DIA/PUR/2012-13/0069 R.K.ENGINEERS, No. 99, Block 1, MIG Karelibaug, Baroda-390018 Phone-0265-2461611 Attn: Mr. D. K.

Narasimhan Sub: Testing of Relays, Circuit breakers, CTs and PTs at GSECL Utran. Ref: Your email dated May 7, 2012 Dear sir, With reference to above email, we are pleased to confirm our order as follows: SCOPE OF WORK: A) RELAY TESTING:

May 7, 2012

All relays shall be tested by single / three phase secondary injection as per manufacturers recommendation using DOBLE Power simulator. The microprocessor relay shall be tested after the relay has been programmed or shall be tested at the default settings. Final setting of all protective & metering devices shall be incorporated as per your system requirements / co-ordination reports. All other voltage & auxiliary relays shall be tested for their pick-up & drop-off values. Their contact changeover shall be checked. B) CTs and PTs TESTING: i) Current Transformer: The CTs shall be cleaned and physically checked. a) Polarity test b) IR test c) Primary injection test for Ratio and circuit checking d) Knee point voltage, exciting current and secondary resistance in case of class PS CTs ii) Potential Transformer The PT's shall be cleaned and physically checked. a. IR values. b. Polarity test. C. Ratio and circuit test C)INDOOR HT BREAKERS : The breakers shall be physically inspected & checked. Contact resistance shall be checked by milli-volt drop test. Open & closing timings of the breaker shall be taken & recorded.

RATE SCHEDULE :

GENERAL TERMS & CONDITIONS : The job shall be completed to the satisfaction of the Engineer in-charge. The quoted rates are service charges only. All spares & consumables will supply by us(GSECL). Single phase & three phase supply will available at site. Test certificates in duplicate shall be submitted within 2 weeks after completion of job. Testing team shall be mobilized within 10 days after receipt of order. Payment terms: 100 % within 15 days on completion of job. (After submission of detailed reports) Report: You will have to give 1 soft copy & 3 hard copies of the report. CUSTOMER: Gujarat State Energy Generation Corporation, 370 MW, CCPP II GBPS, UTRAN (Dist. Surat) 394105. Shutdown is scheduled from 15/05/2012.Exact date will be advised to you soon. Our liaison persons: Mr. Manohar Rahate-09423284423 Mr. Shashikant Utekar-09423364413 Customers Engineer Mr. A .A. Amir (Executive Engineer)-09909940718 Best regards, For Diagnostic Technologies India Pvt. Ltd.

S. D. Korde Managing Director

Vous aimerez peut-être aussi