SECTION 16110 RACEWAYS

ENGG

SUBSECTION INDEX
DESCRIPTION

Part 1 - General 1.01 1.02 1.03 1.04 1.05 Work Included Related Work Reference Standards Quality Assurance Submittals

DATE JOB/EWO

Part 2 - Products 2.01 2.02 Acceptable Manufacturers Materials and Fabrication

REV. NO.

Part 3 - Execution 3.01 3.02 3.03 Inspection Preparation Installation

DISCIPLINE ENGINEER

__ ________ _ DATE: ________

PROJECT ENGINEER
____________ DATE

PART 1 - GENERAL 1.01 Work Included A. B. C. D. E.


Date:

CERTIFIED _ __________
DATE: ________

Rigid Steel Conduits PVC Coated Rigid Steel Conduits PVC Ducts Flexible Couplings Electrical Metallic Tubing (EMT Conduits) Liquid-tight Flexible Metallic Conduit Cable Trays. Fittings I. Supports
DWG. TYPE PLANT NO. INDEX DRAWING NO.

CONSTRUCTION AGENCY
________________ DATE:

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

F. G. H.

SECTION 16110
SHT. NO. REV. NO.

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

1 OF 10

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

PMT

1.02

Related Work A. B. Section 16120 Wires and Cables, Low Voltage Section 16130 - Boxes

ENGG

CERT

1.03
DESCRIPTION

Reference Standards A. Saudi Aramco Engineering Standard (SAES): 1. B. C. SAES-P-104 Wiring Methods and Materials.

Underwriter Laboratory (UL). National Electrical Code (NEC): 1. 2. NEC, Article 300 - Wiring Methods and Materials. NEC, Article 500 - Hazardous (Classified) Locations.

DATE JOB/EWO

REV. NO.

D. E.

National Electrical Manufacturer Association (NEMA): Applicable Listings. American Society for Testing Materials (ASTM).

DISCIPLINE ENGINEER

__ ________ _ DATE: ________

1.04

Quality Assurance A. Conduits and fittings shall be UL listed or approved equal.

PROJECT ENGINEER
____________ DATE

1.05

Submittals A. B. C. D. Shop drawings showing exact routings, coordinated with other trades. Brochures and manufacturers technical Specifications. Samples. Compliances with the specified or approved standards.

CERTIFIED _ __________
DATE: ________

CONSTRUCTION AGENCY
________________ DATE:

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

Date:

SECTION 16110

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DWG. TYPE PLANT NO. INDEX

DRAWING NO.

SHT. NO. REV. NO.

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

2 OF 10

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

PMT

PART 2 - PRODUCTS 2.01 Acceptable Manufacturers A. PVC Conduits and Fittings: 1. Sappco (Saudi Arabia). Fabco (Saudi Arabia). Triangle conduit and cable Company, Inc., New Brunswick, NJ. Carlon Electrical Sciences, Inc., Clevelard, OH. Saudi Ega MK Cable Management (Saudi Arabia) Or approved equal manufacturers.

ENGG

CERT

DESCRIPTION

2. 3. 4. 5.

DATE JOB/EWO

6. B.

Steel Conduits, Electrical Metallic Tubing and Fittings: 1. 2. 0-Z/Gedney (U.S.A.). Triangle PWC, Inc. (U.S.A.). Perma-Cote Industries (U.S.A.). Saudi Steel Pipe (Saudi Arabia). Wheatland (U.S.A.) Approved equal manufacturers.

REV. NO.

DISCIPLINE ENGINEER

__ ________ _ DATE: ________

3. 4. 5. 6. C.

PROJECT ENGINEER
____________ DATE

CERTIFIED _ __________
DATE: ________

Flexible Coupling: 1. 2. Crouse Hinds (U.S.A.). Approved equal manufacturer's.

CONSTRUCTION AGENCY
________________ DATE:

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

D.

Supports: 1. Abahsain - Cope (K.S.A.). WESCOSA - COPE (K.S.A.). Approved equal manufacturers.

Date:

2. 3. 2.02

Materials and Fabrication A. General:


DWG. TYPE PLANT NO. INDEX DRAWING NO.

SECTION 16110
SHT. NO. REV. NO.

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

3 OF 10

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
1. All conduits and accessories shall be completely free from rust or other defects and have same finish throughout the installations. Conduits & fittings shall be as per NEC chapter 5 hazardous locations Only standard manufacturer types of conduits/fittings shall be used.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

CERT

PMT

ENGG

2.

3.
DESCRIPTION

B.

