Vous êtes sur la page 1sur 12

3EK7 Medium Voltage

Silicone Insulated Surge Arresters


www.siemens.com/energy/arrester

Answers for energy.

Setting Standards
The 3EK7 surge arrester from Siemens offers since 1999
superior protection against power surges for the equipment in electrical distribution systems with operating
voltages of up to 72.5 kV. Besides being highly resistant
to environmental pollution of all kinds, its performance
in dealing with earth faults and its e
xcellent short-circuit
ratings are setting entirely new standards. The silicone
on the 3EK7 surge arrester refuses to allow any deposits
of pollution or films of moisture to form on it. Thus,
surface currents caused by pollution will virtually not
occur. The 3EK7 arrester is also very lightweight,
robustand durable, due to its special Cage Design.

The 3EK7s mechanical


features:
Glass-collared MOV,
Silicone rubber housing,
FRP rods and
Aluminium end fittings.
Three types of 3EK7 surge
arresters are available:
3EK7-. C .. surge arresters
according to IEC 60099-4
with metric thread,
3EK7...-. A .. surge arresters
according to IEEE Std C 62.11
with imperial thread.
For special applications:
3EK7...-. B .. surge arresters
according to IEEE Std C 62.11
with metric thread.
2

3EK7 Design
internal pressure, since the resistors are not enclosed
ina sealed mechanical shell. Thus, the arc can escape
through the silicone sheath, leaving the mechanical
support structure of the enclosure unharmed.

3EK7 a top quality product

The silicone rubber housing is molded directly onto


theMOV blocks and the protection cage. It provides
anexcellent sealing system against moisture ingress
and partial discharges. In addition, the MOV blocks
areglass-collared to prevent aging.
Highest quality materials. Silicone rubber is highly
hydrophobic and maintains this ability to repel water
and any deposits of pollution throughout its entire
service life. This results in high tracking and erosion
resistance. Furthermore, the silicone rubber housing
isself-extinguishing and flame-retardant. These advantages provide maintenance free and reliable service
lifefor 3EK7 arresters.

The cage is lightweight design and yet it offers excellent torsional, tensile and cantilever strength: Maximum
working cantilever strength of 350 Nm.

Silicone rubber is resistant to UV and ozone exposure as


well as to all common organic and non-organic solvents
and cleaning agents. Therefore, the 3EK7 is suitable for
any environmental conditions of industrial areas as well
as in desert or coastal regions.

3EK7 arresters are suitable for a temperature range


from 55 C to +60 C.
Application altitude up to 3600 m a.s.l.

Manufacturing plants are certified under ISO 9001


andISO 14001.

3EK7 arresters have been type tested by an independent test laboratory.

Fast delivery

Secure and reliable design

Flexibility in production and in our global network


ofservice and sales facilities provide fast and prompt
supply.

The 3EK7 series is based on a cage of pre-stressed fiberreinforced plastic rods for high mechanical strength,
reducing the risk of internal components being ejected.
In the extremely rare event of the resistors being overloaded, arcing cannot result in a build-up of critical

M12 or 3/8 inch stainless steel stud


Nut, washer
Clamp
End fitting
Silicone housing,
directly molded

Metal oxide varistor MOV


Glass coating
FRP rods

End fitting
Nut, washer
M12 or 3/8 inch stainless steel stud
3

Selection and Main Data

3EK7 Arresters According to IEC 60099-4


Voltage per unit Ur
1.2

Preheating to 60C and stressed with


one high current impulse prior to TOV

1.15
1.1
1.05

Nominal discharge
current In

10 kA

Maximum continuous
operating voltage Uc

48 kV

Rated voltage Ur

60 kV

Long-duration
current impulse

1.0

325 A

Rated short-circuit current

20 kA

Low short-circuit current

600 A

High-current impulse

100 kA

Specified long-term load


SLL (Fstat)

350 Nm

Specified short-term load


SSL (Fdyn)

500 Nm

Energy absorption
capability (thermal)

3.5 kJ/kV Ur

0.95
0.9
0.85
Time in
seconds

0.8
0.1

10

100

1000

Table 1: IEC power-frequency voltage versus time characteristic

Rated
voltage

Continuous
operating
voltage

Ur
[kV]

Uc
[kV]

Arrester type

Maximum values of the residual voltages


at discharge currents of the following impulses

Creepage
distance

8/20s
1 kA
[kV]

8/20s
3 kA
[kV]

8/20s
5 kA
[kV]

