Vous êtes sur la page 1sur 7

CHAPTER EIGHT

INSTALLATION & MAINTENANCE OF “VRLA” BATTERY

General
All POWER STACK batteries are rated to an end cell voltage of 1.75 VPC at all rates
of discharge.

Floating Charge Method


In this type of operation, the battery is connected in parallel with a constant voltage
charger and the critical load circuits. The charger should be capable of maintaining the
required constant voltage at battery terminals and also supply normal connected load where
applicable. This sustains the battery in a fully charged condition and also makes it available
to resume the emergency power requirements in the event of an AC power interruption or
charger failure.

Float and Boost Voltages


Given below are the float and boost voltage recommended for the POWER STACK
battery system. The average “Volts per cell” (VPC) value of the series string should be set to
the recommended voltage under Float and Boost conditions.

RECOMMENDED FLOAT VOLTAGE 2.25 VPC AT 27oC


RECOMMENDED BOOST VOLTAGE 2.30 VPC AT 27oC

Modern constant voltage output charging equipment is recommended for the floating
charger method of operation of batteries. This type of charger, properly adjusted to the
recommended float voltage and following recommended surveillance procedures, will assist
in obtaining consistent serviceability and optimum life. The charging current for the battery
should be limited to 20% of its nominal AH capacity.

After the battery has been given its freshening charge , the charger should be adjusted
to provide the recommended float voltage at the battery terminals.

Do not use float voltage lower or higher than those recommended. This will result in
reduced capacity and/or reduced battery life.

Check and record battery terminal voltage monthly. See Section 8, RECORDS Item
B. If normal battery float voltage is above or below the recommended value adjust charger to
provide proper voltage as measured at the battery terminals.

Voltmeter Calibration
Panel and portable voltmeters used to indicate battery voltage should be accurate at
the operating voltage value. The same holds true for portable meters used to read individual
cell voltages. These meters should be checked against a standard every six months and
calibrated when necessary.

RTTC NAGPUR Page 62 of 68


Recharge
All batteries should be recharged as soon as possible following a discharge with
constant voltage chargers.

Determining State-of-Charge
The approximate state of charge of the battery, to some extent can be determined by
the amount of charging current going to the battery. While charging the current shown by the
charger ammeter will start to decrease and will finally stabilize when the battery becomes
fully charged, if the normal connected load is constant (no emergency load connected). The
state when the current level remains constant, after it has started decreasing, for three
consecutive hours would indicate full state of charge condition and the battery will be ready
for normal use.

If the normal connected load is variable (e.g. Telecom application) the state when the
voltage across the battery terminals is stable for six consecutive hours would indicate full
state of charge condition and the battery is ready for normal use.

Temperature of the Cell


The temperature of the POWER STACK cells cannot be measured during operation.
However, cell temperatures are normally within +5oC of the ambient temperature. All
performance characteristics are measured at ambient temperature and corrected to 27oC.

Section 6 - Equalizing Charge

General
Under normal operating conditions an equalizing charge is not required. An
equalizing charge is a special charge given to a battery when non-uniformity in voltage has
developed between cells. It is given to restore all cells to a fully charged condition. Use a
charging voltage higher than the normal float voltage and for a specified number of hours, as
determined by the voltage used.

Non-uniformity of cells may result from low float voltage due to improper adjustment
of the charger or a panel voltmeter which reads an incorrect (higher) output voltage. Also,
variations in cell temperatures greater than 3oC in the string at a given time due to
environmental conditions or module arrangement, can cause low cells.

Equalizing Frequency
An equalizing charge should be given when the following conditions exist.

(A) The float voltage of the pilot cell (as per section 7) is at least 0.05V below the
average float voltage per cell in the bank.

(B) A recharge of battery is required in a minimum time period following an


emergency discharge.

RTTC NAGPUR Page 63 of 68


(C) Accurate periodic records (see section 8) of individual cell voltages show an
increase in spread since the previous readings.

Equalizing Charge Method


Constant Voltage charging is the method for giving an equalizing charge. Determine
the maximum voltage that may be applied to the system. This voltage, divided by the number
of cells connected in series, will establish the maximum volts per cell that may be used to
perform the equalizing charge in the shortest period of time. Refer to Table-C for voltage and
recommended time periods.

