Masterpact M
Circuit breaker Original device M08 3P/4P M10 3P/4P M12 3P/4P M16 3P/4P M20 3P/4P M25 3P/4P M32 3P/4P
: Standard offer
Switch-disconnector H2 NI HI HF
N1
H1
Consult us for all devices not included in the standard offer. The STR control units (except for communication units) are replaced by the corresponding Micrologic control units according to the speci cation of the existing STR.
30
minutes* and
easy operations
The factory-modied and adapted "Plug and Play" Masterpact NW is designed for installation in the original Masterpact M chassis. On-site implementation is very simple:
Two new racks are installed in place of the original racks in the Masterpact M chassis.
All Masterpact NW functions are pre-wired; ourtechnician has only to connect the functions required according to the accessories tted.
Options
@ Mismatch Protection The mismatch protection ensures that a circuit breaker is installed only in a cradle with compatible characteristics. The kit can be ordered separately. @ Mechanical interlock Mechanical interlock of two or three buncked devices using connecting rods and 2 devices installed side by side using cables are available with the Plug&Play. The kit has to be ordered with the device.
Mechanical interlock using connecting rods for 2 or 3 buncked devices. Mechanical interlock using cable for 2 devices installed side by side.
Standards
@ The "Plug and Play" retrot solutions keeps all Masterpact NW circuit breaker approvals. @ All specic parts are certied in compliance with the following standards: _ IEC 60947 - 1 _ IEC 60947 - 2 @ Conform to marine standards.
The housing is modified and adapted to be compatible with the Masterpact M chassis
Reference List
Existing Circuit Breaker M08H1 3P STR28D M10H1 3P STR28D M12H1 3P STR28D M16H1 3P STR28D M20H1 3P STR28D M25H1 3P STR28D M32H1 3P STR28D Plug&Play Solution P&P M08H1 3P by NW08H1 3P 5.0A P&P M10H1 3P by NW10H1 3P 5.0A P&P M12H1 3P by NW12H1 3P 5.0A P&P M16H1 3P by NW16H1 3P 5.0A P&P M20H1 3P by NW20H1 3P 5.0A P&P M25H1 3P by NW25H1 3P 5.0A P&P M32H1 3P by NW32H1 3P 5.0A Reference 93674 93680 93686 93692 93694 93698 93701
PB104423A35
Common characteristics
Number of poles Rated insulation voltage (V) Impulse withstand voltage (kV) Rated operational voltage (V AC 50/60 Hz) Suitability for isolation Degree of pollution Ui Uimp Ue IEC 60947-2 IEC 60664-1 3/4 1000/1250 12 690/1150 4 (1000 V) / 3 (1250 V)
Basic circuit-breaker
Circuit-breaker as per IEC 60947-2
Rated current (A) Rating of 4th pole (A) Sensor ratings (A)
PB104433A65
at 40 C / 50 C (1)
Icu
Rated service breaking capacity (kA rms) Utilisation category Rated short-time withstand current (kA rms) V AC 50/60 Hz Integrated instantaneous protection (kA peak 10 %) Rated making capacity (kA peak) V AC 50/60 Hz
Ics Icw
Icm
Break time (ms) between tripping order and arc extinction Closing time (ms)
Unprotected circuit-breaker
Tripping by shunt trip as per IEC 60947-2
Type of circuit breaker Ultimate breaking capacity (kA rms) V AC 50/60 Hz Rated service breaking capacity (kA rms) Rated short-time withstand current (kA rms) Icu Ics Icw 220...690 V % Icu 1s 3s
Overload and short-circuit protection External protection relay: short-circuit protection, maximum delay: 350 ms (4) Rated making capacity (kA peak) V AC 50/60 Hz Type of switch-disconnector Rated making capacity (kA peak) AC23A/AC3 category V AC 50/60 Hz Rated short-time withstand current (kA rms) AC23A/AC3 category V AC 50/60 Hz Icm 220...690 V
Earthing switch
Latching capacity (kA peak) Rating short time withstand (kA rms) Icw 60 Hz 50 Hz
440 V (5) 690 V 1150 V AC23A 440 V (5) 690 V AC3 (6) 380/415 V (kW) 440 V (5) (kW) 690 V (kW) 440/690 V (5)
(1) 50 C: rear vertical connected. Refer to temperature derating tables for other connection types. (2) See the current-limiting curves in the additional characteristics section. (3) Equipped with a trip unit with a making current of 90 kA peak. (4) External protection must comply with permissible thermal constraints of the circuit breaker (please consult us). No fault-trip indication by the SDE or the reset button. (5) Available for 480 V NEMA. (6) Suitable for motor control (direct-on-line starting).
