SECTION 16480
MAIN SWITCHBOARD AND MOTOR CONTROL CENTER
PART 1 - GENERAL
1.01 DESCRIPTION
This section describes materials, testing, and installation of main switchboard and motor
control equipment.
1.03 SUBMITTALS
1.04 RATINGS
Motor horsepower ratings and enclosures shown are minimum expected. This does not limit
the equipment size. When motors furnished differ from the minimum ratings indicated, make
the necessary adjustments to wiring, conduit, disconnect devices, motor starters, branch circuit
protection, and other affected material or equipment to accommodate the motors actually
installed, at no additional cost to the Owner.
Payment for the work in this section shall be included as part of the lump-sum bid amount
stated in the Proposal.
Main Switchboard and Motor Control Center
Section 16480 – 2
PART 2 - MATERIALS
A. Motor control centers shall be dead front, dead rear, floor standing, and front
accessible NEMA 3R gasketed construction. The voltage and ampere rating and
physical imensions shall be as indicated in drawings. Wiring shall be NEMA
Class II, Type B, with wiring schematics showing field devices and connections.
Tag control wiring within 2 inches of termination at each device and terminal
board. Schematics shall also show terminal numbers and interior and field wire
numbers.
C. Provide a separate vertical wiring compartment for each motor control center
section. Provide cable supports and a hinged door separate from the unit
starters.
F. Bus bars shall be silver plated copper and braced to withstand the rms
symmetrical short-circuit current ratings as shown in the drawings. Provide full
horizontal bus rating for entire length of the motor control center. Do not taper
the bus.
K. Motor control centers shall comply with applicable NEMA, UL, and ANSI
standards for industrial control. Provide UL label on each motor control center
section.
A. The Service Equipment and its installation arrangement shall conform to the
requirements of the serving utility company and the local authority having
jurisdiction and be in a NEMA 3R enclosure as shown on the drawings.
B. The main service section and pull section shall be 480 volt, three phase, four
wire, 60 hertz, with amperage as indicated on the drawing. The section shall be
configured as close as possible to that shown on the plans. They shall consist of
an underground pull section with landing lugs, meter socket, and a main
disconnect. The 500 ampere thermal and magnetic current limiting type main
disconnect breaker shall be rated to interrupt at least 30,000 symmetrical short
circuit amperes safely. The pull section and metering/main service sections shall
be UL labeled as "Suitable for Use as Service Equipment."
A. Comply with NEMA ICS, Class A, and with NEC Article 430.
E. The Contractor shall verify the motor ratings and coordinate the starter overloads
with the actual horsepower ratings on the motors installed.
F. Provide indicator lights, selector switches, push buttons, meters, etc., as shown
in the wiring diagrams. Mount on the front panel of the starter.
H. Provide control relays, interposing relays, time-delay relays, etc., within the
starter enclosure as shown in the schematic diagrams.
I. Interposing and Control relays shall be plug-in solid State type. Control relays
shall be UL listed with 10 amp rated contacts, and voltage, number of poles, and
pole arrangement as necessary or as indicated in the drawings. Relays shall be
IDEC, Potter-Brumfield or equal. See Section 17010 for additional information on
interposing relays.
K. Control switches shall be round, oiltight type, complete with legend plates and
quantity of contact blocks required for the control function.
L. Indicating lights shall be oiltight type, complete with color of lens indicated in
drawings and legend plate. Lamps shall be as indicated in the Specifications and
drawings. Lamps shall as indicated in Section 13400 entitled "Process
Instrumentation and Control."
A. Provide lightning and surge arresters as shown on the single line diagram.
Arresters shall be listed in accordance with UL-1449, Standard for Safety,
Transient Voltage Surge Suppressors. Arresters shall be solid-state type and
shall operate bidirectionally.
Main Switchboard and Motor Control Center
Section 16480 – 5
PART 3 - EXECUTION
3.01 INSTALLATION
B. Contractor shall install the service entrance equipment / motor control center with
adequate anchors to meet minimum latest adopted Uniform Building Code (UBC)
requirements for seismic zone 4 with a 1.25 importance factor. In addition to
UBC requirements, the anchorage system shall be designed to withstand a
minimum of 0.3 g design lateral seismic force in any horizontal direction.
3.02 TESTS
A. Test the operation of each switch to verify that it performs its function.
B. Set adjustable trip circuit breakers two settings above the setting that causes the
breaker to trip during motor starting. Do not adjust the setting above 1,300% of
the motor nameplate current rating.
END OF SECTION