SYMPHONI SERIES OF LOOP POWERED SOUNDERS AND SOUNDER-BEACONS PRODUCT APPLICATION & DESIGN INFORMATION

INDOOR SOUNDER

OUTDOOR SOUNDER-BEACON

Fig. 1

1.

INTRODUCTION

2.
2.1

TECHNICAL SPECIFICATION
MECHANICAL CHARACTERISTICS
See Fig. 2 228g 310g 218g 300g ABS FR ABS/PC FR White 21-0302 Red 21-0301 50mm or 60mm Besa box or surface mount

The Symphoni Series of Loop Powered Addressable Sounder/ Sounder-Beacons are designed to be driven from an MX controller via the addressable loop. The Symphoni Series of sounders/sounder beacons consist: LPSY800-R LPSY800-W LPSY865 LPAV800-R LPAV800-W LPAV865 Sounder (indoor use) - red housing Sounder (indoor use) - white housing Sounder IP65 (outdoor use) - red housing Sounder-Beacon (indoor use) - red housing Sounder-Beacon (indoor use) - white housing Sounder-Beacon IP65 (outdoor use) - red housing

Dimensions:

Weight: Sounder Indoor: Sounder Outdoor: Sounder-Beacon Indoor: Sounder-Beacon Outdoor: Materials: Indoor: Outdoor: Colour: Mounting Requirements:

The sounder has two volume settings High (103dB 3) or Low (90dB 3). The beacon has two flash rates Slow Flash (1/2Hz) or Fast Flash (1Hz). The Symphoni devices are synchronised, but not synchronous with other MX sounders (801SB/802SB/SNM800) and beacons (SAB800/SAB801). The first flash of the beacon is synchronised with the start of the tone. The Symphoni devices have a built in two port isolator.

The indoor back box has to two drill positions (on the bottom) for gland holes. The outdoor back box has 3 drill positions (top and bottom) for gland holes. The indoor sounder/indoor sounder beacon body clips onto the backbox and can only be removed by the use of a special key. The backbox of the outdoor sounder /outdoor sounder beacon is secured to the mounting surface using the four fixing centers shown in Fig. 2. The Symphoni device is then secured to the backbox by four allan key screws. PAGE 1 of 10

2011 Tyco Safety Products


Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire

SG6 1BE

800 SERIES
17A-02-SYM
3 6/11
INDOOR SOUNDER

DRILL POSITION FOR GLANDS 108

108

96 60

OUTDOOR SOUNDER

FIXING CENTERS

50

110

105

96.5

INDOOR SOUNDER/BEACON

74.5

50

DRILL POSITIONS FOR GLANDS TOP AND BOTTOM

106

DRILL POSITION FOR GLANDS

105

91 60

OUTDOOR SOUNDER/BEACON

FIXING CENTERS

50

110

100

96.5

Fig. 2

Sounder and Sounder-Beacon - Overall and Fixing Dimensions

PAGE 2 of 10

74.5

50

DRILL POSITIONS FOR GLANDS TOP AND BOTTOM

110

EQUIPMENT: PUBLICATION: ISSUE No. & DATE:

800 SERIES
17A-02-SYM
3 6/11

2.2

ENVIRONMENTAL CHARACTERISTICS
Indoor -10C to +55C -25C to +70C Outdoor -20C to +70C -25C to +70C

2.3

ELECTRICAL CHARACTERISTICS
20 - 40Vdc 450A

Addressable Loop Voltage: DC Loop Loading Quiescent:

Temperature: Operating: Storage: Humidity: Pressure: Vibration: Corrosion:

Up to 95% RH (non-condensing) Sounder output is quoted for atmospheric pressure of 1000mBar. Meets the requirements of EN 54-3. passes the SO2 corrosion test from EN 54-3.

