POUR LE SECTEUR TERTIAIRE : - POUR LE SECTEUR INDUSTRIEL :
0 , 1 5 0 T T C / MN
0 825 80 18 18
0 , 1 5 0 T T C / MN
0 825 018 018
DTECTION ET PROTECTION CONTRE LINCENDIE
VESDA LaserPlus
)
Dtecteur multiponctuel technologie laser certifi NF sous le n MPL 036
Multipoint detector with NF certified laser technology under n MPL 036
Grande plage de sensibilit programmable
Wide range of programmable sensitivity
Architecture modulaire
Modular architecture
Programmation par menu droulant sur cran graphique
Programming by pull down menu on graphic screen
Modlisation de linstallation par logiciel de calcul ASPIRE
Modeling of the installation by the ASPIRE calculation software
Surveillance permanente du dbit dair
Permanent monitoring of the air flow
Maintenance aise
Easy maintenance
DE LEXCELLENCE NAT LA SCURIT
VESDA LaserPLUS + afficheur
+ display
VESDA LaserPLUS
LA GAMME VESDA LaserPLUS THE VESDA LaserPLUS RANGE
(
VESDA LaserPLUS + afficheur + programmeur
+ display + programmer
LES POINTS FORTS
LAlarme Feu (Feu 1) : de 0,005 2%
dobscurcissement/m
3 seuils complmentaires (Pralarme, Action, Feu 2) :
de 0,005 20% dobscurcissement/m
Voyants Feu/Drangement
Afficheur
Programmateur
Surveillance permanente du filtre
Mmorisation des 18 000 derniers vnements.
CARACTRISTIQUES TECHNIQUES
Tension dalimentation : 18 30 VCC
Consommation : 500mA typique
T dair ambiant : de 10 +60C
T dair prlev : de 20 +60C
Humidit relative : 10 95% sans condensation
Sensibilit rglable de 0,005 20% obs./m
Surface surveille : 2000m
2
maxi
Dimensions du coffret (L x H x P) en mm :
350 x 225 x 125
Poids : 4kg
Sorties : 5 relais NO : NF programmables et 2 relais
NO : NF pr programms non maintenus (Alarme Feu
et Drangement) ; pouvoir de coupure : 1A 30V
Rseau de prlvement :
- rseau : tube PVC ou ABS (diamtre des tubes entre
19 et 25 mm)
- 4 tubes daspiration
- 100 mtres maxi par tube (200 mtres maxi au total)
- distance entre les orifices de prlvement : entre 1
et 10 mtres (diamtre dun orifice : 3 mm typique).
CERTIFICATIONS ET AGRMENTS
Les qualits de fiabilit et de stabilit du dtecteur
VESDA LaserPLUS ont t values et agres par
diffrentes organisations internationales dont :
- AFNOR (France) n MPL 036
- Factory Mutual (USA) n 0B5A5.AY
- UnderwritersLaboratories (USA) n 310398-5198
- Loss Prevention Council Board (GB) n 305b
- VDS (Allemagne) en cours
- Compatibilit lectromagntique 89/336/CCE (CE)
- Plus de 40 000 installations VESDA dans le monde.
ADVANTAGES
A fire alarm (Fire 1) : from 0.005 to 2% darkening/m
Three complementary thresholds (Prealarm, Action,
Fire 2) : from 0.005 to 20% of darkening/m
Fire/Malfunction lights
Display
Programmer
Permanent filter monitoring
Memorization of the 18,000 last events.
TECHNICAL CHARACTERISTICS
Power supply voltage : 18 to 30 Vdc
Consumption : 500mA typical
Ambient air T : from 10 to +60C
Sampled air T : from 20 to +60C
Relative humidity : 10 to 95% without condensation
Sensitivity adjustable from 0.005 to 20% obs./m
Monitored area : 2000m
2
max
Box dimensions (L x H x D) in mm : 350 x 225 x 125
Weight : 4 kg
Exits : 5 NO : NC programmable relays and 2
preprogrammed unmaintained NO : NC relays
(Fire and Malfunction Alarm) ; breaking capacity :
1A at 30V
Sampling network :
- network : PVC or ABS tube (tube diameter between
19 and 25 mm)
- 4 intake tubes
- 100 meters maximum per tube (200 meters
maximum total)
- distance between sampling orifices : between 1 and
10 meters (orifice diameter 3 mm typical).
CERTIFICATIONS AND APPROVALS
Reliability and stability qualities of the VESDA
LaserPLUS detector were evaluated and approved by
different international organizations including :
- AFNOR (France) n MPL 036
- Factory Mutual (USA) n 0B5A5.AY
- Underwriters Laboratories (USA) n 310398-5198
- Loss Prevention Council Board (GB) n 305b
- VDS (Germany) in progress
- Electromagnetic compatibility 89/336/CCE (CE)
- More than 40 000 VESDA installations throughout
the world.
RSEAU D'ASPIRATION
DE PLAFOND
CEILING EXTRACTION
SYSTEM
SMOKE
STRATIFICATION
ZONE
ZONE DE
STRATIFICATION
DE FUME
RSEAU VERTICAL
VERTICAL NETWORK
Esc
LaserPlus
VESDA
TM
Climatiseur
Air
conditioning
unit
Flux d'air
Air flow Rseau de
prlvement d'air
Air sampling network
Orifice de
prlvement
Sampling
opening
Ordinateur
Computer
Lecteurs
informatiques
Orifice de
prlvement
Data readers Sampling
opening
Esc Esc
LaserPlus
VESDA
TM
optic
linear
optic
optique
linaire
flames
flammes
sprinkleur
ionic
optique
ionique
FEU COUVANT FUMES VISIBLES FLAMMES
3rd PHASE 2nd PHASE PHASE INITIALE
PRALARME ACTION FEU 1 FEU 2
PREALARM FIRE 1 FIRE 2
PHASE FINALE
INITIAL PHASE FINAL PHASE
CHALEUR
SMOULDERING FIRE VISIBLE SMOKE FLAMES HEAT
Esc
LE TEMPS
TIME
L
'
I
N
T
E
N
S
I
T


