General Data LV HRC SITOR Fuse Links 2/2 2/4 2/13 2/15 2/17 2/19 2/22 2/27 2/33 2/35 2/41 2/44 2/46 2/48 SITOR Fuse Links for Special Applications 2/50 2/54 2/57 2/59 2/60 2/73 2/75 2/77 2/78 2/86 2/89 2/90 Product overview Application information Rated voltage 500 V AC Rated voltage 600 V AC Rated voltage 660 V AC Rated voltage: 690 V AC/ 700 V DC Rated voltage 690 V AC, operational class gS Rated voltage 690 V AC, operational class gR Rated voltage 800 V AC Rated voltage 1000 V AC Rated voltage 1500 V AC Rated voltage 2000 V AC Rated voltage 2500 V AC Configuration Aids For rectifiers in electrolysis systems For SITOR thyristor sets For railway supply rectifiers Configuration Aids SITOR cylindrical fuse links NEOZED fuse links SILIZED DIAZED fuse links SILIZED Configuration Aids Technical explanations Specifying the rated current Terms Characteristic curves
Notes on Dimensioning
2/1
Semiconductor Fuses
General Data
Product overview
I Overview
LV HRC SITOR fuse links
Rated voltage Un to 2500 V AC, 700 V DC Rated current In 16 ... 1000 A Operational class: aR, gR, gS Sizes 000 to 3 Range of connection types: - for mounting in LV HRC fuse bases - with bolt-on links, mounting dimensions 80 ... 260 mm - with bolt-on links, with 2 oblong slots - with M12 screw connection
2/2
Siemens ET B1 T 2007
Semiconductor Fuses
General Data
Product overview
SITOR cylindrical fuse links
Rated voltage Un 600/690 V AC, 400/700 V AC Rated current In 1 ... 100 A Operational class: aR Sizes 10 mm x 38 mm, 14 mm x 51 mm and 22 mm x 58 mm
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Siemens ET B1 T 2007
2/3
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
I Benefits
Used in conjunction with the new 3NE1 ...2 fuse range, the 3KL switch disconnectors with fuses have been awarded UL approval.
I Application
Characteristics SITOR fuse links protect converter equipment against short-circuits. The power semiconductors used in these devices (diodes, thyristors, GTOs and others) require high-speed elements for protection due to their low thermal capacity. SITOR fuse links (super quick fuse links for semiconductor protection) are ideal for these types of application. The following types of short-circuit faults can occur: Internal short-circuit: a faulty semiconductor device causes a short circuit within the power converter. External short-circuit: a fault in the load causes a short circuit on the output side of the power converter. Shoot-throughs: In the event of a failure of the chassis converter control system during inverter operation (commutation failure), the converter connection forms a short-circuit type connection between the DC and AC power supply system. Fuse links can be arranged in a number of ways within the converter connection. A distinction is made between phase fuses in threephase current incoming feeders and, if applicable, DC fuses and arm fuses in the arms of the converter connections (see adjacent graphs). In the case of center tap connections, fuse links can only be arranged as phase fuses in three-phase current incoming feeders. When using SITOR fuse links of operational class aR, the overload protection of converter equipment, up to approx. 3.5 times the rated current of the fuse link, is taken from conventional protective devices (for example, thermal-delayed overload relays) or, in the case of controlled power converters, from the current limiter (exception: full range fuses). As semiconductor protection, SITOR fuse links of the3NE1 ...-0 series with gS operational class are also suitable for the overload and short-circuit protection of cables, lines and busbars. All other dual-function fuses of the SITOR series have a gR characteristic. Overload protection is ensured as long as the rated current of the SITOR fuse links of the 3NE1 ...-0 series is selected as In Iz (DIN VDE 0100 Part 430). The rules of DIN VDE 0100 Part 430 must be applied when rating short-circuit protection for cables, lines and busbars. Configuration options
I2_10893
I2_10894
Six-pulse bridge circuit B6 with phase fuses and DC fuse (reversible connection)
I2_10895
Six-pulse bridge circuit B6 with phase fuses and DC fuse (switching for converter)
(
I2_10898
I2_10897
2/4
Siemens ET B1 T 2007
I2_10896
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
Use in switch disconnectors When using SITOR semiconductor fuses in 3KL and 3KM switch disconnectors with fuses and 3NP fuse switch disconnectors, the rated current of the fuse must sometimes be reduced due to the higher power dissipation compared to LV HRC fuses for line protection. Sometimes when using SITOR semiconductor fuses in switch disconnectors, the currents designated can be higher than the rated currents of the switches. These higher currents only apply when using SITOR switch disconnectors with semiconductor fuses and cannot be used when using switch disconnectors with standard LV HRC fuses. You will find further details in the following selection table. When using SITOR semiconductor fuses of the 3NC24, 3NC84, 3NE33 and 3NE43 series, the standard switching capacity of the fuse must not be used as the blades of these fuses (in contrast to LV HRC fuses) are slit. Occasional switching of currents up to the rated current of the fuses is permissible. Due to the mechanical strain on the comparatively long fuse blade, SITOR semiconductor fuses of the 3NE41 series may only be occasionally switched, and only without load. If only switching without load is permissible, this must be clearly stated on the switch itself. The use of SITOR semiconductor fuses > 63 A for overload protection is not permitted even if gR fuses are used (exception: 3NE1). The operational voltage is limited by the rated voltage of the switch disconnector or the fuse. If switching without load, the limit value is the rated insulation voltage of the switch disconnector. The 3NE1 "double protection fuses" can be used as full range fuses (gS) for semiconductor and line protection. Due to the dimensions of the SITOR semiconductor fuses, only the fuses shown in the following selection and ordering data can be used with 3KL and 3KM switch disconnectors with fuses and 3NP fuse switch disconnectors.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Siemens ET B1 T 2007
2/5
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
Load rating of fuse links with SITOR LV HRC fuse bases
SITOR fuse links Order No. Un V AC Operational BG class In A gR gR gR gR gR aR gR gR gR gR gR aR gR gS gR gS gR gS gR gS gR gS gR gS gR gS gR gS gS gR gS gR gS gR gS gR gS gR gR gS gR gR gR gR 3 3 3 3 3 3 3 3 3 3 3 3 00 00 00 00 00 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 150 200 250 300 350 400 150 200 250 350 500 1000 80 100 100 125 125 160 160 200 200 250 250 315 315 350 350 400 450 450 500 500 560 560 630 630 710 710 710 800 800 800 670 850 0.95 0.95 0.95 0.95 0.95 0.95 0.85 0.85 0.85 0.85 0.85 0.95 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 WL mm2 70 95 120 185 240 240 70 95 120 240 2 x 150 2 x (60 x 6) 25 35 35 50 50 70 70 95 95 120 120 2 x 70 2 x 70 2 x 95 2 x 95 2 x 95 2 x 120 2 x 120 2 x 120 2 x 120 2 x 150 2 x 150 2 x 185 2 x 185 2 x (40 x 5) 2 x (40 x 5) 2 x (40 x 5) 2 x (50 x 5) 2 x (50 x 5) 2 x (50 x 5) 2 x (40 x 5) 2 x (40 x 8) Imax = maximum permissible current IWL = maximum permissible current with varying load 3NH3 230/ 3NH4 230 3NH3 030/ 3NH4 030 3NH3 430 3NH3 430 3 3 3 3 3 3 3 3 3 3 3 3 00 00 00 00 00 1 1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 min Cu LV HRC fuse bases Order No. BG Imax A 150 190 240 285 330 400 135 180 250 315 450 800 80 100 100 125 125 160 160 200 200 250 250 315 315 350 350 400 450 450 500 500 560 560 630 630 710 690 710 800 750 800 670 850 IWL A 143 181 228 271 314 380 115 153 213 268 383 800 80 100 100 125 125 160 160 200 200 250 250 315 315 350 350 400 450 450 500 500 560 560 630 630 690 690 710 750 750 800 670 850
3NC2 4
3NC2 423-3 3NC2 425-3 3NC2 427-3 3NC2 428-3 3NC2 431-3 3NC2 432-3 500 500 500 500 500 500 660 660 660 660 660 600 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 600 690 690 600 690 690 690
3NC8 4
3NC8 423-3 3NC8 425-3 3NC8 427-3 3NC8 431-3 3NC8 434-3 3NC8 444-3
3NE1 0
3NE1 020-2 3NE1 021-0 3NE1 021-2 3NE1 022-0 3NE1 022-2
3NE1 2
3NE1 224-0 3NE1 224-2 3NE1 225-0 3NE1 225-2 3NE1 227-0 3NE1 227-2 3NE1 230-0 3NE1 230-2
3NH3 330
3NE1 3
3NE1 331-0 3NE1 331-2 3NE1 332-0 3NE1 333-0 3NE1 333-2 3NE1 334-0 3NE1 334-2 3NH3 330
3NH3 430
3NE1 4
3NE1 435-0 3NE1 435-2 3NE1 436-0 3NE1 436-2 3NE1 437-0 3NE1 437-1 3NE1 437-2 3NE1 438-0 3NE1 438-1 3NE1 438-2 3NE1 447-2 3NE1 448-2 Un = rated voltage BG = size In = rated current WL = varying load factor 3NH3 430
2/6
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
SITOR fuse links Order No. Un V AC Operational BG class In A gS gS gS gS gS gS gS gS aR aR aR aR aR aR aR aR aR aR aR aR aR aR aR aR aR gR gR gR aR aR aR aR aR aR aR aR aR aR gR gR gR gR aR aR aR aR 000 000 000 000 000 000 000 000 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 0 0 0 0 0 0 0 0 2 2 2 2 2 00 00 00 00 00 00 00 00 16 20 25 35 40 50 63 80 100 125 160 200 250 315 350 400 450 400 450 500 560 630 710 800 900 32 40 50 63 80 100 125 160 250 315 450 500 710 25 35 50 63 80 100 125 160 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.95 0.95 1.0 1.0 1.0 0.95 0.95 0.90 0.90 1.0 1.0 1.0 1.0 1.0 1.0 0.95 0.95 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.95 0.95 0.95 0.90 0.95 0.95 0.95 0.95 0.95 WL mm2 1.5 2.5 4 6 10 10 16 25 35 50 70 95 120 185 240 240 2 x 150 240 2 x 150 2 x 150 2 x 185 2 x 185 2 x 200 2 x 200 2 x 200 6 10 10 16 25 35 50 70 120 240 2 x (30 x 5) 2 x (30 x 5) 2 x (40 x 5) 4 6 10 16 25 35 50 70 3NH3 330 3NH3 430 3NH3 120/ 3NH4 230 3NH3 230/ 3NH4 230 3NH3 030/ 3NH4 030 00 00 00 00 00 00 00 00 1 1 1 1 1 2 2 2 2 3 3 3 3 3 3 3 3 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 2 2 3 3 3 00 00 00 00 00 00 00 00 min Cu LV HRC fuse bases Order No. BG Imax A 16 20 25 35 40 50 63 80 100 125 160 200 250 305 335 380 425 400 450 500 560 630 680 700 750 32 40 50 63 80 100 125 160 240 300 425 475 630 25 35 50 63 80 100 125 160 IWL A 16 20 25 35 40 50 63 80 95 119 160 200 250 290 318 342 383 400 450 500 560 630 680 665 713 27 34 43 54 68 85 106 136 204 255 361 404 599 24 33 45 60 76 95 119 152
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
3NE1 8
3NE1 813-0 3NE1 814-0 3NE1 815-0 3NE1 803-0 3NE1 802-0 3NE1 817-0 3NE1 818-0 3NE1 820-0 690 690 690 690 690 690 690 690 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 900 800 690 1000 1000 1000 1000 1000 1000 1000 1000 800 800 800 800 800 690 690 690 690 690 690 690 690
3NE3
3NE3 221 3NE3 222 3NE3 224 3NE3 225 3NE3 227 3NE3 230-0B 3NE3 231 3NE3 232-0B 3NE3 233 3NE3 332-0B 3NE3 333 3NE3 334-0B 3NE3 335 3NE3 336 3NE3 337-8 3NE3 338-8 3NE3 340-8
3NH3 330
3NH3 430
3NE4
3NE4 101 3NE4 102 3NE4 117 3NE4 118 3NE4 120 3NE4 121 3NE4 122 3NE4 124 3NE4 327-0B 3NE4 330-0B 3NE4 333-0B 3NE4 334-0B 3NE4 337
3NE8
3NE8 015-1 3NE8 003-1 3NE8 017-1 3NE8 018-1 3NE8 020-1 3NE8 021-1 3NE8 022-1 3NE8 024-1 Un = rated voltage BG = size In = rated current WL = varying load factor 3NH3 030/ 3NH4 030
min Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load
Siemens ET B1 T 2007
2/7
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
Load rating of fuse links with SITOR 3NP LV HRC fuse switch disconnectors
SITOR fuse links Order No. Un V AC BG In A 3 3 3 3 3 3 3 3 3 3 3 3 150 200 250 300 350 400 150 200 250 WL mm2 0.95 70 0.95 95 0.95 120 0.95 185 0.95 240 0.95 240 0.85 70 0.85 95 0.85 120 3NP54 3NP54 3 3 3 3 3 3 3 3 3 3 3 3 min Cu 3NP LV HRC fuse switch disconnectors Add-on units Order No. BG Imax IWL A 145 180 225 255 330 400 135 180 225 300 425 800 125 165 205 240 295 380 125 165 205 275 400 800 3NP44 70 3 3 3 3 3 3 3NP44 70 3 3 3 3 3 -Order No. BG Imax IWL A 140 175 220 250 320 370 120 160 200 270 385 -120 160 200 235 290 370 120 160 200 270 385 -3NP44 76 3 3 3 3 3 3 3NP44 76 3 3 3 3 3 3NP44 76 3 Busbar devices Order No. BG Imax IWL A 140 175 215 245 315 360 120 155 195 260 375 400 120 160 195 230 285 360 120 155 195 260 375 400 --------------Order No. BG Imax IWL A -------------------------
3NC2 4
3NC2 423-3 3NC2 425-3 3NC2 427-3 3NC2 428-3 3NC2 431-3 3NC2 432-3 500 500 500 500 500 500 660 660 660 660 660 600
3NC8 4
3NC8 423-3 3NC8 425-3 3NC8 427-3 3NC8 431-3 3NC8 434-3 3NC8 444-3
350 0.85 240 500 0.85 2 x 150 1000 0.95 2 x 3NP54 (60 x 6) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 25 35 35 125 125 70 70 95 95 120 120 2x 70 2x 70 2x 95 2x 95 2x 95 3NP53/ 3NP43 3NP53 3NP53/ 3NP43 3NP52/ 3NP42 3NP50
--
--
3NE1 02
3NE1 020-2 3NE1 021-0 3NE1 021-2 3NE1 022-0 3NE1 022-2 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 600 690 690 600 690 690 690 00 80 00 100 00 100 00 125 00 125 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 160 160 200 200 250 250 315 315 350 350 400 450 450 500 500 560 560 630 630 710 710 710 800 800 800 670 850 00 80 00 100 00 98 00 125 00 125 1 1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 160 160 200 200/ 190 250 250/ 235 315 315 350 350 400 450 450 500 500 560 560 630 625 710 690 685 800 750 770 655 820 80 100 101 125 125 160 3NP53/ 160 3NP43 200 200/ 190 250 250/ 235 315 -315 350 350 400 450 450 500 500 560 560 630 625 710 690 685 800 750 770 655 820 --3NP40 70 00 80 00 100 00 98 00 125 00 120 2 2 2 2 2 2 -160 160 200 200 250 250 -315 350 350 400 -425 465 -540 620 600 690 670 -750 710 ---80 100 98 125 120 160 3NP42 76 160 200 200 250 250 -315 350 350 400 -425 465 -540 620 600 650 630 -700 630 ---3NP4376 3NP40 76 00 80 00 100 00 98 00 125 00 120 1 1 1 1 1 1 2 2 3NP43 76 2 2 2 3NP44 76 3 3 3 3 3NP44 76 3 3 3 3 3 3 3 3 3 3 3 3 80 100 98 125 120 ------3NP43 76 2 2 2 2 2 2 ---3NP44 76 3 3 3 -----------------------160 160 200 200 -----160 160 200 200
3NE1 2
