Académique Documents
Professionnel Documents
Culture Documents
load! #1
load! #2
load! #3
primary! circulator
presented by: John Siegenthaler, P.E. Appropriate Designs Holland Patent, NY www.hydronicpros.com
Copyright 2012, J. Siegenthaler, all rights reserved. The contents of this le shall not be copied or transmitted in any form without written permission of the author. All diagrams shown in this le on conceptual and not intended as fully detailed installation drawings. No warranty is made as the the suitability of any drawings or data for a particular application.
crossover! bridge
Hydraulic Separation
Its not just about hydraulic separators...
Todays topics...
What is common piping? Whats the relationship b/w common piping & hydraulic separation? It doesnt have to be perfect What is the ideal hydronic header? Achieving hydraulic separation using low resistance heat souce Achieving hydraulic separation using closely spaced tees Achieving hydraulic separation using a buffer tank Achieving hydraulic separation using a hydraulic separator Divide & Conquer Examples of systems using hydraulic separation
What is COMMON PIPING? Its the piping components shared by two or more circuits.
common piping
The degree to which two or more operating circulators interact with each other depends on the head loss of the common piping. The lower the head loss of the common piping the less the circulators will interfere with each other.
When the head loss of the common piping is very low, there is hydraulic separation between the circuits.
When the head loss of the common piping is very low, there is hydraulic separation between the circuits.
Very little head loss occurs! in this portion of the circuits.
circuit 1 head loss curve including ! common piping (both circulators on) circuit 1 head loss curve including ! common piping (1 circulator on)
Assume that circulator 1 is operating, but that circulator 2 is off. The lower (blue) system head loss curve in gure 2 applies to this situation. Next, assume circulator 2 is turned on, and circulator 1 continues to operate. The ow rate through the common piping increases, and so does the head loss across it. However, because of its spacious geometry, the increase in head loss across the common piping will be very slight. The system head loss curve that is now seen by circulator 1 has very slightly steepened. It is the upper, (green) curve shown in gure 2. The operating point of circuit 1 has moved very slightly to the left, and as a result, the ow rate through circuit 1 has decreased very slightly.
very small change in! head loss across! common piping! when both circuits are on
0 ow rate
VERY small decrease in! circuit 1 ow rate! when circuit 2 is on ow rate in circuit 1 when BOTH circuits! are operating ow rate in circuit 1 when it is the only circuit operating
Imagine a hypothetical situation in which the head loss across the common piping was zero, even with both circuits operating. Because NO head loss occurs across the common piping, it would be impossible for either circulator to inuence the other circulator.
The higher the ow resistance of the common piping, the more each circulator will inuence ow in the other circuit (e.g. the lower the hydraulic separation of the circuits.
6 4 2 0
15
4 psi P at 0 ow
10 5 0 0 2 4 6 8 ow rate (gpm) 10
P=17psi
backseated! ow check
P= 10 psi
larger circulator
ON
ON
smaller circulator
P=17 psi
no ow
zone circulators with spring-loaded check valves compact mod/con boiler purging! valves low ow resistance headers
OK
low ow resistance heat source
purging! valves
NOT OK
Always keep the ow resistance of the common piping as low as possible. This provides hydraulic separation between circulators. Always provide a check valve on each zone circuit.
From the standpoint of hydraulics, each circuit can be designed as if its a stand-along circuit. More on this later...
Primary / secondary piping, using closely spaced tees, is now well known and often used in North America.
primary! circulator
Primary / secondary piping, is one way to achieve hydraulic separation between circulators.
But primary / secondary piping is not the ONLY way to create hydraulic separation...
primary! circulator
primary! circulator
parallel! primary! circuit
crossover! bridge
Both series and parallel primary/secondary systems require a primary circulator. This adds to the installed cost of the system AND adds hundreds, even thousands of dollars in operating cost over a typical system life.
3000 hr 552 w 1kwhr $0.10 1st year cost = = $165.60 yr 1 1000 whr kwhr
Question: What is the ideal header in a hydronic system? Answer: One that splits up the ow without creating head loss Think about a copper basketball with pipes sticking out of it in all directions.
So why dont we build headers like this??? Instead, we approximate the ideal header by making it short & fat
fat
Short / fat headers are GOOD! Long / skinny headers are BAD!
short
fat short
select pipe size that yields a ow velocity no higher than 2 feet per second
Hydraulic separation achieved by low ow resistance heat source & short / fat headers.