Table-C
Temp Cell volts Time
<15° C 2.30 30 hrs
15-32° C 2.30 20 hrs
>32° C 2.30 12 hrs

Raise the voltage to the maximum value permitted by the system equipment or
recommended equalizing charge voltage whichever is lower. When charging current has
tapered and stabilized (no further reduction for three hours). Continue charging for the hours
shown in Table C until the lowest cell voltage ceases to rise. Monitoring of cell voltages
should be started during the final 10% of the applicable time period to determine lowest cell
voltage in the battery system.

Section 7 – Pilot Cell


A pilot cell is selected in the series string to reflect the general condition of all cells in
the battery. The cell selected should be the lowest cell voltage in the series string following
the initial charge. Reading and recording pilot cell voltage monthly serves as an indicator of
battery condition between scheduled overall individual cell readings.

Section 8 – Records
A complete recorded history of the battery operation is most desirable and helpful in
obtaining satisfactory performance. Good records will also show when corrective action may
be required to eliminate possible charging, maintenance or environmental problems.

The following surveillance data must be read and permanently recorded for review by
supervisory personnel so that any necessary remedial action is taken.

(A) Upon completion of the freshening charge and with the battery on float charge
at the proper voltage for one week, read and record the following :

(1) Individual cell voltage


(2) Battery terminal voltage
(3) Ambient temperature

RTTC NAGPUR Page 64 of 68


(B) Every 3 months, a complete set of readings as specified in paragraph A above
must be recorded.

(C) Whenever the battery is given an equalizing charge, an additional set of


readings should be taken and recorded as specified in paragraph A above.

The suggested frequency of record taking is the absolute minimum to protect warranty. For
system protection and to suit local conditions or requirements, more frequent readings may be
desirable.

Section 9 – Temporary Non-use


As installed battery that is expected to stand idle for over 6 months should be treated
as follows.

Give the battery an equalizing charge as per section 6. Following the equalizing
charge, open connections at the battery terminals to remove charge and load from the battery.

Every six months, temporarily connect battery to charger and give it an equalizing
charge.

To return the battery to normal service, re-connect the battery to the charger and load,
give an equalizing charge and return the battery to float operation.

Section 10 – Unit Cleaning


Periodically clean cell covers with a dry 55 mm paintbrush to remove accumulated
dust. If any cell parts appear to be damp with electrolyte or show signs of corrosion, contact
your local representative of the manufacturer.

CAUTION

Do not clean plastic parts with solvents,


detergents, oils, mineral spirits or spray-type
cleaners as these may cause crazing or cracking
of the plastic materials.

Section 11 – Checking Connections


Battery terminals and intercell connections should be corrosion free and tight for
trouble free operation. Periodically these connections should be inspected.

If corrosion is present, disconnect the connector from the terminal.

Gently clean the affected area using a brush or scouring pad. Apply a thin coating of
petroleum jelly to the cleaned contact surfaces, reinstall connectors and retorque connections.

ALL TERMINALS AND INTERCELL CONNECTIONS SHOULD BE RETORQUED


ATLEAST ONCE EVERY YEAR.

Section 12 – Determination of State of Charge of VRLA Batteries

RTTC NAGPUR Page 65 of 68


Sealed Maintenance Free Valve Regulated Lead Acid Batteries represent the state of
the art in Lead Acid technology.

The maintenance-free feature of these batteries often raises a practical problem in the
field. How can the battery bank be monitored ? In conventional flooded batteries, the specific
gravity of the electrolyte gives a fairly good indication of the state of charge of the battery.
However, in a VRLA battery, it is not possible to measure the specific gravity of the
electrolyte since it is completely absorbed in the spun glass microporous separator.

The terminal voltage of the battery is directly related to the concentration of the
electrolyte. Therefore, if one were to measure the open circuit voltage of the battery, the state
of charge can be determined. The Open Circuit Voltage (OCV) readings should be taken 24
hrs. after charging is discontinued. The OCV value is co-related to the state of charge of
VRLA batteries as per the table enclosed.