Rigid Steel Conduits (RSC): 1. Conduits shall conform to NEC Article 344 not less than 1 inch (20 mm) diameter. Conduits shall be hot dipped galvanized, complying with ANSI C80.1. The steel shall be galvanized after cutting and threading. All saddles for surface mounted installation of RSC shall be of the spacer bar type with same finish as the conduits. A tapped earth connection facility shall be provided in every box. All bends shall be cold set made using circular tee conduit boxes. Provide with a coupling, adapters, junction boxes, bushings, connectors, elbows, expansion joints, gaskets, hubs, locknuts, plugs etc.

2.
DATE JOB/EWO

3.

REV. NO.

4. 5.

DISCIPLINE ENGINEER

__ ________ _ DATE: ________

6.

PROJECT ENGINEER
____________ DATE

C.

PVC Coated Rigid Steel Conduits 1. Conduits shall comprise a permanently bonded PVC barrier of corrosion protection to galvanized rigid steel. The coating shall be bonded PVC applied to conduit which has been treated with an epoxy primer to ensure a permanent bond with plastic. The coating shall be continuous, except for the threads and shall be free of flaws. The adhesive strength of the bonding shall be equal to or greater than the tensile strength of the coating. PVC coating shall be a 1 mm (40 mil.) bonded coat per NEMA RN1 (Type A).

CERTIFIED _ __________
DATE: ________

CONSTRUCTION AGENCY
________________ DATE:

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

2.

3.
Date:

D.

PVC Conduits: 1. PVC conduits shall be rigid, heavy gauge, Schedule 40 conforming to industry NEMA standard TC-2, UL-651, SASO and NFPA-70 in all respects.
SECTION 16110

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DWG. TYPE PLANT NO. INDEX

DRAWING NO.

SHT. NO. REV. NO.

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

4 OF 10

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
2. All PVC conduits fittings and accessories shall be obtained from the same manufacturer approved and equal under Project Manufacturers List. No conduit shall be less than (20 mm) inch diameter. Fittings and accessories for PVC conduits shall include, but not be limited to, the adapters, junction/pull boxes, bushings, couplings, elbows, nipples, plugs, seals, etc. All connections and terminations of the PVC conduits and fittings shall be by means of the manufacturers standard adaptor. All boxes shall have brass thread inserts for the fixing of accessories or covers. All saddles shall be of the spacer bar type and from the same manufacturer approved and equal under Project Manufacturers List, as that of the conduit which they are being used to secure.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

ENGG

CERT

PMT

3. 4.

DESCRIPTION

5.

6.

DATE JOB/EWO

7.

REV. NO.

E.

Flexible Couplings: 1. Flexible couplings for vibrating equipment in hazardous areas shall be crouse hinds type ECLK or equal. Flexible couplings shall conform to NEC Article 360.

DISCIPLINE ENGINEER

__ ________ _ DATE: ________

2. F.

PROJECT ENGINEER
____________ DATE

Electrical Metallic Tubing (EMT) Conduits: 1. 2. Conduits shall conform to NEC, Article 358. Conduit shall comply with the requirements of ANSI C80.3.

CERTIFIED _ __________
DATE: ________

CONSTRUCTION AGENCY
________________ DATE:

G.

Liquid Tight Flexible Metallic Conduit: 1. Conduits shall be constructed from galvanized steel core and continuous liquid-tight PVC jacket. Conduits shall conform to NEC 350 not less than 3/4 (20 mm) diameter. All flexible conduits shall be liquid-tight and shall comply with UL1 and shall have a PVC jacket capable of withstanding 194 deg.F (90 deg.C) cable operations.

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

2.

3.
Date:

H.

Cable Trays: 1. Cable trays shall be trough type constructed from aluminum sheets comprising corrugated trough bottom welded to I-beam
DWG. TYPE PLANT NO. INDEX DRAWING NO.

SECTION 16110
SHT. NO. REV. NO.

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

5 OF 10

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
siderails, or one piece construction with no welding except at fittings. Bottom shall be louvered. All sharp edges shall be turned away from cable path. 2. Aluminum cable tray shall be designed, manufactured, rated, and tested in accordance with NEMA VE1. Method A (Loading to Destruction) shall be used for determining the rated load capacity. Minimum individual rung load capacity shall be 90 kg. Cable trays shall be installed as a complete system. Cable tray systems shall not have mechanically discontinuous segments of cable tray runs.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

DESCRIPTION

ENGG

CERT

PMT

3.

I.

Fittings: 1. Fittings shall include but not be limited to adapters, bushings, connectors, couplings, elbows, expansion joints, gaskets, hubs, lock-nuts, nipples, plugs, seals, unions and breathers. Fittings for all metallic conduits shall be of malleable iron or a mixture of gray iron and cast steel. Fittings for rigid steel conduit shall be threaded, hot-dipped galvanized. End fittings and unions for flexible couplings shall be of forged brass and feraloy or steel. Fittings for liquid-tight flexible steel conduits shall be nylon jacketed.