3NE1 224-0 3NE1 224-2 3NE1 225-0 3NE1 225-2 3NE1 227-0 3NE1 227-2 3NE1 230-0 3NE1 230-2 160 160 160 160 200 200 190 190 250 250 235 235 315 315 315 315
3NE1 3
3NE1 331-0 3NE1 331-2 3NE1 332-0 3NE1 333-0 3NE1 333-2 3NE1 334-0 3NE1 334-2 350 350 350 350 400 400 450 425 480 450 510 450 425 480 450 510 350 350 350 350 400 400 ---------------------------------
2x 120 3NP54/ 3NP44 2x 120 3NP54 2x 120 3NP54/ 3NP44 2x 120 3NP54 2x 150 3NP54/ 3NP44 2x 150 3NP54 2x 185 2x 185 2x (40x5) 2x (40x5) 2x (40x5) 2x (50x5) 2x (50x5) 2x (50x5) 2x (40x5) 2x (40x8)
3NE1 4
3NE1 435-0 3NE1 435-2 3NE1 436-0 3NE1 436-2 3NE1 437-0 3NE1 437-1 3NE1 437-2 3NE1 438-0 3NE1 438-1 3NE1 438-2 3NE1 447-2 3NE1 448-2 3NP44 70 3 3 3 3 3 -500 500 535 535 520 520 600 570 540 640 600 580 530 630 600 570 540 630 600 580 530 630
3NP44 70 3 3 ----
min Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load
2/8
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
SITOR fuse links Order No. Un V AC BG In A 000 000 000 000 000 000 000 000 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 0 0 0 0 0 0 0 0 2 2 2 2 2 16 20 25 35 40 50 63 80 100 125 160 200 250 315 350 400 450 400 450 500 560 630 710 800 900 32 40 50 63 80 100 125 160 250 315 450 500 710 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.95 0.95 1.0 1.0 1.0 0.95 0.95 0.90 0.90 1.0 1.0 1.0 1.0 1.0 1.0 0.95 0.95 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 WL mm2 1.5 2.5 4 6 10 10 16 25 35 50 70 95 120 3NP52/ 3NP42 min Cu 3NP LV HRC fuse switch disconnectors Add-on units Order No. BG Imax IWL A 3NP35/ 000 16 3NP40 10 000 20 000 25 000 35 000 000 000 000 1 1 1 1 1 2 2 2 2 3 3 3 3 3 3 3 3 3NP52 1 1 1 1 1 1 1 1 3NP53/ 3NP54 40 50 63 80 95 110 140 175 210 285 310 330 360 360 400 450 510 580 630 630 630 32 40 50 63 80 95 120 150 16 20 25 35 40 50 63 80 90 110 140 175 210 280 300 320 340 345 385 450 510 580 630 630 630 27 34 43 54 68 81 102 128 205/ 3NP44 70 210 255/ 265 370/ 380 400 3NP44 70 570 3NP53/ 3NP43 Order No. BG Imax IWL A 3NP50/ 00 16 3NP40 70 00 20 00 25 00 35 00 00 00 00 2 2 2 2 2 40 50 63 80 100 120 150 190 230 270 290 310 330 345 385 430 490 560 590 605 630 32 38 45 59 76 90 115 144 205 260 375 410 540 16 20 25 35 40 50 63 80 95 114 150 190 230 270 290 310 330 345 385 430 490 560 590 605 630 27 32 40 50 65 78 98 125 200 250 360 395 540 Busbar devices Order No. BG Imax IWL A 3NP40 15/ 000 16 3NP40 16 000 20 000 25 000 35 000 000 000 000 3NP42 76 1 1 1 1 1 3NP43 76 2 2 2 2 3NP44 76 3 3 3 3 3 3 3 3 3NP42 76 1 1 1 1 1 1 1 1 3NP44 76 3 3 3 3NP44 76 3 3 40 50 63 80 95 115 150 185 225 285 310 330 360 340 370 410 450 500 510 520 530 32 38 45 59 76 90 115 144 235 280 390 415 480 16 20 25 35 40 50 63 80 90 109 150 185 225 285 310 330 360 340 370 410 450 500 510 520 530 27 32 40 50 65 78 98 125 210 260 370 400 480 ---Order No. BG Imax IWL A 3NP40 75/ 00 16 3NP40 76 00 20 00 25 00 35 00 00 00 00 3NP43 76 2 2 2 2 2 --------------------------40 50 63 80 100 125 160 200 250 -------------------------16 20 25 35 40 50 63 80 95 119 160 200 250 --------------------------
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
3NE1 8
3NE1 813-0 3NE1 814-0 3NE1 815-0 3NE1 803-0 3NE1 802-0 3NE1 817-0 3NE1 818-0 3NE1 820-0 690 690 690 690 690 690 690 690 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 900 800 690 1000 1000 1000 1000 1000 1000 1000 1000
3NE3
3NE3 221 3NE3 222 3NE3 224 3NE3 225 3NE3 227 3NE3 230-0B 3NE3 231 3NE3 232-0B 3NE3 233 3NE3 332-0B 3NE3 333 3NE3 334-0B 3NE3 335 3NE3 336 3NE3 337-8 3NE3 338-8 3NE3 340-8
185 3NP53 240 240 2x 150 240 3NP54 2x 150 2x 150 2x 185 2x 185 2x 200 2x 200 2x 200 6 10 10 16 25 35 50 70
--
3NE4
3NE4 101 3NE4 102 3NE4 117 3NE4 118 3NE4 120 3NE4 121 3NE4 122 3NE4 124
3NE4 327-0B 800 3NE4 330-0B 800 3NE4 333-0B 800 3NE4 334-0B 800 3NE4 337 800
0.85 120 0.85 240 0.85 2x (30x5) 0.85 2x (30x5) 0.95 2x (40x5) 0.95 0.95 0.90 0.95 0.95 4 6 10 16 25
3NP54
2/3 210/ 220 2/3 270/ 285 2/3 400/ 420 3 450 3 600
3NE8
3NE8 015-1 3NE8 003-1 3NE8 017-1 3NE8 018-1 3NE8 020-1 3NE8 021-1 3NE8 022-1 3NE8 024-1 BG = size In = rated current WL = varying load factor 690 690 690 690 690 690 690 690 00 00 00 00 00 25 35 50 63 80 3NP40 70/ 00 25 00 33 3NP50 00 45 00 54 00 68 3NP50/ 00 89 3NP40 70 00 106 00 130 24 31 41 51 65 85 101 124 -------------------------3NP40 75/ 00 25 3NP40 76 00 33 00 45 00 53 00 68 3NP40 75/ 00 85 3NP40 76 00 100 00 125 24 31 41 50 65 81 95 120 --------------------------
--
--
Un = rated voltage
min Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load
Siemens ET B1 T 2007
2/9
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
Load rating of fuse links with SITOR 3KL/3KM LV HRC fuse switch disconnectors
SITOR fuse links Order No. Un V AC BG In A 3 3 3 3 3 3 3 3 3 3 3 3 150 200 250 300 350 400 150 200 250 WL mm2 0.95 70 0.95 95 0.95 120 0.95 185 0.95 240 0.95 240 0.85 70 0.85 95 0.85 120 3KL61 3KL61 3 3 3 3 3 3 3 3 3 3 3 3 min Cu 3KL/3KM switch disconnectors with fuses 3KL add-on devices Order No. BG Imax IWL Order No. BG Imax IWL A 145 138 3KL62 180 171 225 214 255 242 330 314 400 380 135 115 3KL62 180 153 225 191 300 255 425 361 800 800 3 3 3 3 3 3 3 3 3 3 3 3 A 150 143 -190 181 240 228 270 257 345 328 400 380 140 119 -190 162 240 204 315 268 450 383 630 630 ------------3KM busbar devices Order No. BG Imax IWL A --------------------------------------Order No. BG Imax IWL A -------------------------
3NC2 4
3NC2 423-3 3NC2 425-3 3NC2 427-3 3NC2 428-3 3NC2 431-3 3NC2 432-3 500 500 500 500 500 500 660 660 660 660 660 600
3NC8 4
3NC8 423-3 3NC8 425-3 3NC8 427-3 3NC8 431-3 3NC8 434-3 3NC8 444-3
350 0.85 240 500 0.85 2 x 150 1000 0.95 2 x (60 x 6) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 25 35 35 125 125 70 70 95 95 120 120 2x 70 2x 70 2x 95 2x 95 2x 95 3KL55 3KL52
3NE1 0
3NE1 020-2 3NE1 021-0 3NE1 021-2 3NE1 022-0 3NE1 022-2 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 600 690 690 600 690 690 690 00 80 00 100 00 100 00 125 00 125 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 160 160 200 200 250 250 315 315 350 350 400 450 450 500 500 560 560 630 630 710 710 710 800 800 800 670 850 00 80 80 3KL53 00 100 100 00 100 100 00 125 125 00 125 125 1 1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 160 160 200 200 250 245 315 280 160 3KL57 160 200 200 250 245 315 -280 00 80 80 3KM52 00 100 100 00 100 100 00 125 125 00 125 125 2 2 2 2 2 2 --3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 160 160 200 200 250 250 --160 3KM55 160 200 200 250 250 -3KM57 -00 80 00 100 00 100 00 125 00 125 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 ------------160 160 200 200 250 245 315 280 330 300 375 400 325 400 350 ------------80 100 100 125 125 160 160 200 200 250 245 315 280 330 300 375 400 325 400 350 -------------3KM57 3KM53 00 80 00 100 00 100 00 125 00 125 2 2 2 2 2 2 ---------------------160 160 200 200 250 250 ---------------------80 100 100 125 125 160 160 200 200 250 250 ----------------------
3NE1 2
3NE1 224-0 3NE1 224-2 3NE1 225-0 3NE1 225-2 3NE1 227-0 3NE1 227-2 3NE1 230-0 3NE1 230-2
3KL57
--
3NE1 3
3NE1 331-0 3NE1 331-2 3NE1 332-0 3NE1 333-0 3NE1 333-2 3NE1 334-0 3NE1 334-2 3KL57 330 330 3KL61 300 300 375 375 450 450 500 500 560 560 630 615 450 3KL62 450 500 500 560 3KL62 560 630 615 350 350 3KM57 350 350 400 400 450 450 500 500 560 560 630 630 450 500 500 500 560 -560 630 630 --
2x 120 3KL61 2x 120 2x 120 2x 120 2x 150 3KL61 2x 150 2x 185 2x 185 2x (40x5) 2x (40x5) 2x (40x5) 2x (50x5) 2x (50x5) 2x (50x5) 2x (40x5) 2x (40x8)
3NE1 4
3NE1 435-0 3NE1 435-2 3NE1 436-0 3NE1 436-2 3NE1 437-0 3NE1 437-1 3NE1 437-2 3NE1 438-0 3NE1 438-1 3NE1 438-2 3NE1 447-2 3NE1 448-2
630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630
710 710 710 710 700 700 800 800 800 800 760 760 670 670 790 790
min Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load
2/10
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
SITOR fuse links Order No. Un V AC BG In A 000 000 000 000 000 000 000 000 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 0 0 0 0 0 0 0 0 2 2 2 2 2 16 20 25 35 40 50 63 80 100 125 160 200 250 315 350 400 450 400 450 500 560 630 710 800 900 32 40 50 63 80 100 125 160 250 315 450 500 710 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.95 0.95 1.0 1.0 1.0 0.95 0.95 0.90 0.90 1.0 1.0 1.0 1.0 1.0 1.0 0.95 0.95 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 WL mm2 1.5 2.5 4 6 10 10 16 25 35 50 70 95 120 185 240 240 2x 150 240 2x 150 2x 150 2x 185 2x 185 2x 200 2x 200 2x 200 6 10 10 16 25 35 50 70 3KL57 3KL55 3KL50 00 00 00 00 00 00 00 00 1 1 1 1 1 2 2 2 2 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 2 2 2 3 3 min Cu 3KL/3KM switch disconnectors with fuses 3KL... add-on devices A 16 20 25 35 40 50 63 80 90 110 140 175 210 240 265 290 320 340 380 440 500 540 600 630 630 32 40 50 63 80 95 120 150 16 20 25 35 40 50 63 80 3KL52 00 00 00 00 00 00 00 -2 2 2 2 2 ----3 3 3 3 3 3 3 3 ---------3 3 3 3 3 A 16 20 25 35 40 50 63 -95 115 150 180 220 ----360 400 470 530 580 640 720 800 --------16 20 25 35 40 50 63 -3KM50 00 00 00 00 00 00 00 00 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 3KM55 1 1 1 1 1 1 1 1 2 2 2 2 2 3KM... busbar devices A 16 20 25 35 40 50 63 80 90 110 140 175 210 240 265 290 320 290 320 360 400 400 400 400 400 32 40 50 63 80 95 120 150 16 20 25 35 40 50 63 80 3KM52 00 00 00 00 00 00 00 -2 2 2 2 2 --------------------------A 16 20 25 35 40 50 63 -95 115 150 180 220 -------------------------16 20 25 35 40 50 63 -90 109 150 180 220 -------------------------Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL Order No. BG Imax IWL
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
3NE1 8
3NE1 813-0 3NE1 814-0 3NE1 815-0 3NE1 803-0 3NE1 802-0 3NE1 817-0 3NE1 818-0 3NE1 820-0 690 690 690 690 690 690 690 690 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 900 800 690 1000 1000 1000 1000 1000 1000 1000 1000
3KL52 3KL55
--
3KM52
--
3NE3
3NE3 221 3NE3 222 3NE3 224 3NE3 225 3NE3 227 3NE3 230-0B 3NE3 231 3NE3 232-0B 3NE3 233 3NE3 332-0B 3NE3 333 3NE3 334-0B 3NE3 335 3NE3 336 3NE3 337-8 3NE3 338-8 3NE3 340-8 86 3KL57 105 140 175 210 228 -252 261 288 340 3KL62 380 440 500 540 600 630 630 27 34 43 54 68 81 102 128 90 3KM55 109 150 180 220 ----3KM57 86 3KM57 105 140 175 210 228 -252 261 288 290 -320 360 400 400 400 400 400 27 34 43 54 68 81 102 128
3KL57
3KL61
360 3KM57 400 470 530 580 640 680 750 ---------
3NE4
3NE4 101 3NE4 102 3NE4 117 3NE4 118 3NE4 120 3NE4 121 3NE4 122 3NE4 124
3NE4 327-0B 800 3NE4 330-0B 800 3NE4 333-0B 800 3NE4 334-0B 800 3NE4 337 800
0.85 120 0.85 240 0.85 2x (30x5) 0.85 2x (30x5) 0.95 2x (40x5) 0.95 0.95 0.90 0.95 0.95 4 6 10 16 25
175 149 3KL61 230 196 340 289 425 361 3KL62 600 570
200 170 3KM57 260 221 370 315 450 375 630 600
175 149 -230 196 340 289 380 323 400 400
3KL61
3NE8 0
3NE8 015-1 3NE8 003-1 3NE8 017-1 3NE8 018-1 3NE8 020-1 3NE8 021-1 3NE8 022-1 3NE8 024-1 BG = size In = rated current WL = varying load factor 690 690 690 690 690 690 690 690 00 00 00 00 00 25 35 50 63 80 3KL50 00 00 00 00 00 25 33 45 54 68 24 31 41 51 65 3KL52 00 00 00 00 00 25 35 50 60 68 24 33 45 57 65 3KM50 00 00 00 00 00 25 33 45 54 68 24 31 41 51 65 3KM52 00 00 00 00 00 25 35 50 60 68 24 33 45 57 65 85 101 124
3KL52 3KL52
3KL53
3KM52
3KM53
00 89 00 106 00 130
Un = rated voltage
min Cu = required conductor cross-section Cu Imax = maximum permissible current IWL = maximum permissible current with varying load
Siemens ET B1 T 2007
2/11
Semiconductor Fuses
LV HRC SITOR Fuse Links
Application information
Standards The SITOR fuse links comply with the following standards: IEC 60269-4 EN 60269-4 If noted in the selection and ordering data and characteristic curves, the SITOR fuse links also comply with the following standards and regulations: IEC 60269-2-1 DIN VDE 0636-201 (for installation in LV HRC fuse bases according to VDE 0636/201, as well as in fuse switch disconnectors and switch disconnectors with fuses) u The following SITOR fuse links and LV HRC fuse bases are also u recognized:
Series 3NC1 0.., 3NC1 4.. 3NC2 2.., 3NE1 ... 3NE3 2.., 3NE3 3.. 3NE4 1.., 3NE8 0..-1 3NE8 7..-1 3NC1 038-., 3NC1 09. 3NC1 49., , 3NC2 29. 3NH3 030, 3NH3 120 3NH3 230, 3NH3 330 3NH3 430 Registration number JFHR2 Reference E167357
I More information
Environment-friendly recycling In 1995, seven German manufacturers of LV HRC/HV HRC fuse links founded a non-profit association.
NH
HH
The objective is to provide a useful recycling option for used fuse links and determine an acceptable disposal concept that meets all the requirements of modern environment protection. Used fuse links are sorted according to product type and are accepted back without packaging for recycling, melted down and the recovered materials are fed back into the material cycle. According to the regulations, statutes and articles of the association, any surplus from the recycling process is donated to a university in order to encourage research in the area of fuse link technology. For further information, please visit our Web site at: http://www.nh-hh-recycling.de Disclaimer The products described here were developed as part of an overall plant or machine to perform safety-related functions. A complete failsafe system usually contains sensors, evaluation units, signaling devices and concepts for failsafe disconnection. It is the responsibility of the manufacturer of a plant or machine to ensure the correct overall function. Siemens AG, its branches and affiliated companies (hereafter "Siemens"), is not in a position to guarantee the function of an overall plant or machine that was not designed by Siemens. Siemens can accept no liability for recommendations, either explicit or implicit, contained in the following description. Furthermore, no warranty or liability claims above and beyond those provided for in the Siemens General Terms and Conditions can be derived from the description. Caution Fuses must always be fitted by a qualified technician.
