Académique Documents
Professionnel Documents
Culture Documents
.I
SI
Z
SI
1
.I
S-q
+[Z
SI
u
-Z
SI
1
.I
S
u
(8)
Where:
I
S1
: Total length of Section ST
Similarly, the phase voltage, met by the relay R is:
I
R-q
= Z
R1
1
. I
R-q
+(Z
R1
0
- Z
R1
1
). I
R
0
+ (1 - J
1
). Z
S1
1
. (I
R-q
+
I
-q
) + (1 - J
1
). (Z
S1
0
- Z
S1
1
). (I
R
0
+ I
0
) + I
]
(9)
Which (1 - J
1
) represents the per unit distance between fault
to T point, so the distance in km is obtained by equation (9):
I
R
= I
R1
+ _
I
R-
-_I
+Z
RI
1
.I
R-
+_Z
RI
u
-Z
RI
1
].I
R
u
_
Z
SI
1
.[I
R-
+I
-
+_Z
SI
u
-Z
SI
1
]._I
R
u
+I
u
]
_ . I
S1
(10)
Where:
I
R-q
: Phase voltage measured at bus R, =a,b,c
I
R-q
: Phase current measured at bus R, =a,b,c
Z
R1
1
, Z
R1
0
: Positive and zero sequence impedance of the
section RT
I
R1
: Total length of Section RT
The relay Q estimates the distance in the same way, as
equation (10):
I
= I
1
+ _
I
-
-_I
+Z
I
1
.I
-
+_Z
I
u
-Z
I
1
].I
u
_
Z
SI
1
.[I
R-
+I
-
+_Z
SI
u
-Z
SI
1
]._I
R
u
+I
u
]
_ . I
S1
(11)
Where:
I
-q
: Phase voltage measured at bus Q, =a,b,c
I
-q
: Phase current measured at bus Q, =a,b,c
Z
1
1
, Z
1
0
: Positive and zero sequence impedance of the
section QT
I
1
: Total length of Section QT
I
]
that is used to calculate the fault distance in equations (8),
(10) and (11), obtained as below:
I
]
= S. R
]
. I
1
0
(12)
Where I
1
0
is:
I
1
0
= I
R
0
+ I
S
0
+I
0
(13)
So, the R
f
seen by the relay S equals to:
R
]
=
I
S
-J
1
.|Z
SI
1
.I
S
+I
S
u
._Z
SI
u
-Z
SI
1
_]
S.I
I
u
(14)
As we can see in equations (8), (9) and (10), the calculated
distance to fault is a function of fault point voltage which
computed from equation (13). On the other hand, this
equation also is a function of distance to fault. Dependence of
these equations to each other can be solving simply by
recessive calculation, finally this procedure yields to precise
results.
The above equations calculated distance to fault when
located on section ST. Fault location equations when fault
happen on two other sections are the same as equations
related to section ST. So, due to the limited space, we ignored
to report these equations.
B. Selection of valid subroutine
The proposed algorithm as described in previous sub
section consists of three subroutines. In each case only one of
the subroutines is valid and related to the faulty section. The
procedure has been developed for selecting the valid
subroutine is straightforward and doesnt need any more
calculation than which performed in equations (7) and (10).
Regarding to these two equations:
When u < J
1
< 1 and u
2
, u
3
> 1: Fault occurred in
section ST.
When u < J
2
< 1 and u
1
, u
3
> 1: Fault occurred in
section RT.
When u < J
3
< 1 and u
1
, u
2
> 1: Fault occurred in
section QT.
In the case of J
1
= J
2
= J
3
= 1, the fault is occurred in
tapped point.
III. SIMULATION RESULT
This section describes the results acquired by the proposed
algorithm and its performance when is subjected to different
tests.
A. MATLAB_SIMULINK model
The modeled 400kV test network includes the line
sectionsST: 150 km, RT: 150 km, QT: 50 km, having the
positive (negative) and zero-sequence impedances:
Z
1
= Z
2
= u.u72 +]u.416 , Z
0
= u.S46 + ]1.u66
The equivalent sources:
Z
S
= u.18u2 + ]2.S2S4 , Z
R
= u.2S27 + ]S.2S77
Z
= u.4uS + ]S.642S
were also included.
Existence of the pre-fault load flow in the modeled network
is determined by the assumed phase shift of side R source
(that is -1S
), with respect
to the equivalent source behind bus S (u
).
B. Evaluation of the Fault-Location Algorithm
Fig.5 shows the fault location estimated by the relay S for a
single phase to ground fault located at 60km distant from the
relay S, with 20 fault resistance. The fault occurred at
t=1.5sec and after less than 100ms, the result was recorded.
Fig.5. Fault distance estimated by relay S, when single phase fault to ground
happened at 60km distant from relay S.
2 2 . 5 3 3 . 5 4
6 0. 00 2
60 . 0 02 2
60 . 0 02 4
60 . 0 02 6
60 . 0 02 8
6 0. 00 3
60 . 0 03 2
60 . 0 03 4
Tim e (s ec )
F
a
u
l
t
d
i
s
t
a
n
c
e
(
k
m
)
According to this figure, we can see the effect of recessive
calculation at the first 0.5sec.
For more examination, single phase to ground faults with
different resistances and locations were applied to the
proposed algorithm. In Table I, the fault distance varied from
0.1km to 150km from relay S, while the fault resistance
remained constant at 10. The fault distances which were
measured by other relays are added to tables.
TABLE I
SINGLE PHASE FAULT DISTANCE ESTIMATION WITH FIXED RF
Fault distance
from S (km)
Single phase fault in section S-T
Relay R Relay S Relay Q Rf ()
0.1 299.9111 0.1001 199.9088 10.0001
1 299.0116 1.0001 199.0092 10.0001
10 290.0130 10.0000 190.0103 10.0003
25 275.0120 25.0005 175.0094 10.0000
50 250.0092 50.0010 150.0070 10.0000
100 200.0043 100.0022 100.0029 10.0000
140 160.0017 140.0037 60.0011 10.0001
150 150.0013 150.0041 50.0009 10.0002
In Table II, the fault resistance varied from 0.1 to 500,
while the fault distance remained constant at 75km from relay
S. In these cases, the error calculated by equation from IEEE
PC37.114:
%Error =
(EstimotcJ Foult Iocotion-Actuol Iocotion)1uu
Actuol Iocotion
are also added.
The results show that the error in most cases is less than
0.01%, while the worst case occurred when phase to phase
fault included with 500 resistance. But in this case also, the
error is less than 1%.
IV. CONCLUSION
A new fault location algorithm for three terminal
transmission lines is presented in this paper. The proposed
technique utilizes PMUs on three ends of the transmission
lines. Basic principles and detail formulation are also
illustrated. The advantages claimed for these algorithms are:
(i) Algorithms do not contain simplifying assumptions and
lead to an accurate fault location estimate.
(ii) No limits are set for the magnitude of fault resistance
and overall accuracy is limited only by the accuracy of digital
impedance relays and PMUs.
(iii) Applicable to apply to other basic shunt fault types.
The results of simulation verify the high accuracy of fault
location with various conditions including different fault
resistances, fault locations and fault inception angle.
