ACG Commissioning Guideline Appendix D

Appendix D Sample Functional Performance Test Checklists


NOTES TO APPENDIX D This appendix contains sample functional performance test checklists for a number of commonly used HVAC systems. The information for each system includes the following: 1. a description of the system including its ma!or components ". a table showing all modes of operation with the status or position of key e#uipment in each mode $. a se#uence of operations and %. the functional performance test checklist that corresponds to the preceding information. There is no intention in the appendix to pro&ide sample checklists for all possible systems included in any design. These checklists are intended to pro&ide basic information about each system so that the functional performance test checklists will logically follow from it and they will illustrate a le&el of detail that is appropriate in good commissioning practice and to suggest a practical format. The sample functional performance test checklists are generic' thus they do not apply to any specific pro!ect and so the list of test items is generic not specific. Commissioning agencies must de&elop functional performance test checklists for e&ery system included within the scope of any commissioning pro!ect and those checklists must include e&ery mode of operation and se#uence of operation co&ering normal abnormal and emergency conditions that could occur in the specific design. There is a Table of Contents on the next page listing the sample checklists included in this appendix. AC( assumes no responsibility for how the material in this Appendix might be utili)ed by users of the (uideline' the users assume full responsibility for any and all liability that may arise from any reference to or use of this material.

*age +,1

ACG Commissioning Guideline Appendix D

TABLE OF CONTENTS

Chilled -ater .ystem.................................................................................................+,% -ater /oop Heat *ump .ystem................................................................................+,10 1ake,up Air and 2xhaust .ystem.............................................................................+,"3 *ackaged 4ooftop (as Heat5+6 Cool .ystem.........................................................+,"$ Variable Air Volume .ystem....................................................................................+,"7

*age +,"

CHILLED WATER SYSTEM


.8.T21 +2.C49*T9:; The chilled water system is typical of one that may be installed in a large office building. The system consists of: $ chillers CH,1 through CH,$. Chiller CH,1 is smaller than CH," and CH,$. 1 plate heat exchanger H2,1. 9t is located between the condenser water system <C-.= and the chilled water system <CH-.= in order that condenser water from the cooling towers may be used to directly cool the chilled water without the chiller<s=. " cross,flow cooling towers CT,1 and CT,". 2ach has a high speed and low speed motor dri&ing common shaft mount fans. A modulating condenser water bypass &al&e allows the condenser water to bypass the cooling towers in order to maintain flow without going below the temperature set point. 0 chilled water pumps: " for the plate heat exchanger *,1 > *," and 1 for each chiller *,$ *,% > *,0 0 condenser pumps: 1 for the plate heat exchanger *,? 1 for the filter *,7 and 1 for each chiller *,@ *,A > *,13 A modulating chilled water bypass &al&e controls the differential pressure across the supply and return piping. The chilled water distribution system ser&es cooling coils in air handling units. The system has the following modes of operation: .hutdown :ff .tart,up Bree cooling <occupied or o&erride= Chiller <o&erride= Chiller <occupied=

*age +,$

CHILLED WATER SYSTEM


1:+2. :B :*24AT9:;
Shutdown P-)
<H2,1 chilled water=

Off :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :pen :pen Cycle open5closed Cycle open5closed

Start-u :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :pen :pen Cycle open5closed Cycle open5closed

Fr!! Coo"#n$ 1odulating :ff5:n :n :ff :ff :ff :ff :ff :ff :ff :ff :ff Cycles Cycles

Ch#""!r %o&!rr#d!' :ff :ff :ff :n


<with CH,1=

Ch#""!r %o((u #!d' :ff :ff :ff :ff


<except in high load conditions=

:ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :ff :pen :pen Closed Cycle open5closed

P-*
<H2,1 chilled water=

P-+
<H2,1 condenser water=

P-,
<CH,1 chilled water=

P-<CH," chilled water=

:ff :ff :n
<with CH,1=

:n
<with CH,"=

P-.
<CH,$ chilled water=

:n
<with CH,$=

P-/
<CH,1 condenser water=

:ff
<except in high load conditions=

P-0
<CH," condenser water=

:ff :ff 1odulating


<after free cooling=

:n
<with CH,"=

P-)1
<CH,$ condenser water=

:n
<with CH,$=

CH-)
<Chiller=

:ff
<except in high load conditions=

CH-*
<Chiller=

:ff :ff Cycles Cycles

1odulating
<lead5lag with CH,$=

CH-,
<Chiller=

1odulating
<lead5lag with CH,"=

CT-)2 CT-*
<low and high speed fans=

Cycles Cycles

P-3
<Bilter=

<with *,? @ A > <with *,? @ A > <with *,? @ A > 13= 13= 13=

Cond!n4!r Wat!r B5 a44 6a"&! Ch#""!d Wat!r B5 a44 6a"&! Cond!n4!r Wat!r Ma7!u 6a"&! Ch#""!d Wat!r Ma7!-u 6a"&!

1odulating Closed Cycle open5closed Cycle open5closed

1odulating 1odulating Cycle open5closed Cycle open5closed

1odulating 1odulating Cycle open5closed Cycle open5closed

*age +,%

CHILLED WATER SYSTEM


.2CD2;C2 :B :*24AT9:;. .1 ." .$ This se#uence to be read in con!unction with the control drawings and points list. The ++C system shall determine when the chillers are to operate based on a building demand program by monitoring the &arious space temperatures as well as the outdoor air temperature. Heat exchanger H2,1 shall be initiated as the source of chilled water when the outdoor air is cold enough to permit this. The ++C system shall start the respecti&e chilled water pump and cycle the condenser water pumps and the cooling tower fans in stages in order to maintain the chilled water supply temperature setpoint of %%EB. <ad!ustable=. 1odulate the tower bypass &al&e in order to maintain condenser water temperature if the outdoor air temperature is low and the cooling tower fans are off . .witcho&er from H2,1 to the chillers if the condenser water temperature is abo&e %%EB. <confirm with chiller manufacturer for exact conditions=. Chiller CH,1 shall be enabled if the demand for cooling is during the unoccupied mode < e.g. ,one Bloor on o&erride mode =. Chillers CH," and CH,$ shall operate during the occupied mode based on a lead5lag arrangement with the changeo&er duration being no less than 1 day. The ++C system shall enable the selected chiller for operation and the chiller shall start its respecti&e chilled water and .condenser water pumps. The water flow switches are wired to the chiller control panel. The ++C system shall monitor the status of the chiller through a dry contact pro&ided by the chiller manufacturer and shall annunciate an alarm if this contact indicates the chiller is malfunctioning .witch o&er to an alternate chiller shall be automatically done &ia the ++C system. The ++C system shall monitor the status of each purge and annunciate an alarm on a pump failure. The selected chiller shall immediately be shut down and the alternate chiller selected. The ++C system .hall pro&ide an analog signal <%,"3 mA ",13 V+C = to the chiller control panel which shall be used to reset the chilled water supply temperature set point based on the building cooling load as represented by AHD cooling coil control &al&e positions. As the CH-4 temperature rises abo&e 0"EB the CH-. temperature set point shall be decreased as re#uired 9f any space temperature is abo&e the acceptable limit the CH-. set point shall be reduced accordingly The minimum allowable CH-. temperature shall be %"EB. The second chiller shall be enabled if the CH-4 temperature continues to rise abo&e 0%EB and the lead chiller has been operating at full capacity for at least "3 minutes. 9f the building occupied mode is nearly o&er the ++C system shall determine if the lag chiller may be kept off while still maintaining reasonable space conditions. These limits shall be confirmed with the consultant. :perate all three chillers simultaneously when the cooling load is &ery high. This shall only be done if it is earlier than %:33 *.1. <ad!ustable= and the CH-. temperature is more than 1.3EB abo&e setpoint.

.% .0 .?

.7 .@ .A

.13 .11

.1"

.1$

*age +,0

CHILLED WATER SYSTEM


.1% The ++C system shall modulate the pressure bypass &al&e between the CH-. line and the CH-4 line based on the difference between the two as sensed by a differential pressure transducer in order to maintain water flow through the chillers and H2,1 at all times. The differential pressure setpoint shall be changed to suit the chilled water pump operating at the time. The ++C system shall cycle the cooling tower fans in se#uence as re#uired to maintain the condenser water supply temperature set point. This set point is to be initially set at @3EB but shall be confirmed with the chiller manufacturer to ensure maximum chiller efficiency is maintained and no surging takes place. The ++C system shall monitor the cooling tower fansF current draw and shall annunciate an alarm upon a fan failure. ++C system shall pro&ide a 10 second time delay before the low speed is energi)ed when switching from high speed to low speed fan operation. The ++C system shall monitor a sump water le&el switch in each cooling tower. The ++C system shall open the two way water make up &al&e located in the Gasement 1echanical 4oom when the water le&el is below normal. The &al&e shall close when the desired water le&el is reached. The ++C system shall monitor the current draw of the Cooling Tower Biltration pump and annunciate an alarm upon pump failure.

.10

.1? .17 .1@

.1A

*age +,?

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST CHILLED WATER SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< Shutdown =od!< %h!at#n$ on"5 4!a4on' *lace the system into a seasonal Hshutdown modeI by manual command. Confirm that all 13 pumps <*,1 thru *,13= are commanded :BB by ++C J pump on5off +: points. Confirm that CT,1 and CT," fans both high > low speed are commanded :BB by ++C J CT fan on5off +: points. Confirm that chilled water > condenser water bypass &al&es are commanded to 133K bypass J &al&e A: points L 3. Confirm that cooling tower water make,up solenoid &al&e is closed regardless of tower basin water le&el J solenoid &al&e open5close +: point. Off =od!< %(oo"#n$ 4!a4on' This mode applies when the system is acti&e <i.e. has been taken out of shutdown mode= but the chilled water se#uence is disabled. Confirm that all 13 pumps <*,1 thru *,13= are commanded :BB by ++C J pump on5off +: points. Confirm that CT,1 and CT," fans both high > low speed are commanded :BB by ++C J CT fan on5off +: points. Confirm that chilled water > condenser water bypass &al&es are commanded to 133K bypass J &al&e A: points L 3. .imulate low water le&el in CT,1 basin. Confirm that cooling tower water make,up solenoid &al&e opens. .imulate normal water le&el in CT,1' confirm the solenoid &al&e closes. 4epeat for CT,". /ocation: 2#uipment:
PASS NOTE FAIL

NOTES< 1. ".

Continued on next page: Checks performed by:


print name signature

+ate: *age +,7

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST CHILLED WATER SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< Start-u =od!< This mode applies when the building is occupied <on time schedule or when :BB time o&erride is in effect= and a cooling demand exists. Test 1 J Confirm that :A temp N OOOEB <or simulate this condition=. Test " J place building in Hoccupied statusI by time,of,day <T:+= schedule. Test $ J 2nsure a cooling demand exists or is simulated based on AHD cooling coil control &al&e positions. Confirm that chilled water se#uence is enabled. 4epeat but with Test " placing building in occupied status by manual o&erride. Confirm that chilled water se#uence is enabled. .imulate low water le&el in CT,1 basin. Confirm that cooling tower water make,up solenoid &al&e opens. .imulate normal water le&el in CT,1' confirm the solenoid &al&e closes. Coo"#n$ tow!r o !rat#on< Check condenser water supply <C-.= temp setpoint J A9 point. 4ecord it: OOOOEB .tarting condition J C-. temp is more than "EB below setpoint with condensing water bypass &al&e at least partly open. +uring the following tests simulate C-. temps as needed to test total load range. The actual break points for each stage will depend on the specific ++C settings. 9ncreasing /oad: -hen C-. temp N <setpoint J 1.0EB=' confirm that condenser water bypass &al&e modulates to fully closed to tower J A: point. -hen C-. temp N <setpoint J 3.0EB=' confirm that CT,1fan starts on low speed. -hen C-. temp N <setpoint P 3.0EB=' confirm that CT,"fan starts on low speed. -hen C-. temp N <setpoint P 1.0EB=' confirm that CT,1fan switches from low,speed to high, speed. -hen C-. temp N <setpoint P ".0EB=' confirm that CT,"fan switches from low,speed to high, speed. /ocation: 2#uipment:
PASS FAIL

NOTE

NOTES< 1. ".

