MEASUREMENTS

ISTAT I300
High Accuracy Analogue Transducers

Improving competitiveness and performance is key to any business. New solutions must be developed to optimise the assets, benefit from the latest technology capabilities and adapt to the rapidly changing environment. T&D offers complete solutions for the entire energy chain, from the primary equipment up to the market management software. The ISTAT I300 range of analogue transducers is designed to meet the world market requirements of high accuracy and reliability with a stable output. Available in two compact case sizes of 55mm and 150mm wide, the transducers are supplied to meet the customers precise needs.

APPLICATIONS
Applications can be found in substations of electrical utilities and industry, for interfacing with SCADA (Supervisory Control and Data Acquisition), building management systems, process control equipment and switchboard instrumentation. ISTAT I300 analogue transducers provide local and remote indication for precision electrical measurement and control when used with instruments, data loggers and SCADA systems.

WHY ISTAT I300 ANALOGUE TRANSDUCERS?


Customer Benefits Comprehensive set of measurements Proven reliabilty gained from over 30 years of manufacturing knowledge High accuracy and stability
ISTAT I300 transducers have been designed to provide highly accurate and reliable measurements for integration into control systems. The transducer design was based on research into the market needs on an international and industrial scale.

AREVA T&D

ISTAT I300
Features and benefits
FEATURES
> 0.2% full scale accuracy for current and voltage transducers > 0.2% of reading accuracy for watt and var transducers (based on 0.19% of reading + 0.01% FSD) > 4KV isolation withstand > 3 x continuous current overload rating > Integral dc auxiliary supply option > DIN rail mounting > High packing density > Full range of ac and dc measurements > High stability

AC MODEL RANGE
Model
3CA 3CC 3CD 3CF 3FA to 3FD 3FE to 3FG 3K 3P 3R 3VA 3VC 3VD 3VF 3VL 3VX 3W

Application
Mean sensing Current Triple Mean sensing Current True RMS Current Triple True RMS Current 0.1% Frequency 0.01% Frequency Watt hour Phase Angle range Vars range Mean sensing Voltage Triple Mean sensing Voltage True RMS Voltage Triple True RMS Voltage Linear Inverse Voltage Suppressed Zero Voltage Watts range

Case
55mm 150mm 55mm 150mm 55mm 150mm 150mm 150mm 150mm 55mm 150mm 55mm 150mm 55mm 55mm 150mm

DC MODEL RANGE BENEFITS


Model
3DA 3DB 3DC 3DD 3DH 3DL 3DJ

Application
Tap Position Indicator Voltage Current Summation Thermocouple 3 wire Resistance Thermocouple with CJC

Case
150mm 150mm 150mm 150mm 150mm 150mm 150mm

> Significant gains in overall system accuracy can result from improvements in source measurement > Compliance with international standards ensures transducers can be used world wide > Long life expectancy and very reliable operation in most climates > Quick and simple means of transducer selection > Three voltage or current transducers can be housed in a single 150mm package > Can be integrated into modern control schemes utilising analogue technology > Gives accurate measurements of parameters critical for optimum plant use. > Minimal maintenance costs as readjustment is not required

DC/DC CONVERTER RANGE


Model
3BA 3BB 3BC 3BD 3BE 3BG

Application
24V 32V 48V 110V 125V 220/48V (use with 3BC)

Case
55mm 55mm 55mm 55mm 55mm 55mm

2>3

ISTAT I300: Used by Industrial or Utility engineers, at all voltage levels

RANGE
> AC Mean Sensing Current and Voltage The 3CA current and 3VA voltage transducers will only require an external power supply if a biased 420mA output is required. These transducers require a full specification before manufacture can take place, these settings cannot be changed by the user. The 3CC and 3VC are triple versions and are housed in the larger 150mm case.

