Trane Products Overview

HVAC Products Update

Why update?

Environmental Issue
ODP & GWP Phased out R22 Use of environmental friendly refrigerant
R407C, R410A, R134a, R123

Energy Issue
Building Energy Code Chiller COP Air-Cooled to Water-Cooled plant conversion Airside Energy Recovery

IEQ Issue
Air quality, Humidity control, Acoustic, Thermal Comfort

Products Update 2011

Todays focus

TRANE HVAC Products

Chilled Water

Direct Expansion Unitary

Control Systems

Chillers Commercial Unitary Systems Air Handling Units Mini Split Systems Fan Coil Units VAV Boxes

Chiller Plant Control Space Comfort

Products Update 2011

Chilled Water Products


VAV Boxes

Origin: China, USA Type: Single Duct, Series Fan-Powered, Parallel Fan-Powered DDC Zone Sensors Airflow range: 40 ~ 4000 CFM (single duct), (Standard or LCD) 220 ~ 2500 CFM (fan-powered) Application: Cooling only, hot water reheat, electric reheat Features: Airflow Ring, Air Valve, Transformer, Actuator, SCR motor for fan-powered series Option: Double wall casing, Unit controller (Factory, LonTalk, others) Wireless Sensors Reheat (hot water coil, electric heater) Power fuse, Power disconnect

Single Duct
4 Products Update 2011

Series Fan Power

Parallel Fan Power

Chilled Water Products


Fan Coil Units
Origin: China Model: HFCF, VFCF, HFXF, HCCA Airflow range: 200 ~ 1400 CFM, 1000 ~ 2400 CFM (HCCA series) Type: Concealed type (ceiling or floor mounted), Exposed type (ceiling mounted) Application: Cooling only, heating, 2 or 4-pipes Features: Al fins, blue fins coil with Cu tubes Normal or Hi-static motor w/ overload protection Up to 200Pa ESP for HCCA series HCCA DC brushless motor (DCBL) stepless control Quiet operation, energy saving, comfort DIDW FC fans Max. height 230mm for HFCF series

HFCF

Products Update 2011

Chilled Water Products


Air Handling Units

Quantum Climate Changer Origin: China, Malaysia Model: CLCP, CLCPEuro, CLCP XP Airflow range: 0.5 ~ 25 m3/s Applications: Cooling, heating, direct expansion Features: Eurovent certified for CLCPEuro Double skin construction (50mm or 25mm) Ceiling, floor mounted (HDT, VDT) Flat, Bag, cartridge filter Al fins, blue fins, Cu fins coil with Cu tubes DIDW FC, BC & AF fans, plenum fan (plug fan) Advanced Option: Desiccant dehumidification wheel (CDQ), Heat Recovery wheel, Run Around Coil (RAC), Heat Pipe, Factory Mounted Control (FEC)

CLCPEuro

CLCP
6 Products Update 2011

CLCP XP

Chilled Water Products


Air-Cooled Liquid Chillers
CGAK/R CGAM/ CXAM CGCL CGAN/ CXAN ERTAD CRTAC ERTAC 0 50 100 150 200 250 300 350 400 450

Scroll type Compressor Screw type Compressor

Capacity/ tons

Products Update 2011

Chilled Water Products


Air-Cooled Liquid Chillers
Scroll type compressors
Origin: China, Taiwan, France Model: CGAK/R, CGAM/CXAM, CGCL, CGAN/CXAN Refrigerant used: R407C, R410A Efficiency range: 2.0 ~ 3.1 COP Applications: Cooling only, heat pump CGAN/CXAN Features: 4 ~ 130 ton Capacity control: on/ off steps Brazed plate heat exchanger (Evaporator) Al fins, blue fins, epoxy fins, Cu fins coil with Cu tubes (Condenser) Built-in water pump (single or dual) Propeller type condenser fans, centrifugal type for CGCL only (indoor type applications)
CGAM/CXAM CGCL

CGAK/R

Products Update 2011

Chilled Water Products


Air-Cooled Liquid Chillers
Screw type compressors
Origin: China, France Model: ERTAD, ERTAC, CRTAC, ERTUD (Condenserless) ERTUD Refrigerant used: R134a Efficiency range: 2.1 ~ 3.1 COP Applications: Cooling only, heat recovery (RTAD option) Features: 75 ~ 425 ton Direct driven, twin rotors screw compressors Capacity control: slide valve, continuous modulation Shell & tube heat exchanger (Falling film type evaporator, requires less refrigerant) Al fins, epoxy fins, Cu fins coil with Cu tubes (Condenser) CRTAC Propeller type condenser fans (Standard, Low Noise, Hi-static)
ERTAD

