Table 1 (All Classes in 1 Table)

This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9
Max System Voltage in kV Applied Test From C57.12.00 Nominal Table 7 in kV System Voltage (V, in kV) Delta Gr Y Imp Y 1.2 2.5 5 8.7 15 25 34.5 46 69 10 15 19 26 34 50 70 95 140 10 15 19 26 26 26 26 34 34 10 15 19 26 26 34 50 70 95 Induced Test, in kV Dist. & Class I Class 2, >72.5 kV
2V 3

Basic Insulation Level, in kV Alternates 45 60 75 95 110 150 200 250 350 400 125

Neutral BIL, in kV GrY 30 45 60 75 75 75 75 95 95 Impedance 30 45 60 75 75 95 125 150 200

One Enhanced Hour 7200 cy Min. 30 45 60 75 95 125 150 200 250

Distribution and Class I Power Transformers, =69 kV Nominal System Voltage 1.5 3.5 6.9 11 17.2 26 38 48.3 72.5 1.4 2.9 5.8 10 17.3 28.9 39.8 53.1 79.7

Class II Power Transformers, > 72.5 kV Nominal System Voltage 120 145 166 244 362 550 765 800 Notes: 1.* 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 115 138 161 230 345 500 735 765 173 207 242 345 518 N/A N/A N/A 34* 34* 34* 34* 34* 34* 34* 34* 95* 95* 95* 95* 95* 95* 95* 95* N/A N/A N/A N/A N/A N/A N/A N/A 105 125 145 210 315 475 750 795 120 145 170 240 360 550 850 885 350 450 550 750 1050 1425 1950 1950 450 550 650 825 1175 1550 2050 2050 1675 550 650 750 900 850 110 110 110 110 110* 110* 110* 110* 250 250 350* 350* 350* 350* 350* 350*

14.

Insulation level to conform with service requirements but never less than the level shown. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. Front-of-wave Impulse levels must be specified prior to design of the transformer. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings. All test levels are line to ground. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for application on ungrounded systems. Minimum Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal system voltage, and never less than the applied test level from line to ground. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal system voltage, and never less than the applied test level from line to ground. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kV and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed for their voltage rating. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals.

This example shows Table 1 split into two tables by transformer class: Table 1a (Distribution and Class 1)
This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9
Max System Voltage (kV) Nominal System Voltage (kV) Applied Test From C57.12.00 Table 7 (kV) Delta Gr Y Imp Y Induced Test in kV
2V 3

Basic Insulation Level (kV) Min. Alternates

Neutral BIL (kV) GrY Impedance

Distribution Transformers 1.5 3.5 6.9 11 17.2 26 38 48.3 72.5 1.2 2.5 5 8.7 15 25 34.5 46 69 10 15 19 26 34 50 70 95 140 10 15 19 26 26 26 26 34 34 10 15 19 26 26 34 50 70 95 1.4 2.9 5.8 10 17.3 28.9 39.8 53.1 79.7 30 45 60 75 95 125 125 200 250 150 150 250 350 200 30 45 60 75 75 75 75 95 95 30 45 60 75 75 95 125 150 200

Class I Power Transformers, =69 kV Nominal System Voltage 1.5 3.5 6.9 11 17.2 26 38 48.3 72.5 1.2 2.5 5 8.7 15 25 34.5 46 69 10 15 19 26 34 50 70 95 140 10 15 19 26 26 26 26 34 34 10 15 19 26 26 34 50 70 95 1.4 2.9 5.8 10 17.3 28.9 39.8 53.1 79.7 30 45 60 75 95 150 200 200 250 250 350 45 60 75 95 110 30 45 60 75 75 75 75 95 95 30 45 60 75 75 95 125 150 200

Notes: 1.* Insulation level to conform with service requirements but never less than the level shown. 15. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. 16. Front-of-wave Impulse levels must be specified prior to design of the transformer. 17. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 18. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings. 19. All test levels are line to ground. 20. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for application on ungrounded systems. 21. Minimum Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal system voltage, and never less than the applied test level from line to ground. 22. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal system voltage, and never less than the applied test level from line to ground. 23. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. 24. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels. 25. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. 26. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kV and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed for their voltage rating. 27. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals.

Table 1b (Class II Transformers)


This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9
Max Nominal System System Voltage Voltage (kV) (kV) Delta Gr Y Imp Y 120 145 166 244 362 550 765 800 115 138 161 230 345 500 735 765 173 207 242 345 518 N/A N/A N/A 34* 34* 34* 34* 34* 34* 34* 34* Applied Test From C57.12.00 Table 7 (kV) Induced Test (kV) Class 1 =69 kV Class 2, >72.5 kV One Hour Enhanced 7200 cy. Basic Insulation Level (kV) Min Alternates Neutral BIL (kV) GrY 110 850 110 110 110 110* 110* 110* 110* Impedance 250 250 350* 350* 350* 350* 350* 350*