IZLT2 IZLT2
E220063 E171267
CCC The following SITOR fuse links have the Chinese certification CCC: 3NE1 0..-0 3NE1 8..-0 3NE1 2..-0 3NE3 2.. 3NE3 3.. IEC 60269-4-1 DIN VDE 0636-401 (for screwing onto busbar). SITOR fuse links of size 1 to 3 with gauge 110 mm are also suitable for installation in LV HRC fuse bases according to IEC 60269-2-1 and in fuse switch disconnectors and switch disconnectors with fuses. All SITOR fuse links with rated voltage Un 1000 V are CE-marked according to the low-voltage Directive 73/23/EWG. The CE marking confirms conformance of the products with the requirements of the directive.
2/12
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 500 V AC
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Varying load factor WL Weight approx. Accessories Fuse base, 1-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses
1)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
3NC2 423 3NC2 423-3 gR V AC 500 A A2s A2s K W kg 1501) 7000 33000 26 35 0.85 0.95 3NH3 430 3NX1 011 3NP54 3KL61 30-1.B0
Cooling air speed 1 m/s. In the case of natural air cooling, reduction of 5 %.
Cladding dimensions and grip lugs according to IEC 60269-2-1; but blade slotted according to IEC 60269-4-1.
Siemens ET B1 T 2007
2/13
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 500 V AC
I Characteristic curves
Series 3NC2 4.. Size: Operational class: Rated voltage: Rated current:
3 gR or aR 500 V AC 150 ... 400 A
10 4 6 4
10 5 6 4
[s ]
[A ]
2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4
p
Let-through current
vs
10 4 6 4
4 0 0 3 5 0 3 0 0 2 5 0 2 0 0 1 5 0 A A A A A
2 0 0 A 1 5 0 A
3 0 0 A 2 5 0 A
4 0 0 A 3 5 0 A
10 3 10 3
8 10 4
8 10 5
p
[A ]
6 [A ]
8 10 4
1400 1200
Correction factor
0.8
0.6
0.4
200 0
200
800
2/14
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 600 V AC
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2t
s
1 2 3 4 5 6 7
Breaking I2t value I2tA at Un Power dissipation at In1) Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses
1)
Temperature rise and power dissipation for operation in LV HRC fuse base.
8 9 10 11 12 13 14 15 16 17
Siemens ET B1 T 2007
2/15
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 600 V AC
I Characteristic curves
Series 3NE1 437-1, 3NE1 438-1 Size: 3 Operational class: gR Rated voltage: 600 V AC Rated current: 710 ... 800 A Time/current characteristics diagram
6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2 4
p
I2_10835
10 4
10 5
[s ]
vs
Let-through current
[A ]
8 0 0 A
4
7 1 0 A
8 0 0 A 7 1 0 A
10 4 10 3
8 10 4
8 10 5
p
[A ]
[A ]
6 8 10 5
Correction factor
0.8
0.6
0.4
0.2 0 100 200 300 400 500 600 700 Recovery voltage w [ V ] 800
100
200
800
2/16
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 660 V AC
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Varying load factor WL Weight approx. Accessories Fuse base, 1-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses
1)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
3NC8 423 3NC8 423-3 gR V AC 660 A A2s A2s K W kg 1501) 1100 17600 33 40 0.85 0.95 3NH3 430 3NX1 011 3NP54
3KL61 30-1AB0
Cooling air speed 1 m/s. In the case of natural air cooling, reduction of 5 %.
Cladding dimensions and grip lugs according to IEC 60269-2-1; but blade slotted according to IEC 602269-4-1.
Siemens ET B1 T 2007
2/17
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 660 V AC
I Characteristic curves
Series 3NC8 4.. Size: Operational class: Rated voltage: Rated current: 3
gR or aR 660 V AC 150 ... 1000 A
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2 4
p
10 5 6 4
vs
[A]
[s ]
Let-through current
4 0 0 A
3 5 0 A 3 0 0 A 2 5 0 A 2 0 0 A 1 5 0 A
10 4 6 4
2 1 0 0 0 A 5 0 3 5 2 2 0 A 0 A 5 0 A 0 0 A 1 5 0 A
10 3 10 2
6 8 10 3
6 8 10 4
6 8 10 5
p
[A]
[A ]
6 8 10 5
0.8
1 0 0 0 A
Correction factor
1 0 0 0 A 1 5 0 ... 5 0 0 A
0.6
1 5 0 ... 5 0 0 A
0.4
0.2 0 100 200 300 400 500 600 700 Recovery voltage w [ V ] 800
200 0
200
800
2/18
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC/700 V DC
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2t
s
1 2 3 4 5
3NE8 715-1
3NE8 701-1
3NE8 702-1
3NE8 717-1
3NE8 718-1 aR
690 V AC/700 V DC 20 12 83 40 7 0.9 according to UL 248-13 9 25 19 140 32 40 285 45 10 40 69 490 55 12 50 115 815 60 15 63 215 1550 70 16 0.95
Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Varying load factor WL Certification Weight approx. Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Varying load factor WL Certification Weight approx.
kg
0.13 3NE8 720-1 aR 3NE8 721-1 3NE8 722-1 3NE8 724-1 3NE8 725-1 3NE8 727-1 3NE8 731-1
V A A2s A2s K W
690 V AC/700 V DC 80 380 2700 80 18 0.9 100 695 4950 75 19 0.95 125 1250 9100 80 23 160 2350 17000 100 31 0.9 200 4200 30000 120 36 250 7750 55000 125 42 315 12000 85500 150 54 0.85
6 7 8 9 10 11 12 13 14 15 16 17
Siemens ET B1 T 2007
2/19
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC/700 V DC
I Characteristic curves
Series 3NE8 71.-1, 3NE8 70.-1 Size: 000 Operational class: gR or aR Rated voltage: AC 690 V/ 700 V DC Rated current: 20 ... 63 A Time/current characteristics diagram
I2_10813
10 4 6 4
vs
10 4 6 4 6 3 A 5 0 A 4 0 A 3 2 A 2 5 A 2 0 A
2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 1 2 4 6 8 10 2 2 4
p
Let-through current
2 0 A 2 5 A 3 2 A 4 0 A 5 0 A 6 3 A
[A]
[s ]
10 3 6 4
10 2 10 2
[A]
6 [A ]
8 10 3
0.8
0.6
0.4
0.2 0 100 200 300 400 500 600 700 Recovery voltage w [ V ] 800
Correction factor
100
200
800
2/20
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC/700 V DC
Series 3NE8 72.-1, 3NE8 731-1 Size: 000 Operational class: aR Rated voltage: 690 V AC/ 700 V DC Rated current: 80 ... 315 A Time/current characteristics diagram
I2_10817
1 2 3 4 5 6 7
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 1 2 4 6 8 10 2 2 4 6 8 10 3 2
p
10 5 6 4
vs
[A]
[s ]
Let-through current
10 4 6 4
2 3 1 5 A 2 5 0 A 2 0 0 A 1 6 0 A 1 2 5 A 1 0 0 A 8 0 A
10 3 6 10 2
6 8 10 3
6 8 10 4
6 8 10 5
p
[A]
8 9 10
4 6 8 10 4 [A ]
11 12 13 14
0.8
0.6
0.4
Correction factor
0.2 0 100 200 300 400 500 600 700 Recovery voltage w [ V ]
200 0
800
100
200
800
15 16 17
Siemens ET B1 T 2007
2/21
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gS
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In1) Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole 3-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses 3NH3 030 3NH4 030 3NX1 011 3NP40/3NP50 3KL50 30-1.B00 3KM50 30-1.B00 3KL52 301.B00 3KM52 301.B00 kg A A2s A2s W 3NE1 813-0 3NE1 814-0 3NE1 815-0 3NE1 803-0 3NE1 802-0 3NE1 817-0 3NE1 818-0 3NE1 820-0 gS V AC 690 16 18 200 25 3.0 1.0 according to UL 248-13 0.13 3.5 20 41 430 25 74 780 30 4.0 35 166 1700 35 5.0 40 295 3000 30 50 461 4400 35 6.0 63 903 9000 40 7.0 8.0 80 1843 18000
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In1) Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole 3-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses kg A A2s A2s W
3NE1 021-0 3NE1 022-0 3NE1 224-0 3NE1 225-0 3NE1 227-0 3NE1 230-0 gS V AC 690 100 3100 33000 36 10 1.0 according to UL 248-13 0.20 3NH3 030 3NH4 030 3NX1 011 3NP40 3NP50 3KL52 30-1.B00 3KM52 30-1.B00 3NP42 3NP52 3KL55 30-1.B00 3KM55 30-1.B00 3NP53 3KL57 30-1.B00 3KM57 30-1.B00 0.55 3NH3 230 3NH4 230 3NH3 330 3NH4 330 125 6000 63000 40 11 160 7400 60000 60 24 200 14500 100000 65 27 250 29500 200000 75 30 315 46100 310000 80 38
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In1) Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses kg A A2s A2s W
3NE1 331-0 3NE1 332-0 3NE1 333-0 3NE1 334-0 3NE1 435-0 3NE1 436-0 3NE1 437-0 3NE1 438-0 gS V AC 690 350 58000 430000 75 42 1.0 according to UL 248-13 0.7 3NH3 330 3NX1 011 3NP53 3KL57 30-1.B00 3KM57 30-1.B00 3NP54 3KL61 30-1AB0 3KL62 3NH3 430 0.95 400 84000 590000 85 45 53 450 104000 750000 500 149000 950000 90 56 560 215000 1700000 65 50 630 293000 2350000 70 55 710 437000 3400000 68 60 800 723000 5000000 70 59
1)
Temperature rise and power dissipation for operation in LV HRC fuse base.
2/22
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
gS gS gS gS
3 3 3 3
gS gS gS gS
3 3 3 3
gS gS gS gS
3 3 3 3
Siemens ET B1 T 2007
2/23
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gS
I Characteristic curves
Series 3NE1 8..-0 Size: Operational class: Rated voltage: Rated current: 000
gS 690 V AC 16 ... 80 A
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 1 2 4 6 8 10 2 2 4 6 8 10 3 2
p
10 4 6 4
[s ]
vs
Let-through current
[A]
8 0 A 6 3 A 5 0 A 4 0 A 3 5 A 2 5 A 2 0 A 1 6 A
10 3 6 4
10 2 10 2
[A]
4 6 8 10 4 [A ]
Correction factor
0.8
0.6
0.4
0.2 0 100 200 300 400 500 600 700 Recovery voltage w [ V ] 800
100
200
800
2/24
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gS
Series 3NE1 02.-0, 3NE1 2..-0 Size: 00, 1 Operational class: gS Rated voltage: 690 V AC Rated current: 100 ... 315 A Time/current characteristics diagram
I2_10829
1 2 3 4 5 6 7
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4
p vs
10 5 6 4
[A ]
Let-through current
3 1 5 A 2 5 0 A 2 0 0 A 1 6 0 A 1 2 5 A 1 0 0 A
10 4 6 4
A A /1 6 0 A A
10 3 10 3
8 10 4
8 10 5
p
[A ]
8 9 10
8 10 4
11 12 13 14
Correction factor
0.8
3 N E 1 2 ..-0 3 N E 1 0 2 .-0
0.6
0.4
0.2 0 100 200 300 400 500 600 700 Recovery voltage w [ V ] 800
100
200
800
15 16 17
Siemens ET B1 T 2007
2/25
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gS
Series 3NE1 33.-0, 3NE1 43.-0 Size: 2, 3 Operational class: gS Rated voltage: 690 V AC Rated current: 350 ... 800 A Time/current characteristics diagram
I2_10832
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2 4
p
10 5 6 4
Let-through current
8 0 0 7 1 0 6 3 0 5 6 0 5 0 0 4 5 0 4 0 0 3 5 0 A A A A A A A
vs
[A ]
[s ]
10 4 6
8 0 0 A 7 1 0 6 3 0 5 6 5
A A
0 A 0 0 4 5 0 4 0 3 A
A 0 A 5 0 A
10 3 10 3
8 10 4
8 10 5
p
[A ]
[A ]
6 8 10 5
Correction factor
0.8
0.6
0.4
0.2 0 100 200 300 400 500 600 700 Recovery voltage w [ V ] 800
100
200
800
2/26
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gR
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2t
s
1 2 3 4 5 6 7 8 9 10
3NE1 021-2
3NE1 022-2
3NE1 224-2
3NE1 225-2
3NE1 227-2
3NE1 230-2
Breaking I2t value I2tA at Un Power dissipation at In1) Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In1) Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In1) Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses
1)
according to UL 248-13 kg 0.2 3NH3 030 3NX1 011 3NP50 3KL52 3NE1 331-2 gR V AC 690 A A2s A2s W 350 29500 177000 82 44 1.0 according to UL 248-13 kg 0.7 3NH3 230 3NX1 011 3NP53 3KL57 3NE1 435-2 gR V AC A A2s A2s W 690 560 130000 890000 80 60 1.0 according to UL 248-13 kg 1.0 3NH3 340 3NX1 011 3NP54 3KL61 3NP54 3KL62 630 203000 1390000 82 62 670 240000 1640000 90 65 72 710 265000 1818000 800 361000 2475000 95 82 76 850 520000 3640000 3NH3 340 3NX1 011 3NP54 3KL61 3NE1 436-2 3NE1 447-2 3NE1 437-2 3NE1 438-2 3NE1 448-2 450 46100 276500 100 62 65 500 66400 398000 3NE1 333-2 3NE1 334-2 3NP52 3KL55 3NP53 3KL57 0.55 3NH3 230
11 12 13 14 15 16 17
Temperature rise and power dissipation for operation in LV HRC fuse base.
Siemens ET B1 T 2007
2/27
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gR
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole 3-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses 3NH3 030 3NH4 030 3NX1 011 3NP40 3NP50 3KL50 30-1.B00 3KM50 30-1.B00 3KL52 30-1.B00 3KM52 30-1.B00 kg A A2s A2s W 3NE8 015-1 3NE8 003-1 3NE8 017-1 3NE8 018-1 3NE8 020-1 3NE8 021-1 3NE8 022-1 3NE8 024-1 gR V AC 690 25 30 180 35 7 0.95 according to UL 248-13 0.20 35 70 400 45 9 50 120 700 65 14 63 260 1400 70 16 80 450 2400 80 19 100 850 4200 90 22 125 1400 6500 110 28 160 2800 1300 130 38 aR
2/28
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gR
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
gR gR gR gR
3 3 3 3
gR gR gR
3 3 3
gR gR gR gR gR gR
3NE1 435-2 3NE1 436-2 3NE1 447-2 3NE1 437-2 3NE1 438-2 3NE1 448-2
3 3 3 3 3/1 3
00
gR gR gR gR aR aR aR aR
3NE8 015-1 3NE8 003-1 3NE8 017-1 3NE8 018-1 3NE8 020-1 3NE8 021-1 3NE8 022-1 3NE8 024-1
3 3 3 3 3 3 3 3
Siemens ET B1 T 2007
2/29
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gR
I Characteristic curves
Series 3NE1 022-2, 3NE1 2..-2, 3NE1 33.-2 Size: 00, 1 Operational class: gR Rated voltage: 690 V AC Rated current: 125 ... 500 A Time/current characteristics diagram
I2_10839
10 4
Virtual Pre-arcing Time tVS [s]
10 5 6
C
6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 10 3 2 4 6 10 4 2 4
p
10 4 6 4
10 3 6 10 5
10 5
2000
350 A - 500 A
Correction factor 0.8 Peak arc voltage 1600
160...315 A
160 A - 315 A
0.6
80 A - 125 A
1200
80...125 A 350...500 A
800
0.4
0.2
400
0 0 100 200 300 400 500 600 700 800 Recovery voltage
2/30
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gR
Series 3NE1 4..-2 Size: Operational class: Rated voltage: Rated current: 3
gR 690 V AC 560 ... 850 A
1 2 3 4 5 6 7
10 5 6
C
6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 10 3 2 4 6 10 4 2 4
p
10 3
10 4 6 4
10 5
8 9 10
10 5
11 12 13 14
2000
Correction factor
0.8 Peak arc voltage 0 100 200 300 400 500 600 700 800
1600
0.6
1200
0.4
800
0.2
400
0 Recovery voltage
15 16 17
Siemens ET B1 T 2007
2/31
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 690 V AC, operational class gR
Series 3NE8 0..-1 Size: Operational class: Rated voltage: Rated current: 00
gR or aR 690 V AC 25 ... 160 A
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 1 2 4 6 8 10 2 2 4 6 8 10 3 2 4
p
10 4 6 4
[s ]
vs
Let-through current
1 6 0 A 1 2 5 A 1 0 0 A 8 0 A 6 3 A 5 0 A 3 5 A 2 5 A
[A]
10 3 6 4
10 2 10 2
[A]
[A ]
6 8 10 4
2000 1800 Peak arc voltage s [ V ] 0 100 200 300 400 500 600 700 Recovery voltage w [ V ] 800
Correction factor
0.8
0.6
0.4
0.2
2/32
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 800 V AC
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Varying load factor WL Weight approx. Accessories Fuse base, 1-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses 3NH3 330 3NX1 011 3NP53 3KL57 30-1.B00 3KM57 30-1.B00 3NP54 3KL61 3KL62 3NH3 430 kg A A2s A2s W 3NE4 327-0B aR V AC 800 250 3600 29700 175 105 0.85 0.7 315 7400 60700 170 120 450 29400 191000 190 140 500 42500 276000 195 155 0.95 710 142000 923000 170 3NE4 330-0B 3NE4 333-0B 3NE4 334-0B 3NE4 337
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Cladding dimensions and grip lugs according to IEC 60269-2-1; but blade slotted according to IEC 60269-4-1.
Siemens ET B1 T 2007
2/33
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 800 V AC
I Characteristic curves
Series 3NE4 3..-0B, 3NE4 337 Size: 2 Operational class: aR Rated voltage: 800 V AC Rated current: 250 ... 710 A Time/current characteristics diagram
I2_10851
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2 7 1 0 A 5 0 0 A 4 5 0 A 3 1 5 A 2 5 0 A
10 5 6 4
[s ]
[A ]
Let-through current
vs
7 1 0 A 5 0 0 A 4 5 0 A 3 1 5 A 2 5 0 A
10 4 6 4
10 3 10 3
8 10 4
8 10 5
p
[A ]
4 6 8 10 5 [A ]
Correction factor
0.8
4 5 0 A
1600 1400 1200 1000 800 600 400 200 0 0 200 400 600 800 Recovery voltage w [ V ] 1000
0.6
3 1 5 A
0.4
0.2 0 100 200 300 400 500 600 700 Recovery voltage w [ V ]
800
2/34
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole 3-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses 3NH3 120 3NH4 230 3NX1 011 3NP42, 3NP52 3KL55 30-1.B00 3KM55 30-1.B00 kg A A2s A2s W 3NE4 101 gR V AC 1000 32 40 280 45 12 0.9 according to UL 248-13 0.27 40 75 500 50 13 50 120 800 65 16 63 230 1500 78 20 80 450 3000 82 22 100 900 6000 85 24 125 1800 14000 100 30 160 3600 29000 120 35 3NE4 102 3NE4 117 3NE4 118 aR 3NE4 120 3NE4 121 3NE4 122 3NE4 124
1 2 3 4 5 6 7 8 9 10 11
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole 3-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses kg A A2s A2s W
3NE3 222
3NE3 224
3NE3 225
3NE3 227
according to UL 248-13 0.55 3NH3 230 3NH4 230 3NX1 011 3NP42, 3NP52 3KL55 30-1.B00 3KM55 30-1.B00 3NE3 230-0B aR V AC 1000 A A2s A2s W I2t
A
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value at Un
3NE3 231
3NE3 232-0B
3NE3 233
12 13 14 15 16 17
Temperature rise at In (body center) K Power dissipation at In Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses kg
according to UL 248-13 0.55 3NH3 330 3NX1 011 3NP53 3KL57 30-1.B00 3KM57 30-1.B00
Siemens ET B1 T 2007
2/35
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Varying load factor WL Certification Weight approx. Accessories Fuse base, 1-pole Fuse puller Fuse switch disconnectors Switch disconnector with fuses Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Varying load factor WL Weight approx.
1)
3NE3 332-0B 3NE3 333 aR V AC 1000 A A2s A2s W 400 22600 135000 120 85 1.0 according to UL 248-13 kg 0.7 3NH3 430 3NX1 011 3NP54 3KL61 30-1AB0 3NE3 421 aR V AC 1000 A A2s A2s W kg 100 1800 13500 45 25 1.0 1.15 224 7200 54000 140 85 3NE3 626 450 29500 175000 125 90
3NE3 336
3NE3 337-8 3NE3 338-8 3NE3 340-8 900 800 800 184000 850000 140 130 0.95 690 900 223000 1300000 160 165
3KL62 3NE3 430 3NE3 432 3NE3 635 3NE3 434 3NE3 635-6 3NE3 636 3NE3 637 3NE3 637-11)
2/36
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
aR
Mounting dimensions: 130 mm 3 100 224 315 400 450 4505) 500 630 710 Mounting dimensions: 140 mm, M12 screw connection 3 710 aR
4) 5)
aR
3NE3 421 3NE3 626 3NE3 430 3NE3 432 3NE3 635 3NE3 635-6 3NE3 434 3NE3 636 3NE3 637 3NE3 637-1
1.200 1.300 1.241 1.247 1.179 1.184 1.490 1.213 1.190 1.246
3 3 3 3 3 3 3 3 3 3
Cladding dimensions and grip lugs according to IEC 60269-2-1; but blade slotted according to IEC 60269-4-1. Rated voltage 900 V AC. Rated voltage 800 V AC.
Rated voltage 690 V AC. Design according to 3NE6 4.. and 3NE9 4...
Siemens ET B1 T 2007
2/37
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
I Characteristic curves
Series 3NE4 1.. Size: Operational class: Rated voltage: Rated current: 0
gR or aR 1000 V AC 32 ... 160 A
10 4 6 4
10 4 6 4
1 6 0 A 1 2 5 A 1 0 0 A 8 0 A 6 3 A 5 0 A 4 0 A 3 2 A
[s ]
vs
10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 1 2 4 6 8 10 2 2 4 6 8 10 3 2
p
Let-through current
[A]
10 3 6 4
1 6 0 A 1 2 5 A 1 0 0 A 8 0 A 6 3 A 5 0 A 4 0 A 3 2 A
10 2 10 2
[A]
4 [A ]
6 8 10 4
1
A
2500
Correction factor
0.8
2000
1500
0.6
1000
0.4
500 0.2 0 0 200 400 600 Recovery voltage 800 w [V ] 1000 0 200 400 600 800 1000 Recovery voltage w [ V ] 1200
2/38
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
Series 3NE3 22. Size: Operational class: Rated voltage: Rated current: 1
aR 1000 V AC 100 ... 225 A
1 2 3 4 5 6 7
10 4 6 4
2 2 5 0 2 0 0 1 6 0 1 2 5 1 0 0 A A A A A
[s ]
vs
10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 1 2 4 6 8 10 2 2 4 6 8 10 3 2
p
Let-through current
[A]
10 4 6 4
2 10 3 6 4
2 5 0 A 2 0 0 A 1 6 0 A 1 2 5 A 1 0 0 A
10 2 10 2
6 8 10 3
6 8 10 4
6 8 10 5
p
[A]
8 9 10
4 [A ]
6 8 10 4
11 12 13 14
1
A
2500
Correction factor
0.8
2000
1500
0.6
1000
0.4
500 0.2 0 0 200 400 600 Recovery voltage 800 w [V ] 1000 0 200 400 600 800 1000 Recovery voltage w [ V ] 1200
15 16 17
Siemens ET B1 T 2007
2/39
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1000 V AC
Series 3NE3 23. Size: Operational class: Rated voltage: Rated current: 1
aR 1000 V AC 315 ... 450 A
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4
p
10 5 6 4
[s ]
[A ]
Let-through current
vs
10 4 6 4
4 5 0 A 4 0 0 A 3 5 0 A 3 0 0 A
10 3 10 3
8 10 4
8 10 5
p
[A ]
6 [A ]
8 10 4
1
A
2500
Correction factor
0.8
2000
1500
0.6
1000
0.4
500 0.2 0 0 200 400 600 Recovery voltage 800 w [V ] 1000 0 200 400 600 800 1000 Recovery voltage w [ V ] 1200
2/40
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1500 V AC
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Varying load factor WL Weight approx. Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2t
A
1 2 3 4 5 6 7 8
3NE5 424 aR V AC 1500 A A2s A2s W kg 160 7200 54000 75 56 1.0 1.95 3NE5 627 aR V AC 1500 A A2s A s W kg
2
3NE5 426
3NE5 430
3NE5 431
3NE5 633
3NE5 643
at Un
Temperature rise at In (body center) K Power dissipation at In Varying load factor WL Weight approx.
9 10 11 12 13 14 15 16 17
Siemens ET B1 T 2007
2/41
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1500 V AC
I Characteristic curves
Series 3NE5 4.. Size: Operational class: Rated voltage: Rated current: 3
aR 1500 V AC 160 ... 600 A
10 4 6 4
vs
2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2
p
Let-through current
4 5 0 A 3 5 0 A 3 1 5 A 2 2 4 A 1 6 0 A
[A ]
6 4 2 103 10 3
[s ]
[A ]
4 [A ]
6 8 10 5
4000 3600
Peak arc voltage s [ V ]
I201_10873
Correction factor
0.8
0.6
0.4
[V ]
1500
2/42
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 1500 V AC
Series 3NE5 6.. Size: Operational class: Rated voltage: Rated current: 3
aR 1500 V AC 250 ... 600 A
1 2 3 4 5 6 7
10 4 6 4
6 0 0 A
vs
2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2
p
[s ]
Let-through current
[A ]
4 5 0 A
2 5 0 A
104
6 4
4 5 0 A 2 5 0 A 6 0 0 A
103 10 3 2 4 6 8 10 4 2 4 6 8 10 5
p
[A ]
8 9 10
4 [A ]
6 8 10 5
11 12 13 14
4000 3600
Peak arc voltage s [ V ]
I201_10873
Correction factor
0.8
0.6
0.4
[V ]
1500
15 16 17
Siemens ET B1 T 2007
2/43
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 2000 V AC
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Varying load factor WL Weight approx.
1)
3NE7 425 aR V AC 2000 A A2s A2s W kg 200 18400 138000 85 75 1.0 1.95
3NE7 427 3NE7 431 3NE7 432 3NE7 633 3NE7 633-11)
3NE7 648-11)
3NE7 637-11)
2/44
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 2000 V AC
I Characteristic curves
Series 3NE7 4.., 3NE7 6.. Size: 3 Operational class: aR Rated voltage: 2000 V AC Rated current: 200 ... 710 A Time/current characteristics diagram
I2_10878
1 2 3 4 5 6 7
10 4 6 4
10 5 6 4
vs
2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2
p
Let-through current
7 1 0 6 3 0 5 2 5 4 0 0 3 5 0
A A /4 5 0 A A
[s ]
[A ]
2 5 0 A 2 0 0 A
10 4 6
7 1 0 A 6 3 0 A 5 2 5 A 4 5 0 A 4 0 0 A 3 5 0 A 2 5 0 A 2 0 0 A
10 3 10 3
8 10 4
8 10 5
p
[A ]
8 9 10
4 [A ]
6 8 10 5
11
Peak arc voltage
I2_10880
12 13 14
Correction factor
0.8
3200 2800 2400 2000 1600 1200 800 400 0 0 400 800 1200 1600 2000 Recovery voltage w [ V ] 2400
0.6
0.4
ADA94-5029b
0.2
500
2000
15 16 17
Siemens ET B1 T 2007
2/45
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 2500 V AC
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Varying load factor WL Weight approx. kg A A2s A2s W 3NE9 632-1 aR V AC 2500 400 81000 620000 160 205 1.0 2.5 500 170000 1270000 180 235 630 385000 2800000 198 275 3NE9 634-1 3NE9 636-1A
2/46
Siemens ET B1 T 2007
Semiconductor Fuses
LV HRC SITOR Fuse Links
Rated voltage 2500 V AC
I Characteristic curves
Series 3NE9 63. Size: Operational class: Rated voltage: Rated current: 3
aR 2500 V AC 400 ... 630 A
1 2 3 4 5 6 7
10 4 6 4
10 5 6 4
[A ]
vs
2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2
p
Let-through current
6 3 0 A 5 0 0 A 4 0 0 A
[s ]
10 4 6 4
6 3 0 A 5 0 0 A 4 0 0 A
10 3 10 3
8 10 4
8 10 5
p
[A ]
8 9 10
4 [A ]
6 8 10 5
11
Peak arc voltage
I2_10884
12 13 14
0.8
0.6
0.4
0.2
Correction factor
400
800
500
1000
3000
15 16 17
Siemens ET B1 T 2007
2/47
Semiconductor Fuses
LV HRC SITOR Fuse Links
Configuration Aids
I Dimensional drawings
3NC2 4.., 3NC8 4.. 3NC2 4..-3, 3NC8 4..-3 14 18
12 11,5 71,5 140 108 108 71,5 11,5 14 81 60 70 6 10 70 6
I2_11337
11,5 14 81 60 70 10
18
12
18
12
I2 11336
3NE8 7..-1
3NE1 8..-0
15
I2_06713
70
140
8,5
50,3 2,3
53,8 79,9
49,4 2,2
54 78 100
40,5
48
20
21
10
35,8 53,3
10
21 40
35,8 60
I2_11343
3NE1 4..-2
6 30
8,5
53 79
3 2
66,5
73 149
66,5
2,5
73 135
68
73 151
2 ,5
6 8
52
70
7 3
6 52
10
10
60
6 70
I2_07071
40,5 63,5
I2_06715
25 47,5 60 72
10
1 0
60,4 82,1
I2_06717
6 0 ,4 8 2 ,1
2/48
Siemens ET B1 T 2007
6 7 3
I2 _ 1 2 4 2 7
7 3 1 5 1
Semiconductor Fuses
LV HRC SITOR Fuse Links
Configuration Aids
3NE4 3..-0B, 3NE4 337
11,5 14,5 12,5 10,5
3NE4 1..
15 14
1 2 3 4 5 6 7
107,5
141,5
73,5
47
I2_06450
10
10,5 11,5 71 48 60 10
14,5
12,5
58
I2_11338
3NE3 4.., 3NE3 6.., 3NE3 637-1, 3NE5 4.., 3NE5 433-1, 3NE5 6.., 3NE7 4.., 3NE7 6.., 3NE9 63.-1
14 18 12 c
60
30
65 125
8 9 10
f
110
d a
10,5
73 a
c 81 60 70 10 6 10 6 14 18 12
I2_06473a
11 12
b 31 38 c 12.5 19.5
10
d f g
70
I2_11339
3NE3 3.. 3NE3 635-6 Dimensions a b 128 138 208 208 168 255 c 11.5 13 11.5 13 11.5 13 d 91.5 91.5 171.5 171.5 131.5 220
70 81,5 10
13 14 15 16 17
160 170
M10 70 96 109
I2_11340
3NE5 4.., 3NE7 4.., 240 3NE7 6.. 3NE5 433-1, 3NE7 6..-1 3NE5 6.. 3NE9 63.-1 240 200 287
28
Siemens ET B1 T 2007
2/49
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For rectifiers in electrolysis systems
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I t value I ts (tvs = 1 ms) Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Varying load factor WL Weight approx. Type Operational class (IEC 60269) Rated voltage Un Rated current In3) Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Varying load factor WL Weight approx.
1) 2 2
3NC5 8411)
3NC5 8381)
6302) 185000 888000 110 145 1.2 3NE9 450 aR 900 12504) 7104) 100000 620000 80 210 0.9 150 3NE6 437
6002)
170 1.2 3NE9 450-7 600 3NE6 437-7 900 7105) 100000 2480000 105 210 1.0 620000 110 150
12505)
Maximum tightening torque: - M10 thread (with indicator): 40 Nm - M10 capped thread: 50 Nm, depth of screw entry 9 mm - M24 1.5 thread: 60 Nm. Temperature of water-cooled busbar max. +45 C.
Maximum tightening torque: M10 capped thread: 35 Nm, depth of screw entry 9 mm. Cooling air speed 2 m/s. Bottom (cooled) connection max. +60 C, top connection (M10) max. +110 C.
