Vous êtes sur la page 1sur 29

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-E-BD-0002)

SECTION C-2.4.2 DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 1 of 29

ELECTRICAL DESIGN PHILOSOPHY

UNIT PACKAGE

: CENTRAL POLYMER FACILITY : PACKAGE-1

A Rev. No

20.11.2012 Date

ISSUED WITH FEED PACKAGE Purpose

VB Prepared by

RKS Checked by

VKJ Approved by

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 2 of 29

TABLE OF CONTENTS
1.0 2.0 3.0 4.0 5.0 SCOPE ....................................................................................................................................... 3 SPECIFICATIONS, ITPS & DATASHEETS ............................................................................. 3 STANDARDS ............................................................................................................................. 3 STATUTORY REQUIREMNTS .................................................................................................. 4 SYSTEM DESIGN PHILOSOPHY ............................................................................................. 4 5.1 General ......................................................................................................................... 4 5.2 AREA CLASSIFICATION and EQUIPMENT SELECTION ......................................... 4 5.3 Power system Design ................................................................................................. 5 5.4 Capacity of Electrical system ..................................................................................... 5 5.5 System voltages .......................................................................................................... 6 5.6 Allowable Voltage Drop .............................................................................................. 7 5.7 System Earthing .......................................................................................................... 8 5.8 Short Circuit Capacities .............................................................................................. 8 5.9 Insulation system ........................................................................................................ 9 5.10 Protection and Metering schemes ............................................................................. 9 5.11 DC Power Supply ......................................................................................................... 9 5.12 Emergency Power supply ........................................................................................... 9 5.13 Uninterrupted Power Supply (UPS) ......................................................................... 10 5.14 Power Factor Improvement ...................................................................................... 10 5.15 Harmonics Elimination .............................................................................................. 10 EQUIPMENT DESIGN PHILOSOPHY ..................................................................................... 10 6.1 General ....................................................................................................................... 10 6.2 Transformers.............................................................................................................. 10 6.3 Switch Gear ................................................................................................................ 11 6.4 BUS DUCT .................................................................................................................. 14 6.5 Neutral Grounding Resistor ..................................................................................... 14 6.6 Electric Motors ........................................................................................................... 14 6.7 6.8 6.9 6.10 6.11 6.12 6.13 6.14 6.15 6.16 6.17 6.18 6.19 6.20 6.21 6.22 7.0 Control Station ........................................................................................................... 15 Black Start and Emergency Generators .................................................................. 15 Lighting Systems ....................................................................................................... 16 SOCKET OUTLETS .................................................................................................... 17 Earthing and Lightning Protection .......................................................................... 18 AC/DC Distribution Boards....................................................................................... 20 DC Power Supply Systems ....................................................................................... 20 Uninterruptible Power Supply (UPS) System ......................................................... 21 Batteries ..................................................................................................................... 22 Cables ......................................................................................................................... 22 Cable Tray .................................................................................................................. 23 Equipment Enclosures .............................................................................................. 25 Actuators for Motor Operated Value........................................................................ 25 ELECTRICAL SUBSTATION BUILDINGS ................................................................ 25 CATHODIC PROTECTION ......................................................................................... 28 Electric heat tracing (EHT) System .......................................................................... 29

6.0

33KV OVERHEAD POLE LINE ............................................................................................... 29

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 3 of 29

1.0

SCOPE
This specification along with the applicable project design basis / data form the basis for developing detailed design and engineering for electrical facilities including electrical power system , electrical equipment , Electrical Installation etc .

2.0

SPECIFICATIONS, ITPS & DATASHEETS


The following specifications shall be referred for additional information for procurement, installation and pre-commissioning of electrical equipment and material. CAIRN-TSG-E-SP-0001 CAIRN-TSG-E-SP-0002 CAIRN-TSG-E-SP-0004 CAIRN-TSG-E-SP-0005 CAIRN-TSG-E-SP-0006 CAIRN-TSG-E-SP-0007 CAIRN-TSG-E-SP-0008 CAIRN-TSG-E-SP-0009 CAIRN-TSG-E-SP-0010 CAIRN-TSG-E-SP-0011 CAIRN-TSG-E-SP-0012 CAIRN-TSG-E-SP-0013 CAIRN-TSG-E-SP-0015 CAIRN-TSG-E-SP-0016 CAIRN-TSG-E-SP-0017 CAIRN-TSG-E-SP-0018 CAIRN-TSG-E-SP-0019 CAIRN-TSG-E-SP-0020 CAIRN-TSG-E-SP-0021 CAIRN-TSG-E-SP-0022 CAIRN-TSG-E-SP-0023 CAIRN-TSG-E-SP-0024 CAIRN-TSG-E-SP-0025 Specification for Oil Type Transformers Specification for Medium Voltage Induction Motors Specification for Dry Type Lighting Transformers Specification for Medium Voltage Switch Gears Specification for High Voltage Switch Gears Specification for Power and Control cables Specification for Electrical Heat Tracing Specification for Lighting Systems Spec for FLP control stations Spec for FLP Light fittings and JB's Spec for hazardous Area Plugs , sockets and hand lamps Spec for safe area industrial type control stations Spec for Uninterruptable Power Supply ( AC ) Specification for DC Power supply system Project General - AC-DC Distribution Boards Electrical Cable Tray System Cathodic Protection Project General - Variable Frequency Drives - VFD / Soft Starters Project General - Neutral Grounding Resistor Motor Operated Valve (MOVs) Specification for Packaged Substation Electrical Specification For Construction Power Supply System Electrical Specification for High Mast Lighting

3.0
3.1

STANDARDS
All electrical equipments shall be in conformance with Central Electrical Authority (CEA) Regulations & Indian Electricity Rules 1956 (IER 1956) as applicable. Any other regulatory design requirements and approvals needs to be followed where ever applicable. Employ the standards, as applicable, in the design as per relevant specification a. b. c. Oil Industries Safety Standards ( OISD ) Bureau of Indian Standards (BIS or IS) International Electro-technical Commission (IEC) Standards ( wherever relevant IS standards are not available ) IEEE standards (wherever IS / IEC standards are not available.
Copyright EIL All rights reserved

3.2

d.

Format No. EIL 1650-1296P Rev. 2

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 4 of 29

e.

National Association of Corrosion Engineers (NACE) Recommended Practice for Cathodic Protection NFPA standards as part of fire proofing and design of substation buildings

f. 3.3

Metric SI system of units shall be applied to all dimensions and documents.

4.0

STATUTORY REQUIREMENTS
Indian electricity Act Indian Electricity Rules The Factory Act Oil Mines Regulations Requirements of other statutory bodies as applicable, e.g. Central Electricity Authority (CEA)/State Electrical inspectorate, CCE, DGMS

5.0
5.1

SYSTEM DESIGN PHILOSOPHY


General The Electrical system shall be designed to provide
a. b. c. d. e. f. g. h. i.

safety to plant, personnel and equipment during operation and maintenance Reliability of service flexibility of operation and maintenance Minimal fire risk Reliable Protection system through selective relaying system. Adequate provision for future extension and modification Effective power management and load shedding Low harmonics in the system as per standards Rated performance at applicable environment factors ( Project specific )

5.2

AREA CLASSIFICATION and EQUIPMENT SELECTION 5.2.1 Hazardous classification of areas and installations shall be in accordance with IS 5572 , IS14154, OISD standards and Oil mines regulations act .All the area within the battery limits shall be classified for the degree and the extent of hazard from flammable materials. Following factors shall be considered for proper selection of electrical equipment for use in hazardous area. Area classification as per Zone Gas classification as per Group The characteristic of the gas or vapour involved in relation to the ignition current or minimum ignition energy and safe gap data. Dust classification as per Group. The Characteristic of the dust involved Temperature classification The Ignition temperature of the gas, Vapour or dust involved or the lowest of the ignition temperature if more than one combustible is present.