Technical specification Current nominal input Current range of use Current burden Current overload

Voltage Voltage Voltage Voltage

input range range of use burden overload

Technical specification Current nominal input Current range of use Current burden Current overload

Voltage input range Voltage range of use Voltage burden Voltage overload Frequency range

1 or 5A In 0 to 200% In 1.5VA (0.6VA biased output) 3 x In continuous 25 x In for 3s 50 x In for 1s 63.5 to 440Vn 0 to 150% Vn 1.0VA (0.3VA biased output) 1.5 x Vn continuous 2 x Vn for 10s 45/55 or 55/65Hz

Frequency range

1 or 5A In 0 to 200% In 1.0VA 3 x In continuous 25 x In for 3s 50 x In for 1s 63.5 to 440Vn 0 to 150% Vn 0.1VA 1.5 x Vn continuous 2 x Vn for 10s 45/55 or 55/65Hz

Acuracy of the analogue output Nominal accuracy 0.2% Current reference range 20 to 200% In Voltage reference range 25 to 150% Vn

> Frequency The 3F frequency transducer can be supplied with an accuracy of either 0.1% or 0.01%. It can be supplied with either an ac or dc auxiliary power supply. These transducers require a full specification before manufacture can take place, these settings cannot be changed by the user. 0.1% 45 55 48 58 47 55Hz 65Hz 52Hz 62Hz 53Hz 3FA 3FB 3FC 3FD N/a 0.01% N/a N/a 3FE 3FF 3FG

Acuracy of the analogue output Nominal accuracy 0.2% Current reference range 0 to 200% In (except biased output 0 to 100% In) Voltage reference range 25 to 150% Vn
(except biased output 20 to 100% Vn)

> AC True RMS Current and Voltage The 3CD current and 3VD rms voltage transducers can be supplied with either an ac or dc auxiliary power supply. These transducers require a full specification before manufacture can take place, these settings cannot be changed by the user. The 3CF and 3VF are triple versions and are housed in the larger 150mm case. The 3VX is a variant of the 3VD but is supplied with a suppressed characteristic.

Technical specification Voltage input range Voltage range of use Voltage burden

63.5 to 440V, Vn 0 to 120% V, Vn 1.5VA (0.1%), 0.1VA (0.01%)

Acuracy of the analogue output Nominal accuracy 0.1 or 0.01% Voltage reference range 80 to 120% Vn
for 0.1% and 20 to 120% Vn for 0.01% models

> Watt hour with pulsed and analogue output These transducers can be supplied with either an ac or dc auxiliary power supply with the exception of the 3KF which can also have the option of using the 3B Dc/Dc converter.. These transducers require a full specification before manufacture can take place, these settings cannot be changed by the user. Connection single phase 3 phase, 3 wire 3 phase, 4 wire 3 phase, 3 wire 3 phase, 4 wire 3 phase, 4 wire balanced, 1El balanced, 1El unbalanced, 2 El unbalanced, 2.5 El unbalanced, 3 El Wh 3KA 3KB 3KC 3KD 3KE 3KF

ISTAT I300: comprehensive ac measurement range

Technical specification Current nominal input Current range of use Current burden Current overload

Voltage Voltage Voltage Voltage

input range range of use burden overload

Frequency range

1A or 5A In 0 to 160% In 0.3VA 3 x In continuous 25 x In for 3s 50 x In for 1s 63.5 to 440V, Vn 0 to 150% Vn 0.1VA 1.5 x Vn continuous 2 x Vn for 10s 45/55 or 55/65Hz

Technical specification Current nominal input Current range of use Current burden Current overload

Voltage Voltage Voltage Voltage

input range range of use burden overload

Frequency range

1A or 5A In 0 to 160% In 0.3VA 3 x In continuous 25 x In for 3s 50 x In for 1s 63.5 to 440V, Vn 0 to 150% Vn 0.1VA 1.5 x Vn continuous 2 x Vn for 10s 45/55 or 55/65Hz

Acuracy of the analogue output Nominal accuracy 0.2% of reading Current reference range 10 to 160% In Voltage reference range 80 to 120% Vn Pulse output contact rating Maximum switching power 10W, 10VA Maximum switching voltage 125Vdc, 250Vac Maximum switching current 0.5A Isolation
750V rms between open circuits, 1kVrms between analogue output and relay contacts

TRANSDUCER OUTPUTS
True zero outputs 0 1mA 0 5mA 0 8mA 0 10mA 0 . 20mA 0 5 10mA 1 0 1mA 10 0 10mA 0 ... 10V 10 ...0...10V 0 ... 5V 5 ...0...5V Biased outputs 4 20mA 4 12 20mA Model number reference A B C D E H J K L M N P Model number reference F G

> Watts, Vars, phase angle and power factor These transducers can be supplied with either an ac or dc auxiliary power supply with the exception of the 3WF# and 3RF # which also have the option of using the 3B Dc/Dc converter. These transducers require a full specification before manufacture can take place, these settings cannot be changed by the user. Connection Watts Vars Phase Angle 3PA 3PB

AUXILIARY SUPPLY OPTIONS


AC Voltage Self powered 63.5V 69.3V 100V 110V 115V 120V 208V 220V 230V 240V 380V 415V 440V Model number reference A B C D E F G H J V K L M N

single phase 3 phase, 3 wire balanced, 1El 3 phase, 4 wire balanced, 1El 3 phase, 3 wire unbalanced,2 El 3 phase, 4 wire unbalanced, 2.5 El 3 phase, 4 wire unbalanced, 3 El Phase difference

3WA 3WB

3RA 3RB

3WC 3WD 3WE 3WF # N/a

3RN 3RD 3RH 3RF # N/a

3PC 3PD 3PE N/a 3PG

Acuracy of the analogue output


Nominal accuracy 0.19% of reading plus 0.01% full scale except 3P which are +1 degree 10 to 160% In 3W 40 to 150% Vn 3R 40 to 150% Vn 3P 20 to 150% Vn .

DC Voltage 24V 32V 48V 110V 125V 12V From 3B converter

Model number reference P R S T U W X

Current reference range Voltage reference range

4>5

> Tap Position Indication The 3DA indicates the tap position by measuring the tap resistance proportional to the actual tap position. The 3DA has a maximum of 33 taps. These transducers require a full specification before manufacture can take place, these settings cannot be changed by the user

> 3B DC/DC CONVERTER The 3B provides an isolated DC/DC power supply with the exception of the 3BG which is non isolated. The 3B is only designed for use with the ISTAT I300 transducer. The type and output voltage are: 3BA 3BB 3BC 24V dc 32V dc 48V dc 3BD 3BE 3BG 110V dc 125V dc 220/48V dc

Technical specification Resistance input Input impedance

50 to 10,000 ohms 1M ohm

Acuracy of the analogue output Nominal accuracy 0.5%

ORDERING INFORMATION
> The ISTAT I300 model number comprises of 10 digits, the first 6 designates the basic type of transducer whilst the next 3 are specific to the customers precise configuration. The last digit is for design suffix.

> Tap Position Indication resistor box The 3EA is a resistor box that is used with the 3DA to show the position of the tap changer. Each case has 26 terminals and so a maximum of 25 resistors can be wired out.

6 5

3 W D K E Basic Type, eg Watt 3ph 3wire See Transducer output table, page 4 See Auxiliary Supply Options table, page 4 Frequency

> DC Voltage and current The 3DB voltage and 3DC current transducers measure DC values and convert them to a proportional DC analogue value. These transducers require a full specification before manufacture can take place, these settings cannot be changed by the user

Depending on the transducer, the following information is also required : Input parameters Voltage, Current and power in secondary values Transformer ratios and voltage, current and power in primarly values Scaling information : Output parameters How is the analogue output configured, is it based on primary or secondary values, and what do the maximum and minimum analogue outputs scale to. > 3B DC/DC CONVERTER The DC/DC converter follows a different model numbering system using only 6 digits.

Technical specification Current nominal input Current range of use Voltage input range Voltage range of use Input impedance

1mA to 20mA 0 to 120% In 10mV to 500V 0 to 120% Vn 1M ohm (10mV to 1V dc) 1K ohm/V (1V to 500V dc)

1 3 Basic Type, eg 48V

2 B

3 C

4 0

5 0

6 1

Number of outputs, eg 1or 2 (note)


Note : the 3BG has only a single output, but this can be used to supply upto 8 3BC 48V converters.