The low ow resistance heat source maintains low ow resistance of common piping
The short / fat headers hydraulically separate the distribution circulators from each other.
Hydraulic separation achieved by closely spaced tees & short / high ow ! fat headers.
resistance boiler
The short / fat headers hydraulically separate the distribution circulators from each other. The closely spaced tees hydraulically separate the heat source from the header system.
closely spaced tees size headers for max ow velocity of 2 ft/sec very low ow resistance! common piping!
Hydraulic separation achieved by closely spaced tees & short / fat headers. ouside! The short & fat header and close
sensor multiple! boiler! controller
spacing between supply and return connections results in a low pressure drop between points A and B. Each load circuit is hydraulically separated from the others.
Each circuit must include a check valve. The supply temperature sensor must be downstream of the point of hydraulic separation.
B
drain! valve
Hydraulic separation achieved by buffer tank (piped as shown ) & short / fat headers.
high ow resistance boiler
boiler! circulator
The short / fat headers hydraulically separate the distribution circulators from each other.
size headers for max ow velocity of 2 ft/sec
The buffer tank hydraulically separate the heat source from the header system.
buffer! tank
ThermoCon tank
VENT
evaporator
condenser
Only tanks with sprayed foam insulation should be used for chilled water storage.
TRV
TRV
TRV TRV
manifold! station
indirect water heater buffer tank, also serves as hydraulic separator,! air separator, dirt separator
The short / fat headers hydraulically separate the distribution circulators from each other.
hydraulic separator size headers for max ow velocity of 2 ft/sec very low ow resistance! common piping!
air vent
area = A
ow velocity = 4 ft/sec ow rate = 6.5 gpm ow velocity = 0.44 ft/sec ow rate = 6.5 gpm
diameter = 3" area = 9A almost zero pressure drop b/w! upper and lower connections
drain valve
The low vertical velocity inside the separator produces minimal pressure drop top to bottom. Thus there is very little tendency to induce ow on the load side of the separator.
air vent upper coalescing media encourages! air bubbles to form air bubbles "ride" up the vertical laments of the coalescing media - out of the active ow zone
lower coalescing media encourages! dirt particle to drop! out of active ow zone
drain valve
drain valve
The coalescing media creates tiny vortices that cause gas molecules (mostly oxygen and nitrogen) to form microbubbles. The media also helps microbubble merge together and rise upward out of the active ow zone.
Why companies that offer air and dirt separators also offer hydraulic separators...
air vent air vent
air vent
air vent
CUT
WELD
CUT
WELD
drain valve
drain valve
drain valve
drain valve
Hydraulic! Separator
boiler circuit
distribution system
heating! load(s)
air! separator distribution system boiler circuit closely! spaced! tees sediment! strainer heating! load(s)
As the ow rates of the boiler circuit and distribution system change there are three possible scenarios:
1. Flow in the distribution system is equal to the ow in the boiler circuit.
f1 T1
NOTE:
f2 T2
NOTE:
f1 = f3
(always!)
f2 = f 4
(always!)
T3
f3
f4
T4
T1 = T2 T3 = T4
f1 T1
NOTE:
f2 T2
NOTE:
The mixed temperature (T2) supplied to the distribution system can be calculated with:
f1 = f3
(always!)
f2 = f 4
(always!)
( f4 f1 ) T4 + ( f1 ) T1 T2 = f4
T4
Where: f4 = ow rate returning from distribution system (gpm) f1 = ow rate entering from boiler(s) (gpm) T4 = temperature of uid returning from distribution system (F) T1 = temperature of uid entering from boiler (F)
T3
f3
f4
f2 T2
f1 = f3
(always!)
f2 = f 4
(always!)
( f4 f1 ) T4 + ( f1 ) T1 T2 = f4
Where: T3 = temperature of uid returned to boiler(s) (F) f1 = ow rate entering from boiler(s) (gpm) f2, f4 = ow rate of distribution system (gpm) T1 = temperature of uid entering from boiler (F) T4 = temperature of uid returning from distribution system (F)
f3 T3
f4
T4
Sizing of Hydraulic Separators: Hydraulic separators must be properly sized to provide proper hydraulic, air, and dirt separation. Excessively high ow rates will impede these functions. The size of a hydraulic separator refers to the nominal piping size of the 4 side connections (not the diameter of the vertical barrel). The piping connecting to the distribution side of the Hydro Separator should be sized for a ow of 4 feet per second or less under maximum ow rate conditions.
union connections ange connections
1.25 1.5
2.5
11
18
26
40
80
124
247
485
Boiler manifold with integral hydraulic separator (courtesy Sinus North America).
