Calculation

Ground Floor
Model Power input capacity (w) Unit Quantity Total Power input capacity Capacity ton Unit Quantity Total capacity tons MCS25BW 75.3 1 75.3 1.5 1 1.5 MCS20AW 127 0 0 2 0 0 MCS30AW 156 2 312 2.5 2 5 MCS40AW 183 0 0 3 0 0

1st Floor
Model Power input capacity (w) Quantity Total Power input capacity Capacity ton Quantity Total capacity tons MCS25BW 75.3 0 0 1.5 0 0 MCS20AW 127 0 0 2 0 0 MCS30AW 156 1 156 2.5 1 2.5 MCS40AW 183 0 0 3 0 0

2nd Floor
Model Power input capacity (w) Quantity Total Power input capacity Capacity ton Quantity Total capacity tons MCS25BW 75.3 8 602.4 1.5 8 12 MCS20AW 127 8 1016 2 8 16 MCS30AW 156 17 2652 2.5 17 42.5 MCS40AW 183 4 732 3 4 12

3rd Floor
Model Power input capacity (w) Quantity Total Power input capacity Capacity ton Quantity Total capacity tons MCS25BW 75.3 1 75.3 1.5 1 1.5 MCS20AW 127 10 1270 2 10 20 MCS30AW 156 24 3744 2.5 24 60 MCS40AW 183 5 915 3 5 15

4th Floor
Model Power input capacity (w) Quantity Total Power input capacity Capacity ton Quantity Total capacity tons MCS25BW 75.3 0 0 1.5 0 0 MCS20AW 127 7 889 2 7 14 MCS30AW 156 8 1248 2.5 8 20 MCS40AW 183 15 2745 3 15 45

5th Floor Elevator Room & Plant Room


Model Power input capacity (w) Quantity Total Power input capacity MCS25BW 75.3 0 0 MCS20AW 130 1 130 MCS30AW 156 0 0 MCS40AW 183 1 183

Capacity ton Quantity Total capacity tons

1.5 0 0

2 1 2

2.5 0 0

3 1 3

Calculation
G.Floor FCU Watts 1st Floor FCU Watts 2nd Floor FCU Watts 3rd Floor FCU Watts 4th Floor FCU Watts 5th Floor FCU Watts Motorized valve Watts 2 Ch.W. Pumps Watts Mcquay Chiller Watts Power Consumed (Watts) Power Consumed (Kw) 387.3 156 5002.4 6004.3 4882 313 734.5 22000 219000 258479.5 258.4795

Formula= I= Watts*0.85/Volts
Ampere ? 258480 Rated Ampere = 500 0.85 219708

Formula= Volts*Ampere*1.73*PF*Time/1000=
440 500 1.73 0.85 1 Rated Consuming Units = 324 per hour

Chilled water living Temperature is 7 c Chilled water entering Temperature is 12 c Ambient Temperature is 35 c

Total

541.3 3 387.3 9 3 6.5

Total

541.3 1 156 9 1 2.5

Total

541.3 37 5002.4 9 37 82.5

Total

541.3 40 6004.3 9 40 96.5

Total

541.3 30 4882 9 30 79

Total
544.3 2 313

9 2 5

440

499.3363636

1000

323.51

Calculation
Ground Floor Amperes 1st Floor Amperes 2nd Floor Amperes 3rd Floor Amperes 4th Floor Amperes 5th Floor Elevator Room & Plant Room Amperes 2 Ch.W. Pumps Amperes Mcquay Chiller Amperes Total Amperes 1.69 0.69 8.5 9 14.5 1.2 40 346 421.58

Formula= Volts*Ampere*1.73*PF*Time/1000=
404 422 1.73 0.85 0.35

Actual Consuming Units = 88 per 35min

Chilled water living Temperature is 7 c Chilled water entering Temperature is 12 c Ambient Temperature is 28.5 c Room Temperature is 25 c Chilled water Temperature was 23 c

Chiller LRA Chiller RLA

Note:-

Our chiller takes ampere as per living and ambient temperature requirement. The ampere should be variate according to the both of temperature. Chiller achieve own target temperature with in 35min its maximum time limit.

Suggestion:-

Prevent to any confusion about electric currant consuming please install an 3 phase submeter in the plant room panel. Then we maintain HVAC daily currant consuming sheet. Its better both of parties.

Sheet Example:Time 12:00pm To 13:00pm Previous reading present reading Total unit consum per hour Time 13:00pm To 14:00pm Previous reading present reading Total unit consum per hour

1000

87.7459114

Chiller LRA Chiller RLA

390 76 To 346

rature requirement. The ampere should target temperature with in 35min its

consuming please install an 3 phase subt consuming sheet. Its better both of

Load Calculation
Maintenance Detail

FAN COIL UNITS


Model Power Input In door (w) Input (Amp) Reted cooling (kw) BTU Model Power Input In door (w) Input (Amp) Reted cooling (kw) BTU Model Power Input In door (w) Input (Amp) Reted cooling (kw) BTU MCK25BW MCK20AW V / PH / Hz 230/1/50 V / PH / Hz 230/1/50 75.3 127 0.53 5.86 7.034 20000 24000 MCK30AW MCK40AW V / PH / Hz 230/1/50 V / PH / Hz 230/1/50 156 183 0.69 0.88 8.51 10.25 29500 35000 RCM25DW V / PH / Hz 230/1/50 130 6.448 22000

CHILLED WATER PUMP MOTOR


Model Power Input Reted Power Input Input (Amp) 1LA/163-2AA60 V / PH / Hz 380/3/50 11kw 25

McQuay CHILLER
Model MCS200.2ST022-FCE-E Power Input V / PH / Hz 380/3/50 Reted Power Input 219 kw Input (Amp) 500 Reted cooling (kw) 700 Reted cooling (Tons) 198.8636