Vous êtes sur la page 1sur 6

TECHNICAL SPECIFICATION FOR COPPER COMPONENTS

FOR TECHNICAL BID AND COMPLIANCE STATEMENT FOR UTP CABLING SYSTEM

UTP CABLING SYSTEM Sr No. 1 Compliance Details Type Specification Unshielded twisted pair cabling system, Certificate by Intertek (ETL) for the 4-Connectors channel testing to the Cat 6 Cabling system as per the ANSI/TIA 568 C.2 & as well as the ISO 11801 standards up to 600 MHz. 10 / 100/1000 Ethernet, 155 Mbps ATM, 1000 Mbps IEEE 802.3ab Ethernet, and proposed Cat 6 Gigabit Ethernet ETL Verified / UL Listed 25 year systems warranty; Warranty to cover Bandwidth of the specified and installed cabling system, and the installation costs (a) Attenuation, Pair-to-pair and PS NEXT, ELFEXT and PSELFEXT, Return Loss, ACR and PS ACR for 4connector channel (b) Should perform to CAT6 with short channel (c) 4-Connectors channel testing to the Cat 6 Cabling system as per the ANSI/TIA 568 C.2 & as well as the ISO 11801 standards up to 600 MHz. (d)Should have a PSNEXT margin of 7.5 dB over CAT6 (e) CAT6 cabling system should be tested and verified by the Independent third party laboratories for Zero BER (Bit Error Rate) testing at the data transmission speed of 1 Gbit/s. Deviation Yes / No

Networks Supported TIA / EIA 568 C.2 Warranty

Yes / No

3 4

Yes / No Yes / No

Performance characteristics to be provided along with bid

Yes / No

Yes / No Yes / No Yes / No

UTP CABLE Sr No. Compliance Details Specification Deviation

Type 1 2 3 4 5 Conductors Insulation Jacket Pair Separator Approvals Operating temperature Storage Temperature Frequency tested up to Packing Cable Outer Diameter Delay Skew Bend Radius Impedance UL/NEC Ratings Mutual Capacitance Conductor Resistance Propagation Delay Performance characteristics to be provided along with bid ROHS Compliant

Unshielded Twisted Pair, Category 6, TIA / EIA 568C.2 & ISO/IEC 11801 23 AWG solid bare copper Polyethylene Flame Retardant PVC Cross-member (+) fluted Spline. (a) UL Listed / UL Verified (b) ETL verified to TIA / EIA Cat 6 -20 Deg. C to +60 Deg. C -20 Deg. C to +80 Deg. C

Yes / No Yes / No Yes / No Yes / No Yes / No Yes / No Yes / No

Yes / No Minimum 600 MHz Box of 305 meters .23 inches 45ns MAX. 4 * Cable Diameter 100 Ohms + / - 15 ohms, 1 to 600 MHz. CMR Rated 5.6 NF MAX /100 Mtr. 66.58 Ohms Max / KM 536 ns/100 Mtrs. MAX @ 250 Mhz Yes / No Yes / No Yes / No Yes / No Yes / No Yes / No Yes / No Yes / No Yes / No Yes / No Attenuation, Pair-to-pair and PS NEXT, ELFEXT and PSELFEXT, Return Loss, ACR and PS ACR Yes / No ROHS/ELV Compliant

7 8 9 10 11 12 13 14 15 16

17 18

Sr

Details

UTP JACKS Specification

Compliance

Deviation

No. 1 2 3 4

Type Modular Jack Wire terminal Accessories

PCB based, Unshielded Twisted Pair, Category 6, TIA /EIA 568-C.2 and ISO/IEC 11801 750 mating cycles 200 termination cycles Integrated bend-limiting strain-relief unit for cable entry Integrated hinged dust cover Support cable pair termination process on the jacks at 90 degree angle. Bidder should have a mechanism to maintain the quality of the termination ir-respective of the skill level of the termination staff. Polyphenylene oxide, 94V-0 rated. polycarbonate, 94V-0 rated Beryllium copper, plated with 1.27 mm [.000050] thick gold in localized area and 3.81 mm [.000150] minimum thick tin-lead in solder area over 1.27 mm [.000050] minimum thick nickel under plate Polycarbonate, 94V-0 rated (a) UL Listed / CSA Approved (b) ETL verified to TIA / EIA Cat 6 Attenuation, NEXT, PS NEXT, FEXT and Return Loss

Yes / No Yes / No Yes / No

Yes / No Yes / No Yes / No Yes / No Yes / No Yes / No

5 6 7

Housing 110 Blocks Jack contacts

8 9 10

Wiring blocks Approvals Performance Characteristics to be provided with bid ROHS Compliant

Yes / No Yes / No Yes / No Yes / No

11 ROHS/ELV Compliant

Yes / No

UTP JACK PANELS 24 PORT Sr No. Type 1 2 3 4 5 6 7 8 9 Circuit Identification Port Identification Modular Jack Wire terminal Accessories Materials Housing Wiring blocks Jack contacts Polyphenylene oxide, 94V-0 rated Polycarbonate, 94V-0 rated Beryllium copper, plated with 1.27 mm [.000050] thick gold in localized area and 3.81 mm [.000150] minimum thick tin-lead in solder area over 1.27 mm [.000050] minimum thick nickel under plate Black, powder coated steel UL listed / ETL Verified TIA / EIA 568 A and B; Yes / No 12 ROHS Compliant ROHS/ELV Compliant Yes / No Yes / No Yes / No Ports Port arrangement Compliance Details Specification 24-port, Modular, PCB based, Unshielded Twisted Pair, Category 6, TIA / EIA 568-C.2 and ISO/IEC 11801 24 Configured as 6 Port Module with individually replaceable CAT-6 Jacks Front of each module shall be capable of accepting 9 mm to 12 mm labels 9mm or 12mm Labels on each of 24-ports (to be included in supply 750 mating cycles 200 termination cycles Integrated bend-limiting strain-relief unit for cable entry Deviation Yes / No Yes / No

Yes / No Yes / No

Yes / No Yes / No Yes / No

Panel 10 11 Approvals Termination Pattern

Yes / No Yes / No Yes / No

WORKSTATION / EQUIPMENT PATCH CORDS Sr No. Compliance Details Specification Deviation

1 2 3 4 5 6 7

Type Conductor Length Plug Protection Warranty Insulation ROHS Compliant

Unshielded Twisted Pair, Category 6, TIA / EIA 568C.2 & ISO/IEC 11801 24 AWG 7 / 32, stranded copper conductors 100 Ohm 4 feet, 7 feet, 10 feet Transparent Slim boot 25-year component Flame Retardant Polyethylene ROHS/ELV Compliant

Yes / No Yes / No Yes / No Yes / No Yes / No Yes / No Yes / No

FACE PLATE Sr No. 1 2 3 4 Compliance Details Type Material No. of ports ROHS Compliant Single Gang ABS / UL 94 V-0 One/Two ROHS/ELV Compliant Specification Yes / No Yes / No Yes / No Yes / No Deviation

Vous aimerez peut-être aussi