Académique Documents
Professionnel Documents
Culture Documents
Sunday, Feb 09
The United States has a procedure that tests hoods for capture and containment.
The test variables are based on temperature and the required cfm per linear foot of
hood to capture the effluent; the test is in accordance with UL 710 standards. The
listing is published both on a hood label and a listing card that describes the cfm
and coating surface temperature relationship (Figure 1).
http://www.esmagazine.com/CDA/ArticleInformation/features/BNP__Features__Item/0,2503,91... 10/02/2003
Features Item : Commercial Kitchen Ventilation Design: What You Need To Know Sayfa 2 / 4
The main purpose of the filter in a hood is to prevent flames from entering the
exhaust duct. Also, the quantity of exhaust air also keeps a filter's surface
temperature near 200 degrees F. The filter aspect of the device is to facilitate
condensing of the moisture and grease vapors so it can be captured by centrifugal
separation as the material passes through baffles, turns, cooling surfaces, etc.
Aluminum mesh filters are no longer allowed in Type I hoods. The simplest filter is a
baffle configuration, though a greater surface area is possible with a high-velocity
cartridge filter. Water mist-type hoods also cool and condense grease and moisture
vapors at the filter area.
The grease filter industry is currently developing new types of baffle filters with
larger surface areas that will condense vapors and moisture at the filter rather than
at a cooler location in the duct.
As system designers, we should be aware that as filter types change from baffle to
cartridge to an extended area, the fan static pressure requirement increases.
Chapter 30 in the 1999 ASHRAE Handbook - HVAC Applications has a table that
shows the typical static pressure relationship between filter types and airflow.
Replacement air is provided by a system that brings the air into the structure near
the exhaust area. It should be filtered, heated to a minimum of 50 dgrees in cold
climates, distributed to avoid drafts at the hood, and, in some cases, air conditioned
or cooled. The short-circuit hood was developed to try to introduce the code formula
required air directly into the hood canopy to avoid expensive conditioning. However,
the use of the short circuit is fading with the use of UL 710 lower cfm listings.
Consider avoiding the creation of drafts at the hood which disturb the capture and
containment of a thermal rising plume. Also, avoid a drafty four-way diffuser near
the hood; hood suppliers have front-face grilles and perforated faceplates to supply
air.
Today, air conditioned kitchens are becoming more and more popular to attract and
keep a cooking staff. However, with the advent of kitchen air conditioning, hood
suppliers have found that front-face distribution methods do not provide cook line
comfort; therefore, they are providing low-velocity mass down flow diffusion units
and adjustable-flow units. Rear supply plenums also can be used for untempered
air in mild climates (Figure 2).
http://www.esmagazine.com/CDA/ArticleInformation/features/BNP__Features__Item/0,2503,91... 10/02/2003
Features Item : Commercial Kitchen Ventilation Design: What You Need To Know Sayfa 3 / 4
Efficient system design dictates that duct sizing velocity should be sized near the
2,000-fpm value. Hood collars are generally sized by the manufacturer at 1,800
fpm.
Duct Cleaning
Most duct cleaning is done by power washing the duct and hood interior. Since
water is used, liquid-tight ductwork is important. Type I ductwork is black steel
welded seam construction. Job site history has shown that "welded" duct is not
liquid tight the first time. If the duct leaks and is wrapped and/or enclosed in a
gypsum enclosure, mold will form within the wrap enclosure assembly. Obviously,
mold is bad, therefore, it is important to pressure test to demonstrate liquid
tightness. To ensure liquid tightness, pressure test the duct to 0.10 inches of water.
Next, code-required access panels in horizontal and vertical ducts are required to
allow for cleaning material that power washing will not remove. Consider enclosing
the access door insulating wrap in a double-wall enclosure to prevent damage
every time the access is used.
Third, include a low-point drain access for water used in power washing. However,
pitch the horizontal duct run to the hood collar. NFPA 96 requires that horizontal
duct supports must support the weight of the duct plus 800 pounds. The 800
pounds extra is for duct cleaning equipment and water.
Stack Outlet
Most upblast aluminum power roof ventilations discharge at about 1,000 fpm, or 11
mph. A cross wind could carry the effluent horizontal for a long distance, which
often equates into recirculation of exhaust effluent into intake louvers at the same
level. A solution is the high-velocity upblast stack used in laboratory design (Figure
3).
A simple solution to pollution is dilution. To do this, bleed outdoor air into the roof
fan installation at 1:5 ratio (e.g. 5,000 cfm hood) and add 1,000 cfm of outdoor roof
level air and size for 6,000 cfm. For smoke concerns, another solution is simply to
reduce the fat in the cooking product.
Another point to remember is that replacement air cools the filters and causes
http://www.esmagazine.com/CDA/ArticleInformation/features/BNP__Features__Item/0,2503,91... 10/02/2003
Features Item : Commercial Kitchen Ventilation Design: What You Need To Know Sayfa 4 / 4
moisture and vapor to condense at the filter face rather than in the stack or on the
roof. Any time excess grease gets on the fan or on the roof, the cause is often low
cfm.
Replacement air cools the filters and causes moisture and vapor
to condense at the filter face rather than in the stack or on the
roof. Any time excess grease gets on the fan or on the roof, the
cause is often low cfm.
Conclusions
The IMC is new and recognizes the variable exhaust flow requirements relative to
cooking temperatures. NFPA 96 (2001) is a current standard written in code
language. The UL 710 listing is allowed by the IMC and does reduce airflow
requirements. Duct cleaning is mainly by power washing and liquid tightness in a
design mold avoidance concern in wrapped and enclosed ducts. Pollution and odor
recirculation concerns can be economically resolved by high-velocity stack outlets
and dilution design.ES
EDITOR'S NOTE: Some images associated with this article do not transfer to the
Internet. To review the figures, please refer to the print version of this issue.
Clark is a senior mechanical engineer with Hammel, Green & Abrahamson, Inc.
(HGA). He has over 40 years of experience providing mechanical engineering
design services for a wide variety of projects and is an ASHRAE Fellow. He
has served on numerous national committees, and authored many articles and
papers related to plumbing, fire protection, and HVAC system design. He
emphasizes practical, maintainable, cost- effective designs for all aspects of
his projects. A teacher at heart, he assists in staff development and also is the
department resource for plumbing design issues. Contact him at John Clark,
P.E..
http://www.esmagazine.com/CDA/ArticleInformation/features/BNP__Features__Item/0,2503,91... 10/02/2003