8/20s
10 kA
[kV]

8/20s
20 kA
[kV]

30/60s
125 A
[kV]

30/60s
500 A
[kV]

[mm]

2.4

3EK7 030 - 4 C B 4

6.5

7.1

7.4

8.0

9.1

5.8

6.1

372

4.0

3EK7 050 - 4 C B 4

10.9

11.8

12.3

13.3

15.2

9.7

10.2

372

4.8

3EK7 060 - 4 C B 4

13.0

14.2

14.8

15.9

18.3

11.6

12.2

372

7.2

3EK7 090 - 4 C B 4

19.6

21.2

22.2

23.9

27.4

17.4

18.4

372

12

9.6

3EK7 120 - 4 C C 4

26.1

28.3

29.6

31.8

36.6

23.2

24.5

485

15

12.0

3EK7 150 - 4 C C 4

32.6

35.4

37.0

39.8

45.7

29.0

30.6

485

18

14.4

3EK7 180 - 4 C D 4

39.1

42.5

44.4

47.7

54.9

34.8

36.7

605

21

16.8

3EK7 210 - 4 C D 4

45.6

49.5

51.8

55.7

64.0

40.6

42.9

605

24

19.2

3EK7 240 - 4 C E 4

52.2

56.6

59.1

63.6

73.1

46.4

49.0

775

27

21.6

3EK7 270 - 4 C E 4

58.7

63.7

66.5

71.6

82.3

52.2

55.1

775

30

24.0

3EK7 300 - 4 C F 4

65.2

70.8

73.9

79.5

91.4

58.0

61.2

900

33

26.4

3EK7 330 - 4 C H 4

71.7

77.8

81.3

87.5

101

63.8

67.3

1230

36

28.8

3EK7 360 - 4 C H 4

78.2

84.9

88.7

95.4

39

31.2

3EK7 390 - 4 C H 4

84.7

92.0

96.1

42

33.6

3EK7 420 - 4 C H 4

91.3

99.1

45

36.0

3EK7 450 - 4 C H 4

97.8

48

38.4

3EK7 480 - 4 C H 4

51

40.8

54

110

69.6

73.5

1230

103

119

75.4

79.6

1230

104

111

128

81.2

85.7

1230

106

111

119

137

87.1

91.8

1230

104

113

118

127

146

92.9

97.9

1230

3EK7 510 - 4 C J 4

111

120

126

135

155

98.7

43.2

3EK7 540 - 4 C J 4

117

127

133

143

165

57

45.6

3EK7 570 - 4 C J 4

124

134

140

151

60

48.0

3EK7 600 - 4 C J 4

130

142

148

60

48.0

3EK7 600 - 4 C K 4

130

142

148

Table 4: 3EK7 nominal discharge current 10 kA

Table 2: 3EK7 arrester main data

104

1420

104

110

1420

174

110

116

1420

159

183

116

122

1420

159

183

116

122

1595

Highest voltage
for equipment
Um

Rated lightning
impulse withstand
voltage

[kV]

[kV]

2.75
3.6
5.5
7.2
8.25
12
15.5
17.5
24
25
27
30
36
38
40.5
48.3
52
72.5

30; 45; 60
20; 40
45; 60; 75
40; 60
60; 75; 95
60; 75; 95
85; 110
95
125; 145
125; 145
150
160
170
200
190
250
250
325

Solidly earthed
neutral system

Isolated
neutral system

Impedance earthed
neutral system

Resonant earthed
neutral system

3EK7 030-.C..
3EK7 030-.C..
3EK7 050-.C..
3EK7 060-.C..
3EK7 090-.C..
3EK7 090-.C..
3EK7 120-.C..
3EK7 150-.C..
3EK7 180-.C..
3EK7 210-.C..
3EK7 210-.C..
3EK7 240-.C..
3EK7 270-.C..
3EK7 300-.C..
3EK7 330-.C..
3EK7 390-.C..
3EK7 420-.C..
3EK7 570-.C..

3EK7 050-.C..
3EK7 050-.C..
3EK7 090-.C..
3EK7 090-.C..
3EK7 105-.C..
3EK7 150-.C..
3EK7 210-.C..
3EK7 220-.C..
3EK7 300-.C..
3EK7 330-.C..
3EK7 360-.C..
3EK7 390-.C..
3EK7 450-.C..
3EK7 480-.C..
3EK7 510-.C..
3EK7 600-.C..

