FOR
ILLUMINATION SYSTEM
CONTENT
CONTENT
...............................................
2
1.00.00
SCOPE OF WORK
....................................................
1
2.00.00 SCOPE OF SUPPLY
....................................................
1
3.00.00 SCOPE OF SERVICE
....................................................
2
4.00.00 GENERAL REQUIREMENTS
....................................................
2
5.00.00 DESIGN CRITERIA
....................................................
3
6.00.00 SPECIFIC REQUIREMENTS - SUPPLY
....................................................
7
7.00.00 SPECIFIC REQUIREMENTS-SERVICES
....................................................
15
8.00.00 TESTS
....................................................
21
9.00.00 DRAWINGS, DATA & MANUALS
....................................................
22
RECEPTACLE
31
CEILING FANS
32
LIGHTING POLES / TOWERS
32
SWITCHBOARD
................................
32
MISCELLANEOUS ITEMS
33
ILLUMINATION LEVEL
....................................................
34
Sl. No.
Location
Lighting Fixture Type
Lux Level
................................
34
Sl. No.
Location
Lighting Fixture Type
Lux
Level
................................
34
Sl. No.
Location
Lighting Fixture Type
Lux Level
................................
36
RATINGS AND REQUIREMENTS
....................................................
37
FITTINGS AND ACCESSORIES
....................................................
38
ANNEXURE A
ANNEXURE B
ATTACHMENTS
AVAILABLE POWER SUPPLY
BROAD
LIST
OF AREAS
ILLUMINATED
TO
BE
ANNEXURE
ANNEXURE
ANNEXURE
ANNEXURE
C
D
E
F
OF
TECHNICAL SPECIFICATION
FOR
ILLUMINATION SYSTEM
1.00.00
SCOPE OF WORK
1.01.00
1.02.00
1.03.00
2.00.00
SCOPE OF SUPPLY
2.01.00
2.02.00
The equipment and materials within the scope of supply shall include
but not limited to :
a)
b)
c)
d)
e)
f)
g)
h)
All
i)
blocks.
fittings,
supports,
brackets,
anchors,
clamps
and
connections.
3.00.00
SCOPE OF SERVICE
3.00.01
4.00.00
GENERAL REQUIREMENTS
4.01.00
IS-1913
b)
IS-1977
c)
IS-10322
d)
IS-8623
e)
IS-6064
f)
IS-8828
g)
IEC-598
h)
IS-9224
i)
IS-2959
j)
IS-1248
k)
IS-2705
l)
IS-4160
m)
IS-2713
n)
IS-800
o)
IS-2026
p)
IS-2099
q)
IS-694
r)
IS-1554
s)
IS-9537
t)
IS-5133
5.00.00
DESIGN CRITERIA
5.01.00
Design Basis
5.01.01
The system provides lighting and electric power supply for lighting to
all plant areas under scope of this package. In addition, it also
provides lighting to selected areas during plant emergency
conditions.
5.01.02
5.01.03
5.01.04
5.02.00
System Concept
The lighting system shall comprise of following sub-systems:
5.02.01
Modules with lighting fixtures cables accessories for coal bunker area
& conveyer lighting to be kept under the scope of main plant with
necessary reflection in transformer sizing calculation.
5.02.02
5.02.03
a)
b)
b)
c)
d)
5.02.04
i)
ii)
5.03.00
5.03.01
5.03.02
5.03.03
All equipment and accessories shall have proper enclosure to suit the
site conditions. Hazardous areas shall have flame-proof enclosure.
5.03.04
5.03.05
Heavy duty AYWY FRLS cables will be used only for connections :
f)
a)
g)
h)
5.04.00
Method of Calculation
5.04.01
5.04.02
b)
c)
d)
e)
mounting height.
etc.
5.04.03
Area
Maintenance factor
Control Room
0.65 - 0.75
Switchgear/MCC Room
0.6
- 0.65
0.55 - 0.6
Other factors e.g. lamp burn out factor, ballast factor, temperature
factor, lumen depreciation factor, etc. may also be considered.
5.04.05
5.04.06
5.04.07
Voltage drop at the fixture from the MLDB bus shall not exceed 3%.
5.04.08
Circuit loading of each lighting panel shall be done in such a way that
almost balanced loading in all the phases i.e. R, Y & B is achieved.
5.04.09
area.
5.04.10
6.00.00
6.01.00
6.01.01
6.01.02
6.01.03
6.01.04
6.02.00
Lighting Fixtures
6.02.01
6.02.02
6.02.03
6.02.04
High bay fixtures shall have provision for vibration damper to ensure
rated lamp life.
