30 minutes to perform a retrot of your Masterpact M

"Plug and Play" retrot solution

2009

Fast and easy implementation

Continuity of service guaranteed

Certied "Plug and Play" solution

"Plug and Play" retrot solution


This solution enables retrotting of Masterpact M devices with considerable reduction of on-site intervention time. The existing Masterpact M chassis is retained. Busbar and cable connections are not disturbed, only the circuit concerned needs to be isolated (for as little as 30 minutes*).
The original Masterpact M chassis is kept (no intervention on the switchboard structure)

Masterpact NW adapted for the "Plug and Play" solution

Masterpact M

Circuit breaker Original device M08 3P/4P M10 3P/4P M12 3P/4P M16 3P/4P M20 3P/4P M25 3P/4P M32 3P/4P
: Standard offer

Switch-disconnector H2 NI HI HF

N1

H1

Consult us for all devices not included in the standard offer. The STR control units (except for communication units) are replaced by the corresponding Micrologic control units according to the speci cation of the existing STR.

Fast and simple implementation which keeps the original chassis

30

* Typical time for simple installations.

minutes* and

easy operations

The factory-modied and adapted "Plug and Play" Masterpact NW is designed for installation in the original Masterpact M chassis. On-site implementation is very simple:

Replacement of original racks

Wire guide support replacement

Two new racks are installed in place of the original racks in the Masterpact M chassis.

All Masterpact NW functions are pre-wired; ourtechnician has only to connect the functions required according to the accessories tted.

Chassis spare parts replacement warranty


With the "Plug and Play" retrot solution weguarantee the availability of spare parts for the Masterpact M chassis (plug-in clamps, shutter, wire guide support spring, auxiliary contacts).

High performance of the Masterpact NW


The monitoring and diagnostic functions (Micrologic control unit) of the MasterpactNW circuit breaker enables you to optimise the maintenance of your equipment. The electrical performance characteristics of the Masterpact NW offer equal or greater performance than Masterpact M (selectivity remains unchanged) in the event of a network fault.

Options
@ Mismatch Protection The mismatch protection ensures that a circuit breaker is installed only in a cradle with compatible characteristics. The kit can be ordered separately. @ Mechanical interlock Mechanical interlock of two or three buncked devices using connecting rods and 2 devices installed side by side using cables are available with the Plug&Play. The kit has to be ordered with the device.
Mechanical interlock using connecting rods for 2 or 3 buncked devices. Mechanical interlock using cable for 2 devices installed side by side.

"Plug and Play" retrot solution


The retrot solutions use a factory modied and adapted Masterpact NW which is installed in Masterpact Ms original chassis. Merchant Marine
"The Plug&Play is compliant with Merchant Marine standards. The breaking capacity test and the steady-state sinusoidal vibration tests in accordance with IACS rules and standard IEC 60068.2.6 have been successfully performed on a circuit breaker NW32H1 3 poles draw out version mounted in a chassis of Masterpact M32. The technical documents that show the results of the tests are available."

Standards
@ The "Plug and Play" retrot solutions keeps all Masterpact NW circuit breaker approvals. @ All specic parts are certied in compliance with the following standards: _ IEC 60947 - 1 _ IEC 60947 - 2 @ Conform to marine standards.

More environmentally friendly


@ Masterpact NW units use non-polluting and recyclable materials, and are manufactured in ISO 14001 certied factories. @ The environmental impact is minimised through eco-design.

Schneider Electric France


Projects and Engineering Center 38050 Grenoble Cedex 9 Tel.:+33 (0)4 76 57 60 60 http://www.schneider-electric.com As standards, specications and designs change from time to time, please ask for conrmation of the information given in this publication. This document has been printed on ecological paper. Design: Schneider Electric Photos: Schneider Electric Printed: SERED109001EN 04-2009

2009 - Schneider Electric - All rights reserved

Plug&Play Material List


Plug&Play Description
Plug and Play solution for Masterpact M 3phases
The circuit breaker is equiped with specific power connections

A special label to identify the retrofit circuit breaker.

Special racks for Masterpact NW

The housing is modified and adapted to be compatible with the Masterpact M chassis

Reference List
Existing Circuit Breaker M08H1 3P STR28D M10H1 3P STR28D M12H1 3P STR28D M16H1 3P STR28D M20H1 3P STR28D M25H1 3P STR28D M32H1 3P STR28D Plug&Play Solution P&P M08H1 3P by NW08H1 3P 5.0A P&P M10H1 3P by NW10H1 3P 5.0A P&P M12H1 3P by NW12H1 3P 5.0A P&P M16H1 3P by NW16H1 3P 5.0A P&P M20H1 3P by NW20H1 3P 5.0A P&P M25H1 3P by NW25H1 3P 5.0A P&P M32H1 3P by NW32H1 3P 5.0A Reference 93674 93680 93686 93692 93694 93698 93701

Functions and characteristics

Circuit breakers andswitch-disconnectors


NW08 to NW63

PB104423A35

Common characteristics
Number of poles Rated insulation voltage (V) Impulse withstand voltage (kV) Rated operational voltage (V AC 50/60 Hz) Suitability for isolation Degree of pollution Ui Uimp Ue IEC 60947-2 IEC 60664-1 3/4 1000/1250 12 690/1150 4 (1000 V) / 3 (1250 V)