2)
2/50
Siemens ET B1 T 2007
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For rectifiers in electrolysis systems
I Characteristic curves
Series 3NC5 531, 3NC5 8.. Operational class: aR Rated voltage: 800 V AC (350 A, 600 A), 1000 V AC (600 A, 800 A) Rated current: 350 ... 800 A Time/current characteristics diagram
I2_11432
1 2 3 4 5 6 7
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2
p
105 6 4
[s]
[A]
Let-through current
8 0 0 A 6 3 0 A 6 0 0 A 3 5 0 A
vs
104 6 4
3 5 0 A
2 6 0 0 A 6 3 0 A 8 0 0 A 103 10 3 2
[A]
8 9 10
4 6 8 10 5 [A]
11
Peak arc voltage
1800 Peak arc voltage s [ V ] 1600 1400 1200 1000 800 600 400
3 5 0 A 6 3 0 A 6 0 0 A 8 0 0 A
I2_11435
1
A
2000
12 13 14
Correction factor
0.8
6 3 0 A 6 0 0 A 8 0 0 A
0.6
0.4
3 5 0 A
15 16 17
Siemens ET B1 T 2007
2/51
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For rectifiers in electrolysis systems
Series 3NE6 4.., 3NE9 4.. Operational class: aR, gR Rated voltage: 600 V AC (1250 A), 800 V AC (710 A, 1250 A,), 900 V AC (710 A) Rated current: 710 ... 1250 A Time/current characteristics diagrams
I2_11436 I2_11437
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2
p
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2
[s]
vs
vs
[s]
10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 4 6 8 10 5 [A] 10 -3 10 2 2 4 6 8 10 3 2 4 9 0 0 A
1 2 5 0 A
6 8 10 4
2
p
4 6 8 10 5 [A]
2/52
Siemens ET B1 T 2007
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For rectifiers in electrolysis systems
Series 3NE6 4.., 3NE9 4.. Operational class: aR, gR Rated voltage: 600 V AC (1250 A), 800 V AC (710 A, 1250 A), 900 V AC (710 A) Rated current: 710 ... 1250 A Let-through characteristics (current limitation at 50 Hz)
I2_11438
1 2 3 4 5 6 7
105 6 4 7 1 0 A 2
[A]
8 5 0 /9 0 0 /1 2 5 0 A
Let-through current
104 6 4
103 10 3
[A]
8
Peak arc voltage
1800
Peak arc voltage s [ V ]
7 1 0 A 9 0 0 A
1
8 0 0 A 1 2 5 0 A
A
Correction factor
0.8
I2_11440
2000
9 10 11
0.6
7 1 0 A
9 0 0 A
0.4
0.2
200 0 0 200 400 600 Recovery voltage 800 w [V] 1000 0 200 400 600 800 1000 Recovery voltage w [ V ] 1200
12 13 14 15 16 17
Siemens ET B1 T 2007
2/53
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For SITOR thyristor sets
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I t value I ts (tvs = 1 ms) Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Varying load factor WL Weight approx. Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Varying load factor WL Weight approx.
1) 2 2
3NE4 121-5 aR
3NE3 535-51)
3NE4 330-6B1)
3NE4 333-6B1)
3NE4 334-6B1)
3NE4 337-61)
V AC 800 A A2s A2s K W kg 250 3600 29700 175 105 0.85 0.65
2)
Maximum tightening torque: M10 capped thread: 35 Nm, depth of screw entry 9 mm.
Cooling air speed 0.5 m/s. In the case of natural air cooling, reduction of 5 %.
2/54
Siemens ET B1 T 2007
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For SITOR thyristor sets
I Characteristic curves
Series 3NE3 5.5-5, 3NE4 1..-5 Operational class: aR, gR Rated voltage: 800 V AC (170 A), 1000 V AC (50 A, 100 A, 200 A, 450 A) Rated current: 50 ... 450 A Time/current characteristics diagram
I2_11441
1 2 3 4 5 6 7
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 1 2 4 6 8 10 2 2 4 6 8 10 3 2
p
4 2 10 4 6 4 2 10 3 1 7 0 A 2 0 0 A 1 0 0 A 5 0 A
[s]
vs
1 7 0 A 5 0 A 1 0 0 A 2 0 0 A 4 5 0 A
Let-through current
[A]
6 4 2 10 2 10 2
[A]
8 9 10
4 6 8 10 4 [A]
11
Peak arc voltage
1800 Peak arc voltage s [ V ] 1600 1400 1200 1000 800 600 400
1 7 0 A 2 0 0 A
I2_11444
1
A
2000
12 13 14
Correction factor
0.8
1 7 0 A
0.6
5 0 /1 0 0 A 2 0 0 /4 5 0 A
0.4
15 16 17
Siemens ET B1 T 2007
2/55
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For SITOR thyristor sets
Series 3NE4 3..-6B, 3NE4 337-6 Operational class: aR Rated voltage: 800 V AC Rated current: 250 ... 710 A Time/current characteristics diagram
I2_11445
10 4 6 4 2 10 3 6 4 2 10 2 6 4 2 10 1 6 4 2 10 0 6 4 2 10 -1 6 4 2 10 -2 6 4 2 10 -3 10 2 2 4 6 8 10 3 2 4 6 8 10 4 2
p
105 6 4 7 1 0 A 5 0 0 A 4 5 0 A 3 1 5 A 104 6 4 2 5 0 A
[s]
vs
Let-through current
7 1 0 A 5 0 0 A 4 5 0 A 3 1 5 A 2 5 0 A
[A]
103 10 3
[A]
4 6 8 10 5 [A]
Correction factor
0.8
4 5 0 A
0.6
3 1 5 A
0.4
0.2 0 100 200 300 400 500 600 700 Recovery voltage w [ V ] 800
2/56
Siemens ET B1 T 2007
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For railway supply rectifiers
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2t
s
1 2 3 4 5
3NC7 331-2
Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Varying load factor WL Weight approx.
6 7 8 9 10 11 12 13 14 15 16 17
Siemens ET B1 T 2007
2/57
Semiconductor Fuses
SITOR Fuse Links for Special Applications
For railway supply rectifiers
I Characteristic curves
Series 3NC7 3..-2 Operational class: Rated voltage: Rated current: aR 680 V AC 250 A, 350 A Let-through characteristics (current limitation at 50 Hz)
I2_11449 I2_11450
105 6 4
3 5 0 A 2 5 0 A
[s]
vs
Let-through current
[A]
104 6 4
2 5 0 A
3 5 0 A
103 10 3
[A]
4 6 8 10 5 [A]
Correction factor
0.8
0.6
0.4
0.2 0 100 200 300 400 500 600 700 Recovery voltage w [ V ] 800
2/58
Siemens ET B1 T 2007
Semiconductor Fuses
SITOR Fuse Links for Special Applications
Configuration Aids
I Dimensional drawings
3NC5 531
M10
I2_11369
1 2 3 4 5 6 7
3NC5 8..
11
I2_11370
40 M24
SW41
0,3 91
9 24,5
M10
SW41
M10
b a
73
Type 3NC5 838, 3NC5 841 3NC5 844 3NE6 4.., 3NE9 4..,
10 10 M10
70
70 81,5
b a
I2_11371
100 125
M10
50 28
50
Type 3NE6 437, 3NE9 440-6, 3NE9 450 3NE6 444 3NE3 5..-5
55 10,5
Dimensions a 89 b 76
70 81,5 75,5 83
I2_11372
8 9 10
20
99
M10
73 82,5
60
76 77
I2_11374
60
20
11 12 13 14
I2_11376
60
I2_11373
3NE4 1..-5
47 30
I2_11375
3NC7 3..-2
66 62 12,5 68
53 54
10,5 119
10
10,5
52 57
26 40
10,4
57
7 30 57
79
15 16 17
Siemens ET B1 T 2007
2/59
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
I Overview
Load rating of SITOR cylindrical fuses without strikers in fuse holders/fuse switch disconnectors/fuse disconnectors1)2)
For SITOR Rated fuse links voltage Rated Required Cylindrical fuse bases current conductor crosssection 1-pole 2-pole Cu Type Imax Type In A 3 6 8 10 12 16 20 25 32 1 2 3 4 5 6 10 15 20 25 30 32 40 50 20 25 32 40 50 63 80 100 mm2 1 1 1 1.5 1.5 2.5 2.5 4 6 1 1 1 1 1 1 1.5 1.5 2.5 4 6 6 10 10 2.5 4 6 10 10 16 25 35 3NC2 258-1 3NC1 451-1 3NC1 038-1 A 3 6 8 10 12 16 20 25 32 1 2 3 4 5 6 10 15 20 25 30 32 40 50 20 25 32 40 50 63 80 100 3NC2 291 3NC1 038-2 / 2 3NC1 038-1 Fuse holders/fuse switch disconnectors/ fuse disconnectors1) 3-pole Imax Type A 3 6 8 10 12 16 20 24 28 3NC1 038-3 / 3 3NC1 038-1 1-pole Type 2-pole Imax Type A 3 6 8 10 12 16 20 24 28 3NC1 491 3NC1 091 3 6 8 10 12 16 20 25 30 1 2 3 4 5 6 10 15 20 25 28 31 38 48 20 25 32 40 50 60 74 95 3NC2 292 / 2 3NC2 291 3NC1 492 / 2 3NC1 491 3NC1 092 / 2 3NC1 091 3-pole Imax Type A 3 6 8 10 12 16 20 25 32 1 2 3 4 5 6 10 15 20 24 27 30 37 46 20 25 32 39 48 58 71 90 3NC2 293 / 3 3NC2 291 3NC1 493 / 3 3NC1 491 3NC1 093 / 3 3NC1 091
Imax A
Imax A 3 6 8 10 12 16 20 25 29 1 2 3 4 5 6 10 15 20 23 25 30 36 44 20 25 32 38 46 56 69 85
V AC
Size 10 x 38
3NC1 003 600 3NC1 006 3NC1 008 3NC1 010 3NC1 012 3NC1 016 3NC1 020 3NC1 025 3NC1 032
Size 14 x 51
3NC1 401 660 3NC1 402 3NC1 403 3NC1 404 3NC1 405 690 3NC1 406 3NC1 410 3NC1 415 3NC1 420 3NC1 425 3NC1 430 3NC1 432 3NC1 440 3NC1 450
Size 22 x 58
3NC2 220 690 3NC2 225 3NC2 232 3NC2 240 3NC2 250 3NC2 263 3NC2 280 3NC2 200 600
Fuse tongs: 3NC1 000 Load rating of SITOR cylindrical fuses with strikers in fuse holders/fuse switch disconnectors/fuse disconnectors1)2)
For SITOR fuse links Rated voltage Rated current Required conductor cross-section In V AC A 10 15 20 25 30 32 40 50 690 20 25 32 40 50 63 600 80 100 Cu mm2 1.5 1.5 2.5 4 6 6 10 10 2.5 4 6 10 10 16 25 35
2)
Fuse holders/fuse switch disconnectors/fuse disconnectors1) 1-pole Type 2-pole Type 3-pole Type
Imax A
Imax A
Imax A
Size 14 x 51
3NC1 410-5 690 3NC1 491
10 15 20 25 30 32 38 48
10 15 20 25 30 32 35 46
10 15 20 25 30 31 34 44
3NC1 450-5
Size 22 x 58
3NC2 220-5 3NC2 291
20 25 32 40 45 59 71 94
20 25 31 39 43 55 69 90
20 25 30 37 42 52 68 85
3NC2 200-5
1)
Fuse holders according to IEC 60269-3, UL 512, fuse switch disconnectors (10 x 38, 14 x 51) according to IEC 60947-3, fuse disconnectors (22 x 58) according to IEC 60947-3
The values Imax apply for "stand-alone operation". If several devices are butt-mounted and/or subject to unfavorable cooling conditions, these values may be reduced still further.
2/60
Siemens ET B1 T 2007
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
I Technical specifications
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2t
s
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
3NC1 003 3NC1 006 3NC1 008 3NC1 010 3NC1 012 3NC1 016 3NC1 020 3NC1 025 3NC1 032 aR V A (tvs = 1 ms) A s A2s K W kg
2
600 V AC/400 V DC 3 3 8 30 1.2 0.01 3NC1 401 3NC1 402 3NC1 403 3NC1 404 3NC1 405 3NC1 406 3NC1 410 aR 1.5 6 4 20 8 6 30 25 2 10 9 60 40 2.5 12 15 110 50 3 16 25 150 60 3.5 20 34 200 80 4.8 25 60 250 90 6 32 95 500 110 7.5
Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Weight approx. Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Certification Weight approx. Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Certification Weight approx. Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Temperature rise at In (body center) Power dissipation at In Certification Weight approx.
V A A2s A2s K W kg
according to UL 248-13
3NC1 415 3NC1 420 3NC1 425 3NC1 430 3NC1 432 3NC1 440 3NC1 450 aR V A A2s A2s K W kg 690 V AC/700 V DC 15 10 75 60 5.5 0.02 3NC2 220 3NC2 225 3NC2 232 3NC2 240 3NC2 250 3NC2 263 3NC2 280 3NC2 200 aR V A A2s A2s K W kg 690 V AC/700 V DC 20 34 220 40 4.6 0.06 25 50 300 50 5.6 32 80 450 65 7 40 100 700 80 8.5 50 185 1350 90 9.5 63 310 2600 100 11 80 620 5500 110 13.5 16 600 V AC/700 V DC 100 1250 8000 20 26 120 70 6 25 44 250 80 7 9 7.6 30 58 300 32 95 700 40 110 900 100 8 50 220 1800 110 9
according to UL 248-13
according to UL 248-13
Siemens ET B1 T 2007
2/61
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Certification Weight approx. Type Operational class (IEC 60269) Rated voltage Un Rated current In Melting I2t value I2ts (tvs = 1 ms) Breaking I2t value I2tA at Un Power dissipation at In Certification Weight approx.
1)
3NC1 410-5 3NC1 415-5 3NC1 420-5 3NC1 425-5 3NC1 430-5 3NC1 432-5 3NC1 440-5 3NC1 450-5 aR V A A2s A2s W kg 690 AC/700 DC1) 10 3.6 90 50 4 0.02 3NC2 220-5 3NC2 225-5 3NC2 232-5 3NC2 240-5 3NC2 250-5 3NC2 263-5 3NC2 280-5 3NC2 200-5 aR V A A2s A2s W kg 690 AC/700 DC1) 20 19 240 40 5 0.06 25 34 350 50 6 32 54 500 65 8 40 68 800 80 9 50 135 1500 90 9.5 63 280 3000 100 11 80 600 6000 110 13.5 600 AC/700 DC1) 100 1100 8500 110 16 15 9 100 60 5.5 20 26 500 70 6 25 47 400 80 7 30 58 500 80 9 32 68 600 80 7.6 40 84 900 100 8 50 200 2000 110 9
according to UL 248-13
according to UL 248-13
UL recognized
Fuse bases
Sizes Rated voltage Rated current In V AC V DC A 10 x 38 600 600 32 14 x 51 690 690 50 100 22 x 58
Rated voltage Rated current In Max. power dissipation of fuse link1) Feeder terminals Operational class according to IEC 60947-3 Rated conditional short-circuit current At 400 V Approvals
1)
V AC A W mm2
690 32 3 (6 mm2) 4.3 (10 mm2) 1.5 ... 25 22B/32 A/400 V AC 22B/10 A/690 V AC
kA
These devices have been specially developed for the application of SITOR fuse links with regard to heat tolerance with heat dissipation and are therefore not recommended for standard applications.
2/62
Siemens ET B1 T 2007
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
690/700
600/700 690/700
600/700
Siemens ET B1 T 2007
2/63
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
I Accessories
Size Version Order No. Weight 1 unit approx. kg PS*/ P. unit Unit(s)
14 x 51
22 x 58
3NC1 491-5
14 x 51 22 x 58
Fuse tongs
10 x 38, 14 x 51, 22 x 58
For dimensional drawings, see pages 2/71 and 2/72. For busbars, see chapter "Busbars for modular installation devices".
1)
Fuse holders according to IEC 60269-3, UL 512, fuse switch disconnectors (10 x 38, 14 x 51) according to IEC 60947-3, fuse disconnectors (22 x 58) according to IEC 60947-3 The cylindrical fuse bases can be modularly expanded to make multi-pole bases.
2)
2/64
Siemens ET B1 T 2007
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
I Characteristic curves
Series 3NC1 0 Size: Operational class: Rated voltage: Rated current: 10 mm 38 mm aR 600 V AC/400 V DC 3 ... 32 A Let-through characteristics (current limitation at 50 Hz)
I2_11453 I2_11454
1 2 3 4 5 6 7 8 9 10
2 10 3 6 4 2 10 2 6 4 2 10 1
32 A 25 A 20 A 16 A
3A 6A 8A 10 A 12 A 16 A 20 A 25 A 32 A
12 A 10 A 8A 6A 3A
10 1
6 10 2
10 3
11
Peak arc voltage
1200 Peak arc voltage
I2_11456
1600
12 13 14
Correction factor
0,8
0,6
800
0,4
400 0,2
0 0 100 200 300 400 500 600 700 800 Recovery voltage
15 16 17
Siemens ET B1 T 2007
2/65
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
Series 3NC1 40, 3NC1 41 Size: 14 mm 51 mm Operational class: aR Rated voltage: 660 V AC/700 V DC (1 ... 4 A); 690 V AC/700 V DC (5 ... 50 A) Rated current: 1 ... 10 A Time/current characteristics diagram
I2_11459
10 A 5A
1A 2A 3A 4A 5A 6A 10 A
10 1
6 10 2
4 6 10 5
10 3
1600
Correction factor
0,8
660 V 690 V
1200 Peak arc voltage 0 100 200 300 400 500 600 700 800
0,6
0,4
800
0,2
400
2/66
Siemens ET B1 T 2007
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
Series 3NC1 415, 3NC1 42., 3NC1 440, 3NC1 450 Size: 14 mm 51 mm Operational class: aR Rated voltage: 690 V AC/700 V DC Rated current: 15 ... 50 A Time/current characteristics diagram
I2_11463
1 2 3 4 5 6 7 8 9 10
2 10 3 6 4 2 10 2 6 4 2 10 1
50 A 40 A 32 A 30 A
25 A 20 A 15 A
15 A 20 A 25 A 30 A 32 A 40 A 50 A
10 1
6 10 2
10 3
11 12 13 14
1600
Correction factor
0,8 1200 0,6 Peak arc voltage 0 100 200 300 400 500 600 700 800
0,4
800
0,2
400
15 16 17
Siemens ET B1 T 2007
2/67
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
Series 3NC2 2 Size: Operational class: Rated voltage: Rated current: 22 mm 58 mm aR 690 V AC/700 V DC (20 ... 80 A); 600 V AC/700 V DC (100 A) 20 ... 100 A Let-through characteristics (current limitation at 50 Hz)
I2_11470
100 A 80 A 63 A 50 A
2 10 3 6 4 2 10 2 6 4 2
40 A 32 A 25 A 20 A
20 A 25 A 32 A 40 A 50 A 63 A 80 A 100 A
10 1
10 1
4 6
10 2
6 10 5
10 4
600 V
Correction factor 0,8 Peak arc voltage
0,6
690 V
0,4
0,2 200 0 0 100 200 300 400 500 600 700 800 Recovery voltage 0 0 200 400 600 Recovery voltage 800
2/68
Siemens ET B1 T 2007
I2_11471
10 4
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
3NC1 4..-5 series with striking pin Size: 14 mm 51 mm Operational class: aR Rated voltage: 690 V AC/700 V DC Rated current: 10 ... 50 A Time/current characteristics diagram
I2_13410
1 2 3 4 5 6 7
10 4 6 4 Let-through current
C
2 10 3 6 4 2 10 2 6 4 2 10 1
50 A 40 A 32 A 30 A
10 A 15 A 20 A 25 A 30 A 32 A 40 A 50 A
25 A 20 A 15 A 10 A
10 1
10 2
6 10 3
6 10 4
2
p
6 10 5
8 9 10
10 3
11
Correction factor kA for breaking I2t value
I2_13412
12 13 14
Correction factor
0,8 Peak arc voltage 0 100 200 300 400 500 600 700 800
0,6
0,4
Recovery voltage
800
15 16 17
Siemens ET B1 T 2007
2/69
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
3NC2 2..-5 series with striking pin Size: 22 mm 58 mm Operational class: aR Rated voltage: 690 V AC/700 V DC (20 ... 80 A); 600 V AC/700 V DC (100 A) Rated current: 20 ... 100 A Time/current characteristics diagram
I2_13414
10 4 6 4 Let-through current
C
2 10 3 6 4 2 10 2 6 4 2 10 1
20 A 25 A 32 A 40 A 50 A 63 A 80 A 100 A
40 A 32 A 25 A 20 A
10 1
10 2
4
p
6 10 5
10 4
Correction factor
600 V
0,6
690 V
0,4
Recovery voltage
800
2/70
Siemens ET B1 T 2007
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
I Dimensional drawings
Cylindrical fuse links
3NC1 0
10,2
I2_11377
1 2 3 4 5 6 7 8 9
3NC2 2
I2_11380
9,5 38
16 58
3NC1 4
14,3
I2_11379
10 51
18
36
54
37 49 58
3NC1 49.
I2_11383a
45 81
45 92 96
22,2
10
27 54 81 7 43 49 69
11 12
45
3NC2 29.
I2_11384a
13 14 15 16 17
Siemens ET B1 T 2007
36
1)
72
108
43
70
Fuse holders according to IEC 60269-3, UL 512, fuse switch disconnectors (10 x 38, 14 x 51) according to IEC 60947-3, fuse disconnectors (22 x 58) according to IEC 60947-3
112 118
2/71
Semiconductor Fuses
SITOR Cylindrical Fuse Links
SITOR cylindrical fuse links
Cylindrical fuse holders/cylindrical fuse switch disconnectors/cylindrical fuse disconnectors1) 3NC1 491-5 3NC2 291-5
49 43 69
36
70 43
27
45 92 96
45
122
112 118
I2_12845
I2_12844
28
24
24
21,5
20 41
20 20 60,5
26
3NC1 451-1
I2_11386
76
24
50 50,5
3NC2 258-1
I2_11387
33
1)
66,2 66,5
Fuse holders according to IEC 60269-3, UL 512, fuse switch disconnectors (14 x 51 according to IEC 60947-3), fuse disconnectors (22 x 58) according to IEC 60947-3
2/72
Siemens ET B1 T 2007
110,8
126,5
103,5
90
88
28
143
Semiconductor Fuses
SILIZED Fuse Links
NEOZED fuse links SILIZED
I Benefits
There is a comprehensive range of fuse bases and accessories available for users. When using fuse links with higher power loss than standard fuse links, it is essential to comply with the maximum permissible power dissipation of the fuse base. This particularly applies to safety switching devices, such as MINIZED.
1 2 3 4 5 6 7
I Technical specifications
Series 5SE1 NEOZED fuse links SILIZED
Standards Dimensions Operational class Rated voltage Un Rated current In Rated breaking capacity Mounting position Non-interchangeability Resistance to climate Ambient temperature Type Size In A 5SE1 310 5SE1 316 5SE1 320 5SE1 325 5SE1 335 5SE1 350 5SE1 363 D01 D02 10 16 20 25 35 50 63 Pv W 6.9 6.2 8.1 8.2 16.7 12.0 15.5 k 64 61 64 63 100 80 96 C C V AC V DC A kA AC kA DC DIN VDE 0636-301, IEC 60269-3-1, HD 630.3.1 S3, DIN VDE 0680 DIN VDE 0636-301, IEC 60269-3-1, HD 630.3.1 S3 gR 400 250 10 ... 63 50 8 any, but preferably vertical using adapter sleeves up to 45 at 95 % rel. humidity -5 ... +40, humidity 90 % at 20 I2ts 1 ms A2s 30 31 50 120 145 460 845 4 ms A2s 30 34 56 120 182 540 932 I2ta 230 V AC A2s 56 92 146 166 361 1510 3250 400 V AC A2s 73 120 190 215 470 1960 4230
8 9
PS*/ P. unit Unit(s)
10 11 12 13 14 15 16 17
D02
20 25 35 50 63
5SE1 320 5SE1 325 5SE1 335 5SE1 350 5SE1 363
10 10 10 10 10
Siemens ET B1 T 2007
2/73
Semiconductor Fuses
SILIZED Fuse Links
NEOZED fuse links SILIZED
I Characteristic curves
Series 5SE1 3.. Size: Operational class: Rated voltage: Rated current:
D01, D02 gR 400 V AC/250 V DC 10 ... 63 A
1 0
1 0 6 4 2
[A 2 s ]
1 0
5
s 1 0
-1
v s
[s ]
1 0 6 4 2 1 0 6 4 2
s 1 0
-2
s 1 0
-3
s 1 0
- 4
1 0
6 4 2
1 0 6 4 1 0 2
1 0 6 4 2
0
6 3 A 5 0 A 3 5 A 2 5 A
6 4 2 0 A
-1
1 0 6 4 2 1 0
1 0 6 4 2
3 5 A 2 5 A 5 0 A
6 3 A
2 0 A 1 6 A 1 0 A
1
1 0 A
1 6 A
6 4 2
1 0
-2
6 4 2
1 0
0
1 0
1
2 4
8 1 0
2
8 1 0
3
8 1 0
4
e ff
4 [A ]
8 1 0
5
1 0
-3
1 0
1
1 0
2
4
p
6 [A ]
8 1 0
3
1 0 6 4 2 1 0 6 4 2 1 0
2 3
[A ]
6 3 A 5 0 A 1 2 3 5 A 3 2 A 2 0 A 1 6 A 1 0 A
8 1 0
8 1 0
3
8 1 0
4
e ff
4 [A ]
8 1 0
$ Peak short-circuit current with largest DC component % Peak short-circuit current without DC component
2/74
Siemens ET B1 T 2007
Semiconductor Fuses
SILIZED Fuse Links
DIAZED fuse links SILIZED
I Benefits
There is a comprehensive range of fuse bases and accessories available for users. When using fuse links with higher power loss than standard fuse links, it is essential to comply with the maximum permissible power dissipation of the fuse base. This particularly applies to safety switching devices, such as MINIZED.
1 2 3 4 5 6 7
I Technical specifications
DIAZED fuse links SILIZED
Standards Dimensions Operational class Characteristic Rated voltage Un Rated current In Rated breaking capacity Mounting position Non-interchangeability Degree of protection according to IEC 60529 in the distribution board Resistance to climate Ambient temperature C C V AC V DC A DIN VDE 0635, DIN VDE 0636-301, DIN VDE 0680, IEC 60269-3-1, CEE 16, HD 630.3.1 S3 DIN VDE 0636-301, IEC 60269-3-1, HD 630.3.1 S3 gR super quick 500 500 16 ... 100
kA AC 50, 40 kA DC 8, 1.6 any, but preferably vertical due to screw adapter or adapter sleeves IP20 up to 45 at 95 % rel. humidity -5 ... +40, humidity 90 % at 20
8 9 10 11 12 13 14 15 16 17
DIV
R1"
Siemens ET B1 T 2007
2/75
Semiconductor Fuses
SILIZED Fuse Links
DIAZED fuse links SILIZED
I Characteristic curves
Series 5SD4, 5SD5 Size: Operational class: Characteristic: Rated voltage: Rated current: DII, DIII, DIV
gR
super quick 500 V AC/500 V DC 16 ... 100 A Melting I2ts values diagram
I2 _ 0 6 4 2 6 c
6 4 2
5
[s ]
[A 2 s ]
v s
1 0 6 4 2 1 0 6 4 2
1 0
6 4 2
1 0 0 A
3
1 0 6 4 1 0 2
1 0 6 4 2
0
8 0 A 6 3 A 5 0 A
6 4 2 0 A
-1
1 0 6 4 2 1 0
3 5 A 3 0 A 2 5 A 2 0 A
1 0 6 4 2
3 0 A 2 5 A 3 5 A
5 0 A 6 3 A
8 0 A 1 0 0 A
1 6 A
1 6 A
6 4 2
1 0
0
1 0
-1
1 0
-2
1 0
-3
1 0
- 4
1 0
-2
6 4 2
1 0
1 0
0
2 4
8 1 0
1
8 1 0
2
8 1 0
3
e ff
4 [A ]
8 1 0
4
1 0
-3
1 0
1
1 0
2
4
p
[A ]
8 1 0
3
Type
In A
k 63 69 61 65 62 66 84 77 83
I2ts 1 ms A2s 16.2 35.8 48.9 85 135 340 530 980 1950
I2ta 500 V AC A2s 60 139 205 310 539 1250 1890 4200 8450
16 20 25 30 35 50 63 80 100
1 0
4
[A ]
6 4 2 1 0
3
1 2
1 0 0 A 8 0 A 6 3 A 5 0 A 3 5 A 3 0 A 2 5 A 2 0 A 1 6 A 4 2
1 0
2
1 0
2
8 1 0
3
8 1 0
4
8 1 0
e ff
[A ]
$ Peak short-circuit current with largest DC component % Peak short-circuit current without DC component
2/76
Siemens ET B1 T 2007
I2 _ 0 7 0 7 0 b
1 0
Semiconductor Fuses
SILIZED Fuse Links
Configuration Aids
I Dimensional drawings
5SE1
5,5 max
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
In A 10 ... 16 20 ... 63
Dimensions d 11 15.3 h 36 36
d3 d2
500 V AC/500 V DC
5SD4 20, 5SD4 30, 5SD4 40, 5SD4 80
d
i
d4
DII/E27 16 10 20 12 25 14 30 14
c e
I2_06242a
DIII/E33 35 16 50 18 63 20
49
28
DIV/R1" 80 5 100 7
Dimension d
57
Siemens ET B1 T 2007
2/77
Semiconductor Fuses
Notes on Dimensioning
Technical explanations
I Overview
The fuse links are selected according to rated voltage, rated current, breaking I2t value I2tA and varying load factor, taking into consideration other specified conditions. Unless stated otherwise, all of the following data refer to AC operation from 45 Hz to 62 Hz. Rated voltage Un The rated voltage of a SITOR fuse link is the voltage specified as the r.m.s. value of the AC voltage on the fuse link and in the order and configuration data and the characteristics. Always ensure that the rated voltage of the fuse link you select is such that the fuse link will reliably quench the voltage driving the short-circuit current. The driving voltage must not exceed the value Un + 10 %. Please note that the supply voltage Uv0 of a power converter can also be increased by 10 %. If, in the shorted circuit, two arms of a converter connection are connected in series, and if the short-circuit current is sufficiently high, it can be assumed that voltage sharing is uniform. It is essential to observe the instructions in "Series connection of fuse links" on page 2/84. Rectifier operation With converter equipment that can only be used for rectifier operation, the supply voltage Uv0 is the driving voltage. Inverter operation With converter equipment that can also be used for inverter operation, shoot-throughs may occur as faults. In this case, the driving voltage UWK in the shorted circuit is the sum of the infeed direct voltage (e.g. the e.m.f. of the DC generator) and the AC-line supply voltage. When rating a fuse link, this sum can be replaced by an AC voltage whose r.m.s. value is 1.8 times that of the AC-line supply voltage (UWK = 1.8 Uv0). The fuse links must be rated so that they reliably quench the voltage UWK. Rated current In, load rating The rated current of a SITOR fuse link is the current specified as r.m.s. value of the alternating current for the frequency range 45 Hz to 62 Hz in the Selection and ordering data and characteristic curves, as well as on the fuse link itself. When operating fuse links with rated current, the following are considered normal operating conditions: Natural air cooling with an ambient temperature of +45 C Conductor cross-sections equal test cross-sections (see Test cross-sections table), for operation in LV HRC fuse bases and switch-disconnectors, please refer to the Selection and ordering data Conduction angle of a half-period 120 el Continuous load maximum with rated current. For operating conditions that deviate from the above, the permissible load current In of the SITOR fuse link can be determined using the following formula: In = ku x kq x k x kl x WL x In whereby In Rated current of the fuse link1) ku Correction factor; ambient temperature (page 2/79) kq Correction factor; conductor cross-section (page 2/79) k Correction factor; conduction angle (page 2/79) kl Correction factor; forced-air cooling (page 2/79) WL Varying load factor (page 2/80) Test cross-sections
Rated current In Test cross-sections (series 3NC1 0, 3NC1 1, 3NC1 4, 3NC1 5, 3NC2 2, 3NE1 ..., 3NE8 0.., 3NE4 1) Cu mm2 1.0 1.5 2.5 4 6 10 10 16 25 35 50 70 95 120 2 x 70 2 x 95 2 x 95 2 x 120 2 x 120 2 x 150 2 x 185 2 x (40 x 5) 2 x (50 x 5) 2 x (80 x 4) (all other series) Cu mm2 45 45 45 45 45 45 45 60 80 100 125 150 185 240 260 320 320 400 400 480 560 560 720 720 960
A 10 16 20 25 35 40 50 63 80 100 125 160 200 224 250 315 350 400 450 500 560 630 710 800 900 1000 1250
1)
When using SITOR fuse links in LV HRC fuse bases according to IEC/EN 60269-2-1 and fuse switch disconnectors and switch disconnectors with fuses, please also refer to the data in the selection and ordering data.
2/78
Siemens ET B1 T 2007
Semiconductor Fuses
Notes on Dimensioning
Technical explanations
Correction factor; ambient temperature ku The influence of the ambient temperature on the permissible load of the SITOR fuse links is taken into account using the correction factor ku as shown in the following graph.
1 ,2 1 ,1 1 ,0 Correction factor k 0 ,9
I2 _ 1 2 6 3 6
Correction factor; conduction angle k The rated current of the SITOR fuse links is based on a sinusoidal alternating current (45 Hz to 62 Hz). However, in converter operation, the arm fuses are loaded with an intermittent current, whereby the conduction angle is generally 180 el or 120 el. With this load current wave form, the fuse link can still carry the full rated current. In the case of smaller conduction angles, the current must be reduced in accordance with the following graph.
1 ,1 1 ,0 0 ,9 0 ,8 0 ,7 0 ,6 0 ,5 3 0 4 5 6 0 1 8 0 2 4 0 9 0 1 2 0 Valve conducting period
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Correction factor k
0 ,8
-4 0
-2 0
0 + 2 0 + 6 0 + 4 0 Ambient temperature
+ 8 0 C
Correction factor; conductor cross-section kq The rated current of the SITOR fuse links applies to operation with conductor cross-sections that correspond to the respective test cross-section (see the table on page 2/78). In the case of reduced conductor cross-sections, the correction factor kq, must be used as shown in the following graph.