Form tting insulation is supplied with all manifolds. Flexible piping connects each boiler to low manifold. (Boilers have integral circulators and check valves.) Notice that two additional boilers can be added to the front side of lower manifold.
How about 8 mod/cons with integral hydraulic separator (courtesy Sinus North America).
Think of the output per unit of mechanical room oor area Each boiler can be independently serviced . Flexible piping connects each boiler to low manifold. (Boilers have integral circulators and check valves.)
Example of Hydro Separator Installation in New System: Magna Steel Corporation - Connecticut
Example of Hydro Separator Installation in Old System: Because hydraulic separators remove sediment fromsystems theyre ideal for applications where new boilers are retrot to old distribution systems.
hydraulic! separator
A hydraulic separator is a great way to interface a new mod/con boiler to a older steam conversion system.
WHY?
existing cast-iron radiators (converted from steam) mod/con boiler! w/ compact heat exchanger vent
The will allow the ow rate in the earth loop to be different than the ow rate through the heat pump array - more on this later...
zone! valve
heating mode
Hydraulic Separators will likely become a key component in multiple ground source heat pump applications.
reversing! valve
evaporator
balancing! valve
purge
uid feeder
condenser
Hydraulic Separators will likely become a key component in multiple ground source heat pump applications.
heating mode
compressor
AB
evaporator condenser
A B 12D
A AB B
compressor
circulator! w/ check
reversing! valve
AB
evaporator condenser
A B 12D
A AB B
TXV
heating mode
compressor
circulator! w/ check
reversing! valve
size all header piping for maximum ow velocity of 2 ft/sec to provide hydraulic separation
evaporator
condenser
A AB B
TXV
temperature! sensor geothermal manifolds hydro! separator chilled water buffer tank purging! valves earth loop circuits purge
TXV
circulator! w/ check
heating mode
VENT
From the standpoint of hydraulics, each circuit can be designed as if its a stand-along circuit.
panel radiator
TRV
TRV TRV
This portion of system lled with 40% solution of inhibited propylene glycol
TRV TRV
3/4" copper
manifold G! (garage)
P8
30 psi! PRV
strap-on! aquastat! contacts! close at 100F! open at 50F to / from other! radiators These panel radiators are representative! of second oor heating distribution system! exact size and number of panels may vary,! but all are supplied with 1/2" PEX-AL-PEX tubing, and controlled by individual thermstatic radiator valves.
P&TRV
ll/purge
P7
HW 12D CW
1.25" copper 1.25" copper tank acqustat
12D
1" copper 12- circuit manifold distribution system using PEX or PEX-AL-PEX tubing 3/4" fast ll piping
P1
3/4" copper
12D
2" air separator
12D
P6
MRHL
12D
PRV
LWCO
2" copper brass unions! (typical) 2" copper balancing! valve cast-iron sectional boiler! with oil burner
balancing! valve
12D
3/4" copper
oor! drain
3/4" copper
12D
3/4" copper
3/4" copper
3/4" copper
3/4" copper
3/4" copper
3/4" copper
3/4" copper
3/4" copper
1" copper
1" copper
purging! valves
3/4" copper
manifold A
manifold C
manifold B
manifold D
manifold E
manifold F
3/4" copper
1" copper
1" copper
1" copper
1" copper
3/4" copper
3/4" copper
P3
outdoor! sensor
P5
P2
1.25" copper
12D
P4
1.25" copper
zone valves
TRV
TRV TRV
Hydraulic separation allows designers to think of an overall system as a collection of independent (hydraulically isolated) circuits. In this system, hydraulic separation was achieved using short / fat header in combination with low ow resistance heat source.
P7 P1
P6
P3
P5
P2
P4
DHW
P&TRV
heating is off
to / from other heating zones
water heater
cooling mode
reversing! valve
evaporator TXV
condenser
buffer tank
VENT
geothermal manifolds
OUTSIDE
INSIDE
! outdoor unit
purge! valve
Calef
Spirotherm
Taco
Please visit our website for more information (publications & software) on hydronic systems:
www.hydronicpros.com