Class II Power Transformers, > 72.5 kV Nominal System Voltage 95* N/A 105 120 350 450 550 95* 95* 95* 95* 95* 95* 95* N/A N/A N/A N/A N/A N/A N/A 125 145 210 315 475 750 795 145 170 240 360 550 850 885 450 550 750 1050 1425 1950 1950 550 650 825 1175 650 750 900

1550 1675 2050 2050

Notes: 1.* Insulation level to conform with service requirements but never less than the level shown. 2. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. 3. Front-of-wave Impulse levels must be specified prior to design of the transformer. 4. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 5. The Insulation levels for Class 1 and Class 2 transformers shall be selected from this table for both the high-voltage and lowvoltage windings. 6. All test levels are line to ground. 7. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for application on ungrounded systems. 8. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal system voltage, and never less than the applied test level from line to ground. 9. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. 10. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels. 11. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. 12. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals.

Table 2
High Frequency Test Tables BIL kV Crest 1.2 X 50 -sec 30 45 60 75 95 110 125 150 200 250 350 450 550 650 750 825 900 1050 1175 1300 1425 1550 1675 1800 1950 2050 Chopped Wave kV Crest 1.1*BIL 33 50 66 83 105 120 138 165 220 275 385 495 605 715 825 900 990 1155 1290 1430 1570 1705 1845 1980 2145 2255 Minimum Time to Flashover, -sec 1.0 1.5 1.5 1.5 1.8 2.0 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 Front Of Wave Minimum Time to Flashover, -sec Switching Impulse kV Crest 0.83*BIL

kV Crest

165 195 220 260 345 435

0.5 0.5 0.5 0.5 0.5 0.5 280 375 460 540 620 685 745 870 975 1080 1180 1290 1390 1550 1620 1700

580 0.58 N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified

Notes: 1. Front-of-Wave tests must be specified prior to the design of the transformer. 2. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 3. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings. 4. Phase to ground specified Switching impulse levels are not always possible for low voltage windings.

Table 1b This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9
Max System Voltage (V) Nominal System Voltage (V) Applied Test From C57.12.00 Table 7 Delta Gr Y Imp Y Induced Test
2V 3

Basic Insulation Level Min. Alternates

Neutral BIL GrY Impedance

Distribution Transformers 1.5 3.5 6.9 11 17.2 26 38 48.3 72.5 1.2 2.5 5 8.7 15 25 34.5 46 69 10 15 19 26 34 50 70 95 140 10 15 19 26 26 26 26 34 34 10 15 19 26 26 34 50 70 95 1.4 2.9 5.8 10 17.3 28.9 39.8 53.1 79.7 30 45 60 75 95 125 125 200 250 150 150 250 350 200 30 45 60 75 75 75 75 95 95 30 45 60 75 75 95 125 150 200

Class I Power Transformers, < or = 69 kV Nominal System Voltage 1.5 3.5 6.9 11 17.2 26 38 48.3 72.5 1.2 2.5 5 8.7 15 25 34.5 46 69 10 15 19 26 34 50 70 95 140 10 15 19 26 26 26 26 34 34 10 15 19 26 26 34 50 70 95 1.4 2.9 5.8 10 17.3 28.9 39.8 53.1 79.7 30 45 60 75 95 150 200 200 250 250 350 45 60 75 95 110 30 45 60 75 75 75 75 95 95 30 45 60 75 75 95 125 150 200

Notes: 1. Insulation level to conform with service requirements but never less than the level shown. 13. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. 14. Front-of-wave Impulse levels must be specified prior to design of the transformer. 15. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 16. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings. 17. All test levels are line to ground. 18. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for application on ungrounded systems. 19. Minimum Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal system voltage, and never less than the applied test level from line to ground. 20. Minimum Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal system voltage, and never less than the applied test level from line to ground. 21. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. 22. Voltages greater than Maximum System Voltage shall use the next higher voltage class test levels. 23. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. 24. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kV and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed for their voltage rating. 25. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals.

Table 2 High Frequency Test Tables BIL kV Crest 1.2 X 50 -sec 30 45 60 75 95 110 125 150 200 250 350 450 550 650 750 825 900 1050 1175 1300 1425 1550 1675 1950 1950 2050 Notes: 1. 5. 6. 7. Chopped Wave kV Crest 1.1*BIL 33 50 66 83 105 120 138 165 220 275 385 495 605 715 825 900 990 1155 1290 1430 1570 1705 1845 2145 2145 2255 Minimum Time to Flashover, -sec 1.0 1.5 1.5 1.5 1.8 2.0 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 Front Of Wave Minimum Time to Flashover, -sec Switching Impulse kV Crest 0.83*BIL

kV Crest

165 195 220 260 345 435 580

0.5 0.5 0.5 0.5 0.5 0.5 0.58 280 375 460 540 620 685 745 870 975 1080 1180 1290 1390 1550 1620 1700

N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified N/A unless specified

Front-of-Wave tests must be specified prior to the design of the transformer. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage and low-voltage windings. Phase to ground specified Switching impulse levels are not always possible for low voltage windings.