DATE JOB/EWO

2.

REV. NO.

3.
DISCIPLINE ENGINEER

__ ________ _ DATE: ________

4.

PROJECT ENGINEER
____________ DATE

5.

CERTIFIED _ __________
DATE: ________

J.

Supports: 1. Channels shall be fabricated from structural steel in 12, 14 or 16 gauge as required. Steel fittings shall be die formed from hotrolled steel of structural quality. An epoxy resin paint shall be bonded to the metal by an approved method such as cathodic negatively charged electro deposition process. Materials and finishes shall meet ASTM specifications and NEMA standards for metal framing. All other supports and accessories shall be fabricated for the application, such as concrete inserts, hangers, straps, clamps, anchors, bolts, screws, etc., and shall be hot dipped galvanized malleable iron.
SECTION 16110

CONSTRUCTION AGENCY
________________ DATE:

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

2.

3.
Date:

4.

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DWG. TYPE PLANT NO. INDEX

DRAWING NO.

SHT. NO. REV. NO.

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

6 OF 10

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

PMT

CERT

PART 3 - EXECUTION 3.01 Inspection A. Conduits and fittings shall be free from objectionable lines, striations, bubbles, welds, and other manufacturing defects that would impair the service of the conduit. The bore of the conduit shall be circular in crosssection with smooth interior surfaces free from rough and flaky areas. The conduits and fittings shall be free from all substances that injuriously effect any wire or cable covering.

DESCRIPTION

ENGG

3.02

Preparation A. Cut and Threads: 1. 2. All cut ends of conduits shall be reamed to remove rough edges. All field threads shall be full and continuous. Field threads shall be of the same lengths as a factory cut thread of a similar sized conduit. Threads shall be field cut using a standard conduit cutting die with a 62 mm per meter (3/4 in.) taper per ft. Raw threads should be protected with CRC "Zinc-It" or equal. Running threads are not permitted for any applications. A minimum engagement of five full threads shall be made at all fittings.

REV. NO.

DATE JOB/EWO

DISCIPLINE ENGINEER

__ ________ _ DATE: ________

3. 4.

PROJECT ENGINEER
____________ DATE

CERTIFIED _ __________
DATE: ________

B.

Field Bends: 1. Field bends may be made with a hand bender on 38 mm (1-1/2 in.) and smaller conduits only. Larger size conduit shall be bend with a machine bender or be factory supplied. Heating of metal conduit to facilitate bending is not permitted. All bends shall be made so that the conduit is not injured, and so that the internal diameter of the conduit will not be effectively reduced. 3. The inner edge radius of all field bends shall not be less than shown in the following table:

CONSTRUCTION AGENCY
________________ DATE:

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

2.

Date:

Minimum Radius of Conduit Field Bends Nominal Size Of Conduit (inches)


CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &
DWG. TYPE PLANT NO. INDEX DRAWING NO.

Minimum Bending Radius Hand Bender Bending Machine


SECTION 16110
SHT. NO. REV. NO.

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

7 OF 10

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
mm 12 20 25 30 38 50 63 75 88 100 112 in. 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4 4-1/2 5 6 mm 100 125 150 200 250 in. 4 5 6 8 10 mm 100 115 145 185 210 240 270 330 380 410 510 610 760 in. 4 4-1/2 5-3/4 7-1/4 8-1/4 9-1/2 10-1/2 13 15 16 20 24 30
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

DESCRIPTION

ENGG

CERT

PMT

DATE JOB/EWO

125 150

REV. NO.

4.

DISCIPLINE ENGINEER

No more than four quarter bends (360o total) shall be made in one run between outlets, fittings or outlet bodies including any bends located immediately at the outlet, fitting, or outlet body. Notice should be taken of the minimum bending radii of all cables before specifying the bending radius of a conduit bend. Minimum bending radii shall be as recommended by the cable manufacturer.

__ ________ _ DATE: ________

5.

PROJECT ENGINEER
____________ DATE

CERTIFIED _ __________
DATE: ________

C.

Allowable Conduit Fill: Conduit shall be sized to conform requirements of fill in accordance with NEC Chapter 9, Table 1. Maximum conduit runs: Conduit runs shall be such that maximum pulling tension does not exceed the allowable tension on the conductor, pulling device, sidewall pressure.

CONSTRUCTION AGENCY
________________ DATE:

D.

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

3.03

Installation A. All conduit runs are shown diagrammatically to outline general routing of conduits. Avoid interfering with pipes, ducts, structural members or other equipment. Deviations shall be made in accordance with Saudi Aramco instructions and at no extra cost to Saudi Aramco. Crushed or deformed conduits shall not be used. Conduit and fittings shall be installed in accordance with NEC.
SECTION 16110

Date:

B. C.

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DWG. TYPE PLANT NO. INDEX

DRAWING NO.

