Ground Floor
Model Power input capacity (w) Unit Quantity Total Power input capacity Capacity ton Unit Quantity Total capacity tons MCS25BW 75.3 1 75.3 1.5 1 1.5 MCS20AW 127 0 0 2 0 0 MCS30AW 156 2 312 2.5 2 5 MCS40AW 183 0 0 3 0 0
1st Floor
Model Power input capacity (w) Quantity Total Power input capacity Capacity ton Quantity Total capacity tons MCS25BW 75.3 0 0 1.5 0 0 MCS20AW 127 0 0 2 0 0 MCS30AW 156 1 156 2.5 1 2.5 MCS40AW 183 0 0 3 0 0
2nd Floor
Model Power input capacity (w) Quantity Total Power input capacity Capacity ton Quantity Total capacity tons MCS25BW 75.3 8 602.4 1.5 8 12 MCS20AW 127 8 1016 2 8 16 MCS30AW 156 17 2652 2.5 17 42.5 MCS40AW 183 4 732 3 4 12
3rd Floor
Model Power input capacity (w) Quantity Total Power input capacity Capacity ton Quantity Total capacity tons MCS25BW 75.3 1 75.3 1.5 1 1.5 MCS20AW 127 10 1270 2 10 20 MCS30AW 156 24 3744 2.5 24 60 MCS40AW 183 5 915 3 5 15
4th Floor
Model Power input capacity (w) Quantity Total Power input capacity Capacity ton Quantity Total capacity tons MCS25BW 75.3 0 0 1.5 0 0 MCS20AW 127 7 889 2 7 14 MCS30AW 156 8 1248 2.5 8 20 MCS40AW 183 15 2745 3 15 45
1.5 0 0
2 1 2
2.5 0 0
3 1 3
Calculation
G.Floor FCU Watts 1st Floor FCU Watts 2nd Floor FCU Watts 3rd Floor FCU Watts 4th Floor FCU Watts 5th Floor FCU Watts Motorized valve Watts 2 Ch.W. Pumps Watts Mcquay Chiller Watts Power Consumed (Watts) Power Consumed (Kw) 387.3 156 5002.4 6004.3 4882 313 734.5 22000 219000 258479.5 258.4795
Formula= I= Watts*0.85/Volts
Ampere ? 258480 Rated Ampere = 500 0.85 219708
Formula= Volts*Ampere*1.73*PF*Time/1000=
440 500 1.73 0.85 1 Rated Consuming Units = 324 per hour
Chilled water living Temperature is 7 c Chilled water entering Temperature is 12 c Ambient Temperature is 35 c
Total
Total
Total
Total
Total
541.3 30 4882 9 30 79
Total
544.3 2 313
9 2 5
440
499.3363636
1000
323.51
Calculation
Ground Floor Amperes 1st Floor Amperes 2nd Floor Amperes 3rd Floor Amperes 4th Floor Amperes 5th Floor Elevator Room & Plant Room Amperes 2 Ch.W. Pumps Amperes Mcquay Chiller Amperes Total Amperes 1.69 0.69 8.5 9 14.5 1.2 40 346 421.58
Formula= Volts*Ampere*1.73*PF*Time/1000=
404 422 1.73 0.85 0.35
Chilled water living Temperature is 7 c Chilled water entering Temperature is 12 c Ambient Temperature is 28.5 c Room Temperature is 25 c Chilled water Temperature was 23 c
Note:-
Our chiller takes ampere as per living and ambient temperature requirement. The ampere should be variate according to the both of temperature. Chiller achieve own target temperature with in 35min its maximum time limit.
Suggestion:-
Prevent to any confusion about electric currant consuming please install an 3 phase submeter in the plant room panel. Then we maintain HVAC daily currant consuming sheet. Its better both of parties.
Sheet Example:Time 12:00pm To 13:00pm Previous reading present reading Total unit consum per hour Time 13:00pm To 14:00pm Previous reading present reading Total unit consum per hour
1000
87.7459114
390 76 To 346
rature requirement. The ampere should target temperature with in 35min its
consuming please install an 3 phase subt consuming sheet. Its better both of
Load Calculation
Maintenance Detail
McQuay CHILLER
Model MCS200.2ST022-FCE-E Power Input V / PH / Hz 380/3/50 Reted Power Input 219 kw Input (Amp) 500 Reted cooling (kw) 700 Reted cooling (Tons) 198.8636