TABLE II
SINGLE PHASE FAULT WITH VARIABLE FAULT RESISTANCE
Fault real
Rf ()
Measured
Rf ()
Relay R Relay S Relay Q
Fault
distance(km)
Error (%)
Fault
distance(km)
Error (%)
Fault
distance(km)
Error (%)
0.1 0.1001 225.0046 0.0020 75.0001 0.0001 125.0027 0.0022
1 1.0001 225.0048 0.0021 75.0002 0.0003 125.0029 0.0023
5 5.0001 225.0056 0.0025 75.0008 0.0011 125.0037 0.0030
10 10.0000 225.0065 0.0029 75.0015 0.0020 125.0047 0.0038
50 49.9994 225.0140 0.0062 75.0075 0.0100 125.0127 0.0102
100 99.9988 225.0233 0.0104 75.0150 0.0200 125.0227 0.0182
200 199.9974 225.0420 0.0187 75.0229 0.0305 125.0428 0.0342
500 499.9934 225.0980 0.0436 75.0747 0.0996 125.1029 0.0823
REFERENCES
[1] S. Kang, S. Lee, Y. Kwon, Y. Kang, A fault Location
Algorithm for Parallel Transmission Line with a Teed Circuit,
IEEE PES Summer Meeting, Vol. 2, pp. 921-926, 2001.
[2] D. Novosel, D. G. Hart, E. Udren, and M. M. Saha, Fault
Location Using Digital Relay Data, IEEE Computer
Applications in Power, pp. 45-50, Jul. 1995.
[3] L. Eriksson, M. M. Saha, and G. D. Rockefeller, An Accurate
Fault Locator with Compensation for Apparent Reactance in the
Fault Resistance Resulting from Remote-End Infeed, IEEE
Trans. on Power Apparatus and Systems, Vol. PAS-104, No. 2,
pp. 424-436, Feb. 1985.
[4] IEEE Guide for determining fault location on AC transmission
and distribution lines, IEEE Standard C37.114-2004, Dec. 2004.
[5] Girgis AA, Hart DG, Peterson WL, A new fault location
technique for two- and three-terminal lines, IEEE Trans. on
Power Delivery Vol. 7, No. 1, pp.98-107, 1992.
[6] M. Kezunovic, B. Perunicic, Automated transmission line fault
analysis using synchronized sampling at two ends, IEEE Trans
on Power System, Vol. 11, No. 1, pp.441-447, 1996.
[7] M. M. Saha, J. Izykowski, E. Rosolowski, A method of fault
location based on measurements from impedance relays at the
line ends, In: Proc of 8th Int Conf on Developments in Power
System Protection DPSP, IEE CP500, pp. 176-179, 2004.
[8] R. K. Aggarwal, D. V. Coury, A. T. Johns, A. Kalam, A
practical approach to accurate fault location on extra high
voltage teed feeders, IEEE Trans. on Power Delivery, Vol. 8,
No. 3, pp. 874-883, Jul. 1993.
[9] M. Abe, T. Emura, N. Otsuzuki, and M. Takeuchi,
Development of a new fault location system for multi-terminal
single transmission lines, IEEE Trans. on Power Delivery, Vol.
10, No. 1, pp. 159-168, Jan. 1995.
[10] T. Nagasawa, M. Abe, N. Otsuzuki, T. Emura, Y. Jikihara, and
M. Takeuchi, Development of a new fault location algorithm
for multi-terminal two parallel transmission lines, IEEE Trans.
on Power Delivery, Vol. 7, No. 3, pp. 1516-1532, Jul. 1992.
[11] T. Funabashi, H. Otoguro, Y. Mizuma, L. Dube, and A.
Ametani, Digital fault location for parallel double-circuit
multi-terminal transmission lines, IEEE Trans. Power
Delivery, Vol. 15, No. 2, pp. 531-537, Apr. 2000.
[12] J. Izykowski, E. Rosolowski, M. M. Saha, M. Fulczyk and P.
Balcerek, A fault location method for application with current
differential relays of three terminal lines, IEEE Trans. on
Power Delivery, Vol. 22, No. 4, pp. 2099-2107, Oct. 2007.
[13] J. Izykowski, R. Molag, E. Rosolowski and M. M. Saha,
Accurate location of faults on power transmission lines with
use of two-end unsynchronized measurements IEEE Trans. on
Power Delivery, Vol. 21, No. 2, pp. 627633, April 2006.