3EK7 030-.C..
3EK7 030-.C..
3EK7 050-.C..
3EK7 090-.C..
3EK7 090-.C..
3EK7 105-.C..
3EK7 150-.C..
3EK7 150-.C..
3EK7 210-.C..
3EK7 220-.C..
3EK7 240-.C..
3EK7 270-.C..
3EK7 330-.C..
3EK7 330-.C..
3EK7 360-.C..
3EK7 420-.C..
3EK7 450-.C..

3EK7 050-.C..
3EK7 050-.C..
3EK7 090-.C..
3EK7 090-.C..
3EK7 105-.C..
3EK7 150-.C..
3EK7 210-.C..
3EK7 220-.C..
3EK7 300-.C..
3EK7 330-.C..
3EK7 360-.C..
3EK7 390-.C..
3EK7 450-.C..
3EK7 480-.C..
3EK7 510-.C..
3EK7 600-.C..

Table 3: Typical 3EK7 arresters for system voltages according to IEC 60099-4

Flashover
distance

Specified
Specified
long-term
short-term
load SSL (Fdyn) load SLL (Fstat)

Housing
insulation

Height
H1)

Weight

[mm]

Lightning impulse
withstand voltage
1.2/50s
[kV]

Power frequency
withstand voltage
1 min., wet
[kV]

[N]

[N]

[mm]

[kg]

180

104

49

2940

2050

170

1.5

180

104

49

2940

2050

170

1.5

180

104

49

2940

2050

170

1.6

180

104

49

2940

2050

170

1.6

210

122

57

2500

1750

200

1.9

210

122

57

2500

1750

200

2.0

248

144

67

2080

1450

240

2.3

248

144

67

2080

1450

240

2.4

286

166

77

1850

1290

270

2.7

286

166

77

1850

1290

270

2.8

318

184

86

1660

1160

300

3.1

418

242

113

1250

870

400

3.9

418

242

113

1250

870

400

4.0

418

242

113

1250

870

400

4.1

418

242

113

1250

870

400

4.1

418

242

113

1250

870

400

4.2

418

242

113

1250

870

400

4.3

484

281

131

1060

740

470

4.9

484

281

131

1060

740

470

5.0

484

281

131

1060

740

470

5.0

484

281

131

1060

740

470

5.1

520

302

140

980

680

510

5.3

1) Refer to figure 1 on page 8

Selection and Main Data

3EK7 Arresters According to IEEE Std C 62.11


Voltage per unit MCOV

Heavy duty

1.8

Riser pole

Maximum continuous
operating voltage
29 kV
MCOV

29 kV

Duty-cycle voltage

36 kV

36 kV

Short-circuit current
0.2s

20 kA

20 kA

1.5

Low-current,
long-duration

250 A

250 A

1.4

Low-current
pressure relief

600 A

600 A

High-current,
short-duration

100 kA

100 kA

Lightning impulse
classifying current

10 kA

10 kA

Energy absorption
capability (thermal)

4.6 kJ/kVMCOV 4.6 kJ/kVMCOV

Maximum design
cantilever load-static
(MDCL)

2478 inch-lbf 2478 inch-lbf

Preheating to 140F/60C
no prior duty
heavy duty
riser pole

1.7
1.6

1.3
1.2
1.1
1.0
0.01

Time in
seconds
0.1

10

100

1000

10000

Table 5: ANSI temporary overvoltage

Table 6: 3EK7 distribution arrester main data

3EK7 heavy duty


Duty-cycle
voltage

MCOV

TOV Capability
w/o duty

[kV]

[kV]

for 0.1s
[kV]

