DATA SHEET
PROJECT NAME: AN HOI DIESEL POWER PLANT CLIENT: CON DAO COMMITTEE PROJECT NO.:
REV. NO.
DATE
DESCRIPTION
PREP'N
REVIEW
CHECK
APPROVAL
PREP'N
REVIEW
CHECK
APPROVAL
PAGE: 1 of 9
DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
0
Service Description:
22000 50 N/A
V Hz
5% 2%
Non-Hazardous
UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
Standard of Manufacture Type Location Rated voltage Rated frequency Number of phases Rated lightning impulse withstand voltage (IEC 60694) Rated short duration power frequency w'stand voltage Rated short time withstand current and time Internal arc fault withstand, to IEC 60298 Annex AA Duration of internal arc fault test Rated peak withstand current Earth busbar withstand current and time Busbar system: Rated normal current (main busbar) Phase segregated busbars Busbar arrangement (Single / Duplicate) Busbar identification Busbar material Busbar insulation Future busbar extension at either end Yes/No Yes/No A Yes / No 400 VTA Single Colour coded (R-Y-B) HDHC copper Yes No secs kA (peak) kA (rms) kV (peak) kV (rms) kA (rms) kV Hz Air insulated, metal enclosed Indoor, non-hazardous 24 50 3 95 50 (1 minute) 12.5 kA for 1 secs Criteria 1 through 6 1 125 12.5 kA for 1 secs
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
49 50
PAGE: 2 of 9
DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
0
Service Description:
MV SWICHGEAR
ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 C Outdoor Max: Altitude: 40 C < 1000m System Voltage: System Frequency: Neutral Earthing:
Isolated neutral
VENDOR'S RESPONSE
Power consumption Panel exterior paint colour Panel interior paint colour
Paint specification Overall dimensions of the switchboard: Total weight Largest shipping section dimensions Shipping sections (number and weights) Expected assembly heat dissipation Ingress protection rating Earthing: Method of busbar earthing Rated short circuit current and time Asymmetrical peak making current capability Key interlock kA kA pk Yes/No (L X W x H) LxWxH mm kg mm kg kW
VTA
VTA (Note 7) VTA VTA VTA VTA
IP42
TEST REQUIREMENTS
0
41 42 43 44 45 46 47 48 49
0
50 51 52 53
PAGE: 3 of 9
DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55
0
Service Description:
MV SWICHGEAR
ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 C Outdoor Max: Altitude: 40 C < 1000m System Voltage: System Frequency: Neutral Earthing:
Isolated neutral
PARTICULARS OF EQUIPMENT CIRCUIT BREAKER PANEL DATA (* Current Rating Amps) Number of circuit breakers Panel type Rated normal current Rated voltage Rated short time withstand current and time Rated peak withstand current Rated short circuit breaking current Rated dc component of short circuit breaking current Insulation levels: Rated lightning impulse withstand voltage (IEC 60694) Rated short duration power frequency withstand voltage Trip coil: Voltage Power Close coil: Voltage Power Circuit breaker closing time Circuit breaker opening time Mechanical endurance Electrical endurance Anti pumping device Mechanical operations counter Manual mechanical trip facility Closed/open position indication Charged/discharged spring indication Emergency shutdown (ESD) trip Load shedding trip Power cable entry Control cable entry Gland plate
No.
A
0
110 kV across contacts 60 kV across contacts for 1 min 230 VAC (from UPS source) VTA N/A N/A VTA VTA VTA VTA Yes Yes Yes Yes
0
(D x W x H)
mm
0
VTA
"Closed" indication (Red) "Open" indication (Green) Tripped circuit or blown fuse indication (Amber) Anti-condensation heater 'ON' indication Indication Earth switchgear Free contacts for remote Indications HV switchgear Closed HV switchgear opened Earth switch connected / disconnected
Yes/No
0
56
PAGE: 4 of 9
DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
0
Service Description:
MV SWICHGEAR
ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 C Outdoor Max: Altitude: 40 C < 1000m System Voltage: System Frequency: Neutral Earthing:
Isolated neutral
PARTICULARS OF EQUIPMENT
Control mode
0
Ammeter & selector switch Voltmeter & selector switch Trip & control circuit supervision Digital multimeter functions Relay Types Differential Feeder Protection Lockout Trip Circuit Supervision Under voltage/Overvoltage Other
Yes Yes Yes Yes (as per Single line Diagrams) Make Model
Yes/No Yes/No
Yes/No
Communications Communications with DCS: Protocol DCS control inputs DCS status outputs Hardware Redundant Yes/No Yes/No Yes/No
0
Type of cable Voltage grade No. of cables and conductor size Cable entry Incomers: Type of cable Voltage grade No. of cables and conductor size Cable entry kV mm
0
kV
0
mm Top/bottom
Top/bottom
0
52 53
0
54
PAGE: 5 of 9
DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 Location: Ambient air temp: Humidity:
Service Description: MV PANEL ENVIRONMENTAL CONDITIONS POWER SYSTEM
22000 50
V Hz
5% 2%
Isolated neutral
Non-Hazardous
UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
Standard of Manufacture Type Location Rated voltage Rated frequency Number of phases Rated lightning impulse withstand voltage (IEC 60694) Rated short duration power frequency w'stand voltage Rated short time withstand current and time Internal arc fault withstand, to (IEC 60298 Annex AA.6) Duration of internal arc fault test Rated peak withstand current Earth busbar withstand current and time Busbar system: Rated normal current (main busbar) Phase segregated busbars Busbar arrangement (Single / Duplicate) Busbar identification Busbar material Busbar insulation Future busbar extension at either end Panel exterior paint colour Panel interior paint colour
0
Air insulated, metal enclosed Indoor, non-hazardous kV Hz 24 50 3 kV (peak) kV (rms) kA (rms) 95 50 (1 minute) 12.5 kA for 1 secs Criteria 1 through 6 sec kA (peak) kA (rms) 1 125 12.5 kA for 1 secs
A Yes / No
Yes/No Yes/No
Paint specification Overall dimensions of the switchboard: Total weight Largest shipping section dimensions Shipping sections (number and weights) Expected assembly heat dissipation Ingress protection rating Document/drawings: Single line diagrams Project specification
0
LxWxH
mm kg
(L X W x H)
mm kg kW
IP42
PAGE: 6 of 9
DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
0
Service Description:
MV PANEL
ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 C Outdoor Max: Altitude: 40 C < 1000m System Voltage: System Frequency: Neutral Earthing:
Isolated neutral
PARTICULARS OF EQUIPMENT Anti condensation heater Anti condensation heater rating & voltage Power cable entry Control cable entry Gland plate Overall dimensions of the panel: (D x W x H)
VENDOR'S RESPONSE
W/V
VTA
18 19 20 21 22
0
23
0
24 25 26 27 28
TEST REQUIREMENTS
0
29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
0
52 53 54 55
DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 Location: Ambient air temp: Humidity:
Service Description: MV PANEL
091135-PVG-EK-003 PAGE: 7 of 9
ENVIRONMENTAL CONDITIONS Indoor Min: 87% 13.8 C Outdoor Max: Altitude: 40 C < 1000m System Voltage: System Frequency: Neutral Earthing:
Isolated neutral
PARTICULARS OF EQUIPMENT CIRCUIT BREAKER DATA (* Current Rating Amps) Number of circuit breakers Panel type Rated normal current Rated voltage Rated short time withstand current and time Rated peak withstand current Rated short circuit breaking current Rated dc component of short circuit breaking current Insulation levels: Rated lightning impulse withstand voltage (IEC 60694) Rated short duration power frequency withstand voltage INDICATION & METERING Anti condensation heater Anti condensation heater rating & voltage Power cable entry Control cable entry Gland plate
No.
A
0
kV (peak) kV (rms)
Yes/No W/V
(D x W x H)
mm
0 0
VTA
"Closed" indication (Red) "Open" indication (Green) Blown fuse indication (Amber) Anti-condensation heater 'ON' indication Control mode selector switch
Yes/No
Metering Kilowatt Hours meter Number of phases Current transformer Potential Transformer LIGHTNING SURGE ARRESTORS Rated voltage Rated frequency Continuous operating voltage Nominal discharge current Power frequency reference voltage Lightning impulse residual voltage Steep current impulse residual voltage Switching impulse residual voltage kV Hz
0
Yes/No
0
Yes 3 phase
Make
Model
Yes/No Yes/No
Yes Yes
24 48 - 62 19.2
0
kV kA kV kV kV
0
kV
PAGE: 8 of 9
DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
0
Service Description:
MV PANEL
ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 C Outdoor Max: Altitude: 40 C < 1000m System Voltage: System Frequency: Neutral Earthing:
Isolated neutral
PARTICULARS OF EQUIPMENT LIGHTNING SURGE ARRESTORS (Continuing) Rectangular current withstand 2000 s High current withstand 4/10 s Line discharge Class
kA
0
VTA VTA 1
0
kA
Partial discharge Creepage distance Lightning impulse withstand Power frequency withstand (wet 1 min) HV CABLES Cable in
0
Type of cable Voltage grade No. of cables and conductor size Cable entry Cable out Type of cable Voltage grade No. of cables and conductor size Cable entry kV mm
0
kV
0
mm Top/bottom
Top/bottom
0
31 32 33 34 35 36 37 38 39 40 41 42
0
43 44 45 46 47 48
0
49
0
50
0
51 52
0
PAGE: 9 of 9
DATA SHEET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
0
Service Description:
MV SWICHGEAR / PANEL
ENVIRONMENTAL CONDITIONS Location: Ambient air temp: Humidity: Indoor Min: 87% 13.8 C Outdoor Max: Altitude: 40 C < 1000m System Voltage: System Frequency: Neutral Earthing:
Isolated neutral
1. Withdrawable circuit breakers shall be interchangeable with others of the same voltage and current rating. 2. Circuit breaker operating mechanisms shall be of the motor/manual spring charge, stored energy, manual/electrical release type. 3. Rated short time withstand & breaking currents for circuit breakers shall be not less than ratings for main busbar.
0
4. Refer to High Voltage Switchgear Specification for additional information. 5. Refer to Metering & Protection SLD 6. Refer to Electrical Equipment Layout for additional information. 7. VTA = Vendor to advise. 8. N/A = Not Application
27 28 29 30 31 32 33 34 35
0
36 37 38 39 40 41 42 43 44 45 46 47 48 49
0
50
0
51 52 53