The EnerSys range of PowerSafe V Front Terminal Valve Regulated Lead Acid (VRLA) batteries has been designed specically for use in applications that demand the highest levels of quality and reliability, now with optional top termination on many V series models. With proven compliance to the most rigorous international standards, PowerSafe V batteries are recognized worldwide as the premium battery for Telecom applications. The PowerSafe V batterys reputation for long service life, together with excellent high rate performance, also makes it ideal for high integrity, utility-industry switch gear applications. PowerSafe V batteries deliver superior performance while occupying less space than conventional standby power batteries. The PowerSafe V Front Terminal battery's compact design, suitable for 19 inch, 23 inch and ETSI (European Telecommunications Standards Institute) racking, provides users with the benet of increased energy density. With electrical connections at the front or on top on many models, installation and inspection are safer, quicker and easier. PowerSafe V batteries are designed using proven gas recombination VRLA technology, which removes the need for regular water addition by controlling the evolution of hydrogen and oxygen during charging. Each cell incorporates its own safety valve that allows automatically the controlled release of small amounts of gas when pressure builds up within the cell. The use of gas recombination technology for lead acid batteries has totally changed the concept of standby power. This technology provides the user with the freedom to use lead acid batteries in a wide range of applications.
T E R M I N A L
NCR48-V-170-4
NCR24-V-170-5-B
RESERVE POWER
Publication No: US-VFT-RS-009 August 2010
range is designed for safer installation and easy maintenance in cabinets or on stands, close to the point of use. A separate battery room is not necessary
It is recommended that PowerSafe V Front Terminal batteries are installed on their base Recommended oat charge voltage (27.36 VDc, 54.72 VDc) at 68F (20C) (27.18 VDc, 54.36 VDc) at 77F (25C) Six-month shelf life Reduced maintenance - no water addition required Maximum AC ripple voltage 0.5% RMS or 1.5% P.P. Operating temperature On Charger: -4F (-20C) to 122F (50C) Off Charger: -20F (-30C) to 113F (45C) Only water should be used to clean cover and container
General Specications
Capacity (Ah)
PowerSafe V Battery Type Number Nominal of Voltage Cells (V) 10 hr rate to 1.80Vpc @ 20C 8 hr rate to 1.75Vpc @ 77F Length mm in
Dimensions
Width mm in Overall Height mm in kg Typical Weight lbs Short Circuit Current (A) Internal Resistance (m) Installation Torque in-lbs Nm
Notes: * With rope handles; Optional handle MISC-0345 Data subject to change without notice
W L
Telcordia Values
PowerSafe Battery Type
CLEI
CPR
12V155FS 12V170F
12V155FS
www.enersys.com
Publication No. US-VFT-RS-009 - August 2010 - Subject to revisions without prior notice. E.&O.E.
12V30FT 12V38FT 12V62FT 12V92F-FT* 8V100F* 12V100FC 12V101F 12V105FS* 12V125F* 12V145F* 12V155FS* 12V170F* 12V170FS* 12V190F*
6 6 6 6 4 6 6 6 6 6 6 6 6 6
12 12 12 12 8 12 12 12 12 12 12 12 12 12
31 38 62 92 100 100 100 105 125 145 150 170 170 190
31 38 62 92 100 100 101 107 126 145 155 170 170 190
303 303 303 417 384 395 510 561 561 452 561 561 561 561
11.9 11.9 11.9 16.4 15.1 15.6 20.8 22.1 22.1 17.8 22.1 22.1 22.1 22.1
97 97 97 105 125 108 110 125 105 172 125 125 125 125
3.8 3.8 3.8 4.1 4.9 4.3 4.3 4.9 4.1 6.8 4.9 4.9 4.9 4.9
159 184 264 256 228 287 235 228 316 238 283 316 283 316
6.3 7.2 10.4 10.1 9.0 11.3 9.3 9.0 12.4 9.4 11.1 12.4 11.1 12.4
10.8 12.5 19.7 28.0 32.0 30.8 33.5 40.5 46.0 47.6 57.0 67.0 50.5 57.3
23.8 27.6 43.5 61.7 70.5 67.9 73.9 90.0 101.4 105.0 125.6 147.7 111.3 126.3
1327 1500 2100 2500 3636 1900 2108 2455 2845 4100 3714 3667 2950 3625
9.87 8.53 5.87 5.05 2.20 6.60 5.92 4.40 5.07 3.00 3.30 3.40 4.30 3.50
44 44 44 44 44 44 80 80 80 80 80 80 80 80
5 5 5 5 5 5 9 9 9 9 9 9 9 9