ERTAC

Products Update 2011

Chilled Water Products


Falling Film Evaporator
Patented evaporator design Higher efficiency using less
refrigerant charge
Vapor to Compressor Suction Liquid Distributors Liquid from Separator

Provides almost oil free


refrigerant to maximize heat transfer performance
Vapor Vapor

Better Oil Return


Oil & Refrigerant Mix

10

Products Update 2011

Chilled Water Products


Water-Cooled Liquid Chillers
CGWP CGWH CGWN RTWS RTWD RTHD CVGF CVHE/F/G 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300

Scroll type Compressor

Screw type Compressor

Centrifugal Compressor

Capacity/ tons

11

Products Update 2011

Chilled Water Products


Water-Cooled Liquid Chillers
Scroll type compressors
Origin: Taiwan, France Model: CGWP, CGWH, CGWN Refrigerant used: R407C, R410A Efficiency range: 3.5 ~ 4.5 COP Applications: Cooling only Features: 14 ~ 140 ton Capacity control: on/ off steps Brazed plate heat exchanger (Evaporator) Shell & tube heat exchanger (Condenser) Built-in water pump (single or dual) Microprocessor control
CGWP CGWH

CGWN

12

Products Update 2011

Chilled Water Products


Water-Cooled Liquid Chillers
Screw type compressors
Origin: China, USA Model: RTWS, RTWD, RTHD Refrigerant used: R134a Efficiency range: 4.6 ~ 6.0 COP RTWS Applications: Cooling only, heat pump (RTWD option) Features: 58 ~ 410 ton Direct driven, twin rotors screw compressors Dual refrigerant circuit for RTWD Capacity control: slide valve, continuous modulation RTHD Shell & tube heat exchanger Falling film type evaporator Compact size, smaller footprint Microprocessor control

RTWD
13 Products Update 2011

Chilled Water Products


Ease of Installation

Fit through single-width door (RTWS, RTWD) or double-width door (RTHD) without removal of any components

Installation Benefits
Faster, quicker retrofit opportunities Less floor space in new construction Suitable for retrofit and system upgrade

14

Products Update 2011

Chilled Water Products


Water-Cooled Liquid Chillers

Centrifugal type compressors Origin: China, USA Model: CVGF, CVHE/F/G Refrigerant used: R134a, R123 Efficiency range: 5.1 ~ 6.9 COP Applications: Cooling only, heat recovery (CVHE/F/G option) Features: 170 ~ 1200 ton Multi-stages compressor, hermetic type Gear drive centrifugal compressor for CVGF Direct drive centrifugal compressor for CVHE/F/G Capacity control: Inlet Guide Vane, AFD (Option) Shell & tube heat exchanger (Flooded type) 1 or 2 stage(s) economizer EarthWiseTM Purge Unit Adaptive control Rapid restart from power failure
CVHE/F/G
15

CVGF

Products Update 2011

Chilled Water Products


Tracer AdaptiViewTM

Color, Animated, Graphical, Touch Screen Open Protocols (Modbus RTU, BACNet, LONTalk) Adjustable Height Dental Arm 24 Local Languages Industry Leading Control Algorithms
Adaptive Control Feed Forward Control Variable Flow Compensation Adaptive Frequency Drives Compatible with Tracer Chiller Plant Control

Modbus

16

Products Update 2011

Additional Information
Green Refrigerants

Balance of Environmental Issues


Minimal Ozone Depletion Potential (ODP) Minimal Global Warming Potential (GWP) Chiller Efficiency (COP) Short Atmospheric Life Operating Pressure (Lowest possible leakage rate)

17

Products Update 2011

Environmental Impact of Refrigerant


Ozone Depletion Potential (ODP)
1 0.9 ODP (R-11=1.0) 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 CFC- CFCHC 11 12 FC-22 HC FC123 HFC- HFC- HFC- HFC134a 410A 407C 245fa

Global Warming Potential (GWP)


12000 10000 GWP (CO2= 1.0) 8000 6000 4000 2000 0
CFC11 CFC12 HCFC- HCFC22 123 HFC134a HFC410A HFC407C HFC245fa

Energy Efficiency (COP)


100

Atmospheric Life (years)


80 Years 60 40 20

6.8 6.6 6.4 6.2 6 5.8 5.6 5.4 CFC- CFC- HCFC- HCFC- HFC- HFC- HFC- HFC11 12 22 123 134a 410A 407C 245fa

COP

0 CFC11 CFC- HCFC- HCFC- HFC12 22 123 134a HFC410A HFC407C HFC245fa

18

Products Update 2011

Ozone Depletion Potential (ODP)


