Vous êtes sur la page 1sur 14

The 10 Steps in Design of Post-Tensioned Floors

Dr Bijan O Aalami
Professor Emeritus,
San Francisco State University Principal, ADAPT Corporation; bijan@PT-structures.com

301 Mission Street San Francisco, California High Seismic Force Region

www.adaptsoft.com

Column supported multistory building


Four Seasons Hotel; Florida High Wind Force Region

Two-way flat slab construction

Post-Tensioning Systems
Unbonded System
12.7 mm (0.5"*)

WIRE

CORROSION INHIBITING COATING

PLASTIC SHEATHING

NOTE: * NOMINAL DIAMETER

(a) STRAND

(b) TENDON

Multi-level parking structures One-way beam and slab design

GREASE FILLED PLASTIC CAP SHEATH TUBE

STRAND

(c) ANCHORAGE ASSEMBLY

Example of a Floor System using the Unbonded Post-tensioning System

Post-Tensioning Systems Grouted System

An example of a grouted system hardware with flat duct

Example of a Floor System Reinforced with Grouted Post-Tensioning System

Preliminary Considerations Design of Post-Tensioned Floors

Dimensions (sizing) Structural system

Optimum spans; optimum thickness One-way/two-way; slab band Service performance; strength condition

Boundary conditions; connections Load Path; Design strips Design sections; design values

Preliminary Considerations Design of Post-Tensioned Floors

Preliminary Considerations Design of Post-Tensioned Floors Selection of load path for two-way systems Design Strips

Dimensions (sizing)

Optimum spans; optimum thickness

An optimum design is one in which the


reinforcement determined for service condition is used in its entirety for strength condition. governed mostly by: Hypothetical tensile stresses (USA), or
crack width (EC2) Tendon spacing (USA)

PT amount in service condition is

Common spans: 25 30 ft (8 9 m) Span/thickness ratios


40 - 45 for interior 35 for exterior with no overhang

Subdivide the structure into design strips in two orthogonal directions


(Nahid slab)

Preliminary Considerations Design of Post-Tensioned Floors Subdivide the floor along support lines in design strips
1 A 2 3 4 5

Preliminary Considerations Design of Post-Tensioned Floors


Subdivide slab along support lines in design strips in the orthogonal direction
1 A B 2 3 4 5

C
C

D
D

E F

E F Y X G

Y X

An important aspect of load path selection in a two-way system is that every point of the slab should be assigned to a specific design strip. No portion of the slab should be left unassigned.

Preliminary Considerations Design of Post-Tensioned Floors

Design sections

Design sections extend over the entire

Design values

design strip and are considered at critical locations, such as face of support and mid-span

Actions, such as moments at each design


section are reduced to a single representative value to be used for design

559 is the area (total) value of bending moment at face of support

10 Steps Design of Post Tensioned Floors

Step 1 Geometry and Structural System

Select design strip and Idealize 1. Geometry and Structural System 2. Material Properties 3. Loads 4. Design Parameters 5. Actions due to Dead and Live Loads 6. Post-Tensioning 7. Code Check for Serviceability 8. Code Check for Strength 9. Check for Transfer of Prestressing 10. Detailing
square the boundary

Extract; straighten the support line;

Step 1 Geometry and Structural System

Step 2 Material Properties

Select design strip and Idealize

Extract; straighten the support line;

square the boundary Model the slab frame with a row of supports above and below. This represents an upper level of multi-story concrete frame. Assume rotational fixity at the far ends; Assume roller support at the far ends

Concrete

Weight 24 kN/m3 28 day cylinder 40 MPa Elastic modulus 35,220 MPa Long-term deflection factor 2 fy Elastic modulus
460 MPa 200,000 MPa

Non-Prestressed reinforcement

Prestressing

Strand diameter Strand area Ultimate strength Effective stress Elastic modulus

13 mm 99 mm2 1,860 MPa 1,200 MPa 193,000 MPa

View of idealized slab-frame

Step 3 Loads

Step 4 Design Parameters

Selfweight

Based on member volume Min (partitions)


1 kN/m2

Applicable code

Superimposed dead load Live load

ACI 318-11; EC2 EN 1992-1-1:2004 IBC 2012 Local codes, such as California Building
Code (CBC 2011); or otherwise