Basic circuit-breaker
Circuit-breaker as per IEC 60947-2
Rated current (A) Rating of 4th pole (A) Sensor ratings (A)
PB104433A65

at 40 C / 50 C (1)

Type of circuit breaker Ultimate breaking capacity (kA rms) V AC 50/60 Hz

Icu

Rated service breaking capacity (kA rms) Utilisation category Rated short-time withstand current (kA rms) V AC 50/60 Hz Integrated instantaneous protection (kA peak 10 %) Rated making capacity (kA peak) V AC 50/60 Hz

Ics Icw

220/415/440 V 525 V 690 V 1150 V % Icu 1s 3s 220/415/440 V 525 V 690 V 1150 V

Icm

Break time (ms) between tripping order and arc extinction Closing time (ms)

Circuit-breaker as per NEMA AB1


Breaking capacity (kA) V AC 50/60 Hz 240/480 V 600 V

Unprotected circuit-breaker
Tripping by shunt trip as per IEC 60947-2
Type of circuit breaker Ultimate breaking capacity (kA rms) V AC 50/60 Hz Rated service breaking capacity (kA rms) Rated short-time withstand current (kA rms) Icu Ics Icw 220...690 V % Icu 1s 3s

Overload and short-circuit protection External protection relay: short-circuit protection, maximum delay: 350 ms (4) Rated making capacity (kA peak) V AC 50/60 Hz Type of switch-disconnector Rated making capacity (kA peak) AC23A/AC3 category V AC 50/60 Hz Rated short-time withstand current (kA rms) AC23A/AC3 category V AC 50/60 Hz Icm 220...690 V

Switch-disconnector as per IEC 60947-3 and Annex A


Icm Icw 220...690 V 1150 V 1s 3s 135 1 s 3 s

Earthing switch
Latching capacity (kA peak) Rating short time withstand (kA rms) Icw 60 Hz 50 Hz

Mechanical and electrical durability as per IEC 60947-2/3 at In/Ie


Service life Mechanical C/O cycles x 1000 Type of circuit breaker Rated current C/O cycles x 1000 Electrical IEC 60947-2 with maintenance without maintenance In (A) without maintenance

440 V (5) 690 V 1150 V AC23A 440 V (5) 690 V AC3 (6) 380/415 V (kW) 440 V (5) (kW) 690 V (kW) 440/690 V (5)

(1) 50 C: rear vertical connected. Refer to temperature derating tables for other connection types. (2) See the current-limiting curves in the additional characteristics section. (3) Equipped with a trip unit with a making current of 90 kA peak. (4) External protection must comply with permissible thermal constraints of the circuit breaker (please consult us). No fault-trip indication by the SDE or the reset button. (5) Available for 480 V NEMA. (6) Suitable for motor control (direct-on-line starting).

Type of circuit breaker or switch-disconnector Rated operational current Ie (A) C/O cycles x 1000 Electrical without maintenance IEC 60947-3 Type of circuit breaker or switch-disconnector Rated operational current Ie (A) Motor power

C/O cycles x 1000 Electrical IEC 60947-3 Annex M/IEC 60947-4-1

without maintenance

A-8

Sensor selection
Sensor rating (A) Ir threshold setting(A) 250 (1) 400 100 160 to 250 to 400 (1) For circuit-breaker NW02 , please consult us. 630 250 to 630 800 320 to 800 1000 400 to 1000 1250 500 to 1250 1600 630 to 1600 2000 800 to 2000 2500 1000 to 2500 3200 1250 to 3200 4000 1600 to 4000 5000 2000 to 5000 6300 2500 to 6300

NW08 NW10 NW12 NW16


800 800 400 to 800 N1 42 42 42 100 % B 42 22 88 88 88 25 < 70 42 42 1000 1000 400 to 1000 H1 65 65 65 1250 1250 630 to 1250 H2 100 85 85 1600 1600 800 to 1600 L1 (2) 150 130 100 H10 50

NW20
2000 2000 1000 to 2000 H1 65 65 65 100 % B 65 36 143 143 143 25 < 70 65 65 H2 100 85 85 H3 150 130 100 L1 (2) 150 130 100 H10 50

NW25 NW32 NW40


2500 2500 1250 to 2500 H1 65 65 65 100 % B 65 65 143 143 143 25 < 70 65 65 3200 3200 1600 to 3200 H2 100 85 85 4000 4000 2000 to 4000 H3 150 130 100 H10 50

NW40b NW50 NW63


4000 4000 2000 to 4000 H1 100 100 100 100 % B 100 100 220 220 220 25 < 80 100 100 5000 5000 2500 to 5000 H2 150 130 100 6300 6300 3200 to 6300