Continued on next page: Checks performed by:


print name signature

+ate: *age +,@

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST CHILLED WATER SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< Cont#nu!d +ecreasing /oad: -hen C-. temp Q <setpoint P ".3EB=' confirm that CT," fan switches from high,speed to low, speed with a 10 sec delay between deacti&ating high,speed and acti&ating low,speed. -hen C-. temp Q <setpoint P 1.3EB=' confirm that CT,1 fan switches from high,speed to low, speed with a 10 sec delay between deacti&ating high,speed and acti&ating low,speed. -hen C-. temp Q setpoint' confirm that CT," fan shuts :BB. -hen C-. temp Q <setpoint J 1.3EB=' confirm that CT,1 fan shuts :BB. -hen C-. temp Q <setpoint J ".3EB=' confirm that condenser water bypass &al&e starts to modulate open to tower. /ocation: 2#uipment:
PASS NOTE FAIL

Check operation of: Test fan failure alarms on CT,1 low and high speed J based on fan current draws and commanded state. Test CT," fan failure alarms as abo&e. 2nable any of pumps *,? *,@ *,A or *,13' confirm that cooling tower filtration pump *,7 is acti&ated by ++C. Test se&eral combinations of *,? *,@ *,A and *,13. Test *,7 failure alarm J low or no current draw when pump is commanded :;. Test cooling tower filter backwash se#uence timer and operation. Test operation of chemical treatment feed pumps J 1 for corrosion control " for biocides.

NOTES< 1. ".

Continued on next page. Checks performed by:


print name signature

+ate: *age +,A

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST CHILLED WATER SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< Cont#nu!d Fr!! (oo"#n$ =od! > thru h!at !?(han$!r< %o((u #!d or o&!rr#d! =od!4' %on(! !r da5' -hen :A temp <A9= Q %0EB <ad!ustable= confirm that pumps *,"<+:= and *,?<+:= start. -hen :A temp <A9= N 03EB <ad!ustable= confirm that pumps *,"<+:= and *,?<+:= stop. Chilled water operation: As cooling load increases so does chilled water flow thus reducing chilled water system supply pressure. -hen supply pressure drops below setpoint confirm that pump *,1 starts <+:= and modulates <A:= to maintain CH- supply pressure. -hen supply pressure rises abo&e setpoint confirm that after a time delay pump *,1 stops <+:=. /ocation: 2#uipment:
PASS NOTE FAIL

Condensing water operation J increasing cooling load: -hen CH-. temp N <setpoint J 1.3EB=' confirm that condenser water bypass &al&e modulates to fully open to tower J A: point. -hen CH-. temp N <setpoint J 3.0EB=' confirm that CT,1fan starts on low speed. -hen CH-. temp N <setpoint=' confirm that CT," fan starts on low speed. -hen CH-. temp N <setpoint P 3.0EB=' confirm that CT,1fan switches from low,speed to high, speed. -hen CH-. temp N <setpoint P 1.3EB=' confirm that CT," fan switches from low,speed to high, speed. -hen CH-. temp N <setpoint P 1.0EB= free cooling cannot meet cooling load' confirm that chiller se#uence is enabled. -hen lead chiller has started' confirm that pumps *,1 *," and *,? stop.

NOTES< 1. ".

Continued on next page: Checks performed by:


print name signature

+ate:

*age +,13

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST CHILLED WATER SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< Cont#nu!d Condensing water operation J decreasing cooling load: 4ele&ant when CH-. temp stays below setpoint P 1.0EB -hen CH-. temp Q <setpoint P 3.70EB=' confirm that CT," fan switches from high,speed to low, speed with a 10 sec delay between deacti&ating high,speed and acti&ating low,speed. -hen CH-. temp Q <setpoint P 3."0EB=' confirm that CT,1 fan switches from high,speed to low, speed with a 10 sec delay between deacti&ating high,speed and acti&ating low,speed. -hen CH-. temp Q <setpoint J 3."0EB=' confirm that CT," fan shuts :BB. -hen CH-. temp Q <setpoint J 3.70EB=' confirm that CT,1 fan shuts :BB. -hen CH-. temp Q <setpoint J 1."0 EB=' confirm that condenser water bypass &al&e starts to modulate open to bypass. /ocation: 2#uipment:
PASS FAIL NOTE

Check operation of: *,1 status alarm <+9=<aux. contact= *," status alarm <+9=<aux. contact= *,? status alarm <+9=<aux. contact= *,7 status alarm <+9=<aux. contact= Ch#""!r =od!<%o&!rr#d! =od!<' Confirm that acti&ating manual o&erride enables chiller operation in o&erride mode. CH,1 <+:= enabled when C-. <A9= N 13 C. *umps *,$ > *,@ hardwire start from CH,1. Chilled water bypass &al&e <A:= ++C modulates to maintain system differential pressure <A9= setpoint CH,1 <A:= CH-. setpoint <A9= is reset from demand based on the AHD RR CH- control &al&e <A:= position and the CH-4 <A9= temperature.

NOTES< 1. ".

Continued on next page: Checks performed by:


print name signature

+ate: *age +,11

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST CHILLED WATER SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< Cont#nu!d Ch#""!r =od! %o((u #!d =od!' .e#uence written with CH," as lead chiller CH,$ as lag chiller Temper <warm= C-. to N03EB <ad!ustable= if needed using H2,1 -hen C-. N 03EB' confirm CH," <+:= is enabled when CH-4 <A9= N 0"EB for N "3R min. and T:+ Q 1?:33 and CH-. temperature N %%EB. Confirm pumps *,% > *,A hardwire start from CH," :peration J increasing cooling load: Chilled water bypass &al&e <A:= ++C modulates to maintain system differential pressure <A9= setpoint CH," <A:= CH-. setpoint is reset from demand based on the AHD RR CH- control &al&e <A:= position and the CH-4 <A9= temperature. CH-. minimum limit is %"EB <ad!ustable=' CH-4 maximum limit is 0"EB <ad!ustable=. Confirm that CH,$ <+:= is enabled when CH-4 <A9= N 0%EB <ad!ustable= for N "3 min. and T:+ Q 1?:33. Confirm pumps *,0 > *,13 hardwire start from CH,$. CH,$ <A:= CH-. setpoint is reset from demand based on the CH-. bypass &al&e <A:= position and the CH-4 <A9= temperature. Confirm that CH,1 <+:= is enabled when CH-4 <A9= N 0%EB <ad!ustable= for N "3 min. and T:+ Q 1?:33. Confirm pumps *,$ > *,@ hardwire start from CH,1. :peration J decreasing cooling load: Confirm that CH,1 is disabled and pumps *,$ > *,@ stopped when CH-. temp is Q <setpoint J 1.3EB= for N 13 min. or T:+ N 1?:33. Confirm that CH,$ is disabled and pumps *,0 > *,13 stopped when CH-. temp is Q <setpoint J 1.3EB= for N 13 min. or T:+ N 1?:33. Confirm that CH," is disabled and pumps *,% and *,A stopped when CH-. temp Q <setpoint J 1.3EB= for N 13 min and AHDRR CH- control &al&e positions indicate less than minimum load. /ocation: 2#uipment:
PASS FAIL NOTE

NOTES< 1. ".

Continued on next page: Checks performed by:


print name signature

+ate: *age +,1"

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST CHILLED WATER SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< Cont#nu!d Check operation of: +aily ++C alternation of lead5lag CH," $<+:= *,$ or *,@ failure as sensed by CH-.<+9= and C-.<9= flow switches status<alarm= stops CH, 1<+:= and enables CH,$<+:=. *,0 or *,13 failure as sensed by CH-.<+9= and C-.<9= flow switches status<alarm= stops CH, $<+:= and enables CH,1<+:=. *,% or *,A failure as sensed by CH-.<+9= and C-.<9= flow switches status<alarm= stops CH, "<+:= and enables the lead chiller. CH-.<A9= and CH-4<A9= common header temperatures /ocation: 2#uipment:
PASS FAIL NOTE

NOTES< 1. ".

Checks performed by:


print name signature

+ate: *age +,1$

WATER LOOP HEAT P9MP SYSTEM

.8.T21 +2.C49*T9:; The water loop heat pump system is typical of one that may be installed in retail commercial or office buildings. 2ach ceiling,space mounted heat pump ser&es a specific )one of the building. The system consists of water loop piping throughout the building with: water loop temperature control panel <probably ++C= with return water temperature sensor and flow switch single stage gas fired hot water boiler <G,1= on a branch circuit with a circulation pump <*,1= heat re!ecter <H4,1= with packaged controls <external reset= cooling coil isolation damper fan spray pump sump heater and drain " parallel main loop circulation pumps <*," > *,$= a heat pump for each )one <H*,1 H*," etc.= with local heating5cooling thermostat. The ceiling space is pro&ided with a separate source of outside air. The outside air &entilation system is not included in this sample system. The system has the following modes of operation: :ff <.hutdown= .tart,up ;o load demand , mixed heating5cooling Heating Cooling 1:+2. :B :*24AT9:;
Wat!r Loo Off %Shutdown' B-)
<boiler=

Start-u :ff :ff Closed :ff :ff :n


<lead5lag=

No "oad :ff :ff Closed :ff :ff :n


<lead5lag=

H!at#n$ :n :n Closed :ff :ff :n


<lead5lag=

Coo"#n$ :ff :ff :pen Cycles


<:ff5:n=

:ff :ff Closed :ff :ff :ff :ff

P-)
<boiler pump=

HR-) Da= !r
<Heat re!ecter=

HR-) Fan
<Heat re!ecter=

HR-) S ra5 Pu=


<Heat re!ecter=

Cycles
<:ff5:n=

P-*
<main water loop=

:n
<lead5lag=

P-,
<main water loop=

:ff
<lead5lag=

:ff
<lead5lag=

:ff
<lead5lag=

:ff
<lead5lag=

*age +,1%

WATER LOOP HEAT P9MP SYSTEM

H!at Pu= 4 Fan Co= r!44or R!&!r4#n$ 6a"&! Off %Shutdown' :ff :ff , Start-u :n :ff , No d!=and :n :ff , H!at#n$ :n :n Heat Coo"#n$ :n :n Cool

.2CD2;C2 :B :*24AT9:;. 1.1 ."3 ."1 ."" 1A9; -AT24 /::* The main water loop circulates water "%57. The main water loop circulation pumps operate on a lead5lag5backup basis. The packaged heat re!ecter shall be enabled from the main water loop controller based on the loop heat re!ection demand as sensed by the main water loop return water temperature sensor. The local packaged heat re!ecter controls shall operate the damper fan and spray pump to maintain setpoint as determined <enabled5 disabled= by the main water loop controller. The main water loop controller shall cycle the boiler off and on to maintain the water loop return water temperature setpoint. The boiler circulation pump shall be switched by the boiler and an inline flow switch in the boiler branch line shall allow the boiler to fire. H2AT *D1*. /ocal heating5cooling thermostats shall control the heat pumps. These shall allow % time,of,day setpoints<programs= and auto5manual fan control.

."$

1.1 .1

*age +,10

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST WATER LOOP HEAT P9MP SYSTEM
*4:M2CT: .ystem: Area .er&ed: /ocation: 2#uipment:
PASS FAIL NOTE

SE;9ENCE OF OPERATION< MAIN WATER LOOP Start u =od!< 9nitiate water,loop circulation ++C start,up se#uence with *," as lead pump. Confirm that *," starts and runs. Confirm that water,loop flow switch confirms flow <*," status L :;= .imulate failure of *,"' confirm <1= that water,loop flow switch indicates no flow <"= that *," no,flow alarm is generated and <$= that lag pump *,$ starts and runs. No "oad =od!< Applies when water,loop return water temp. is between minimum and maximum setpoints of %3EB and A3EB. Confirm that either *," or *,$ are :;. Confirm that *,1 and G,1 are :BB' i.e. water loop does not re#uire any supplementary heat. Confirm that H4,1 is :BB' i.e. water loop does not re#uire any heat re!ection. H!at#n$ =od!< Applies when water loop return temp. <-/4T= is at or below minimum setpoint. :n decreasing -/4T if -/4T Q <min. setpoint J 1.3EB= confirm that G,1 is enabled. Confirm se#uence of *,1 start boiler loop flow switch indicating flow and that G,1 then fires. :n increasing -/4T if -/4T N <min setpoint P 1.3EB= confirm that G,1 is disabled and that G,1 stops and *,1 stops after a time delay of OOOO sec..

NOTES< 1. ".

Continued on next page. Checks performed by:


print name signature

+ate: *age +,1?

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST WATER LOOP HEAT P9MP SYSTEM
*4:M2CT: .ystem: Area .er&ed: /ocation: 2#uipment:
PASS FAIL NOTE

SE;9ENCE OF OPERATION< MAIN WATER LOOP %(ont@d' Coo"#n$ =od!< Applies when water loop return temp. <-/4T= is at or below minimum setpoint. :n increasing -/4T: 9f -/4T N <max setpoint= confirm that H4,1 damper is enabled and it :*2;.. 9f -/4T N <max setpoint P ".3EB= confirm that H4,1 fan is enabled and it .TA4T. > 4D;.. 9f -/4T N <max setpoint P %.3EB= confirm that H4,1 spray pump is enabled and it .TA4T. > 4D;.. :n decreasing -/4T: 9f -/4T Q <max setpoint P 1.3EB= confirm that H4,1 spray pump is disabled and .T:*.. 9f -/4T Q <max setpoint , 1.3EB= confirm that H4,1 fan is disabled and .T:*.. 9f -/4T Q <max setpoint , $.3EB= confirm that H4,1 damper is disabled and it C/:.2.. Check operation of: H4,1 sump le&el control water makeup <local H4 control= H4,1 sump heater <local H4 control= J confirm heater is locked out when :A temp N %3EB HEAT P9MPS Check operation of indi&idual heat pumps using the local heating and cooling thermostats: off5on switch J entire heat pump is either :BB or :; <ready for operation upon thermostat signal. fan on5auto switch J :; L fans operates constantly' ADT: L fan operates only when compressor operates. time,of,day programs Check air and water inlet and outlet temperatures

NOTES< 1. ".

Checks performed by:


print name signature

+ate: *age +,17

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST WATER LOOP HEAT P9MP SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< Cont#nu!d H!at Pu= 4< %(ont#nu!d' Heat H* Ban *ump /ocation :n5:ff Auto5:; 9+ /ocation: 2#uipment:

T:+ *rogram

Heating -ater,side Air,side 9nlet :utlet 9nlet :utlet

Cooling -ater,side Air,side 9nlet :utlet 9nlet :utlet

Comments:

Checks performed by:


print name signature

+ate: *age +,1@

MA:E-9P AIR AND EXHA9ST SYSTEM

.8.T21 +2.C49*T9:; This make,up air and exhaust system is typical of one that may be installed in a commercial5industrial building ser&ing a specific area of the building where there is a need to supply 133K outside air to balance a significant exhaust air re#uirement. 2xamples of this are industrial shops kitchens boiler rooms etc. The system consists of: ceiling mounted supply fan <.B= ducted to the outside air with: motori)ed inlet <supply= open5closed damper <:A+= hot water heating coil and control &al&e <HCV= roof mounted exhaust fan <2B= with barometric back,draft damper. controls by a central ++C system space and supply air temperature sensors fan motor current relays free)estat air distribution ductwork with supply and exhaust grilles <constant &olume= 1:+2. :B :*24AT9:; :ff .hutdown Bree)estat <acti&ated= Closed :ff :ff Closed Closed :ff :ff :pen Dnoccupied <.ystem :ff= Closed :ff :ff Closed :ccupied

2#uipment :A+ <dampers= .B <fan= 2B <fan= HCV <&al&e=

:pen :n :n 1odulating

*age +,1A

MA:E-9P AIR AND EXHA9ST SYSTEM

.2CD2;C2 :B :*24AT9:;. 1.1 ." .$ .% .0 .? 1." .1 ." 1.$ .1 ." .$ 1.% .1 :CCD*92+ 1:+2 :ccupied mode shall be determined by the time,of,day <T:+= programming. The supply fan <.B= shall start5stop from a hard,wired connection to the outside air damper <:A+= limit switch. The outside air damper shall be open5closed by the ++C system. The supply fan shall run continuously. The exhaust fan shall be started by the ++C system once the supply fan status is pro&ed on. The heating control &al&e <HCV= shall modulate to maintain the supply air temperature setpoint. D;:CCD*92+ 1:+2 Dnoccupied mode shall be determined by the time,of,day <T:+= programming. :utside air damper closed supply fan off heating control &al&e closed unless outside air temperature is less than $3EB and exhaust fan off. B422S2 *4:T2CT9:; A hard,wired free)estat shall stop the supply fan close the outside air damper and open the heating control &al&e 133K. The exhaust fan shall be stopped by the ++C system. The heating control &al&e shall be opened prior to running the supply fan in cold weather. A/A41. The ++C system shall annunciate an alarm when: , the free)estat is actuated , the supply fan fails to start <indicated by motor amps= , the exhaust fan fails to start <indicated by motor amps= , the supply air temperature is lower than OOOB.

*age +,"3

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST MA:E-9P AIR AND EXHA9ST SYSTEM
*4:M2CT: .ystem: Area .er&ed:
SE;9ENCE OF OPERATION< Start-u < 9f :A temp Q OOO EB confirm that heating coil &al&e <HCV= opens 133K for OOO seconds prior to opening :A damper and starting supply fan. Confirm that :A damper opens. Confirm that when :A damper is open as sensed by limit switch that supply fan <.B= starts. -hen supply airflow is pro&en confirm that exhaust fan <2B= starts. H!at#n$< :ccupied mode: Confirm that HCV modulates to maintain the supply air temperature <.AT= setpoint of OOO EB Dnoccupied mode: As the makeup air system does not pro&ide primary space heating confirm that .B and 2B stay :BB and HCV stays closed unless free)estat has been triggered <see below=. Fr!!A! Prot!(t#on< Trip the free)estat <manually or with an ice pack=. Confirm that the following actions occur: .B stops :A damper closes tightly HCV opens 133K to heat 2B stops Bree)estat alarm is generated A"ar=4 and 4tatu4 #nd#(at#on4< .imulate .B failure' confirm .B failure alarm is generated .imulate 2B failure' confirm 2B failure alarm is generated -hen supply fan is :; simulate .AT Q <setpoint J $.3EB=' confirm low .AT alarm is generated. -hen .B is :BB simulate .AT Q <setpoint J $.3EB=' confirm low .AT alarm is ;:T generated. NOTES< 1. ".

/ocation: 2#uipment:
PASS FAIL NOTE

Checks performed by:


print name signature

+ate: *age +,"1

PAC:A8ED ROOFTOP 8AS HEATBDX COOL SYSTEM

.8.T21 +2.C49*T9:; The roof top unit is typical of one that may be installed in a commercial5industrial5office building ser&ing a specific area of the building. The system consists of: packaged roof top unit<4TD= with: supply fan <.B= modulating outside,air return,air and relief dampers <1A+= operated by a single motor gas heating with a single stage burner <(G= +56 cooling <+6= with single stage compressor " coils and fan. local unit controller <usually supplied by unit manufacturer or other dedicated controller= c5w: outside and supply air temperature sensors. heating5cooling thermostat air distribution ductwork with supply and return grilles <constant &olume= 1:+2. :B :*24AT9:;
:ff <.hutdown= 2#uipment 1A+
<dampers=

Dnoccupied :ff Closed


<to :A=

:ccupied Bree Cooling 1odulating :n :ff :ff Heating 1inimum


<:5A=

Closed
<to :A=

Heating Closed
<to :A=

Cooling 1inimum
<:5A=

.B
<fan=

:ff :ff :ff

:ff :ff :ff

:n :n :ff

:n :n :ff

:n :ff :n

(G
<burner=

+6
<comp. and cond. fan=

*age +,""

PAC:A8ED ROOFTOP 8AS HEATBDX COOL SYSTEM

.2CD2;C2 :B :*24AT9:;. 1.1 ." .$ .% .0 .? .7 1.0 .1 ." .$ :CCD*92+ 1:+2 :ccupied mode shall be determined by the time,of,day <T:+= programming. The supply fan shall run continuously. The mixed air dampers shall modulate to pro&ide free cooling <economi)er operation= as determined by the supply air temperature <.AT= and the outside air temperature<:AT=. The mixed air dampers shall be positioned to pro&ide minimum outside air when the unit is in either gas heating or +56 cooling modes. The gas burner shall cycle on5off to maintain the space temperature heating setpoint. The +56 cooling shall cycle on5off to maintain the space temperature cooling setpoint when the economi)er operation is unable to maintain the cooling setpoint. D;:CCD*92+ 1:+2 Dnoccupied mode shall be determined by the time,of,day <T:+= programming. The supply fan and gas burner shall cycle on5off as re#uired to meet the set,back heating setpoint. The mixed air dampers shall be closed to the outside air.

*age +,"$

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST PAC:A8ED ROOFTOP 8AS HEATBDX COOL SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< O((u #!d =od!< Confirm that .B is :; -hen heating is re#uired confirm that: 1A+ is positioned to minimum :A setpoint <&alue set by TAG agency=. +6 cooling if :BB (G cycles :;5:BB to maintain space heating temp. setpoint. 4ecord the following data: :A temp. OOOO EB 1ax. space temp. when (G stops OOOO EB' 1in. space temp. when (G starts OOOO EB 1ax. supply air temp. <.AT= OOOO EB' 1in. .AT OOOO EB -hen heating is not re#uired and free cooling can maintain space temp below cooling setpoint confirm that: (G and +6 cooling are both :BB. 1A+ modulates from min. :A position to 133K open to :A to maintain space cooling setpoint OOOO EB -hen cooling is re#uired confirm that: 1A+ is positioned to minimum :A setpoint <&alue set by TAG agency=. +6 cooling cycles :;5:BB to maintain space cooling temp. setpoint. 4ecord the following data: :A temp. OOOO EB 1ax. space temp. when +6 starts OOOO EB' 1in. space temp. when +6 stops OOOO EB 1ax. supply air temp. <.AT= OOOO EB' 1in. .AT OOOO EB NOTES< 1. ". /ocation: 2#uipment:
PASS FAIL NOTE

Continued on next page: Checks performed by:


print name signature

+ate: *age +,"%

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST PAC:A8ED ROOFTOP 8AS HEATBDX COOL SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< 9no((u #!d =od!< -hen space temp. N night setback heating setpoint confirm that: 1A+ is tightly closed to :A. Heating and cooling are both :BB .upply fan <.B= is :BB. -hen space temp. Q night setback heating confirm than: 1A+ stays tightly closed to :A and cooling stays :BB. .B is started (as heating <(G= fires -hen space temp. rises to N night setback heating setpoint confirm (G and .B turn :BB. /ocation: 2#uipment:
PASS FAIL NOTE

NOTES< 1. ".

Checks performed by:


print name signature

+ate:

*age +,"0

6ARIABLE AIR 6OL9ME SYSTEM

.8.T21 +2.C49*T9:; The air handling system is typical of one that may be installed in a commercial5industrial building ser&ing a specific area or floor of the building. The system consists of: air handling unit<AHD= with: supply fan with &ariable speed dri&e <V.+= motor control modulating outside,air return,air and relief dampers heating and cooling coils steam humidification air filters coil circulation pumps modulating heating coil control &al&e <HCV= and cooling coil control &al&e <CCV= return fan &ariable air &olume <VAV= boxes with ++C controllers direct digital control <++C= system The AHD has ducted access to untempered outside air. The supporting steam heating and cooling water systems are outside the scope of this example. The system has &arious modes of operation: :ff <.hutdown= .tart,up -arm,up ;ormal 2conomi)er Bire Bree)e

*age +,"?

6ARIABLE AIR 6OL9ME SYSTEM

1:+2. :B :*24AT9:;
2#uipment ;ormal :utdoor Air +amper 4eturn Air +amper 4elief Air +amper Heating Coil *ump Heating Coil control &al&e .B,1 Humidifier enable HD,1 control &al&e Cooling coil control &al&e 4B,1 Closed :pen Closed :ff Closed :ff Closed Closed .hutdown Bire :pen Closed :pen :n Bree)e Closed :pen Closed :n Bree Cooling. ;ormal :peration Heating Cooling 1odulating ;ight Heating

1odulating 1inimum

1odulating 1odulating 1odulating 1odulating 1odulating 1odulating 1odulating 1odulating :ff Closed :n :pen :n :ff :n 1odulating :n :pen 1odulating

1odulating :pen :n Closed Closed :ff Closed Closed

1odulating Closed :n :pen :n Closed

1odulating 1odulating Closed

Closed :ff

1odulating Closed :n :ff

Closed :n

Closed :n

1odulating Closed :n :n

*age +,"7

6ARIABLE AIR 6OL9ME SYSTEM

.2CD2;C2 :B :*24AT9:;. 1.1 .% .0 .? .7 .@ (2;24A/ :n a signal to start the supply and return fans open the return air dampers and crack the outdoor air damper <0K open=. .tart the supply and return <AHD,1 only= fans on a minimum speed. After fan status is pro&en modulate the dampers in a normal manner. 1odulate the speed of the supply fans to maintain the re#uired duct static pressure. 1odulate the speed of the return fan to maintain the re#uired building pressuri)ation. Dse the &olume probes to determine the appropriate return &olume <i.e. return &olume L supply &olume P building pressuri)ation &olume' where the building pressuri)ation &olume is to be determined on site=. :n a signal to start an exhaust fan open its motori)ed damper. -hen the damper end switch is made start the fan. -hen no heating is re#uired the mixing dampers shall modulate to pro&ide the amount of free cooling <up to 133K outdoor air= re#uired to maintain the supply air temperature <.AT= setpoint. -hen the dampers are at the minimum outdoor air position heating shall be allowed. -hen the dampers are at the 133K outdoor air position cooling shall be allowed. -hen the outdoor air temperature <:AT= is below %3EB start the heating coil circulating pump whether the fan is running or not. -hen cooling is re#uired modulate the cooling coil &al&e start pump *," to maintain the re#uired .AT setpoint. The .AT shall be reset from the systemFs associated room temperature sensors. A return air humidity sensor and a supply air high limit humidity sensor shall control the humidifiers. :n a call for humidification the humidifier isolation &al&e shall open. After unit heat up has been pro&en by an internal temperature switch the humidifier control &al&es shall modulate to maintain the re#uired humidity sub!ect to the supply air high limit. The humidifiers shall only operate if the associated supply fan is on. 9nstall a low temperature sensor on the discharge side of the heating coil <set for approx. %3EB=. :n a low temperature alarm shut off the fans enable the heating coil pump and open the heating coil &al&e.

.A .13 .11 .1" .1$ .1% .10

.1?

*age +,"@

6ARIABLE AIR 6OL9ME SYSTEM

1.? .1 ." .$

VAV G:62. 1odulate the control damper to maintain the re#uired room temperature. <Bor those boxes with reheat coils= 9f heating is re#uired modulate the ",way reheat control &al&e to maintain the re#uired room temperature with the control damper set at minimum airflow position. .witch the box mode between HdayI and HnightI modes based on time,of,day or operator command.

*age +,"A

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST 6ARIABLE AIR 6OL9ME SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< 9no((u #!d =od!< Confirm that: .upply fan <.B= is :BB and its VB+ speed L 3K 4eturn fan <4B= is :BB and its VB+ speed L 3K 1A+ is tightly closed to :A. Humidifier control &al&e is fully closed <A: L 3K= VAV boxes are in unoccupied HnightI mode. 9f :AT T %1 EB then confirm that: H-H coil pump is :BB Heating coil control &al&e <HCV= is closed to 3K 9f :AT Q %3EB then confirm that: H-H coil pump starts and runs HCV mo&es to 13K open position. Start u =od!< .imulate time of day <T:+= to start of occupied hours. Confirm that fan start,up se#uence occurs as follows: 9f a&g. space temp <from VAV box sensors= Q <occupied heating setpoint J ".3EB= then 1A+ stays closed to :A otherwise 1A+ opens to 0K :A. .B and 4B start at minimum VB+ speed -hen .B operating status is pro&en modulate fan speed to maintain supply duct static pressure at setpoint OOOO H -( -hen 4B operating status is pro&en modulate fan speed to maintain building pressure at setpoint OOOO H -( HD,1 humidifier isolation &al&e opens when return air relati&e humidity Q $0K VAV boxes mo&e from unoccupied mode to occupied HdayI mode /ocation: 2#uipment:
PASS FAIL NOTE

NOTES< 1. ".

Continued on next page: Checks performed by:


print name signature

+ate: *age +,$3

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST 6ARIABLE AIR 6OL9ME SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< War=-u < 1A+ stays closed to :A until a&g. space temp N occupied heating setpoint. -hen a&g. space temp N occupied setpoint then 1A+ mo&es to min. :A position OOOO K :A /ocation: 2#uipment:
PASS FAIL NOTE

O((u #!d Cnor=a"D =od!< Confirm supply air temp. <.AT= setpoint reset logic. 1in. .AT setpoint L OOOO EB' max. .AT setpoint L OOOO EB -hen a&g. space temp. N <cooling setpoint P 1.3EB= confirm that .AT setpoint L min. -hen a&g. space temp. Q <heating setpoint J 1.3EB= confirm that .AT setpoint L max. .AT control: 9f .AT Q <setpoint J 1.3EB= confirm that: 1A+ is at min. :A position Cooling coil pump of :BB and CCV is closed. HCV modulates to maintain .AT L <setpoint J 1.3EB=. Heating coil pump starts when HCV N 13K open' stops when HCV Q 0K open. 2xcept if :A temp Q %3EB then heating coil pump is :; at all times. 9f .AT N setpoint and Q <setpoint P 1.3EB= confirm that: Heating coil pump is :BB and HCV is closed. Cooling coil pump is :BB and CCV is closed. 1A+ modulates between min. position and 133K :A to maintain .AT L setpoint.

NOTES< 1. ".

Continued on next page: Checks performed by:


print name signature

+ate: *age +,$1

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST 6ARIABLE AIR 6OL9ME SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< O((u #!d %nor=a"' =od!%(ont#nu!d'< 9f .AT N <setpoint P 1.3EB= confirm that: 1A+ is at 133K :A position if return air temp. <4AT= T :A temp.' or at min. position if 4AT Q :A temp. Heating coil pump is :BB and HCV is closed. CCV modulates to maintain .AT P <setpoint P 1.3EB= Cooling coil pump starts when CCV N 13K open' stops when CCV Q 0K open. /ocation: 2#uipment:
PASS FAIL NOTE

Humidity: Confirm that humidifier is :BB when HCV Q 0K open. -hen humidifier is enabled confirm that HD,1 control &al&e modulates to maintain return air 4H L setpoint. Confirm that the humidity control &al&e action is delayed 13 minutes after the isolation &al&e opens. F#r! =od!< Hardwire stop .B from fire alarm system wired to .B speed controller Confirm that: .B stops J +: L :BB .B VB+ L 3K 4B stops J +: L :BB 4B VB+ L 3K 1A+ mo&es to 3K :A position Humidifier stops J control &al&e L 3K open and isolation &al&e closed. VAV boxes go to unoccupied HnightI mode. NOTES< 1. ".

Continued on next page: Checks performed by:


print name signature

+ate:

*age +,$"

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST 6ARIABLE AIR 6OL9ME SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< Fr!!A! =od!< :n low temperature free)estat<+9= <auto reset type= U %3EB for 13 seconds.: Confirm that: .B hardwire stopped while free)estat acti&ated as abo&e. .B stops J +: L :BB .B VB+ L 3K 4B stops J +: L :BB 4B VB+ L 3K 1A+ mo&es to 3K :A position Humidifier stops J control &al&e L 3K open and isolation &al&e closed. Heating coil pump starts and HCV goes to 13K open position. Confirm that free)e mode can be reset by operator toggling ++C Hfree)e reset pointI. A"ar=4 and 4tatu4 (h!(74< .AT <A9= 4AT <A9= Bilter high +* <A9=. H-H coil pump status<A9= CH- coil pump status<A9= .B status <A9= NOTES< 1. ". /ocation: 2#uipment:
PASS FAIL NOTE

Continued on next page.

Checks performed by:


print name signature

+ate:

*age +,$$

H6AC COMMISSIONIN8
F9NCTIONAL PERFORMANCE TEST CHEC:LIST 6ARIABLE AIR 6OL9ME SYSTEM
*4:M2CT: .ystem: Area .er&ed: SE;9ENCE OF OPERATION< Cont#nu!d 6A6 Bo?!4< The VAV boxes shall modulate the damper and 4eheat HCV to maintain the ++C room setpoint during Hday modeI and Hnight modeI < different setpoints in each VAV box controller=. .imulate heating and cooling conditions. /ocation: 2#uipment:

VAV 9+

/ocation

+ay 1ode

;ight 1ode

Heating

Cooling

Comments:

Checks performed by:


print name signature

+ate: *age +,$%