5.2.2

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 5 of 29

Environment condition in which apparatus is to be installed the selected electrical equipments apparatus shall be adequately protected against corrosive and solvent agencies, water ingress, thermal and mechanical stresses as determined by the environmental conditions. 5.2.3 All the electrical Equipment installed in hazardous areas shall be selected as per IS-5571 and IS 14154 and shall meet the requiremnts of relevant IS and statutory regulations . However , electrical equipments for Zone 2 areas as a minmum shall be EX(e) / EX (n)type as per IS/ IEC codes . increased saftety type Ex(e) equipment shall not be used in zone 1 areas . Type of explosion protection to be used for individual equipment shall not be as specfied in the job design data. As far as possible Pressurised electrical equipments need to be avoided as along as other alternative is available. In case using pressurised equipment (Type Ex (p) then on failure of pressurisation system, the following minimum actions shall be provided. 1. For Zone 1 the equipment needs to switched off and alarm needs to be initiated. 2. For Zone 2 Alarm needs to be initiated 5.2.5 All electrical equipment to be used in classified areas shall be certified by CMRI /CPRI/ERTL or equivalent recognized independent test house such as BASEEFA/LCIE/PTB/UL/FM. All equivalent (Indigenous and imported) shall also have valid statutory approvals as applicable for use in the specified hazardous area . The indigenous equipment shall confirm to Indian standards and shall be approved by CCE/ DGMS as applicable based on mines non mines application. All mines application shall be under DGMS jurisdiction and shall be defined based on project condition in design basis. All mines area electrical equipments to be used in hazardous area are type tested by other reputed agencies outside India, the vendor shall approach applicable statutory bodies specified above and get the equipment approved by them for use in the specified area of utilization prior to energization. The product transported along the pipe rack is heavy crude combined with water and is deemed non-hazardous. The well heads will be classified zones. The hazardous area motors (Ex (e), or Ex (d) fed by variable frequency drive shall be certified as a combination for the specified location by independent test house and shall have valid statutory approvals. Non -sparking (Ex (n) motors shall not be used were solid state starters/ VFDs are used for separating purpose of the motor. In case of flame proof motor and variable frequency drive combination may not be certified together if direct temperature control by embedded temperature sensors are provided which will disconnect the motors.

5.2.4

5.2.6

5.2.7

5.2.8 5.2.9

5.3

Power system Design The power distribution shall be designed in accordance with project specification taking into account all possible factors affecting the choice of the system to be adopted such us required continuity of supply , flexibility of operation , operating cost , reliability of supply from available power sources , total load and the concentration of individual loads .

5.4

Capacity of Electrical system

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 6 of 29

All the components of the electrical system shall be sized to suit the maximum load, under the most severe operating conditions. Accordingly, the maximum simultaneous consumption of power, required by continuously operating loads shall be considered and an additional margin shall be taken into account for intermittent service loads, if any. The amount of electrical power consumed by each process unit shall be calculated for its operation at the design capacity. System design shall permit direct on line starting of all motors unless specified otherwise 5.5 System voltages

Power distribution between terminal to well pads and remote areas outside the terminal

33KV + 10%, 3ph, 3W, 50 Hz + 3%, solidly grounded. ( To be referred with Design basis of specific projects )

Power distribution

415V + 6%, 3ph, 3W, 50Hz + 3%. 240 V, +/- 6 %, 3 PH, 3 W system for Lighting and Small power ( To be referred with Design basis / SLD of specific projects )

Utilization voltage (Motors/Heaters > 160KW)

6.6KV + 6%, 3ph, 3W, 50 Hz + 3%, resistance grounded

Utilization voltage (250W <=Motors/Heaters <=160KW , Welding socket outlet) Motors < 250W, Lighting, Space Heaters, Single phase socket outlet Protection, Control & Indication Supply for 33KV/6.6KV Breakers* Charging of HV Switchgears and 415V Breaker
*

415V + 6%, 3ph, 3W, 50 Hz+ 3%, resistance grounded 240V + 6%, 2 ph, 2 W, 50 Hz+ 3%, solidly grounded

Switchboard

and

415V

110V+ 10%, DC, 2W, Ungrounded

110V+ 10%, DC, 2W, Ungrounded

415V contactor feeders control and indication supply UPS system DC system

240V+ 6%, 2ph, 2W, 50 Hz+ 3%, solidly grounded 230 V+ 1%, 1ph, 50 Hz+ 1% 110 V + 10%, DC and 24V DC. 24V DC is generated internally

Process Control & Instrumentation system

230V+ 1%, 1ph, 50 Hz + 1%, (from UPS System)


Copyright EIL All rights reserved

Format No. EIL 1650-1296P Rev. 2

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 7 of 29

Communication System

230V+ 1%, 1ph, 50 Hz + 1%, (from UPS System)

Instrument and Local Control panel (LCP)

24V DC generated within the instrument panels (original source will be from 230V UPS system).

* 415V switchgear control power supply can be 240V, 2ph, 50Hz, where 110V DC is unavailable. 240V, 2ph, 50Hz supply shall be derived from the Switchboards Control Power Transformer (CPT). 5.6 Allowable Voltage Drop The maximum allowable voltage drops, as a percentage of the system During Normal Operating and Start up Sl. No System Description Operating condition Maximum Permissible voltage drop 0.5 % 0.5 %

1 2 3

Main Bus Bus duct or cable between secondary and HV switch board transformer

Stabilized Stabilized Stabilized

Cable between PCC / MCC and MCC or auxiliary switch board MCC / Auxiliary switch board near PCC / MCC Remotely located MCC / board to PCC / PMCC Auxiliary switch

0.5 % 2 to 2.5 % ( Note 3

4 5 6

Cable between HV switch Board and HV Motor Cable between PCC / PMCC and motor Cable between MCC and motor ( distance between Motor and MCC in different area / 100 meters away ) Cable between MCC and motor ( distance between Motor and MCC in same area and remote form PCC ) Cable between auxiliary switch board / LDB and lighting Circuits between lighting panel and Lighting points DC supply circuits for electrical systems From Main DCDB to DC Sub DB From DC Sub DB to farthest consumer From Main UPS DB to UPS Sub DB From UPS Sub DB to farthest consumer At the bus bar of the worst affected switch board (Start up of the large HV motors with other loads on the bus or reacceleration of a group of motors of HV motors ( Simultaneous start up or group

Stabilized Stabilized Stabilized

3% 5% 5%

Stabilized

3%

8 9 10 10 11 12 13 14

Stabilized Stabilized Stabilized Stabilized Stabilized Stabilized Stabilized Startup

1.5 % Note 2 4% 5% 2% 3% 2 % Note 1 3 % Note 1 15 %

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002) reacceleration of HV motors is not envisaged ) 15 At the bus bar of the worst affected MV switch board ( PCC / PMCC / MCC )

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 8 of 29

16

Cables between HV switch board and Motors

17

Cables between MV switch board

18

33 KV OH line

Startup of large MV motor with other loads on the bus , or reacceleration of a group of MV motors Motor startup or reacceleration Motor startup or reacceleration Stabilized

10 %

5 % ( note 8) 15 % Note 8 ) 3% (

Notes 1. Minimum voltage available across any instrument in the field shall be as per instrumentation design basis. Distribution system for instrumentation supplies shall be designed accordingly. in case of any conflict between electrical design basis and instrumentation design basis , the later shall govern regarding instrumentation power supplies. In case of difficulty in achieving specified voltage drops in cables up to lighting panel 5 % drop from auxiliary switch board up to lighting points may be permitted. Higher voltage drop may be permitted between PCC / PMCC and remote mounted MCC/ ACB; if overall voltage drops up to motor (PCC to motor) is limited within 5.5 %. The Voltage available at the motor terminals during startup must be sufficient to ensure positive starting or reacceleration of the motor (even with the motor fully loaded, if required), without causing any damage to the motor . For medium voltage motors, the voltage available at the motor terminals must not be less than 75 % of the rated value during startup or reacceleration. For high voltage motors, the voltage available at the motor terminals must not be less than 80 % of the rated value during startup or reacceleration. Based on the sizing criteria as defined, including voltage drop criteria, cables for 415 V motors shall be selected as per cable sizing table indicated in design data. Higher voltage drop in motor cables may be permitted, in case the condition given in note 4, 5, 6 are complied. System Earthing System earthing for incoming supply and primary / secondary HV distribution, LV distribution system shall be as per design basis / SLD.

2.

3.

4.

5.

6.

7.

8.

