Vous êtes sur la page 1sur 3

Limitron Class J

JKS 600Vac, 70-600A, Fast-Acting Fuses


Dimensions - in
4.63" 3.63" 2.63" 0.38" 65 to 100A 5.75" 4.38" 3.0" 0.75" 1" 0.28" 1.13" 0.13" 7.13" 5.25" 3.38" 0.41" 1.63" 0.53" 225 to 400A 8.0" 6.0" 3.75" 1.5" 0.38" 100 to 200A 1.38" 0.19" 0.69" 450 to 600A 2.13" 1.88" *2" 0.25"

1.13" 0.28"

0.53" 2" 2.5" 0.38"

Description: Advanced protection Class J current-limiting, fast-acting fuses. Catalog Symbol: JKS-(amp) Ratings: Volts 600Vac Amps 70-600 IR 200kA Vac RMS Sym. Agnecy Information: CE, UL Listed Class J (Guide # JDDZ, File # E4273) CSA HRCI-J (Class 1422-02, File # 53787) Catalog Numbers (amps)
JKS-70 JKS-80 JKS-90 JKS-100 JKS-110 Amp Rating 70100 110200 225400 450600 JKS-150 JKS-175 JKS-200 JKS-225 JKS-250 Carton Qty. 5 1 1 1 JKS-350 JKS-400 JKS-450 JKS-500 JKS-600

Features: Single element, current limiting fuses provide superior shortcircuit protection Protects low interrupting capacity circuit breakers. Limits the short-circuit current to meet the interrupting capacity requirements of existing equipment On older systems available short-circuit current may exceed the interrupting capacity of the circuit breakers, fuses can be installed in series with existing equipment Well suited for lighting and heating circuits and other noninductive loads Provides component short-circuit protection in compliance with NEC 110.10, where protection devices shall clear a fault without extensive damage to the circuit components High interrupting rating helps meet the requirements of future system expansion and the increases in available utility short-circuit current Fuses can easily be selectively coordinated Recommended Fuse Blocks and Holders
Fuse Amps 0-30 35-60 0-30 35-60 0-30 35-60 0-30 35-60 1-Pole 2-Pole Open Blocks J60030-1 J60030-2 J60060-1 J60060-2 Pyramid Blocks JP60030-1 JP60030-2 JP60060-1 JP60060-2 CH Series Holders CH30J1 CH30J2 CH60J1 CH60J2 Safety J Holders JT60030 JT60060 3-Pole J60030-3 J60060-3 JP60030-3 JP60060-3 CH30J3 CH60J3

Carton Quantity and Weight

For additional information on the Class J fuse blocks and holders, see data sheets # 1114 (open blocks), #1108 (pyramid blocks), # 2144 (CH Series) and # 1152 (Safety J). Fuse Reducers For Class R Fuses
Equipment Fuse Clips 60A 100A 200A Desired Fuse (Case) Size 30A 30A 60A 60A Catalog Numbers (Pairs) 600V J-63 J-13 J-16 J-26

Not for bolt-in applications.

0713

BU-SB13736

Page 1 of 3

Data Sheet # 1027

Limitron Class J
JKS 600Vac, 70-600A, Fast-Acting Fuses
Time-Current Curves - Average Melt

100A

200A

400A

600A

300

AMP RATING

100

10

TIME IN SECONDS

0.1

RMS SYMMETRICAL CURRENT IN AMPS

0713

BU-SB13736

Page 2 of 3

10,000
Data Sheet # 1027

40

100

1,000

0.01

Limitron Class J
JKS 600Vac, 70-600A, Fast-Acting Fuses
Current-Limitation Curves
400,000

INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS

300,000

200,000

100,000 80,000 60,000 50,000 40,000 30,000 20,000

600 400 200 100

10,000 8,000 6,000 5,000 4,000 3,000

A
2,000

80,000 100,000

PROSPECTIVE SHORT-CIRCUIT CURRENTSYMMETRICAL RMS AMPS

Current-Limiting Effects Prosp. Let-Through Current S.C.C. (Apparent RMS Symmetrical Vs. Fuse Rating) 100A 200A 400A 600A 5000 2000 3000 4000 5000 10,000 3000 4000 6000 9000 15,000 3000 4000 7000 10,000 20,000 3000 5000 8000 11,000 25,000 3000 6000 9000 12,000 30,000 3000 6000 9000 13,000 35,000 4000 6000 9000 13,000 40,000 4000 7000 10,000 14,000 50,000 4000 7000 10,000 15,000 60,000 5000 7000 11,000 16,000 70,000 5000 8000 11,000 17,000 80,000 5000 8000 12,000 17,000 90,000 6000 9000 13,000 18,000 100,000 6000 9000 13,000 18,000 150,000 6000 9000 14,000 22,000 200,000 7000 10,000 16,000 24,000

The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 0713 BU-SB13736 Page 3 of 3 Data Sheet # 1027

200,000

1,000

2,000

4,000 5,000 6,000

3,000

8,000 10,000

30,000

40,000 50,000 60,000

20,000

1,000

AMP RATING

Vous aimerez peut-être aussi