1 1 1 Double main and transfer bus ACSR Moose conductor spaced 250 mm. in square formation 1250 Amp 31.5 KA 2 Moose Conductor used for transfer of one feeder at a time through transfer bus breaker spaced at 250 mm

Transfer bus

Minimum clearance Phase to Phase Clearance Phase to Earth clearance Ground clearance Equipment bus height Section clearance 2700 mm 2300 mm 2580 mm 6200 mm from plinth level 4500 mm

LIST OF EQUIPMENTS
Circuit breaker SF6 Make Type Rating Breaking Capacity Insulation Level No. of Breaks per pole Type of Operating Mechanism Gas Pressure Closing time Opening time ABB Germany-10 Nos ABB India- 1 No ELF SL-5-2 and ELF SL-4-1 245/220 kv,2000 A 40 kv 1050 kv (Peak) Two Closing : Spring, Opening : Hydraulic 7 Kg/cm2 70m Sec. 20 m Sec.

Isolator (without E/S) Make No. of Provided Type Rating No. of Poles Rated SC with stand Current S & S Madras 10 RC 300 Horizontal Centre Break, Tandem 245 kv, 1250 A 3 31.5 kA, 1 Sec.

Isolator (With Single E/S) Make No. of Provided Type Rating No. of Poles Rated SC with stand Current S & S Madras 10 RC 300 Horizontal Centre Break 245 kv, 1250 A 3 31.5 kA, 1 Sec.

Isolator (With Double E/S) Make No. of Provided Type Rating No. of Poles Rated SC with stand Current S & S Madras 2000 A-2 Nos., 1250 A - 10 Nos RC 300 Horizontal Centre Break 245 kv, 2000 A 3 31.5 kA, 1 Sec.

Current Transformer Make No. of Provided Type Rating No. of Cores ABB India 30 Nos (1200-600/1A), 3 No (2000-1000/1) TMBR 245 kv, 1245 A 5

CVTs Make No. of Provided Type Rating No. of Cores Ratio Capacitance in pF-Primary Capacitance in pF-Intermediate Capacitance in pF-Effective ABB India 21 WP 245 N, Single Phase 245 kv 3 220/3 kv/110/3 V 4868 48400 4400 + 10%, -5%

Lightening Make No. of Provided Type Rating Minimum discharge Capacity WSI 27 CPL-II, Heavy duty Station class 198 kv, 11 kA 5 kj/kv

Bus Post Insulator Make Nos Provided Type WSI Bangalore 71 Solid Core 220 kv

Wave Trap Make Nos Provided Rating WSI 6 0.5 mH, 1250 A, 220 kv

Contral & Relay Panel Make Nos. Provided ABB India 2

Bay Marshaling Kiosk Make Nos. Provided Saravana, Switchgear 11

Marshaling Cubical (CT/CVTs) Make Nos Provided Saravana, Switchgear 11 (CT), 7 (CVT)

Batteries for PLCC System Make Type Rating Exide Ltd. Lead acid Cell, 2 Volts/Cell 48V, 300 AH

Battery Charger (PLCC) Make Nos. Provided Chhabi 1 (Normal), 1 (Reserve)

PLCC Equipments & Panel Make Nos Provided ABB India 8

Disturbance Recorder (Provided on Dausa & Bhilwara Feeders Make Type ABB India Industic 65 C

Distance to Fault Locator (Provided on Dausa & Bhilwara Feeders) Make Type ASEA RANZA