5.7

5.8

Short Circuit Capacities Each short circuit interrupting device shall be designed to have rated service short circuit breaking capacity (Ics) equal to or higher than the maximum value of short circuit current

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 9 of 29

calculated, at its location. The related switchgear and bus ducts shall withstand the above maximum available fault current for a maximum period of one second. The sizing of high voltage cables also be based on the short circuit withstand capacity for a minimum time period as dictated by the protection system as defined in design basis, in addition to the maximum anticipated load current . 5.9 Insulation system The insulation of electrical facilities shall be designed considering the system voltage, the system neutral earthing and the over voltages due to system fault, switching or lightning surges. Lightning / Surge arrestors shall be provided wherever necessary

5.10

Protection and Metering schemes 5.10.1 5.10.2 The protective system shall be selected and coordinated to ensure the following Protection of equipment against damage , which occur due to internal or external short circuits or atmospheric discharges Uninterrupted operation of those parts of the system , which are not affected by the fault Personnel safety Protection relays shall be numerical based smart and communicable type relays. In general, quick acting relays (with time delays, if necessary) shall be used and all the fault tripping shall be done through high speed tripping relays. All the protection system communication needs to be wired to central control system for monitoring and event logging purpose. All the protection inputs commands and signals shall be hard wired. The protective relays shall be compatible to time synchronization with GPS . Metering shall be provided to keep record of power consumption and supervision of all concerned parameters like current, voltage, frequency, power factor etc as specified. For this dedicated data concentrator with HMI shall be considered. In addition to this metering as per statutory requirement with relevant class of accuracy as per their guidelines and approval needs to be provided. The power system study Load flow , short circuit analysis , motor starting and re acceleration analysis , harmonic study , relay coordination , DC load flow ,cable sizing calculation needs to carried out by ETAP software .

5.10.3

5.10.4

5.11

DC Power Supply Independent DC Power supply system shall be provided for the following Plant shutdown system including DC Instrumentation

Electrical switch gear controls including critical lighting Each DC power supply system shall include charger cum- rectifier, batteries and DC distribution board. Battery backup time shall be as specified in design data. 5.12 Emergency Power supply The emergency power supply system, wherever envisaged, shall feed the following: Electrical loads essential for the safe shutdown of the plant Emergency lighting Process plant instruments as required Communication equipment
Copyright EIL All rights reserved

Format No. EIL 1650-1296P Rev. 2

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 10 of 29

Fire detection and alarm system DC supply system Ups System Firefighting equipment excluding main firewater pump. Loads critical for process , plant and personnel safety Project specific loads other than above for commercial reasons. Emergency power could be from a different power source or Emergency generator as per project design basis / SLD. Where emergency generator is envisaged emergency power supply shall be made available within a time period of 30 seconds from the instant of failure of normal supply / under voltage system activated. Manual start provision shall be provided in the system .

5.13

Uninterrupted Power Supply (UPS) Uninterrupted power supply system shall be provided for meeting critical loads that cannot withstand a momentary interruption in voltage like critical instrumentation and control system equipments like DCS , PLC etc . Separate battery bank shall be provided for UPS system. Battery backup time shall be as specified in project design basis. The UPS system shall be double redundant ( battery bank, charging and inverter units ) with a single automatic regulated by pass arrangement

5.14

Power Factor Improvement Capacitor banks shall be provided to improve the power factor in order to meet the minimum stipulated power factor by the power supply authorities. Absence of regulation design consideration needs to given to meet 0.9 lagging. Harmonics Elimination Design consideration and equipment selection needs to carried out to reduce the overall harmonics within 5 % in the system by following ways Harmonics needs to reduced at the source of generation like VFD , UPS etc and all this equipments needs to meet IEEE 519 compliance and within 5 % THD .

5.15

6.0 6.1

EQUIPMENT DESIGN PHILOSOPHY General The equipment shall in general confirm to CEIL standard specification. Equipments shall be selected and sized as per philosophy given below Transformers 6.2.1 All transformers except lighting transformers shall be three phase, oil immersed, double wound type suitable for outdoor use, unless otherwise specified. Lighting transformers shall be dry type unless otherwise specified In general KVA rating and percentage impedance of each transformer shall be selected to limit the rated current and short circuit current o values which are within the current rating and interrupting capacity of switch gear available.

6.2

6.2.2

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 11 of 29

Transformers rated more than 2500 KVA shall have provision for fan cooled rating unless otherwise specified to increase the rating from the normal specified rating . The KVA rating shall be decided on the following basis and should be as far as possible a standard value. Sizing shall include 10 Percent margin for future growth. In systems having redundancy for transformers, with transformers without any forced cooling, each transformer shall be rated to or equal to or greater than the 8 hr maximum demand of the load plus 10 % margin for future growth. In systems having redundancy for transformers, with transformers having forced cooling , each transformer shall be rated equal to or greater than the 8 hrs maximum demand of the load plus 10 % margin for future growth within 110 % of its self cooled ONAN rating and shall be fitted with automatic forced air cooling fans . Where redundancy in number of transformers is not provided, rating shall be equal to generated than 8 hr maximum demand plus 10 percent margin for future load growth. fan cooled rating , where applicable , shall be reserved as spare capacity for further future load growth . 100 % stand by transformers shall be provided in all unit offsite and utility substations unless otherwise specified. Unless otherwise specified dry type transformers shall be used for Heat tracing and lighting transformers. Heat tracing transformers shall be rated for 30 % spare capacity considering the unequal loading. Heat tracing transformers secondary side shall be protected with ELR and CBCT with CBCT installed on the secondary side in the transformer itself.

6.2.3

6.2.4

6.2.5

6.2.6

6.3

Switch Gear 6.3.1 All switchgear and associated equipment fed from generators and transformers shall have rating at least equal to the rating of respective generator and transformers feeding it, under any circuit configuration. Generator incomer shall be rated to the maximum power output of the generator set over entire operating temperature range. Transformer incomer shall be rated equal to forced cooled rating of transformer or 110 % of ONAN rating as applicable. Bus tie circuit breakers shall have rating higher of the following 6.3.3 Largest incoming circuit breaker Maximum running load on either side of the bus section

6.3.2

All other switch gears not directly fed from generator and transformers shall have rating at least to the maximum demand under any circuit configuration plus a provision for 10 % future load growth. Incomers of these switch gears shall be designed to cater to the complete load including 10 % margin for future load growth All HV switch gear up to 33 KV shall be GIS and VCB / VC for individual feeders depending upon the utility All HV breakers above 33 KV shall be GIS switch gear with SF6 breakers for individual feeders Spare outgoing feeders shall be provided in all the switch gear. For HV switch boards the number of spares shall be as indicated in SLD / Project specific Design basis.

6.3.4

6.3.5

6.3.6

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 12 of 29

6.3.7

For other switch boards ( and where not specifically indicated in the SLD including HV switch gear , at least one number of each type of outgoing feeders or 10 % of each out going feeder whichever is more shall be provided as spare in switch boards Separate feeders shall be provided in the switch board for each load / motor. However as an exception maximum two numbers of welding receptacles may be connected to one power feeders looped from the first to second receptacles Circuit breakers / contactors controlling motor feeders shall have a rating of at least 125 % of the maximum continuous rating of the connected motors.

6.3.8

6.3.9

6.3.10 All circuit breakers shall be of single break type having one pole per phase. Circuit breakers for MV generator incomer shall be with four poles. Alternatively three phase breaker with adequately rated air break contactor for neutral isolation may be provided where ever applicable. 6.3.11 In case of HV vacuum circuit breaker, surge suppressors shall be provided for all out going feeders . 6.3.12 All High voltage feeders and incomers shall have Numerical protection relays according to their service like transformers, generators, motors 6.3.13 Rated service short circuit breaking capacities (Ics 0 for all breakers and MCCBs shall be equal to or higher than the maximum specified value of short circuit current at the point of installation . MCCB with backup fuses are not acceptable. 6.3.14 Air circuit breakers (ACB) shall be provided in MV ( 415 Volts and below ) switch boards for all feeders rated from 400 A and MCCB s shall be provided for all feeders rated below 400 Amps . Switch fuse unit is not acceptable 6.3.15 All MCCBs, ACBs for individual feeders, incomers otherwise specified. shall be communicable type unless

