Busbar Trunking Systems, Overview

2/3 2/4 2/6

Contents Technical Overview System Overview

Siemens LV 70 2004

Busbar Trunking Systems, Overview

2/2

Siemens LV 70 2004

Busbar Trunking Systems, Overview


Contents
CD system (25 A 40 A) BD01 system (40 A 160 A)

Technical overview of busbar trunking systems System overview of busbar trunking systems Contents CD system overview Description Engineering CD system (25 A 40 A) Technical data Dimensions

Page 2/4 2/6 3/1 3/2 3/4 3/6 3/14 3/20 3/22

Technical overview of busbar trunking systems System overview of busbar trunking systems Contents BD01 system overview Description Engineering BD01 system (40 A 160 A) Technical data Dimensions

Page 2/4 2/6 4/1 4/2 4/4 4/7 4/12 4/30 4/33

BD2 system (160 A 1250 A)

Technical overview of busbar trunking systems System overview of busbar trunking systems Contents BD2 system overview Description Engineering Fire barriers BD2 system (160 A 1250 A) Technical data Dimensions

Page 2/4 2/6 5/1 5/2 5/4 5/12 5/23 5/30 5/77 5/84

Siemens LV 70 2004

2/3

Busbar Trunking Systems, Overview


Technical Overview
Busbar trunking systems Rated current A CD 30 40 2 25 Rated operational voltage V AC 400 Frequency Hz 50 60 2, 3, 4, 2 4 (PE = enclosure) IP54 Number of active conductors Degree of protection Ambient temperature min./max. C 5/+ 40

2
BD01 40 63 100 125 160 400 50 60 4 (PE = enclosure) IP54 5/+ 40

BD2A BD2C

160 400 500 1250

690

50 60

IP52 IP54 with accessories IP55 on request

5/+ 40

LDA1 LDA8 LDC2 LDC8

1100 4000 2000 5000

1000

50 60

4 or 5

IP34 IP54

5/+ 40

LXA01 LXA10 LXC01 LXC10

800 4500 1000 6300

690

50 60

3, 4, 5, 6 (PE = enclosure)

IP54

5/+ 40

2/4

Siemens LV 70 2004

Busbar Trunking Systems, Overview


Technical Overview
Mounting position Length m Edgewise 2 3 On one side: every 0.5 or 1 m On both sides: every 0.5 or 1 m Up to 16 A Insulated Cu conductors, painted sheet steel housing Tap-off points Tap-off units Material Combustive energy kWh/m 0.1 0.48

2
Edgewise, flat (tap-off points downwards) 2 3 On one side: every 0.5 or 1 m Up to 63 A Insulated Al or Cu conductors, painted sheet steel housing 0.76 Can be combined with networkable tap-off units for lighting control systems

Edgewise, flat and vertical

0.5 3.25

Without, on both sides: every 0.25 or 0.5 m offset

Up to 400 A

Al or Cu busbars, painted sheet steel housing

0.6 0.67 (without tap-off points)

Can be combined with networkable tap-off units for lighting control systems, remote switching and load monitoring

Horizontal, edgewise and vertical

0.5 3.2

Without, on both sides: every 1 m

Up to 800 A

Insulated Al or Cu busbars, painted sheet steel housing

4.16 8.83 (without tap-off points)

Information about the LD and LX systems: from your Siemens sales outlet. Can be combined with networkable tap-off units for remote switching and load monitoring

Horizontal, edgewise and vertical

0.35 3

Without, on one side: every 0.5 m on both sides: every 0.5 m

Up to 1250 A

Insulated Al or Cu busbars, painted aluminium housing

1.95 11.07 (without tap-off points)

Siemens LV 70 2004

2/5

Busbar Trunking Systems, Overview


System Overview

6 1
B 0 1 -K B D

3
B D 0 1

B 0 1 -K

2/6

Siemens LV 70 2004

Busbar Trunking Systems, Overview


System Overview
Up to 40 A Up to 160 A Networkable busbar trunking system 6 Networkable function expansions for combination with known tap-off units Applications: large area lighting control systems remote switching and signalling in industrial applications load monitoring of decentral power tap-offs Bus systems EIB, AS-I, LON Simple and easy to plan Flexible with expansion and change Module system Can be retrofitted to existing installations Simple contact establishment to bus line with insulation displacement feature Can be used with the BD01, BD2, LD, LX systems

CD system 3 Reduced planning costs through simplified engineering Quick-release plug-in connection for fast assembly Tap-off points on both sides for optimized utilization of the busbar Even electrical loading of the CD system conductors achieved by connecting an equal number of tap-off plugs to each individual phase Versatility through high degree of protection to IP54 of the standard version Tap-off plugs allow fast, flexible load relocation (even on live systems).

BD01 system Flexible power supply Junction units for changes in direction Fast, simple planning Time-saving assembly Reliable mechanical and electrical connection High stability, low weight Positive opening and closing of tap-off points Versatile tap-off units Few basic elements Modular system reduces stock-holding High degree of protection to IP54 with tap-off points at sides and bottom for extreme ambient conditions, otherwise IP50. a Page 4/2

a Page 3/2

Up to 1250 A

Up to 5000 A

Design software BusbarSelect Design software for busbar trunking systems up to 1250 A This CD-ROM is available free of charge from your sales outlet.

BD2 system 1 Fast, simple planning Time-saving, cost-efficient assembly Reliable, safe operation Flexible modular system with simple solutions for every application Early planning of power distribution possible without precise knowledge of consumer locations Fast operational readiness through quick, simple assembly High degree of protection to IP54 for use in harsh industrial environments Innovative construction: No compensating units for expansion compensation required. a Page 5/2

LD system 4 The busbar trunking system for optimized power distribution in industry. Detailed information about this system is available from your sales outlet.

Up to 6300 A

Technical Information These planning aids are available from your sales outlet. LV 71.T Planning Guide SIVACON 8PS Busbar trunking systems LDA/LDC, BD2A/BD2C 160 A to 5000 A LV 72.T Planning Guide SIVACON 8PS Busbar trunking systems LXA/LXC over 800 A

LX system 5 The busbar trunking system for power transmission and distribution in buildings. Detailed information about this system is available from your sales outlet.

Leaflet

E20001-A220-P309-X-7600 SIVACON 8PS Save and Flexible Power Distribution up to 6300 A

Siemens LV 70 2004

2/7

Busbar Trunking Systems, Overview


Notes

2/8

Siemens LV 70 2004

Vous aimerez peut-être aussi