3
6
9
10
12
15
18
21
24
27
30
33
36

2.55
5.10
7.65
8.40
10.2
12.7
15.3
17.0
19.5
22.0
24.4
27.5
29.0

4.3
8.5
12.8
14.0
17.0
21.2
25.6
28.4
32.6
36.7
40.7
45.9
48.4

MCOV

TOV Capability
w/o duty

Arrester part number

3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7

030
060
090
100
120
150
180
210
240
270
300
330
360

3AB
3AB
3AB
3AB
3AC
3AD
3AD
3AE
3AF
3AF
3AH
3AH
3AH

4
4
4
4
4
4
4
4
4
4
4
4
4

Protective Level Maximum discharge voltage


FOW
[kV] cr

8/20s
1.5 kA
[kV] cr

8/20s
3 kA
[kV] cr

8/20s
5 kA
[kV] cr

8/20s
10 kA
[kV] cr

8/20s
20 kA
[kV] cr

8/20s
40 kA
[kV] cr

45/90s
125 A
[kV] cr

10.5
21.6
30.9
32.3
41.0
51.3
61.5
67.3
77.6
87.7
96.6
108
119

8.1
16.7
23.9
25.0
31.7
39.6
47.5
52.0
59.9
67.7
74.6
83.6
92

8.5
17.4
25.0
26.2
33.2
41.5
49.8
54.5
62.7
70.9
78.1
87.6
96

8.8
18.2
26.1
27.3
34.7
43.3
52.0
56.9
65.6
74.1
81.7
91.5
100

9.5
19.6
28.1
29.4
37.3
46.6
55.9
61.2
70.5
79.7
87.8
98.4
108

10.9
22.5
32.3
33.8
42.9
53.6
64.3
70.4
81.1
91.7
101
113
124

12.6
26.1
37.4
39.1
49.6
62.0
74.3
81.4
93.8
106
117
131
144

6.9
14.3
20.5
21.5
27.2
34.0
40.8
44.7
51.5
58.2
64.1
71.8
78.8

3EK7 riser pole


Duty-cycle
voltage

[kV]

[kV]

for 0.1s
[kV]

3
6
9
10
12
15
18
21
24
27
30
33
36

2.55
5.10
7.65
8.40
10.2
12.7
15.3
17.0
19.5
22.0
24.4
27.5
29.0

3.8
7.6
11.4
12.5
15.1
18.9
22.7
25.2
29.0
32.7
36.2
40.8
43.1

Arrester part number

3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7
3EK7

030
060
090
100
120
150
180
210
240
270
300
330
360

4AB
4AB
4AB
4AC
4AD
4AD
4AE
4AF
4AH
4AH
4AH
4A J
4AK

4
4
4
4
4
4
4
4
4
4
4
4
4

Protective Level Maximum discharge voltage


FOW
[kV] cr

8/20s
1.5 kA
[kV] cr

8/20s
3 kA
[kV] cr

8/20s
5 kA
[kV] cr

8/20s
10 kA
[kV] cr

8/20s
20 kA
[kV] cr

8/20s
40 kA
[kV] cr

45/90s
125 A
[kV] cr

8.9
17.7
26.4
29.3
35.2
43.9
52.7
61.5
70.2
79.1
87.7
96.6
105

6.8
13.6
20.3
22.6
27.1
33.9
40.7
47.4
54.2
61.0
67.8
74.6
81.3

7.1
14.2
21.3
23.7
28.4
35.5
42.6
49.7
56.8
63.9
71.0
78.1
85.2

7.4
14.8
22.2
24.7
29.7
37.1
44.5
51.9
59.3
66.7
74.2
81.6
89.0

8.0
15.9
23.9
26.6
31.9
39.9
47.8
55.8
63.8
71.8
79.7
87.7
95.7

9.2
18.3
27.5
30.6
36.7
45.9
55.0
64.2
73.4
82.5
91.7
101
110

10.6
21.2
31.8
35.4
42.4
53.0
63.6
74.2
84.8
95.4
106
117
127

5.8
11.6
17.5
19.4
23.3
29.1
34.9
40.7
46.6
52.4
58.2
64.0
69.9

System L-L Voltage


[kV]

Four-wire multigrounded
neutral wye

Three-wire low impedance


grounded neutral circuit

3EK7030-.A..

3EK7060-.A..

2.4

Three-wire high impedance


grounded neutral circuit
3EK7030-.A..

4.16

3EK7060-.A..

4.26

3EK7060-.A..

4.8

3EK7060-.A..

6.9

3EK7090-.A..

8.3

3EK7060-.A..

3EK7090-.A..

12

3EK7120-.A..

20.78

3EK7090-.A..
3EK7090-.A..
or
3EK7100-.A..
3EK7100-.A..
3EK7100-.A..
or
3EK7120-.A..
3EK7150-.A..

22.86

3EK7150-.A..

3EK7210-.A..

24.94

3EK7180-.A..

3EK7270-.A..

27.6

3EK7210-.A..

3EK7300-.A..

34.5

3EK7270-.A..

3EK7360-.A..

12.47
13.2
13.8

3EK7150-.A..
3EK7150-.A..
3EK7150-.A..

3EK7180-.A..

3EK7210-.A..

23

3EK7300-.A..