Acuracy of the analogue output Nominal accuracy 0.2% Current reference range 0 to 120% In Voltage reference range 0 to 120% Vn

> 3EA RESISTOR BOX The 3EA resistor box has 9 digits in the model number, the first 3 identify the type, the next 2 digits the number of resistors, the next 3 digits the resistor values and the last digit being the design suffix.

6 3

7 9

8 0

9 B

3 E A 2 2 Type Number of resistors, eg 22 Resistor value, eg 390 ohms Design suffix, eg B

A special 3EA resistor box has been designed for use with the MICOM KVGC voltage regulation relay, this is called 3EA22A390A

ISTAT I300: comprehensive dc measurement range

> Resistance The 3DL (3-wire measurement) transducer measures a resistance value and converts this to a proportional DC analogue value. The 3DL is designed for use with PT100 temperature probes. These transducers require a full specification before manufacture can take place, these settings cannot be changed by the user.

Dc Technical specification Voltage input 12 to 125V, Vx Operating range 80 to 140% Vx Power supply burden 2VA

> Compliance and open circuit voltage on the analogue output

Technical specification Resistence input Input impedance

Compliance voltage Open circuit voltage

15V (note below) 25V

10 to 300 ohms 1M ohm

Note: The compliance voltage for mean sensing 0...1mA output is 12V, for combined Watt/Var is 11V.

Acuracy of the analogue output Nominal accuracy 0.5%

> Temperature Reference range 0 50 C except 3F 0 . 40 C 0.008%/ C except 3VX 0.04%/C 3F class 0.1Hz 0.004%/C 3F class 0.01Hz 0.001%/C 3P 0.02 degree / C -10 . . . +60 C

> Temperature (thermocouple) The 3DH transducer measures temperature and converts this to a proportional DC analogue value. The 3DH is designed for use with thermocouples. The 3DJ also offers cold junction compensation (CJC). These transducers require a full specification before manufacture can take place, these settings cannot be changed by the user. Temperature co-efficient

Nominal range of use

> Applicable standards

Technical specification Voltage input Input range Input impedance

Isolation
5mV to 50mV, Vn 0 to 120% Vn 1M ohm 4kV rms 50Hz for 60 seconds

Impulse test
5kV (1.2/50us) for BS923 and IEC 60255-22-1

Acuracy of the analogue output Nominal accuracy 1.0% Voltage reference range 0 to 100% Vn

Surge withstand
IEC 60255-22-1 and ANSI C37-90A IEEE std 472 SWC where applicable

Electromagnetic compatibility

TECHNICAL SPECIFICATION
> Auxiliary supply Transducers can be supplied as self powered, dc or ac powered.

EN50081-2:1994 Emissions EN50082-2:1995 Immunity Directive 89/336/EEC

Safety requirements
EN61010-1:1993 Directive 72/23/EEC

Humidity, non condensing


93% RH

Ac Technical specification Voltage input Operating range Frequency range Power supply burden

63.5 to 440V , Vx 80 to 120% Vx 45 - 65Hz 2VA

6>7

CASE OUTLINE AND FIXING DETAILS

Detachable terminal covers 120 55

1,5

35

55

78

74

Terminal No.1

10,7

Terminal pitch

DIN rail fixing 35 x 7,5 DIN rail to spec EN 50 022 (B.S. 5584)

3 2 Holes 5,4 to accept M5 stud fixing as alternative to DIN rail 9

128

60

40 7,5 Outline of 55mm case

Detachable terminal covers


150

1,5 120

55 35

78

74

Terminal No.1

10,7

Terminal pitch

DIN rail fixing 35 x 7,5 DIN rail to spec EN 50 022 (B.S. 5584) 4 Holes 5,4 to accept M5 stud fixing as alternative to DIN rail 9

128

60

135 7,5 Outline of 150 mm case

AREVA T&D Worldwide Contact Centre: http://www.areva-td.com/contactcentre/ Tel.: +44 (0) 1785 250 070

www.areva-td.com www.areva-td.com/measurements

Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

AUTOMATION-L3-I300-BR-07.05-1039-GB - - AREVA - 2005. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA. ISTAT and MiCOM are registered trademarks of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP