k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 1 of 395 Issue 7











NIPPON OIL EXPLORATION (MALAYSIA) LTD


HELANG CENTRAL PLATFORM


GAS & CONDENSATE FISCAL METERING SYSTEM
HDP/PO/01/209



COMPUTER SYSTEM FUNCTIONAL DESIGN SPECIFICATION




NIPPON VDRL CODE:
1.12/2.18


VENDORS DOCUMENT NUMBER:
1614/2005

Notes:



E 14.02.04 Final As Built ACL NAL
D 13.01.03 Inc Comments ACL WM
C 29.01.02 Inc Comments ACL MW
B 05.01.02 Not Issued ACL MW
A 12.11.01 For Approval ACL MW
Rev. Date Issue Status Prep. By Checked By Approved By

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 2 of 395 Issue 7















Functional Design Specification



Helang Metering System


Flow Metering System




Prepared for:

Alderley Systems Ltd


















Alderley Controls Limited
Arnoldsfield Estate
The Downs
Wickwar
Wotton-under-Edge
Glos
GL12 8JB

+44 (0)1454 292100
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 3 of 395 Issue 7
Contents
1 REVISION CONTROL ............................................................................................................................................6
2 INTRODUCTION....................................................................................................................................................8
2.1 Standards and specifications...................................................................................................................8
2.2 Document Scope.....................................................................................................................................8
2.3 Abbreviations and Acronyms .................................................................................................................9
3 SCOPE OF SUPPLY..............................................................................................................................................10
3.1 Panel Hardware.....................................................................................................................................10
3.2 Equipment Supplied Loose...................................................................................................................10
3.3 Software and configuration...................................................................................................................10
3.4 Documentation......................................................................................................................................10
4 SYSTEM OVERVIEW...........................................................................................................................................11
4.1 Gas Export Metering System................................................................................................................11
4.2 Condensate Export Metering System ...................................................................................................11
5 PANEL ...............................................................................................................................................................12
5.1 Panel shell.............................................................................................................................................12
5.2 Field cable handling..............................................................................................................................12
5.3 Power ....................................................................................................................................................13
5.4 Earthing ................................................................................................................................................14
5.5 Zener Barriers .......................................................................................................................................14
5.6 Wiring...................................................................................................................................................14
5.7 Wire identification................................................................................................................................14
5.8 Accessories ...........................................................................................................................................15
6 SYSTEM FEATURES............................................................................................................................................16
6.1 Introduction ..........................................................................................................................................16
6.2 Computer Hardware .............................................................................................................................17
6.3 Ram Battery..........................................................................................................................................21
6.4 Signal Handling ....................................................................................................................................21
6.5 System Communications ......................................................................................................................22
6.6 Stream Status ........................................................................................................................................24
6.7 Maintenance Mode ...............................................................................................................................24
6.8 Security System....................................................................................................................................25
6.9 Totals ....................................................................................................................................................26
6.10 Configuration and Constants ................................................................................................................27
6.11 Alarms ..................................................................................................................................................27
6.12 Display Units and formats ....................................................................................................................29
7 CONDENSATE STREAM FLOWCOMPUTERS....................................................................................................31
7.1 General Features ...................................................................................................................................31
7.2 Functions ..............................................................................................................................................34
7.3 Input / Output Definition ......................................................................................................................36
7.4 Calculations ..........................................................................................................................................39
7.5 Displays ................................................................................................................................................45
7.6 Alarms ..................................................................................................................................................46
8 PROVER COMPUTER ..........................................................................................................................................51
8.1 General Features ...................................................................................................................................51
8.2 Proving .................................................................................................................................................51
8.3 Proving Sequences................................................................................................................................54
8.4 Prover Connection Schedule.................................................................................................................58
8.5 Calculations ..........................................................................................................................................60
8.6 Displays ................................................................................................................................................66
Alarms ..............................................................................................................................................................71
9 GAS STREAM FLOWCOMPUTER.......................................................................................................................78
9.1 General Features ...................................................................................................................................78
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 4 of 395 Issue 7
9.2 Functions ..............................................................................................................................................84
9.3 Input / Output Definition ......................................................................................................................86
9.4 Calculations ..........................................................................................................................................88