Table 7: Typical 3EK7 arresters for system voltages according to the latest IEEE Std C 62.11

Creepage
distance

Flashover
distance

Power frequency withstand voltage 1 min., wet

Lightning impulse withstand voltage 1.2/50s

Height
H1)

Weight

45/90s
500 A
[kV] cr

[inch]

[inch]

[kV]

[kV]

[inch]

[lbs]

7.3
15.1
21.6
22.6
28.7
35.9
43.0
47.1
54.3
61.4
67.6
75.8
83.2

14.65
14.65
14.65
14.65
19.09
23.82
23.82
30.51
35.43
35.43
48.43
48.43
48.43

7.09
7.09
7.09
7.09
8.27
9.76
9.76
11.26
12.52
12.52
16.46
16.46
16.46

49
49
49
49
57
67
67
77
86
86
113
113
113

104
104
104
104
122
144
144
166
184
184
242
242
242

6.69
6.69
6.69
6.69
7.87
9.45
9.45
10.63
11.81
11.81
15.75
15.75
15.75

2.8
3.2
3.2
3.5
4.1
5.1
5.4
6.1
6.7
7.0
8.2
8.5
8.9

Creepage
distance

Flashover
distance

Power frequency withstand voltage 1 min., wet

Lightning impulse withstand voltage 1.2/50s

Height
H1)

Weight

45/90s
500 A
[kV] cr

[inch]

[inch]

[kV]

[kV]

[inch]

[lbs]

6.1
12.3
18.4
20.5
24.6
30.7
36.8
43.0
49.1
55.3
61.4
67.5
73.7

14.65
14.65
14.65
19.09
23.82
23.82
30.51
35.43
48.43
48.43
48.43
55.91
62.80

7.09
7.09
7.09
8.27
9.76
9.76
11.26
12.52
16.46
16.46
16.46
19.06
20.47

49
49
49
57
67
67
77
86
113
113
113
131
140

104
104
104
122
144
144
166
184
242
242
242
281
302

6.69
6.69
6.69
7.87
9.45
9.45
10.63
11.81
15.75
15.75
15.75
18.50
20.08

2.8
3.2
3.5
3.5
4.1
4.4
5.1
5.4
6.1
6.7
7.0
8.2
8.5

1) Refer to figure 1 on page 8

Table 8: 3EK7 heavy duty

Table 9: 3EK7 riser pole


7

74

18.2

14.2
38.5

36

M12

31.5

64

Drawings and Accessories

41

94

104

2.5

20

14

108
154

14.2
18.2
74

64
31.5

H*

Figure 2: NEMA insulating bracket for Ur 15 kV


Order code P12; 0.35 kg

38.5

41

36

104
94

2.5

M12

14

20
152
198

14.5

17 26
60

54

54

60

12

17 26

12

15

Figure 4: DIN insulating bracket for Ur 15 kV


Order code P22; 0.85 kg

104

15

104

156
197

14.5

Figure 3: NEMA insulating bracket for Ur 36 kV


Order code P12; 0.5 kg

Figure 1: 3EK7 surge arrester main dimensions


*please see tables on page 5 or 7

200
241

Figure 5: DIN insulating bracket for Ur 36 kV


Order code P22; 1.0 kg

SW14
(width across flats 9/16")
(214)
(173)

24.5

(60)

57

75
260

21.5

(17)

(26)

(15)

M12 or 3/8"

Figure 7: Bird protection cap


Order code M81; 50 g
12

16

30

13

60

26

14.5

Figure 6:Disconnector
Order code P31; 0.1 kg

15

75

197
13

14

20
30

13

40

33

260

152
M12

Figure 9: DIN metal bracket (hot dip galvanised)


Order code P21; 0.6 kg

14

30
(15)
(87)

200

24

30
60

Figure 8:L-bracket
Order code M12; 0.1 kg

200

10,2

14 or 10.2

260

14

260

25

25

50

50

13

13

450
(10)
152

152
202

20

202

Figure 11: NEMA metal bracket (hot dip galvanized)


Order code P11; 0.6 kg

Figure 10: Insulated ground lead/Insulated line lead


Order code R51; 0.09 kg, 16 mm2
269

178

Figure 12: Transformer bracket 8.7"


Order code Q11; 0.6 kg

18
78

78,5

25

260

43

Figure 13: Transformer bracket 11"


Order code Q12; 0.7 kg

24
3

43

30
60

20

M12

40

20

64
57

200

43

40

20

20

42,9

43

41

25

14,3

14.3

57

20

20

(63,5)

64
(57,2)

14.3

(41,4)