65 36 143 143 143 25

85 50 190 220 187 187 25

30 30 80 330 286 220 10

50 50 105 25

85 75 190 220 187 187 25

65 65 150 330 286 220 25

30 30 80 330 286 220 10

50 50 105 25

85 75 190 220 187 187 25

65 65 150 330 286 220 25

50 50 105 25

100 100 270 330 286 220 25

65 65

100 85

150 100

100 85

150 100

150 100

100 85

150 100

150 100

HA 50 100 % 50 36 105 NA 88 42 HA 105 50 36

HF (3) 85 85 50 187 HF 187 85 50 HA10 105 50 50

HA 50 100 % 50 36 105

HF (3) 85 85 75 187

HA 55 100 % 55 55 121

HF (3) 85 85 75 187 HA 121 55 55 HF 187 85 75 HA10 105 50 50

HA 85 100 % 85 85 187 HA 187 85 85

NW08/NW10/NW12

NW16
HA 105 50 36 HF 187 85 50 HA10 105 50 50

NW20
HA 105 50 36 HF 187 85 75 HA10 105 50 50

NW25/NW32/NW40 NW40b/NW50/NW63

25 12.5 N1/H1/H2 L1 800/1000/1250/1600 10 3 10 3 H1/H2/HA/HF 800/1000/1250/1600 10 10 H1/H2/HA/HF 800 1000 335 to 450 450 to 560 400 to 500 500 to 630 y 800 800 to 1000 6

H10 0.5

1250 560 to 670 500 to 800 1000 to 1250

1600 670 to 900 800 to 1000 1250 to 1600

20 10 H1/H2 H3 L1 2000 8 2 3 6 2 3 H1/H2/H3/HA/HF 2000 8 6 H1/H2/H3/HA/HF 2000 900 to 1150 1000 to 1300 1600 to 2000

H10 0.5

H1/H2 H3 2500/3200/4000 5 1.25 2.5 1.25 H1/H2/H3/HA/HF 2500/3200/4000 5 2.5

H10 0.5

10 5 H1 H2 4000b/5000/6300 1.5 1.5 1.5 1.5 H1/H2/HA 4000b/5000/6300 1.5 1.5

A-9

Functions and characteristics

Micrologic control units


Overview of functions

All Masterpact circuit breakers are equipped with a Micrologic control unit that can be changed on site. Control units are designed to protect Power circuits and loads. Alarms may be programmed for remote indications. Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy management.

Dependability
Integration of protection functions in an ASIC electronic component used in all Micrologic control units guarantees a high degree of reliability and immunity to conducted or radiated disturbances. On Micrologic A, P and H control units, advanced functions are managed by an independent microprocessor.

Accessories
Certain functions require the addition of Micrologic control unit accessories, described on page A-20. The rules governing the various possible combinations can be found in the documentation accessible via the Products and services menu of the www.schneider-electric.com web site.

Micrologic name codes

Current protection
Micrologic 2: basic protection
Protection: long time + instantaneous
DB101116

2.0 A
X Y Z
X: type of protection b 2 for basic protection b 5 for selective protection b 6 for selective + earth-fault protection b 7 for selective + earth-leakage protection. Y: control-unit generation Identification of the control-unit generation. 0 signifies the first generation. Z: type of measurement b A for ammeter b P for power meter b H for harmonic meter.

Micrologic 5: basic protection


Protection: long time + short time + instantaneous
DB101117

PB100772-32

Micrologic 6: selective + earth-fault protection


Protection: long time + short time + instantaneous + earth fault
DB101117 DB101118

Micrologic 7: selective + earth-leakage protection


Protection: long time + short time + instantaneous + earth leakage up to 3200A
DB101117 DB101119

A-10

Measurements and programmable protection


A: ammeter b I1, I2, I3, IN, Iearth-fault, Iearth-leakage and maximeter for these measurements b fault indications b settings in amperes and in seconds. P: A + power meter + programmable protection b measurements of V, A, W, VAR, VA, Wh, VARh, VAh, Hz, Vpeak, Apeak, power factor and maximeters and minimeters b IDMTL long-time protection, minimum and maximum voltage and frequency, voltage and current imbalance, phase sequence, reverse power b load shedding and reconnection depending on power or current b measurements of interrupted currents, differentiated fault indications, maintenance indications, event histories and time-stamping, etc. H: P + harmonics b power quality: fundamentals, distortion, amplitude and phase of harmonics up to the 31st order b waveform capture after fault, alarm or on request b enhanced alarm programming: thresholds and actions.

2.0 A

DB101121

DB101120

DB101122

5.0 A

5.0 P

5.0 H

DB101123

DB101124

6.0 A

6.0 P

6.0 H

DB101123

DB101124

7.0 A

7.0 P

7.0 H

DB101124

DB101124

DB101122

A-11

Functions and characteristics

Micrologic control units


Micrologic A ammeter

Micrologic A control units protect power circuits. They also offer measurements, display, communication and current maximeters. Version 6 provides earth-fault protection, version 7 provides earth-leakage protection.

"Ammeter" measurements
Micrologic A control units measure the true (rms) value of currents. They provide continuous current measurements from 0.2 to 20 In and are accurate to within 1.5 % (including the sensors). A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the I1, I2, I3, IN, Ig,In, stored-current (maximeter) and setting values by successively pressing the navigation button. The optional external power supply makes it possible to display currents < 20 % In. Below 0.05 In, measurements are not significant. Between 0.05 and 0.2 In, accuracy is to within 0.5 % In + 1.5 % of the reading.