6.02.05
Fixtures shall be furnished complete with lamps and integrally / nonintegrally or separately mounted control gear & accessories as
applicable for different types of fixtures. These shall include holders,
ballast, capacitor, starter, ignitors, etc.
6.02.06
Lighting fixture
b)
6.03.00
Lamps
6.03.01
General lighting service (GLS) lamps shall be with clear glass and
screwed caps.
6.03.02
All fluorescent lamps shall be bi-pin rotary type and either cool
daylight or white as per Annexure-C. Lamp holders shall be spring
loaded, low contact resistance type and shall have resistance to
wear.
6.03.03
screwed
6.03.04
cap.
Lamps shall be suitable for use in position and capable of withstanding small vibrations. Restrictions and special features, if any,
shall be clearly indicated in the bid.
6.03.05
6.03.06
6.04.00
6.04.01
copper
Ballasts shall be heavy duty, low loss & polyester-filled type with
6.04.02
winding .
Ballasts for Mercury / Sodium vapour lamps shall be provided with
suitable tapping to set the voltage within range specified.
6.04.03
6.04.04
6.04.05
6.04.06
Electronic Ballasts shall be suitable for 220 V DC and also 240 V AC.
6.04.07
6.04.08
It shall be Flicker-free warm start, ideal for areas with high switching
frequency.
6.04.09
6.04.10
6.04.11
6.05.00
6.05.01
6.05.02
6.05.03
6.05.04
6.05.05
Two ground pads with M10 G.I. bolts and nuts shall be provided on
each Lighting Distribution Board and Lighting Panel for connection to
ground conductors of appropriate size.
6.05.06
6.05.07
6.05.08
6.05.09
6.06.00
6.06.01
6.06.02
6.06.03
6.06.04
6.06.05
MCCB & MCB shall be suitable for manual closing and opening and
also automatic trip on overload and short circuit.
6.06.06
Time switch in street lighting panels shall be clock switch type with
ON-OFF time setting facility, which shall ensure respective ON-OFF
operation in every 24 Hours cycle. Voltmeter / Ammeter shall be of
accuracy class 2.0 or better as per IS:1248. Voltmeter / Ammeter
selector switch shall be of reputed make.
6.07.00
Receptacles
6.07.01
6.07.02
6.07.03
6.07.01
6.08.00
6.08.01
The fans shall have three well balanced blades, and shall be
reasonably free from noise. Pedestal fans shall also be provided as
per Owner requirement.
6.08.02
Fan motor shall be totally enclosed type with copper winding and
class E insulation.
6.08.03
6.09.00
6.09.01
6.09.02
Switch boards / boxes located in control room and office areas shall
be flush mounted type on brick wall with only the switch knob
projecting outside.
6.09.03
Switch boards / boxes shall have conduit knock outs on the sides.
Adequate provision shall be made for ventilation of these boxes.
6.09.04
6.09.05
6.10.00
6.10.01
6.10.02
a)
b)
b)
6.11.00
Maintenance Equipment
6.11.01
The Contractor shall supply four (4) nos. of wheel mounted adjustable aluminium ladder for the maintenance of street lights as per
Annexure-C.
6.11.02
For the maintenance of lighting fixtures within the power house, the
contractor shall also supply three (3) nos. free standing adjustable
aluminium ladder, adjustable from 5m. to 10m.
6.12.00
Special Requirement
6.12.01
6.12.02
6.12.03
In all the air filtration units and air handling units, one marine type
lamp (of 100 Watt approx.) shall be supplied and the wiring & fixing
of the same has to be done by the contractor.
6.13.00
6.13.01
6.13.02
6.13.03
for
R-Phase
BLACK
for
Neutral
YELLOW for
Y-Phase
WHITE
for
+ Ve D.C.
BLUE
B-Phase
GREY
for
- Ve D.C.
for
10 Sq. mm.
Stranded conductor
2.5 Sq. mm. Copper
Stranded conductor.
From lighting panel to 5/15A receptacles
Copper
Stranded conductor.
6.14.00
6.14.01
6.14.02
6.14.03
Each piece of conduit shall be straight, free from blister and other
defects and covered with capped bushings at both ends.
6.14.04
Flexible conduits shall be made with bright, cold rolled annealed and
electro-galvanised mild steel strips and coated with PVC.
6.15.00
Junction Box
6.15.01
6.15.02
6.15.03
6.15.04
6.16.00
Terminals
6.16.01
6.16.02
6.17.00
6.18.00
24 V Supply Module
Each 24V A.C. supply module shall have one (1) no air-cooled two
winding, 500VA, 1-phase, 50HZ, 240/24V transformer with 5A (240V
side) and 15A (24V side) HRC fuse and necessary 240V and 24V
terminals for incoming and outgoing connections. The 240V
terminals of 24V AC supply module shall be fed from respective
lighting panels. A group of 5A, 24V AC receptacles located near
Boiler access doors and condenser area shall be wired up from 24V
side of each 24V A.C. supply module.
The 24V A.C. supply modules shall be sheet steel enclosed with
louvers and shall be suitable for outdoor use. The 24V A.C. supply
modules shall be suitable for wall / steel structure / column
mounting. Switches shall be mounted at the front on sheet steel
enclosure.
The module shall be complete with required length flexible cable,
one (1) no. 3 pin 240 V, 5/15A plug; one (1) no. 5/15A ON/OFF switch
and one (1) no. 3 pin 240 V, 5/15A socket outlet.
6.18.01
6.19.00
Nameplate
Nameplates shall be furnished for identification of devices and
circuits. All switches, controls and indications shall be permanently
and legibly marked in English as to clearly indicate their functions.
All lighting fixtures, receptacles, fans, junction boxes etc. shall be
properly marked up indelibly with corresponding circuit numbers.
6.20.00
Samples
Owner reserves the right to call for samples if considered necessary
and the same shall be submitted by the Bidder free and without any
obligation.
7.00.00
SPECIFIC REQUIREMENTS-SERVICES
7.01.00
7.01.01
7.01.02
The materials shall include but shall not be limited to the following :
a)
Consumables
b)
Hardware
c)
Materials
Junction
boxes,
terminal
blocks,
connectors, ferrules, lugs, brass glands,
rigid / flexible conduits, cables, ground
wires, etc.
7.01.03
Supply of cement, sand, stone, etc. required for the execution of the
contract shall be the responsibility of the Contractor.
7.02.00
Testing Equipment
7.02.01
7.03.00
Installation - General
7.03.01
7.03.02
7.04.00
Lighting Fixtures
7.04.01
7.04.02
7.04.03
7.04.05
7.04.06
7.04.07
7.05.00
Receptacles
Receptacles shall be installed at locations shown in approved
drawings.
7.06.00
7.06.01
7.07.00
7.08.00
7.08.01
7.08.02
7.09.00
Conduit System
7.09.01
7.09.02
7.09.03
7.09.04
7.09.05
7.09.06
7.09.07
7.09.08
7.09.09
7.09.10
7.09.11
7.09.12
7.09.13
7.09.14
7.09.15
7.09.16
7.09.17
conduits.
The Battery Room installation shall be made with acid fume proof
7.09.18
Field bends shall have a minimum radius of four (4) times the
conduit diameter. All bends shall be free of kinks, indentations or
flattened surfaces. Heat shall not be applied in making any conduit
bend.
7.09.19
7.09.20
7.09.21
7.09.22
7.09.23
In control rooms and office areas provided with false ceiling conduct
run shall be concealed type, embedded in the walls.
7.09.24
7.10.00
Wiring
7.10.01
7.10.02
Wire shall not be pulled through more than two equivalent 90 0 bends
in a single conduit run.
7.10.03
7.10.05
7.10.06
A.C. and D.C. circuits shall not be run in the same conduit and
junction boxes. Circuits fed from different transformers shall be run
through different conduits and Junction boxes.
7.10.07
7.10.08
7.11.00
Cabling
7.11.01
7.11.02
Buried cables shall be laid and covered with sand / riddled earth and
protected from damage by bricks at sides and precast concrete stab
at top. Buried cables shall have cable markers at 50M interval and
projecting 150 mm above ground. At cable bends and joints markers
shall be provided wherever required.
7.11.03
7.12.00
Grounding
7.12.01
7.12.02
7.12.03
7.12.04
7.12.05
Each street lighting Pole shall be grounded at two points by two nos.
50x6 mm G.I flat risers from two (2) nos. earthing spike 40 mm dia &
3 m long directly driven into ground at a depth of 1m from ground
level. The junction box at each lighting pole is grounded at two (2)
points from two (2) nos. earthing terminals by 8 SWG GI wire. One 8
SWG G.I wire shall be taken upto the junction box from lighting
fixtures and connected to grounding point.