Type of circuit breaker or switch-disconnector Rated operational current Ie (A) C/O cycles x 1000 Electrical without maintenance IEC 60947-3 Type of circuit breaker or switch-disconnector Rated operational current Ie (A) Motor power
without maintenance
A-8
Sensor selection
Sensor rating (A) Ir threshold setting(A) 250 (1) 400 100 160 to 250 to 400 (1) For circuit-breaker NW02 , please consult us. 630 250 to 630 800 320 to 800 1000 400 to 1000 1250 500 to 1250 1600 630 to 1600 2000 800 to 2000 2500 1000 to 2500 3200 1250 to 3200 4000 1600 to 4000 5000 2000 to 5000 6300 2500 to 6300
NW20
2000 2000 1000 to 2000 H1 65 65 65 100 % B 65 36 143 143 143 25 < 70 65 65 H2 100 85 85 H3 150 130 100 L1 (2) 150 130 100 H10 50
50 50 105 25
50 50 105 25
50 50 105 25
65 65
100 85
150 100
100 85
150 100
150 100
100 85
150 100
150 100
HA 50 100 % 50 36 105
HF (3) 85 85 75 187
HA 55 100 % 55 55 121
NW08/NW10/NW12
NW16
HA 105 50 36 HF 187 85 50 HA10 105 50 50
NW20
HA 105 50 36 HF 187 85 75 HA10 105 50 50
NW25/NW32/NW40 NW40b/NW50/NW63
25 12.5 N1/H1/H2 L1 800/1000/1250/1600 10 3 10 3 H1/H2/HA/HF 800/1000/1250/1600 10 10 H1/H2/HA/HF 800 1000 335 to 450 450 to 560 400 to 500 500 to 630 y 800 800 to 1000 6
H10 0.5
20 10 H1/H2 H3 L1 2000 8 2 3 6 2 3 H1/H2/H3/HA/HF 2000 8 6 H1/H2/H3/HA/HF 2000 900 to 1150 1000 to 1300 1600 to 2000
H10 0.5
H10 0.5
A-9
All Masterpact circuit breakers are equipped with a Micrologic control unit that can be changed on site. Control units are designed to protect Power circuits and loads. Alarms may be programmed for remote indications. Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy management.
Dependability
Integration of protection functions in an ASIC electronic component used in all Micrologic control units guarantees a high degree of reliability and immunity to conducted or radiated disturbances. On Micrologic A, P and H control units, advanced functions are managed by an independent microprocessor.
Accessories
Certain functions require the addition of Micrologic control unit accessories, described on page A-20. The rules governing the various possible combinations can be found in the documentation accessible via the Products and services menu of the www.schneider-electric.com web site.
Current protection
Micrologic 2: basic protection
Protection: long time + instantaneous
DB101116
2.0 A
X Y Z
X: type of protection b 2 for basic protection b 5 for selective protection b 6 for selective + earth-fault protection b 7 for selective + earth-leakage protection. Y: control-unit generation Identification of the control-unit generation. 0 signifies the first generation. Z: type of measurement b A for ammeter b P for power meter b H for harmonic meter.
PB100772-32
A-10
2.0 A
DB101121
DB101120
DB101122
5.0 A
5.0 P
5.0 H
DB101123
DB101124
6.0 A
6.0 P
6.0 H
DB101123
DB101124
7.0 A
7.0 P
7.0 H
DB101124
DB101124
DB101122
A-11
Micrologic A control units protect power circuits. They also offer measurements, display, communication and current maximeters. Version 6 provides earth-fault protection, version 7 provides earth-leakage protection.
"Ammeter" measurements
Micrologic A control units measure the true (rms) value of currents. They provide continuous current measurements from 0.2 to 20 In and are accurate to within 1.5 % (including the sensors). A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the I1, I2, I3, IN, Ig,In, stored-current (maximeter) and setting values by successively pressing the navigation button. The optional external power supply makes it possible to display currents < 20 % In. Below 0.05 In, measurements are not significant. Between 0.05 and 0.2 In, accuracy is to within 0.5 % In + 1.5 % of the reading.
E46028
Communication option
In conjunction with the COM communication option, the control unit transmits the following: b settings b all ammeter measurements b tripping causes b maximeter readings.
Protection
Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image before and after tripping. Setting accuracy may be enhanced by limiting the setting range using a different long-time rating plug. Overload protection can be cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of I2t type (ON or OFF) for short-time delay. Earth-fault protection Residual or source ground return earth fault protection. Selection of I2t type (ON or OFF) for delay. Residual earth-leakage protection (Vigi). Operation without an external power supply. q Protected against nuisance tripping. k DC-component withstand class A up to 10 A. Neutral protection On three-pole circuit breakers, neutral protection is not possible. On four-pole circuit breakers, neutral protection may be set using a three-position switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral protection at Ir (4P 4d). Zone selective interlocking (ZSI) A ZSI terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
1 long-time threshold and tripping delay 2 overload alarm (LED) at 1,125 Ir 3 short-time pick-up and tripping delay 4 instantaneous pick-up 5 earth-leakage or earth-fault pick-up and tripping delay 6 earth-leakage or earth-fault test button 7 long-time rating plug screw 8 test connector 9 lamp test, reset and battery test 10 indication of tripping cause 11 digital display 12 three-phase bargraph and ammeter 13 navigation buttons
Fault indications
LEDs indicate the type of fault: b overload (long-time protection Ir) b short-circuit (short-time Isd or instantaneous li protection) b earth fault or earth leakage (Ig or In) b internal fault (Ap). Battery power The fault indication LEDs remain on until the test/reset button is pressed. Under normal operating conditions, the battery supplying the LEDs has a service life of approximately 10 years.
Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units, the operation of earth-fault or earth-leakage protection can be checked by pressing the test button located above the test connector.
Note: Micrologic A control units come with a transparent leadseal cover as standard.
A-12
Protection
Long time Current setting (A) Tripping between 1.05 and 1.20 x Ir Time setting Time delay (s) Accuracy: 0 to -30 % Accuracy: 0 to -20 % Accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Instantaneous Pick-up (A) Isd = Ir x Accuracy: 10 % Time delay
Micrologic 2.0 A
0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 Other ranges or disable by changing long-time rating plug 0.5 1 2 4 8 12 16 20 24 50 100 200 300 400 500 600 12.5 25 2 4 8 12 16 20 24 0.7(1) 1 5.5 8.3 11 13.8 16.6 0.7(2) 0.69 1.38 2.7 20 minutes before and after tripping
DB101126 DB101129 DB101128 DB101127
1.5
2.5
10
Ammeter
Continuous current measurements Display from 20 to 200 % of In Accuracy: 1.5 % (including sensors) Maximeters
Micrologic 2.0 A
I2 I3 IN I1 No auxiliary source (where I > 20 % In) I1 max I2 max I3 max IN max
Protection
Long time Current setting (A) Ir = In x Tripping between 1.05 and 1.20 x Ir Time setting Time delay (s) Accuracy: 0 to -30 % Accuracy: 0 to -20 % Accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Short time Pick-up (A) Isd = Ir x Accuracy: 10 % Time setting tsd (s) Settings Time delay (ms) at 10 x Ir (I2t Off or I2t On) Instantaneous Pick-up (A) Accuracy: 10 % Time delay Earth fault Pick-up (A) Accuracy: 10 %
1.5 0 20 80 2
10
I2t Off I2t On tsd (max resettable time) tsd (max break time) Ii = In x
10
12
15
off
Max resettable time: 20 ms Max break time: 50 ms Ig = In x In y 400 A 400 A < In < 1250 A In u 1250 A Settings Micrologic 6.0 A A B C 0.3 0.3 0.4 0.2 0.3 0.4 500 640 720 0 0.1 0.2 0.1 0.2 20 80 140 80 140 200 Micrologic 7.0 A 0.5 1 2 60 60 140 140 140 200 230 230 320 D 0.5 0.5 800 0.3 0.3 230 320 3 350 350 500 E 0.6 0.6 880 0.4 0.4 350 500 5 800 800 1000 F 0.7 0.7 960 G 0.8 0.8 1040 H 0.9 0.9 1120 J 1 1 1200
Time setting tg (s) Time delay (ms) at In or 1200 A (I2t Off or I2t On) Residual earth leakage (Vigi) Sensitivity (A) Accuracy: 0 to -20 % Time delay Dt (ms)
10
20
30
Ammeter
Continuous current measurements I2 I3 IN Ig Display from 20 to 200 % of In I1 IDn Accuracy: 1.5 % (including sensors) No auxiliary source (where I > 20 % In) Maximeters I1 max I2 max I3 max IN max Ig max IDn max Note: All current-based protection functions require no auxiliary source. The test / reset button resets maximeters, clears the tripping indication and tests the battery.
A-13
Locking
On the device
DB101159
1 Reset button for mechanical trip indication. 2 OFF pushbutton. 3 OFF position lock. 4 Electrical closing pushbutton. 5 ON pushbutton. 6 Springs charged indication. 7 Pushbutton locking. 8 Contact position indication. 9 Operation counter.
PB100811-32
A-35
Locking
On the chassis
DB101160
Mismatch protection. Door interlock. Racking interlock. Keylock locking. Padlock locking. Position indicator. Chassis front plate (accessible with cubicle door closed). 8 Racking-handle entry. 9 Reset button. 10 Racking-handle storage. 1 2 3 4 5 6 7
PB104366A32
PB104367A34
Door interlock.
PB104368 A32
Racking interlock between crank and OFF pushbutton IBPO (for NW only)
Racking interlock.
PB100815-32R_SE
This option makes it necessary to press the OFF pushbutton in order to insert the racking handle and holds the device open until the handle is removed.
Mismatch protection ensures that a circuit breaker is installed only in a chassis with compatible characteristics. It is made up of two parts (one on the chassis and one on the circuit breaker) offering twenty different combinations that the user may select.
A-36
Indication contacts
Indication contacts are available: b in the standard version for relay applications b in a low-level version for control of PLCs and electronic circuits. M2C and M6C contacts may be programmed via the Micrologic P and H control units.
Standard V AC 240/380 480 690 24/48 125 250 24/48 240 380 24/48 125 250
PB100806-32
PB100807-20
V DC
PB100820-32
Standard V AC 240/380 480 690 24/48 125 250 24/48 240 380 24/48 125 250
V DC
V DC
PB100816-32
V DC
A-37
Indication contacts
PB100817-32
PB100778-52
Standard V AC 240 380 480 690 24/48 125 250 24/48 240 380 24/48 125 250
Low-level V AC
V DC
These contacts, used with the Micrologic P and H control units, may be programmed via the control unit keypad or via a supervisory station with the COM communication option. They require an external power supply module. They indicate: b the type of fault b instantaneous or delayed threshold overruns. b They may be programmed: b with instantaneous return to the initial state b without return to the initial state b with return to the initial state following a delay. Characteristics M2C/M6C
Minimum load Breaking capacity (A) p.f.: 0.7 V AC V DC 240 380 24 48 125 250 100 mA/24 V 5 3 1.8 1.5 0.4 0.15
DB117038
A-38
DB101170
Remote operation
Remote ON / OFF
Two solutions are available for remote operation of Masterpact devices: b a point-to-point solution b a bus solution with the COM communication option.
The remote ON / OFF function is used to remotely open and close the circuit breaker. It is made up of: b an electric motor MCH equipped with a springs charged limit switch contact CH b two voltage releases: v a closing release XF v an opening release MX. Optionally, other functions may be added: b a ready to close contact PF b an electrical closing pushbutton BPFE b remote RES following a fault. A remote-operation function is generally combined with: b device ON / OFF indication OF b fault-trip indication SDE.
