SIPROTEC

Motor Protection

SIPROTEC Motor protection

Protection functions for various types of motor faults


Fault
n Stator thermal overload n Rotor thermal overload during start n too long or blocked n too frequent n Earth-fault n Short-circuit n Loss of phase n Bearing overload n Overheating of plant on unloaded drives
(Pumps, compressors)

Protection
n Stator thermal overload protection n 2 Protection principles for the rotor overload protection n Motor starting time supervision n Restart inhibit n Earth-fault protection (I0>;U0>; (U0, I0)) n Overcurrent time protection n Current differential protection n Negative sequence protection (I2/IN) n Temperature sensors (RTDs) n Undercurrent protection, Active power protection (P<) n Undervoltage protection

ANSI - No.

49

48 66 50G 50 87 46 38 37 32U 27 40

49R 64G 51 67G

n Undervoltage

(Starting torque not reached M ~ U2 or start too long) (of a synchronous motor)

n Asynchronous operation

n Underexcitation protection

Scope of motor protection functions provided by SIPROTEC devices.

Protection functions

ANSI

7SJ60

7SJ61

7SJ62

7SJ63/64

7UM61

7UM62

Stator overload protection Starting time supervision Locked rotor protection Restart inhibit Earth-fault protection non-directional directional Overcurrent time protection Current differential protection Negative sequence protection Temperature supervision (via RTD - module) Undercurrent protection Active power protection (P<) Undervoltage protection Underexcitation protection Frequency protection Breaker failure protection Freely programmable logic (PLC) Control functions Measuring transducers Flexible serial interfaces nn

49 48 48 66, 49R 64G 50G 67G 50, 51 87 46 38 37 32U (37) 27 40 81 50BF

X X X X

X X X X

X X X X

X X X X

X X X X

X X X X

X 1) X X 1) X X X 1) X 1) X X X X

X X X X X X X

X X X X X X X

X X X X X X X X

X X X X X X X X X X X X X X X X

X X X1) X X X X X X X

X X X X X X

X X X X X X

2/3

1)

in preparation (7SJ602)

A device that best suits your requirement can be selected


3

Motor protection selection table

Asynchronous Motor
100 kW - 500 kW
7SJ60 Basic device 7SJ61 + more I/Os + control functions + flexible serial interfaces + better local HMI (4line display; digital keyboard)

Synchronous Motor
< 2MW
7UM61 (Option: Generator Basic)

500 kW - (1-2) MW
7SJ62 Basic device + control functions 7UM61 + more I/Os (7UM612) + control functions + high accuracy + high sensitivity + operating range in a wide frequency band (11Hz - 68Hz)

< 10 MW
7UM62 (Option: Generator Basic)

or with control functions via bay mimic diagram in graphic display 7SJ63 Basic device 7SJ64 + synchro check function + high sensitivity + extensive control function + 1 serial interface more

> 2 MW
7UM62 + differential protection + control functions + high accuracy + high sensitivity + operating range in a wide frequency band (11Hz - 68Hz)

> 10 MW

+
7UM62 (Option: Generator Basic)

7UM61 (Option: Generator Basic) or with control functions via bay mimic diagram in graphic display

7SJ64 (Option: Maximum functionality + Synchro check)

Application example: Protection of a small motor


100 kW - 500 kW

A (L 1) B (L 2) C (L 3) ANSI 52 A (L 1) B (L 2) C (L 3) N

7SJ600/602
n Stator thermal overload protection n Starting time supervision n Earth-fault protection n Overcurrent time protection n Negative sequence protection 49 48 50G 50, 51 46

Motor

Application example: Protection of a medium sized motor


500 kW - (1-2) MW

A (L 1) B (L 2) C (L 3) ANSI 52 A (L 1) B (L 2) C (L 3) N

7SJ62/63
n Stator thermal overload protection 49 66, 49R 48 50G 64G 67G

IEE

n Restart inhibit (rotor protection) n Starting time supervision n Earth-fault protection (non-directional, directional)

VE

C (L 3) A (L 1)

n Overcurrent time protection 50, 51 n Negative sequence


Motor

protection n Undervoltage protection n Undercurrent protection n Breaker failure protection n external RTD - module

46 27 37 50BF 38

Application example: Protection of a large motor


> 2 MW

A (L 1) B (L 2) C (L 3) ANSI 52
e

7UM62
R 13 R 14 R 15 R 17 R 18 R 16 J1 J2 J3 J4 J5 J6

VE

VA(L1) VB(L2) VC(L3)


IA(L1)S2 IB(L2)S2 IC(L3)S2

7UM62
n Stator thermal overload protection n Restart inhibit (rotor protection) n Earth-fault protection
(non-directional, directional)

49 66, 49R 50G 64G 67G 87M 50, 51 46 27 37 32U 81

Q8 Q7 K 13 +

IEE2

n Starting time supervision 48

RTD module

7XV5662 (6 meas. junctions)

Measuring transducer for injection of any analog signal e.g. speed, vibration, pressure

TD1

K 14 K 15 + K 16 K 17 +

TD2

TD3

To serial interface

K 18 J7 J8 Q1 Q2 Q3 Q4 Q5 Q6 IEE1

n Differential protection n Overcurrent time protection n Negative sequence protection n Undervoltage protection n Undercurrent protection n Active power protection n Frequency protection

IA(L1)S2 IB(L2)S2 IC(L3)S2

From RTD module

Port C or D

n Breaker failure protection 50BF