6.3.16 Circuit breakers for capacitors shall have a current rating of at least 135 % of the capacitor rated current. Circuit breakers capability to interrupt applicable capacitive current shall be specifically verified. 6.3.17 The switch board components like circuit breakers , Main horizontal and vertical bus bars , bus bar joints , bus bar supports etc shall be designed to withstand the maximum specified short circuit current for a minimum of 1 second , unless otherwise specified . 6.3.18 For motors rated above 5 .5 KW, CT shall be provided in the switch gear for ammeter on the local push button station. 6.3.19 The maximum rating of bus bar for MCC / ACB / LDB should preferably be limited to 800 amps. ACB shall be used for incomers and the tie breakers and these shall have suitable mechanical interlocks. 6.3.20 Top entry bus duct as incomer for PMCC/PCC fed from Transformers rated 750kVA and above and bottom entry cables as incomers for other boards. Bottom entry cables as feeders for all boards or us specified during detailed engineering 6.3.21 Start / Stop control from DCS, emergency stop form ESD system, shall be hard wired Motor ON / OFF status indication to DCS shall be soft communication however provision shall be made in the system for hard communication as well 6.3.22 Other communication between the DCS and ACB incomers/ feeders, will be via TCP / IP Mod bus protocol
Format No. EIL 1650-1296P Rev. 2 Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 13 of 29

6.3.23 Control room to interface with Instrumentation via marshalling cabinet / data concentrator or project specific. 6.3.24 All feeders for motor shall have motor control unit (MCU) and shall be microprocessor based devise with integrated control , monitoring and protection functions with a communication facility serving a single power module . The MCU shall be configured to suit the protection, control and monitoring requirements for following motor starter functions . Non reversing direct Online Reversion Direct Online ( Rev DOL ) Star delta Motor ( SD )

MCU protection device are to include the following options as minimum . Thermal Over load Under load , stall protection under voltage detection Earth leakage Motor temperature protection by probes Phase Imbalance and loss protection Long start protection ( stall )

All MCU data shall be available via serial link via modbus TCP / IP to the central communication system for Electrical system and DCS / ECS. 6.3.25 Similarly all Power feeders shall be fully self contained and draw out type fitted with MCCB which shall be used as Isolator, short circuit protective device, Over current protection, measuring units for current and voltage measurement for data logging. 6.3.26 All feeders shall include as a minimum on /off indicating lights and trip indication 6.3.27 All outgoing feeders will have earth fault protection 6.3.28 Tropical protection for PCC/PMCC/MCC 6.3.29 Thermostatically controlled space heater for panels 6.3.30 All the switch boards Suitable for future expansion on both sides 6.3.31 Bus bars for the switch boards shall be copper unless otherwise specified 6.3.32 The switch boards shall have centralized individual HMI Unit to monitor all feeders and incomers of the particular switch boards feeders. This unit shall have additional features to interface with DCS, SCADA, Power management system etc based on overall system philosophy of specified project. 6.3.33 All HV switchgears shall have IR windows installed as per OEM design 6.3.34 The vertical / horizontal / tap off bus bars shall be insulated and all joints shall be shrouded with high thermal capability non flammable shrouds 6.3.35 The protective relays of switchgear shall have a dedicated control MCB 6.3.36 The short circuit capacity of current transformers shall be in accordance with the short circuit capacity of the switchgear
Format No. EIL 1650-1296P Rev. 2 Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 14 of 29

6.3.37 The switchgear control shall be designed for earthing through earthing truck and At least two earthing truck per rating of switch gear shall be considered per switchboard 6.3.38 All switchgear, modules shall be suitable for applying Lockout procedure and shall be designed to have all safety features not to have access to live terminals and interlocks to ensure to protect accidental closing while racking in and door opening while in service 6.3.39 The transformer incomer feeders shall have NGR monitoring relay as well apart from other protective relays as appropriate 6.4 BUS DUCT 6.4.1 LV bus ducts will be provided for interconnection of transformers rated 750kVA and above from the transformer secondary to the 415V PMCC/PCCs. Non-phase segregated, self cooled type, 3 phase, 3 wire. Copper bus bars with heat shrinkable PVC Sleeves. Enclosure will be fabricated from 3mm thick (min) aluminum sheets for ratings above 3000A and 2mm thick (min) sheet steel otherwise. Seal-off bushings with wall frame assembly wherever the bus duct crosses wall from outdoor to indoor All bus ducts shall have temperature monitoring system and connected to nearest data concentrator or switch board HMI or DCS. If there is no provision to hookup to the nearest system then standalone temperature indicator with alarm shall be provided The Rating of the bus bar ducts connected to breakers shall have same continuous and short circuit rating as that of breakers. Similarly bus ducts connecting to two bus sections shall have same continuous and short circuit rating as that of main bus bars Neoprene rubber bellows for enclosure wherever expansion joints are provided. The outdoor portion of the bus bar shall be minimum IP 55

6.4.2 6.4.3 6.4.4

6.4.5

6.4.6

6.4.7

6.4.8 6.4.9

6.4.10 The adopter box on both ends of the bus duct shall be designed as part of the bus duct.

6.5

Neutral Grounding Resistor The NGR shall be rated to withstand the fault current for 10 seconds and shall be out door type with IP 55 enclosure. The NGR element shall be stainless steel / nichrome Electric Motors 6.6.1 In general, three phase squirrel cage motors designed for direct online starting shall be used. Motors shall be totally enclosed, fan cooled type and suitable for continuous outdoor use. All motors shall be continuous maximum rated with possible exception of crane and hoist motors, soot blowers, turbine starting motors etc., which may be rated for the envisaged duty cycle High voltage motors shall be suitable for starting under specified load condition with 80 % of the rated at the terminal s and medium voltage motors shall be suitable for starting under specified load condition with 75 % of the rated voltage at the terminals. For heavy duty motors such us reciprocating compressor /agitator/crusher etc .high starting torque motors shall be provided and starting time shall be limited to ensure adequate protection by motor protection relays.
Copyright EIL All rights reserved

6.6

6.6.2

6.6.3

6.6.4

Format No. EIL 1650-1296P Rev. 2

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 15 of 29

6.6.5

Induced voltage across the shafts ends of motors shall not exceed 200 mv (rms) for ball and roller bearings and 400 mV (rms ) for sleeve bearings . Wherever it exceeds specified limit, the non driving end bearing shall be insulated from the motor frame to avoid circulating current. The insulated bearing end shield or pedestal shall bear a prominent warning.

6.7

Control Station 6.7.1 Motors shall be controlled in the field at the motor location. Local control station shall have Start / Stop pushbuttons and HOA selector switch. In H position start control transfers to only local, in A position control transfers to DCS, while in O position, the motor start is disabled. Circuit breakers shall be wired for both local and remote operations. Local-Remote Selector Switch for contactor fed motor shall be located in the 415V PMCC/PCC/MCC DCS shall control and monitor motors through logic or by the control room operator. Each starter shall have an ESD stop in the control circuit. Each substation shall have two operator consoles (workstations) for monitoring and control of protection relays.

6.7.2 6.7.3

6.7.4

6.7.5

6.8

Black Start and Emergency Generators 6.8.1 The Black Start and Emergency System shall consist of packaged diesel generators each housed in a self container shipping enclosure complete with intake air louvers, exhaust, silencer, controls, air start compressor, battery chargers and battery banks, etc. Quantities and ratings of the packaged generators will be indicated on the single-line diagrams. The Emergency generator set shall be designed to start automatically on power failure and fee the selected loads. It shall be capable of taking care of the load variations like starting of largest motor with specified base loads. Generator shall be designed to take care of harmonics as per IEEE 519. All the generators shall equip with Numerical Generator Protection system and synchronizing panel and shall be capable for parallel operation with the main grid. The Emergency generator set shall have at least 10 % spare capacity for meeting future requirements The Package shall be installed with fire suppression and F&G systems which are compatible with the plant F&G system. All emergency / backup generators shall have 1 + 1 redundant battery system with dedicated battery charger and shall have provision for both trickle and boost charging The exhaust of emergency / backup generators shall be designed to meet necessary pollution control board regulations All the engine parameters shall be monitored and shall be controlled with suitable PLC in place. The DG sets shall be preferably located in a separate building other than the E-house, in a safe area to reduce noise level in substation. Exhaust of diesel engine shall be kept away from the process/hydrocarbon handling areas and diesel day tanks shall be located outside the DG room. Suitable ventilation system shall be provided to avoid heat accumulation in the DG room.

