Vous êtes sur la page 1sur 2

NRC30

Powerful and flexible digital control module for management of intelligent DC power systems

Key Features Advanced microprocessor technology with CAN bus communication Individual control of up to 31 rectifiers Automatic rectifier detection and configuration Hot-plug facility Measurement of input mains voltage and frequency (single, or three phase) Comprehensive battery management capabilities with battery voltage, current and temperature measurement and event history log Mapped Float Temperature Compensation curve for optimum battery charging Three battery charge modes available float, equalise and commissioning Battery discharge test with automatic/manual initiation Two levels of low voltage detection to enable initial disconnect of non-essential load Automatic detection of rectifier and system faults, with event history log Local and remote system alarm reporting (optional modem) Software-configurable Urgent and Non-urgent alarm outputs System security via passwordprotected, multi-level access Win30, Windows-compatible supervision software and webbased Java viewer available 19/subrack mounting options CE, UL marked For use with software: Win30, Javaview30 For use with rectifiers: SMi1800, SMi2800 For use in systems: MTP1800iC, MTP2800i, MTP2800iHP

Power

Reliability

81 SAFT Power Systems AEG SVS Power Systems Harmer

Simmons

NRC30
Powerful and flexible digital control module for management of intelligent DC power systems

SPECIFICATION
Input Input voltage Nominal current Battery Charge Modes

18 60Vdc 300mA (48V input) Float, Equalise, Commissioning, (Configurable float temperature compensation (FTC) curve), Four battery tapping points for monitoring of cell/string voltage balance Automatic programmable, or manually triggered battery test, (Test undertaken at constant discharge current)

Battery Test

Connections Alarm outputs Contact breaker inputs Load current measurement Battery current measurement Voltage measurement inputs Low voltage disconnect

Two software configurable volt-free changeover relay contacts (250Vac rating) Three opto-isolated inputs for detecting system contact breaker status (22-60V input range) Analogue input Analogue input Four analogue inputs for battery tapping point measurement LVD1 drive/feedback controls battery low voltage contactor, LVD2 drive/feedback controls non-essential load contactor

Mains measurement Voltage Frequency Communications

Single or three phase; range 0-305Vac L-N 0-65Hz, resolution 0.1Hz Direct RS232 connection* and optional modem connection*, or SNMP via Java Viewer (*Win30 Windows interface software package available) Industry standard communication protocol utilised (ANSI 1.317)

Protection Input EMC Safety

Internal input fusing EN55022-Class B, EN50082-2 Meets EN60950 and UL1950 requirements

Mechanical specification 19 mounting Weight Subrack mounting

44.4mm (1U) H, 445mm (19) W, 300mm D 3.6kg 129mm (3U) H, 71mm W, 256mm D Weight 0.8kg

Environmental Operating Temperature Altitude

-10C to +60C ambient 0 4000m operating

Power

Reliability
82

SAFT Power Systems

AEG SVS Power Systems

Harmer

Simmons