7.12.06
Two (2) nos. earthing spike 3m long & 40 mm dia directly driven into
ground at a depth of 1m from ground level shall be provided for each
flood lighting tower grounding. 2 nos. 50 x 6 mm GI flat risers from
this spikes shall be taken upto grounding termination lighting panel
on tower platform. The sheet steel cubicle housing the power supply
Isolator at base of flood lighting tower shall be connected at two (2)
points from these two earthing risers by 8 SWG G.I. wire. The flood
lighting fixtures shall be grounded by one (1) no. 8 SWG G.I wire
running through the lighting conduit upto the above lighting panel.
Two (2) nos. separate spike of 3m long & 40 mm dia directly driven
into ground at a depth of one (1) m from ground level shall be
provided for connection of the lightning mast on top of flood lighting
tower through two (2) nos. 50x6 mm G. I. flat down conductor.
7.13.00
7.13.01
Equipment foundations panel foundations and all other civil work will
be provided by the Contractor.
7.14.00
7.14.01
7.14.02
7.14.03
The Contractor shall make use of his own arrangements for pumping
out any water that may be accumulated in the excavation.
7.14.04
7.15.00
7.15.01
7.15.02
7.15.03
7.16.00
Painting
7.16.01
Street light poles shall be given two coats of aluminium paints after
installation.
All steel fabrication shall be given two coats of redoxide primer
followed by two coats of battleship gray shade 632 of IS-5.
7.16.02
7.16.03
All equipment shall be given touch-up paint as required after
installation.
7.17.00
7.17.01
7.17.02
The Engineer shall arrange for joint inspection of the installation for
completeness and correctness of the work. Any defect pointed out
during such inspection shall be promptly rectified by the Contractor.
7.17.03
7.17.04
8.00.00
TESTS
8.01.00
Shop Tests
8.01.01
8.01.02
b)
c)
Operational tests.
8.02.00
Site Tests
8.02.01
Contractor shall thoroughly test and meggar all cables, wires and
equipment to prove that the same are free from ground and short
circuit.
8.02.02
8.02.03
8.02.04
8.02.05
8.02.06
A test shall be made to ensure that earth pins of socket outlets are
connected to the earth wire or sheath of the cable to which the
socket outlet is connected.
8.02.07
A test shall be made to ensure that all socket outlets are connected
with the positioning of the phase, neutral and earth contacts in order
as detailed in the appropriate standards.
8.03.00
Test Witness
8.03.01
8.03.02
The Contractor shall give at least thirty (30) days advance notice of
shop tests and seven (7) days advance notice of site tests.
8.04.00
Test Certificates
a)
b)
c)
9.00.00
9.01.00
9.02.01
9.02.02
b)
c)
9.02.03
9.02.04
9.03.00
9.03.01
b)
c)
d)
e)
g)
h) Portable emergency lights.
h)
9.03.02
9.03.03
9.03.04
9.03.05
9.03.06
Key Single Line Diagram for lighting distribution, board wise single
line diagram with feeder loading, cable schedule and interconnection
chart, design calculation for lighting.
9.03.07
Cable Schedule.
9.03.08
9.03.09
9.03.10
The Bidder may note that the drawings, data and manuals listed are
minimum requirement only. The Bidder shall ensure that all other
necessary write-ups, curves and information required to fully
describe the equipment offered are submitted with his bi
ANNEXURE-A
JOB NO :
AVAILABLE POWER SUPPLY
1.0
System Voltage
1.1
A.C. Supply
3 phase, 50 Hz,
grounded system.
wire
effectively
D.C. Supply
2.0
2.1
Permissible Variation
:Equipment and
accessories shall be suitable for operation
over the entire range of voltage /
frequency variations as listed below :
A.C. Supply
Voltage 10%
Frequency 5%
Combined
Voltage+ Frequency 10% (absolute sum)
D.C. Supply
25
ANNEXURE-B
JOB NO :
BROAD LIST OF AREAS TO BE ILLUMINATED
Purpose of this list is to give general guidance on major areas to be illuminated.
The list is however not exhaustive. Scope of illumination has been marked in Dwg.
No. All areas / buildings listed may not be in the scope of civil works of the Main
Plant Contractor; but the responsibility for provision of illumination of all the areas
indicated in Dwg. shall lie with the Main Plant Contractor. Illumination engineering
shall be done by the Main Plant Contractor based on the detail layout developed
for rooms / areas during detail engineering and considering the guidance provided
in Lighting Notes & Details Drawing No.:
1.
2.
3.
5.
6.
7.
8.
ANNEXURE-B
JOB NO :
27
ANNEXUREC
JOB NO :
TYPES OF LIGHTING FIXTURE
Lighting fixture shall be furnished complete with associated lamp and
integral control gear fully wired-up. Control gear shall include ballast,
starter, capacitor, electronic ignitor, connector block etc.
Sl. No.
Type
Description
1.1
1.2
CA
1.3
DA
1.4
DB
1.5
EB
1.6
ANNEXUREC
JOB NO :
Sl. No.
Type
Description
1.7
1.8
1.9
1.10
1.11
LA
1.12
LB
1.13
MA
ANNEXUREC
JOB NO :
Sl. No.
Type
Description
terminal block, electrochemically brightened
anodised reflector, pendant mounting.
and
1.14
MC
1.15
1.16
PA
1.17
PB
1.18
PC
2.0
2.1
ANNEXUREC
JOB NO :
Sl. No.
Type
Description
outgoing feeders.
2.2
2.3
2.4
LP-2
2.5
LP-3
2.6
SLP
2.7
DCELP
2.8
FLP
3.0
3.1
RECEPTACLE
RA
ANNEXUREC
JOB NO :
Sl. No.
Type
Description
type.
3.2
RB
3.3
RC
3.4
RD
4.0
CEILING FANS
4.1
FA
4.2
FB
5.0
5.1
TA/TB
5.2
TC
6.0
SWITCHBOARD
6.1
S-1
6.2
S-2
6.3
S-3
ANNEXUREC
JOB NO :
Sl. No.
7.0
7.4
Type
Description
MISCELLANEOUS ITEMS
7.1
M1
7.2
M2
7.3
M3
M4
ANNEXURED
JOB NO :
ILLUMINATION LEVEL
Sl. No.
1.
2.
3.
Location
Lux Level
400
300
G and A
300
4.
Turbine Hall
MB and A
300
5.
DA/DB
200
Power House
LBandPA/PB
7.
8.
9.
10.
DA/DB and A
DA/DB
DA/DB
11.
200
200
DA/DB and A
Battery Rooms
250
200
100
H and B
DA/DB
200
DA/DB
200
DA/DB
200
Sl. No.
Location
16.
AHU Room
DA/DB
200
17.
DA/DB
200
18.
H and B
250
H and B
250
19.
200
Lux Level
ANNEXURED
JOB NO :
(with false ceiling)
20.
300
21.
22.
150
Chemical laboratory
DA and A
23.
100
LA/LB
24.
100
Power
conveyor floor
25.
100
26.
100
28.
MC
Boiler Area
Boiler Platforms
ESP hopper area, platforms
and ESP top
LA/LB
100
30.
100
31.
250
32.
70
Coal
MC
100
29.
House
MC
towers
27.
100
50
LA/LB
H and B
DA/DB
and/or
LA
ANNEXURED
Sl. No.
33.
70
Location
Level
JOB NO :
Lighting Fixture Type
Lux
LB/CB
34.
Ash Silo
LA/LB
100
35.
MB or MC *
250
36.
MB or MC *
250
37.
38.
N/I
39.
250
250
20
ceiling)
40.
Office Room
(with false ceiling)
250
Medium bay fixtures shall be used where the room height is 8 M. Otherwise
high bay fixtures are to be used.
Lux level for A.C. Emergency lighting in control room shall be 50 and for
other areas 20 lux.
ANNEXURE-E
JOB NO :
RATINGS AND REQUIREMENTS
OF
LIGHTING TRANSFORMER
Type
KVA rating
Voltage rating
Cooling
P.V. Impedance
Voltage control
Vector Group
Class of Insulation
The secondary neutral of the transformer shall be brought out for getting a
grounded 4-wire supply. Each transformer shall be routine tested and one
transformer shall be type tested in accordance with relevant standard.
The transformer shall be liable for rejection if the tolerance on the quoted values
of losses, impedance, temperature rise, etc. exceeds the specified values of
relevant standard.
The transformer shall be mounted inside sheet steel enclosure, which shall be an
integral part of Lighting Distribution Board.
ANNEXURE- F
JOB NO :
FITTINGS AND ACCESSORIES
OF
LIGHTING TRANSFORMER
Each transformer shall be equipped with fittings and accessories as listed below :
1.
2.
Handling and lifting lugs both for enclosure and core-coil assembly.
3.
4.
5.
Door handle operated safety limit switch with 1NO + 1NC contact.
6.
Ground bus.
7.
8.
Note
All indication, alarm, trip contacts provided shall be rated for 0.5A at 220 V D.C.
and 5A at 240 V A.C.