41

25,4

78

18

18

(8)

14

14

145 144,8

14

280 (11")

221 (8.7")

200
260

Drawings and Accessories


310 (12.25")

18
14

86

64

86

54

20

43

30
60

55

40

40

200

19

43

55
200
260

Figure 14: Transformer bracket 12.25"


Order code Q13; 0.8 kg

Figure 15: Transformer bracket 14.5"


Order code Q14; 0.8 kg

227

12
3x

15.2

198

18

28

71

18
10.5150

142

M12

20

14

66

41

220

20

0120

25

73

253.5
M12

Figure 16: NEMA X-arm bracket


Order code Q51; 1.3 kg

Figure 17: Mounting plate, 37 mm height


Order code Q81; 1.6 kg

M11

M13

86

818

(8)

41

(8)

2.5

25,4

78,5

cable 8 14

45
260

78,5

818

28

cable 14 18

24
30
(15)
(87)

200

25,4

92

30
60

M12

20

M12

200
M12

Figure 18: Line clamp


Order code M11 or M13; 0.1 kg
10

Figure 19: Stainless steel cap 200


260
Order code M71; 5 g

24
3

30
(15)
(87)

200

30
60

M12

260

260

260

M12

24

260

14.3

69

30
(15)
(87)

46

40

25

63
57

40

14.3

41

76

35

18

368 (14.5")
327

78

14

178

Order information
Outline drawings for common design
options are shown in figure 20, 21 and 22

Part number

3 E K 7 300

Medium voltage surge arrester

3 E K 7

Rated voltage in kV x 10

Z R51 M81 P12 P31

300

Classification
Distribution class, heavy duty (IEEE)

Nominal discharge current In = 10 kA (IEC)


or distribution class, riser pole (IEEE)

Standard
IEEE Std C 62.11 with imperial-thread terminals

IEEE Std C 62.11 with metric-thread terminals

IEC - 60099-4 with metric-thread terminals

Housing size, creepage distance

Figure 20: 3EK7 surge arrester with


accessories P12 and P31

170 mm

200 mm

240 mm

270 mm

300 mm

400 mm

470 mm

510 mm

Form of sheds
Alternating sheds

Accessories*

High-voltage terminal equipped with


Line clamp M11

M11

L-bracket

M12

Line clamp M13

M13

Line lead, insulated, 455 mm/18 inch, 16 mm2


Stainless steel cap

R51
M71

Bird protection cap

M81

Earth terminal equipped with


NEMA metal bracket (hot dip galvanized steel)

Figure 21: 3EK7 surge arrester with


accessories P12, P31 and Q51

P11

NEMA insulating bracket

P12

DIN metal bracket (hot dip galvanized steel)

P21

DIN insulating bracket

P22

Disconnector

P31

Ground strap, 245 mm

P52

Ground lead, insulated, 455 mm/18 inch, 16 mm2

R51

Mounting auxiliaries
Transformer bracket (8.7 inch)

Q11

Transformer bracket (11 inch)

Q12

Transformer bracket (12.25 inch)

Q13

Transformer bracket (14.5 inch)

Q14

X-arm bracket

Q51

Mounting plate for 200 mm and 10 inch bolt circle

Q81

*Other additional parts on request, not all combinations are possible

Standard accessories at

Figure 22: 3EK7 surge arrester


with accessories P12, P31, P52 and Q11

high-voltage terminal: M12 or 3/8 inch stud, standard clamp,


washer and nut
earthing terminal: M12 or 3/8 inch stud, washer and nut
11

Published by and copyright 2011:


Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany

Siemens AG
Energy Sector
Power Transmission Division
High Voltage Products
Nonnendammallee 104
13629 Berlin, Germany
www.siemens.com/energy/arrester

Please contact us at:


Phone: +49 30 386 33 222
Fax:
+49 30 386 26 721
E-mail: arrester.energy@siemens.com

Power Transmission Division


Order No. E50001-G630-A110-V2-4A00 | Printed in Germany |
Dispo 30002 | c4bs No. 7457 |
TH 263-110140 | W | 472573 | WS | 11111.0

Printed on elementary chlorine-free bleached paper.


All rights reserved.
Trademarks mentioned in this document
are the property of Siemens AG, its affiliates,
or their respective owners.

Subject to change without prior notice.


The information in this document contains general
descriptions of the technical options available, which
may not apply in all cases. The required technical
options should therefore be specified in the contract.

Vous aimerez peut-être aussi