6.8.2

6.8.3

6.8.4

6.8.5

6.8.6

6.8.7

6.8.8

6.8.9

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 16 of 29

6.9

Lighting Systems 6.9.1 Plant lighting will be broadly classified into 3 categories Normal lighting Emergency lighting Critical lighting

Normal and emergency lighting will be on 240V AC (phase-phase) Supply whereas critical lighting will be on 110V DC. In CPP and Mangala Process Terminal area, under normal conditions, both emergency and normal lighting will be fed by normal power source. On failure of normal supply, emergency lighting loads will be fed from emergency generator supply. Critical lighting shall be automatically kept ON during normal/emergency power failure by 110V DC battery. In the event of normal power failure, emergency lighting may be provided to facilitate safe shutdown of the plant, access to fire fighting facilities and escape route for safe evacuation of plant operating personnel. Emergency lighting will be 20-25% of normal lighting load. Probable areas for critical lighting are Control Rooms, Substations, Central Fire Station, Emergency Escape Routes, critical valves and devises identified for safe shutdown etc. Well pads and remote area terminals will not have emergency lighting due to absence of emergency power source. Instead critical lighting with self contained battery will perform the functions of emergency lighting.

6.9.2

415/240V, 3ph, 50Hz lighting transformer of adequate capacity will be used to feed AC lighting circuits. Lighting transformers shall be located inside floor/wall mounted Sub Lighting Distribution Boards. Lighting power distribution shall be through Main Lighting Distribution Boards (MLDBs), Sub Power and Lighting Distribution Boards (SPLDBs) and Sub Lighting Distribution Boards (SLDBs). MLDBs shall receive 415V, 3ph, 50Hz supply from PMCC/PCC/MCC and distribute to SPLDBs in each building. SPLDBs apart from feeding HVAC and other three phase power loads, shall also feed SLDBs. SLDBs shall have 415/240V, 3ph, 50Hz lighting transformer of adequate capacity Separate panel boards are provided for indoor and outdoor lighting. Enclosure of indoor panel boards will have min IP 4X protection and outdoor panel boards will be housed outdoors in an IPW 55 enclosure. Lighting circuits will be R-Y, Y-B, B-R and emergency repeated in series. Branch circuit protection shall be provided by miniature circuit breakers (MCBs). The total estimated load of each circuit shall not exceed 80% of the branch circuit rating. Lighting methods and material shall be suitable for the area classification in which they are to be installed. Indoor Lighting Each lighting circuit load shall not exceed 2000VA (240V, 2ph). 2 x 36 Watts, decorative, mirror optic, low glare, high power factor, surface mounted fluorescent lamp fixture for Control Room and offices. Industrial type, slotted reflector, open bottom in utility areas. Lighting for Control Room will be two levels.
Copyright EIL All rights reserved

6.9.3

6.9.4

6.9.5 6.9.6

6.9.7

6.9.8 a. b.

c. d.

Format No. EIL 1650-1296P Rev. 2

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 17 of 29

e. 6.9.9

Switching will be local double pole toggle devices. Outdoor Lighting

a. Each lighting circuit load shall not exceed 6000VA (240V, 3ph). b. Control is photocell/timer switching with manual override of 3pole contactors fed from 32A. c. 32 Amp, 3 pole outdoor panel board circuit breakers. Cable size for exterior lighting circuits shall be a minimum of 3/C 6mm2. However, final lighting feeder sizes shall be determined after all de-rating and voltage drop factors are considered, especially the extended distances involved.

d. Aircraft warning lights shall be provided for structures of height 20 meters and above such as communication tower and flare stack as per Directorate General of Civil Aviation (DGCA) regulations. e. Staircase and exterior lighting will be wall/back mounted compact with side hinged cover, aluminum housing, epoxy finish, 240V ballast suitable for 100W metal halide (MH) lamp. f. Flood lighting fixture will be die cast aluminum, multi-tap ballast; yoke mount with slip fitter adapter 400W MH mounted on 12m galvanised steel poles, 2 per pole.

g. Flood lighting using adequate number of 400W die-cast aluminum metal halide fixtures mounted on 25m, galvanised steel pole may also be used. In which case it will be possible to lower / raise the fixtures manually and electrically for bulb replacement. h. Street lighting will be standard cobra head luminaries, 240V ballast, 250W MH, on a 9m galvanized steel pole 6.9.10 Levels of illumination for the design of lighting systems shall be based on the illumination intensities as per OISD Recommended Practice 149. Some of the values are summarized as given below: Area Description Control Room Inst, Equipment room/Offices/Laboratory Substation/Switchgear Room/UPS Room Kitchen/Mess/Prayer Room/Guard Room Shelter for other skids Outdoor Areas and Roads Outdoor Operational areas/Platforms Walkways/Staircases Change Room Toilet Lux 500/250 lux 2 level 300 lux 200 lux 300 lux 150 lux 10 lux 50 lux 50 lux 100 lux

These are in-service values after applying a maintenance factor of 0.7 and a utilization factor depending on the type of the fixture. These figures are the minimum vertical component values for the locations described on a horizontal plane being 0.75m from the floor levels in buildings and the ground or platform levels in other areas Solar Power: All the building shall have roof mounted solar PV modules and associated systems to cater the power required from Normal and emergency power DBs during day hours. 6.10 SOCKET OUTLETS

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 18 of 29

6.10.1 Single phase socket outlets shall be fed at 240(ph-ph) from Sub Lighting Distribution Boards. Three phase socket outlets / welding receptacles shall be fed from SPLDBs located in Substation / Facility buildings 6.10.2 Receptacles will have necessary mechanical interlocks, suitable protections for site conditions and earthing facilities. All receptacles will have looping facility. 6.10.3 Substation, Control Room and Office Rooms will have decorative type receptacles, with ELCB (100mA sensitivity) controlled socket, 240V, 1 phase 15 A, 3 pin at 10 meter interval. Not more than four socket outlets shall be supplied by one circuit. 6.10.4 In plant area 240 V, 2 phase, 15 A, 3 pin ELCB (100mA sensitivity) controlled industrial type receptacles will be provided at 15m spacing. 6.10.5 In outdoor area, 415 V, 63 A, ELCB (100mA) controlled TPNE welding socket spaced 50m apart. 6.10.6 A maximum of two welding receptacles will be connected in one circuit. 6.10.7 All outdoor socket outlet/ receptacles will be of flameproof (Ex d) construction and rated for temperature class T3, gas group IIA/B. 6.10.8 One outdoor 415V, 3 Phase+ E, 200A socket outlet shall be installed for each group (every 2) of power transformers, for oil treatment purposes. 6.10.9 All receptacles specified above shall have interlocked type and provided with one matching plug. 6.10.10 All receptacles shall have looping facility 6.10.11 All the sockets shall have cable entry at the bottom. 6.10.12 Each branch circuit shall be protected with EL+MCBs and the main incomer shall have ELCB in addition to the MCB / MCCB 6.10.13 Each branch circuit shall be double pole unless otherwise specified 6.10.14 The control rooms shall be provided with critical lighting fed from utility UPS supply. 6.11 Earthing and Lightning Protection 6.11.1 Earthing systems power system neutral earthing and plant earthing. Power system neutral earthing employs following methods: a. b. Solid earthing for 33kV system High resistance earthing for 415V system

6.11.2 Plant earthing design will generally be carried out in accordance with the requirements of Indian Electricity Rules and Code of Practice for Earthing BIS 3043. 6.11.3 Earth fault protection relays shall be provided for HV/LV distribution systems to limit the fault current to a maximum of 750 milliamps for 415V systems and 100 Amps for 33kV system. 6.11.4 The resistance value of plant earthing system will not be more than 1 Ohm. 6.11.5 Main earth grid of 70mm2 bare copper conductor will be used below ground. Above ground green / yellow PVC insulated copper conductors shall be used. 6.11.6 Earth rod of 20 mm diameter 3m copper clad steel rods shall be used
Copyright EIL All rights reserved

Format No. EIL 1650-1296P Rev. 2

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 19 of 29

6.11.7 Earthing of HV motors will be provided by connection to the main earth grid with 70mm2 PVC insulated copper conductors. LV motors, cable trays, metallic equipment, enclosures and other items listed in paragraphs 6.11.10 and 6.11.11 below will be connected to the main earth grid with 35mm2 PVC insulated copper conductors. 6.11.8 A separate ground system for the Instrumentation , DCS , ECWS etc shall be established as specified requirements . The UPS shall be grounded to this system ground bus. The resistance of this grounding system shall not exceed 1 ohm. 6.11.9 The step and touch potential calculations will be based on a soil resistivity report. 6.11.10 The following shall be connected to ground system at one location a. b. Cable armoring (single core power cables) Metallic enclosures of electric equipment including cable boxes, local control stations etc Lighting poles Lighting fittings and control panels Lightning protection ground rods

c. d. e.

6.11.11 The following shall be connected to ground system at two locations: a. b. c. d. e. f. g. h. i. j. k. l. m. n. Cable armoring (multi-core power cables) Generator and Transformer neutral points Transformer tank bodies Substation building ground bus bars High Voltage Switchboards and PMCC/MCC/PCC ground buses Motor / generator machine frames Buildings (metallic parts / piles, 1 per corner) Pipe rack steel Frames of skids Tanks, vessels, towers, stacks Base plate of rotating machinery All non-current carrying metallic structures All metallic structure / units Metal fences, gates, side rails etc ( Shall be earthed at every 3 meters and wherever the fence direction changes ) All metallic structure / units including permanent access ladders

o.

6.11.12 Grounding cable joints shall be: Compression type below grade Bolted or compression type joints (above ground).

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 20 of 29

6.11.13 Lightning protection will be provided to equipment, structure and buildings which are higher than 20 meters or as per the risk index analysis worked as per IS 2309 / BS 6651. For lightning protection, the value of 5 Ohms as earth resistance will be desirable. 6.11.14 Lightning protection system shall consist of air rods, down conductors and ground rods. Air rods shall be of fully stainless steel (316). Installed as follows: a. Drive a 3m long ground rod 1m from the structure; connect the rod to the unit with minimum 70mm2 green/yellow insulated copper conductor. Connect the rod to the plant system ground grid with a 70mm bare copper conductor routed below grade. Repeat this procedure at each unit.
2

b.

c.

6.11.15 All earth pits shall be chemically treated type 6.12 AC/DC Distribution Boards 6.12.1 This section covers main and sub distribution boards required for distribution of 415V for non motor loads, 240V/230V (UPS)/110V DC power for loads and lighting 6.12.2 Indoor use, metal clad, vertical self-standing or wall mounting type, with min. IP 4X enclosure in Substation/PMCC room and for other places min. IPW 55 6.12.3 Generally single incomer with associated protection and control logic 6.12.4 Generally for incomers and feeders MCCBs will be used. 6.12.5 Single front, fixed-out type construction. 6.12.6 Copper bus bars with heat shrinkable PVC Sleeves. 6.12.7 Identical breaker/contactor will be interchangeable. 6.12.8 Top or bottom entry cables as incomers and feeders 6.12.9 Tropical protection for AC/DC Distribution Boards 6.12.10 Thermostatically controlled space heater for panels 6.12.11 10 % spare feeders shall be provided in DBs 6.12.12 All the DBs shall have cable entry at the bottom. 6.13 DC Power Supply Systems 6.13.1 DC Power supply system comprises the converters, battery banks and the Main DC Distribution Boards (Main DCDBs). 6.13.2 System shall supply continuous 110V dc power to HV and LV switchgear, relays and critical lighting. 6.13.3 The dc power supply system shall be a fully redundant system consisting of two units operating in parallel. 6.13.4 Each unit shall consists of one 100% nickel cadmium battery bank, one 100% Float-cumboost charger with 100% loading capability but operating at 50% load. Batteries shall be placed in a separate well ventilated room on racks. 6.13.5 In case of normal power failure to the float-cum-boost chargers, each battery unit shall have sufficient capacity to supply the total 110V DC system loads for 1 hour. Each battery unit
Format No. EIL 1650-1296P Rev. 2 Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 21 of 29

shall cater to 50% of the loads (ie., connected only to the respective Main DCDB) for 2 hours. 6.13.6 Under normal condition the Float-cum-boost charger will take care of all DC load connected to its Main DCDB and keep the battery under charged condition. In case of failure of normal supply, battery will feed the DC load requirement. Retransfer of load on resumption of normal supply will be done without interruption of supply to loads. 6.13.7 AC input to the DC system shall be 415V 6%, 3 phase, 50Hz+ 3% from the plant 415V CPP Emergency Power and Motor Control Center. 6.13.8 Ingress protection of panels shall be IP41. 6.13.9 A relay shall be connected to the DC busbars in the DC Power System to detect the presence of earth leakage current flowing due to a fault somewhere in the outgoing subcircuits. This relay shall be sensitive to a low level of current (in the order of milli-amps), and shall raise an alarm when the current exceeds a pre-set level. 6.13.10 The battery charger / rectifier shall feed the load and keep the batteries under fully charged condition. Provision shall also be made for necessary boost charging / initial charging of battery 6.13.11 Each battery charger and DCDB shall be sized to cater to selected battery capacity 6.13.12 Each DCDB shall have at least 10 % spare for future loads 6.13.13 All the DBs shall have cable entry at the bottom. 6.13.14 The battery chargers shall have intelligent monitoring / metering system and shall display the capacity of the battery, battery voltage, rectifier voltage and current and events and alarms and communicable for remote monitoring 6.14 Uninterruptible Power Supply (UPS) System 6.14.1 Uninterruptible Power Supply system comprises the converters, inverters, static automatic transfer switch, battery banks, constant voltage by-pass transformer with maintenance by pass switch and Main UPS Distribution Board 6.14.2 One complete Uninterruptible Power Supply (UPS) system consisting of two parallel units (for redundancy) shall be provided for powering the plant DCS, FGS, SIS and I/Os. 6.14.3 The system input shall be 3 phase, 415V 6%, 50Hz+ 3% , Output shall be 230V 1%, 1ph, 50Hz 1%. 6.14.4 UPS system shall consist of two parallel units (each including a 100% converter, a 100% solid state inverter, 100% nickel cadmium battery bank, static automatic transfer switch), and a constant voltage by-pass transformer with maintenance by pass switch. Batteries to be placed in a separate well ventilated room on racks. 6.14.5 Both units shall operate in parallel, each shall provide 50% load but each shall have 100% loading capability. Battery backup time shall be at least 2 hours for each battery unit and total of 4 hours for the complete system. 6.14.6 Under normal condition, the converter will feed the inverter load requirement through static switch and keep the battery under charged condition. On failure of supply to converter, the battery will start feeding the inverter load requirements automatically without interruption. Reverse transfer on resumption of normal power will also be automatic. The inverter will be operating in synchronization with the bypass mains within specified voltage and frequency limits.
Format No. EIL 1650-1296P Rev. 2 Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 22 of 29

6.14.7 Usually, the two UPS units will operate in parallel and share total load requirement equally. On failure of inverter of one of the UPS the other UPS will start feeding 100% of the load automatically without any interruption. In case of failure of both the inverters, the bypass mains will take care of 100% of the load through static bypass switch automatically without interruption. Forward and reverse transfer of load will be done automatically and without any interruption of supply to loads. 6.14.8 UPS shall be fed from 415V Emergency PMCC. Out of three inputs one input can be fed from Normal power supply also. 6.14.9 Ingress protection of panels shall be IP41. 6.14.10 A relay shall be connected to the AC bus bars in the UPS to detect the presence of earth leakage current flowing due to a fault somewhere in the outgoing sub-circuits. This relay shall be sensitive to a low level of current (in the order of milli-amps), and shall raise an alarm when the current exceeds a pre-set level. 6.14.11 UPS system shall be sized to take care of the crest factor of the load current. 6.14.12 Each branch circuit of the UPS distribution system shall have a fast acting MCB with auxiliary contact for alarm in each circuit of distribution . The MCB shall be fast clearing type and the MCB rating shall be coordinated with the rating of the UPS system . Normally the largest branch circuit shall not exceed 25 % of the UPS system rating. 6.14.13 Each UPS shall have at least 20 % spare feeders and the UPS shall be designed to cater additional 20 % for future loads 6.15 Batteries Batteries shall be of adequate capacity to meet the backup requirements as envisaged in the duty cycle as well as to take care of future load growth of 10 %. While sizing the battery, temperature correction factor, and ageing factor shall be considered in addition to the maintenance factor. Batteries shall be complete will battery rack and shall be maintenance free. Cables 6.16.1 Hv cables shall be dry cured XLPE insulated, extruded PVC sheathed, armored type with copper conductors. All cables rated for 3.8/ 6.6 KV above shall be provided with both conductor screening and insulation screening 6.16.2 MV power cables shall be XLPE insulated, extruded PVC sheathed, armored type with copper conductors. 6.16.3 The control cables shall be PVC insulated, extruded PVC sheathed, armored type with copper conductors. Special cables like twisted or shielded control cables etc shall be used as applicable for numerical relays, VSD etc to suit selected equipment as per equipment suppliers recommendation. 6.16.4 The cables shall be sized based on the maximum continuous load current, the voltage drop, system voltage, system earthing and short circuit withstand criteria as applicable. The de rating due to ambient air temperature, ground temperature, grouping and proximity of cables with each other, thermal resistivity of soil etc shall be taken in to account. 6.16.5 Cables connected in parallel shall be of the same type, cross section and termination. 6.16.6 As an exception within substation areas, un-armored cables may be used if specified and agreed upon 6.16.7 All power and control cables shall be in continuous lengths (unless otherwise agreed upon) without any splices or intermediate joints. The cables used for lighting and wires in conduits
Copyright EIL All rights reserved

