Vous êtes sur la page 1sur 21

GE Industrial

12-24kV Vacuum Circuit Breaker

GE imagination at work

SecoVac 12-24kV
More Than 80 Years of Interrupter Experience
GE pioneered experimental vacuum interrupters in the 1920's. Refined it and introduced the world's first vacuum interrupter distribution breaker in the 1960's. To date, this interrupter design has been the world leader in vacuum technology and has accumulated over 45 years of reliable field service.

World Class Quality


Manufactured, assembled and tested all in the same sophisticated facility, SecoVac is the product of state of the art manufacturing processes assured by ISO 9001:2000 and ISO14001 certification. Precision Tooled parts, computer aided design and advanced production techniques, as well as the protection of the "E Coat" (cathodic electrocoating) paint process have resulted in a standard of excellence unmatched in the industry.

Universal Applications
SecoVac is designed, assembled and tested to meet or exceed applicable IEC, GB and DL standards. It is suitable for applications in all major industries including T & D, Oil & Gas, Automotive, Processing Plants, Iron and Steel mill, Mining, Commercial Buildings, etc. It provides protection for all types of applications: cable, overhead lines, motors, capacitors, transformers, busbar sections, etc.

Environment Friendly
Selecting low environmental impact technologies has become increasingly important to engineers tasked with choosing equipment for an application. With commitment to environment protection, the solid insulation of epoxy resin is used for SecoVac series MV embedded pole vacuum circuit breaker instead of SF6 gas.

GE imagination at work

SecoVac 12-24kV
Predominant Vacuum Technology
Vacuum switching technology is nowadays the dominant switching principle in medium voltage. Innovative developments are leading to a continuously increasing market growth, based on the fundamental advantages such as reliability, availability, compactness and, last but not least, the environmental friendliness of the vacuum as a switching medium.

Automatic Pressure Gelation


A special cushion layer made of high insulation, gas tight and strong elastic material was employed around the surface of the ceramic tube of vacuum interrupter before it was embedded, so the cracking is thoroughly avoided. SecoVac is the first completed series MV embedded pole vacuum circuit breaker in the world which employs the latest and mature technology of Automatic Pressure Gelation (APG) to embed the vacuum interrupter and connection terminals within epoxy resin. Compared with complete air insulated vacuum circuit breaker or assembly pole vacuum circuit composite insulation, SecoVac is of solid insulation, on one hand, the risk of insulation fault caused by adverse operating environment such as dust, humidity and small animals are eliminated thoroughly, so SecoVac is a vacuum circuit breaker with high environmental resistance. On the other hand, thanks to the embedded pole design, the distribution of electrical field of the pole is much even than that in the assembly pole vacuum circuit breaker, so the insulation strength is improved dramatically.

Vacuum Interrupter
The switching element of the vacuum circuit-breaker is the vacuum interrupter. It consists of an arc chamber, which is located between two ceramic insulators. Terminal studs connect the contacts to the external terminals. One contact is fixed within the housing, the other one is moveable. The metal bellows enable the contact movement and provide a hermetic connection to the interrupter housing. The contact stroke is only a few millimeters. The internal pressure in the vacuum interrupter is less than 10-7 bar. The vacuum circuit-breaker has no arc-quenching medium. The properties of the contact material and the contact geometry define the switching behavior and the switching capacity. After contact separation, the resultant arc evaporates contact material from the contact surfaces. The arc current thus flows throw a material vapour plasma until the next current zero. Near the current zero, the arc is extinguished, and the metal vapour looses its conductivity within a few microseconds as a consequence of the recombination of the charge carrier ions. In this way, the contact gap is de-ionized and the dielectric strength restored very fast. The metal vapour condenses on the contact surfaces. Only a very small portion condenses on the arc chamber wall. The arc chamber wall has the function of a vapour shield, to prevent condensation of the metallic vapour onto the insulators 2 4 1 7 3