D
E

L
'
I
N
C
E
N
D
I
E

-

F
I
R
E

I
N
T
E
N
S
I
T
Y
thermique
thermal
LaserPlus
VESDA
TM
DESCRIPTION
N dun concept original, le VESDA LaserPLUS
instaure une nouvelle gnration de systmes
de dtection multiponctuelle de fume. Utilisant
les dernires technologies, il ralise des
performances incomparables tout en simplifiant
les oprations de mise en service, dexploitation
et de maintenance.
Sa plage de sensibilit trs tendue et son
extrme rapidit de raction le destine tout
naturellement aux locaux stratgiques ou vitaux
des entreprises et aux difices de trs grande
hauteur ou de volume important.
Le VESDA LaserPLUS constitue la solution idale
dans les applications pour lesquelles les
systmes de dtection conventionnels se rvlent
inefficaces ou trop lents : environnements
chargs en poussire, en humidit ou daccs
difficile.
Le VESDA LaserPLUS sintgre parfaitement
tous les systmes de protection incendie de la
gamme CHUBB SCURIT.
Il dtecte les feux couvants ds leur naissance,
bien avant que les fumes ou les flammes ne
soient visibles. Mme si le VESDA LaserPLUS est
trs sensible, il prsente un taux dalarmes
intempestives trs faible, y compris dans les
zones forte concentration de poussire ou
dhumidit, grce sa fonction dadaptation
automatique AUTOLEARN.
DESCRIPTION
The VESDA LaserPLUS originated from an
innovative concept and sets up a new generation
of multipoint smoke detection system. It uses the
latest technologies and has incomparable
performances, and also simplifies startup and
maintenance operations.
Its very wide sensitivity range and extremely fast
reaction speed make it naturally suitable for
company strategic or vital premises and very tall
buildings or very large buildings.
VESDA LaserPLUS is an ideal solution for
applications for which conventional detection
systems are inefficient or too slow : environments
with dust, humidity or difficult access.
VESDA LaserPLUS integrates perfectly into all
fire protection systems in the CHUBB SECURITY
range.
It detects smoldering fires as soon as they start
to develop, well before there are any visible
smoke or flames. Even if the VESDA LaserPLUS is
very sensitive, its false alarm ratio is very low,
even in areas with a strong concentration of dust
or humidity due to its automatic AUTOLEARN
adaptation function.
Courbe de dveloppement d'un incendie - Fire progress curve
Adjustment
opening
Orifice
d'quilibrage
Length 100m maxi/tube
Long. 100m maxi/tube
Distance
1 10m
Air sampling
Prlvement d'air
Dtail
Detail
Tableau de signalisation incendie
conventionnel ou adressable
Conventional or addressable
fire signalling chart
Reading opening (typically 3mm)
Orifice de prlvement ( 3mm typique)
Esc
B
E
D
J
I
H G
K
F
C
A
A
B
C
D
E
Module de synthse (voyants feu/drangement)
et volet d'accs aux bornes de raccordement
Status module (fire/fault lights) and access
to the connectors
Module de programmation Programming module
4 entres d'air 4 air intakes
Module d'affichage Display module
Volet d'accs au filtre Filter access
F
G
H
I
J
K
Avertisseur sonore Audio alarm
Indicateurs des seuils d'alarme Alarm threshold indicators
chelle gradue lumineuse de quantit de fume (20 LED)
Graduated lighted scale for amount of smoke (20 LED)
Afficheur digital multifonctions (sensibilit du dtecteur,
concentration des fumes, numro d'adresse)
Multifunction digital display (sensitivity of the detector,
smoke concentration, address number)
Voyants des alarmes Alarm lights
Voyants des drangements Fault lights
Le VESDA LaserPLUS est un systme dynamique : lair
ambiant de la zone surveille est aspir dans un rseau
de tuyauterie munie dorifices de prlvement. Cet air
est ensuite achemin vers une chambre danalyse par
une pompe centrifuge haut rendement permettant
dquiper des sites de trs grands volumes. Les temps de
rponse restent cependant courts, mme pour de faibles
quantits de fumes. Un filtre mcanique double action
permet la fois :
dliminer la poussire pour assurer une analyse
optimale de la fume,
de garantir la propret de la tte de dtection pendant
plusieurs annes.
Le VESDA LaserPLUS utilise la source lumineuse intense
dun laser combine deux cellules optiques
extrmement efficaces pour dterminer avec prcision la
concentration de fume.
En prsence de particules de fume, la lumire est
rflchie vers les cellules optiques. Cette fume est
visualise sur lchelle lumineuse du Module dAffichage.
Les diffrentes alarmes sont alors actives lorsque les
seuils correspondants sont atteints. Un avertisseur
sonore met un son continu pour lAlarme Feu et un son
modul pour les drangements. Le tableau de
signalisation incendie reoit une information de synthse
des drangements. Ces derniers sont hirarchiss sur le
dtecteur selon leur importance. Le dtecteur fait la
diffrence entre un drangement de type maintenance,
o il est toujours capable de signaler un feu, et un
drangement plus grave lempchant de fonctionner
normalement. Ce second type de drangement ncessite
une intervention immdiate du service Maintenance de
CHUBB SCURIT. Pendant quune alarme est active, le
dtecteur maintient sa surveillance pour avertir dune
ventuelle amplification ou propagation de lincendie.
