Training Report
HUB
A
HUB
B
CPM UA UB
Connection dialog:
Control Builder program
Cases:
1. Client Problems
If the back up server that has problems just do the case no 1, because if
SERVER A is the primary server so the SERVER B is just a client. The same
case happened if the primary server is SERVER B so the SERVER A is just a
client
In this condition all the clients is displaying Nan value in all indication, in
normal condition the primary server being handled by the other server and just
connect to server that active and do the procedure as bellow:
All the power to DCS computer shutdown and when it come back the system
restart not in normal way. It may cause the CPM not working or Idle. So the
connection to server abnormal, we can see the red light in network card to
CPM so in these case do the bellow procedure:
1. check server A & B the light on the network card is green or red, if red
restart the computer if green do the next procedure.
2. in control builder program on server B right click to CPM01 that is in
blue color and choose active tab and select CEE and all content.
3. If you see the server A is ok
4. Change Manually from the station program, the primary server to A
5. Client connect to A
5. Trend Error