E46028

Communication option
In conjunction with the COM communication option, the control unit transmits the following: b settings b all ammeter measurements b tripping causes b maximeter readings.

Protection
Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image before and after tripping. Setting accuracy may be enhanced by limiting the setting range using a different long-time rating plug. Overload protection can be cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of I2t type (ON or OFF) for short-time delay. Earth-fault protection Residual or source ground return earth fault protection. Selection of I2t type (ON or OFF) for delay. Residual earth-leakage protection (Vigi). Operation without an external power supply. q Protected against nuisance tripping. k DC-component withstand class A up to 10 A. Neutral protection On three-pole circuit breakers, neutral protection is not possible. On four-pole circuit breakers, neutral protection may be set using a three-position switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral protection at Ir (4P 4d). Zone selective interlocking (ZSI) A ZSI terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.

Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
1 long-time threshold and tripping delay 2 overload alarm (LED) at 1,125 Ir 3 short-time pick-up and tripping delay 4 instantaneous pick-up 5 earth-leakage or earth-fault pick-up and tripping delay 6 earth-leakage or earth-fault test button 7 long-time rating plug screw 8 test connector 9 lamp test, reset and battery test 10 indication of tripping cause 11 digital display 12 three-phase bargraph and ammeter 13 navigation buttons

Fault indications
LEDs indicate the type of fault: b overload (long-time protection Ir) b short-circuit (short-time Isd or instantaneous li protection) b earth fault or earth leakage (Ig or In) b internal fault (Ap). Battery power The fault indication LEDs remain on until the test/reset button is pressed. Under normal operating conditions, the battery supplying the LEDs has a service life of approximately 10 years.

Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units, the operation of earth-fault or earth-leakage protection can be checked by pressing the test button located above the test connector.

Note: Micrologic A control units come with a transparent leadseal cover as standard.

A-12

Protection
Long time Current setting (A) Tripping between 1.05 and 1.20 x Ir Time setting Time delay (s) Accuracy: 0 to -30 % Accuracy: 0 to -20 % Accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Instantaneous Pick-up (A) Isd = Ir x Accuracy: 10 % Time delay

Micrologic 2.0 A
0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 Other ranges or disable by changing long-time rating plug 0.5 1 2 4 8 12 16 20 24 50 100 200 300 400 500 600 12.5 25 2 4 8 12 16 20 24 0.7(1) 1 5.5 8.3 11 13.8 16.6 0.7(2) 0.69 1.38 2.7 20 minutes before and after tripping
DB101126 DB101129 DB101128 DB101127

tr (s) 1.5 x Ir 6 x Ir 7.2 x Ir

1.5

2.5

10

Max resettable time: 20 ms Max break time: 80 ms

Ammeter
Continuous current measurements Display from 20 to 200 % of In Accuracy: 1.5 % (including sensors) Maximeters

Micrologic 2.0 A
I2 I3 IN I1 No auxiliary source (where I > 20 % In) I1 max I2 max I3 max IN max

Protection
Long time Current setting (A) Ir = In x Tripping between 1.05 and 1.20 x Ir Time setting Time delay (s) Accuracy: 0 to -30 % Accuracy: 0 to -20 % Accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Short time Pick-up (A) Isd = Ir x Accuracy: 10 % Time setting tsd (s) Settings Time delay (ms) at 10 x Ir (I2t Off or I2t On) Instantaneous Pick-up (A) Accuracy: 10 % Time delay Earth fault Pick-up (A) Accuracy: 10 %

Micrologic 5.0 / 6.0 / 7.0 A


Micrologic 5.0 / 6.0 / 7.0 A 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 Other ranges or disable by changing long-time rating plug 0.5 1 2 4 8 12 16 20 24 50 100 200 300 400 500 600 12.5 25 2 4 8 12 16 20 24 0.7(1) 1 5.5 8.3 11 13.8 16.6 0.7(2) 0.69 1.38 2.7 20 minutes before and after tripping

tr (s) 1.5 x Ir 6 x Ir 7.2 x Ir

1.5 0 20 80 2

2 0.1 0.1 80 140 3

2.5 0.2 0.2 140 200 4

3 0.3 0.3 230 320 6

4 0.4 0.4 350 500 8

10

I2t Off I2t On tsd (max resettable time) tsd (max break time) Ii = In x

10

12

15

off

Max resettable time: 20 ms Max break time: 50 ms Ig = In x In y 400 A 400 A < In < 1250 A In u 1250 A Settings Micrologic 6.0 A A B C 0.3 0.3 0.4 0.2 0.3 0.4 500 640 720 0 0.1 0.2 0.1 0.2 20 80 140 80 140 200 Micrologic 7.0 A 0.5 1 2 60 60 140 140 140 200 230 230 320 D 0.5 0.5 800 0.3 0.3 230 320 3 350 350 500 E 0.6 0.6 880 0.4 0.4 350 500 5 800 800 1000 F 0.7 0.7 960 G 0.8 0.8 1040 H 0.9 0.9 1120 J 1 1 1200

Time setting tg (s) Time delay (ms) at In or 1200 A (I2t Off or I2t On) Residual earth leakage (Vigi) Sensitivity (A) Accuracy: 0 to -20 % Time delay Dt (ms)

I2t Off I2t On tg (max resettable time) tg (max break time)

IDn Settings Dt (max resettable time) Dt (max break time)

10

20

30

Ammeter

Micrologic 5.0 / 6.0 / 7.0 A

Continuous current measurements I2 I3 IN Ig Display from 20 to 200 % of In I1 IDn Accuracy: 1.5 % (including sensors) No auxiliary source (where I > 20 % In) Maximeters I1 max I2 max I3 max IN max Ig max IDn max Note: All current-based protection functions require no auxiliary source. The test / reset button resets maximeters, clears the tripping indication and tests the battery.

A-13

Locking

On the device

DB101159

1 Reset button for mechanical trip indication. 2 OFF pushbutton. 3 OFF position lock. 4 Electrical closing pushbutton. 5 ON pushbutton. 6 Springs charged indication. 7 Pushbutton locking. 8 Contact position indication. 9 Operation counter.

PB100811-32

Pushbutton locking VBP


The transparent cover blocks access to the pushbuttons used to open and close the device. It is possible to independently lock the opening button and the closing button. The locking device is often combined with a remote operating mechanism. The pushbuttons may be locked using either: b three padlocks (not supplied) b lead seal b two screws.

Access to pushbuttons protected by transparent cover.


PB100810-32

Device locking in the OFF position VCPO by padlocks, VSPO by keylocks


The circuit breaker is locked in the OFF position by physically maintaining the opening pushbutton pressed down: b using padlocks (one to three padlocks, not supplied) b using keylocks (one or two different keylocks, supplied). Keys may be removed only when locking is effective (Profalux or Ronis type locks). The keylocks are available in any of the following configurations: b one keylock b one keylock mounted on the device + one identical keylock supplied separately for interlocking with another device b two different key locks for double locking. Profalux and Ronis keylocks are compatible with each other. A locking kit (without locks) is available for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell). Accessory-compatibility For Masterpact NT: 3 padlocks or 1 keylock For Masterpact NW: 3 padlocks and/or 2 keylocks

Pushbutton locking using a padlock.


PB100812-32

Cable-type door interlock IPA


This option prevents door opening when the circuit breaker is closed and prevents circuit breaker closing when the door is open. For this, a special plate associated with a lock and a cable is mounted on the right side of the circuit breaker. With this interlock installed, the source changeover function cannot be implemented.
OFF position locking using a padlock.
PB104365A40

OFF position locking using a keylock.

A-35

Functions and characteristics

Locking

On the chassis

DB101160

Mismatch protection. Door interlock. Racking interlock. Keylock locking. Padlock locking. Position indicator. Chassis front plate (accessible with cubicle door closed). 8 Racking-handle entry. 9 Reset button. 10 Racking-handle storage. 1 2 3 4 5 6 7

PB104366A32

PB104367A34

Disconnected position locking by padlocks (standard) or keylocks (VSPD option)


Mounted on the chassis and accessible with the door closed, these devices lock the circuit breaker in the disconnected position in two manners: b using padlocks (standard), up to three padlocks (not supplied) b using keylocks (optional), one or two different keylocks are available. Profalux and Ronis keylocks are available in different options: b one keylock b two different keylocks for double locking b one (or two) keylocks mounted on the device + one (or two) identical keylocks supplied separately for interlocking with another device. A locking kit (without locks) is available for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell).

Disconnected position locking by padlocks.


PB104352A32

Disconnected position locking by keylocks.

Connected, disconnected and test position locking


The connected, disconnected and test positions are shown by an indicator andc are mechanically indexed. The exact position is obtained when the racking handle blocks. A release button is used to free it. As standard, the circuit breaker can be locked only in "disconnected position". On request, the locking system may be modified to lock the circuit breaker in any of the three positions: "connected", "disconnected" or "test".

Door interlock catch VPEC


Mounted on the right or left-hand side of the chassis, this device inhibits opening of the cubicle door when the circuit breaker is in connected or test position. It the breaker is put in the connected position with the door open, the door may be closed without having to disconnect the circuit breaker.

Door interlock.
PB104368 A32

Racking interlock VPOC


This device prevents insertion of the racking handle when the cubicle door is open.

Cable-type door interlock IPA


This option is identical for fixed and drawout versions.

Racking interlock between crank and OFF pushbutton IBPO (for NW only)
Racking interlock.
PB100815-32R_SE

This option makes it necessary to press the OFF pushbutton in order to insert the racking handle and holds the device open until the handle is removed.

Automatic spring discharge before breaker removal DAE (for NW only)


This option discharges the springs before the breaker is removed from the chassis.

Mismatch protection VDC


Mismatch protection.

Mismatch protection ensures that a circuit breaker is installed only in a chassis with compatible characteristics. It is made up of two parts (one on the chassis and one on the circuit breaker) offering twenty different combinations that the user may select.

A-36

Indication contacts

Indication contacts are available: b in the standard version for relay applications b in a low-level version for control of PLCs and electronic circuits. M2C and M6C contacts may be programmed via the Micrologic P and H control units.

ON/OFF indication contacts OF


Two types of contacts indicate the ON or OFF position of the circuit breaker: b microswitch type changeover contacts for Masterpact NT b rotary type changeover contacts directly driven by the mechanism for Masterpact NW. These contacts trip when the minimum isolation distance between the main circuit-breaker contacts is reached. OF NT NW
Supplied as standard Maximum number Breaking capacity (A) p.f.: 0.3 AC12/DC12 4 4 4 12 Minimum load: 100 mA/24 V 6 10/6 (1) 6 10/6 (1) 6 6 2.5 10/6 (1) 0.5 10/6 (1) 0.3 3 Minimum load: 2 mA/15 V 5 6 5 6 5 3 5/2.5 6 0.5 6 0.3 3

Standard V AC 240/380 480 690 24/48 125 250 24/48 240 380 24/48 125 250

PB100806-32

PB100807-20

V DC

Low-level V AC ON/OFF indication contacts (OF) (rotary type). V DC

(1) Standard contacts: 10 A; optional contacts: 6 A.

Fault-trip indication contacts SDE


Circuit-breaker tripping due to a fault is signalled by: b a red mechanical fault indicator (reset) b one changeover contact SDE. Following tripping, the mechanical indicator must be reset before the circuit breaker may be closed. One SDE is supplied as standard. An optimal SDE may be added. This latter is incompatible with the electrical reset after fault-trip option (RES). SDE NT/NW
Supplied as standard Maximum number Breaking capacity (A) p.f.: 0.3 AC12/DC12 1 2 Minimum load: 100 mA/24 V 5 5 3 3 0.3 0.15 Minimum load: 2 mA/15 V 3 3 3 3 0.3 0.15

ON/OFF indication contacts (OF) (microswitch type).

PB100820-32

Standard V AC 240/380 480 690 24/48 125 250 24/48 240 380 24/48 125 250

V DC

Low-level V AC Additional fault-trip indication contacts (SDE).

V DC

PB100816-32

Combined connected/closed contacts EF


The contact combines the device connected and the device closed information to produce the circuit closed information. Supplied as an option for Masterpact NW, it is mounted in place of the connector of an additional OF contact. EF NW
Maximum number Breaking capacity (A) p.f.: 0.3 AC12/DC12 Standard V AC 240/380 480 690 24/48 125 250 24/48 240 380 24/48 125 250 8 Minimum load: 100 mA/24 V 6 6 6 2.5 0.8 0.3 Minimum load: 2 mA/15 V 5 5 5 2.5 0.8 0.3

V DC Combined contacts. Low-level V AC

V DC

A-37

Functions and characteristics

Indication contacts

PB100817-32

Connected, disconnected and test position carriage switches


Three series of optional auxiliary contacts are available for the chassis: b changeover contacts to indicate the connected position CE b changeover contacts to indicate the disconnected position CD. This position is indicated when the required clearance for isolation of the power and auxiliary circuits is reached b changeover contacts to indicate the test position CT. In this position, the power circuits are disconnected and the auxiliary circuits are connected. Additional actuators A set of additional actuators may be installed on the chassis to change the functions of the carriage switches. NT NW
Contacts Maximum number Standard with additional actuators CE/CD/CT 3 3 3 9 0 0 6 3 0 6 0 3 Minimum load: 100 mA/24 V 8 8 8 8 8 8 6 6 2.5 2.5 0.8 0.8 0.3 0.3 Minimum load: 2 mA/15 V 5 5 5 5 5 5 2.5 2.5 0.8 0.8 0.3 0.3 CE/CD/CT 3 2 1

CE, CD and CT connected/disconnected/test position carriage switches.

PB100778-52

Breaking capacity (A) p.f.: 0.3 AC12/DC12

Standard V AC 240 380 480 690 24/48 125 250 24/48 240 380 24/48 125 250

V DC M2C programmable contacts: circuit-breaker internal relay with two contacts.


PB100781-32

Low-level V AC

V DC

M2C / M6C programmable contacts


M6C programmable contacts: circuit-breaker external relay with six independent changeover contacts controlled from the circuit breaker via a three-wire connection. (maximum length is 10 meters).

These contacts, used with the Micrologic P and H control units, may be programmed via the control unit keypad or via a supervisory station with the COM communication option. They require an external power supply module. They indicate: b the type of fault b instantaneous or delayed threshold overruns. b They may be programmed: b with instantaneous return to the initial state b without return to the initial state b with return to the initial state following a delay. Characteristics M2C/M6C
Minimum load Breaking capacity (A) p.f.: 0.7 V AC V DC 240 380 24 48 125 250 100 mA/24 V 5 3 1.8 1.5 0.4 0.15

DB117038

A-38

DB101170

M2C: 24 VDC power supplied by control unit (consumption 100mA).

M6C: external 24 V DC power supply required (consumption 100 mA).

Remote operation
Remote ON / OFF

Two solutions are available for remote operation of Masterpact devices: b a point-to-point solution b a bus solution with the COM communication option.

The remote ON / OFF function is used to remotely open and close the circuit breaker. It is made up of: b an electric motor MCH equipped with a springs charged limit switch contact CH b two voltage releases: v a closing release XF v an opening release MX. Optionally, other functions may be added: b a ready to close contact PF b an electrical closing pushbutton BPFE b remote RES following a fault. A remote-operation function is generally combined with: b device ON / OFF indication OF b fault-trip indication SDE.

PB104349A68

Wiring diagram of a point-to-point remote ON / OFF function


DB111783

Note: an opening order always takes priority over a closing order. If opening and closing orders occur simultaneously, the mechanism discharges without any movement of the main contacts. The circuit breaker remains in the open position (OFF). In the event of maintained opening and closing orders, the standard mechanism provides an anti-pumping function by blocking the main contacts in open position. Anti-pumping function. After fault tripping or intentional opening using the manual or electrical controls, the closing order must first be discontinued, then reactivated to close the circuit breaker. When the automatic reset after fault trip (RAR) option is installed, to avoid pumping following a fault trip, the automatic control system must take into account the information supplied by the circuit breaker before issuing a new closing order or blocking the circuit breaker in the open position (information on the type of fault, e.g. overload, short-time fault, earth fault, earth leakage, short-circuit, etc.).

Wiring diagram of a bus-type remote ON / OFF function


DB101165

Note: MX communicating releases are of the impulse type only and cannot be used to lock a circuit breaker in OFF position. For locking in OFF position, use the remote tripping function (2nd MX or MN). When MX or XF communicating releases are used, the third wire (C3, A3) must be connected even if the communication module is not installed. When the control voltage (C3-C1 or A3-A1) is applied to the MX or XF releases, it is necessary to wait 1.5 seconds before issuing an order. Consequently, it is advised to use standard MX or XF releases for applications such as source-changeover systems.

A-39

Functions and characteristics

Remote operation
Remote ON / OFF

PB100808-32

PB100797-23

Electric motor MCH


The electric motor automatically charges and recharges the spring mechanism when the circuit breaker is closed. Instantaneous reclosing of the breaker is thus possible following opening. The spring-mechanism charging handle is used only as a backup if auxiliary power is absent. The electric motor MCH is equipped as standard with a limit switch contact CH that signals the charged position of the mechanism (springs charged). Characteristics
Power supply V AC 50/60 Hz V DC Operating threshold Consumption (VA or W) Motor overcurrent Charging time Operating frequency CH contact 48/60 - 100/130 - 200/240 - 277- 380/415 - 400/440 - 480 24/30 - 48/60 - 100/125 - 200/250 0.85 to 1.1 Un 180 2 to 3 In for 0.1 s maximum 3 s for Masterpact NT maximum 4 s for Masterpact NW maximum 3 cycles per minute 10 A at 240 V

Electric motor MCH for Masterpact NT.

Electric motor MCH for Masterpact NW.

Voltage releases XF and MX


Their supply can be maintained or automatically disconnected. Closing release XF The XF release remotely closes the circuit breaker if the spring mechanism is charged. Opening release MX The MX release instantaneously opens the circuit breaker when energised. It locks the circuit breaker in OFF position if the order is maintained (except for MX communicating releases).
Note: whether the operating order is maintened or automatically disconnected (pulse-type), XF or MX communicating releases (bus solution with COM communication option) always have an impulse-type action (see diagram).

DB117037

Characteristics
Power supply V AC 50/60 Hz V DC Operating threshold Consumption (VA or W)

XF

MX

24 - 48 - 100/130 - 200/250 - 277 - 380/480 12 - 24/30 - 48/60 - 100/130 - 200/250 0.7 to 1.1 Un 0.85 to 1.1 Un Hold: 4.5 Hold: 4.5 Pick-up: 200 (200 ms) Pick-up: 200 (200 ms) Circuit-breaker response time at Un 55 ms 10 (Masterpact NT) 50 ms 10 70 ms 10 (NW y 4000 A) 80 ms 10 (NW > 4000 A)

PB100809-16

Ready to close contact PF


The ready to close position of the circuit breaker is indicated by a mechanical indicator and a PF changeover contact. This signal indicates that all the following are valid: b the circuit breaker is in the OFF position b the spring mechanism is charged b a maintained opening order is not present: v MX energised v fault trip v remote tripping second MX or MN v device not completely racked in v device locked in OFF position v device interlocked with a second device. Characteristics NT/NW
Maximum number Breaking capacity (A) p.f.: 0.3 AC12/DC12 Standard V AC 240/380 480 690 24/48 125 250 24/48 240 380 24/48 125 250 1 Minimum load: 100 mA/24 V 5 5 3 3 0.3 0.15 Minimum load: 2 mA/15 V 3 3 3 3 0.3 0.15

XF and MX voltage releases.

PB100818-16

V DC

Low-level V AC Ready to close contacts PF. V DC

A-40

PB100798-56

Electrical closing pushbutton BPFE


Located on the front panel, this pushbutton carries out electrical closing of the circuit breaker. It is generally associated with the transparent cover that protects access to the closing pushbutton. Electrical closing via the BPFE pushbutton takes into account all the safety functions that are part of the control/monitoring system of the installation. The BPFE connects to the closing release (XF com) in place of the COM module. The COM module is incompatible with this option. Different types of voltage exist and the XF electromagnet is compulsary if the BPFE option is selected.
DB101167

Electrical closing pushbutton BPFE.

Remote reset after fault trip


Electrical reset after fault trip RES Following tripping, this function resets the fault trip indication contacts SDE and the mechanical indicator and enables circuit breaker closing. Power supply: 110 / 130 V AC and 200 / 240 V AC. The use of XF closing release is compulsory with this option.
DB116359

Automatic reset after fault trip RAR Following tripping, a reset of the mechanical indicator (reset button) is no longer required to enable circuit-breaker closing. The mechanical (reset button) and electrical SDE indications remain in fault position until the reset button is pressed. The use of XF closing release is compulsory with this option.

A-41

Functions and characteristics

Remote operation
Remote tripping

PB104369A68

This function opens the circuit breaker via an electrical order. It is made up of: b a shunt release second MX b or an undervoltage release MN b or a delayed undervoltage release MNR: MN + delay unit. These releases (2nd MX or MN) cannot be operated by the communication bus. The delay unit, installed outside the circuit breaker, may be disabled by an emergency OFF button to obtain instantaneous opening of the circuit breaker. Wiring diagram for the remote-tripping function
DB101172 DB101175 DB117188

DB100809-16

Voltage releases second MX


MX or MN voltage release.

When energised, the MX voltage release instantaneously opens the circuit breaker. A continuous supply of power to the second MX locks the circuit breaker in the OFF position. Characteristics
Power supply V AC 50/60Hz V DC 24 - 48 - 100/130 - 200/250 - 277- 380/480 12 - 24/30 - 48/60 - 100/130 - 200/250 0.7 to 1.1 Un 0.85 to 1.1 Un Pick-up: 200 (80 ms) 50 ms 10 Hold: 4.5

Operating threshold Permanent locking function Consumption (VA or W) Circuit-breaker response time at Un

Instantaneous voltage releases MN


The MN release instantaneously opens the circuit breaker when its supply voltage drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on the release, it is impossible to close the circuit breaker, either manually or electrically. Any attempt to close the circuit breaker has no effect on the main contacts. Circuitbreaker closing is enabled again when the supply voltage of the release returns to 85 % of its rated value. Characteristics
V AC 50/60 Hz V DC Operating threshold Opening Closing Consumption (VA or W) MN consumption with delay unit (VA or W) Circuit-breaker response time at Un Power supply 24 - 48 - 100/130 - 200/250 - 380/480 24/30 - 48/60 - 100/130 - 200/250 0.35 to 0.7 Un 0.85 Un Pick-up: 200 (200 ms) Hold: 4.5 Pick-up: 200 (200 ms) Hold: 4.5 40 ms 5 for NT 90 ms 5 for NW

MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of the MN release can be delayed. This function is achieved by adding an external delay unit in the MN voltage-release circuit. Two versions are available, adjustable and non-adjustable. Characteristics
Power supply V AC 50-60 Hz /DC Operating threshold Delay unit consumption Circuit-breaker response time at Un Non-adjustable 100/130 - 200/250 Adjustable 48/60 - 100/130 - 200/250 - 380/480 Opening 0.35 to 0.7 Un Closing 0.85 Un Pick-up: 200 (200 ms) Hold: 4.5 Non-adjustable 0.25 s Adjustable 0.5 s - 0.9 s - 1.5 s - 3 s

A-42

Accessories

PB104740

Auxiliary terminal shield CB


Optional equipment mounted on the chassis, the shield prevents access to the terminal block of the electrical auxiliaries.

PB104382A32

Operation counter CDM


The operation counter sums the number of operating cycles and is visible on the front panel. It is compatible with manual and electrical control functions. This option is compulsory for all the source-changeover systems.

DB101173

Escutcheon CDP
Optional equipment mounted on the door of the cubicle, the escutcheon increases the degree of protection to IP40 (circuit breaker installed free standing: IP30) . It is available in fixed and drawout versions.

Blanking plate OP for escutcheon


Used with the escutcheon, this option closes off the door cut-out of a cubicle not yet equipped with a device. It may be used with the escutcheon for both fixed and drawout devices.

Transparent cover CCP for escutcheon


Optional equipment mounted on the escutcheon, the cover is hinged and secured by a screw. It increases the degree of protection to IP54, IK10. It adapts to drawout devices.

Escutcheon CDP with blanking plate.


PB100776-42

Transparent cover CCP for escutcheon.

A-43

Schneider Electric Industries SAS


35, rue Joseph Monier CS 30323 F- 92506 Rueil Malmaison Cedex RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Design: Schneider Electric Photos: Schneider Electric Printed: Imprimerie du Pont-de-Claix/JPF - made in France

LVPED208008EN

09-2009