Académique Documents
Professionnel Documents
Culture Documents
2182
Portland Cement Association 1999 All rights reserved This information is copyright protected. PCA grants permission to electronically share this document with other professionals on the condition that no part of the file or document is changed
Portland Cement Association 2001 This information is copyright protected. PCA grants permission to electronically share this document with other professionals on the condition that no part of the file or document is changed
ABSTRACT
This work was carried out in order to provide additional data on the use of low C3A-content (Type II) cements containing limestone. Five cements with varying limestone contents were made from one clinker and performance tests on mortar and concrete samples were conducted. In terms of compressive strength of both the mortars and concretes, there was no difference between the cements; there was no measurable trend and the results were within the precision of the test methods. The results were all well above the minima required in ASTM C 150. Similarly, mortar shrinkage results were all very similar and within the precision of the test method. In sulfate expansion tests there was no significant difference between the cements at the ages referenced in ASTM C 150. All the cements were well within the requirements specified in ASTM C 150. There was no trend in sulfate resistance exhibited with the inclusion of limestone as the variable in the long-term C 1012 and C 452 tests.
KEYWORDS
Sulfate resistance, Compressive strength, Type II cement, Interground limestone
INTRODUCTION
This work was carried out in order to provide additional data on the use of low C3A-content (Type II) cements containing limestone. Five cements with varying limestone contents were made from the same clinker and performance tests on mortar and concrete samples were conducted.
MATERIALS
Portland cements were ground by a commercial manufacturing plant from a single Type II clinker having C3A content of less than 8%. All the cements were ground so that at least 92% of each passed the No.-325 sieve. Two limestones, having different CaCO3 contents, were interground in the cements at three addition levels up to a nominal 5%. Table 1 describes the labeling of the five cements and their limestone contents. Two samples of each cement (labeled a and b) were provided by the manufacturer, each with different sulfate contents. The a and b samples were then blended at CTL to achieve the optimum sulfate content. Calculation of the optimum sulfate content was based on 3-day strengths and analyses provided by the manufacturer. Aggregates used in the concretes were siliceous sand and stone from Eau Claire, WI. To minimize the number of variables, no admixtures were used.
Mortars. The mortars were prepared at a constant water content and the flow for all mixes was within the range 105 115. The strength results are given in Table 6 and Figure 1. ASTM C 596 Drying Shrinkage of Mortar Containing Hydraulic Cement. The results are given in Table 7 and Figure 2.
ASTM C 1012 Standard Test Method for Length Change of Hydraulic Cement Mortars Exposed to a Sulfate Solution. As a point of reference, the maximum limit of expansion specified in ASTM C 1157 for type MS cements is 0.10 at 6 months when tested according to ASTM C 1012. The results are given in Table 8 and Figure 3. ASTM C 452 Standard Test Method for Potential Expansion of Portland-Cement Mortars Exposed to Sulfate. The maximum expansion limit for ASTM C 150 Type V cement is 0.04% at 14 days when tested according to ASTM C 452. The results are given in Table 9 and Figure 4
Concrete Tests Five concrete mixes were prepared as shown in Table 10. Mixes were designed to have constant materials proportions with a water-cement ratio of 0.50 and a cement content of 550 pounds per cubic yard. Samples from the mixes were used to determine slump and air content in accordance with ASTM C 143 and C 231, respectively, and compressive strength at 7 and 28 days to ASTM C 39. The properties and cylinder compressive strengths of the concrete mixes are given in Table 10.
DISCUSSION
In terms of compressive strength of both the mortars and concretes, there was no difference between the cements; there was no measurable trend and the results were within the precision of the test methods. The results were all well above the minima required in ASTM C 150. Similarly, mortar shrinkage results were all very similar and within the precision of the test method. In the sulfate expansion tests there was no significant difference between the cements at the ages referenced in ASTM C 150. All the cements were well within the requirements specified in ASTM C 150. There was no trend in sulfate resistance exhibited with the inclusion of limestone as the variable in the long-term C 1012 and C 452 tests.
CONCLUSION
Five interground cements made with low C3A-content (Type II) clinker and different amounts of high- and low-calcium limestone were subjected to several tests including their ability to resist external sulfate attack. The inclusion of limestone was shown to result in no significant difference in performance.
ACKNOWLEDGEMENT
The research reported in this paper (PCA R&D Serial No. 2182) was conducted by Construction Technology Laboratories, Inc., with the sponsorship of the Portland Cement Association (PCA Project Index No 95-07c). The contents of this paper reflect the views of the author, who is responsible for the facts and accuracy of the data presented. The contents do not necessarily reflect the views of the Portland Cement Association.
TABLES
Table 1. Description and Labeling of Cements
Label 0.0% 2.5% Lo Ca 3.5% Lo Ca 3.0% Hi Ca 5.0% Hi Ca Limestone type None Low CaCO3 Low CaCO3 High CaCO3 High CaCO3 Limestone content, % by mass of cement 0.0 2.5 3.5 3.0 5.0
0.74 61 15 8 11
0.21 -
0.56
0.02
0.72 0.23 63 11 7 10
0.67 0.33 62 10 7 10
Calculated compounds
0.74
0.78
0.90
0.79
0.45
0.50
0.57
0.50
0.70
0.80
0.78
0.73
0.69
Insoluble 0.26 0.76* 0.84* 0.48 0.54 residue (%) * Note: Exceeds allowable limit in ASTM C 150. Thus, in practice the amount of limestone would need to be reduced. For purposes of this test series, limit was intentionally exceeded.
FIGURES
50 40 Strength, Mpa 30 20 10 0 0 10 20 30 Age (days) 40 50 60 0.0% 2.5% Lo Ca 3.5% Lo Ca 3.0% Hi Ca 5.0% Hi Ca
0.150
Shrinkage, %
0.050
0.100 0.0% 2.5% Lo Ca 3.5% Lo Ca 3.0% Hi Ca 5.0% Hi Ca 6 month limit specified in ASTM C 1157
0.060
0.040
0.020
0.10 0.08 Expansion (%) 0.06 0.04 0.02 0.00 0 100 200 Age (days) 300 400 0.0% 2.5% Lo Ca 3.5% Lo Ca 3.0% Hi Ca 5.0% Hi Ca 14 day limit specified in ASTM C 150