1 0.9 0.8 0.7 ODP (R-11=1.0) 0.6 0.5 0.4 0.3 0.2 0.1
ODP=0.012

0 CFC-11 CFC-12 HCFC-22 HCFC123 HFC134a


ODP=0.000015 19 Products Update 2011

HFC410A

HFC407C

HFC245fa

Global Warming Potential (GWP)


12000

10000

GWP (CO2= 1.0)

8000

6000

4000

2000
GWP=76

GWP=1320

0 CFC-11 CFC-12

HCFC-22 HCFC-123 HFC-134a HFC-410A HFC-407C HFC-245fa

20

Products Update 2011

ODP versus GWP


CFC-11 12 113 114 115 HCFC-22 123 124 141b 142b HFC-32 125 134a 143a 152a 227ea 236fa 245fa 1.0 0.8 0.6 0.4 0.2 0.0 2000 4000 6000 8000 10000 GWP (relative to CO2)
JMC 2001

ODP (relative to R-11)


Products Update 2011

J. M. Calm and G. C. Hourahan, Refrigerant Data Summary, Engineered Systems, 18(11):74-88, November 2001 (based on 1998 WMO and 2001 IPCC assessments) 21

Water Cooled Chiller Efficiency (COP)

6.8 6.6 6.4 COP 6.2 6 5.8 5.6 5.4 CFC-11 CFC-12 HCFC-22 HCFC-123 HFC-134a HFC-410A HFC-407C HFC-245fa

22

Products Update 2011

Atmospheric Half Life (Years)


100

80

Years

60

40

20

0 CFC-11 CFC-12 HCFC-22 HCFC123 HFC-134a HFC410A HFC407C HFC245fa

23

Products Update 2011

Chiller Operating Pressure


310.0 Condenser (100 ) (38oC) 270.0 Operating Pressure (psig) 230.0 190.0 150.0 110.0 70.0 30.0 -10.0 R-11
24 Products Update 2011

Off Line (72 ) (22oC) Evaporator (38 ) (3.3oC)

R-123

R-12

R-134a

R-22

R-410A

Maximize Maximize Lifetime Lifetime System System Performance Performance


25 Products Update 2011

Any Questions?

26

Products Update 2011

TRANE HVAC Products

Chilled Water

Direct Expansion Unitary

Control Systems

Todays focus
Chillers Commercial Unitary System Air Handling Units Mini Split Systems Fan Coil Units VAV Boxes Space Comfort Chiller Plant Control

27

Products Update 2011

Commercial Unitary
Rooftop Air Conditioners
Origin: US (R410A) Model:
TSC/ WSC (3 ~ 10 Tons) TCH/ WCH (12 ~ 25 Tons) Applications: Cooling only, heat pump Features: Down flow/ horizontal discharge Airside economizers CO2 sensors BACnet interface

TSC/ WSC (US Origin)

TCH/ WCH (US Origin)

28

Products Update 2011

Commercial Unitary
Rooftop Air Conditioners

Origin: China (R407C), Model: CTKH/CWKH (20.5 ~ 50 Tons) Applications: Cooling only, heat pump Features: Down flow/ horizontal discharge Airside economizers CO2 sensors Power exhaust fans BACnet interface

CTKH/ CWKH (China Origin)

29

Products Update 2011

Commercial Unitary
Direct Expansion AHU

Origin: China, Malaysia Refrigerant used: R407C Capacity: 22 ~ 170 kW Single skin type Floor or ceiling mounted Indoor application Origin: China, Malaysia Refrigerant used: R407C Capacity: 22 ~ 340 kW Double skin type Floor or ceiling mounted Indoor or outdoor application

30

Products Update 2011

Commercial Unitary
Air Handling Units
Origin: Malaysia Model: CLCPEuro (Indoor Type DX-AHU) CLCP XP (Outdoor Type DX-AHU) Airflow range: 0.5 ~ 25 m3/s Features: Eurovent certified for CLCPEuro CLCPEuro Double skin (25 or 50mm) Ceiling, floor mounted Pre-filter: 2 Al filter Secondary filter: 15 bag filter, 12 cartridge filter FC, BC, Airfoil fan, Plug fan Advanced Option: Desiccant wheel (CDQ) Heat Recovery wheel
CLCP XP

31

Products Update 2011

Commercial Unitary
Condensing Units

Origin: China Refrigerant used: R407C Capacity: 22 ~ 70 kW Scroll compressors LCD display thermostat

Origin: Malaysia Refrigerant used: R407C Capacity: 70 ~ 340 kW Scroll compressors LCD display control module

32

Products Update 2011

Commercial Unitary
Water-Cooled Packaged Units

Origin: Malaysia, USA Model: WCVS, GEHB/GEVB Refrigerant used: R407C, R410A Applications: Cooling only, heat pump (GEH/V series option) Features: 1.5 ~ 20 tons (USA) 20 ~ 100 tons (Malaysia) Single skin construction (USA) Double skin construction (Malaysia)
GEHB / GEVB

WCVS

33

Products Update 2011

Mini Split Systems


Wall Mounted Type (Non Inverter Type)

Origin: China Model: 4MCW Series Refrigerant used: R410A Applications: Cooling only, Heat Pump Features: 2.6 ~ 7.0 kW (Cooling) 3.0 ~ 7.5 kW (Heating) 1 to 1 and 1 to 2 available Energy Label Grade 1 or 2 Option: Inverter type available for 1 to 1 4MYW Series
4MCW/ 4MYW

34

Products Update 2011

Mini Split Systems


Wall Mounted Type (Non Inverter and Inverter Type)
Thin
The depth of indoor unit of 1hp is 170mm and that of 1.5hp is 180mm

Extra air intake slot


On top front direction to assist air intake to indoor unit Allow top clearance of indoor as low as 50mm

One piece casing


Convenient design for indoor panel replacement.
4MCW/ 4MYW

35

Products Update 2011

Mini Split Systems


Wall Mounted Type (Non Inverter and Inverter Type)
Multi temperature display
Both set-point temperature and room temperature will be shown on indoor display

4 fan speed (Turbo/ High/ Mid/ Low)


Turbo give most powerful cooling in short time. Turbo button on the remote controller.

Fan blow function.


Indoor fan will still work for several minutes after the outdoor unit turn off to blow away all the residual water on the evaporator to avoid fungi and mold forming.

36

Products Update 2011

Mini Split Systems


Wall Mounted Type (Non Inverter and Inverter Type)

37

Products Update 2011

Mini Split Systems


Cassette type (Non Inverter Type)

Origin: China Model: 4MWC Series Refrigerant used: R410A Applications: Heat Pump Features: 3.2 ~ 14.0 kW (Cooling) 4.0 ~ 15.0 kW (Heating) Single split type Drain pump as standard accessory

4MWC

38

Products Update 2011

Mini Split Systems


Ducted type (Non Inverter Type)

Origin: China Model: 4MWD Series Refrigerant used: R410A Applications: Heat Pump Features: 3.2 ~ 14.0kW (Cooling) 4.0 ~ 15.0kW (Heating) ESP: Max 25Pa Option: Inverter type available for 1 to 1 4MYD Series Drain pump for indoor unit

4MWD/ 4MYD

Low height design: 220mm for 1hp and 1.5hp indoor unit
39 Products Update 2011

Mini Split Systems


Ducted type (Non Inverter Type)

Origin: Thailand Model: MCD Series Refrigerant used: R407C Applications: Cooling only Features: 3.5 ~ 17.5kW ESP: 50-75Pa

MCD

40

Products Update 2011

Mini Split Systems


Multi-split type (Inverter Type) Free Match

Origin: China Refrigerant used: R410A Applications: Heat Pump Features: 4.7 ~ 12.4 kW (Cooling) 5.3 ~ 13.2 kW (Heating) Inverter Compressor Min. 1 to 2 Max. 1 to 5 Provide flexibility to residential projects Mix & match for indoor units

41

Products Update 2011

Mini Split Systems


Multi-split type (Inverter Type) Free Match

18,000Btu/hr (2 ports)

24,000Btu/hr (2 ports)

28,000Btu/hr (4 ports)

No diversity factor 100% capacity matched with total capacity of indoor units 2 types of indoor unit available for residential project Wall mounted type/ duct type
42 Products Update 2011

Cu/ blue fins Al condenser coil as standard No refnet joint Error code shown on indoor unit display

Mini Split Systems


Job Reference
Project The Cliverden () Cyberport Residential R1a & 1b (1-2) 15 Homantin Hill () Primrose Hill () 81 Boardcast Drive () Festival City Phase 3 (3) Lot 2064 Hung Shui Kiu () KIL11073 Hoi Wang Road Developer Kerry PCCW Kerry Kerry Cheung Kong MTRC/ Cheung Kong Cheung Kong Sino Nan Fung Chinese State K Wah Qty 600 9000 450 1750 630 6540 3350 3100 Year 2002 2003 2004 2009 2010 2010 2010 2011

43

Products Update 2011