The first APG process

Vacuum interrupter after surface treatment

Injection of LSR through APG process

The second APG process

LSR buffering layer molding

Injection of epoxy resin through APG process

1 Fixed contact piece 2 Connection disc 3 Ceramic insulator 4 Arc chamber 5 Metal bellows 6 Guide

Embedded poles
Vacuum interrupter has extremely high internal dielectric strength resulting from the ULV while the external dielectric strength is however limited by the insulation capacity of the air, therefore also requires embedding the chamber in a solid material, In such cases, the vacuum interrupter is additionally well protected against external mechanical influences such as impacts. The main advantages of embedded poles are high dielectric strength without additional external compensation in air, usability in an extremely wide range of climatic conditions, and good protection of the vacuum interrupter from dust, mechanical impacts and moisture. On the operating mechanism side, it is equipped with modularized, standardized and simplified spring mechanism, the whole spring mechanism is made up of separated closing and opening modules which can be preassembled and easily replaced on-site of end-users without any changing of the original dynamic characteristic of the breaker, so the lead time for delivery and down time for maintenance will be shortened.

5 6

7 Moving contact piece 8 Moving contact piece terminal

SecoVac 01

SecoVac 12-24kV
Product Performance Features

2 1

4 5

20
1. Tulip Contact 11. Insulated Coupling Rod 12. Opening Spring 13. Earthing Contact of Cart 14. Classis of Cart 15. Hole for Driving Screw 16. Locking Piece 17. Operating Shaft 18. Operation Cover 19. Closing Spring 20. Secondary Plug

19 6 7 8 9 17 1 16 18

2. Contact Arm 3. Lower Contact Terminal 4. Upper Contact Terminal 5. Embedded Pole 6. Vacuum Interrupter 7. Moving contact pieces 8. Metal Bellows

9. Disc Spring for Contact Pressure 10. Shutter Driving Plate

10

11

12

13

14

15

Unique and Proven Embedded Pole Technology


SecoVac series MV embedded pole vacuum circuit breaker uses the latest and mature technology of Automatic Pressure Gelation (APG) to embed the vacuum interrupter and connection terminals within epoxy resin. The vacuum interrupter is cast in the epoxy resin, so inside the epoxy resin there is no screw fixation that will cause the concentrated harsh electrical field inside the epoxy resin and will consequently result in decrease of the electrical insulation strength of the pole. Thanks to the embedded pole technology, the assembly of the pole is simplified, and the assembly accuracy as well as quality of the embedded pole is easily to be controlled by the state of the art production process. The embedded pole technology also obviously improve the environmental resistant capability of the breaker, as the primary circuit of the breaker is completely embedded inside the epoxy resin, the risk of insulation fault caused by adverse operating environment such as dust, humidity, ingression of small animals, polluted ambient and high altitude operating site are eliminated thoroughly. The key know how of the embedded pole technology is the buffering layer between epoxy resin and ceramic housing of vacuum interrupter, the material and processing of the buffering layer is essential to ensure the integrity of epoxy resin of the embedded pole provide adequate adhesion between each other in any circumstance. Our patented LSR (Liquid Silicon Rubber) buffering layer and double APG (Auto Pressure Gelation) process adopted in the producing of the embedded pole thoroughly eliminates the cracking of the epoxy resin caused by the large difference of thermal expansion coefficient between epoxy resin and ceramic in case of rapid changing of the ambient temperature. APG process for LSR buffering layer ensures that there will not be any air gap or bubble between the buffering layer and ceramic housing, hence, the high electrical insulation strength of the embedded pole of SecoVac series MV embedded pole vacuum circuit breaker is guaranteed. The partial discharge value of embedded pole manufactured by our patented LSR (Liquid Silicon Rubber) buffering layer and double APG (Auto Pressure Gelation) process is below 5pc with an applied testing voltage of 1.2Um.

SecoVac 02

SecoVac 12-24kV
Modular Operation Mechanism
SecoVac series MV embedded pole vacuum circuit breaker is equipped with modularized, standardized and simplified operating mechanism, the mechanism consists of separated closing and opening modules, all the mechanical parts of the mechanism are integrated into these two modules . The closing and opening modules are universal to whole series of SecoVac embedded pole vacuum circuit breaker regardless of ratings, it means there is only one kind of closing and opening module for the whole SecoVac products family, thanks to such a design, the maintenance time and cost for the mechanism is low, the replacement of modules can be easily carried out on site. There is no impact on the original dynamic characteristic of the breaker after the replacement of modules, so the retest of the breaker is not required after the replacement of modules. Another feature of the operating mechanism of SecoVac series MV embedded pole vacuum circuit breaker is that the total number of parts of the mechanism is reduced compared with the traditionally designed mechanism, so that the reliability of the mechanism is enhanced significantly. The opening damper of the mechanism plays a very important role to ensure reliable performance and high mechanical endurance of SecoVac series MV embedded pole vacuum circuit breaker. By adoption of the opening damper, the overtravel and re-bounce of moving contacts of vacuum interrupters during the opening of this VCB is reduced to a minimum. The lower overtravel of the moving contacts means lower mechanical stress to the bellow of the vacuum interrupter, so the designed mechanical endurance of the vacuum interrupter is guaranteed. The lower re-bounce of the contact ensures low arc re-striking probability during the breaking of capacitive current, so the occurrence rate of operating overvoltage is reduced. By the contribution of the opening damper, SecoVac has successfully passed type tested as Class C2 breaker in accordance with IEC standards.

closing module

opening module

integrated VCB

opening damper

SecoVac 03

SecoVac 12-24kV
The State of the art Processing and Advanced Quality Control

The high quality of the embedded pole is achieved by using the latest APG (Auto Pressure Gelation) technology and advanced vacuum mixing and degassing technology that are carried out by the equipment. The Vogel clamping machine is an essential piece of equipment to ensure the mechanical and insulating strength of the embedded pole of SecoVac series MV embedded pole vacuum circuit breaker. As well as the processing facilities, the testing facilities are also very important to the quality control of the breaker. In the manufacturing process of SecoVac VCB, from incoming material quality control to the final inspection and testing, every step is strictly calibrated and tested by means of testing facilities. For every embedded pole, before it goes into the breaker assembly line, it shall go through following inspections and testing carried out in factory: X-ray inspection Power frequency withstand voltage test Partial discharge measurement Extremely high and low temperature impulse test Before delivery, the following tests and inspections will be done for SecoVac series MV embedded pole vacuum circuit breaker in factory by means of advanced testing equipments: Dynamic characteristics measurement Power frequency withstand voltage testing Inspection of interlocking system between breaker and withdrawable unit Secondary wiring inspection Circuit resistance measurement

Full Range Product with High Technical Parameters


Rated voltage up to 24kV Rated current up to 4000A Rated short circuit breaking current up to 50kA Mechanical endurance up to 30,000 operating cycles Rated short circuit breaking times up to 50 times DC component of short circuit breaking current up to 62% Large external creep distance reaches 20mm/kV

SecoVac 04

SecoVac 12-24kV
Breaker Features

Front Panel
This front panel fits into a collar-frame in the equipment when the breaker is in the CONNECT position. It provides a metal barrier between the breaker compartment and the secondary device compartment. Well marked and easy-to-read operating controls and indicators include TRIP button, CLOSE button, OPEN/CLOSE indicator, CHARGE/DISCHRGE indicator, OPERATIONS counter and provision for manual charging the breaker.

Primary Disconnect
The primary disconnect finger set is rugged and easy to inspect. Designed for optimum contact, built of silver-plated copper and tested for continuous and short time current. Cycloid design is more convenient to connect and expand wider contact area than flat design. These disconnects provide proper contact integrity throughout the life of the gear for the critical primary disconnect function.

Breaker Mechanism
All the mechanical parts of the mechanism are integrated into opening and closing modules individually. The closing and opening modules are universal to whole series of SecoVac embedded pole vacuum circuit breaker in spite of the ratings. Such design assures no mechanical readjustment after the replacement, thereby not only shortens lead-time but also reduces operation and maintenance cost.

Interlock System
For personnel safety, SecoVac is designed with a number of mechanical and electrical interlocks. For example, breaker contacts must be open before the breaker can be moved to or from the CONNECT position. A positive mechanical stop is provided when the breaker reaches the CONNECT or TEST/DISCONNECT positions. Mechanical interference interlocks are provided to permit only the insertion of properly rated breakers into any specific compartment. These and other necessary interlocks provide a comprehensive protection system. Furthermore, springs automatically discharge when the breaker is withdrawn from the CONNECT position and breakers cannot be inserted in the closed position.

SecoVac 05

SecoVac 12-24kV
Technical Data

Description
Rated voltage Rated current Rated power frequency withstand voltage (1min) Rated lightning impulse withstand voltage (peak values) Rated short circuit breaking current Rated short time withstand current (4S) Rated peak withstand current Rated peak making current Rated short circuit current breaking times Electrical endurance Mechanical endurance Operating sequence Rated auxiliary control voltage* Opening time Breaking time Closing time

Unit
kV A kV 7.2/12 630/1250/1600/2000/2500/3150/4000 42 24 630/1250/1600/2000/2500 65

kV

75

125

kA

20/25/31.5/40/50

20/25/31.5

kA

20/25/31.5/40/50

20/25/31.5

kA

50/63/80/100/125

50/63/80

kA

50/63/80/100/125

50/63/80

No. of times

50

50

No. of times No. of times

274(E2)

IEC 62271-100:2006

274(E2)

IEC 62271-100:2006

30000

20000

O-0.3s-CO-180s-CO O-180s-CO-180s-CO V AC 110/220; DC110/220

O-0.3s-CO-180s-CO O-180s-CO-180s-CO AC 110/220; DC110/220

ms ms ms

35~70 25~35 40~50

35~70 25~35 40~50

*Other voltages are available on request.

SecoVac 06

SecoVac 12-24kV
Overall Dimension 12kV SecoVac Withdrawable

620

520

205

35

10

42.5

40

62

260

98

74

154

19

76

C D E 13

25

320 370 383 438

3132

296

0 200 + -3

50

A 8 16 P P 16

Journey 8~10mm

Width of Switchgear (mm) 650

Parameter (12kV) 630A Isc31.5kA 1250A Isc31.5kA

P (mm) A (mm) C (mm) 150 150 210 210 275 275 502 502 650 650 850 850 466 466 616 616 812 812

D (mm) E (mm) L (mm) 500 500 640 640 836 836 503 503 653 653 853 853 498 498 648 648 844 844

Weight (kg) 105 105 120 120 130 130

800

630A Isc31.5kA 1250A Isc31.5kA

1000

630A Isc31.5kA 1250A Isc31.5kA

22

630

SecoVac 07

SecoVac 12-24kV
12kV SecoVac Withdrawable

M

40 62.5

48.5

4)

1)

130

2) 310

W

3) U 165 76 25 320 370 4 50 200 -3


+0

R 280

C D E

19

383 293 2 296 359.5

A 16 P P 16

Journey 8~10mm

Width of Switchgear (mm) 800

Parameter12kV 1250A Isc40kA/50kA

55

P (mm) 210 210 210 275 275 275 275 275 275

A (mm) 650 650 650 850 850 850 850 850 850

C (mm) 616 616 616 812 812 812 812 812 812

D (mm) 640 640 640 836 836 836 836 836 836

E (mm) 653 653 653 853 853 853 853 853 853

L (mm) 648 648 648 844 844 844 844 844 844

W (mm) M (mm) 49 79 79 49 79 79 109 109 109 85 115 115 85 115 115 149 149 149

R (mm) 684 684 684 684 684 684 725 725 725

U (mm) 694 694 694 694 694 694 735 735 735

Weight (kg) 200 200 200 220 220 220 295 295 295

1600A Isc50kA 2000A Isc50kA 1250A Isc40kA/50kA 1600A Isc50kA 2000A Isc50kA 2500A Isc50kA 3150A Isc50kA 4000A* Isc50kA

1000

Note: 1)The heat radiator is only necessary for SecoVac with rated current equal to higher than 2500A. 2)The lifting hook should be remove before SecoVac is put into switchgear panel. 3)Contact arm system for SecoVac with rated current upto 2000A. 4)Contact arm system for SecoVac with rated current 2500A and above. *The forced fan cooling is necessary when SecoVac with rated current 4000A is installed in metal-enclosed switchgear.

SecoVac 08

21.5

SecoVac 12-24kV
L - Frame for 12kV SecoVac Withdrawable
G-G

705

205 (H) 260


35

G W
688 ( D )

Width of Switchgear (mm) 650

SecoVac 630A Isc31.5kA 1250A Isc31.5kA 630A Isc31.5kA

Phase to Phase Distance (mm) 150 150 210 210 275 275

Depth (mm) 688 688 688 688 688 688

Height (mm) 705 705 705 705 705 705

Width (mm) 510 510 660 660 860 860

800 1250A Isc31.5kA 630A Isc31.5kA 1000 1250A Isc31.5kA

SecoVac 09

SecoVac 12-24kV
L - Frame for 12kV SecoVac Withdrawable

B-B B

B W

280

310

688 ( D )

Width of Switchgear (mm)

SecoVac 1250A Isc = 40kA / 50kA

Phase to Phase Depth (mm) Height (mm) Distance (mm) 210 210 210 275 275 275 275 688 688 688 688 688 688 688 850 850 850 860 860 860 860

Width (mm) 660 660 660 860 860 860 860

(mm) 49 79 79 49 79 79 79

800

1600A Isc40kA 2000A Isc40kA 1250A Isc = 40kA / 50kA 1600A Isc40kA

1000 2000A Isc40kA 2500A Isc40kA

SecoVac 10

SecoVac 12-24kV
L - Frame for 12kV SecoVac Withdrawable

C-C C

860 ( H )

860 ( W ) C

280

109

310

688 ( D )

275 ( P )

275 ( P )

Width of Switchgear (mm) 1000 1000

SecoVac 3150A Isc50kA 4000A Isc50kA

Phase to Phase Distance (mm) 275 275

Depth (mm) 688 688

Height (mm) 860 860

Width (mm) 860 860

Note: Forced cooling fan is necessary when SecoVac rated 4000A

SecoVac 11

SecoVac 12-24kV
24kV SecoVac Withdrawable

L 40 15 42.5

775 +3 0

310

35

93

325

74

167

76

19

C D E

25

320 383 447 296


0 300 -3

22

4 50

13.5

4512

A 16 P P 16

Journey 810mm

Width of Switchgear (mm) 800

SecoVac 630A Isc31.5kA 1250A Isc31.5kA

P (mm) 210 210 275 275

A (mm) C (mm) D (mm) E (mm) L (mm) 650 650 850 850 622 622 812 812 646 646 836 836 653 653 853 853 648 648 844 844

Weight (kg) 125 125 135 135

1000

630A Isc31.5kA 1250A Isc31.5kA

SecoVac 12

790

SecoVac 12-24kV
24kV SecoVac Withdrawable

844 49 2) 1)

109

310

167

815

79

325

135

167

76

19

812 836 853

25

320 383 447

22

13.5 4412

296

0 300 -3

830 50
Dimension of Contact

3)

850 16 275 275

16 8

Journey 810mm

1) The heat radiator is only necessary for SecoVac with rated current equal to or higher than 2500A 2) 109 is adapted for SecoVac with rated current 3150A 3) 79 is adapted for SecoVac with rated current 1600-2500A

Width of Switchgear (mm)

SecoVac

1600A Isc31.5kA 2000A Isc31.5kA 1000 2500A Isc31.5kA 3150A Isc31.5kA

79 79 79 109

SecoVac 13

SecoVac 12-24kV
L - Frame for 24kV SecoVac Withdrawable

210

210

2 1

W
Width of Switchgear (mm) 800 Phase-to- phase distance (mm) 210 210 275 275 275 275 275

471

310

SecoVac 630A Isc31.5KA 1250A Isc31.5KA 630A Isc31.5KA 1250A Isc31.5KA 1600A Isc31.5KA 2000A Isc31.5KA 2500A Isc31.5KA

Depth (mm) Height (mm) Width (mm) 870 870 870 870 870 870 870 937 937 937 937 937 937 937 794 794 994 994 994 994 994

1000

Caution: Remove support part 1 and 2 before L-Frame in use.

SecoVac 14

SecoVac 12-24kV
Internal Wiring Diagram

Opening circuit

2nd opening circuit

Close blocking circuit

Closing circuit

Charging circuit

Over current release (A phase)

Over current release (B phase)

Over Under current voltage release release (C phase)

Truck Rack Block magnet

Closing monitor circuit

Y0 Y1 Y2 Y3 Y4 Y7-Y9 Y10 P M V0-V5


Service position Test position

Blocking Magnet for withdrawable unit---V0 Closing block magnet First opening release Closing release Undervoltage release Indirect overcurrent release ( optional ) Second opening release ( optional ) Manual charging Charging motor Rectifier ( V0 & V5 optional )

S1 S2 S3 S8 S9 K0 R0 JP1 JS1

Auxiliary switch of charging Motor Auxiliary switch of block magnet- Y1 Auxiliary switch of VCB Auxiliary switch for test position Auxiliary switch for service position Anti-pumping relay Resistance Bypass of R0 Connector of K0 ( the internal anti-pumping function will be dismissed if it is cut )

Notes:
1. 2. 3. Aux.switch-S1 shown for VCB-mechanism is discharged. VCB in opening and service status. The optional components are not included in basic version if not specified .

Withdrawable Installation for AC Control


Opening circuit 2nd opening circuit Close blocking circuit Closing circuit Charging circuit
Over current release (A phase) Over current release (B phase) Over Under current voltage release release (C phase)

Truck Rack Block magnet

Closing monitor circuit

Y0 Y1 Y2 Y3 Y4 Y7-Y9 Y10 P M
Service position Test position

Blocking Magnet for withdrawable unit---V0 Closing block magnet First opening release Closing release Undervoltage release Indirect overcurrent release ( optional ) Second opening release ( optional ) Manual charging Charging motor

S1 S2 S3 S8 S9 K0 R0 JP1 JS1

Auxiliary switch of charging Motor Auxiliary switch of block magnet- Y1 Auxiliary switch of VCB Auxiliary switch for test position Auxiliary switch for service position Anti-pumping relay Resistance Bypass of R0 Connector of K0 (the internal anti-pumping function will be dismissed if it is cut )

Notes:
1. 2. 3. Aux.switch-S1 shown for c.b.-mechanism discharged. VCB in opening and service status. The optional components are not includerd in basic version if not specified .

Withdrawable Installation for DC Control

SecoVac 15

SecoVac 12-24kV
Internal Wiring Diagram

Opening circuit

2nd opening circuit

Close blocking circuit

Closing circuit

Charging circuit

Over current release (A phase)

Over current release (B phase)

Over Under current voltage release release (C phase)

Closing monitor circuit

Notes:
1. 2. 3. 4. Aux.switch-S1 shown for VCB-mechanism is discharged. VCB in opening status. The optional components are not included in basic version if not specified . Auxiliary switch S2 should be bypassed when block magnet Y1 is not required. Y1 Y2 Y3 Y4 Y7-Y9 Y10 P M V0-V5 Closing block magnet First opening release Closing release Undervoltage release Indirect overcurrent release ( optional ) Second opening release ( optional ) Manual charging Charging motor Rectifier ( V0 & V5 optional ) S1 S2 S3 K0 R0 JP1 JS1 Auxiliary switch of charging Motor Auxiliary switch of block magnet- Y1 Auxiliary switch of VCB Anti-pumping relay Resistance Bypass of R0 Connector of K0 ( the internal anti-pumping function will be dismissed if it is cut )

Fixed Installation for AC Control


Over current release (A phase) Over current release (B phase) Over Under current voltage release release (C phase)

Opening circuit

2nd opening circuit

Close blocking circuit

Closing circuit

Charging circuit

Closing monitor circuit

Notes:
1. 2. 3. 4. 5. Aux.switch-S1 shown for VCB-mechanism is discharged. VCB in opening status. The optional components are not includerd in basic version if not specified . Auxiliary switch S2 should be bypassed when block magnet Y1 is not required. The connect points in dashed are as should be connected with positive pole. Y1 Y2 Y3 Y4 Y7-Y9 Y10 P M Closing block magnet First opening release Closing release Undervoltage release Indirect overcurrent release ( optional ) Second opening release ( optional ) Manual charging Charging motor S1 S2 S3 K0 R0 JP1 JS1 Auxiliary switch of charging Motor Auxiliary switch of block magnet- Y1 Auxiliary switch of VCB Anti-pumping relay Resistance Bypass of R0 Connector of K0 ( the internal anti-pumping function will be dismissed if it is cut )

Fixed Installation for DC Control

SecoVac 16

SecoVac 12-24kV
Product Type
SecoVac / Rated short circuit breaking current (kA): 20, 25, 31.5, 40, 50 Rated current (A): 630, 1250, 1600, 2000, 2500, 3150, 4000 Rated voltage (kV): 12, 24 SecoVac Vacuum Circuit Breaker

Ordering Information

Coding System of Catalogue Number


Symbol Meaning of the code

Basic type designation

Operating mechanism

Rated short circuit breaking current

Type of control voltage

Phase-to-phase distance

SEV SEV 12 24

W
SecoVac

Installation mode

Rated current

Control voltage

Rated voltage

From 7.2kV up to 12kV 24kV

T 06 12 16 20 25 31 40 20 25 31 40 50 A D 11 22 P15 W P21 F P27 W F

Spring operating mechanism Rated current: 630 A Rated current: 1250A Rated current: 1600A Rated current: 2000A Rated current: 2500A Rated current: 3150A Rated current: 4000A Rated short circuit breaking current: 20kA Rated short circuit breaking current: 25kA Rated short circuit breaking current: 31.5kA Rated short circuit breaking current: 40kA Rated short circuit breaking current: 50kA AC auxiliary control voltage DC auxiliary control voltage Rated auxiiary control voltage: 110V Rated auxiiary control voltage: 220V Phase-to-phase distance 150mm Phase-to-phase distance 210mm Phase-to-phase distance 275mm Withdrawable installation Fixed installation

SecoVac 17

SecoVac 12-24kV
Checking list for SecoVac Order

Customer : Breaker type Rated voltage Rated current Rated short-circuit breaking current Distance of Pole (P) Motor-operated (M) *Blocking magnet Y1 Shunt releases ONOFF Y2Y3 Over-current releases Y7Y8Y9 ( optional ) Under-voltage release Y4 ( optional ) Truck blocking Y0 ( optional ) Anti-pump relay K0 2nd Release Y10 ( optional ) Secondary wiring Withdrawable ( W type ) SecoVac 7.2kV 630A 20kA 150mm DC220V DC220V DC220V Other Disabled Y7/Y9 ( AC5A ) Disabled DC220V Disabled DC220V Standard 12kV 1250A 25kA

Project : Quantity 24kV 1600A 31.5kA 210mm DC110V DC110V DC110V AC220V AC220V AC220V 2000A 40kA 2500A 50kA 275mm AC110V AC110V AC110V

Order NO.

3150A

4000A

Other Other

Y7/Y8/Y9 ( AC5A ) AC220V AC110V

DC110V

DC110V

AC220V

AC110V

Other

Non-standard ( Attached drawing .NO. : earthing with connecter on the sides of truck Other

Earthing mode: earthing with copper bar at the bottom of truck Secondary wiring:

connect with terminal strips on the top of cabinet with control wiring plug with control wiring plug installed on the top of cabinet

Fixed ( F type ) Mechanical interlock:

Other Disabled sticking out 120mm on the left side of principal axis with opening release Other

( Please attach concerned drawing or data in case any special requests. ) Other items 1. 2. 3. * Blocking magnet Y1: Standard for withdrawable part; optional for fixed part. Prepare date Check date

SecoVac 18

GE Industrial
APO Headquarters
China
23F,Building C,Hi-Tech Building, 900 Yishan Road, Shanghai 200233 Tel: +86 21 2401 3333 Fax: +86 21 5423 5080

Australia
125-127 Long Street Smithfield, Sydney NSW 2164 Australia Tel: +61 (0)2 8788 6911 Fax: +61 (0)2 9729 0433

India
The Millenia, Level 6, Tower B, # 1 & 2 Murphy Road, Ulsoor Bangalore - 560 008 India Tel: +91 80 4143 4000 Fax: +91 80 4143 4199

Indonesia
BRI II Tower, 15th Floor Suite 1505 Jl. Jendral Sudirman No. 44-46 Jakarta 10210 Indonesia Tel: +62 21 5730 429 Fax: +62 21 574 7089

Japan
Akasaka Park Bldg., 5-2-20 Akasaka, Minato-ku, Tokyo 107-6112 Japan Tel: +81 03 5544 6781 Fax: +81 03 5544 6760

Malaysia
Suite 3B-8-3, Block 3B, Leval 8, Plaza Sentral, Jalan Stesen Sentral, Kuala Lumpur Sentral 50470, Kuala Lumpur, Malaysia. Tel: +603 2273 9788 Fax: +603 2273 3481

Philippines
1873 P.Domingo St Makati City Philippines 1207 Tel: +63 2 895 7051/59 Fax: +63 2 890 8186

Singapore
240 Tanjong Pagar Road, #06-00 GE Tower Singapore 088540 Tel: +65 6220 7022 Fax: +65 6326 3015

Taiwan
6F, No. 8 Sec. 3 Min-Sheng E. Road. Taipei, Taiwan 10480 Tel: +886 2 2183 7000 Fax: +886 2 2516 6829

Thailand
1126/2, Vanit Building II 16th Floor Room 1603, New Petchburi Road, Makkasan Ratchathewi Bangkok 10400 Thailand Tel: +66 2 255 8721 Fax: +66 2 255 8733

Vietnam
Floor 7 Saigon Centre 65 Le Loi Street District 1 Ho Chi Minh City, Vietnam Tel: +84 8 914 6490 Fax: +84 8 827 8229

Korea
3F.,GE Tower,71-3, Cheongdam-dong, Ganam-gu, Seoul 135-100 Korea Tel: +82 2 6201 4505 Fax: +82 2 6201 4545

New Zealand Hongkong


15/F, The Lee Gardens, 33 Hysan Avenue. Causeway Bay Tel: +852 62943050 Fax: +852 23760013 Level 10, Lurnley House 7 City Road. Auckland. Tel: +64 9 353 6706 Fax: +64 9 353 6707

This company reserves the right to improve the products according to the situation. This publication describes the status of the products at the time of its issuing and may not reflect future condition of the product. Publication NO.GE/SV12-24/CA/2008/001

GE imagination at work

Vous aimerez peut-être aussi