Alarm: Sounder: Low Volume 3.4mA Sounder: High Volume 8.5mA Sounder + Beacon: Slow Flash + Low Volume 6.5mA Sounder + Beacon: Fast Flash + Low Volume 7.6mA Sounder + Beacon: Slow Flash + High Volume 11.1mA Sounder + Beacon: Fast Flash + High Volume 13mA Isolator Maximum Loop Voltage: Minimum Loop Voltage: Maximum Rated Continuous Current (Isolator Closed): Maximum Rated Switching Current (s/c): Maximum Leakage Current (Isolator Open): Maximum Series Impedance (Isolator Closed): Isolator Switching Threshold (Isolator Closed to Open): 40Vdc 19Vdc

EMC: The Symphoni devices comply with the following: Product family standard EN50130-4 in respect of Conducted Disturbances, Radiated Immunity, Electrostatic Discharge, Fast Transients and Slow High Energy EN61000-6-3 for Emissions IP Rating: Indoor: Outdoor: IP21C (EN 60529) IP65 (EN54-3 approved to IP33C)

2A 2A 6mA into zone (10mA into Isolator) 0.25 19V or below 3.3V from s/c

Sound Performance SPL @ 1m: 103dB 3 (high volume) 90dB 3 (low volume) Note: Performance at 90 at a distance of 1m not tested by VdS when approving the DIN 1Hz sweep tone. Sound Dispersion: Horizontal: Pole Mounted: Light Performance Flash Power/Light Output: 2 candela minimum on axis, spacial distribution 60 @ 1.5cd Flash Rate /s: Fast Flash 1Hz or Slow Flash 1/2Hz Synchronisation: 30ms in 30 minutes maximum >90% over 90 (45 from axis) >80% over 360 (from axis)

Isolator Switching Threshold (Isolator Open to Closed):

2.4

SOUNDER TONES

Table 1 details the tones available for selection in MX Consys. (Future use expandable to 32 tones). 2.4.1 APPROVED TONES

The following tones are approved by LPCB to the specifications as shown in Tables 2 to 5. The DIN 1Hz Sweep tone is approved by VdS to the specification as shown in Tables 6 and 7. The data applies to both horizontal and vertical planes.

2011 Tyco Safety Products


Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire

PAGE 3 of 10
SG6 1BE

800 SERIES
17A-02-SYM
3 6/11
Monitored (High 103db Frequency and Low Name Pattern Rate (Hz) 90db-No pulsing in Consys) Dutch Slow Whoop Sweep 500 to 1200 500Hz rising to 1200Hz over 3.5s Yes silence 0.5s repeat 7Hz Fast Sweep Sweep 800 to 970 0.1428s ramp 7Hz Yes BS 1Hz Sweep Sweep 800 to 970 1Hz Yes 2 Tone Alternating 660/880 500ms per tone Yes Temporal 4 Intermittent 880 500ms on 500ms off x 4 followed Yes by 1.5s silence Temporal 3 Intermittent 880 500ms on 500ms off x 3 followed Yes by 1.5s silence March Time Beep Intermittent 880 500ms on 500ms off Yes Continuous 970 Continuous 970 Steady Yes Continuous 850 Continuous 850 Steady Yes DIN 1 Hz Sweep Sweep 1200 to 500 1200Hz falling to 500Hz over 1s Yes and repeat Banshee LF Buzzer Sweep 800 to 950 120Hz Yes 3Hz Banshee Fast Sweep 800 to 950 3 Hz Yes Sweep 9Hz Banshee Fast Sweep 800 to 950 9Hz Yes Sweep Alternating Alternating 554/440 554Hz for 100ms and 440Hz for Yes 400ms Yodalarm Alternating 800 / 1000 250ms for each frequency Yes Conventional Bell Continuous 1450 Steady Yes (Note1) Tone Description Monitored with Pulse Pattern Assigned in Consys No No No No No No No No No No No No No No No No

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Table. 1 Sounder Tones Note1 This is a simulated bell tone with a limited bandwidth. It is not advisable to mix conventional bells and electronic sounders producing a simulated bell tone.

PAGE 4 of 10

Device Mode

EQUIPMENT: PUBLICATION: ISSUE No. & DATE: Operational Performance Maximum Volume dB(A) Angle 40V 20V 15 84.0 83.0 93.9 92.5 45 75 96.3 95.1 96.2 94.8 105 93.1 92.1 135 165 82 81.8 Table. 2 Continuous 850Hz Operational Performance Maximum Volume dB(A) Angle 40V 20V 15 85.4 84.4 95.2 94.2 45 75 97.7 96.3 97.0 95.8 105 94.0 93.3 135 165 84.9 84.1 Table. 3 Dutch Slow Whoop 500Hz to 1200Hz Operational Performance Maximum Volume dB(A) 40V 20V 84.2 83.4 94.3 93.7 97.3 96.0 96.7 95.5 93.9 93.2 84.6 83.8 Table. 4 7Hz Fast Sweep

800 SERIES
17A-02-SYM
3 6/11

Operational Performance Maximum Volume dB(A) Angle 40V 20V 89.4 88.5 15 45 93.9 93.0 98.0 96.7 75 105 100.0 98.8 96.3 95.3 135 88.1 87.3 165 Table. 6 DIN 1Hz Sweep - High Volume Operational Performance Low Volume dB(A) Angle 40V 20V 15 79.2 78.3 84.5 83.5 45 75 89.7 88.8 91.3 90.5 105 87.1 86.2 135 165 78.5 77.4 Table. 7 DIN 1Hz Sweep - Low Volume

2.5

ADDRESS PROGRAMMING

Angle 15 45 75 105 135 165

Operational Performance Maximum Volume dB(A) Angle 40V 20V 81.2 79.7 15 92.8 91.0 45 95.0 94.3 75 105 94.4 93.6 92.0 90.9 135 81.2 80.9 165 Table. 5 Temporal 3 880Hz

PROGRAMMING PORT

Fig. 3

Symphoni Programming Port

The Symphoni devices have a default factory set address of 255, this must be set to the loop address of the device using the 801AP MX Service Tool. The sounder is programmed with the address prior to being installed by using the internal

2011 Tyco Safety Products


Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire

PAGE 5 of 10
SG6 1BE

800 SERIES
17A-02-SYM
3 6/11
Technical Publications of the relevant Control and Indicating equipment. programming port (see Fig. 3). The Symphoni Sounder-Beacons use 2 consecutive addresses on the MX addressable loop, starting from the chosen programmed address number. These addresses are automatically generated when a Symphoni Sounder-Beacon is selected in MX Consys. The address configuration is as follows: Address n n+1 Type Sounder Device Beacon Device
L00P IN MONITOR MX SYMPHONI MONITOR LOOP OUT

2.9
+VE

ISOLATOR OPERATION
+VE

2.6

SYMPHONI CONFIGURATION
-VE -VE

Sounder tone (Device Mode), sounder volume output (Sensitivity) and beacon flash rate (Device Mode) are configured in MX Consys. Note: It is not possible to select different tones for different Symphoni devices connected to the MX panel. For system loading, refer to Publication 17A-02-LOOP System Loading Guidelines. 2.6.1 BELL MAPPING

Fig. 4

Simplified Isolator Diagram

The built-in isolator serves as a protection device against short circuits. It operates by isolating the section of line containing the short circuit from devices on the line and from the rest of the line (refer to Fig. 4). Optimum operation requires the line to be wired as a loop, so that a section of line with a short circuit can be isolated between a pair of isolator devices (including MX Symphoni devices). In order to enable the isolators use in a looped circuit, it is capable of passing current in both directions (Loop IN to Loop OUT or Loop OUT to Loop IN). In the event of a line short circuit, the line isolator continues to power its associated MX Symphoni Sounder or Sounder-Beacon, providing that either Loop IN or Loop OUT remains intact. When a short circuit develops, the adjacent isolator devices will isolate both sides of the loop from the faulty device/cable. The operation of the MX loop driver means that there are effectively 2 operational modes for the built-in isolator. i) When the loop is first powered, if a section of the line appears as a low impedance (with an equivalent resistance of <400), the isolator will restrict the power to that section of line until the fault is cleared. ii) If a short circuit is introduced onto the line when the loop is already powered up, in most instances the controllers internal protection will switch in before the line isolator. The voltage is then removed from the line by the controller, on restoration, the isolator devices will isolate the low impedance section of the line.

If it is required for the sounder to operate as a Bell Map output, then the Group to which the device belongs must be put into the Bell Map Outputs Supergroup. To achieve this, select group 50 Bell Map Output SG and then select "Edit Members". Use "Add member" to include the Points group into the Bell Map Output SG. If the sounder base needs including in any sounder Walk Test, then super group number 51 "Sounders to walktest SG", will have to be edited to add the point's group to the list of supergroup members. For the beacon to be included as a visual output controlled by the Bell Map, the points group needs to be included in Bell Map Visuals SG, 58.

2.7

OUTPUT PULSE PATTERN

Output pulse patterns are restricted such that the period between every High to Low transition and the following Low to High transition is a multiple of 2 seconds. Pulse patterns are also restricted to continuous tone patterns only.

2.8

FAULT MONITORING

Both the sounder and beacon are monitored. The last 2 columns of Table 1, Sounder Tones, on page 4 define if the sounder is monitored, as a function of volume setting and system configuration. Sounder Monitoring is also referred to as Reflective Sound Monitoring (RSM). For further details on the application of this function, refer to the PAGE 6 of 10

EQUIPMENT: PUBLICATION: ISSUE No. & DATE:

800 SERIES
17A-02-SYM
3 6/11

3.

CABLING

Cables are to be selected in accordance with Publication 17A-02-D1 and the requirements of the current issue of BS5839. Cabling should be connected as shown in Fig. 5, ensuring correct polarity. Each terminal connection will accept wire size up to 2.5mm2 (MICC or similar). Note: Couplers are to be used with MICC cable. Suitable glands must be used with the outdoor device to keep the IP65 rating.

0832 Tyco Safety Products Dunhams Lane Letchworth SG6 1BE UK 07 0832-CPD-0572

4.

CPD INFORMATION

EN 54-3: 2001 + A1: 2002 EN 54-17: 2005 Symphoni MX Addressable loop powered Type B sounder for use in fire detection and alarm systems for buildings

0832 LPSY865 Tyco Safety Products Dunhams Lane Letchworth SG6 1BE UK 07 0832-CPD-0571 EN 54-3: 2001 + A1: 2002 EN 54-17: 2005 Symphoni MX Addressable loop powered Type A sounder for use in fire detection and alarm systems for buildings LPSY800-R LPSY800-W Installation Instructions 25-8320 Service Instructions 17A-04-S Installation Instructions 25-8320 Service Instructions 17A-04-S

2011 Tyco Safety Products


Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire

PAGE 7 of 10
SG6 1BE

800 SERIES
17A-02-SYM
3 6/11

0832 Tyco Safety Products Dunhams Lane Letchworth SG6 1BE UK 07 0832-CPD-0573 EN 54-3: 2001 + A1: 2002 EN 54-17: 2005 Symphoni MX Addressable loop powered Type A sounder beacon for use in fire detection and alarm systems for buildings LPAV800-R LPAV800-W Installation Instructions 25-8320 Service Instructions 17A-04-S

0832 Tyco Safety Products Dunhams Lane Letchworth SG6 1BE UK 07 0832-CPD-0574 EN 54-3: 2001 + A1: 2002 EN 54-17: 2005 Symphoni MX Addressable loop powered Type B sounder beacon for use in fire detection and alarm systems for buildings LPAV865 Installation Instructions 25-8320 Service Instructions 17A-04-S

5.

ORDERING INFORMATION
516.800.960 516.800.961 516.800.962 516.800.963 516.800.964 516.800.965

LPSY800-R Sounder (indoor use) - red housing: LPSY800-W Sounder (indoor use) - white housing: LPSY865 Sounder IP65 (outdoor use) - red housing: LPAV800-R Sounder-Beacon (indoor use) - red housing: LPAV800-W Sounder-Beacon (indoor use) - white housing: LPAV865 Sounder-Beacon IP65 (outdoor use) - red housing:

PAGE 8 of 10

EQUIPMENT: PUBLICATION: ISSUE No. & DATE:

800 SERIES
17A-02-SYM
3 6/11

-VE +VE

+VE L1 -VE R MX CONTROLLER IN OUT IN SCREEN OUT IN OUT L L2 R L L2 L1

LOOP LOOP +VE -VE

801RIL REMOTE INDICATOR

Fig. 5

Simplified Wiring Diagram

2011 Tyco Safety Products


Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire

PAGE 9 of 10
SG6 1BE

800 SERIES
17A-02-SYM
3 6/11

PAGE 10 of 10