NEMA 250

COPYRIGHT 2002; National Electrical Manufacturers Association

-| ||| | |||| | | ||| || |||| || || ||||| || | ---

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

COPYRIGHT 2002; National Electrical Manufacturers Association

-| ||| | |||| | | ||| || |||| || || ||||| || | ---

ANSI Approval Date August 30,2001

NEMA Standards Publication No. ANSIINEMA 250-1997 Enclosures for Electrical Equipment ( I O00 Volts Maximum)

Published by:

National Electrical Manufacturers Association 1300 North 17th Street, Suite 1847 Rosslyn, VA 22209

O Copyright 2001 by the National Electrical ManufacturersAssociation. All rights including translation into other languages, reserved under the Universal Copyright Convention, the Berne Convention for the Protection of Literary and Artistic Works, and the International and Pan American Copyright Conventions.

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

NOTICE AND DISCLAIMER

The information in this publication was considered technically sound by the consensus of persons engaged in the development and approval of the document at the time it was developed. Consensus does not necessarily mean that there is unanimous agreement among every person participating in the development of this document. The National Electrical Manufacturers Association (NEMA) standards and guideline publications, of which the document contained herein is one, are developed through a voluntary consensus standards development process. This process brings together volunteers and/or seeks out the views of persons who have an interest in the topic covered by this publication. While NEMA administers the process and establishes rules to promote fairness in the development of consensus, it does not write the document and it does not independently test, evaluate, or verify the accuracy or completeness of any information or the soundness of any judgments contained in its standards and guideline publications. NEMA disclaims liability for any personal injury, property, or other damages of any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the publication, use of, application, or reliance on this document. NEMA disclaims and makes no guaranty or warranty, expressed or implied, as to the accuracy or completeness of any information published herein, and disclaims and makes no warranty that the information in this document will fulfill any of your particular purposes or needs. NEMA does not undertake to guarantee the performance of any individual manufacturer or sellers products or services by virtue of this standard or guide. In publishing and making this document available, NEMA is not undertaking to render professional or other services for or on behalf of any person or entity, nor is NEMA undertaking to perform any duty owed by any person or entity to someone else. Anyone using this document should rely on his or her own independent judgment or, as appropriate, seek the advice of a competent professional in determining the exercise of reasonable care in any given circumstances. Information and other standards on the topic covered by this publication may be available from other sources, which the user may wish to consult for additional views or information not covered by this publication. NEMA has no power, nor does it undertake to police or enforce compliance with the contents of this document. NEMA does not certify, test, or inspect products, designs, or installations for safety or health purposes. Any certification or other statement of compliance with any health or safety-related information in this document shall not be attributable to NEMA and is solely the responsibility of the certifier or maker of the statement.

COPYRIGHT 2002; National Electrical Manufacturers Association

-| ||| | |||| | | ||| || |||| || || ||||| || | ---

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

S T D a N E M A 250-ENGL 1997
NEMA 250-1997 Page ii

b470247 051b480 Lb9 H

5.2.2 Ventilated Enclosures Test Method..............................................................................................19 5.2.3 Evaluation .....................................................................................................................................19 5.3 DRIP TEST ........................................................................................................................................... 19 5.3.1 Method A ....................................................................................................................................... 19 5.3.2 Method B....................................................................................................................................... 19 19 5.3.3 Evaluation ..................................................................................................................................... 5.4 RAIN TEST ........................................................................................................................................... 19 5.4.1 Method.......................................................................................................................................... 19 5.4.2 Evaluation ..................................................................................................................................... 20 5.5 DUST TEST .......................................................................................................................................... 23 5.5.1 Outdoor Dust Test ........................................................................................................................ 23 5.5.2 Indoor Dust Tests ......................................................................................................................... 24 5.6 EXTERNAL ICING TEST...................................................................................................................... 25 25 5.6.1 Test Method.................................................................................................................................. 5.6.2 Evaluation ..................................................................................................................................... 26 5.7 HOSEDOWN TEST .............................................................................................................................. 26 5.7.1 Test Method.................................................................................................................................. 26 5.7.2 Evaluation..................................................................................................................................... 26 5.8 Indoor Corrosion Protection (Rust-ResistanceTest (24-Hour Salt Spray Test)) ..................................26 5.8.1 Test Equipment.............................................................................................................................26 5.8.2 Salt Solution.................................................................................................................................. 27 5.8.3 Air Supply...................................................................................................................................... 27 5.8.4 Temperature ................................................................................................................................. 27 5.8.5 Test Procedure ............................................................................................................................. 27 27 5.8.6 Evaluation..................................................................................................................................... 5.9 OUTDOOR CORROSION PROTECTION ........................................................................................... 27 5.9.1 600 Hour Salt Spray Test.............................................................................................................. 27 5.9.2 Evaluation..................................................................................................................................... 27 5.9.3 1200 Hour Moist Carbon Dioxide .Sulfur Dioxide . Air Test ........................................................27 5.1 O TYPE 4X CORROSION PROTECTION ............................................................................................. 28 5.1 0.1 Evaluation................................................................................................................................... 28 28 5.1 1 SUBMERSION TEST.......................................................................................................................... .1Test Method................................................................................................................................ 28 5.1 i 5.1 1.2 Evaluation................................................................................................................................... 28 5.12 PRESSURE TEST .............................................................................................................................. 28 5.1 2.1 Alternate Tests............................................................................................................................ 28 5.13 OIL EXCLUSION TEST ...................................................................................................................... 29 29 5.13.1 Test Method................................................................................................................................ 5.13.2 Evaluation................................................................................................................................... 29 29 5.14 GASKET TESTS................................................................................................................................. 5.1 4.1 Aging Test................................................................................................................................... 29 5.14.2 Evaluation................................................................................................................................... 30 5.1 4.3 Oil immersiontest ....................................................................................................................... 30

APPENDIX A

..............................................................................................................................................

31

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

NEMA 250-1997 Page iii

FOREWORD
This Standards Publication covers the classification and description of enclosures for electrical equipment. Enclosures for rotating apparatus have not been included. The primary purpose of this publication is to permit a potential user to determine:
1. The type of enclosure appropriate for the application. 2. The features the enclosure is expected to have. 3. The tests applied to the enclosure to demonstrate its conformanceto the description.

These standards are used by the electrical industry to provide guidelines for the manufactureand proper application of enclosures and to promote the benefits of repetitive manufacturingand widespread enclosure availability.

Each type of enclosure is described in general and functional terms where practicable, and omits referenceto structural details and specific applications except where they are essential to the identification of the enclosure type. For such structural details and specific applications, see the appropriate NEMA product standards publication.
Individual product standards publications incorporating enclosure constructionunique to the product design may reflect the type of designations contained herein provided the design tests for such construction equal or exceed the requirements of these Standards Publication. User needs have been considered throughout the development of this publication. Proposed or recommended revisions should be submitted to: Vice President Engineering Department National Electrical Manufacturers Association 1300 N. 17th Street Suite 1847 Rosslyn, VA 22209 Publication250-1997 revises and supersedes Publication 250-1991.

This Standards Publication was developed by the NEMA Sections listed below. Section approval of the standard does not necessarily imply that all section members voted for its approval or participated in its development. At the time it was approved, the Sections were composed of the following members:
INDUSTRIAL CONTROL & SYSTEMS SECTION

AB6 Control, Inc.-Wichita Falls, TX Automatic Switch Company-Florham Park, NJ Baldor Electric Company-Woodinville, W A Balluff, Inc.-Florence, KY Bussmann Div/Cooper Indust.-Ellisville, MO CEGELEC Automation 1nc.-Pittsburgh, PA Control Concepts Corporation-Beaver, PA I Cutler-Hammer, Inc.-Milwaukee, W Cyberex, Inc.-Mentor, OH Eaton Corporation-Cutler Hammer-Milwaukee, WI Echelon-Palo Alto, CA Electrical Power Systems, Inc.-Tulsa, OK Electro Switch Corporation-Weymouth, MA Elliott Control Company-Hollister, CA Emerson Electric Company-Grand Island, NY

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

NEMA 250-1997
Page iv

Entrelec, Inc-Irving, TX Firetrol, Inc.-Cary, NC GE-Plainville, CT General Equipment & Mfg. Co., Inc.-Louisville, KY Gettys Corporation-Amherst, NY Giddings & Lewis, 1nc.-Fond Du Lac, WI Hamischfeger Corportion-Milwaukee, WI Honeywell IAD-Ft. Washington, PA Hubbell IncorporateckMadison, OH Joslyn Clark Controls, Inc.-lancaster, SC Killark Electric Mfg. Company-St. Louis, MO Klockner-Moeller Corporation-Franklin, MA Lexington Switch & ControtMadison, OH MagneTek, Inc.-New Berlin, WI Master Control Systems, Inc.-Lake Bluff, IL Metron, Inc.-Denver, CO Micro Switch-Freeport, IL 0-Z Gedneynit Of General Signal Corporation-Tulsa, OK Omron Electronics, Inc.-Schaumburg, IL Onan Corporation-Minneapolis, MN Pepperl + Fuchs, Inc.-Twinsburg, OH A Phoenix Contact, Inc.-Harrisburg, P R Stahl, Inc.-Woburn, MA Reliance Electric Co./Rockwell Automation-Euclid, OH Rittal Corporation-Springfield, OH Robicon-New Kensington, PA Rockwell Automation-Milwaukee, WI Russelectric, Inc.-Hingham, MA Siemens Energy & Automation, Inc.-Alpharetta, GA Siemens-Fumas Controls-Batavia, IL Sprecher & Schuh, Inc.-Houston. TX Square D Company-Lexington, KY Texas Instruments, Inc.-Dallas, TX Toshiba Intemational Corporation-Houston, TX Turck, Inc.-Minneapolis, MN WAG0 Corporation-Brown Deer, WI Yaskawa Electric America, Inc.-Northbrook, IL Zenith Controls, Incorporated-Chicago,IL

MOLED CASE BREAKER SECTION


ABB Control, Inc.-Wichita Falls, TX American Circuit Breaker Corp.-Albemarle, NC GE-Farmington, CT Cutler-Hammer Inc.-Piitsburgh, PA A Klockner-MoellerCotporation-Franklin, M Siemens Energy & Automation, Inc.-Norcross, GA SPD Technologies-Philadelphia, PA Square D Company-Cedar Rapids, IA Thomas & Betts Corporation-Memphis, TN
CONDU FITTINGS SECTION

Adalet-Plm-Cleveland, OH Appleton Electric Company-Chicago, IL Arlington Industries, Inc.-Scranton, PA Bridgeport F ~ n g sInc.-Bridgeport, , CT Crouse Hinds Division-Syracuse, NY Erico, Inc.-Solon, OH Halex Company, The-Cleveland, OH Hubbell Incorporated-Bridgeport, CT

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

NEMA 250-1997 Page v

Killark Electric Mfg. Company-St Louis, MO Minerallac Company-Addison, IL Myers Electric Products, Inc.-Fullerton, CA Neer ManufacturingCompany, Inc.-Lexington, OH 0-Z Gedney-Tenyville, CT Pass & Seymour/Legrand-Syracuse, NY Producto Electric Corporation-Orangeburg, NY . Progressive Machine Die, Inc.-Walton Hills, OH Raco, Inc.-South Bend, IN Red Dot DivisioMoston, MA Regal Manufacturing-Industry, CA Steel City-Memphis, TN Steel Electric Products Co, Inc.-Brooklyn, NY The Halex Company-Cleveland, OH Thepitt ManufacturingCo., 1nc.-Meadow Lands, PA Thomas & Betts Corporation-Memphis, TN

SWITCH SECTION
American Circuit Breaker Corp-Albemarle, NC Boltswitch, Inc.-Ctystal Lake, IL Bussmann Div/Cooper Industries-St. Louis, MO Cutler-Hammer Inc.-Pittsburgh, PA GE-Plainville, CT Hubbell Incorporated-Bridgeport, CT Pringle Electrical Mfg. Co., The-Fort Washington, PA Siemens Energy & Automation, Inc.-Norcross, GA Square D Company-Lexington, KY Test Switch Technology, Inc.-Canton, OH Thomas & Betts Corporation-Memphis, TN

PANELBOARDAND DISTRIBUTIONBOARD SECTION


American Circuit Breaker Corp.-Albemarle, NC B-Line Systems, 1nc.-Portland, OR Lamson & Sessions Company-Cleveland, OH Current Technology, Inc.-Irving, TX Cutler-Hammer Inc.-Pittsburgh, PA GE-Plainville, CT Hubbell Incorporated-Bridgeport, CT Milbank ManufacturingCompany-Kansas City, MO Penn Panel & Box Company-Collingdale, PA Pnngle Electrical Mfg. Co., The-Fort Washington, PA Siemens Energy 8 Automation, Inc.-Grand Prairie, TX Square D Company-Lexington, KY The Durham Company-Lebanon, MO Thomas & Betts Corporation-Memphis, TN

COPYRIGHT 2002; National Electrical Manufacturers Association

-| ||| | |||| | | ||| || |||| || || ||||| || | ---

PIN 81SLEEVE PLUG, RECEPTACLE& CONNECTOR SECTION


Adalet-Plm-Cleveland, OH Appleton Electric Company-Chicago, IL Arrow Hart Wiring Devicec-Syracuse, NY Bryant Electric, Inc.-Milford, CT Crouce Hinds Division-Syracuse, NY Hubbell Incorporated-Bridgeport, CT Joy Molded Rubber ProdJDiv. of Cooper Industries-Lagrange, NC Killark Electric Mfg. Company-St Louis, MO Meltric Corporation-Cudahy, WI

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

NEMA 250-1997 Page vi

Pass & SeymouriLegrand-Syracuse, NY R Stahl, Inc.-Woburn, MA Thomas & Betts MIPCO-Brooksville, FL Thomas & Betts Corporation-Memphis, TN W.T. Storey Inc.-Dalmatia, PA

STEEL RIGID CONDUIT & ELEC. METALLICTUBING SECTION


Allied Tube 8 Conduit Corporation-Harvey, IL Conduit Pipe Products-Westerville, OH LTV Steel Tubular Products Co.-Youngstown, OH OCAL, Inc.-Van Nuys, CA Perma-Cote Industries-Uniontown, PA Picoma Industries, Inc.-Waynesboro, PA Robroy Industries, Inc.-Verona, PA Shamrock Conduit Products, Inc.-Barnesville, OH Western Tube & Conduit Corp.-Long Beach, CA Wheatland Tube Company-Collingswood, NJ WIRING DEVICE SECTION AMP Incorporated-Harrisburg, PA Arrow Hart Wiring Devices-Syracuse, NY Bryant Electric, Inc.-Milford, CT Carlon Electrical Productc-Cleveland, OH Daniel Woodhead Company-Northbrook, IL Eagle Electric Mfg. Company, Inc.-Long Island City, NY Ericson Manufacturing Company -Willoughby, OH GE-Warwick, RI Hubbell Incorporated-Bridgeport, CT Leviton Manufacturing Company, Inc.-Little Neck, NY Lutron Electronics Company, Inc.-Coopersburg, PA Marinco/Marine Industries Company-Napa, CA McGill Electrical Product Group-Valparaiso, IN MYTECH Corporation-Austin, TX Pass & SeymourAegrand-Syracuse,NY Steel City-Memphis, TN Technology Research Corporation-Clearwater, FL The Wiremold Company-West Hartford, UNENCO Services, Inc.-Alameda, CA Watt Stopper, Inc, The-Canta Clara, CA Wiremoid Company, T h e W e s t Hartford, CT ELECTRICAL MEASURING EQUIPMENT SECTION
-| ||| | |||| | | ||| || |||| || || ||||| || | ---

ABB Power T & D Company Inc.-Raleigh, NC APTECH, Inc.-Charlotte, NC B-Line Systems, Inc.-Portland, OR GE-Somersworth, NH Meter Devices Company, Inc.-Canton, OH Milbank Manufacturing CompanyKansas City, MO Siemens Energy & Automation, Inc.-Norcross, GA Square D Company-Lexington, KY The Durham Company-Lebanon, MO Thomas & Betts Corporation-Memphis, TN

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

Section 1 GENERAL
1.1 SCOPE

This standard covers enclosures for electrical equipment rated not more than 1000 Volts and intended to be installed and used as follows: a. Non-hazardous locations 1. Enclosures for indoor locations, Types 1,2,5,12,12K, and 13; and 2. Enclosures for indoor or outdoor locations, Types 3,3R,3S,4,4X, 6, and 6P.

b. Hazardous locations 1. Enclosures for indoor locations, Types 7 and 9; 2. Enclosures for indoor or outdoor locations, Type 8; and 3 . Enclosures for mining applications, Type 10. Requirements for enclosures for non-hazardous locations are contained in the body of the standard. Requirements for enclosures for hazardous locations are contained in Supplement A of the standard. This standard covers the requirements to provide protection to the enclosed equipment against specific environmental conditions. This standard supplements requirements for enclosures that are contained in the individual product standards. This standard does not cover the requirements for protection of devices against conditions such as condensation, icing, corrosion, or contamination which may occur within the enclosure or which may enter via conduit or unsealed openings.
A product that contains features, characteristics, components, materials, or systems new or different from those in use when the standard was developed, and that involves a risk of fire, electric shock, or injury to persons shall be evaluated using the appropriate additional component and end-product requirements as determined necessary to maintain the level of safety for the user of the product as originally anticipated by the intent of this standard.

1.2

REFERENCES

The following publications are adopted in part, by reference in this publication, and are available from the organizations below.
1.2.1 Normative References The following normative documents contain provisions, which through reference in this text, constitute provisions of this Standards Publication. By reference herein these publications are adopted, in whole or in part as indicated, in this SP. American National Standards Institute (ANSI) 11 West 42nd Street New York, NY 10036 American Society of Mechanical Engineers (ASME) 345 East 47th Street New York, NY 1O017-2392

ANWASME 81.20.1 ANSVASME 894.1 1M

Pipe Threads, General Purpose (inch)


Twist Drills

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

STDONEMA 250-ENGL 1997


NEMA 250-1997 Page 2

b470247 051b48b b87

American Society for Testing and Materials (ASTM) 1 O0 Barr Harbor Drive West Conshohocken. PA 19428

ASTM A 6531A 653M ASTM B117 ASTM B555 ASTM 0471 ASTM ES27

Standard Specification for Steel Sheet, Zinc-Coated (Galvanized)or ZincIron Alloy-Coated (Galvannealed)by the Hot-Dip Process Salt Fog Testing Standard Guide for Measurement of ElectrodepositedMetallic Coating Thicknessby the Dropping Test ubber Prope@- ffect of Liquids ubber-Establishing Replacement Immersion Reference Oils for ASTM No. 2 and No. 3 Immersion Oils Used in Test Method 0471
International Electrotechnical Commission (IEC) 3, rue de Varemb P.O. Box 131 1211 Geneva 20 Switzerland

IEC 529

Degrees of protection provided by enclosures (IP Code)


National Electrical Manufacturers Association (NEMA) 1300 North 17th Street, Suite 1847 Rosslyn, VA 22209 National Fire Protection Association (NFPA) 1 Batterymarch Park PO Box 9101 Quincy, MA 02269

ANSIMFPA 70 ANSIMFPA 496 ANSIMFPA 497M


-| ||| | |||| | | ||| || |||| || || ||||| || | ---

National Electrical Code Purged and Pressurized Enclosures for Electrical Equipment Classification of Gases, Vapors and Dust for Electrical Equipment in Hazardous (Classified)Locations
Superintendent of Documents US Government Printing Office Washington, DC 20402

30 CFR Part 18

Electric Motor-Driven Mine Equipment and Accessories


Underwriters Laboratories Inc. (UL) 333 Pfingsten Road Northbrook, IL 60062

ANSIAJL 50 ANSIIUL 94 ANSVUL 514B ANSVUL 698 ANSINL 7466 ANSINL 877 ANSINL 886 ANSVUL 894

Enclosures for Electrical Equipment Tests for Flammability of Plastics Materials for Parts in Devices and Appliance Fittings for Conduit and Outlet Boxes Industrial Control Equipment for Use in Hazardous (Classified) Locations Poleric Materials Use in Electrical Equipment Evaluations Circuit Breakers and Circuit-BreakerEnclosures for Use in Hazardous (Classified) Locations Outlet Boxes and Fittings for Use in Hazardous (Classified) Locations Switches for Use in Hazardous (Classified)Locations

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

STD*NEMA 250-ENGL 3997

W b470247 051b487 513 W


NEMA 250-1997 Page 3

ANSIL 1332
--

Organic Coatings for Steel Enclosure for Oufdoor-UseElecfrical Equipment

COPYRIGHT 2002; National Electrical Manufacturers Association

| ||| | |||| | | ||| || |||| || || ||||| || | ---

1.3

DEFINiTIONS

The following definitions are applicable in this standard.


Cover: An unhinged portion of an enclosure that covers an opening. Degree of Protection: The extent of protection provided by an enclosure against access to hazardous parts, against ingress of foreign solid objects and/or against ingress of water and verified by standardized test methods. Design lests: Tests to demonstrate performance of a product designed to applicable standards. (Note: Design tests are not intended to be production tests.) Door: A hinged portion of an enclosure that covers an opening. Enclosure: A surrounding case constructed to provide a degree of protection to personnel against incidental contact with the enclosed equipment and to provide a degree of protection to the enclosed equipment against specified environmental conditions. Hazardous (Classified) Locations: Areas which may contain hazardous (classified) materials in sufficient quantity to create an explosion. (See Article 500 of the National Electrical Code.) Hazardous (Classified) Materiais: Gases, vapors, combustible dusts, fibers, or flyings which are explosive under certain conditions. incidental Contact: Accidental or unintentional contact. indoor Locations: Areas which are protected from exposure to the weather. Knockout: A portion of the wall of an enclosure so fashioned that it may be removed readily by a hammer, screw- driver, and pliers at the time of installation in order to provide a hole for the attachment of an auxiliary device or raceway, cable, or fitting. Non Hazardous Locations: Areas which do not contain hazardous (classified) materials in sufficient quantity to create an explosion. Nonventiiated: Constructed so as to provide no intentional circulation of extemal air through the enclosure. Oii-Resistant Gaskets: Gaskets made of material which is resistant to oil and oil fumes. Outdoor Locations: Areas which are exposed to the weather. Ventilated: Constructed so as to provide for the circulation of external air through the enclosure to remove excess heat, fumes, or vapors.

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

NEMA 250-1997 Page 5

Section 2
ENCLOSURE TYPES, FEATURES, AND APPLICATIONS
2.1
GENERAL

The features of each enclosure Type are applicable only when the enclosure is completely and properly installed.
All mechanical and electrical parts mounted on or through an enclosure shall pass the applicable tests for the enclosure Type unless otherwise specified.

2 . 2

SPECIFIC TYPES

Table 2-1 and Table 2-2 are guides for comparing specific applications of enclosures. The specific enclosure Types, their applications, and the environmental conditions they are designed to protect against are as follows:
Type 1 - Enclosures constructed for indoor use to provide a degree of protection to personnel against incidentalcontact with the enclosed equipment and to provide a degree of protection against falling dirt. Type 2 - Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment, to provide a degree of protection against falling dirt, and to provide a degree of protection against dripping and light splashing of liquids. Type 3 - Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust; and that will be undamaged by the extemal formation of ice on the enclosure. Type 3R - Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, and snow; and that will be undamaged by the external formation of ice on the enclosure. Type 3s Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust; and in which the external mechanism(s) remain operable when ice laden. Type 4 Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, and hose-directed water, and that will be undamaged by the external formation of ice on the enclosure. Type 4X - Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, hose-directed water, and corrosion; and that will be undamaged by the external formation of ice on the enclosure. Type 5 - Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against settling airborne dust, lint, fibers, and flyings; and to provide a degree of protection against dripping and light splashing of liquids.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

Previous page is blank


COPYRIGHT 2002; National Electrical Manufacturers Association Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

S T D - N E M A 250-ENGL 1997
NEMA 250-1997
Page 6

b470247 05Lb489 396 9

Type 6 Enclosures constructed for either indoor or outdoor use to provide a degree of protectionto personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against hosedirected water and the entry of water during occasional temporary submersion at a limited depth; and that will be undamaged by the extemal formation of ice on the enclosure. Type 6P - Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against hose-directed water and the entry of water during prolonged submersion at a limited depth; and that will be undamaged by the external formation of ice on the enclosure. Type 12 - Enclosures constructed (without knockouts) for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibers, and flyings; and against dripping and light splashing of liquids. Type 12K Enclosures constructed (with knockouts) for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibers, and flyings; and against dripping and light splashing of liquids. Type 13 - Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt: against circulating dust, lint, fibers, and flyings; and against the spraying, splashing, and seepage o f water, oil, and noncorrosive coolants.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

S T D * N E M A i50-ENGL 1797

9 b470247 05Lb470 008


NEMA 250-1997 Page 7

Table 2-1 Comparison of Specific Applications of Enclosures for Indoor Nonhazardous Locations
Type of Enclosure

Provides a Degreeof ProtectionAgainst the Following EnvironmentalConditions


Incidental contact with the enclosed equipment Falling dirt Falling liquids and light splashing Circulating dust, lint, fibers, and flyings ** Settling airborne dust, lint, fibers, and flyings ** Hosedown and splashing water Oil and coolant seepage Oil or coolant spraying and splashing Corrosive agents

1'

2"

4X

6P

12

12K

13

x x ...

x x x

x x x x x

x x x x x

x x x x ...

x x x x x

x x x x x

x x x x ...

x x x x

x x x x ... x

...
...

...
... ... ...
... ...

...

...........................................................................................

Occasional temporary submersion Occasional prolonged submersion


**

... ... ... ...

...
...
...

...
x

...
...

...

... ... ... ...

... ... x ...

...
x x x

... ... ... ...

... ... ... ...

... ... ...

These endosures may be ventilated. These fibers and flyings are nonhazardous materials and are not consideredClass 111 t y p e ignitable fibers or combustible flyings. For Class 111 type ignitable fibers or combustibleflyings see the National Electrical Code, Article 500.

Table 2-2 Comparison of Specific Applications of Enclosures for Outdoor Nonhazardous Locations
Type of Enclosure
|| | ---

Provides a Degreeof ProtectionAgainst the Following EnvironmentalConditions


Incidental contact with the enclosed equipment Rain, snow, and sleet ** Sleet *** ................................................................. Hosedown Corrosive agents .........................................

3
X

3R*
X X

3s
X
X X

4
X X

4x
X X

6P
X

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

... ... ...

1..

...
... ...

X X

...
...

... ...

... ...

Occasional temporary submersion Occasional prolonged submersion These enclosures may be ventilated.

...

** External operating mechanisms are not required to be operable when the enclosure is ice covered.

*** External operating mechanisms are operable when the enclosure i s ice covered. See 5.6.

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

--

||| |

Windblown dust, lint, fibers, and flyings

...

||||

. . . . . . . . . . . . . . . . . . . . . . . .

"

... X ... .................. ..........................................................................

...................

... . . . . . . . . X

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

...

...

| |

||| ||

|||| ||

|| |||||

Page 9

Section 3 CONSTRUCTION
3.1

GENERAL

The construction requirements in this Standard are supplemental to the construction requirements in the individual product standards. In cases o f conflict the product standards shall take precedence.
3.2 UNITS OF MEASUREMENT

Unless noted otherwise the first units of measurement shown in this standard are metric units. These measurementsare normally followed by an English unit of measurement in parenthesis. The units of measurement are intended as alternative measurements and are not intended to be exact conversions.
3.3 MATERIALS GENERAL
|| | ---| ||| | |||| | | ||| || |||| || || |||||

Enclosures shall be made of metal or polymeric materials which meet the requirements of 3.4.
3.4 MATERIALS POLYMERIC

A polymeric enclosure or a polymeric part of an enclosure necessaiy to maintainthe integrity of an electrical enclosure, shall comply with the applicable requirementsin the UL Standard for Polymeric Materials- Use in Electrical Equipment Evaluations, UL 746C and also with any additional requirements specified in this Standard.
A polymeric plug or other closure made of a material classed in accordance with the UL Standard for Tests for Flammability of Plastic Material for Parts in Devices and Appliances, UL 94 is acceptable under any one of the following conditions:

a. Not more than 650 mm2 (1 in2)in area and is: 1. Classed as 94-5VA, 94-5VB, 94V-O, 94V-1, or 94\1-23 or 2. Classed as 94HB and complies with the Flammability- 127 mm (5 inch) test in the UL Standard for Ptymeric Materials Use in Electrical Equipment Evaluations, UL 746C. b. More than 650 mm (1 in2) in area and is: 1. Classed as 94-5VA or'94-5VB and complies with the Resistance to Impact (normal and cold) test in the UL Standard for Polymeric Materials - Use in Electrical Equipment Evaluations, UL 746C; or 2 . Classed as 94V-O, 94V-II94V-2, or 94HB and complies with the Flammability 127 mm (5 inch) Flame and the resistance to Impact (normal and cold) test in the UL Standard for Polymeric Materials - Use in Electrical Equipment Evaluations, UL 746C.

3.5

CORROSION PROTECTION GENERAL

Enclosures shall not be constructed of metals in any combination such as to cause galvanic action which will adversely affect any part of the equipment exposed to moisture. Copper, bronze, brass containing at least 80 percent copper, stainless steel, or aluminum may be used without additional protection against corrosion. Hinges and other attachments used on an enclosure shall be resistant to corrosion and shall comply with the same requirements as the enclosure.
3.5.1

Indoor Corrosion Protection

Both the inside and outside surfaces of an enclosure made of ferrous material shall be protected against corrosion by enameling, galvanizing, or other equivalent means. Types 1,2, 5, 12, 12K,and 13

COPYRIGHT 2002; National Electrical Manufacturers Association

Previous page is blank

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

~~ ~

~~~~~

STD-NEMA 250-ENGL L997


NEMA 250-1997 Page 10

b470247 05Lb492 980

ferrous enclosures, and external ferrous parts attached to these enclosure Types and not protected by one of these means shall be tested as described in 5 . 8 .
3.5.2 Outdoor Corrosion Protection Types 3,3R, 3S, 4,4X, 6, and 6P ferrous enclosures, and extemal ferrous parts attached to these enclosure Types, shall be protected against corrosion by one of the coatings or finishes in 3.5.2.1 through 3.5.2.5. 3.5.2.1 Galvanized G90

Hot-dipped mill-galvanized sheet steel conforming with the coating Designation G90 in Table I of ASTM Designation A653lA653M-95.
3.5.2.2 Zinc Coating

A zinc coating, other than that provided on hot- dipped mill-galvanized sheet steel, uniformly applied to an average thickness of not less than 0.015 mm (0.00061 inch) on each surface with a minimum thickness of 0.014 mm (0.00054 inch). The thickness of coating shall be established by the metalliccoating-thickness test described in ASTM B555. An annealed coating shall comply with 3.5.3.

Zinc Coating with Paint A zinc coating conforming with 3.5.2.3.1 or 3.5.2.3.2 and with one coat of an organic finish of the epoxy or alkyd-resin type or other outdoor paint applied after forming on each surface. The acceptability of the paint may be determined by consideration of its composition or by corrosion tests if these are considered necessary.
3.52.3

3.5.2.3.1 Galvanized G60 Hot-dipped mill-galvanized sheet steel conforming with the coating Designation G60 or A60 in Table I of ASTM Designation A653lA653M-95. 3.5.2.3.2 Zinc Coating other than Galvanized
--

A zinc coating, other than that provided on hot- dipped mill-galvanized sheet steel, uniformly applied to an average thickness of not less than 0.010 mm (0.00041 inch) on each surface with a minimum thickness of 0.009 mm (0.00034 inch). The thickness of the coating shall be established by the metalliccoating-thickness test described in ASTM 8555.

COPYRIGHT 2002; National Electrical Manufacturers Association

| ||| | |||| | | ||| || |||| || || ||||| || | ---

3.5.2.4 Paint Paint may be accepted when the applicable requirements for Organic Coatings for Steel Enclosures for Outdoor Use Electrical Equipment, UL 1332, indicate that it provides equivalent protection.
3.5.2.5 Other Finishes

All other finishes shall comply with 5.9. 3.5.3 Annealed Coating An annealed coating on sheet steel that is bent or similarly formed or extruded or rolled at edges of holes after annealing shall be additionally painted in the affected area if the process damages the zinc coating. Bends and Forms on Zinc Coatings 3.5.4 If flaking or cracking of the zinc coating at the outside radius of the bent or formed section is visible at 25 power magnification, the zinc coating is considered to be damaged. Simple sheared or cut edges and punched holes are not required to be additionally protected.

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

h470247 051h493 317


NEMA 250-1997 Page 11

3.5.5 Hot Ripped Galvanized Damage A hot-dipped mill-galvanized G90 coating shall not be damaged during handling or fabrication to the extent that the base metal is exposed.

Exception No. 1: Uncoated cross-sectional surfaces at cut edges and drilled openings are acceptable. Exception No. 2: The base metal may be exposed if (1) the maximum width and length of the exposed metal does not exceed the thickness and length of any cut edge on the sheet or (2) the surface has one coat of an organic finish of the epoxy or alkyd-resin type, or other outdoor paint applied after fabrication. Sheet steel that employs a hotdipped mill-galvanized G90 coating that is drawn, formed, extruded, or rolled shall be additionally painted with one coat of an organic finish of the epoxy or alkyd-resin type or other outdoor paint in the areas that are affected by a process that damages the coating as determined by the requirement in 3.5.4.
3.5.6 Cast iron An enclosure of cast iron or malleable iron at least 3.2 mm (1/8 inch) thick shall be protected against corrosion by (1) a 0.0038 mm (0.00015 inch) thick coating of zinc, cadmium, or the equivalent, on the outside surface and a visible coating of such metal on the inside surface, or (2) one coat of an organic finish of the epoxy of alkyd-resin type or other outdoor paint on each surface. The acceptability of the paint may be determined by consideration of its composition or, if necessary, by the corrosion tests specified in 5.9. 3.5.7 Type 4X Corrosion Protection Type 4X enclosures, and extemal parts attached to these enclosures, shall be manufactured of Amencan Iron and Steel Institute (AISI) Type 304 Stainless steel, polymencs, or materials with equivalent corrosion resistance. If material other than Type 304 Stainless Steel is used it shall be tested in accordance with 5.9 and 5.10. 3.6 OPENINGS
|| ||||| -| ||| | |||| | | ||| || |||| || || | ---

Openings provided in an enclosure shall comply with the tests for the enclosure type with the openings unfilled except that openings in accordance with 3.6.1, if provided in the test enclosure, shall be filled to maintain the environmental integrity of the enclosure.
3.6.1 Equipment Openings All enclosures may be provided with openings intendedto be closed at installation by equipment. Such openings shall comply with the performance requirements in this standard and with the requirements in the appropriate end product standard when the intended equipment is installed. See 4.6. 3.6.2 Ventilation Type 1,2, and 3R enclosures may be ventilated. 3.6.3 Drainage Openings Type 2 and 3R enclosures shall have provisions for drainage. Drainage openings shall not be less than 3.2 mm in diameter (1/8 inch in diameter) or more than 6.4 mm in diameter (1/4 inch in diameter) unless baffled or provided with a drainage fitting.

For Type 2 and 3R enclosures that also meet the requirements of other enclosure types, the drainage openings shall be closed by a removable plug. The enclosure shall meet the requirements of the other enclosure types with the plug installed. See 4.7.

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

STD-NEMA 250-EMGL 3997 H 6470247 0536494 753 M


NEMA 250-1997 Page 12

3.7

MOUNTING

If mounting means are provided for Types 3,3S, 4,4X, 6,6P, 12,12K and 13 these means shall be external to the equipment cavity.
3.8
CONDUIT CONNECTION

Enclosures shall be designed for use with appropriate conductor entty provisions to maintain the specified environmental capability after proper installation.
3.9

HUBS AND FITTINGS

A conduit hub or fitting may be shipped separateiy if the necessary hardware, gaskets, and instructions are provided either with the enclosure or the fitting.
An enclosure provided without conduit hubs shall be marked in accordance with 4.5.
3.10

KNOCKOUTS

All enclosure types except Type 12 shall be permitted to have knockouts. When knockouts are provided, dimensions should be as shown in Table 3-1. Knockouts shall meet the appropriate design tests for the enclosure Type in which they are provided.

COPYRIGHT 2002; National Electrical Manufacturers Association

-| ||| | |||| | | ||| || |||| || || ||||| || | ---

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

Table 3-1 Knockout Dimensions


Conduit Size Trade Sue
11 2 314 1 1-114 1-112 2 2-11 2 3 3-1I2 4 5 6
I

Knockout Diameter, Inches Minimum


0.859 1.O94 1.359 1.71 9 1.958 2.433 2.938 3.563 4.063 4.563 5.625 6.700

Metric Designator
16 21 27 35 41
53 63 78

Nominal
0.875 1.109 1.375 1.734 1.984 2.469 2.969 3.594 4.125 4.641 5.71 9 6.813

Maximum
0.906 1.141 1.406 1.766 2.106 2.500 3.000 3.625 4.156 4.672 5.750 6.W

91
103

129 155

3.11

EXTERNAL OPERATING MECHANISMS

External operating mechanisms, when mounted on or through the enclosure, shall pass the applicable test for the enclosure Type unless otherwise specified. External operating mechanisms on a Type 3s enclosure shall support the additional weight of ice and shall withstand the removal of ice by a hand tool. See 5.6.2.
3.12 ACCESS TO INTERIOR

Type 3, 3R, 3S, 5, 12, and 12K enclosures shall require the use of a tool to gain access to the equipment cavity or shall have provisions for locking.
3.1 3 CLOSING HARDWARE

All closing hardware for Type 5, 12, 12K enclosures shall be captive.
3.14 GASKETS

A gasket of an elastomeric or thermoplastic material used to comply with the requirements for a Type 2, 3,3R, 3S, 4,4X, 5,6,6P, 12,12K, or 13 enclosure, shall be subjected to the tensile strength and elongation
tests in 5.14.1.
If gaskets are providedfor Type 12, 12K, and 13 enclosures they shall be oil resistant and shall comply with the Oil ImmersionTest in 5.14.3.
A gasket shall be secured with adhesive or by mechanical means. The gasket and its securing means shall not be damaged when the joint is opened.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

S T D - N E M A 250-ENGL 3997
NEMA 250-1 997 Page 14

b470247 051b49b 52b

3.15

OBSERVATION WINDOWS

A material covering an observation opening and forming a part of the enclosure shall be reliably secured in such a manner that it cannot be readily displaced in service, shall provide mechanical protection of the enclosed parts, and shall meet the requirements for the enclosure Type.
Glass used for an opening not more than 102 mm (not more than 4 inches) in any dimension shall not be less than 1.40 mm (not less than 0.055 inch) thick. Glass used for an opening having no dimension greater than 305 mm (greater than 12 inches) shall be not less than 2.92 mm (not less than 0.1 15 inch) thick. Glass used to cover a larger opening shall have the necessary mechanical strength and shall otherwise be acceptable for the purpose.

COPYRIGHT 2002; National Electrical Manufacturers Association

-| ||| | |||| | | ||| || |||| || || ||||| || | ---

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

Section 4
MARKING
4.1

TYPE DESIGNATIONS

Enclosures shall be designated by the Type number to indicate the environmental conditions for which they are suitable. See Section 2 and Table 2-1 and Table 2-2. Enclosures which meet the requirements for more than one Type enclosure may be designated by a combination of Type numbers, the lower number being given first.
4.2

SUPPLEMENTAL MARKINGS

Enclosures may be additionally marked with the following supplemental markings. These are relative terms for reference purposes only and do not imply enclosure capabilities.
Raintight A Type 3, 3S, 4,4X, 6, or 6P enclosure may be marked "Raintight". Rainproof - A Type 3R enclosure may be marked "Rainproof". Watertight A Type 4,4X, 6, or 6P enclosure may be marked "watertight". Corrosion Resistant A Type 4X or 6P enclosure may be marked "Corrosion Resistant". Driptight A Type 2,5,12,12K, or 13 enclosure may be marked "Driptight". Dusttight A Type 3,3S, 5,12,12K, or 13 enclosure may be marked "Dusttight".
4.3

LOCATION OF MARKINGS

Type designation and supplemental markings may be placed at any point on the inside or outside surface of the enclosure or door where they will be readily visible after installation. Other required markings may be provided in instructions provided with the enclosure
4.4

ENCLOSURE ORIENTATION

If the acceptability of a Type 2 or 3R enclosure is dependent upon a particular mounting orientation, the enclosure shall be marked to indicate the required orientation unless the mounting is obvious.

If a Type 2 or 3R enclosure has knockouts for conduit in the sides or back of the enclosure in which the equipment to be installed is not known, it shall be marked to indicate the area in which live parts are to be installed.

4.5

CONDUIT HUBS and CLOSURE PLATES

If a Type 3,3R or 3s enclosure has provisions for one or more field-installed separable conduit hubs or closure plates, the enclosure shall be marked with the name or trademark of the manufacturer of the hubs or plates, the catalog number, or conduit sizes of fittings that have been found acceptable for use with the enclosure. If the field-installed separable conduit hubs or closure plates are provided with the enclosure the marking may be omitted.
If a Type 3, 3R or 3s enclosure has no provisions for field installation of conduit hubs, the enclosure shall be marked to indicate that raintight hubs that comply with the requirements of the UL Standard for Fittings for Conduit and Outlet Boxes, UL 5148 are to be used.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

A Type 4,4X, 6 or 6P enclosure shall be marked to indicate that watertight fittings are to be used.

A Type 2,5,12,12K, or 13 enclosure shall be marked to indicate the type o f fittings to be used.
4.6 EQUIPMENT OPENINGS

Enclosures provided with equipment openings intended to be closed at installation by field installed equipment shall be marked to indicate that the field installed equipment shall be suitable for the same environmental conditions and shall be installed in accordance with the installation instructions provided.

4.7

DRAINAGE OPENINGS

Types 2 and 3R enclosures that also comply with other enclosure shall be provided with instructions indicating that the drainage hole plugs shall be removed for Type 2 or 3R applications and shall be in place for other applications.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

Section 5 DESIGN TESTS

5.1
-| ||| | |||| | | ||| || |||| || || ||||| || | ---

GENERAL

Each enclosure Type shall be evaluated to the specific design tests as outlined in Table 5-1 to demonstrate conformance with this standard. To assure realistic testing, the enclosure and its enclosed equipment shall be mounted as intended for use in service.

Table 5-1 Applicable Design Tests


Enclosure Type
1

Applicable Tests

Clause

Rod Entry Indoor Corrosion Protection


Rod Entry Drip Indoor Corrosion Protection Gasket Outdoor Dust External Icing Outdoor Corrosion Protection Gasket

5.2
5.8

5.2 5.3

5 . 8
5.14 5.5.1 5.6 5.9 5.14 5.2 5.4 5.6 5.9 5.14 5.5.1 5.6 5.9 5.14 5.6 5.7 5.9 5.14

.3R

Rod Entry Rain External Icing Outdoor Corrosion Protection Gasket


Outdoor Dust External Icing Outdoor Corrosion Protection Gasket External Icing Hosedown Outdoor Corrosion Protection Gasket

3s

Continued

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

STD*NEMA 250-ENGL 1997 m b470247 051b500 887


NEMA 250-1997 Page 18

Table 5-1 (Continued) Enclosure TYP


4x

Applicable Tests

Clause 5.6 5.7 5.9 5.10 5.14 5.5.2.2 5.8 5.1 4 5.6 5.7 5.9 5.1 1 5.1 4 5.6 5.7 5.9 5.1 O 5.12 5.14 5.5.2.1 5.8 5.14 5.8 5.13 5.14

External Icing Hosedown Outdoor Corrosion Protection 4X Corrosion Protection Gasket Settling Dust Indoor Corrosion Protection Gasket External icing Hosedown Outdoor Corrosion Protection Submersion Gasket Extemal icing Hosedown Outdoor Corrosion Protection 4X Corrosion Protection Air Pressure Gasket Circulating Dust Indoor Corrosion Protection Gasket indoor Corrosion Protection Oil Exclusion Gasket

6P

12,12K

13

5.2

ROD ENTRY TEST


This test is intended to simulate incidental contact with enclosed equipment.

5.2.1 Non-ventilated Enclosures Test Method For Nonventilated Enclosures with live parts located less than 102 mm (less than 4 inches) from the f 3.2 mm (a diameter of opening this test shall be made by attempting to insert a rod having a diameter o 1 1 8 inch).

For Nonventilated Enclosures with live parts located 102 mm or more (4 inches or more) from the opening this test shall be made by attempting to insert a rod having a diameter o f 12.7 mm (a diameter of 1 1 2 inch).

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

Page 19

5.2.2

Ventilated Enclosures Test Method

For Ventilated Enclosures with live parts located less than 102 mm (less than 4 inches) from the opening this test shall be made by attempting to insert a rod having a diameter of 12.7 mm (a diameter of 112 inch).
|| | ---| ||| | |||| | | ||| || |||| || || |||||

For Ventilated Enclosures with live parts located 102 mm or more (4 inches or more) from the opening this test shall be made by attempting to insert a rod having a diameter of 19 mm (a diameter of 314 inch).
5.2.3 Evaluation

The enclosure shall be considered to have met the requirements if the rod cannot enter the enclosure.
5.3

DRIP TEST This test is intended to simulate dripping and light splashing of liquids.

5.3.1 Method A The enclosure shall be mounted beneath a drip test apparatus which extends beyond all exposed sides o f the enclosure. The drip test apparatusahall be equipped with uniformly distributed drip sources. There shall be one drip source for each 129 cm (20 in2)of test surface area and each drip source shall have a drip rate of at least 20 drops of water per minute. The enclosure shall be subjected to continuously dripping water for 30 minutes.

Conduit shall be connected as intended.


5.3.2 Method B The enclosure with conduit connected shall be mounted as intended and the top exposed to a water spray falling for 1 hour at the rate of 25 1O mmh at any angle up to 15" from the vertical.

5.3.3 Evaluation A Type 2 enclosure shall be considered to have met the requirements if at the conclusion of the test there is no significant accumulation of water within the enclosure and no water has entered the enclosure at a level higher than the lowest live part.

Exception: Water shall be permitted to enter above live parts ifthe equipment is so constructed that no water is visible on the live parts, insulating material, or mechanism parts and no water has entered any space within the enclosure in which wiring may be present under any proper installation conditions.
5.4

RAIN TEST
This test is intended to simulate falling rain.
A device that meets the requirements of this test also meets the requirements of the Drip Test (5.3).

5.4.1

Method

A complete enclosure with conduit connected shall be mounted as in actual service except that the conduit shall be connected without using pipe thread sealing compound. Rigid conduit shall be threaded into the opening in the enclosure and tightened with the torque as specified in Table 5-2.
The test apparatus shall consist of at least three spray heads mounted in a water supply pipe rack as shown in Figure 5-1. Spray heads shall be constructed in accordance with the details shown in Figure 5-2.

f The enclosure is to be positioned in the focal area of the spray heads so that the greatest quantity o water is likely to enter the enclosure. The water pressure is to be maintained at 34.5 kPa (5 psi) at each spray head and a continuous water spray shall be applied for one hour.

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

5.49 Evaluation A Type 3R enclosure shall be considered to have met the requirements if at the conclusion of the test f water within the enclosure and no water has entered the enclosure there is no significant accumulation o at a level higher than the lowest live part. Exception: Water shall be permitted to enter above live parts if the equipment i s so constructed that no water is visible on the live parts, insulating material, or mechanism parts and no water has entered any space within the enclosure in which wiring may be present under any proper installation conditions.
|| ||||| -| ||| | |||| | | ||| || |||| || || | ---

Table 5-2 Tightening Torque


Torque Newton-Meters Pound-Inches

Conduit Size Trade Size Metric Designator

90.4 113
180.8

800 1 O00
1600

3/4and smaller 1, 1-1/4, and 1-1/2


2 and larger

2 1 and smaller 27,35, and 41 53 and larger

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

STDmNEMA 250-ENGL 1997

b470247 05Lb503 59b

m
NEMA 250-1997 Page 21

SEE DETAIL ' A I 7

Il

r WATER PRESSURE GAGE FOR EACH SPRAY HEAD

p IEZOMETER ASSEMBLY
DETAIL 'A'

EACH SPRAY HE

item
A

mm
71O 1400

inch
28

B
C

55
2-114 9 3

55
230
75

D
E

This material is repmduced, with pennission, from Undemiters Laboratories Inc. Standard for Safety for Enclosures for Electicai Equipment, UL 50, Copyright 1995 (by Underwriters Laboratories Inc.), copies of which may be purchased from Underwriters Laboratories lnc., Publications Stock, 333 Pfingsten Road, Northbrook, Illinois 662-296.

Figure 5-1 Rain-test spray-head piping

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

NEMA 250-1997 Page 22

STD-NEMA 250-ENGL 3997

= 6470247 053b504

422

COPYRIGHT 2002; National Electrical Manufacturers Association

-| ||| | |||| | | ||| || |||| || || ||||| || | ---

This material is reproduced, w i t h petmission, from Underwriters Laboratories inc. Standard for Safety for Enclosures for Electrical Equipment, UL 50, Copyright 1995 (by Underwritem Laboratories lnc.), copies of which mav be 'ourchased from Underwriters Laboratories Inc., Publications Stock, 333 hingsten Road, Norlhbrook, Iliinois 60062-2096:
~~

are available f r o mUnderwriters Laboratories

b ANWASME ~ 9 4 . 1 ~ 1r~ i isize i


Optional To serve as wench gdp.
~~

Figure 5-2 Rain-test spray head

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

STDmNEMA 250-ENGL 1997

= b470247 051ib505 3 b 9
NEMA 250-1997 Page 23

5.5
5.5.1

DUSTTEST
Outdoor Dust Test

This test is intended to simulate windblown dust.


A device that meets the requirements of this test also meets the requirements of the Circulating Dust Test (5.5.2.1), the Settling Dust Test (5.5.2.2), the Rod Entry Test ( 5 . 2 ) , the Drip Test (5.3), and the Rain Test (5.4).
5.5.1.1

Dust Blast Method

The enclosure shall be subjected to a blast of compressed air mixed with dry Type 1 general-purpose Portland cement, using a suction-type sand blast gun which is equipped with a 4.7 mm diameter (3/16 inch diameter) air jet and a 9.5 mm diameter (3/8 inch diameter) nozzle. The air shall be dry and at a pressure of 620 to 690 kPa (90 to 100 psi). The cement shall be applied at a rate of 2.27 kghinute (5 pounddmin). The nozzle shall be held 305 to 380 mm (12 to 15 inches) away from the enclosure, and the blast of air and cement shall be directed at all points of potential dust entry, such as seams, joints, external operating mechanisms, and so forth. The total volume of concrete sprayed shall be at least 5.9 kg per linear meter of test length (4 pounds per linear foot of test length). The test length is equal to the sum of the height, width, and depth o f the test specimen.

A conduit shall be permitted to be installed to equalize the internal and extemal pressures.
5.5.1.2 Evaluation The enclosure shall be considered to have met the requirements if at the conclusion of the test no dust has entered the enclosure.
5.5.1.3

Hose Method This test is an alternate to the Dust Blast Method described in 5.5.1.1,

The enclosure and its external mechanisms shall be subjected to a stream of water from a hose which has a 25 mm inside diameter (1 inch inside diameter) nozzle that delivers at least 170 Umin (45 gaVmin). The water shall be directed at all points of potential dust entry such as seams, joints, external operating mechanisms, and such from a distance of 3.0 to 3.5 m (10 to 12 feet). The nozzle shall be moved along each test point one time at a uniform nominal rate of 6 mmlsec (Y* inlsec).

A conduit shall be permitted to be installed to equalize internal and external pressures but shall not serve as a drain.
5.5.1.4 Evaluation
|| | ---| ||| | |||| | | ||| || |||| || || |||||

The enclosure shall be considered to have met the requirements if at the conclusion of the test no water has entered the enclosure.

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

5.5.2

Indoor Dust Tests

5.5.2.1 Circulating Dust Test This test is intended to simulate an indoor industrial environment of circulating dust, lint, fibers, and flyings.
A device that meets the requirements of this test also meets the requirements of the Settling Dust Test (5.5.2.2), the Rod Entry Test (5.2), and the Drip Test (5.3).

5.5.2.1.1 Dust Method The enclosure shall be placed in its intended mounting position in an airtight chamber having an internal volume not less than 0.169 m3 (6 fi3). The volume of the chamber shall be not less than 150 percent of the volume of the enclosure under test (L x W x H). The test chamber shall be maintained at ambient room temperature and 20-50 percent relative humidity.

At least 1.5 kg of dry Type 1 general-purpose Portland cement per cubic meter of test chamber (at least 1.5 ounces per cubic foot) shall be circulated by means of a blower suction unit for five minutes so as to completely envelop the enclosure under test. The air velocity at the outlet of the blower is to be maintained at approximately 305 &min (1O00 ft/min).
5.5.2.1.2 Evaluation Dust Method The enclosure shall be considered to have met the requirements if at the conclusion of the test no dust has entered the enclosure. 5.5.2.1.3 Atomized-Water Method (Method A) This test is an alternate to the Dust Method described in 5.5.2.1.1.

The enclosure shall be subjected to a spray of atomized water using a nozzle which produces a round pattern 75 to 100 rnm in diameter when measured 300 mm from the nozzle (3to 4 inches in diameter when measured 12 inches from the nozzle). The air pressure shall be 200 kPa (30psi) and the nozzle shall deliver water at a rate of 11.4 L (3gallons) per hour. The nozzle shall be held from 300 to 380 mm (12 to 15 inches) from the enclosure and the spray of water shall be directed at all points of potential dust entry such as seams, joints, external operating mechanisms, and such. The nozzle shall be moved along each test point one time at a uniform nominal rate of 6 mrrsec (Yi idsec).
A conduit shall be permitted to be installed to equalize the intemal and external pressures but shall not serve as a drain.

A seam is the junction of, or the joint between, two pieces. When two covers or doors are adjacent, their common edges shall be considered a single seam.

5.5.2.1.4

Evaluation Atomized Water Method (Method A)

The enclosure shall be considered to have met the requirements if at the conclusion of the test no water has entered the enclosure.
5.5.2.2 Settling Dust Test This test is intended to simulate an indoor industrial environment of settling airborne dust, lint, fibers, and fiyings.
A device that meets the requirements of this test also meets the requirements of the Rod Entiy Test (5.2) and the Drip Test ( 5 . 3 ) .

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

5.5.2.2.1 Dust Method

At least 0.85 kg of dry Type 1 General Purpose Portland cement per cubic meter of test chamber (at least 0.85 ounces per cubic foot) is to be circulated by means of a blower suction unit so as to completely envelop the enclosure under test. The air velocity at the outlet of the blower is to be 304.8 d m i n (1000 Wmin). The blower shall be cycled 15 seconds on and 30 seconds off for seven complete cycles.
5.5.2.2.2 Evaluation Dust Method

The enclosure shall be considered to have met the requirements ifat the conclusion of the test no dust has entered the enclosure.
5.5.2.2.3 Atomized-Water Method (Method B) This test is an alternate to the dust method described in 5 . 5 . 2 . 2 . 1 .
|| | ---| ||| | |||| | | ||| || |||| || || |||||

The enclosure shall be subjected to a spray of atomized water using a nozzle that produces a round pattern 75 to 100 mm in diameter when measured 300 mm from the nozzle (3to 4 inches in diameter when measured 12 inches from the nozzle). The air pressure shall be 170 kPa (25 psi) and the nozzle shall deliver water at a flowrate of 1 1.4 hour (3 gaihour). The nozzle shall be held from 460 to 530 mm (18 to 21 inches) away from the enclosure and the spray of water shall be directed at ali points of potential settling airborne dust entry such as seams, joints, external operating mechanisms, and such. The nozzle shall be moved along each test point one time at a uniform nominal rate of 11 mmls (7/16 irsec).

A conduit shall be permitted to be installed to equalize the internal and external pressure, but shall not serve as a drain.
A seam is the junction of, or the joint between, two pieces. When two covers or doors are adjacent, their common edges shall be considered a single seam.

5.5.2.2.4

Evaluation Atomized Water Test (Method B)

The enclosure shall be considered to have met the requirements if at the conclusion of the test no water has entered the enclosure.

5.6

EXTERNAL ICING TEST

This test is intended to simulate freezing rain, sleet, and snow.

A Type 3,3R, 4,4X, 6, and 6P enclosure which has no external cavities to trap water when mounted in the normal position shall be considered to be acceptable and need not be tested. 5.6.1 Test Method The enclosure shall be mounted in a room which can be cooled to -7C ( 2 0 F ) . A metal test bar which is 25.4 mm in diameter by 600 mm long (1 inch in diameter and 2 feet long) shall be mounted in a horizontal position in a location where it will receive the same general water spray as the enclosure under test.
Provision shall be made for spraying the entire enclosure from above with water at an angle of approximately 45 degrees from the vertical. The water shall be between 0C and 3C (32Fand 37F). Spraying facilities which provide between 40 and 80 L per hour per square meter (1 and 2 gallons per hour per square foot) of area to be sprayed have been found effective. The room temperature shall be lowered to 35F (2C). The spray of water shall be started and continued for at least 1 hour, maintaining the room temperature between 1 O C and 3C (33F and 37F).

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

STD-NEMA 250-ENG1 1997


NEMA 250-1997 Page 26

6470247 0516508 078

At the end of this time, the room temperature shall be lowered to between -7C and -3C (20F and 27F) while continuing the water spray. (The rate of change in the room temperature is not critical and shall be whatever is obtainable with the cooling means employed.) The water spray shall be controlled so as to cause ice to build up on the bar at a rate of approximately 6.35 mm/hour (1/4 inhour) and shall be continued until 20 mm (314 inch) of ice has formed on the top surface of the bar. The spray shall then be discontinued but the room temperature shall be maintained between -7C and -3C (20Fand 27F) for 3 hours to assure that all parts o f the enclosure and ice coatings have been equalized to a constant temperature.
5.6.2

Evaluation

A Type 3s enclosure and its extemal mechanisms shall be considered to have met the requirements of this test if while ice laden, they can be manually operated by one person without any damage to the enclosure, the enclosed equipment, or mechanism.

When an auxiliary mechanism is provided to break the ice, it shall be included and utilized in the test. A separate test is required for each maintained position of each external operator. If necessary, it shall be possible to gain access to the enclosure interior using an appropriate hand tool without causing functional damage to the enclosure.
A Type 3,3R, 4, 4X, 6, and 6P enclosure shall be considered to have met the requirements if at the conclusion of the test the enclosure is found to be undamaged after the ice has melted.

5.7

HOSEDOWN TEST

This test is intended to simulate a hosedown condition.


A device that meets the requirements of this test also meets the requirements of the Rod Entry Test

(5.2), Drip Test (5.3), Rain Test (5.4), and Dust Tests (5.5).
Test Method The enclosure and its external mechanisms shall be subjected to a stream of water from a hose which has a 25 mm inside diameter (1 inch inside diameter) nozzle that delivers at least 240 L per min (65 gallons per minute).
5.7.1

The nozzle shall be held from 3.0 to 3.5 m (10 to 12 feet) away from the enclosure and the spray of water shall be directed at all points of potential water entry such as seams, joints, external operating mechanisms, and such. The nozzle shall be moved along each test point one time at a uniform nominal rate of 6 mmlsec (W idsec).
A conduit shall be permitted to be installed to equalize internal and external pressures but shall not serve as a drain.

Evaluation The enclosure shall be considered to have met the requirements if at the conclusion of the test no water has entered the enclosure.
5.7.2
5.8

indoor Corrosion Protection (Rust-Resistance Test (24-Hour Salt Spray Test))

Unless the enclosures comply with 3.5.1, the enclosures, or representative parts of the enclosures, shall be subjected to the test described below or in Salt Spray (Fog) Testing, ASTM B117-1985.

Test Equipment The test apparatus shall consist of a fog chamber, a salt-solution reservoir, a supply of compressed air, atomizing nozzles, support for the enclosure, provision for heating the chamber, and means of control. It shall not permit drops of solution which accumulate on the ceiling or cover of the chamber to fall on the enclosure being tested, shall not permit drops of solution which fall from the enclosure to be returned to
5.8.1

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

~~

S T D = N E M A 250-ENGL 1997

6470247 051b509

TO4

NEMA 250-1997 Page 27

the solution reservoir for respraying, and shall be constructed of materials which will not affect the corrosiveness of the fog.
5.8.2 Salt Solution The salt solution shall be prepared by dissolving 5 parts by weight of salt in 95 parts by weight of either distilled water or water containing not more than 200 parts per million of total solids. The salt shall be sodium chloride which is substantially free of nickel and copper and which contains, when dry, not more than 0.1 percent of sodium iodide and not more than 0.3 percent of total impurities. 5.8.3 Air Supply The compressed air supply to the nozzle(s) for atomizing the sait solution shall be free of oil and dirt and shall be maintained between 69 and 172 kPa (between 10 and 25 psi). 5.8.4 Temperature The temperature of the salt spray chamber shall be maintained between 33C and 36C (between 92F and 97F). The noule(s) shall be directed or baffled so that none of the spray can impinge directly on the enclosure being tested. 5.8.5 Test Procedure The chamber shall be closed and the spray operated continuously except for the short daily interruption necessary to inspect, rearrange, or remove the test specimens, to check and replenish the solution in the reservoir, and to make necessaiy recordings.

The test shall be run continuously for 24 hours. At the end of the test, the specimens shall be removed from the chamber and washed in clean running water which i s not warmer than 38C (100F) to remove salt deposits from their surface, and then dried immediately. Corrosion products, other than rust, shall be permitted to be removed by light brushing if required, to observe the condition of the underlying stratum.
5.8.6 Evaluation The enclosure shall be consideredto have met the requirements of this test if there is no rust except at those points where protection is impractical, such as machined and mating surfaces of cast enclosures and sliding surfaces of hinges, shafts, and so forth. 5.9

OUTDOOR CORROSION PROTECTION

Finishes other than as described in 3.5.2.1 to 3.5.2.5, such as special metallic finishes, or metallic finish combined with paint shall be tested as described in 5.9.1 and 5.9.3.
5.9.1

600 Hour Salt Spray Test Comparative tests shall be conducted in accordance with 5.8 except the test time shall be 600 hours.

The comparison shall be with G90 galvanized sheet steel (without annealing, wiping, or other surface treatment) conforming with 3.5.2.1.
5.92

Evaluation

An enclosure shall be considered to have met the requirements of this test if upon completion it does not show pitting, cracking, or other deterioration more severe than that resulting from a similar test on G90 galvanized steel.
5.9.3 1200 Hour Moist Carbon Dioxide Sulfur Dioxide Air Test Tested and evaluated in accordance with UL 1332.

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

~~~

STDONEMA 250-ENGL 3997


NEMA 250-1997 Page 28

6470247 0536530 72b 9

5.10

TYPE 4X CORROSION PROTECTION

A Type 4X and 6P enclosure shall be tested with comparison tests in accordance with 5.8 except the test time shall be 200 hours.
The comparison shall be with Amencan Iron and Steel Institute Type 304 stainless steel.
5.10.1 Evaluation An enclosure shall be considered to have met the requirements of this test if upon completion it does not show pitting, cracking, or other deterioration more severe than that resulting from a similar test on passivatedAmerican Iron and Steel Institute Type 304 stainless steel. 5.11 SUBMERSION TEST

This test is intended to simulate temporary submersion at a limited depth.


A device that meets the requirements of this test also meets the requirements of the Rod Entry Test (5.2).

5.1 1.1 Test Method The complete enclosure shall be mounted in a tank with the conduit connected using pipe-thread sealing compound. The conduit shall be tightened with the toque values specified in Table 5-2.

The tank shall be filled with water so that the highest point of the enclosure is 1.8 m below the surface (6 feet below the surface) of the water. After 30 minutes, the enclosures shall be removed from the tank, the excess water removed from the surface of the enclosure, and the enclosure opened. The enclosure need not be submersed to a depth o f 1.8 m (depth of 6 feet) if an equivalent pressure differential between the interior and the exterior of the enclosure is maintained for the required period of time. This differential shall be permitted to be achieved either by reducing the air pressure inside the enclosure or pressurizing the water surrounding the enclosure.
5.11.2 Evaluation

The enclosure shall be considered to have met the requirements if at the conclusion of the test no water has entered the enclosure.
5.12 PRESSURE TEST

This test is intended to simulate prolonged submersion at a limited depth. A device that meets the requirements of this test also meets the requirements of the Rod Entry Test (5.2) and the Submersion Test (5.1 1).
5.12.1 Aiternate Tests

The internal PressurizationTest in 5.12.1.1 and the External Pressurization Test in 5.12.1.3 are alternate test methods and either may be conducted.
5.12.1.1 Internal PressurizationTest The complete enclosure with conduit, pressure gage, and check valve shall be pressure tested. The internal air pressure of the enclosure shall be raised to 40 kPa (6 psig) and the check valve closed. Aiter 24 hours the pressure shall be checked.

The conduit shall be connected using pipe-thread sealing compound and shall be tightened with the toque specified in Table 5-2.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

-~

STDmNEMA 250-ENGL 1777

6470247 05Lb5LL bb2

NEMA 250-1 997 Page 29

5.12.1.2 Evaluation Internal Pressurization The enclosure shall be considered to have met the requirements if at the conclusion of the test the internal pressure is a minimum of 26 kPa (4 psig) and there is no permanent deformation of the enclosure. 5.12.1.3 External Pressurization Test Submerge the complete enclosure, connected as intended for use, in water so that the highest point of the enclosure is 1 . 8m below the surface (6feet below the surface) for a period of 24 hours. The enclosure need not be submerged to a depth of 1 . 8 m (depth of 6 feet) if the equivalent pressure differential between the interior and exterior of the enclosure is maintained for the required period of time. This differential shall be permitted to be achieved by pressurizingthe water around the enclosure to simulate a depth of 1 . 8 m (depth of 6 feet). 5.12.1.4 Evaluation The enclosure shall be considered to have met the requirements if at the conclusion of the test no water has entered the enclosure.
5.13

OIL EXCLUSION TEST

This test is intended to simulate spraying water, oil and noncorrosive coolant. A device that meets the requirements of this test also meets the requirements of the Rod Entry Test ( 5 . 2 ) , the Rain Test (5.4), and the Dust Tests (5.5). The compatibility o f the gasket with other sealing materials and liquids to which it is exposed may have to be determined by tests.
5.13.1

Test Method

The enclosure shall be subjected to a stream of test liquid consisting of water and a wetting agent. The concentration of the wetting agent shall be approximately 0 . 1 percent by weight (or by volume if the wetting agent is liquid). The liquid shall be supplied through a nozzle with a 1 O mm diameter opening ( 3 1 8 inch diameter opening) which delivers at least 7 Umin (2gavrnin). Note: One such wetting agent is Rohm and Haas' Triton X-100. The stream shall be directed upon the enclosure from all angles from a distance of 300 to 460 mm (a distance of 12 to i8 inches) for 30 minutes. If the enclosure houses an externally operated device, the device shall be operated at a rate of approximately 30 operations per minute for the duration of the test. A conduit shall be permitted to be installed to equalize internal and extemal pressures but shall not serve as a drain.
5.13.2 Evaluation The enclosure shall be considered to have met the requirements if at the conclusion of the test no test liquid has entered the enclosure. 5.14

GASKET TESTS

5.14.1 Aging Test 3S,4,4X, 5,6,6P, 12,12K, or 13 enclosure shall be of such Gasket material used in a Type 2,3,3R, quality that samples subjected to a temperature of 69-70C (156-158F) in circulating air for 168 hours have a tensile strength of not less than 75% and an elongation of not less than 60% of values determined for unaged samples.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

~-

STDONEMA 250-ENGL LYY7


NEMA 250-1997 Page 30

~~

6470247 OSLbS12 STY

Evaluation f At the conclusion of the tests, there shall be no visible deterioration, deformation, melting, or cracking o the material and the material shall not harden as determined by normal hand flexing.
5.1 4 9

5.14.3 Oil immersiontest Gasket material, if used in a Type 12,12K, or 13 enclosure, shall not swell more than 25 percent or shrink more than 1 percent as a result of immersion in ASTM Reference Oil No. 3 (see the Standard l e s t Method for Rubber PropertyEffec of Liquids, ASTM D471-79, for oil specifications) or IRM Immersion Oil 903 (see ASTM ES27-94) for 70 hours at room temperature.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

STD-NEMA 250-ENGL I997 m 6470247 05Ib5L3 435 m


NEMA 250-1997 Page 31

APPENDIX A Comparison Between NEMA Enclosure Type Numbers and IEC Enclosure Classification Designations
IEC Publication 529 Classification of Degrees of Protection Provided by Enclosures provides a system for specifying the enclosures of electrical equipment on the basis of the degree of protection provided by the enclosure. IEC 529 does not specify degrees of protection against mechanical damage of equipment, risk of explosions, or conditions such as moisture (produced for example by condensation), corrosive vapors, fungus, or vermin. The NEMA Standard for Enclosures for Electrical Equipment does test for environmental conditions such as corrosion, rust, icing, oil, and coolants. For this reason, and because the test and evaluations for other characteristics are not identical, the IEC Enclosure Classification Designations cannot be exactly equated with the enclosure Type numbers in this Standard. The IEC designation consists of the letters IP followed by two numerals. The first characteristic numeral indicates the degree o f protection provided by the enclosure with respect to persons and solid foreign objects entering the enclosure. The second characteristic numeral indicates the degree of protection provided by the enclosure with respect to the harmful ingress of water. Table A-1 provides an equivalent conversion from the enclosure Type numbers in this Standard to the IEC Enclosure Classification Designations. The enclosure type numbers meet or exceed the test requirements for the associated IEC Classification; for this reason Table A-1 cannot be used to convert from IEC Classifications to enclosure Type numbers.

Table A-1
Conversion of EnclosureType numbers to IEC ClassificationDesignations (Cannot be used to convert IEC ClassificationDesignations to NEMA Type numbers)
Enclosure
Type Number

I
I

IEC Endosure Classification Deslgnaion

1
2
3 3R

IP1o IP11 IPS IP14

3s
4 and 4X

IP54
IP56

5
6 AND 6P 12 AND 12K
13

I P52
IP67 IP52

IP54

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

NEMA 250-1997 Page 32

Supplement A
DESCRIPTIONS, APPLICATIO IS, FEATURES, AND TEST CRITERIA OF Ei CLOSURES FOR HAZARDOUS (CLASSIFIED) LOCATIONS SA1.l GENERAL

Type 7 and 10 enclosures, when properly installed and maintained, are designed to contain an internal explosion without causing an extemal hazard. Type 8 enclosures are deigned to prevent combustion through the use of oil-immersed equipment. Type 9 enclosures are designed to prevent the ignition of combustible dust. Hazardous locations (other than in mines) are classified according to the flammability or combustibility of the materials which may be present and also according to the likelihood that a flammable or combustible concentration is present (For definitions and classifications see the National Electrical Code, Article 500, and ANSVNFPA 497M, Classificationof Gases, Vapors and Dust for Electrical Equipment in Hazardous (C/assjfied)Locations. Descriptions and tests in this standards publication cover equipment which is suitable for installation in locations classed as Division 1 or Division 2. In Division 2 locations, other types of protection and enclosures for nonhazardous locations may be installed if the equipment does not constitute a source of ignition under normal operating conditions. (See the specific sections of Articles 501 through 503 of the National Electrical Code.) Enclosures for non-hazardous locations described in the main part of this standards publication which have met the requirements of the dust test described in 5.5, may be used in Class II,Group G, Division 2, and Class III, Division 1 and 2 locations. Hazards may he reduced or eliminated and equipment installed in enclosures suitable for nonhazardous locations by adequate positive pressure ventilation from a source of clean air in conjunction with effective safeguards against ventilation failure. See ANSINFPA '496, Purged and Pressunied Enclosures for Electrical Equipment, for detailed requirements.

SA2.1

SPECIFIC TYPES

Table SA-1 is a guide for comparing specific applications of enclosures. The specific enclosure Types, their applications, and the environmental conditions they are designed to protect against are as follows:
Type 7 - Enclosures constructed for indoor use in hazardous locations classified as Class I, Division 1, Groups A, B, C, or D as defined in NFPA 70. Type 8 - Enclosures constructed for either indoor or outdoor use in hazardous locations classified as Class I, Division 1, Groups A, B, C, and D as defined in NFPA 70. Type 9 Enclosures constructed for indoor use in hazardous locations classified as Class II, Division 1, Groups E,F, or G as defined in NFPA 70. Type 10 - Enclosures constructed to meet the requirements of the Mine Safety and Health Administration, 30 CFR, Part 18.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

STD*NEflA 250-ENGL 1997

6470247 051b5L5 208

m
NtMA 250-1997

Page 33

Table SA-1 Comparison of Specific Applications of Enclosures for Indoor Hazardous Locations (If the installation is outdoors and/or additional protection is required by Table 2-1 and Table 2-2, a combination-type enclosure is required)
Provides a Degree of Protection Against Atmospheres Typically Containing EnclosureTypes 7 and 8, Class I Groups ** Enclosure Type 9 Class II Groups

(SeeNFPA 497M for Complete Listing)

Class
I

A X

Acetylene Hydrogen, manufacturedgas Diethyl ether, ethylene, cyclopropane Gasoline, hexane, butane, naphtha, propane, acetone, toluene, isoprene Metal dust Carbon black, coal dust, coke dust Flour, starch, grain dust Fibers, flyings Methane with or without coal dust

...
X

I I
II
II

... ...
...

... ...
x ...

... ... ...

... ... ...


x
... ... ... ... ...

...

...

... ...
...
x

...
...
... ... x ... ... ...

... ... ... ...


...

... ... ...


...

II III MSHA

... ... ... ...

... ...
... ...

... ...

...
. . 1

... ... ...

...
x x

... ... ... ...


x

...

...

...

...

* For Class Ili type ignitable fibers or combustible flyings see the National Electrical Code, Article 500. ** Due to the characteristicsof the gas, vapor, or dust, a product suitable for one Class or Group may not be suitable for another

C l a s s or Group unless marked on the product.

SA3.1

ENCLOSURE FEATURES

SA3.1.1 Type 7 Enclosures

Type 7 enclosures shall be capable of withstanding the pressures resulting from an intemal explosion of specified gases, and contain such an explosion sufficientthat an explosive gas-air mixture existing in the atmosphere surrounding the enclosure will not be ignited. Enclosed heat generating devices shall not cause external surfaces to reach temperatures capable of igniting explosive gas-air mixtures in the surrounding atmosphere. Enclosures shall meet explosion, hydrostatic, and temperature design tests. When completely and properly installed Type 7 enclosures: a. Provide a degree of protectionto a hazardous gas environment from an internal explosion or from operation of internal equipment b. Do not develop surface temperatures which exceed prescribed limits for the specific gas corresponding to the atmospheres for which the enclosure is intended, when internal equipment is operated at rated load. c. Withstand a series of internal explosion design tests which determine: 1. The maximum pressure effects of the gas mixture. 2. Propagation effects of the gas mixtures. d. Withstand, without rupture or permanent distortion, an intemal hydrostatic design test based on the maximum intemal pressure obtained during explosion tests and on a specified safety factor. e. Are marked with the appropriate Class and Group(s)for which they have been qualified.
SA3.1.2 Type 8 Enclosures

Type 8 enclosures and enclosed devices are arranged such that all arcing contacts, connections, and so forth, are immersed in oil. Arcing is confined under the oil such that it will not ignite an explosive mixture of the specified gases in intemal spaces above the oil or in the atmosphere surrounding the

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

____

STD-NEMA 250-ENGL 1977 m b470247 051b51b 144 m


NEMA 250-1997 Page 34

enclosure. Enclosed heat generating devices shall not cause external surfaces to reach temperatures capable of igniting explosive gas-air mixtures in the surrounding atmosphere. Enclosures shall meet operation and temperature design tests. Enclosures intended for outdoor use shall also meet the rain test. When completely and properly installed, Type 8 enclosures: a. Provide, by oil immersion, a degree of protection to a hazardous gas environment from operation of internal equipment. b. Do not develop surface temperatures which exceed prescribed limits for the specific gas corresponding to the atmospheres for which the enclosure is intended, when internal equipment is at rated load. c. Withstand a series of operation design tests with oil levels arbitrarily reduced and with flammable gas-air mixtures introduced above the oil. d. When intended for installation outdoors, shall exclude water under test conditions which are intended to simulate rain. e. Are marked with the appropriate Class and Group@)for which they have been qualified.
SA3.2.3 Type 9 Enclosures

Type 9 enclosures shall be capable of preventing the entrance of dust. Enclosed heat generating devices shall not cause external surfaces to reach temperatures capable of igniting or discoloring dust on the enclosure or igniting dust-air mixtures in the surrounding atmosphere. Enclosures shall meet dust penetration and temperature design tests, and aging of gaskets (if used). When completely and properly installed, Type 9 enclosures: a. Provide a degree of protection to a hazardous dust environment from operation of internal equipment. b. Do not develop surface temperatures which exceed prescribed limits for the Group corresponding to the atmospheres for which the enclosure is intended, when internal equipment is operated at rated load. c. Withstand a cenes of operation design tests while exposed to a circulating dust mixture, to determine that dust does not enter the enclosure and that operation of devices does not cause ignition of the surrounding atmosphere. d. Are marked with the appropriate Class and Group(s) for which they have been qualified. SA3.1.4 Type 10 Endosures Nonventilated Type 10 Enclosures are constructed for mine use and to meet the requirements of the Mine Safety and Health Administration.
SA4.1

ENCLOSURETEST CRITERIA

SA4.1.1 Type 7 Enclosures


Type 7 enclosures shall he tested and evaluated in accordance with the applicable portions of: a. ANSINL 698. Industrial Control Equipment for Use in Hazardous (Classified) Locations. b. ANSWL 877, Circuit Breakers and Circuit Breaker Enclosures for Use in Hazardous (Classified) Locations. c. ANSVUL 886, Outlet Boxes and Fittings for Use in Hazardous (Classified) Locations, d. ANSILJL894. Switches for Use in Hazardous (Classified) Locations.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

STDmNEMA 250-ENGL 1997

b470247 051b517 080

NEMA 250-1997 Page 35

SA4.1.2 Type 8 Enclosures

Type 8 enclosures shall be tested and evaluated in accordance with the applicable portions of: a. ANSIAJL 698, Industrial Control Equipment for Use in Hazardous (C/assified)Locations. b. ANSVUL 877, Circuit Breakers and Circuit- Breaker Enclosures for Use in Hazardous (classified) Locations. c. Rain test described in 5.4.
SA4.1.3 Type 9 Enclosures
-| ||| | |||| | | ||| || |||| || || ||||| || | ---

Type 9 enclosures shall be tested and evaluated in accordance with the applicable portions of: a. ANSIAJL 698, Industrial Control Equipment for Use in Hazardous (Classified) Locations. b. ANSIAJL 877, Circuit Breakers and Circuit Breaker Enclosures for Use in Hazardous (Classified) Locations. c. ANSI/UL 886, Outlet Boxes and Fittings for Use in Hazardous (classified)Locations. d. ANSIAJL 894, Switches for Use in Hazardous (Classified) Locations.
SA4.1.4 Type 10 Enclosures

The design test for Type 10 enclosures shall be in accordance with the Mine Safety and Health Administration, 30 CFR, Part 18.

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

COPYRIGHT 2002; National Electrical Manufacturers Association

Document provided by IHS Licensee=Aramco HQ/9980755100, User=, 09/12/2002 04:42:34 MDT Questions or comments about this message: please call the Document Policy Management Group at 1-800-451-1584.

--

||| |

||||

| |

||| ||

|||| ||

|| |||||

|| | ---