SHT. NO. REV. NO.

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

8 OF 10

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
D. PVC conduits shall be used only where cast into slabs, built or chased into walls etc. Where conduits are surface run in ceiling voids, shaft spaces, plant rooms etc. galvanized RSC or EMT shall be used. Adaptation between PVC and metal conduits shall be through metal boxes. Metal conduits either Rigid Steel Conduits (RSC) or Electrical Metallic Tubings (EMT) shall be installed in exposed locations as required. EMT shall be used inside buildings, generally above suspended ceiling, with the exceptions of below grade within the building structure or external underground or at exposed locations liable to be damaged mechanically. RSC shall be installed exposed on surface at all such locations where conduits are liable to be damaged mechanically. Protective bushings shall be provided on PVC coated steel horizontal stub outs and bells shall be provided on PVC horizontal stub outs. Verify exact stub up location and termination requirement for items and equipment being served, for all necessary power and control. Where conduits turn out of or penetrate a slab, they shall be not less than 65 mm on centers. Location and sizing of conduit sleeves passing through floors and walls that are not shown on the Drawings shall be the responsibility of the Contractor. All sleeves, unless otherwise noted, shall be rigid galvanized steel extended 150 mm above floor and capped when not in use. Space between conduits and sleeves shall be closed with duct-seal at a minimum 50 mm deep at top and bottom of conduit sleeve. Only watertight flexible conduits shall be used and shall conform to NEC Article 350 & 351. Last portion of connection to motors or other vibrating equipment shall be by a flexible conduit, connected to rigid conduit by connectors. Conduit fittings shall be used as required and matching the conduit system being used. Metallic conduits entering gasketed boxes or equipment enclosures shall be provided and terminated with gasketed hubs, with bonding screws. Conduits are not to cross pipes, vents or openings. Make holes for conduits passing through walls, floors and ceilings with approved filling fire resisting material to all thickness. Metallic conduits entering non-gasketed sheet-metal boxes or enclosures shall be provided and terminated with general purpose hubs.
DWG. TYPE PLANT NO. INDEX DRAWING NO.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

ENGG

CERT

PMT

E.

DESCRIPTION

F.

G.
DATE JOB/EWO

H.

REV. NO.

I.

DISCIPLINE ENGINEER

J.

__ ________ _ DATE: ________

PROJECT ENGINEER
____________ DATE

CERTIFIED _ __________
DATE: ________

K.

CONSTRUCTION AGENCY
________________ DATE:

L.

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By:

M.

N.

Date:

O. P.

Q.

SECTION 16110
SHT. NO. REV. NO.

CONSTRUCTION SPECIFICATIONS
KAUST TOWN CENTER RESIDENTIAL &

DOC

COMMUNITY SUPPORT BUILDINGS RABIGH SAUDI ARABIA

K55
JOB/EWO#

VE-417361 BI-25-00002

14-Sep-07

9 OF 10

00

Saudi Aramco 2616-ENG (3/99)


OPERNS.


SAUDI ARAMCO OIL COMPANY
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

PMT

ENGG

CERT

R.

Concealed conduits shall be installed such that only 2 cross at a given point, and be sufficiently within slab to prevent slab cracking. Supports shall be provided to alleviate stress on cables where they enter a conduit or other enclosure from the tray. Location of supports for cable tray systems shall be in accordance with the recommendations of NEMA VE2 or NEMA FG1. The maximum spacing between expansion joints shall be based on a temperature differential of 55oC (100oF) and expansion gap settings shall be in accordance with the recommendations of NEMA VE2 or NEMA FG1, based on a minimum temperature of 0oC and a maximum temperature of 55oC. Threads of metallic conduits shall be of sufficient length to allow conduits to butt together within couplers. Support all metal conduits every 10 ft (3 inches). Pull boxes shall be provided in conduits not exceeding 3m in length. Pull boxes shall be used at maximum 12m spacing and shall be accessible at all times.

S.

T.
DESCRIPTION

U.

DATE JOB/EWO

V.

W. X.

REV. NO.

DISCIPLINE ENGINEER

__ ________ _ DATE: ________

PROJECT ENGINEER
____________ DATE

- END OF SECTION -

CERTIFIED _ __________
DATE: ________

CONSTRUCTION AGENCY
________________ DATE:

OPERATIONS
______________ DATE:_________ REVISION CERTIFICATION EDSD VERIFICATION THIS INDICATES THAT REV. NO.________ OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS,, CONTROL NUMBER BY DRAWING COMPLETION CERTIFICATE (DCC) NO.: __________________________ By: