Vous êtes sur la page 1sur 12

ITEM DESCRIPTION

NAME OF THE WORK: EXTENTION/CONSTRUCTION OF BUILDING AT ARCI NAME OF THE BUILDING: SOLAR CELL VOL.III - ELECTRICAL BOQ - TECHNICAL
SL Item No Code CONDUIT Technical Description Supply, Installation of 25mm dia 2.0mm thick PVC conduit pipe (MAKE:PRECISION / AVONPLAST-BLACK COLOR) with all required accessories such as long bends, junction boxes, base saddles (ONE BASE SADDLE AT EVERY 500MM) to draw the circuit wiring/ point wiring. The scope includes small civil works such as entry of 25mm pvc pipe concealed through walls and finishing the wall to the original condition after laying the pipe includes painting. All other accessories materials should be included in the item rate such as base saddles, junction boxes, L - bows, T - bends, Fischer make nylon grip gutti (imported make), GI screws in sitting rooms/ room. Supply, Installation of 25mm dia 2.0mm thick PVC conduit pipe (MAKE:PRECISION / AVONPLAST-BLACK COLOR) with all required accessories such as long bends, junction boxes, base saddles (ONE BASE SADDLE AT EVERY 500MM) to draw the circuit wiring/ point wiring. The scope includes laying 25mm pvc pipe on walls/ roof slabs, after laying the pipe includes painting. All other accessories materials should be included in the item rate such as base saddles, junction boxes, L - bows, T - bends, Fischer make nylon grip gutti (imported make), GI screws in labs/ clean rooms.

125001089

125001090

POINT WIRING Supply, Installation, Testing and Commissioning of Point wiring to be drawn from SWITCH BOARD(SB) to ceiling rose - 3runs of 1sqmm PVC insulated copper conductor flexible wires (FRLS) to be drawn seperately from sub DB to first ceiling rose . And from second ceiling rose neutral and earth wire to be looped near from first ceiling rose,but 1seperate 1run phase wire should be drawn seperately from SB to second ceiling rose. Similarly all neutral and earth wires should be looped near ceiling roses for that SB. And all ceiling roses should get 1run 1 sqmm wire for phase directly from SB Pl Note: 1. Maximum 9no of 1Sq.mm size wires are allowed in a single 25mm dia pvc pipe, if more than 9nos of wires are required to run one more 25mm dia pvc pipe should be laid. 2. Measurements will be taken per mtrs as per site condition per run of three wire i.e. phase wire and neutral & earth wires 3.Finolex/Anchor/ L&T make fire retardant low smoke type wires are only accepted. 4.Neutral and earth wire shoud be looped for maxium of four fittings 5. Color code shall be as per IS only. Supply, Installation, Testing and Commissioning of circuit wiring to be drawn from Main LIGHTING distribution BOARD to first Switch Board (SB) of the circuit - 3runs of 2.5sqmm PVC insulated copper conductor flexible wires (FRLS) to be drawn separately from Main LDB to sub DB and clean room lighting wiring for phase, neutral & earthing. Pl Note: 1. Maximum 8no of 2.5Sq.mm size wires are allowed in a single 25mm dia pvc pipe, if more than 8nos of wires are required to run, one more 25mm dia pvc pipe should be laid. 2. Measurements will be taken per mtrs as per site condition per run of three wire i.e. phase wire and neutral & earth wires 3.Finolex/ Anchor/ L&T- make fire retardant low smoke type wires are only accepted. 4. Color code shall be as per IS only.

125001091

125001092

Page 1 of 12

SL No

Item Code

Technical Description Supply, Installation, Testing and Commissioning of circuit wiring to be drawn from Main distribution BOARD to power point - 3runs of 4sqmm PVC insulated copper conductor flexible wires (FRLS) to be drawn separately from SPN DB to AC points and power points for phase, neutral & earthing separately. Pl Note: 1. Maximum 6no of 4sqmm size wires are allowed in a single 25mm dia pvc pipe, if more than 6nos of wires are required to run, one more 25mm dia pvc pipe should be laid. 2. Measurements will be taken per mtrs as per site condition per run of three wires i.e. phase wire and neutral & earth wires 3.Finolex/Anchor/ L&T- make fire retardant low smoke type wires are only accepted. 4. Looping for earth wire and neutral for 4 points and separate phase wire to be drawn. 5. Color code shall be as per IS only.

125001093

SOCKET & SWITCH 6 125001094 Supply,Installation,Testing, Commissioning along with necessary accessories, 1-way Switch - 6A Make : Siemens/ MDS/ Anchor/ L&T/ Scheinder Supply,Installation,Testing ,Commissioning along with necessary accessories, 3 pin switch and socket combined (6A) Make : Siemens/ MDS/ Anchor/ L&T/ Scheinder Supply,Installation,Testing,Commissioning along with necessary accessories 16 / 6A UNI.S.S. neon combined (Anchor Penta IVORY (4282)/ Siemens/ MDS/ L&T/ Scheinder) . Supply, installation, testing & fixing of sheet steel enclosure fitted with plug & socket of IP30 degree of protection with 20A SP MCB (C - Series). AC BOX -20A SP MCB Make : Siemens / L&T/ Scheinder/ Legrand Supply, installation, testing & fixing of sheet steel enclosure fitted with plug & socket of IP30 degree of protection with 40A 4P Isolator. SS box with 40A 4P Isolator Make : Siemens / L&T/ Scheinder/ Legrand Supply, installation, testing & fixing of sheet steel enclosure fitted with plug & socket of IP30 degree of protection with 32A TP MCB (C- Series). INDUSTRIAL SOCKET -32A TP MCB Make : Siemens / L&T/ Scheinder/ Legrand Supply, installation, testing & fixing of sheet steel enclosure of IP30 degree protection with 16A TP MCB (C- Series) for Flume Hood. INDUSTRIAL SOCKET -16A TP MCB Make : Siemens / L&T/ Scheinder/ Legrand

125001095

125001096

125001097

10

125001098

11

125001099

12

125001100

SWITCH BOARDS Supply, Installation & Commissioning of MS Box of 14 gauge size 6" X 6" X 2" depth with 3.5mm white heylam (both sides) sheet cover cutted to required shape to mount no. of switches/ sockets as required at site/ARC I officials. Painting: Initially two coats of red 13 125001101 oxide, finally two coats of required color enamel paint to be mounted on wall with 2no.s of anchor bolts of required size or welding, at required height as directed by ARC I officials. Provision should be made to enter the 25mm dia PVC conduit as per the site requirement for 6A switch sockets, Toilet switch boards. Earthing provision to be made inside the box

Page 2 of 12

SL No

Item Code

Technical Description Supply, Installation & Commissioning of MS Box of 14 gauge size 6" X 8" X 2" depth with 3.5mm white heylam (both sides) sheet cover cutted to required shape to mount no. of switches/ sockets as required at site/ARC I officials. Painting: Initially two coats of red

14

125001102

oxide, finally two coats of required color enamel paint to be mounted on wall with 2no.s of anchor bolts of required size or welding, at required height as directed by ARC I officials. Provision should be made to enter the 25mm dia PVC conduit as per the site requirement for 16A Switch socket. Earthing provision to be made inside the box Supply, Installation & Commissioning of MS Box of 14 gauge size 10" X 12" X 2" depth with 3.5mm white heylam (both sides) sheet cover cutted to required shape to mount no. of switches/ sockets as required at site/ARC I officials. Painting: Initially two coats of red oxide, finally two coats of required color enamel paint to be mounted on wall with 2no.s of anchor bolts of required size or welding, at required height as directed by ARC I officials. Provision should be made to enter the 25mm dia PVC conduit as per the site requirement for switch boards. Earthing provision to be made inside the box Supply,Installation & Commissioning of MS Box of 14 gauge size 10" X 8" X 2" depth with 3.5mm white heylam (both sides) sheet cover cutted to required shape to mount no. of switches/ sockets as required at site/ARC I officials. Painting: Initially two coats of red oxide, finally two coats of required color enamel paint to be mounted on wall with 2no.s of anchor bolts of required size or welding, at required height as directed by ARC I officials. Provision should be made to enter the 25mm dia PVC conduit as per the site requirement. Earthing provision to be made inside the box

15

125001103

16

125001104

LIGHTING FIXTURES/ FITTINGS Labor charges for removing, cleaning, servicing, testing and refixing of existing Light/ Fan 17 125001105 fittings. Note: Before procuring new fittings, contractor must take approval from ARCI officials. Supply and Fixing of Tube Lights (36 W - Life max)Philips on wall / Ceiling with / TW 18 125001106 round blocks with copper choke, starter etc., including 1No of 36W power saving tube etc., complete. Note: Before procuring new fittings, contractor must take approval from ARCI officials. Supply and fixing of 3X36W Recess Mounted IP 54 bottom opening type clean room luminaire with 3 no. of 36 watts lamps in false ceiling. The fitting arrangement should be hanged from ceiling with 2no.s Anchor bolt with height adjustable nut, bolt and S.S. Chain including cost of all materials and labor charges etc., complete. Make: Philips FBS 650 3xPLL 36W EBP FOP GT/ Wipro. Supply and fixing of 1x11 W mirror light with all standard accessories diffuser and 1No 11W CFL lamp etc. in toilets, including all materials. Make: Philips FBS450/236 M2 AG HF PL-L 36W/ Wipro. Supply, and Fixing of Ceiling fan of 1200mm with 3 blades & double ball bearings without Regulators and all standard accessories and giving connections etc.,complete. Make: Crompton/ Havells/ Orient/ usha astra Supply and erecting electronic step type fan regulator for ceiling fans of 1200mm sweep complete erected on existing board. Make : Siemens/ MDS/ Anchor/ L&T/ Scheinder Supply and erecting fresh air exhaust fan of heavy duty 300mm size (12"), Metallic body plastic blades, wire mesh, etc. including outside GI louvers and all materials. Make: Orient/ Crompton Greeves/Bajaj. Supply and Installation of 2x36/40W industrial box type tube light luminaire with 2Nos copper / VPIT chokes, starters, with condenser and 2Nos 36/40W tube etc., including cost and conveyance of all materials, and all labor charges etc., complete. Make: Philips TMC055 2xTLD-36W EBE/ Wipro.

19

125001107

20

125001108

21

125001109

22

125001110

23

125001111

24

125001112

Page 3 of 12

SL No 25

Item Code 125001113

Technical Description Supply and Installation of 2x36W surface mounting mirror optic luminaire with powder coated CRCA sheet steel housing with Aluminium mirror reflectors with VPIT chokes, Starters, Condensor etc., complete with 2Nos 36W tubes etc.,complete. Make: Philips TCS 398/ 236 MDGN HPF/ Wipro.

EXTERNAL LIGHTING Supply and installation of Integral street light luminaire of 70W HPSV lamp fitting comprises of single piece die cast Aluminum body with copper wound ballast and capacitor, Igniter, with pot optics including 70W HPSV lamp on 1.5mtr.40mmdia GI pipe 26 125001114 bracket and anti-tilting 25x3mm MS flat to be grouted on wall etc., complete. Make: Philips SGP 301 1XSON70W FG/ Wipro. Supply and fixing of weather proof syntex junction box of size 340mmX160mmX90mm (HxWxD) (Model No. GS-JB-3416-S) with hinged door and locking arrangements for fixing 27 125001115 1No. 6A DP MCB and 3-ph 20A connector on wall for the control of street light point including fixing with necessary arrangements etc., complete. Fabrication, Supply, Fixing, Erection including excavation, concreting and cooping of G.I. Poles for post top lanterns with 'B' class 4 mtrs long 60.25mm outer dia with base plate of 12"X12"X6mm thick and suitable pole cap, with control gear box and 70W luminarie, 70W 28 125001116 lamp including cost of all materials etc., complete. Luminare Make: Philips SPC 101 1XSON70W E/ Wipro. Supply of 4C x 6 Sq.mm PVC XLPE Copper armoured U.G. cable. Grade with ISI mark stranded / solid, copper conductor complete as per IS 694-1961 for external lighting on 29 125001117 walls/ in cable excavation. Make: Finolex/ Universal/ Unistar Laying and Fixing of 4C X 6 Sqmm Cable for external lighting in ground/ walls with 30 304005001 required fixing materials including base saddles at every 500mm as directed by ARCI officials Labor for Earth work excavation, of size 100mm wide x 300mm depth for laying of 4C x 6Sqmm PVC XLPE Copper Armored U.G cables. Stacking of removed earth from all 31 304005002 along the trench on either side after back filling and reinstatement. Excess removed earth should be transported to specified place as per direction of the ARC I officials Supply, installation, testing & commissioning of cable termination (labour,material & equipments) of the cable at ONE end using double compression gland (Grip make), 32 125001118 Aluminum or copper lugs (dowells make) for crimping including aluminum cable tag and making good as per IS Code. 4C X 6 SQMM CU .AR. CABLE DISTRIBUTION BOARDS Supply,fixing,testing & commissioning of horizontal TPN Distribution Boards double door as per IP43 degree protection supplied with busbar, wire sets, blanking plates, cable ties, identification labels, earth bar & insulated neutral bar as standard with one no. 63A 4P MCB (C-Series) as incomer, 18no.s of 6A SP MCB (B-Series) as outgoer and fixing with 33 226001003 25x3mm MS Angle frame and frame to be grouted in wall and DB to be fixed on Angle. TPN Distribution board double door - 6 way (Clean room LDB, External lighting DB) Make : Siemens / L&T/ Scheinder/ Legrand Supply,fixing,testing & commissioning of vertical TPN Distribution Boards double door as per IP43 degree protection supplied with busbar,wire sets, blanking plates, cable ties, identification labels, earth bar & insulated neutral bar as standard with one no. 125A 4P MCCB as incomer, 8no.s of 32A TP MCB (C-Series) as outgoer and fixing with 25x3mm MS Angle frame and frame to be grouted in wall and DB to be fixed on Angle. Verticle TPN Distribution board double door - 12 way (Clean room power DB, PDB on Gr. floor and First floor) Make : Siemens / L&T/ Scheinder/ Legrand

34

226001004

Page 4 of 12

SL No

Item Code

Technical Description Supply,fixing,testing & commissioning of vertical TPN Distribution Boards double door as per IP43 degree protection supplied with busbar,wire sets, blanking plates, cable ties, identification labels, earth bar & insulated neutral bar as standard with one no. 125A 4P MCCB as incomer, 4no.s of 40A TP MCB (C-Series) as outgoer and fixing with 25x3mm MS Angle frame and frame to be grouted in wall and DB to be fixed on Angle. Verticle TPN Distribution board double door - 4 way (AC DB) Make : Siemens / L&T/ Scheinder/ Legrand Supply,fixing,testing & commissioning of SPN Distribution Boards double door as per IP43 degree protection supplied with busbar,wire sets, blanking plates, cable ties, identification labels, earth bar & insulated neutral bar as standard with one no. 63A DP MCB (CSeries) as incomer, 4no.s of 20A SP MCB (C-Series) as outgoer and fixing with 25x3mm MS Angle frame and frame to be grouted in wall and DB to be fixed on Angle. SPN Distribution board double door - 6 way (Lab/ room PDB's) Make : Siemens / L&T/ Scheinder/ Legrand Supply,fixing,testing & commissioning of SPN Distribution Boards double door as per IP43 degree protection supplied with busbar,wire sets, blanking plates, cable ties, identification labels, earth bar & insulated neutral bar as standard with one no. 63A DP MCB (CSeries) as incomer, 6no.s of 20A SP MCB (C-Series) as outgoer and fixing with 25x3mm MS Angle frame and frame to be grouted in wall and DB to be fixed on Angle. SPN Distribution board double door - 8 way (Lab/ room PDB's) Make : Siemens / L&T/ Scheinder/ Legrand Supply,fixing,testing & commissioning of SPN Distribution Boards double door as per IP43 degree protection supplied with busbar,wire sets, blanking plates, cable ties, identification labels, earth bar & insulated neutral bar as standard with one no. 100A DP Isolator as incomer, 10no.s of 20A SP MCB (C-Series) as outgoer and fixing with 25x3mm MS Angle frame and frame to be grouted in wall and DB to be fixed on Angle. SPN Distribution board double door - 12 way (Lab/ room PDB's) Make : Siemens / L&T/ Scheinder/ Legrand

35

226001005

36

226001006

37

226001007

38

226001008

TELEPHONE AND LAN SYSTEM Supply, fixing, testing and commissioning of Telephone sockets including modular MS box 39 125001119 of suitable size flush/ surface mounted with front plate and all accessories complete Make : Legrand/ L & T / M K / Salzer. Note: Before procuring, contractor must take permission from ARCI officials. Supply and laying of 2 Pair telephone cable in the existing conduit pipe with connections etc.,complete for telephone sockets. Make : Finolex / Polycab/ Gold Medal. Note: Before procuring, contractor must take permission from ARCI officials. Supply and laying of 50 Pair armoured telephone cable to be laid from telephone exchange to building premises through trench/ GI pipe (at road crossings) including, complete with all material and labor charges. Make : Finolex / Universal Note: Before procuring, contractor must take permission from ARCI officials. Supply and fixing of 50 pair MDF krone pair box with MS enclosure with lock and key arrangement etc complete with all labor charges. Make : Krone / equivalent. Note: Before procuring, contractor must take permission from ARCI officials. Supply, fixing, testing and commissioning of LAN points for internet connections including modular MS boxes flush/ surface mounted with front plate and all accessories complete Make: Beldan / D Link / Legrand. Note: Before procuring, contractor must take permission from ARCI officials. Supply, laying, termination, testing and commissioning of RJ 45 cable in existing conduit/ GI pipe for LAN points including cost and conveyance of all materials and labor. Make: D Link / Legrand. Note: Before procuring, contractor must take permission from ARCI officials.

40

125001120

41

125001121

42

125001122

43

125001123

44

125001124

Page 5 of 12

SL No

Item Code

Technical Description Excavation of cable trench of size 300 mm wide x 750 mm depth in wet , dry & rocky conditions of the soil for Telephone cable/ GI pipe (for LAN cable) laying on a fine sand bed of 150mm in the excavated trench after Telephone cable/ GI pipe laying again cover the cable/ GI pipe by 150mm sand cover all size with red bricks and back filling. Stacking of removed earth from all along the trench on either side after back filling and reinstatement. The excavated / removed excess sand should be transported to designated place as per ARC I official. Note: Before excavation, contractor must take permission from ARCI officials Supply and laying of GI pipe of 50mm dia with all types of bends/T's/L's/ Coupling as per site conditions class B pipe for the run of LAN cable to the building premises GI pipe make: Tata Note: Before excavation, contractor must take permission from ARCI officials. Supply and laying of GI pipe of 50mm dia with all types of bends/T's/L's/ Coupling as per site conditions class B pipe including Cutting the tar road or cement road along with culverts either side of the road to make cable trench of size of 300mm wide x 750mm depth, laying of 50mm dia GI pipes and remaking to original shape both road with tar, pcc & culverts with bricks, plastering as directed by ARC I Officials for the run of incoming 50pair Telephone cable at the road crossings. GI pipe make: Tata Supply, installation, testing and commissioning of Cast Iron Cable markers duly showing the direction of cable route for telephone and LAN cables from telephone excahnge to the building premises. The markers are required to be fixed on GI angle of size 35 x 35 x 6mm of length 700mm and grouted in PCC of size 200 x 200 x 200mm at every interval of 15 to 20 metres length as directed by ARC I officials.

45

304005003

46

125001125

47

125001126

48

125001127

PANELS Design, fabrication, Supply, installation, testing and commissioning of 3 phase 415V, 4 wire cubical panel board made out of 14gauge CRCA sheet steel Rittal make with powder coating including all mentioned below switchgears. All incoming and outgoing cables should be from bottom entry. The panel shall be consisting of given rated bus bars of same size in all phases and neutral supported with DMC/SMC supports barriers and heat shrinkable color code sleeves. The metering shall be provided as specified. The panels shall have short circuit capacity of minimum 50 KA. and equipped with bus bar and cable chambers. The panel maximum height must not exceed 1.6Mtrs. The job includes supply and fixing of MS Channel duly painted of size 100mm x 50mm x 5mm thick to be placed as support to the panels on trench of required length for placing the panel. Main Incomer: 800A 4P EDO type ACB (Make: L&T/ Legrand/ Schneider) - 1 No. Metering Set: 0-800A Digital Ammeter - 1 No. 0-500V Digital Volt meter - 1 No. R, Y, B Indication lamps LED type - 3 Nos. 800/5A C.T coils - 3 Nos. 400/5A C.T coils - 3 Nos. Ammeter between Earth and Neutral Bus with CT's - 1 No. KW, KVA, KWH, KVAH meters each (Make: Enercon/ HPL) - 1 No. PF Meter (Make: Enercon/ HPL) - 1 No. Outgoing: 3 phase 415V 315A 4P MCCBs (Make: L&T/ Legrand/ Schneider) - 4 Nos. 200A 4P MCCBs (Make: L&T/ Legrand/ Schneider) - 2 Nos. 125A 4P MCCBs (Make: L&T/ Legrand/ Schneider) - 1 Nos. Bus Bars suitable for 415kV,3Phase 100x10mm Al. Alloy suitable for 415V with heat shrinkable color coded bus bars for phases and neutral All the GA Drawings shall be approved by ARCI/Consultant Page 6 of 12

49

226001009

SL No

Item Code

Technical Description Design, fabrication,Supply, installation, testing and commissioning of 3 phase 415V & 3Phase 220V, 4 wire cubical panel board made out of 14gauge CRCA sheet steel Rittal make with powder coating including all mentioned below switchgears. The panel shall accomodate a dry type transformer of 120KVA 3ph/ 3ph of voltages 415V/ 220V with the incoming and outgoing of transformer will be part of the bus bar and switches as per SLD. Both the buses should be segregated.All incoming and outgoing cables should be from bottom entry.The panel shall be consisting of given rated bus bars of same size in all phases and neutral supported with DMC/SMC supports barriers and heat shrinkable colour code sleeves. The metering shall be provided as specified. The panels shall have short circuit capacity of minimum 50 KA. and equipped with bus bar and cable chambers. The panel maximum height must not exceed 1.6Mtrs. The job includes supply and fixing of MS Channel duly painted of size 100mm x 50mm x 5mm thick to be placed as support to the panels on trench of required length for placing the panel.

50

226001010

Main Incomer: 1000A 4P EDO type ACB (Make: L&T/ Legrand/ Schneider) - 1 No. Metering Set: 0-1000A Digital Ammeter - 1 No. 0-500V Digital Volt meter - 1 No. R, Y, B Indication lamps LED type - 3 Nos. 1000/5A C.T coils - 3 Nos. 500/5A C.T coils - 3 Nos. Ammeter between Earth and Neutral Bus with CT's - 1 No. KW, KVA, KWH, KVAH meters each (Make: Enercon/ HPL) - 1 No. PF Meter (Make: Enercon/ HPL) - 1 No. Outgoing: 3 phase 415V 315A 4P MCCB (Make: L&T/ Legrand/ Schneider) - 2 Nos 200A 4P MCCBs (Make: L&T/ Legrand/ Schneider) - 2 Nos. (one for transformer primary incomer) 125A 4P MCCB (Make: L&T/ Legrand/ Schneider) - 6 Nos. 32A 4P MCB (Make: L&T/ Legrand/ Schneider) - 1 No. Bus Bars suitable for 415kV,3Phase 125x10mm Al. Alloy suitable for 415V with heat shrinkable color coded bus bars for phases and neutral Dry Type transformer inbuilt IN PANEL 120kVA ,415V/220V, Star/Star Connection, 200A/ 315A, 3-ph, 50Hz supply The insulation should be rated for 1.1kV & it should withstand short circuit & other standard tests as per IS norms. Sub Incomer: 3 phase 220V (Transformer Secondary) 315A 4P MCCB (Make: L&T/ Legrand/ Schneider) - 1 No. Metering Set: 0-315A Digital Ammeter - 1 No. 0-500V Digital Volt meter - 1 No. R, Y, B Indication lamps LED type - 3 Nos. 315/5A C.T coils - 3 Nos. 150/5A C.T coils - 3 Nos. Ammeter between Earth and Neutral Bus with CT's - 1 No. Outgoing: 3 phase 220V 200A 4P MCCB (Make: L&T/ Legrand/ Schneider) - 1 No. 160A 4P MCCB (Make: L&T/ Legrand/ Schneider) - 1 No. 63A 4P MCB (Make: L&T/ Legrand/ Schneider) - 1 No. 32A 4P MCB (Make: L&T/ Legrand/ Schneider) - 2 Nos. 16A 4P MCB (Make: L&T/ Legrand/ Schneider) - 1 No. Bus Bars suitable for 220kV,3Phase 75x6mm Al. Alloy suitable for 220V with heat shrinkable color coded bus bars for phases and neutral Page 7 of 12

SL No

Item Code

Technical Description All the GA Drawings shall be approved by ARCI/Consultant

GI PIPE 51 125001128 Supply and laying of GI pipe of 50mm dia with all types of bends/T's/L's/ Coupling as per site conditions class B pipe for the run of U.G Cables under flooring at a depth of 300mm to clean room machinery GI pipe make: Tata Supply and laying of GI pipe of 100mm dia with all types of bends/T's/L's/ Coupling as per site conditions class B pipe for the run of U.G Cables under flooring at a depth of 300mm to clean room machinery GI pipe make: Tata Supply and laying of GI pipe of 150mm dia with all types of bends/T's/L's/ Coupling as per site conditions class B pipe for the run of U.G Cables under flooring at a depth of 300mm to clean room machinery GI pipe make: Tata

52

125001129

53

125001130

CABLES AND TERMINATIONS Supply of 3.5C x 300 Sq.mm PVC XLPE aluminum armoured U.G. cable. Grade with ISI mark stranded, complete as per IS 1554-1964 from sub-station to building incoming. 54 125001131 Make: Finolex/ Universal Note: 1) This item operation will be under discreation of ARC I 2) If the item is operated, a prior permission to be taken from ARC I Officials for procurement of cables. 3) Inspection of cables will be done at cable manufacturing unit by ARC I Officials before despatch of materials. Labor charges for run of 3.5C x 300Sqmm PVC XLPE aluminum armoured U.G cable in existing trench / PVC pipes /cable tray / hume pipes and also required ladders/ supports/ cable ties/ scafolding/ cable drum handling/ cable pulling and removing materials (as directed by ARC I officials) Labor for excavation of cable trench of size 1000mm wide x 1000mm depth in wet, dry, and rocky conditions of the soil for cable laying. The cables shall be laid on fine sand bed of 150mm (Sand with out sharp edges) and lay the cable of 8runs of 300 Sqmm in two 56 304005005 layers (three cables per layer) and cover the cable by providing fine sand up to 150mm as cushioning to laid cables and for protection cover with red bricks and backfill with the excavated earth and complete the reinstatement. The excess earth/ soil shall be removed from the site and transported to the place as per direction of the ARC I officials. Labor for excavation of cable trench of size 600mm wide x 1000mm depth in wet, dry, and rocky conditions of the soil for cable laying. The cables shall be laid on fine sand bed of 150mm (Sand with out sharp edges) and lay the cable of 3runs of 300 Sqmm and cover the cable by providing fine sand up to 150mm as cushioning to laid cables and for protection cover with red bricks and backfill with the excavated earth and complete the reinstatement. The excess earth/ soil shall be removed from the site and transported to the place as per direction of the ARC I officials. Supply, installation, testing & commissioning of cable termination (labour,material & equipments) of the cable at ONE end using double compression gland (Grip make), Aluminum or copper lugs (dowells make) for crimping including aluminum cable tag and making good as per IS Code. 3.5C X 300 SQMM AL .AR. CABLE Supply of 4C x 240 Sq.mm PVC XLPE Copper armoured U.G. cable. Grade with ISI mark stranded, complete as per IS 1554-1964 from panel to sputtring system and seevapouration machines in clean room. Make: Finolex/ Universal Labor charges for run of 4C x 240Sqmm PVC XLPE copper armoured U.G cable in existing GI pipe/ cable tray and also required supports/ cable ties/ cable drum handling/ cable pulling and removing materials (as directed by ARC I officials)

55

304005004

57

304005006

58

125001132

59

125001133

60

304005007

Page 8 of 12

SL No

Item Code

Technical Description Supply, installation, testing & commissioning of cable termination (labour,material & equipments) of the cable at ONE end using double compression gland (Grip make), Aluminum or copper lugs (dowells make) for crimping including aluminum cable tag and making good as per IS Code. 4C X 240 SQMM CU .AR. CABLE Supply of 4C x 95 Sq.mm PVC XLPE Copper armoured U.G. cable. Grade with ISI mark stranded, complete as per IS 1554-1964 from panel to AC/ De-dusting panel and Lamination equipment in clean room. Make: Finolex/ Universal Labor charges for run of 4C x 95Sqmm PVC XLPE copper armoured U.G cable in existing GI pipe/ cable tray and also required supports/ cable ties/ cable drum handling/ cable pulling and removing materials (as directed by ARC I officials) Supply, installation, testing & commissioning of cable termination (labour,material & equipments) of the cable at ONE end using double compression gland (Grip make), Aluminum or copper lugs (dowells make) for crimping including aluminum cable tag and making good as per IS Code. 4C X 95 SQMM CU .AR. CABLE Supply of 4C x 50 Sq.mm PVC XLPE Copper armoured U.G. cable. Grade with ISI mark stranded, complete as per IS 1554-1964 from panel to sustrate cleaning system in clean room. Make: Finolex/ Universal Labor charges for run of 4C x 50Sqmm PVC XLPE copper armoured U.G cable in existing GI pipe/ cable tray and also required supports/ cable ties/ cable drum handling/ cable pulling and removing materials (as directed by ARC I officials) Supply, installation, testing & commissioning of cable termination (labour,material & equipments) of the cable at ONE end using double compression gland (Grip make), Aluminum or copper lugs (dowells make) for crimping including aluminum cable tag and making good as per IS Code. 4C X 50 SQMM CU .AR. CABLE Supply of 4C x 16 Sq.mm PVC XLPE Copper armoured U.G. cable. Grade with ISI mark stranded, complete as per IS 1554-1964 from existing PDB to LDB's. Make: Finolex/ Universal Labor charges for run of 4C x 16Sqmm PVC XLPE copper armoured U.G cable with required fixing materials including base saddles at every 500mm (as directed by ARC I officials) Supply, installation, testing & commissioning of cable termination (labour,material & equipments) of the cable at ONE end using double compression gland (Grip make), Aluminum or copper lugs (dowells make) for crimping including aluminum cable tag and making good as per IS Code. 4C X 16 SQMM CU .AR. CABLE Supply of 4C x 6 Sq.mm PVC XLPE Copper armoured U.G. cable. Grade with ISI mark stranded, complete as per IS 1554-1964 from panel to scrubbing system, CBD system, solar light simulator, four-prop resistivity system in clean room, ODU's, power DB to 32A TP industrial socket . Make: Finolex/ Universal Note: 1) This item operation will be under discreation of ARC I 2) If the item is operated, a prior permission to be taken from ARC I Officials for procurement of cables. 3) Inspection of cables will be done at cable manufacturing unit by ARC I Officials before despatch of materials. Labor charges for run of 4C x 6Sqmm PVC XLPE copper armoured U.G cable in existing GI pipe/ cable tray/ on walls with required fixing materials including base saddles at every 500mm (as directed by ARC I officials) with No.10 SWG G.I wire for earth connections for the cables.

61

125001134

62

125001135

63

304005008

64

125001136

65

125001137

66

304005009

67

125001138

68

125001139

69

304005010

70

125001140

71

125001141

72

304005011

Page 9 of 12

SL No

Item Code

Technical Description Supply, installation, testing & commissioning of cable termination (labour,material & equipments) of the cable at ONE end using double compression gland (Grip make), Aluminum or copper lugs (dowells make) for crimping including aluminum cable tag and making good as per IS Code. 4C X 6 SQMM CU .AR. CABLE Supply of 4C x 2.5 Sq.mm PVC XLPE Copper armoured U.G. cable. Grade with ISI mark stranded, complete as per IS 1554-1964 from power DB to 16A TP Flume hood socket Make: Finolex/ Universal Labor charges for run of 4C x 2.5Sqmm PVC XLPE copper armoured U.G cable with required fixing materials including base saddles at every 500mm (as directed by ARC I officials) with No.10 SWG G.I wire for earth connections for the cables. Supply, installation, testing & commissioning of cable termination (labour,material & equipments) of the cable at ONE end using double compression gland (Grip make), Aluminum or copper lugs (dowells make) for crimping including aluminum cable tag and making good as per IS Code. 4C X 2.5 SQMM CU .AR. CABLE Supply of 3.5C x 70 Sq.mm PVC XLPE aluminum armoured U.G. cable. Grade with ISI mark stranded, complete as per IS 1554-1964 from panel to power DB's in ground and first floor, AC VTPN DB, clean room power sockets DB. Make: Finolex/ Universal Labor charges for run of 3.5C x 70Sqmm PVC XLPE copper armoured U.G cable with required fixing materials including base saddles at every 500mm as directed by ARC I staff/ officials and also required ladders/ supports/ scafolding/ cable drum handling/ cable pulling & removing materials Supply, installation, testing & commissioning of cable termination (labour,material & equipments) of the cable at ONE end using double compression gland (Grip make), Aluminum or copper lugs (dowells make) for crimping including aluminum cable tag and making good as per IS Code. 3.5C X 70 SQMM CU .AR. CABLE

73

125001142

74

125001143

75

304005012

76

125001144

77

125001145

78

304005013

79

125001146

LT CABLE MARKER 80 125001147 Supply, installation, testing and commissioning of Cast Iron LT Cable markers duly showing the direction of cable route. The markers are required to be fixed on GI angle of size 35 x 35 x 6mm of length 700mm and grouted in PCC of size 200 x 200 x 200mm at every interval of 15 to 20metres length as DIRECTED BY ARCI OFFICIALS

HUME PIPE Supply and Laying NP2 class RCC hume pipe with bends, Collars and other accessories of 450mm dia including Cutting the tar road or cement road along with culverts either side 81 125001148 of the road to make cable trench of size of 600(width) mmx1000(depth)mm laying of 450mm dia hume pipes and remaking to original shape both road with tar, pcc & culverts with bricks, plastering as directed by ARC I Officials for the run of power cables. EARTHING Supply, installation, testing and commissioning and providing independent earthing with 100 mm. Dia "B" Class 3.0 meter long GI Pipe and covered with mesh of suitable size funnel enclosed in Cement concrete Chamber of 450 x 450 x 450 mm. With suitable RCC precast cover with lifting arrangements. The GI pipe required to be provided with staggered holes of 16 Nos. of 12 mm. dia to the Earth electrode, filling with 200mm layers height of salt and charcoal around dia 400mm(keeping gi pipe in center) and from the bottom of the pipe to the bottom of the CC chamber. The connection from the electrode will be through 50 x10 mm. GI strip provided at the top with 12mm holes(4nos) of the GI pipe along with GI(10mm) nut bolts and washers complete

82

125001149

Page 10 of 12

SL No

Item Code

Technical Description Providing independent earthing for Clean Room equipments with 600mm x 600mm x 3.15mm thick copper plate rigidly fixed to 40mm dia G.I Pipe of 3mt. length connected with reducers providing G.I funnel with wire mesh as per National Electric Code including C.C.Chamber of size 400m x 400m x 400mm covered with R.C.C. Slab filling with salt and charcoal from the bottom giving earth connection from electrode G.I strip of 25mm x 6mm x 200mm length with all accessories and labor charges complete as per IS specifications 732/1982. Supply, fixing, laying, commissioning and testing of the following GI Strip as earthing conductor / bus from equipment to earth bus & as a earth bus it self in a room complete with required GI nut bolts at every 2mtrs and fixing GI strip to wall /beam /angles to with 8mm anchor bolt & nut terminations of 50 X 6 MM GI STRIP at height decided by ARCI officials in a work shop/ room/ building. Supply, fixing, laying, commissioning and testing of the following GI Strip as earthing conductor from equipment/earth bus to earth pit/ station complete with required nut bolts and terminations 25 X 3 MM GI STRIP in excavated trench of 300mmx300mm depth in all types of soils ,after laying the GI strip refilling the earth back Supply, fixing, laying, commissioning and testing of the following Cu Strip as earthing conductor from equipment/earth bus to earth pit/ station complete with required nut bolts and terminations 25 X 3 MM CU STRIP in excavated trench of 300mmx300mm depth in all types of soils ,after laying the GI strip refilling the earth back Supply, fixing, laying, commissioning and testing of the 8 SWG GI WIRE as earthing conductor / bus from equipment to earth bus & as a earth bus it self in a room complete with required MATERIAL FOR FIXING at every 2mtrs and fixing gi WIRE to wall /beam /angles with REQUIRED MATERIALS AND bolt & nut FOR terminations at height decided by ARCI officials in a work shop/room/ building.

83

125001150

84

125001151

85

125001152

86

125001153

87

125001154

Lighting Arrestor As per the direction of ARCI staff Supply, installation, testing Commissioning and handing over to ARCI Lightning arrestor of copper to be installed at the height of 9mts i.e. on the first floor of the building with concrete basement with complete material machinery and man power. (FRANKLIN ROD)

88

125001155

Page 11 of 12

PROJECT: SOLAR CELL, ARC I LIST OF APPROVED MAKES S.No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Item Description Air Circuit Breaker Moulded Case Circuit Breaker Miniature Circuit Breaker Distribution Boards Amphere Meter DIGITAL Voltage Meter DIGITAL Single core and Multi core PVC insulated copper wires Fire Retardent Low Smoke. Multi core AL. AR.Cables Multi core CU. AR.Cables Cable Glands Cable Lugs Switches & Sockets PVC conduits Light Fittings (luminaries) Telephone sockets LAN Sockets Telephone Cables LAN Cables GI pipe Audio/ Video System Makes L&T/ Legrand/ Schneider L&T/ Legrand/ Schneider L&T/ Legrand/ Schneider Siemens/ Legrand/ L&T/ Schneider Enercon/ HPL Enercon/ HPL Finolex/ Anchor/ L&T Finolex/ Polycab/ Univarsal Finolex/ Polycab/ Univarsal Grip Dowell Siemens/ MDS/ Anchor/ L&T/ Schneider Precision/ Avon Plast Phillips/ Wipro Legrand/ L&T/ MK/ Salzer Beldon/ D Link/ Legrand Finolex/ Polycab/ Gold Medal D Link/ Legrand Tata Bosch

Vous aimerez peut-être aussi