6.16

Format No. EIL 1650-1296P Rev. 2

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 23 of 29

shall have appropriate junction boxes with adequately sized terminals. Unless otherwise agreed, cable joints in hazardous area shall not be permitted. 6.16.8 Outer PVC sheath of all cables used shall be flame retardant type conforming to category AF as per IS: 10810. 6.16.9 The cable shall have a low smoke or zero halogen property. The minimum Oxygen Index shall be 29 6.16.10 All incoming cables to switch gear / UPS/ DC system / DBs and other equipment shall be sized for maximum load including 10 % future load growth. Cable for capacitor banks shall be sized for 135 % of the rated capacitor current. 6.16.11 Maximum cross section area for multi core cables is 300mm2 and 630mm2 for single core unless otherwise agreed upon. 6.16.12 All control cables shall have minimum 10 % spare cores, except that control cable having seven cores may have one core as spare. 6.16.13 Cables shall be designed to Bureau of Indian Standards (BIS) 6.16.14 The armor for single core cables shall be of non magnetic material. 6.16.15 Fire resistance cables shall be used for ESD, telecom and other critical systems 6.16.16 Conductors of all sizes of cables shall be stranded and shall not be solid copper . 6.16.17 6.6KV and 11KV cables shall be Unearthed UE grade where as the 33KV and 415 V cable shall be Earthed (E) grade. 6.16.18 The cable outer sheath shall have special coating / treatment for UV protection 6.17 Cable Tray 6.17.1 Cable tray will be manufactured as galvanized steel ladder type, H style, with 157mm (6) side rails and 129mm (5) loading depth, using standard widths of 900 mm (36), 600mm (24), 300 mm (12), or 150mm (6). Ladder rung spacing shall be 225mm (9) on centers. 6.17.2 Cable tray shall have 1.5 safety factor and be capable of bearing149kg/m (100lb/ft) load for 900mm width, be supported at 6m span intervals, and same equivalent for other sizes. Actual cable tray length must be equal to or exceed the supporting span interval. 6.17.3 Cable trays shall be routed on dedicated tiers of the pipe racks and on sleepers to equipment. When required, inverted V type cable tray covers shall be used. 6.17.4 A separate tray system will be utilized for each voltage level as indicated in the Cable Tray Voltage Separation Matrix below: Cable Tray Voltage Separation Matrix

Cable Tray Voltage/Type (see legend below) A B C D


Format No. EIL 1650-1296P Rev. 2

Separation of Cable Trays (mm) A 150 150 150 150 B 150 150 150 150 C 150 150 150 150 D 150 150 150 150 E 600 600 600 150 F 600 600 600 150
Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 24 of 29

E F

600 600

600 600

600 600

150 150

150 150

150 150

Cable Tray Voltage/Type Legend A. B. C. D. E. F. 33kV 11kV / 6.6 kV Low Voltage Power (415V / 240V Lighting / 230V UPS / 110VDC) Control (240V Motor Control / 240V Lighting) Instruments / Fire and Gas / Fiber Optic Paging and Alarm

Note: For all cable trays stacked vertically, there shall be a minimum vertical working clearance of 300mm from the top of the lower tray to the bottom of the tray above. 6.17.5 Multi-core HV cables will be arranged in a single layer with one cable diameter spacing between them. Single core HV cables shall be arranged in trefoil formation in single layer, with one trefoil cable diameter spacing between them. 6.17.6 Low voltage power cables will be arranged in single layer with no spacing between them in single layer. 6.17.7 Motor control cables will be laid with no spacing between them horizontally and vertically in two layers. 6.17.8 In case separate trays are not practical for power and control cables, barriers shall be used in same cable tray. 6.17.9 Instrument cable trays will be loaded to 50% of the total available cross sectional area of a given cable tray. This area is determined by multiplying the inside width by the allowable loading depth, times 50%. 6.17.10 If required, two optical fiber cables shall run for redundancy, in different trays / routes. However, lengths must be the same within 10m. 6.17.11 Trays will be connected by expansion splice plates between their sections and fitted with expansion guide clamps at every 36 to 40m intervals. Tray will be connected at other junctions by standard splice plate and fitted with hold-on clamps. 6.17.12 The trays shall be supported at appropriate intervals both vertically and horizontally, as required by the cable tray manufacturers design criteria. 6.17.13 The maximum length of single cable tray shall be 3 Meters. 6.17.14 Ladder type cable trays shall be manufactured and installed in accordance with the following: NEMA VE-1 NEMA VE-2 IEC 61537
Format No. EIL 1650-1296P Rev. 2

Metallic Cable Tray Systems Metallic Cable Tray Installation Guidelines Cable Tray Systems and Cable Ladder Systems
Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 25 of 29

6.18

Equipment Enclosures 6.18.1 All equipment shall be entirely suitable for the site service conditions as specified in specifications and shall be protected against dust, humidity, sulfurous and atmosphere and designed to obviate the entry of vermin and insects. 6.18.2 The degree of protection for enclosures shall be according to IEC 60529 and IEC 60144 as follows: Indoor equipment : IP 4X

Outdoor Equipment : IP 55

6.19

Actuators for Motor Operated Value MOVs shall be provided with integral starters. the necessary local / remote selector switch , start / stop control switches or push button s , torque limit switches etc shall be provided on actuator for local / remote control depending on the mode of selection . In case of failure of torque limit switches, the mechanical design shall be adequate to stall and trip the motor without any damage. The control circuit may AC operated for short distance and DC operated for extended distances where required. MOVs with 2 wire control shall comply to job specification and control supply shall be supplied therein.

6.20

EHOUSE SUBSTATION BUILDING E-house Sub station shall be Modular type E-House will be under CPF Contractors scope and shall comply with Specification for Packaged substation, CAIRN-TSG-E-SP-0023..

6.20.1

Sub-station shall have fire extinguishers, first aid boxes and other safety equipment as Per statutory requirements. Insulating mats shall be of synthetic rubber and required voltage rating shall be provided in front of switchboards. Separation walls between transformers in all substations and safe inter transformer distances for switchyard transformers shall be as per clause 5.3.11 & 5.3.12 of OISD Std- 173. Equipment like transformers, neutral grounding resistors, reactors and HV capacitor Banks shall be located in bays adjacent to the sub-station building. All bays shall have well drained floor, surfaced with gravel or other suitable material. In order to prevent oil, whether from a small leakage or outflow from transformer tank, from reaching and polluting the water bearing stratum, transformers shall have the following provisions, depending on the oil capacity of the transformer. Oil Capacity up to 2,000 liters: Transformers installed adjacent to sub-station/buildings or in Switchyards shall be provided with a layer of 100 mm deep stones of about 40 mm granulation, all around the Transformer, for a width of 20 % of the transformer height or with a minimum width of about 800 mm.