Sometimes, it may not possible to disconnect the batteries from service for 24 hrs. and
then check the OCVs. Then the pattern of charging current delivered by a temperature
compensated voltage – regulated charger after a discharge provides the alternate method for
determining the full state of charge. The temperature compensation factor is –3 mV per cell
o
C rise from ambient temperature of 27oC.

Under normal conditions the batteries are floated at around 2.25 volts per cell, i.e. in a
DOT System 24 cells are floated at 53.5 volts. During charging as the cells approach full
charge, the battery voltage rises to approach the charger output voltage, i.e. 53.5 volts and the
charging current decreases to the float current value of around 50 mA/100 AH for VRLA
batteries. So, when the charging current has stabilised at the float current for three
consecutive hours or the voltage across the battery bank terminals is constant for six
consecutive hours, then the battery bank can be considered as having reached full state of
charge.

If the charging voltage has been set at a value higher (but equal to or less than 2.30
VPC) than normal float voltage (so as to reduce charging time), it is normal practice to
reduce the charging voltage to the float value of 2.25V after 12 hrs. Then the float current
will soon stabilize and the above methods can be adopted for determining the state of charge.
CAUTION:

It was noticed in some of the exchanges during the normal course of day to day
working, the exchange failing due to low voltage condition even though the batteries appear
to be in healthy condition while they are on float as indicated by the daily readings recorded.
To avoid this it is recommended that the batteries be discharged periodically, say once in a
month by switching off the FR and the exchange load may be allowed to be taken by the
battery for half an hour. The individual cell readings are to be taken and no cell voltage
should fall below 2.10 V. Some cells which are faulty, may show negative values with

RTTC NAGPUR Page 66 of 68


reference to the other cells. If the voltage of any individual cell differs from others in this
manner it is recommended that the cell be replaced.
Table
% State of Charge Open Circuit Voltage
100 2.15
90 2.13
80 2.11
70 2.09
60 2.07
50 2.05
40 2.03
30 2.01
20 1.97
0 1.95
Float charging is at 2.23 VPC and the recommended boost charge voltage is 2.30 VPC.
If the charger does not have a float cum boost mode, it is important to switch over
to float after boost not later than 24 hours under steady current conditions.
Safety precautions
In normal use, VRLA batteries will not release hydrogen and oxygen gasses, will not
release acid mist and will not leak acid. Thus they are more safer than conventional lead acid
batteries. However, under abnormal conditions, or as a result of damage, misuse or abuse,
these potentially hazardous conditions can occur. Hence the instructions given by the supplier
is to be strictly followed.

Stacking limitation
The recommended limits on stacked battery configurations are as follows . See the
diagram also .

Module arrangements Max Modules


Horizontal single stack 8 High
Horizontal multiple stack 8 High

Module assembly
This design is arranged to provide the shortest connections between modules using
rigid lead coated copper strip connectors to maximise system performance
Modules are identified with a label located at the end of the module.
Each module is provided with a protective cover to prevent accidental contact with
module live electrical connections.

RTTC NAGPUR Page 67 of 68


Acceptance test for VLRA batteries
Charge the battery bank at 55.2v for 20 hours irrespective of the state of charge of the
battery. Keep the battery under open circuit for not less than 12 hours and not more than 24
hours . Then discharge the battery at a constant current of I = 0.1 x C 10 Amps. Stop discharge
when the voltage of the battery falls to 42.0 V irrespective of individual cell reading .
Time in hours elapsing between the beginning and end of discharge shall be taken as
period of discharge
The average ambient temperature during discharge shall be the average of the ambient
temperatures noted at hourly intervals during discharge.
Correction for variation of capacity with temperature to 27o C shall be made in
accordance with the formula given below

Capacity at 27o C = Ct + Ct x R (27 - t )


100

Where Ct = Obtained capacity at t o C


R = variation factor from the table shown below
t = average room temperature

Variation factor in
capacity per degree C
Discharge Rate
R percent
C10 0.43
C5 0.58
C3 0.68

The actual capacity corrected to 27o C shall not be less than 90 % of the rated capacity.
*****

RTTC NAGPUR Page 68 of 68

Vous aimerez peut-être aussi