DUCT WORKS METHOD OF STATEMENT

DUCT WORK METHOD STATEMENT


1. Definition: This method of statement specifies the process the duct work, which includes all the air movers, air handling units, kitchen and bathroom exhaust either install inside building or on roof. All in accordance with specification section 15890 and SMACNA's sheet metal and air conditioning contractors' standards 2. Delivery, Handling Storage :  Duct work will be delivered to site in one meter length boxes as in sizes as the related shop drawing indicates.  The boxes will be stored at specified closed room in the basement floor.  The type of insulation and cladding will be as to (Smacna)'s standards and as indicated in table 2. 3. Fabrication and insulation:  The thickness of the sheet metal will be as stated in SMACNA's standards and as specified in the table no.1.  all anchor bolts ,angles, bars and channels will be installed at site as the manufactures recommendation (HILTY) which is clearly shown in the related material submittal  all longitudinal seams for the rectangular duct shall be double corner seam as indicated in SMACNA 's attached sheet

 all rectangular duct shall be receive cross breaking treatment in order to obtain more strength for all sizes  The type of rectangular duct reinforcement will be as SMACNA 's standards and as indicated in table 1  sealant will be added to all transverse joints  The type of rectangular duct insulation is fiber glass rigid boards having a 48 kg/m3 density and 25 mm thickness as indicated in the bill of quantity and specifications as indicated in table 2.  All exposed insulation shall receive another layer of duct cladding having a sheet metal thickness of 0.7 mm to protect it from weather as indicated in table 2 4. Testing; all duct tightness will receive a light test to insures air leakage

Material Used MATERIAL TYPE manufacture or trade mark SABIC Country of origin international manufacturing standard Bs 2989 grade z2 ASTM (C-411,C732,D-2202) ASTM E - 84 CLASS 1 NFPA 701 (UL 214) UL 181, NFPA 90 A specifications

galvanized sheet metal duct sealant STAR flexible duct AERODUCT connector reinforced OMNIAIR insulated flexile duct fiber glass rigid boards insulation IZOCAM

kingdom of Saudi Arabia united Arab emirates

G90,275gr/m2

10 Cm width vinyl

United states of America

Turkey

ISO 9001, ISO 14001 And OHSAS 18001 ,(CE)

48 KG/M3 ,25 MM THICKNESS

Table no.1 Method of fabrication for all duct works as per SMACNA'S standards duct longest location reinforcement spacing reinforcement code as side between transverse SMACNA recommendation dimension in joints mm up to 900 inside 1000 slip and drive type i.e. T1 ,T3 building 900 ~1500 on roof 1000 flanged type i.e. E, 25*32

sheet metal thickness (mm) 0.7 0.9

service

Table no.2 insulation and cladding schedule air-conditioned supply and return return duct work supply duct work plenum boxes from AHU-1 and ,i.e. fan coil units acoustic fan coil units and Ahu-1, insulation 25 mm fiber glass boards with 48 kg/m3 density 25 mm fiber glass boards with 48 kg/m3 density, with 0.7 mm duct cladding for exposed 25 mm fiber glass boards with 48 kg/m3 density, with 0.7 mm duct cladding elastomeric foam insulation 6mm thick to reduce generated sound not applicable not applicable air passes inside ducts at room temperature 25 mm fiber glass boards with 48 kg/m3 density

location inside building above false ceiling inside building exposed areas, and shafts on roof exposed to weather

fresh air duct work, exhaust duct work from kitchen and wet areas not applicable air passes inside ducts at room temperature not applicable air passes inside ducts at room temperature

25 mm fiber glass boards with 48 kg/m3 density, with 0.7 mm duct cladding

25 mm fiber glass boards with 48 kg/m3 density, with 0.7 mm duct cladding