6.20.2

6.20.3

6.20.4

6.20.5

6.20.6

Oil Capacity exceeding 2,000 liters: Transformers installed with oil containing pits. adjacent to sub-station/building or in Switchyards shall be Provided
Copyright EIL All rights reserved

Format No. EIL 1650-1296P Rev. 2

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 26 of 29

The oil containing pit may be shaped as per OISD standard 173. The pit shall extend all around the transformer for a width of 20 % of the transformer height, with a minimum width of about 800 mm. In case oil capacity exceeds 9,000 liters, in any chamber, provision shall be made for draining away of any oil, which may escape or leak from the tanks, to a waste oil tank. 6.20.7 The following clearances will be maintained around equipment as minimum, unless specified otherwise:

Sl. NO 1 2 3 4 5

Description Front clearance for HV Switchboard Front clearance for other switch boards Rear Clearance for HV switch board Rear clearance for other switchboard which requires Maintenance switch board Rear clearance for MV switchboard and other panels which requires no Maintenance on the rear side and the panels rear is not having any openings Side clearance between switch boards or from nearest obstruction Clear height of bus-duct from FFL Head clearance

Clearance 2500mm 2000mm 1500 mm 1000 MM 200 mm or more than 1000mm.

1000 mm after considering space for future panels as specified . 3000mm 2000mm

7 8

Battery rack to wall for clearance for Single row / double tier Double row , single tier Double row , double tier Front clearance for wall mounted equipment Front clearance for operation station annunciation / control panel Front-Front of 2 switchboards facing each other

100mm 100mm 750mm 1000mm 2500mm 2000 mm

10 11 12

6.20.8

Electrical equipment installed in battery room such as exhaust fan, lighting and circuit breakers / receptacles shall be of flameproof and corrosion proof construction and certified for gas group IIC classified locations. This particular clause may be deviated based on vendor recommendation. The switches, lighting, sockets, and equipment in substation buildings and battery rooms shall be as per drawings, specifications, and IS/IEC standards.

6.20.9

6.20.10 Battery room and ventilation arrangement and approved by CEIL

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 27 of 29

6.21

HIGH VOLTAGE SWITCHBOARD Only major relays, meters and controls are indicated in the hardware data sheets. Any auxillary relays, timers, switches etc as required while developing the control schematic and felt necessary for safe operation, even if these are not specifically included, shall be supplied by the Contractor. All relays, metering and control components shall be mounted on the panel front only. All dummy panels and rear extensions required for bus trunking, cable terminations, mounting of relays, metering and control components etc shall be supplied by the Contractor. The following change over scheme shall be provided in 6.6kV Air insulated switchgear. a. Change over scheme for two incomers and one bus coupler Auto manual change over scheme for switchboard with two incomers and one bus coupler breakers shall comply with the logic described briefly as follows. Safety interlocks as deemed necessary shall however be considered during detailed engineering. b. Auto Change over: Auto / Manual change over between the two incomers and one bus coupler shall be in such a way that those two incomer breakers are ON at a time and bus-coupler breaker is normally open. Bus coupler breaker is made ON automatically in case the incoming supply at incomer breaker no.1 or 2 fails and respective breaker trips on under voltage. Blocking of auto transfer (i.e closing of bus-coupler) if any incomer breaker trips due to a fault. c. Manual Change over: Incomer no.1 and 2 breakers are ON, Bus-coupler breaker is OFF. Manual closing of bus coupler with momentary paralleling (interlocked with check synchronizing relay) of the incoming supplies to facilitate taking out any of the incomer breakers for maintenance. Trip incomer 1 or 2 (preselected) after closing of incomer 1 or 2 or coupler to avoid continuous paralleling of incomers) d. Initiation of Auto changeover: When the incoming supply to breaker no.1 or 2 fails, the respective incomer is tripped through under voltage relays and a timer. The time delay is in the range of 0.5 to 5 sec. Breaker trip on under voltage is blocked in case of the power failure on both the incomers. The voltage on healthy bus section has been above the set value of normal voltage for a specified duration (settable through an Off delay timer0.5-5 secs) and the incomer breaker of healthy bus is closed in service position. Bus-coupler is open and in service position Auto/ Manual switch is set for Auto operation. e. Closing of bus coupler breaker under auto operation: One of the incomer breaker has tripped on under voltage. The residual voltage on the bus that has lost supply is less than 40% of normal voltage. Incoming voltage of healthy incomer has been above 80% of normal voltage for a specific duration (Through timer 0.5 sec-5 sec) Auto/Manual switch is set for AUTO operation.

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002) f. Manual transfer after auto changeover

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 28 of 29

When supply is again available at incomer breaker after the Auto changeover has already taken place, it is possible to restore the system to normal operation condition by operating selector switch (meant for tripping incomer no.1 or 2 or bus-coupler and by setting auto/manual switch in Manual mode. In manual transfer the closing circuit shall be interlocked through check synchronizing relay. 6.21.1 MEDIUM VOLTAGE SWITCHBOARD Rating of Power cum motor control centre (PMCC) shall be decided Contractor and same shall be suitable for a minimum fault level of 50kA for one sec. The connection from Transformer secondary to PMCC incomer shall be through Bus-duct. No. of outgoing feeders shall be decided based on system requirement. Feeders as required, based on final approved single line diagram shall be provided with no cost and time implication to the Company. All protective relays in PMCC for incomers and outgoing breaker feeders shall be numerical type (digital microprocessor based and communicable type). Only major relays, meters amd controls are indicated in data sheets. Any auxillary relays, timers, switches etc as required while developing the control schematic and felt necessary for safe operation even if these are not specifically included shall be supplied by the Contractor. All relays, metering and control components shall mounted on the panel front only. All dummy panels and rear extensions required for bus trunking, cable terminations,mounting of relays, metering and control components etc shall be supplied by Contractor All hardware signals ( with minimum requirement specified below) from various motor feeders for DCS/LCS interface shall be wired and terminated in the respective feeder module: Breaker/contactor ON indication in service position Breaker/contactor OFF indication in service position Breaker/contactor Tripped due to electrical fault Process start command (Auto) Process STOP command Process TRIP command Interface for auto manual selector switch Remote Start command (manual) Remote Stop command Emergency Stop command Ammeter

Current rating for these DCS/ Other location contacts shall be0.5A,110VDC or 240 V AC The change over scheme as mentioned in Cl 6.21 for 6.6kV switchboard shall be provided in PMCCs also. Contractor shall develop scheme for automatic start-up of Emergency Diesel generator in case of power failure. Shutdown of Emergency Diesel generator after power restoration shall also be done automatically. Provision shall also be provided to start the emergency diesel generator in Test mode and load the generator for some time without the need to disturb the electrical system while in operation. All individual feeders in MV switchboard shall be provided with ELR and CBCT to trip the feder incase of earth fault (sensitivity setting range shall be 30mA to 300mA) 6.22 CATHODIC PROTECTION

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

ELECTRICAL DESIGN PHILOSOPHY (M205EIL-CPF-16-50-BD-0002)

DOCUMENT No. A358-CPF-16-50-BD-0002 Rev-A


Page 29 of 29

6.22.1

6.22.2 6.22.3

6.22.4 6.22.5

A cathodic protection system for the protection of underground pipelines and underground steel structures shall be provided utilizing impressed current with manual control and designed in accordance with the National Association of Corrosion Engineers (NACE) and BS 7361. Transformers shall be oil immersed and rectifiers shall be SCR type. They shall be operated on 415V, 3 phases, 50Hz and installed in non-hazardous areas preferably. The anode(s) shall be high silicon cast iron with coke breeze backfill, suitable for burial and with sufficient quantity and size to have a minimum life expectancy of 20 years. Anodes shall be buried to a depth sufficient to provide adequate protection. Necessary test posts shall be installed along the protected underground pipelines for periodic measurements of the metal to soil potential. The protective potential along the underground pipelines / structures shall not be less than 1.0 volt negative with respect to copper / copper sulphate electrode cell, neither shall be more than 1.5 volt negative.

6.23 Electric heat tracing (EHT) System 6.23.1 Individual EHT circuit design calculation shall be performed utilizing an industry accepted software program. 6.23.2 Self regulating (SR) type cables may be utilized for field applications as deemed necessary. 6.23.3 For the most part, mineral insulated (MI) heating cables, shall be determined from circuit calculations and factory fabricated. A skin effect current tracing (SECT) system may be considered for lines longer than 1000 m and intermediate powering station is available 6.23.4 Heat tracing system is project specific and passed on process parameters 7.0 33KV OVERHEAD POLE LINE Over head lines needs to be considered for transfer of power from terminal which has power generation facilities to other remote area location if generation of power is not possible in remote area other than emergency power generation.

Format No. EIL 1650-1296P Rev. 2

Copyright EIL All rights reserved

Vous aimerez peut-être aussi