1 ,0 0 0 ,9 5 0 ,9 0 0 ,8 5 b 0 ,8 0 0 ,7 5
I2 _ 1 2 6 3 9
3 6 0 e l
Correction factor k
Correction factor; forced-air cooling kl In the case of increased air cooling, the current carrying capacity of the fuse link increases with the air speed, air speeds > 5 m/s do not effect any significant further increase of current carrying capacity.
1 ,4 1 ,3 1 ,2 1 ,1 1 ,0 0 2 4 Air velocity 6
l
0 ,6 5
1 0 0 %
8 0
m /s
I2 _ 1 2 6 3 8
0 ,7 0
Correction factor k
I2 _ 1 2 6 3 7
Siemens ET B1 T 2007
2/79
Semiconductor Fuses
Notes on Dimensioning
Technical explanations
Varying load factor WL The varying load factor WL is a reduction factor by which the nonaging current carrying capacity of the fuse links can be determined for any load cycles. Due to their design, the SITOR fuse links have a range of different varying load factors. In the characteristic curves of the fuse links, the respective varying load factor WL for >10000 load changes (1 hour "ON", 1 hour "OFF") is specified for the expected operating time of the fuse links. In the event of a lower number of load changes during the expected operating time, it may be possible to use a fuse link with a smaller varying load factor WL as shown in the following graph. In the case of uniform loads (no load cycles and no shutdowns), the varying load factor can be taken as WL = 1. For load cycles and shutdowns that last longer than 5 min. and are more frequent than once a week, you need to select the varying load factor WL specified in the characteristic curves of the individual fuse links.
I2 _ 1 2 6 4 0
1.1
LA / n
1.0
1.0 0.95
0.9
0.9 0.85
0.8
0.8
0.7
0.6 10 1
10 2
10 3
10 5
Fuse currents for operation in power converter The r.m.s. value of the fuse current can be calculated for the most common converter connections from the (smoothed) direct current Id or the conductor current IL according to the following table.
Converter connection R.m.s. value of the conductor current (phase fuse) (M1) (M2) (M3) (M6) (M3.2) (B2) (B6) (W1) 1.57 Id 0.71 Id 0.58 Id 0.41 Id 0.29 Id 1.0 Id 0.82 Id 1.0 IL R.m.s. value of the branch-circuit current (arm fuse) -----0.71 Id 0.58 Id 0.71 IL
One-pulse center tap connection Double-pulse center tap connection Three-pulse center tap connection Six-pulse center tap connection Double three-pulse center tap connection (parallel) Two-pulse bridge circuit Six-pulse bridge circuit Single-phase bidirectional connection
2/80
Siemens ET B1 T 2007
Semiconductor Fuses
Notes on Dimensioning
Technical explanations
I t values In the event of a short-circuit, the current of the fuse link increases during melting time ts up to let-through current Ic (melting current peak). During the arc quenching time tL, the electric arc develops and the short-circuit current is quenched (see the following graph).
c
1 0 ,8 0 ,6 0 ,4 0 ,2
1 2 3 4
Correction factor k
I2 _ 1 2 6 4 2
t
A
I2 _ 1 2 6 4 1
1 0 0
2 0 0
4 0 0 3 0 0 5 0 0 Recovery voltage U
w
6 0 0
7 0 0 V
5 6 7 8 9 10 11
The integral of the current squared I dtover the entire switching period (ts+tL), known as the breaking I 2t value, determines the heat to be fed to the semiconductor device that is to be protected during the breaking procedure. In order to ensure sufficient protection, the breaking I 2t value of the fuse link must be smaller than the I 2t value of the semiconductor device. As the temperature increases, i.e. preloading increases, the breaking I 2t value of the fuse link decreases almost in the same way as the I 2t value of a semiconductor device, so that it is enough to compare the I 2t values in a non-loaded (cold) state. The breaking I 2t value (I 2tA) is the sum of the melting I 2t value (I 2ts) and the quenching I 2t value (I 2tL).
Taking into account the recovery voltage Uw The recovery voltage Uw is derived from the voltage driving the short-circuit current. For most faults, the driving voltage is equal to the supply voltage Uv0, however, for shoot-throughs it is 1.8 times the value for the supply voltage Uv0 (see rated voltage, page 2/78). If the shorted circuit contains two arms of a converter connection and thus two fuse links in series, and if the short-circuit current is sufficiently high (see series connection, page 2/84) it can be assumed that there is a uniform voltage sharing, i.e. Uw = 0.5 x Uv0 or, in the case of shoot-throughs Uw = 0.9 x Uv0. Influence of the power factor p.f. The specifications in the characteristic curves for the breaking I 2t values (I 2tA) refer to power factor = 0.35 (exception: for 3NC5 8.., 3NE6 4.., 3NE9 4.. SITOR fuse links the following applies: p.f. = 0.2). The dependence of the breaking I 2t values on the power factor at 1.0 x Un and at 0.5 x Un is shown in the following graph.
1 2 0 % Cleaning- 2 value 2 A at cos (as a % of 2 A at cos = 0.35 or 0.2) b
Melting I t value I ts The melting value I 2t can be calculated for the value pairs of the time/current characteristic curve of the fuse link for any periods. As the melting time decreases, the melting value I 2t tends towards a lower limit value at which almost no heat is dissipated from the bottleneck of the fuse element to the environment during the melting process. The melting I 2t values specified in the Selection and ordering data and in the characteristic curves correspond to the melting time tvs = 1 ms. Melting I 2t value I 2tL While the melting I 2t value is a characteristic of the fuse link, the quenching I 2t value depends on circuit data, such as the recovery voltage Uw the power factor p.f. of the shorted circuit the prospective current Ip (current at the installation site of the fuse link if this is bridged) The maximum quenching I 2t value is reached at a current of 10 x In to 30 x In. Breaking I 2t value I 2tA, correction factor kA The breaking I 2t values of the fuse link are specified in the characteristic curves for the rated voltage Un. In order to determine the breaking I 2t value for recovery voltage Uw the correction factor kA must be taken into account. I 2tA (at Uw) = I 2tA (at Un) x kA The characteristics "correction factor kA" (see the following graph) is specified in the characteristic curves for the individual fuse series. The breaking I 2t values determined in this way apply to prospective currents Ip 10 x In and p.f. = 0.35.
1 0 0 a
8 0
6 0 0
I2 _ 1 2 6 4 3
00.2 ,2
00.4 ,4
12 13 14 15 16 17
Dependence of breaking I 2t value I 2tA p.f. at 1.0 Un at 0.5 Un a = 3NC5 8.., 3NE6 4.., 3NE9 4.. for SITOR fuse links (reference to p.f. = 0.2) b = for all other SITOR fuse links (reference to power factor = 0.35)
Siemens ET B1 T 2007
2/81
Semiconductor Fuses
Notes on Dimensioning
Technical explanations
Time/current characteristics The solid time/current characteristic curves in the following graph specify the time to melting for the non-loaded fuse link in a cold state (max. +45 C).
1 x 1 0 1 x 1 0 1 x 1 0 1 x 1 0 1 x 1 0 1 x 1 0 1 x 1 0 1 x 1 0
1 2 3 4
V ir tu a l p r e - a r c in g tim e t
Taking into account preloading, residual value factor RW Preloading the fuse link shortens the permissible overload duration and the melting time. The residual value factor RW can be used to determine the time that a fuse link can be operated during a periodic or non-periodic load cycle, above and beyond the previously determined permissible load current In, with any overload current ILa without aging. The residual value factor RW is dependent on the preloading V (Ieff r.m.s. value of the fuse current during the load cycle at permissible load current In') I eff V = -----In
v s
3 5 A
1 6 0 A
and the frequency of the overloads (see the following graph, curves a and b).
1 00.8 ,8 Rest value factor R W 00.6 ,6 00.4 ,4 00.2 ,2 0 0 00.2 ,2 0 ,4 0.4 0 ,6 0.6 b a c
I2 _ 1 2 6 4 4
-1
-2
I2 _ 1 2 6 5 7
-3
1 x 1 0
1
2 4
6 8 1 x 1 0
2
6 8 1 2 x 1 0 3 P r o s p e c tiv e s h o r t- c ir c u it c u r r e n t
p
4 6
8 1 x 1 0 A
If the time/current characteristic curve in the long-time range (tvs > 30 s) is dashed (fuse links of aR operational class), this specifies the limit of the permissible overload in a cold state. If the dashed part of the characteristic curve is exceeded, there is a risk of damage to the ceramic body of the fuse link. The fuse links can only be used for short-circuit protection. In this case, an additional protective device (overload relay, circuit-breaker) is required to protect against overload. In the case of controlled converter equipment, the current limiter is sufficient. If the time/current characteristic curve is solid over the entire setting range (fuse links of operational class gR or gS), then the fuse link can operate in this range. This means it can be used both for overload and short-circuit protection. Actual melting time The virtual melting time tvs is specified in the time/current characteristic curve, depending on the prospective current. It is a value that applies to the current squared (di/dt) = ). In the case of melting times tvs < 20 ms the virtual melting time tvs deviates from the actual melting time ts. The actual melting time may be several milliseconds longer (depending on the rate of current rise). Within a range of several milliseconds, during which the rise of the short-circuit current can be assumed to be linear, the actual melting time for a sinusoidal current rise and 50 Hz is as follows: 3 xI t s t = -------------s 2 I c
2
Permissible overload and melting time for previous load a = Frequent surge/load cycle currents (> 1/week) b = Infrequent surge/load cycle currents (< 1/week) c = Melting time for preloading
Permissible overload duration = residual value factor RW x melting time tvs (time/current characteristic curve) A reduction of the melting time of a fuse link in the case of preloading can be derived from curve c. Melting time = residual value factor RW x melting time tvs (time/current characteristic curve)
2/82
Siemens ET B1 T 2007
Semiconductor Fuses
Notes on Dimensioning
Technical explanations
Let-through current Ic The let-through current Ic can be determined from the current limiting characteristics (current limitation at 50 Hz) specified for the respective fuse link. This depends on the prospective current and the DC component when the short-circuit occurs (instant of closing). The following graph shows the let-through current Ic of a fuse link, depending on the prospective short-circuit current Ip using the 3NE4 333-0B SITOR fuse link as an example. Peak arc voltage s During the quenching process, a peak arc voltage s occurs at the connections of the fuse link, which can significantly exceed the supply voltage. The level of the peak arc voltage depends on the design of the fuse link and the level of the recovery voltage. The characteristic curve shown below depends on the recovery voltage Uw (see the following graph).
2000 1800 1600 1400 1200 1000 800 600 400 200 1 x 1 0
3
I2 _ 1 2 6 4 5
1 2 3 4 5 6 7 8 9 10 11 12
1 x 1 0
L e t-th ro u g h c u rre n t
1 x 1 0
4 5 0 A
U n lim ite d p e a k v a lu e s : D C c o m p o n e n t 5 0 % D C c o m p o n e n t 0 %
100 0 200
I2 _ 1 2 6 5 8
1 x 1 0
1 2 4 6 1 2 4 6 1 2 x 1 0 2 x 1 0 3 x 1 0 4 P r o s p e c tiv e s h o r t- c ir c u it c u r r e n t p
1 x 1 0 A
The peak arc voltage occurs as a cutoff voltage at the semiconductor devices not in the shorted circuit. In order to prevent voltagerelated hazards, the peak arc voltage must not exceed the peak cutoff voltage of the semiconductor devices. Power dissipation, temperature rise On reaching the rated current, the fuse elements of the SITOR fuse links have a considerably higher temperature than the fuse elements of line protection fuse links. The power dissipation specified in the characteristic curve is the upper variance coefficient if the fuse link is loaded with the rated current. In the case of partial loads, this power dissipation decreases as shown in the following graph
100 Power dissipation at partial load (as a % of the power % dissipated at rated current) 80
Rated breaking capacity The rated breaking capacity of all SITOR fuse links is at least 50 kA, unless higher values are specified in the characteristic curves. This data applies to a test voltage of 1.1 x Un, 45 Hz to 62 Hz and 0.1 p.f. 0.2. In the case of inception voltages that are below the rated voltage, or rated currents of the fuse links that are below the maximum rated current of a fuse series, the breaking capacity is considerably higher than the rated breaking capacity.
60
40
20
I2 _ 1 2 6 4 6
100 %
13 14 15 16 17
The temperature rise specified in the characteristic curve applies to the respective reference point and is determined when testing the fuse link (test setup according to DIN VDE 0636, Part 23 and IEC 269-4).
Siemens ET B1 T 2007
2/83
Semiconductor Fuses
Notes on Dimensioning
Technical explanations
Parallel and series connection of fuse links Parallel connection If an arm of a converter connection has several semiconductor devices so that the fuse links are connected in parallel, only the fuse link connected in series to the faulty semiconductor device is tripped in the event of an internal short-circuit. It must quench the full supply voltage. To boost the voltage, two or more parallel fuse links can be assigned to a single semiconductor device without reducing the current. The resulting breaking I 2t value increases with the square of the number of parallel connections. In this case, in order to prevent incorrect distribution of the current, you should only use fuse links of the same type. Series connection There are two kinds of series connection available: Series connection in the converter arm 2 fused converter arms through which a short-circuit current flows in series In both cases, uniform voltage sharing can only be assumed if the melting time of the SITOR fuse link does not exceed the value specified in the following table.
SITOR fuse links Type 3NC1 0.. 3NC1 4.. 3NC1 5.. 3NC2 2.. 3NC2 4.. 3NC5 8.. 3NC7 3.. 3NC8 4.. 3NE1 0.. 3NE1 2.. 3NE1 3.. 3NE1 4.. 3NE1 8.. 3NE3 2.. 3NE3 3.. 3NE3 4.. 3NE3 5.. 3NE3 6.. 3NE4 1.. 3NE4 3.. 3NE5 4.. 3NE5 6.. 3NE6 4.. 3NE7 4.. 3NE7 6.. 3NE8 0.. 3NE8 7.. 3NE9 4.. 3NE9 6.. Maximum melting time for uniform voltage sharing ms 10
Use with direct current For fuse links that are to be used in DC circuits, some data may vary from the data specified in the characteristic curves for alternating current. Permissible direct voltage The permissible direct voltage Uperm of the fuse links depends on the rated voltage Un, of the time constants = L/R in the DC circuit and on the prospective current Ip. The permissible direct voltage refers to the rated voltage Un and is specified depending on the time constants , the prospective current is a parameter (see the following graphs).
1.00
p
20
n p
= 10
n p
=5
20
30
40
50
60 =L/R
70
Time constant
m s
80
40 10
10
0.80 perm. DC vol tage U perm rated voltage Un (600 V)
20
n p
20 10 10 20
= 10
n p
=5
10 20 10 20 10 10 20
10
20
30
80 m s
Cooling conditions for series-connected fuse links should be approximately the same. If faults are expected, during which the specified melting times are exceeded (as a result of a slower current rise), it can no longer be assumed that voltage sharing is uniform. The voltage of the fuse links must then be rated so that a single fuse link can quench the full supply voltage. It is best to avoid the series connection of fuse links in a converter connection arm and instead use a single fuse link with a suitably high rated voltage.
Melting I 2t value I 2tA The breaking I 2t value I 2tA depends on the voltage, on the time constants = L/R and on the prospective current Ip. It is calculated from the I 2tA value specified in the characteristic curve for the respective fuse link at rated voltage Un and correction factor kA whereby, instead of the recovery voltage Uw, the direct voltage is used against which the fuse link is to switch. The breaking I 2t value determined in this way applies under the following conditions: Time constants L/R 25 ms for Ip 20 x In Time constants L/R 10 ms for Ip = 10 x In The breaking I 2t values increases by 20 % For Ip 20 x In and time constants L/R = 60 ms For Ip = 10 x In and time constants L/R = 35 ms
2/84
Siemens ET B1 T 2007
I2 _ 1 2 6 4 8
Semiconductor Fuses
Notes on Dimensioning
Technical explanations
Peak arc voltage s The peak arc voltage sis determined from the curve specified in the characteristics for the respective fuse link, whereby instead of the recovery voltage Uw, the direct voltage is used against which the fuse link is to switch. The peak arc voltage determined in this way applies under the following conditions: Time constants L/R 20 ms for Ip 20 In Time constants L/R 35 ms for Ip = 10 In The switching voltages increase by 20 % For Ip 20 In and time constants L/R = 45 ms For Ip = 10 In and time constants L/R = 60 ms Indicator An indicator shows the switching of the fuse link. The indicator of the SITOR fuse links has a transformer operational voltage between 20 V (Un 1000 V) and 40 V (Un > 1000 V). Accessories Fuse bases, fuse pullers Some of the SITOR fuse links can be inserted in matching fuse bases. The matching fuse bases (single-pole and three-pole) and the respective fuse pullers are listed in the technical specifications, from page page 2/4. Note Even if the values of the rated voltage and/or current of the fuse bases are lower than that of the allocated fuse link, the values of the fuse link apply. Fuse switch disconnectors, switch disconnectors with fuses Some series of SITOR fuse links are suitable for operation in 3NP4 and 3NP5 fuse switch disconnectors or in 3KL and 3KM switch disconnectors with fuses (see catalogs LV 10 and LV 30). When using switch disconnectors, the following points must be observed: Because, compared to LV HRC fuses, the power dissipation of the SITOR fuse links is higher, the permissible load current of the fuse links sometimes needs to be reduced, see below (Configuration manual). Fuse links with rated currents In > 63 A may also not be used for overload protection when they have gR operational class. Note All fuse links of the 3NE1 ... series with rated currents In from 16 A to 850 A and gR or gS operational classes can be used for overload protection. The rated voltage and rated isolation voltage of the switch disconnectors must at least correspond to the available voltage. When using fuse links of the 3NE3 2.., 3NE3 3.., 3NE4 3.., 3NC2 4.. and 3NC8 4.. series the switching capacity of the fuse switch disconnectors must not be fully utilized due to the slotted blade. Occasional switching of currents up to the rated current of the fuse link is permissible When used in fuse switch disconnectors, fuse links of the 3NE4 1.. series may only be occasionally switched, and only without load, as this places the fuse blade under great mechanical stress. In the technical specifications, from page 2/4, the switch disconnectors are allocated to their respective individual fuse links. The permissible load of the fuse link and the required conductor cross-section can be found in the configuration manual "Configuring SITOR", Order No.: E20001-A700-P302.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Siemens ET B1 T 2007
2/85
Semiconductor Fuses
Notes on Dimensioning
Specifying the rated current
I Overview
Specifying the rated current In for non-aging operation with varying load Power converters are often operated not with a continuous load, but with varying loads, that can also temporarily exceed the rated current of the power converter. The selection process for non-aging operation of SITOR fuse links for four typical types of load is as follows:1) Continuous load Unknown varying load, but with known maximum current Varying load with known load cycle Occasional surge load from preloading with unknown surge outcome The diagrams for the correction factors ku, kq, k , kl, page 2/79, and the residual value factor RW, see page 2/82, must be observed. The varying load factor WL for the fuse links is specified on page 2/80. Specifying the required rated current In of the fuse link is carried out in two steps: 1. Specifying the rated current In based on the r.m.s. value Irms of the load current: 1 I n > I eff -----------------------------------------------------k u k q k k l WL
Load current
Load current
La
1 I n I max k u k q k k l WL
Imax = maximum load current of the fuse link (r.m.s. value)
Permissible load current In' of the selected fuse link: In = ku kq kl kl WL In 2. Checking the permissible overload duration of current blocks exceeding the permissible fuse load current In'. Melting time tvs (time/current characteristics) x residual value factor RW overload duration tk To do this, you require the previous load ratio I eff V = -----In as well as the characteristic curve "permissible overload and melting time for previous load" (page 2/82, curve a) and the "time/current characteristic curve" for the selected fuse link. If a determined overload duration is less than the respective required overload duration, then you need to select a fuse link with a greater rated current In (taking into account the rated voltage Un and the permissible breaking I 2t value) and repeat the check. Continuous load I eff =
La La
' n
RMS
La2
I2_12651
S D
k=n
I eff = k=1
2
2 Lak
---------------------------------------SD
2 2
I La 1 t 1 + I La 2 t 2 + I La 3 t 3 ---------------------------------------------------------------SD
Load current
1 I n I La --------------------------------------------------------k u k q k k l WL
ILa = load current of the fuse link (r.m.s. value) Fewer than 1 shutdown per week: WL = 1 More than 1 shutdown per week: WL = see technical specifications, from page 2/4.
1)
In the case of varying loads that cannot be assigned to one of the four types of load shown here, please contact us.
2/86
Siemens ET B1 T 2007
I2 _ 1 2 6 4 9
I2_12650
Semiconductor Fuses
Notes on Dimensioning
Specifying the rated current
Occasional surge load from preloading with unknown surge outcome Specifying the required rated current In of the fuse link is carried out in two steps: 1. Specifying the rated current In based on the previous load current Iprev: 1 I n > I prev --------------------------------------------------------k u k q k k l WL Permissible load current In' of the selected fuse link: In' = ku x kq x k x kl x WL x In 2. Checking the permissible overload duration of the surge current Isurge Melting time tvs (time/current characteristics) x residual value factor RW surge wave duration tsurge To do this, you require the previous load ratio I eff V = -----In as well as the characteristic curve "permissible overload and melting time for previous load" (page 2/82, curve a or b) and the "time/current characteristic curve" for the selected fuse link. If a determined overload duration is less than the required overload duration tsurge, then you need to select a fuse link with a greater rated current In (taking into account the rated voltage Un and the permissible breaking I 2t value) and repeat the check.
surge
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
L a
Direct current Id = Idn = 850 A ILa = Id x 0.58 = 493 A Selected: 3NE3 335 SITOR fuse link (560 A/1000 V), WL = 1 breaking I 2t value I 2tA = 360 x 103 x 0.53 = 191 x 103 A2s test cross-section to page 2/78: 400 mm2
The following correction factors are to be applied: ku = 1.02 ( u = +35 C) kq = 0.91 (conductor cross-section, double-ended, 40 % of test cross-section) k = 1.0 (conduction angle = 120) kl = 1.0 (no forced-air cooling) Required rated current In of the SITOR fuse link: 1 I n I La ------------------------------------------------------ = 493 A k u k q k k l WL 1 - = 531 A 493 A ------------------------------------------------------------------------1, 02 0, 91 1, 0 1, 0 1, 0
La
Load current
surge
interval
n'
prev
= 4 3 5 A
L a
Sample selections For a converter assembly in circuit (B6) A (B6) C, whose rated direct current is Idn = 850 A, fuse links that can be installed as arm fuses should be selected. The choice of fuse is shown for different operation modes of the converter assembly. Data for converter assembly Supply voltage UN = 3 50 Hz 400 V AC Recovery voltage UW = 360 V = UN x 0.9 (for shoot-throughs) Thyristor T 508N (from eupec), l2t value i2 dt = 320 x 10 3A2s (10 ms, cold) Fuse links, natural air cooling ambient temperature u = +35 C Conductor cross-section for copper fuse link: 160 mm2 Conversion factor direct current Id/fuse load current ILa: ILa = Id x 0.58 For the following examples, it is assumed, in the case of loads that exceed the rated direct current of the converter assembly, that the converter assembly is rated for this load.
Max. direct current Idmax = 750 A Max. fuse current Imax = Idmax x 0.58 = 435 A Selected: 3NE3 334-0B SITOR fuse link (560 A/1000 V), WL = 1 breaking I 2t value I 2tA = 260 x 103 x 0.53 = 138 x 103 A2s test cross-section to page 2/78: 400 mm2
The following correction factors are to be applied: ku = 1.02 ( u = +35 C) kq = 0.91 (conductor cross-section, double-ended, 40 % of test cross-section) k = 1.0 (conduction angle = 120) kl = 1.0 (no forced-air cooling) Required rated current In of the SITOR fuse link: 1 I n I max ------------------------------------------------------ = 493 A k u k q k k l WL 1 - = 469 A 435 A ------------------------------------------------------------------------1, 02 0, 91 1, 0 1, 0 1, 0
I2 _ 1 2 6 5 4
I2 _ 1 2 6 5 3
Siemens ET B1 T 2007
2/87
Semiconductor Fuses
Notes on Dimensioning
Specifying the rated current
Varying load with known load cycle
L a 1 L a
= 6 9 6 A
L a 3
= 5 8 0 A
surge
n' e ff L a 2
L a
= 1 0 1 5 A
= 3 1 7 A = 2 9 0 A
I2 _ 1 2 6 5 5 prev
t = 4 0 6 A
surge
= 8 s
t
1
t2 S D = 3 3 0 s
t
3
t
4
t t
t1 = 20 s t2 = 240 s t3 = 10 s t4 = 60 s
tsurge = 8 s
Fuse current: ILa1 = 1200 x 0.58 = 696 A ILa2 = 500 x 0.58 = 290 A ILa3 = 1000 x 0.58 = 580 A R.m.s. value of load current
Fuse current: Iprev = Idprev x 0.58 = 406 A Isurge = Idsurge x 0.58 = 1015 A Conditions: tinterval 3 tsurge and tinterval 5 min must be fulfilled.
2 2
I eff =
Selected: 3NE3 333 SITOR fuse link (560 A/1000 V), WL = 1 breaking I2t value I2tA = 360 x 103 x 0.53 = 191 x 103 A2s test cross-section to page 2/78: 400 mm2
Selected: 3NE3 333 SITOR fuse link (450 A/1000 V), WL = 1 breaking I2t value I2tA = 175 x 103 x 0.53 = 93 x 103 A2s test cross-section to page 2/78: 320 mm2
The following correction factors are to be applied: ku = 1.02 ( u = +35 C) kq = 0.94 (conductor cross-section, double-ended, 50 % of test cross-section) k = 1.0 (conduction angle = 120) kl = 1.0 (no forced-air cooling) 1. Required rated current In of the SITOR fuse link: 1 I n I eff ------------------------------------------------------ = 493 A k u k q k k l WL 1 - = 331 A 317 A ------------------------------------------------------------------------1, 02 0, 94 1, 0 1, 0 1, 0 Permissible load current In' of the selected fuse link: In = ku x kq x k x kl x WL x In = 1.02 x 0.94 x 1.0 x 1.0 x 1.0 x 450 = 431 A 2. Checking the permissible overload duration of current blocks exceeding the permissible fuse load current In'. Previous load ratio: I eff V = ------ = 317 ------- = 0,74 431 In Residual value factor RW: for V = 0.74 of curve a (characteristic curve page 2/82, frequent surge/load cycle currents) RW = 0.2 Current block ILa1: melting time tvs: 230 s (from time/current characteristic curve for 3NE3 333) tvs x RW = 230 s x 0.2 = 46 s > t1 Current block ILa3: melting time tvs: 1200 s from time/current characteristic curve for 3NE3 333) tvs x RW = 1200 s x 0.2 = 240 s > t3
The following correction factors are to be applied: ku = 1.02 ( u = +35 C) kq = 0.91 (conductor cross-section, double-ended, 40 % of test cross-section) k = 1.0 (conduction angle = 120) kl = 1.0 (no forced-air cooling) 1. Required rated current In of the SITOR fuse link: 1 I n I prev ------------------------------------------------------ = 493 A k u k q k k l WL 1 - = 437 A 406 A ------------------------------------------------------------------------1, 02 0, 91 1, 0 1, 0 1, 0 Permissible load current In' of the selected fuse link: In' = ku x kq x k x kl x WL x In = 1.02 x 0.91 x 1.0 x 1.0 x 1.0 x 560 = 520 A 2. Checking the permissible overload duration of the surge current Isurge Previous load ratio: I prev - = 406 ------- = 0,78 V = --------520 In Residual value factor RW: for V = 0.78 of curve a (characteristic curve page 2/82, frequent surge/load cycle currents) RW = 0.18 Surge current Isurge: melting time tvs: 110 s (from time/current characteristic curve for 3NE3 333) tvs x RW = 110 s x 0.18 = 19.8 s > tsurge Correction factors can be found on page 2/78 and page 2/79.
2/88
Siemens ET B1 T 2007
I2 _ 1 2 6 5 6
Semiconductor Fuses
Notes on Dimensioning
Terms
I Overview
The following provides an explanation of the standard terms used when using fuse links for semiconductor protection. Further definitions can be found in EN 60269-1. Rated breaking capacity The rated breaking capacity is the highest prospective short-circuit current Ip that the fuse link can blow under prescribed conditions at 1.1 rated voltage. Rated frequency The rated frequency is the frequency for which the fuse link is rated with regard to power dissipation, current, voltage, characteristic curve and breaking capacity. Rated voltage Un The rated voltage is the designated voltage of the fuse and according to which test conditions and operational voltage limits are determined. For SITOR fuse links, the rated voltage is always the r.m.s. value of an AC voltage. Rated current In The rated current of a fuse link is the designated current of the fuse link and is the current up to which it can be continuously loaded under prescribed conditions (see page 2/78) without adverse affects. Operational class The operational class is the designation of the function class of a fuse link in connection with the object to be protected. gS operational class: Full range semiconductor safety fuse for use in safety switching devices gR operational class: Full range semiconductor protection aR operational class: Back-up semiconductor protection Let-through current Ic The let-through current Ic is the maximum instantaneous value of the current reached during a switching operation of the fuse. Let-through current characteristic curve The let-through current characteristic curve specifies the value of the let-through current at 50 Hz as a function of the prospective current. Function class The function class means the ability of a fuse link to carry specific currents without damage and to switch off over-currents within a certain range (breaking capacity range). Function class a Back-up fuses: Fuse links, that carry currents at least up to their rated current and can interrupt currents above a specific multiple of their rated current up to their rated breaking capacity. Function class g Full range fuses: Fuse links that can continuously carry currents up to at least their rated current and can interrupt currents from the smallest melting current through to the rated breaking capacity.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
I 2t value The I 2t value (joule integral) is the integral of the current squared over a specific time interval: t1 I t =
2
i t0
dt
Specifies the I 2t values for the melting process (I 2ts) and for the shutdown cycle (I 2tA, sum of melting and quenching I 2t value). Power dissipation Power dissipation is the power loss during the load of a fuse link with its rated current under prescribed conditions. Peak arc voltage s The peak arc voltage is the highest value of the voltage that occurs at the contacts of the fuse link during the arc quenching time. Residual value factor RW The residual value factor is a reduction factor for determining the permissible load period of the fuse link with currents that exceed the permissible load current In' (see rated current In). Prospective short-circuit current Ip The prospective short-circuit current is the r.m.s. value of the linefrequency AC component, or the value of the direct current to be expected in the event of a short-circuit occurring after the fuse, were the fuse to be replaced by a component of negligible impedance. Virtual time tv The virtual time is the time span calculated when a I2t value is divided by the square of the prospective current:
tv
i d-t = ---------------2
Ip
The time/current characteristic curve gives the virtual melting time tvs. Varying load factor WL The varying load factor is a reduction factor for the rated current with varying load states. Recovery voltage Uw The recovery voltage (r.m.s. value) is the voltage that occurs at the contacts of a fuse link after the power is cut off. Time/current characteristic curve The time/current characteristic curve specifies the virtual time (e.g. the melting time) as a function of the prospective current under specific operating conditions.
Siemens ET B1 T 2007
2/89
Semiconductor Fuses
Notes on Dimensioning
Characteristic curves
I Overview
Legend tvs = Virtual melting time Ic = Max. let-through current Ieff = r.m.s. value of the prospective short-circuit current I2ts= Melting I2t value I2ta= Breaking I2tvalue In = Rated current Pv = Rated power dissipation = Temperature rise ka = Correction factor for I2t value Uw = Recovery voltage s = Peak arc voltage ip = Peak short-circuit current $ = Peak short-circuit current with largest DC component % = Peak short-circuit current without DC component U = Voltage i = Current ts = Melting time tL = Arc quenching time Time/current characteristics Melting times of fuse links are shown in the time/current diagrams with logarithmic scale and depending on their currents. The melting time characteristic curve runs from the smallest melting current, which just about melts the fuse element, asymptotic to the I2t lines of the same joule value in the range of the higher short-circuit currents, which specifies the constant joule value I2t. To avoid overcomplication, the time/current characteristic curve diagrams omit the I2t lines (c).
1 1
P
The Siemens characteristic curves show the mean virtual melting time characteristic curves recorded at an ambient temperature of (20 5) C. They do not apply to preloaded fuse links. The fuse element of the fuse links melts so quickly at very high currents that the surge short-circuit current Ip is prevented from occurring. The highest instantaneous value of the current reached during the shutdown cycle is called the let-through current Ic. The current limitations are specified in the current limiting diagrams, otherwise known as let-through current diagrams.
U
: Arc voltage
10 9 t [s]
10 5 a
s L
10 1 c
100 A 50 A 10 A 6A
101 1
min
10 2
10 3
10 4
1 [A]
General representation of the time/current characteristic curve of a fuse link of gL/gG operational class Imin : a : b : c : Smallest melting current Melting time/current characteristic Break time characteristic curve I2t line
I2_06997b
The shape of the characteristic curve depends on the outwards heat transfer from the fuse element. DIN VDE 0636 specifies tolerancedependent time/current ranges within which the characteristic curves of the fuse must lie. Deviations of 10 % are permissible in the direction of the current axis. With Siemens LV HRC fuse links of gL/gG operational class, the deviations work out at less than 5 % a mark of outstanding quality. For currents up to approx. 20 In, the melting time-current characteristic curves are the same as the break time characteristic curves. In the case of higher short-circuit currents, the two characteristic curves move apart, influenced by the respective arc quenching time. The difference between both lines (= arc quenching time) also depends on the power factor, the operational voltage and the breaking current.
eff
Current limitation diagram; let-through current diagram of LV HRC fuse links, size 00, operational class gL/gG, rated currents, 6 A, 10 A, 50 A, 100 A
I2_06998a
2/90
Siemens ET B1 T 2007