Residential Office Shopping mall Parking structure

2.0 kN/m2 2.5 kN/m2 3.5 kN/m2 2.0 kN/m2

Cover for protection against corrosion

Cover to rebar

Not exposed to weather


Exposed to weather

Lateral loads Wind Earthquake Example assumes


Superimposed DL Live load
SDL= 2 kN/m2 LL = 3 kN/m2

20 mm 50 mm

Cover to tendon

Not exposed to weather 20 mm Exposed to weather 25 mm

Step 4 Design Parameters

Step 4 Design Parameters

Cover for fire resistivity

Cover for fire resistivity


panels.

Identify restrained and unrestrained


panels.
Restrained or Unrestrained Aggregate Type 1 hr Unrestrained Carbonate Siliceous Lightweight Carbonate Siliceous Lightweight Cover Thickness, mm. for Fire Endurance of 1.5 hr 2 hr 40 40 40 20 20 20 3 hr 50 50 50 25 25 25 4 hr 30 30 30

Identify restrained and unrestrained

Restrained

For 2-hour fire resistivity


Restrained Unrestrained
20 mm. 40 mm

Step 4 Design Parameters

Step 4 Design Parameters

Allowable Stresses or Crack Width


Selection for Two-Way System Based on ACI

Allowable deflections (EC2/ approx. ACI)

Total load case

For

Tension 0.5fc 0.60fc Compression Sustained load case Tension 0.5fc Compression 0.60 fc

visual impact use total deflection Span/250 Use camber, if necessary

Total deflection subsequent to installation of


members that are likely to be damaged Span/350

Based on EC2

Frequent load case


Tension Ft = 0.30 fck (2/3) Compression 0.60fck Quasi permanent load case Tension Ft = 0.30 fck (2/3) Compression 0.45fck Crack width normal exposure (?) Unbonded Bonded

Immediate deflection due to live load Span/500 Long-term deflection magnifier 2. This brings
the total long-term deflection to 3,

Step 5 Actions due to Dead and Live Loads

Step 5 Actions due to Dead and Live Loads

Analyze the design strip as a single

In-house simple frame program


level frame structure with one row of supports above and below, using
(Simple Frame Method; SFM); or in-house Equivalent Frame Program (EFM); Specialty commercial software

Analyze the design strip as a single level


frame structure with one row of supports above and below.

All the three options yield safe designs.

But, each will give a different amount of reinforcement. The EFM is suggested by ACI-318. To some extent, it accounts for biaxial action of the prototype structure in the frame model. Accuracy and ability of commercial software for optimization varies

Step 6 Post-Tensioning

Step 6 Post-Tensioning Selection of PT force and profile

Selection of design parameters


Selection of PT force and profile Effective force/tendon selection option
- force selection

Two entry value assumptions must be made to


initiate the computations. Select precompression and % of DL to balance

Calculation of balanced loads;

adjustments for percentage of load balanced loads

Calculation of actions due to balanced

Step 6 Post-Tensioning

Step 6 Post-Tensioning
Assume simple parabola for hand calculation

Selection of design parameters

Select average precompression 1 MPa Target to balance 60% of DL Assume simple parabola mapped within
the bounds of top and bottom covers Force diagram of simple parabola

Selection of PT force and profile

STEP 6 Post-Tensioning Calculation of balanced loads;


adjustment of % of DL balanced
F121_ACI_PT_2_way_082012

STEP 6 Post-Tensioning
Calculation of balanced loads; adjustment of % of DL balanced
F121_ACI_2-way_PT_force_082012

Assume P/A =150psi[1MPa]


1

Select critical span


2

Select max drape

Select max drape using tendons from critical span

Calculate %of DL balanced (%DL)

Calculate %of DL balanced (%DL)


Yes %DL < 50%? No

P /A<300ps i [2MP a]? Yes Increase P/A No

No

%DL > 80%? Yes P/A>125psi [0.8MPa]?

No %DL > 80%?

Yes

No Reduce drape

Yes Reduce P/A

Is it practical to reduce P/A or tendons? No Yes

Go to next span

Rais e tendon to reach %DL ~ 60%

Reduce P/A or tendons to %DL balanced ~ 60% ; P/A >= 125 psi [0.8 MPa]

Member with widely different spans

Move to next span

Exit after last span

STEP 6 Post-Tensioning Calculation of balanced loads


Lateral forced from continuous tendons Lateral force from terminated tendons Moments from change in centroid of member

STEP 6 Post-Tensioning Calculation of balanced loads


Lateral forced from continuous tendons Lateral force from terminated tendons Moments from change in centroid of member

Force from terminated tendon

Example of force from continuous tendon

P = 500 k a = 93 mm ; b = 186 mm ; L = 9 m ; c = {[93/186]0.5/[1 + (93/186)0.5]} * 9.00 = 3.73 m Wb/tendon = 2 P*a/c2 = 119.0 kN * (2*93/1000)/3.732 = 119.0 kN / tendon * 0.013 / m =1.59 kN/m / tendon

L = 10 m ; a = 93 mm ; P = 119 kN; c =0.20*10 = 2.00 m Wb = (3 * 119.0 * 2 * 93 / 1000) / 2.02 16.60 kN/m Concentrated force at dead end = 2*16.60 = 33.20 k

STEP 6 Post-Tensioning Calculation of balanced loads


Lateral forced from continuous tendons Lateral force from terminated tendons Moments from change in centroid of member

STEP 6 Post-Tensioning Calculation of actions due to balanced loads


Check balanced loads for static equilibrium
Determine moments/shears from balanced loads applied the frame used for dead and live loads Note down reactions from balanced loads

Example of force from change in member centroid

Moment at face of drop = M M = P * shift in centroid =P * (Yt-Left Yt-Right) P = 23*119 kN; Yt-Left = 120 mm ; Yt-Right = 146 mm M= 23*119(120 146)/1000 = -71.16 kNm

STEP 6 Post-Tensioning Calculation of actions due to balanced loads


Obtain moments at face-of-supports and mid-spans
Note the reactions. The reactions are hyperstatic actions.

STEP 7 Code Check for Serviceability Code requirements for serviceability


Load combinations Stress/crack width check Minimum reinforcement Deflection check.
Load combination Frequent (Total) load condition 1.00DL + 0.50LL + 1.00PT Quasi Permanent (Sustained) load condition 1.00DL + 0.30LL + 1.00PT

Comments: Moments and precompression will be used for serviceability check. Reactions will be used for Strength check.

Stress check

Using engineering judgment, select the locations th likely to be critical. Typically, these are at the face of and for hand calculation at mid-span At each section selected for check, use the design a applicable to the entire design section and apply tho the entire cross-section of the design section to arri the hypothetical stresses used in code check. = (MD + 0.5ML + MPT) / S + P/A S = I/Yc ; I = second moment of area of ; Yc = distance to farthest tension fiber

STEP 7 Code Check for Serviceability ACI Minimum Reinforcement


F114_041112

STEP 7 Code Check for Serviceability ACI 318-11 Minimum Reinforcement


Rebar over support is function of geometry of the design strip and the strip in the orthogonal direction Rebar in span is a function of the magnitude of the hypothetical tensile stress

ACI Minimum Rebar for two-way systems


1 PT system? 2 Unbonded Bonded 9 `

At supports As = 0.0075Acf

Calculate the cracking moment Mcr at supports and spans Does Mcr exceeed 1.2xmoment capacity? No

10

In span calculate hypothetical tension stress ft

11

Yes 12

ft ? tension stress 6 No added rebar required

Add rebar to increase Moment capacity to 1.2 Mcr

ft > 2 root 'c [ft > 0.17 root f'c ]

ft =< 2 root 'c [ ft =< 0.17 root f'c ]

Add rebar to resist force in tensile zone

No added rebar required

As = 0.00075 * Acf
EXIT

As = Area of steel required Acf = Larger of cross-sectional area of the strip in direction of analysis and orthogonal to

STEP 7 Code Check for Serviceability ACI 318-11 Minimum Reinforcement


Rebar in span is a function of the magnitude of the hypothetical tensile stress

STEP 7 Code Check for Serviceability EC2 Minimum Reinforcement


Minimum based on cross-sectional area Minimum based on hypothetical tensile stress

In span, provide rebar if the hypothetical tensile stress exceeds 0.166fc The amount of reinforcement As is given by: As = N / (0.5*fy) where N is the tensile force in tension one