PB104349A68
Note: an opening order always takes priority over a closing order. If opening and closing orders occur simultaneously, the mechanism discharges without any movement of the main contacts. The circuit breaker remains in the open position (OFF). In the event of maintained opening and closing orders, the standard mechanism provides an anti-pumping function by blocking the main contacts in open position. Anti-pumping function. After fault tripping or intentional opening using the manual or electrical controls, the closing order must first be discontinued, then reactivated to close the circuit breaker. When the automatic reset after fault trip (RAR) option is installed, to avoid pumping following a fault trip, the automatic control system must take into account the information supplied by the circuit breaker before issuing a new closing order or blocking the circuit breaker in the open position (information on the type of fault, e.g. overload, short-time fault, earth fault, earth leakage, short-circuit, etc.).
Note: MX communicating releases are of the impulse type only and cannot be used to lock a circuit breaker in OFF position. For locking in OFF position, use the remote tripping function (2nd MX or MN). When MX or XF communicating releases are used, the third wire (C3, A3) must be connected even if the communication module is not installed. When the control voltage (C3-C1 or A3-A1) is applied to the MX or XF releases, it is necessary to wait 1.5 seconds before issuing an order. Consequently, it is advised to use standard MX or XF releases for applications such as source-changeover systems.
A-39
Remote operation
Remote ON / OFF
PB100808-32
PB100797-23
DB117037
Characteristics
Power supply V AC 50/60 Hz V DC Operating threshold Consumption (VA or W)
XF
MX
24 - 48 - 100/130 - 200/250 - 277 - 380/480 12 - 24/30 - 48/60 - 100/130 - 200/250 0.7 to 1.1 Un 0.85 to 1.1 Un Hold: 4.5 Hold: 4.5 Pick-up: 200 (200 ms) Pick-up: 200 (200 ms) Circuit-breaker response time at Un 55 ms 10 (Masterpact NT) 50 ms 10 70 ms 10 (NW y 4000 A) 80 ms 10 (NW > 4000 A)
PB100809-16
PB100818-16
V DC
A-40
PB100798-56
Automatic reset after fault trip RAR Following tripping, a reset of the mechanical indicator (reset button) is no longer required to enable circuit-breaker closing. The mechanical (reset button) and electrical SDE indications remain in fault position until the reset button is pressed. The use of XF closing release is compulsory with this option.
A-41
Remote operation
Remote tripping
PB104369A68
This function opens the circuit breaker via an electrical order. It is made up of: b a shunt release second MX b or an undervoltage release MN b or a delayed undervoltage release MNR: MN + delay unit. These releases (2nd MX or MN) cannot be operated by the communication bus. The delay unit, installed outside the circuit breaker, may be disabled by an emergency OFF button to obtain instantaneous opening of the circuit breaker. Wiring diagram for the remote-tripping function
DB101172 DB101175 DB117188
DB100809-16
When energised, the MX voltage release instantaneously opens the circuit breaker. A continuous supply of power to the second MX locks the circuit breaker in the OFF position. Characteristics
Power supply V AC 50/60Hz V DC 24 - 48 - 100/130 - 200/250 - 277- 380/480 12 - 24/30 - 48/60 - 100/130 - 200/250 0.7 to 1.1 Un 0.85 to 1.1 Un Pick-up: 200 (80 ms) 50 ms 10 Hold: 4.5
Operating threshold Permanent locking function Consumption (VA or W) Circuit-breaker response time at Un
MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of the MN release can be delayed. This function is achieved by adding an external delay unit in the MN voltage-release circuit. Two versions are available, adjustable and non-adjustable. Characteristics
Power supply V AC 50-60 Hz /DC Operating threshold Delay unit consumption Circuit-breaker response time at Un Non-adjustable 100/130 - 200/250 Adjustable 48/60 - 100/130 - 200/250 - 380/480 Opening 0.35 to 0.7 Un Closing 0.85 Un Pick-up: 200 (200 ms) Hold: 4.5 Non-adjustable 0.25 s Adjustable 0.5 s - 0.9 s - 1.5 s - 3 s
A-42
Accessories
PB104740
PB104382A32
DB101173
Escutcheon CDP
Optional equipment mounted on the door of the cubicle, the escutcheon increases the degree of protection to IP40 (circuit breaker installed free standing: IP30) . It is available in fixed and drawout versions.
A-43
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Design: Schneider Electric Photos: Schneider Electric Printed: Imprimerie du Pont-de-Claix/JPF - made in France