Académique Documents
Professionnel Documents
Culture Documents
(2)
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 4, July-August (2013), IAEME
69
Fig. 1: Power loss indices of 37 bus unbalanced radial distribution system
The most suitable buses for the capacitor placement are chosen based on the condition that
PLI must be greater than PLI tolerance value, it should be lies in between 0 and 1. The tolerance
value for a chosen system is selected by experimenting with different values in descending order of
the PLI limits. The best value of the tolerance value gives the highest profit and satisfies the system
constraints. Fig.1 shows power loss index vs bus number for 37 bus URDS. From experimentation
the best value of PLI tolerance is set as 0.6. It is concluded that buses 2, 10, 11, 33, 37 are the best
candidate buses for the capacitor placement. Assume capacitor at candidate buses with size varying
the integer steps of the standard size capacitors (50 kVAr per phase).
4. ARTIFICIAL BEE COLONY METHOD
Artificial Bee Colony (ABC) is one of the most recently defined method by Dervis Karaboga
in 2005, motivated by the intelligent behavior of honeybees. ABC as an optimization tool provides a
population based search procedure in which individuals called food positions are modified by the
artificial bees with time and the bees aim is to discover the places of food sources with high nectar
amount and finally the one with the highest nectar. In this method [10], [11], the colony of artificial
bees consists of three groups of bees: employed bees, onlookers and scouts. First half of the colony
consists of the employed artificial bees and the second half includes the onlookers. For every food
source, there is only one employed bee. In other words, the number of employed bees is equal to the
number of food sources around the hive. The employed bee whose food source has been abandoned
becomes a scout [12]. Thus, ABC system combines local search carried out by employed and
onlooker bees, and global search managed by onlookers and scouts, attempting to balance
exploration and exploitation process [13]. This ABC method is used for finding optimal size of
capacitors at optimal locations.
5. RESULTS AND ANALYSIS
To check the validity of the proposed ABC method, 25 bus and 37 bus unbalanced radial
distribution systems have been considered. In addition, the results of these systems were compared
with those obtained via existing PSO method [8]. The proposed ABC method results were obtained
after carrying out 100 independent runs.
Energy saving cost has been calculated as the difference of energy loss cost without capacitor
and with capacitor. The net saving has been calculated as the difference of energy saving cost and the
capacitor installation and purchase cost. The rate of energy loss cost has been considered as Rs. 3 per
0
0.2
0.4
0.6
0.8
1
1.2
0 10 20 30 40
Bus number
Power Loss Indices (PLI)
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 4, July-August (2013), IAEME
70
kWh, depreciation factor is 0.2, installation cost Rs. 50,000 and the cost of the three phase capacitor
is Rs. 200 for the cost benefit analysis [14]. The Control parameters of existing and proposed
methods of both test systems are given in Table 1.
Table 1: Control parameters of existing and proposed methods for both test systems
Existing method [8] Proposed method
Number of generations=100; Population size=20
Wmax=0.9; Wmin=0.2 ; c1 = 2; c2 = 2
MaxCycle=100
Colony size=40
1) Example: 1
The 37 bus unbalanced radial distribution system is considered as first example for testing the
efficacy of proposed method. In order to study the effect of capacitor placement at multiple
locations, an attempt was made to place capacitor at more than one location. The locations of
capacitor placement is obtained as discussed in section 3 i.e., candidate buses for the placement of
capacitors. The optimal sizes of capacitors are obtained by proposed and existing optimization
methods. Summary of test results of 37 bus unbalanced radial distribution system is given in Table 2.
The net saving obtained by existing and proposed methods are Rs. 3,09,007 and Rs. 3,15,304 for the
total size of capacitor of 300 kVAr and 250 kVAr respectively.
From Table 2, it is observed that the minimum voltages in phases A, B and C are improved
from 0.9497, 0.9578 and 0.9445 p.u to 0.9622, 0.9712 and 0.9598 p.u by existing method, 0.9625,
0.9718 and 0.9601 p.u by proposed method respectively. Also observed that the active power loss in
phases of A, B and C is reduced from 31.56, 23.67 and 30.44 kW to 25.47, 20.41 and 24.99 kW by
existing method and 25.23, 20.36 and 24.81 kW by proposed method respectively.The reactive
power loss in phases A, B and C is reduced from 24.01, 22.32 and 29.19 kVAr to 20.41, 18.83 and
24.65 kVAr by existing method and 20.21, 18.78 and 24.49 kVAr by proposed method respectively.
From table 2 it is also observed that the total active and reactive power demand of test system is
reduced by placing capacitors at optimal locations by proposed method than existing method.
2) Example: 2
The 25 bus unbalanced radial distribution system is considered as second example for testing
the efficacy of proposed method. The line and load data of this test is taken from [14]. The selection
of locations for capacitors is same as second example. For this test system 0.4 is taken as PLI
tolerance which is selected by experimentation. The PLI values for 25 bus unbalanced radial
distribution system is shown in Fig. 2. From this Fig. 2, the buses 9, 12, 14 and 15 are selected as
optimal locations.
Fig. 2: Power loss indices of 25 bus unbalanced radial distribution system
0
0.2
0.4
0.6
0.8
1
1.2
0 5 10 15 20 25 30
Bus number
Power loss indices (PLI)
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 4, July-August (2013), IAEME
71
Summary of test results of 25 bus unbalanced radial distribution system is given in Table 3.
The net saving obtained by existing and proposed methods are Rs. 10,87,405 and Rs. 11,00,689 for
the total size of capacitor of 450 kVAr and 500 kVAr respectively. From Table 3, it is observed that
the minimum voltages in phases A, B and C are improved from 0.9284, 0.9284 and 0.9366 p.u to
0.9545, 0.9522 and 0.9611 p.u by existing method, 0.9567, 0.9542 and 0.9631 p.u by proposed
method respectively. Also observed that the active power loss in phases of A, B and C is reduced
from 52.82, 55.44 and 41.86 kW to 37.58, 39.22 and 29.51 kW by existing method and 37.34, 38.92
and 29.32 kW by proposed method respectively. The reactive power loss in phases A, B and C is
reduced from 58.32, 53.29 and 55.69 kVAr to 41.56, 38.05 and 39.77 kVAr by existing method and
41.36, 37.58 and 39.23 kVAr by proposed method respectively.
Table 2: Summary of test results of 37 bus unbalanced radial distribution system
Description
Before capacitor placement Existing method [8] Proposed method
Phase
A
Phase
B
Phase C Phase A Phase B Phase C Phase A Phase B Phase C
Size of the
Capacitor(Qc
in kVAr)
with node
number
2
--- --- ---
0 0 0 50 50 50
10 0 0 0 50 50 50
11 100 100 100 50 50 50
33 100 100 100 100 100 100
37 50 50 50 50 50 50
Minimum voltage 0.9497 0.9578 0.9445 0.9622 0.9712 0.9598 0.9625 0.9718 0.9601
Max. Volt. regulation 0.0503 0.0422 0.0555 0.0378 0.0288 0.0402 0.0375 0.0282 0.0399
Improvement of max.
Voltage regulation (%)
--- --- --- 24.8509 31.7535 27.5676 25.4473 33.1754 28.1081
Net
saving(Rs.)
Best
---
309007 315304
Worst 222161 248654
Average 307764 309321
Total active power loss
(kW)
31.56 23.67 30.44 25.47 20.41 24.99 25.23 20.36 24.81
Total active power loss
reduction (%)
--- --- --- 19.32 13.77 17.89 20.05 13.99 18.49
Total reactive power loss
(kVAr)
24.01 22.31 29.20 20.41 18.83 24.65 20.21 18.78 24.49
Total reactive power loss
reduction (%)
--- --- --- 15.02 15.62 15.56 15.86 15.84 16.10
Total active Power
demand(kW)
885.56 789.67 1163.44 879.47 786.41 1157.99 879.23 786.36 1157.81
Total reactive Power
demand(kVAr)
442.01 397.31 580.19 438.40 393.83 575.65 438.21 393.78 575.49
Total Feeder Demand
(kVA)
989.75 883.99 1300.09 982.68 879.51 1293.19 982.38 879.44 1292.95
Released feeder capacity
(kVA)
--- --- --- 7.07 4.48 6.90 7.36 4.55 7.13
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 4, July-August (2013), IAEME
72
Table 3: Summary of test results of 25 bus unbalanced radial distribution system
Description
Before capacitor placement Existing method [8] Proposed method
Phase
A
Phase B Phase C Phase A Phase B Phase C Phase A Phase B Phase C
Size of the
Capacitor (Qc
in kVAr)
with node
number
9
--- --- ---
150 150 150 150 150 150
12 100 100 100 100 100 100
14 0 0 0 150 150 150
15 200 200 200 100 100 100
Minimum voltage 0.9284 0.9284 0.9366 0.9545 0.9522 0.9611 0.9567 0.9542 0.9631
Max. Volt. Regulation (%) 7.16 7.16 6.34 4.55 4.78 3.89 4.33 4.58 3.69
Improvement of max. Voltage
regulation (%)
--- --- --- 36.4525 33.2402 38.6435 39.5251 36.0335 41.7981
Net
saving(Rs.)
Best
---
1087405.2260 1100689.5266
Worst 1059162.1232 1093939.6864
Average 1086473.9888 1099873.1927
Total active power loss (kW) 52.82 55.44 41.86 37.58 39.22 29.51 37.34 38.92 29.32
Total active power loss
reduction (%)
--- --- --- 28.85 29.26 29.50 29.31 29.80 29.96
Total reactive power loss
(kVAr)
58.32 53.29 55.69 41.86 38.05 39.77 41.36 37.58 39.23
Total reactive power loss
reduction (%)
--- --- --- 28.22 28.60 28.59 29.08 29.48 29.56
Total active Power
demand(kW)
1126.12 1138.74 1125.16 1110.88 1122.52 1112.81 1110.64 1122.22 1112.62
Total reactive Power
demand(kVAr)
850.32 854.29 855.69 833.86 839.05 839.77 833.36 838.58 839.23
Total Feeder Demand
(kVA)
1411.09 1423.57 1413.57 1389.02 1401.45 1394.12 1388.53 1400.93 1393.64
Released feeder capacity
(kVA)
--- --- --- 22.07 22.12 19.45 22.56 22.64 19.93
6. CONCLUSION
The proposed ABC method successfully achieved the optimal solutions. The results of the
proposed method were compared with existing method for capacitor placement at multiple locations.
The proposed method shows that the sizes of capacitors at optimal locations improve the net saving
significantly than the sizes of capacitor obtained by existing method. The real and reactive power
demand effect is reduced on total system due to capacitors placement. The minimum voltage is also
improved by proposed method than existing method.
REFERENCES
[1] J.J. Grainger and S.H Lee, Optimum size and location of shunt capacitors for reduction of
losses on distribution feeders, IEEE Transactions on Power Apparatus and Systems, Vol.
PAS- 100, No. 3, PP. 1105-1118, 1981.
[2] M.E. Baran and F.F. Wu, Optimal capacitor placement on radial distribution systems, IEEE
Transactions on Power Delivery, Vol. 4, No. 1, PP. 725-734, 1989.
[3] H.D.Chiang, , J.C. Wang, O. Cockings and H.D. Shin, Optimal capacitor placements in
distribution systems, IEEE Transactions on Power Delivery, Vol. 5, No. 2, PP. 643-649,
1990.
[4] C.J. Bridenbaugh, D.A. Di Mascio and R. D Aquila, Voltage control improvement through
capacitor and transformer tap optimization, IEEE Trans. Power Syst., Vol. 7, No. 1,
PP. 222 226, 1992.
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976
6545(Print), ISSN 0976 6553(Online) Volume 4, Issue 4, July-August (2013), IAEME
73
[5] S. Sundharrajan and A. Pahwa, Optimal selection of capacitors for radial distribution
systems using a genetic algorithm, IEEE Trans. on Power Systems. Vol.9, PP.1499-1507,
1994.
[6] T.S. Abdul-Salam, A.Y. Chikhani and R. Hacka, A new technique for loss reduction using
compensating capacitors applied to distribution systems with varying load condition, IEEE
Trans. on Power Delivery, Vol.9, No.2, PP.819-827, 1994.
[7] C.S. Chen, C.T. Hsu and Y.H. Yan, Optimal distribution feeder capacitor placement
considering mutual coupling effect of conductors, IEEE Trans. on Power Delivery, Vol.10,
No.2, PP.987-994, 1995.
[8] P. Umapathi Reddy, S. Sivanagaraju and P. Sangameswara Raju, Particle swarm
optimization based approach for loss reduction in unbalanced radial distribution system,
International Journal of Engineering Science and Technology (IJEST), Vol. 3, No.11, PP.
8030-8038, November 2011.
[9] Radial Distribution test feeders - www.ewh.ieee.org/soc/pes/dsacom/testfeeders.html.
[10] D. Karaboga and B. Basturk, Artificial bee colony optimization algorithm for solving
constrained optimization problems, Springer-Verlag, IFSA, LNAI 4529, PP. 789798, 2007.
[11] D. Karaboga and B. Basturk, On the performance of artificial bee colony algorithm,
Elsevier Applied Soft Computing, Vol. 8, PP.687697, 2007.
[12] S. Hemamalini and Sishaj P. Simon, Economic load dispatch with valve-point effect using
artificial bee colony algorithm, xxxii national systems conference, nsc 2008, december 17-
19, 2008.
[13] Chin Soon. Chong, Hean Low. Malcolm Yoke, Appa Iyer. Sivakumar and Khen. Leng Gay,
A Bee Colony Optimization Algorithm to Job Shop Scheduling, Proc. of the 2006 Winter
Simulation Conference, PP.1954- 1961, 2006.
[14] J.B.V. Subramnyam, Optimal capacitor placement in unbalanced radial distribution
networks, Journal of Theoretical and Applied Information Technology, Vol. 6, N0. 1,
PP.106-115, 2009.
[15] Suresh Kamble and Dr. Chandrashekhar Thorat, Characterization of Voltage Sag Due to
Balanced and Unbalanced Faults in Distribution Systems, International Journal of Electrical
Engineering & Technology (IJEET), Volume 3, Issue 1, 2012, pp. 197 - 209, ISSN Print:
0976-6545, ISSN Online: 0976-6553.
[16] S.Neelima and Dr. P.S.Subramanyam, Effect of Load Levels on Sizing and Location of
Capacitors in Distribution Systems, International Journal of Electrical Engineering &
Technology (IJEET), Volume 3, Issue 3, 2012, pp. 31 - 42, ISSN Print: 0976-6545,
ISSN Online: 0976-6553.
[17] G.Vasu, J. Nancy Namratha and V.Rambabu, Large Scale Linear Dynamic System
Reduction Using Artificial Bee Colony Optimization Algorithm, International Journal of
Electrical Engineering & Technology (IJEET), Volume 3, Issue 1, 2012, pp. 145 - 155,
ISSN Print: 0976-6545, ISSN Online: 0976-6553.