The VESDA LaserPLUS is a dynamic system : ambient air
in the monitored zone is drawn into a pipe network
provided with drawing off orifices. This air is then
transferred to an analysis chamber by a high efficiency
centrifugal pump to equip very large volume sites.
However, response times are still very short even for low
smoke quantities. A double mechanical action filter:
eliminates dust to provide optimum smoke analysis,
guarantee cleanliness of the detection head for
several years.
VESDA LaserPLUS uses the intense light source of a
laser combined with two extremely efficient optical cells
to precisely determine the smoke concentration.
When smoke particles are present, light is reflected to
the optical cells. This smoke is displayed on the light
scale of the Display Module. The different alarms are
then activated when the corresponding thresholds are
reached. A sound alarm emits a continuous sound for the
Fire Alarm and a modulated sound for malfunctions. The
fire signaling panel receives malfunction synthesis
information. This information is hierarchized on the
detector depending on its importance. The detector
makes the difference between a maintenance type
malfunction in which it is always capable of signaling a
fire, and a more serious malfunction preventing it from
operating normally. This second type of malfunction
requires immediate action by the CHUBB SECURITY
Maintenance service. As long as an alarm is activated,
the detector continues monitoring to signal if the fire
grows or starts to propagate.
OPERATING PRINCIPLES PRINCIPE DE FONCTIONNEMENT
Une activit exigeant une perte dexploitation
minimale : salles informatiques, salles de contrle,
tlcommunications, salles blanches
quipements et armoires stratgiques : process
industriels, simulateurs de vols, automates
Hauts plafonds ou vitesse dair leve : atriums,
entrepts de stockage, hangars davions
Environnements chargs en poussire, humidit,
tempratures extrmes : filatures, menuiseries,
entrepts frigorifiques
Monuments historiques ou btiments forte
contrainte esthtique : cathdrales, galeries dart
Combles inaccessibles.
An activity requiring minimum loss of operations :
computer rooms, control rooms, telecommunications,
clean rooms, etc.
Strategic equipment and cabinets : industrial
processes, flight simulators, logic controllers, etc.
High ceilings or high air speed : atriums, storage
workshops, aircraft hangars, etc.
Environment containing large quantities of dust,
humidity, extreme temperatures : spinning machines,
wood working, refrigeration warehouses, etc.
Historic monuments or buildings with serious esthetic
constraints : cathedrals, art galleries, etc.
Inaccessible roof space.
AREAS OF APPLICATION DOMAINES D'APPLICATION
Lorsque les plafonds sont trs hauts ou sans isolation,
certains facteurs imprvisibles tels que la stratification
de lair surgissent alors. Ce phnomne diminue
lefficacit des dtecteurs de fume conventionnels.
De par limplantation de rseaux de prlvement en
toiture et sur les parois, le systme VESDA LaserPLUS
permet de capter les feux couvants tous les niveaux.
When ceilings are very high or uninsulated, some
unpredictable factors such as air stratification can occur.
This phenomenon reduces the efficiency of conventional
smoke detectors.
Due to the arrangement of sampling networks on the roof
and on walls, the VESDA LaserPLUS system is capable of
detecting smoldering fires at all levels.
VOLUMES DE GRANDE HAUTEUR ET ENTREPTS HIGH CEILING AREAS AND WAREHOUSES
Architecture du systme VESDA LaserPLUS - Architecture of the VESDA LaserPLUS System
(
Les flux dair levs, rencontrs dans les salles
informatiques ou dans les autocommutateurs, transportent
rapidement les gaz de combustion vers le systme de
traitement dair et les loignent des dtecteurs de fume
conventionnels, en les diluant de faon importante.
Dans ce cas, limplantation des points de captation devant
les grilles daspiration rend le systme VESDA LaserPLUS
particulirement efficace.
High air flows that exist in computer rooms and in PABXs
quickly carry combustion gases towards the air treatment
system and keep them away from conventional smoke
detectors, significantly diluting them.
In this case, the arrangement of sensors in front of intake
grills makes the VESDA LaserPLUS system particularly
efficient.
SALLES AVEC CLIMATISATION OU VENTILATION ROOMS WITH AIR-CONDITIONING OR FAN
(
RSEAU D'ASPIRATION
DE PLAFOND
CEILING EXTRACTION
SYSTEM
SMOKE
STRATIFICATION
ZONE
ZONE DE
STRATIFICATION
DE FUME
RSEAU VERTICAL
VERTICAL NETWORK
Esc
LaserPlus
VESDA
TM
Climatiseur
Air
conditioning
unit
Flux d'air
Air flow Rseau de
prlvement d'air
Air sampling network
Orifice de
prlvement
Sampling
opening
Ordinateur
Computer
Lecteurs
informatiques
Orifice de
prlvement
Data readers Sampling
opening
Esc Esc
LaserPlus
VESDA
TM
optic
linear
optic
optique
linaire
flames
flammes
sprinkleur
ionic
optique
ionique
FEU COUVANT FUMES VISIBLES FLAMMES
3rd PHASE 2nd PHASE PHASE INITIALE
PRALARME ACTION FEU 1 FEU 2
PREALARM FIRE 1 FIRE 2
PHASE FINALE
INITIAL PHASE FINAL PHASE
CHALEUR
SMOULDERING FIRE VISIBLE SMOKE FLAMES HEAT
Esc
LE TEMPS
TIME
L
'
I
N
T
E
N
S
I
T


D
E

L
'
I
N
C
E
N
D
I
E

-

F
I
R
E

I
N
T
E
N
S
I
T
Y
thermique
thermal
LaserPlus
VESDA
TM
DESCRIPTION
N dun concept original, le VESDA LaserPLUS
instaure une nouvelle gnration de systmes
de dtection multiponctuelle de fume. Utilisant
les dernires technologies, il ralise des
performances incomparables tout en simplifiant
les oprations de mise en service, dexploitation
et de maintenance.
Sa plage de sensibilit trs tendue et son
extrme rapidit de raction le destine tout
naturellement aux locaux stratgiques ou vitaux
des entreprises et aux difices de trs grande
hauteur ou de volume important.
Le VESDA LaserPLUS constitue la solution idale
dans les applications pour lesquelles les
systmes de dtection conventionnels se rvlent
inefficaces ou trop lents : environnements
chargs en poussire, en humidit ou daccs
difficile.
Le VESDA LaserPLUS sintgre parfaitement
tous les systmes de protection incendie de la
gamme CHUBB SCURIT.
Il dtecte les feux couvants ds leur naissance,
bien avant que les fumes ou les flammes ne
soient visibles. Mme si le VESDA LaserPLUS est
trs sensible, il prsente un taux dalarmes
intempestives trs faible, y compris dans les
zones forte concentration de poussire ou
dhumidit, grce sa fonction dadaptation
automatique AUTOLEARN.
DESCRIPTION
The VESDA LaserPLUS originated from an
innovative concept and sets up a new generation
of multipoint smoke detection system. It uses the
latest technologies and has incomparable
performances, and also simplifies startup and
maintenance operations.
Its very wide sensitivity range and extremely fast
reaction speed make it naturally suitable for
company strategic or vital premises and very tall
buildings or very large buildings.
VESDA LaserPLUS is an ideal solution for
applications for which conventional detection
systems are inefficient or too slow : environments
with dust, humidity or difficult access.
VESDA LaserPLUS integrates perfectly into all
fire protection systems in the CHUBB SECURITY
range.
It detects smoldering fires as soon as they start
to develop, well before there are any visible
smoke or flames. Even if the VESDA LaserPLUS is
very sensitive, its false alarm ratio is very low,
even in areas with a strong concentration of dust
or humidity due to its automatic AUTOLEARN
adaptation function.
Courbe de dveloppement d'un incendie - Fire progress curve
Adjustment
opening
Orifice
d'quilibrage
Length 100m maxi/tube
Long. 100m maxi/tube
Distance
1 10m
Air sampling
Prlvement d'air
Dtail
Detail
Tableau de signalisation incendie
conventionnel ou adressable
Conventional or addressable
fire signalling chart
Reading opening (typically 3mm)
Orifice de prlvement ( 3mm typique)
Esc
B
E
D
J
I
H G
K
F
C
A
A
B
C
D
E
Module de synthse (voyants feu/drangement)
et volet d'accs aux bornes de raccordement
Status module (fire/fault lights) and access
to the connectors
Module de programmation Programming module
4 entres d'air 4 air intakes
Module d'affichage Display module
Volet d'accs au filtre Filter access
F
G
H
I
J
K
Avertisseur sonore Audio alarm
Indicateurs des seuils d'alarme Alarm threshold indicators
chelle gradue lumineuse de quantit de fume (20 LED)
Graduated lighted scale for amount of smoke (20 LED)
Afficheur digital multifonctions (sensibilit du dtecteur,
concentration des fumes, numro d'adresse)
Multifunction digital display (sensitivity of the detector,
smoke concentration, address number)
Voyants des alarmes Alarm lights
Voyants des drangements Fault lights
Le VESDA LaserPLUS est un systme dynamique : lair
ambiant de la zone surveille est aspir dans un rseau
de tuyauterie munie dorifices de prlvement. Cet air
est ensuite achemin vers une chambre danalyse par
une pompe centrifuge haut rendement permettant
dquiper des sites de trs grands volumes. Les temps de
rponse restent cependant courts, mme pour de faibles
quantits de fumes. Un filtre mcanique double action
permet la fois :
dliminer la poussire pour assurer une analyse
optimale de la fume,
de garantir la propret de la tte de dtection pendant
plusieurs annes.
Le VESDA LaserPLUS utilise la source lumineuse intense
dun laser combine deux cellules optiques
extrmement efficaces pour dterminer avec prcision la
concentration de fume.
En prsence de particules de fume, la lumire est
rflchie vers les cellules optiques. Cette fume est
visualise sur lchelle lumineuse du Module dAffichage.
Les diffrentes alarmes sont alors actives lorsque les
seuils correspondants sont atteints. Un avertisseur
sonore met un son continu pour lAlarme Feu et un son
modul pour les drangements. Le tableau de
signalisation incendie reoit une information de synthse
des drangements. Ces derniers sont hirarchiss sur le
dtecteur selon leur importance. Le dtecteur fait la
diffrence entre un drangement de type maintenance,
o il est toujours capable de signaler un feu, et un
drangement plus grave lempchant de fonctionner
normalement. Ce second type de drangement ncessite
une intervention immdiate du service Maintenance de
CHUBB SCURIT. Pendant quune alarme est active, le
dtecteur maintient sa surveillance pour avertir dune
ventuelle amplification ou propagation de lincendie.
The VESDA LaserPLUS is a dynamic system : ambient air
in the monitored zone is drawn into a pipe network
provided with drawing off orifices. This air is then
transferred to an analysis chamber by a high efficiency
centrifugal pump to equip very large volume sites.
However, response times are still very short even for low
smoke quantities. A double mechanical action filter:
eliminates dust to provide optimum smoke analysis,
guarantee cleanliness of the detection head for
several years.
VESDA LaserPLUS uses the intense light source of a
laser combined with two extremely efficient optical cells
to precisely determine the smoke concentration.
When smoke particles are present, light is reflected to
the optical cells. This smoke is displayed on the light
scale of the Display Module. The different alarms are
then activated when the corresponding thresholds are
reached. A sound alarm emits a continuous sound for the
Fire Alarm and a modulated sound for malfunctions. The
fire signaling panel receives malfunction synthesis
information. This information is hierarchized on the
detector depending on its importance. The detector
makes the difference between a maintenance type
malfunction in which it is always capable of signaling a
fire, and a more serious malfunction preventing it from
operating normally. This second type of malfunction
requires immediate action by the CHUBB SECURITY
Maintenance service. As long as an alarm is activated,
the detector continues monitoring to signal if the fire
grows or starts to propagate.
OPERATING PRINCIPLES PRINCIPE DE FONCTIONNEMENT
Une activit exigeant une perte dexploitation
minimale : salles informatiques, salles de contrle,
tlcommunications, salles blanches
quipements et armoires stratgiques : process
industriels, simulateurs de vols, automates
Hauts plafonds ou vitesse dair leve : atriums,
entrepts de stockage, hangars davions
Environnements chargs en poussire, humidit,
tempratures extrmes : filatures, menuiseries,
entrepts frigorifiques
Monuments historiques ou btiments forte
contrainte esthtique : cathdrales, galeries dart
Combles inaccessibles.
An activity requiring minimum loss of operations :
computer rooms, control rooms, telecommunications,
clean rooms, etc.
Strategic equipment and cabinets : industrial
processes, flight simulators, logic controllers, etc.
High ceilings or high air speed : atriums, storage
workshops, aircraft hangars, etc.
Environment containing large quantities of dust,
humidity, extreme temperatures : spinning machines,
wood working, refrigeration warehouses, etc.
Historic monuments or buildings with serious esthetic
constraints : cathedrals, art galleries, etc.
Inaccessible roof space.
AREAS OF APPLICATION DOMAINES D'APPLICATION
Lorsque les plafonds sont trs hauts ou sans isolation,
certains facteurs imprvisibles tels que la stratification
de lair surgissent alors. Ce phnomne diminue
lefficacit des dtecteurs de fume conventionnels.
De par limplantation de rseaux de prlvement en
toiture et sur les parois, le systme VESDA LaserPLUS
permet de capter les feux couvants tous les niveaux.
When ceilings are very high or uninsulated, some
unpredictable factors such as air stratification can occur.
This phenomenon reduces the efficiency of conventional
smoke detectors.
Due to the arrangement of sampling networks on the roof
and on walls, the VESDA LaserPLUS system is capable of
detecting smoldering fires at all levels.
VOLUMES DE GRANDE HAUTEUR ET ENTREPTS HIGH CEILING AREAS AND WAREHOUSES
Architecture du systme VESDA LaserPLUS - Architecture of the VESDA LaserPLUS System
(
Les flux dair levs, rencontrs dans les salles
informatiques ou dans les autocommutateurs, transportent
rapidement les gaz de combustion vers le systme de
traitement dair et les loignent des dtecteurs de fume
conventionnels, en les diluant de faon importante.
Dans ce cas, limplantation des points de captation devant
les grilles daspiration rend le systme VESDA LaserPLUS
particulirement efficace.
High air flows that exist in computer rooms and in PABXs
quickly carry combustion gases towards the air treatment
system and keep them away from conventional smoke
detectors, significantly diluting them.
In this case, the arrangement of sensors in front of intake
grills makes the VESDA LaserPLUS system particularly
efficient.
SALLES AVEC CLIMATISATION OU VENTILATION ROOMS WITH AIR-CONDITIONING OR FAN
(
RSEAU D'ASPIRATION
DE PLAFOND
CEILING EXTRACTION
SYSTEM
SMOKE
STRATIFICATION
ZONE
ZONE DE
STRATIFICATION
DE FUME
RSEAU VERTICAL
VERTICAL NETWORK
Esc
LaserPlus
VESDA
TM
Climatiseur
Air
conditioning
unit
Flux d'air
Air flow Rseau de
prlvement d'air
Air sampling network
Orifice de
prlvement
Sampling
opening
Ordinateur
Computer
Lecteurs
informatiques
Orifice de
prlvement
Data readers Sampling
opening
Esc Esc
LaserPlus
VESDA
TM
optic
linear
optic
optique
linaire
flames
flammes
sprinkleur
ionic
optique
ionique
FEU COUVANT FUMES VISIBLES FLAMMES
3rd PHASE 2nd PHASE PHASE INITIALE
PRALARME ACTION FEU 1 FEU 2
PREALARM FIRE 1 FIRE 2
PHASE FINALE
INITIAL PHASE FINAL PHASE
CHALEUR
SMOULDERING FIRE VISIBLE SMOKE FLAMES HEAT
Esc
LE TEMPS
TIME
L
'
I
N
T
E
N
S
I
T


D
E

L
'
I
N
C
E
N
D
I
E

-

F
I
R
E

I
N
T
E
N
S
I
T
Y
thermique
thermal
LaserPlus
VESDA
TM
DESCRIPTION
N dun concept original, le VESDA LaserPLUS
instaure une nouvelle gnration de systmes
de dtection multiponctuelle de fume. Utilisant
les dernires technologies, il ralise des
performances incomparables tout en simplifiant
les oprations de mise en service, dexploitation
et de maintenance.
Sa plage de sensibilit trs tendue et son
extrme rapidit de raction le destine tout
naturellement aux locaux stratgiques ou vitaux
des entreprises et aux difices de trs grande
hauteur ou de volume important.
Le VESDA LaserPLUS constitue la solution idale
dans les applications pour lesquelles les
systmes de dtection conventionnels se rvlent
inefficaces ou trop lents : environnements
chargs en poussire, en humidit ou daccs
difficile.
Le VESDA LaserPLUS sintgre parfaitement
tous les systmes de protection incendie de la
gamme CHUBB SCURIT.
Il dtecte les feux couvants ds leur naissance,
bien avant que les fumes ou les flammes ne
soient visibles. Mme si le VESDA LaserPLUS est
trs sensible, il prsente un taux dalarmes
intempestives trs faible, y compris dans les
zones forte concentration de poussire ou
dhumidit, grce sa fonction dadaptation
automatique AUTOLEARN.
DESCRIPTION
The VESDA LaserPLUS originated from an
innovative concept and sets up a new generation
of multipoint smoke detection system. It uses the
latest technologies and has incomparable
performances, and also simplifies startup and
maintenance operations.
Its very wide sensitivity range and extremely fast
reaction speed make it naturally suitable for
company strategic or vital premises and very tall
buildings or very large buildings.
VESDA LaserPLUS is an ideal solution for
applications for which conventional detection
systems are inefficient or too slow : environments
with dust, humidity or difficult access.
VESDA LaserPLUS integrates perfectly into all
fire protection systems in the CHUBB SECURITY
range.
It detects smoldering fires as soon as they start
to develop, well before there are any visible
smoke or flames. Even if the VESDA LaserPLUS is
very sensitive, its false alarm ratio is very low,
even in areas with a strong concentration of dust
or humidity due to its automatic AUTOLEARN
adaptation function.
Courbe de dveloppement d'un incendie - Fire progress curve
Adjustment
opening
Orifice
d'quilibrage
Length 100m maxi/tube
Long. 100m maxi/tube
Distance
1 10m
Air sampling
Prlvement d'air
Dtail
Detail
Tableau de signalisation incendie
conventionnel ou adressable
Conventional or addressable
fire signalling chart
Reading opening (typically 3mm)
Orifice de prlvement ( 3mm typique)
Esc
B
E
D
J
I
H G
K
F
C
A
A
B
C
D
E
Module de synthse (voyants feu/drangement)
et volet d'accs aux bornes de raccordement
Status module (fire/fault lights) and access
to the connectors
Module de programmation Programming module
4 entres d'air 4 air intakes
Module d'affichage Display module
Volet d'accs au filtre Filter access
F
G
H
I
J
K
Avertisseur sonore Audio alarm
Indicateurs des seuils d'alarme Alarm threshold indicators
chelle gradue lumineuse de quantit de fume (20 LED)
Graduated lighted scale for amount of smoke (20 LED)
Afficheur digital multifonctions (sensibilit du dtecteur,
concentration des fumes, numro d'adresse)
Multifunction digital display (sensitivity of the detector,
smoke concentration, address number)
Voyants des alarmes Alarm lights
Voyants des drangements Fault lights
Le VESDA LaserPLUS est un systme dynamique : lair
ambiant de la zone surveille est aspir dans un rseau
de tuyauterie munie dorifices de prlvement. Cet air
est ensuite achemin vers une chambre danalyse par
une pompe centrifuge haut rendement permettant
dquiper des sites de trs grands volumes. Les temps de
rponse restent cependant courts, mme pour de faibles
quantits de fumes. Un filtre mcanique double action
permet la fois :
dliminer la poussire pour assurer une analyse
optimale de la fume,
de garantir la propret de la tte de dtection pendant
plusieurs annes.
Le VESDA LaserPLUS utilise la source lumineuse intense
dun laser combine deux cellules optiques
extrmement efficaces pour dterminer avec prcision la
concentration de fume.
En prsence de particules de fume, la lumire est
rflchie vers les cellules optiques. Cette fume est
visualise sur lchelle lumineuse du Module dAffichage.
Les diffrentes alarmes sont alors actives lorsque les
seuils correspondants sont atteints. Un avertisseur
sonore met un son continu pour lAlarme Feu et un son
modul pour les drangements. Le tableau de
signalisation incendie reoit une information de synthse
des drangements. Ces derniers sont hirarchiss sur le
dtecteur selon leur importance. Le dtecteur fait la
diffrence entre un drangement de type maintenance,
o il est toujours capable de signaler un feu, et un
drangement plus grave lempchant de fonctionner
normalement. Ce second type de drangement ncessite
une intervention immdiate du service Maintenance de
CHUBB SCURIT. Pendant quune alarme est active, le
dtecteur maintient sa surveillance pour avertir dune
ventuelle amplification ou propagation de lincendie.
The VESDA LaserPLUS is a dynamic system : ambient air
in the monitored zone is drawn into a pipe network
provided with drawing off orifices. This air is then
transferred to an analysis chamber by a high efficiency
centrifugal pump to equip very large volume sites.
However, response times are still very short even for low
smoke quantities. A double mechanical action filter:
eliminates dust to provide optimum smoke analysis,
guarantee cleanliness of the detection head for
several years.
VESDA LaserPLUS uses the intense light source of a
laser combined with two extremely efficient optical cells
to precisely determine the smoke concentration.
When smoke particles are present, light is reflected to
the optical cells. This smoke is displayed on the light
scale of the Display Module. The different alarms are
then activated when the corresponding thresholds are
reached. A sound alarm emits a continuous sound for the
Fire Alarm and a modulated sound for malfunctions. The
fire signaling panel receives malfunction synthesis
information. This information is hierarchized on the
detector depending on its importance. The detector
makes the difference between a maintenance type
malfunction in which it is always capable of signaling a
fire, and a more serious malfunction preventing it from
operating normally. This second type of malfunction
requires immediate action by the CHUBB SECURITY
Maintenance service. As long as an alarm is activated,
the detector continues monitoring to signal if the fire
grows or starts to propagate.
OPERATING PRINCIPLES PRINCIPE DE FONCTIONNEMENT
Une activit exigeant une perte dexploitation
minimale : salles informatiques, salles de contrle,
tlcommunications, salles blanches
quipements et armoires stratgiques : process
industriels, simulateurs de vols, automates
Hauts plafonds ou vitesse dair leve : atriums,
entrepts de stockage, hangars davions
Environnements chargs en poussire, humidit,
tempratures extrmes : filatures, menuiseries,
entrepts frigorifiques
Monuments historiques ou btiments forte
contrainte esthtique : cathdrales, galeries dart
Combles inaccessibles.
An activity requiring minimum loss of operations :
computer rooms, control rooms, telecommunications,
clean rooms, etc.
Strategic equipment and cabinets : industrial
processes, flight simulators, logic controllers, etc.
High ceilings or high air speed : atriums, storage
workshops, aircraft hangars, etc.
Environment containing large quantities of dust,
humidity, extreme temperatures : spinning machines,
wood working, refrigeration warehouses, etc.
Historic monuments or buildings with serious esthetic
constraints : cathedrals, art galleries, etc.
Inaccessible roof space.
AREAS OF APPLICATION DOMAINES D'APPLICATION
Lorsque les plafonds sont trs hauts ou sans isolation,
certains facteurs imprvisibles tels que la stratification
de lair surgissent alors. Ce phnomne diminue
lefficacit des dtecteurs de fume conventionnels.
De par limplantation de rseaux de prlvement en
toiture et sur les parois, le systme VESDA LaserPLUS
permet de capter les feux couvants tous les niveaux.
When ceilings are very high or uninsulated, some
unpredictable factors such as air stratification can occur.
This phenomenon reduces the efficiency of conventional
smoke detectors.
Due to the arrangement of sampling networks on the roof
and on walls, the VESDA LaserPLUS system is capable of
detecting smoldering fires at all levels.
VOLUMES DE GRANDE HAUTEUR ET ENTREPTS HIGH CEILING AREAS AND WAREHOUSES
Architecture du systme VESDA LaserPLUS - Architecture of the VESDA LaserPLUS System
(
Les flux dair levs, rencontrs dans les salles
informatiques ou dans les autocommutateurs, transportent
rapidement les gaz de combustion vers le systme de
traitement dair et les loignent des dtecteurs de fume
conventionnels, en les diluant de faon importante.
Dans ce cas, limplantation des points de captation devant
les grilles daspiration rend le systme VESDA LaserPLUS
particulirement efficace.
High air flows that exist in computer rooms and in PABXs
quickly carry combustion gases towards the air treatment
system and keep them away from conventional smoke
detectors, significantly diluting them.
In this case, the arrangement of sensors in front of intake
grills makes the VESDA LaserPLUS system particularly
efficient.
SALLES AVEC CLIMATISATION OU VENTILATION ROOMS WITH AIR-CONDITIONING OR FAN
(
Rf. : 9001018CS Rv 1 Soucieux de lamlioration constante de ses produits, le groupe CHUBB Scurit se rserve le droit de modifier tout moment les spcifications de ce document. Document
non contractuel. The CHUBB Scurit Group is continuously making efforts to improve its products, and reserves the right to modify the specifications in this document at any time.
Non-contractual document - Proximity BBDO.
POUR LE SECTEUR TERTIAIRE : - POUR LE SECTEUR INDUSTRIEL :
0 , 1 5 0 T T C / MN
0 825 80 18 18
0 , 1 5 0 T T C / MN
0 825 018 018
DTECTION ET PROTECTION CONTRE LINCENDIE
VESDA LaserPlus
)
Dtecteur multiponctuel technologie laser certifi NF sous le n MPL 036
Multipoint detector with NF certified laser technology under n MPL 036
Grande plage de sensibilit programmable
Wide range of programmable sensitivity
Architecture modulaire
Modular architecture
Programmation par menu droulant sur cran graphique
Programming by pull down menu on graphic screen
Modlisation de linstallation par logiciel de calcul ASPIRE
Modeling of the installation by the ASPIRE calculation software
Surveillance permanente du dbit dair
Permanent monitoring of the air flow
Maintenance aise
Easy maintenance
DE LEXCELLENCE NAT LA SCURIT
VESDA LaserPLUS + afficheur
+ display
VESDA LaserPLUS
LA GAMME VESDA LaserPLUS THE VESDA LaserPLUS RANGE
(
VESDA LaserPLUS + afficheur + programmeur
+ display + programmer
LES POINTS FORTS
LAlarme Feu (Feu 1) : de 0,005 2%
dobscurcissement/m
3 seuils complmentaires (Pralarme, Action, Feu 2) :
de 0,005 20% dobscurcissement/m
Voyants Feu/Drangement
Afficheur
Programmateur
Surveillance permanente du filtre
Mmorisation des 18 000 derniers vnements.
CARACTRISTIQUES TECHNIQUES
Tension dalimentation : 18 30 VCC
Consommation : 500mA typique
T dair ambiant : de 10 +60C
T dair prlev : de 20 +60C
Humidit relative : 10 95% sans condensation
Sensibilit rglable de 0,005 20% obs./m
Surface surveille : 2000m
2
maxi
Dimensions du coffret (L x H x P) en mm :
350 x 225 x 125
Poids : 4kg
Sorties : 5 relais NO : NF programmables et 2 relais
NO : NF pr programms non maintenus (Alarme Feu
et Drangement) ; pouvoir de coupure : 1A 30V
Rseau de prlvement :
- rseau : tube PVC ou ABS (diamtre des tubes entre
19 et 25 mm)
- 4 tubes daspiration
- 100 mtres maxi par tube (200 mtres maxi au total)
- distance entre les orifices de prlvement : entre 1
et 10 mtres (diamtre dun orifice : 3 mm typique).
CERTIFICATIONS ET AGRMENTS
Les qualits de fiabilit et de stabilit du dtecteur
VESDA LaserPLUS ont t values et agres par
diffrentes organisations internationales dont :
- AFNOR (France) n MPL 036
- Factory Mutual (USA) n 0B5A5.AY
- UnderwritersLaboratories (USA) n 310398-5198
- Loss Prevention Council Board (GB) n 305b
- VDS (Allemagne) en cours
- Compatibilit lectromagntique 89/336/CCE (CE)
- Plus de 40 000 installations VESDA dans le monde.
ADVANTAGES
A fire alarm (Fire 1) : from 0.005 to 2% darkening/m
Three complementary thresholds (Prealarm, Action,
Fire 2) : from 0.005 to 20% of darkening/m
Fire/Malfunction lights
Display
Programmer
Permanent filter monitoring
Memorization of the 18,000 last events.
TECHNICAL CHARACTERISTICS
Power supply voltage : 18 to 30 Vdc
Consumption : 500mA typical
Ambient air T : from 10 to +60C
Sampled air T : from 20 to +60C
Relative humidity : 10 to 95% without condensation
Sensitivity adjustable from 0.005 to 20% obs./m
Monitored area : 2000m
2
max
Box dimensions (L x H x D) in mm : 350 x 225 x 125
Weight : 4 kg
Exits : 5 NO : NC programmable relays and 2
preprogrammed unmaintained NO : NC relays
(Fire and Malfunction Alarm) ; breaking capacity :
1A at 30V
Sampling network :
- network : PVC or ABS tube (tube diameter between
19 and 25 mm)
- 4 intake tubes
- 100 meters maximum per tube (200 meters
maximum total)
- distance between sampling orifices : between 1 and
10 meters (orifice diameter 3 mm typical).
CERTIFICATIONS AND APPROVALS
Reliability and stability qualities of the VESDA
LaserPLUS detector were evaluated and approved by
different international organizations including :
- AFNOR (France) n MPL 036
- Factory Mutual (USA) n 0B5A5.AY
- Underwriters Laboratories (USA) n 310398-5198
- Loss Prevention Council Board (GB) n 305b
- VDS (Germany) in progress
- Electromagnetic compatibility 89/336/CCE (CE)
- More than 40 000 VESDA installations throughout
the world.
Rf. : 9001018CS Rv 1 Soucieux de lamlioration constante de ses produits, le groupe CHUBB Scurit se rserve le droit de modifier tout moment les spcifications de ce document. Document
non contractuel. The CHUBB Scurit Group is continuously making efforts to improve its products, and reserves the right to modify the specifications in this document at any time.
Non-contractual document - Proximity BBDO.
POUR LE SECTEUR TERTIAIRE : - POUR LE SECTEUR INDUSTRIEL :
0 , 1 5 0 T T C / MN
0 825 80 18 18
0 , 1 5 0 T T C / MN
0 825 018 018
DTECTION ET PROTECTION CONTRE LINCENDIE
VESDA LaserPlus
)
Dtecteur multiponctuel technologie laser certifi NF sous le n MPL 036
Multipoint detector with NF certified laser technology under n MPL 036
Grande plage de sensibilit programmable
Wide range of programmable sensitivity
Architecture modulaire
Modular architecture
Programmation par menu droulant sur cran graphique
Programming by pull down menu on graphic screen
Modlisation de linstallation par logiciel de calcul ASPIRE
Modeling of the installation by the ASPIRE calculation software
Surveillance permanente du dbit dair
Permanent monitoring of the air flow
Maintenance aise
Easy maintenance
DE LEXCELLENCE NAT LA SCURIT
VESDA LaserPLUS + afficheur
+ display
VESDA LaserPLUS
LA GAMME VESDA LaserPLUS THE VESDA LaserPLUS RANGE
(
VESDA LaserPLUS + afficheur + programmeur
+ display + programmer
LES POINTS FORTS
LAlarme Feu (Feu 1) : de 0,005 2%
dobscurcissement/m
3 seuils complmentaires (Pralarme, Action, Feu 2) :
de 0,005 20% dobscurcissement/m
Voyants Feu/Drangement
Afficheur
Programmateur
Surveillance permanente du filtre
Mmorisation des 18 000 derniers vnements.
CARACTRISTIQUES TECHNIQUES
Tension dalimentation : 18 30 VCC
Consommation : 500mA typique
T dair ambiant : de 10 +60C
T dair prlev : de 20 +60C
Humidit relative : 10 95% sans condensation
Sensibilit rglable de 0,005 20% obs./m
Surface surveille : 2000m
2
maxi
Dimensions du coffret (L x H x P) en mm :
350 x 225 x 125
Poids : 4kg
Sorties : 5 relais NO : NF programmables et 2 relais
NO : NF pr programms non maintenus (Alarme Feu
et Drangement) ; pouvoir de coupure : 1A 30V
Rseau de prlvement :
- rseau : tube PVC ou ABS (diamtre des tubes entre
19 et 25 mm)
- 4 tubes daspiration
- 100 mtres maxi par tube (200 mtres maxi au total)
- distance entre les orifices de prlvement : entre 1
et 10 mtres (diamtre dun orifice : 3 mm typique).
CERTIFICATIONS ET AGRMENTS
Les qualits de fiabilit et de stabilit du dtecteur
VESDA LaserPLUS ont t values et agres par
diffrentes organisations internationales dont :
- AFNOR (France) n MPL 036
- Factory Mutual (USA) n 0B5A5.AY
- UnderwritersLaboratories (USA) n 310398-5198
- Loss Prevention Council Board (GB) n 305b
- VDS (Allemagne) en cours
- Compatibilit lectromagntique 89/336/CCE (CE)
- Plus de 40 000 installations VESDA dans le monde.
ADVANTAGES
A fire alarm (Fire 1) : from 0.005 to 2% darkening/m
Three complementary thresholds (Prealarm, Action,
Fire 2) : from 0.005 to 20% of darkening/m
Fire/Malfunction lights
Display
Programmer
Permanent filter monitoring
Memorization of the 18,000 last events.
TECHNICAL CHARACTERISTICS
Power supply voltage : 18 to 30 Vdc
Consumption : 500mA typical
Ambient air T : from 10 to +60C
Sampled air T : from 20 to +60C
Relative humidity : 10 to 95% without condensation
Sensitivity adjustable from 0.005 to 20% obs./m
Monitored area : 2000m
2
max
Box dimensions (L x H x D) in mm : 350 x 225 x 125
Weight : 4 kg
Exits : 5 NO : NC programmable relays and 2
preprogrammed unmaintained NO : NC relays
(Fire and Malfunction Alarm) ; breaking capacity :
1A at 30V
Sampling network :
- network : PVC or ABS tube (tube diameter between
19 and 25 mm)
- 4 intake tubes
- 100 meters maximum per tube (200 meters
maximum total)
- distance between sampling orifices : between 1 and
10 meters (orifice diameter 3 mm typical).
CERTIFICATIONS AND APPROVALS
Reliability and stability qualities of the VESDA
LaserPLUS detector were evaluated and approved by
different international organizations including :
- AFNOR (France) n MPL 036
- Factory Mutual (USA) n 0B5A5.AY
- Underwriters Laboratories (USA) n 310398-5198
- Loss Prevention Council Board (GB) n 305b
- VDS (Germany) in progress
- Electromagnetic compatibility 89/336/CCE (CE)
- More than 40 000 VESDA installations throughout
the world.