Based on cross-sectional area of section

Based on value of hypothetical tensile stresses for crack control Check probable crack width Add rebar based using the code

Asmin (0.26* fctm *bt*d / fyk) 0.0013* bt *d

h = member thickness; b = design section width

STEP 7 Deflection Check Read deflections from the frame analysis of the
design strip for dead, live and PT; (DL , LL , and PT ). . Make the following load combinations and check against the allowable values for each case Total Deflection (1 + 2)(DL + PT + 0.3 LL ) + 0.7 LL < span/250 This is on the premise of sustained load being 0.3 time the design live load. It is for visual effects; Provide camber to reduce value, where needed and practical Immediate deflection from live load immediate = 1.00L < span/500 This check is applicable, where non-structural members are likely to be damaged. Otherwise, span/240 applies Presence of members likely to be damaged from sustained deflection (1+ 2)(0.3 LL ) + 0.7 LL < span/350

STEP 8 Strength Check Steps in strength check


Load combinations Determination of hyperstatic actions Calculation of design moments (Mu) Calculate capacity/rebar for design moment Mu Check for punching shear Check/detail for unbalanced moment at support

Load combinations (EC2) U1 = 1.35DL + 1.50LL + 1.0HYP where, HYP is moment due to hyperstatic actions from prestressing Determination of Hyperstatic actions Direct Method based on reactions from balanced loads Indirect Method Using primary and post-tensioning moments

STEP 8 Strength Check


Determination of Hyperstatic actions Direct Method based on reactions from balanced loads

STEP 8 Strength Check


A comment on capacity versus demand Post-tensioned members possess both a positive and negative moment capacity along the member length Rebar needs to be added, where capacity falls short of demand First, find the capacity and compare it with demand

STEP 8 Strength Check


The figure below shows the forces on a PT member. In calculating the force from PT tendons, use either the code formulas or the following simplified procedure, based on parametric study of common building structures can be sued.

STEP 8 Strength Check


Check for adequate ductility ACI Ductility is deemed adequate, if c/dt <= 0.345 EC2 Ductility is deemed adequate, if c/h<= 0.43 h = member thickness This condition guarantees that steel will yield, before concrete in compression crushes.

USING EC2 Assume tendon stress under service condition 1,200 MP Assume tendon stress at ultimate limit state 1300 MPa USING ACI Tendon Length 38 m for single end stressing; ; length 35 m length 75 m double end stressing fps is conservatively 1,480 MPa if span is less than 11 m fps is conservatively 1,340 MPa if span is greater than

Punching Shear Design


PUNCHED OUT COLUMN REGION Mu

STEP 9 Check for Transfer of Prestressing At stressing: Tendon has its maximum force; Concrete is at its weakest strength; and Live load to counteract prestressing is absent
Hence the member is likely to experience stresses more severe than when in service Add rebar when representative

SHEAR STRESS DUE TO kM u

D108/SLIDES/060591

Vu

SHEAR STRESS DUE TO Vu

CRITICAL SURFACE

(hypothetical) tension stresses exceed a threshold


Do not exceed representative

hypothetical compressive stresses

TWO-WAY SLAB

ILLUSTRATION OF CRITICAL SURFACE FOR THE EVALUATION OF PUNCHING SHEAR STRESSES

Refer to ACI 318-11 section 11.11

STEP 9 Check for Transfer of Prestressing Load combination U = 1.00*Selfweight + 1.15*PT Tension stress Compression stress
STAGGER

STEP 10 Detailing

Position of rebar
MID-SPAN SEE PLAN EQ. EQ. STAGGER TOP REBAR AT SUPPORT TYP. DROP CAP COLUMN BOTTOM WALL SUPPORT EQ. EQ. EQ. EQ.

SUPPORT

Check for allowable stresses

If tension exceeds, provide rebar in tensile zone to resist Nc

If compression exceeds, wait until concrete


gains adequate strength
Lc/6

PLAN
POST-TENSIONED SLAB Lc/6

*
DROP COLUMN Lc/3 Lc SUPPORT LINE Ld

ELEVATION

Thank you for listening.

www.adaptsoft.com; bijan@adaptsoft.com

Vous aimerez peut-être aussi