9.5 C5+Liquid Calculations........................................................................................................................98
9.6 Displays ..............................................................................................................................................101
9.7 Alarms ................................................................................................................................................102
10 BACK-UP GAS FLOWCOMPUTER .................................................................................................................107
10.1 General Features .................................................................................................................................107
10.2 Functions ............................................................................................................................................107
10.3 Input / Output Definition ....................................................................................................................107
10.4 Calculations ........................................................................................................................................109
10.5 Displays ..............................................................................................................................................110
10.6 Alarms ................................................................................................................................................112
11 BUY BACK GAS FLOWCOMPUTER ...............................................................................................................119
11.1 General Features .................................................................................................................................119
11.2 Functions ............................................................................................................................................120
11.3 Input / Output Definition ....................................................................................................................121
11.4 Calculations ........................................................................................................................................122
11.5 Displays ..............................................................................................................................................123
11.6 Alarms ................................................................................................................................................125
12 SUPERVISORY COMPUTERS .........................................................................................................................129
12.1 Hardware Specification ......................................................................................................................129
12.2 General Features .................................................................................................................................130
12.3 Meter Factor Linearisation .................................................................................................................132
12.4 Functions ............................................................................................................................................135
12.5 Input / Output Definition ....................................................................................................................137
12.6 Calculations ........................................................................................................................................139
12.7 Displays ..............................................................................................................................................141
12.8 MMI Display Details ..........................................................................................................................142
12.9 Alarms ................................................................................................................................................148
12.10 Printing and Reports .......................................................................................................................158
12.11 Report Formats ...............................................................................................................................160
13 COMMUNICATIONS......................................................................................................................................180
13.1 Chromatograph Communications .......................................................................................................180
13.2 Analyser Control.................................................................................................................................184
13.3 Modbus Communications...................................................................................................................186
14 PLC.............................................................................................................................................................195
14.1 PLC Connection Schedule..................................................................................................................196
15 SAMPLE LOOP P& ID CONTROLLER.............................................................................................................199
15.1 Connection Schedule ..........................................................................................................................200
16 VALIDATION SYSTEM..................................................................................................................................201
16.1.................................................................................................................................................................201
17 OFF-LINE METERING P.C. ...........................................................................................................................203
17.1 Functions ............................................................................................................................................204
17.2 Laboratory Data..................................................................................................................................204
17.3 Condensate Calculations.....................................................................................................................205
17.4 Reports................................................................................................................................................207
18 APPENDIX....................................................................................................................................................209
18.1 Flowcomputer Specification...............................................................................................................209
18.2 S600 Connection Schedules ...............................................................................................................210
19 AS- BUILT REPORTS....................................................................................................................................227
20 AS-BUILT DISPLAYS ...................................................................................................................................244
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 5 of 395 Issue 7
20.1 S600 Gas Export .................................................................................................................................244
20.2 Gas Back Up.......................................................................................................................................275
20.3 Buy Back Gas .....................................................................................................................................325
20.4 Export Condensate..............................................................................................................................351
20.5 Prover .................................................................................................................................................376
21 APPENDIX....................................................................................................................................................396
21.1 Supervisory Displays ..........................................................................................................................396
21.2 Calculation Flowcharts .......................................................................................................................396

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 6 of 395 Issue 7
J RLVISION CON1ROL

Section Issue Date By Comment
All 1.0 21/09/2001 B Horner Original
All 2.0 03/12/2001 B Horner Incorporate Customer Comments
All 3.0 23/01/2002 B Horner Incorporate Customer Comments
All 4.0 05/04/2002 B. Horner Update to As-Built status
All 5.0 14/11/2002 B. Horner Add flow charts, incorporate customer comments
All 6.0 23/06/2003 B. Horner Incorporate UGSA Mods FDS
All 7.0 19/01/2004 B. Horner Incorportae UGSA C5+ mods addendum.


Holds

Hold Paragraph Description






Variations

The following changes in this document are the subject of outstanding variation requests. If they are included
in this document, their inclusion in this document is provisional, subject to acceptance of Alderley Controls
commercial and delivery terms.

Variation Paragraph Description





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 7 of 395 Issue 7
Document QA Record


Client: Alderley Systems Ltd
Order No. 01/JK/1614
Project Title. Helang metering System
Works Order Reference. M1914
Document Title. Functional Design Specification
File Reference k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
Prepared By:

Brian Horner
Reviewed By:

Mike Seabrook

Client Approval (Stamp/Sign)























Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 8 of 395 Issue 7
2 IN1RODUC1ION
It is the purpose of this document to describe the Helang Central metering system to be supplied to Alderley
Systems on purchase order 01/JK/1614.

2.J Standards and specifications
The metering computer system operates to the following major standards -

AGA8 - Natural Gas Density and Compressibility, Second Printing, July 1994
ISO 6976 Natural gas calculation of Calorific Value, Density and Relative Density, 1995
API MPMS Chapter 12, Calculation of Petroleum Quantities.
API MPMS Chapter 12.2, Calculation of Liquid Petroleum Quantities Measured by Turbine or
Displacement Meters.
API MPMS Chapter 4 Proving Systems
ISO 5167 Measurement of fluid flow by means of Orifice Plates, Nozzles and Venturi Tubes inserted
in Circular Cross Section Conduits running full, 1998
Correction Factor (CTLm) IP Paper 2 (ASTM D 1250)
Correction Factor (CPLm) API Ch 11.2.1M, 1984
Density Correction API Ch 12
Conversions API 2564 Ch15
Measured Density Solartron User Manual
GPA Standard 2186-02
GPA Standard 8173-94
GPA Standard 2145-92
ASTM D -1250:IP200, Table 52

All calculations are performed to full accuracy without rounding or truncation

2.2 Document Scope

The items listed and functionality explicitly detailed in the FDS will be supplied by Alderley Controls Ltd to
Alderley Systems Ltd. Any additional items or functionality, implicit or not, are above and beyond the scope of
supply.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 9 of 395 Issue 7

2.3 Abbreviations and Acronyms
The following table lists all the abbreviations and acronyms used in this FDS.

Abbreviation Meaning
AC Alternating current
ACL Alderley Controls Limited
ADC Analogue to digital converter
AGA American Gas Association
ATM Acceptance test manual
CCR Central control room
CER Central equipment room
CPU Central processor unit
DAC Digital to analogue converter
DC Direct current
DCS Distributed Control System
DRAM Dynamic Random Access Memory (not battery supported)
S600 Daniel flow measurement computer
EEPROM Electrically erasable programmable read only memory
FDS Functional design specification
FPGA Field programmable gate array
FSK Frequency shift keying
GPA Gas Processors Association
HART Highway Addressable Remote Transducer
H/W Hardware
IC Integrated circuit
IS Intrinsically safe
ISO International Organisation for Standardisation
KIMS Kelton Instrument Management System
mA Milli-ampere
MOV Motor operated valve
MPMS Manual of Petroleum Measurement Standards
MTBF Mean Time Between Failures
O&M Operation and maintenance manual
PC IBM compatible personal computer
PRT Platinum resistance thermometer
PSU Power Supply Unit
RAM Random access memory
RTC Real Time Clock
S/W Software
SCSI Small Computer System Interface (normally for disc drives)
SPIR Spare parts and interchangeability record
SRAM Static Random Access Memory (usually battery supported)
t Metric tonne
UCP Unit control panel
UPS Un-interruptable power supply
UTP Un twisted pair
UVPROM, PROM UV erasable programmable read only memory
V Volts
VAC Volts, alternating current
VDC Volts, direct current
VDU Visual display unit



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 10 of 395 Issue 7
3 SCOPL OI SUPPLY

3.J Panel Hardware
Item Qty Description Model
1 3 Export Gas Flowcomputer Daniel S600
2 1 Back Up Gas Flowcomputer Daniel S600
3 1 Buy Back Gas Flowcomputer Daniel S600
4 2 Condensate Flowcomputer Daniel S600
5 1 Prover Computer Daniel S600
6 1 PLC Modicon Momentum
7 2 Operator Workstation AMC-500 4U Rack mount PC
8 1 Electronic Chart Recorder Eurotherm 4101C
9 1 Sample loop P & ID flow controller Eurotherm 2604
10 1 3 bay Panel incorporating above and c/w
terminals, barriers etc
Rittall PS 4808 series


3.2 Lquipment Supplied Loose

Item Qty Description Model
1 1 Laser Printer (Colour) Laserjet 4500N
2 1 Dot Matrix Printer c/w Sound Abatement cover
& paper receptacle
Epson LQ 680
3 1 Validation System Kelton Instrument Management System
4 1 Off-Line Metering PC Compaq EVO


3.3 Software and configuration
Item Qty Description
1 2 Supervisory flow computer configuration (two identical copies)
2 2 Citect software licence (single user)
3 2 Turbine meter configuration
4 3 Gas Export configuration
5 1 Gas Buy back configuration
6 1 Gas Back Up configuration
7 2 Microsoft Windows NT licence
8 1 Citect version 5 PC configuration
9 1 Database Configuration on Off-Line Metering PC

3.4 Documentation
The following documentation will be supplied:
Item Description
1 Functional Design Specification (FDS), incorporating:
System overview diagram
2 Operation and Maintenance Manual (O&M)
3 Completed Acceptance Test Manual (ATM)
4 Recommended spares list - commissioning
5 Recommended spares list - 2 years operation

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 11 of 395 Issue 7
4 SYS1LM OVLRVILW
This Functional Design Specification describes the metering system to be supplied for use on the Helang
Central Platform

The metering system consists of a gas export metering system and condensate export metering system, prover,
back up and buy back gas metering implemented using Daniel S600 flowcomputers. The supervisory functions
are incorporated in a pair of PCs in duty standby mode and a PLC providing additional supervisory I/O.
The measurement computers are housed in a 3-bay panel for installation in the Instrument Equipment Room.
The panel will house all computers, the PCs, monitor and keyboard with integral trackerball, the
chromatograph controller and recorder, barriers and terminals to connect to the plant instrumentation.

The workstation provides overall supervision and control of the gas export metering system, the condensate
export metering system, prover system and buy back gas metering.
Two printers are provided with the system; a laser printer for metering report printing and screen dumps from
the workstation, and a dot matrix printer for alarm printing. The printers are supplied loose for mounting on
suitable tables (by others) in the Central Control room.

The gas and condensate flowcomputers are connected to each of the supervisory computers via dual redundant
data highways. The primary connection uses Ethernet and the secondary connection is an RS485 serial link
using Modbus protocol.
An off-line metering PC is provided for entry of laboratory data for the Condensate system and re-calculation of
the component mass totals heat content and standard volume for the period covererd by the laboratory sample
results. The offline PC is connected to the system Ethernet highway and prints reports to the system laser
printer.
4.J Gas Lxport Metering System
The gas export metering system consists of 3 x 50 % orifice plate meter runs each connected to a dedicated flow
computer. Each flowcomputer accepts analogue (4-20mA) signals from 4 x DP transmitters, 1 x Pressure
transmitter and a temperature element (PRT).
Density measurement is performed using a pulse input from a densitometer in each meter run.
A common gas chromatograph installed upstream of the meter runs provides gas composition via a serial link to
the supervisory computer and the gas export flowcomputers and is used for density calculation according to
AGA8. The gas composition is downloaded from the supervisory computer to the back up gas flowcomputer
and the buy back gas flowcomputer.
A time and flow proportional pulse output is provided from the PLC for the gas sampling system.

A single back up flowcomputer accepts the signals for three sets of back up transmitters and provides a
metering back up for all three streams.
4.2 Condensate Lxport Metering System
The condensate export metering system consists of 2 x 100% turbine meter runs and a bi directional loop
prover.
A dedicated flowcomputer is provided for each meter run and the prover loop.
The flowcomputers accept dual pulse inputs from the turbine meter, an analogue (4-20mA) signal representing
pressure and a PRT signal representing temperature.
Dual densitometers mounted in the header provide pulse signals to each flowcomputer for density measurement.
Temperature and pressure measurements at the densitometer header are also wired to each flowcomputer.
A time and flow proportional pulse output is provided from the PLC to the sample system on the densitometer
loop.

4.2.J Prover Computer
A dedicated S600 computer is provided to interface to the bi-directional sphere type prover.
The prover computer accepts analogue (4-20mA) signals representing inlet and outlet pressures, and PRT
signals representing inlet and outlet temperatures.
Four sphere switches are fitted to the prover and a pair of switches are selected for use by the prover computer.
The prover computer is connected to the supervisory computers and in addition communicates with the
condensate stream computers via a dedicated serial bus to gather data and control the stream valves.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 12 of 395 Issue 7
S PANLL
One Rittall 3 bay panel will be provided for the field interface devices and the Supervisory computers to be
installed in the Instrument Equipment Room. The metering equipment will be front of panel mounted with rear
access afforded by three hinged removable doors.

S.J Panel shell
The panel shell will consist of three Rittal PS4800 bays, with front of panel dimensions nominally 2400mm
wide x 800 deep x 2000 high. Details are summarised below:
Number of bays 3
Cable entry Bottom fitted with Rittal clamp rails and cable clamps
Front doors None
Ventilation Louvred Rear Doors, Roof fans.
Rear doors 3
Plinth Standard (add 100mm to height)
Colour RAL 7032 Light Grey
Lifting 12 eyebolts

S.2 Iield cable handling
Field cable armour will be made off to glands fitted in detachable gland plates at the bottom of the panel. Rittal
clamp rails type PS 4193 shall be fitted complete with cable clamps.
Field cable cores will be routed in open slot trunking dedicated to field wiring, and terminated in the panel as
follows:
Signal type Termination
Not intrinsically safe Klippon SAKR/35 - beige
Intrinsically safe Klippon SAKR/35 - blue
Incoming Power Klippon SAK - beige

Sufficient barriers will be provided to terminate all used field loops. Any additional spare cores of IS cables are
terminated to blue Klippon SAK/35 terminals clipped to the isolator mounting rail. Terminals and isolators will
be mounted on top hat profile rail.
All terminal rails including those in AC and DC circuit breakers and distribution boxes will provide 25% spare
capacity.
Trunking lids for IS wires on the hazardous area side of the Zener barrier are colour coded blue. All other
wiring, including IS circuits on the safe area side of Zener barrier are run in standard grey trunking. All
trunking will be Tehalit type.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 13 of 395 Issue 7
S.3 Power
The panel accepts dual 240V +/- 10% AC 50Hz +/- 60Hz feeds from a UPS system, one nominated primary
feed and one backup. In the event of failure of the primary supply automatic switchover to the back up supply
will occur.
Incoming AC power is terminated to EMC filters mounted in a screened enclosure. In order to meet EC
requirements for conducted RFI immunity, the sheath of the incoming supply cables must be made off to an
EMC gland attached to the filter box.
AC power passes from the transient filter through an isolator into a fuse box fitted with approximately 5 double
pole magnetic over current circuit breakers. Circuit breakers ratings are generally selected to protect panel
wiring, individual pieces of equipment being protected by their own fuses.
Two 24VDC power supplies, supplied from the AC feed, are combined with diodes to ensure bumpless transfer.
Each 24V supply will provide an alarm output. 24VDC power is distributed via 8-way fuse modules with
power status indication.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 14 of 395 Issue 7
S.4 Larthing
The panel is fitted with three separate and independent earth bars:
Safety Earth (SE) for connection of panel steel work, chassis of all devices and ground of AC
power equipment.
Instrument Earth (IE) for connection of cable shields and negative side of analogue nad digital
loops
Intrinsically Safe Earth (IS) for connection of Zener barrier earth.
All removable panels and doors are bonded to protective earth bar using yellow / green wire. It is critical to the
safe and reliable operation of the panel that clean, reliable earth connections be provided for all earth rails.

S.S Zener Barriers
MTL 700 series zener barriers will be used for IS signals, as follows:
Sensor type Interface
HART & 4-20mA inputs MTL 787S
Densitometer Inputs MTL 787S
The analogue signal representing % age full from the gas sample can will be interfaced using an Elco 325
barrier

S.6 Wiring
Signal type Wire type Colour Size
(mm
2
)
Power distribution (+24V) PVC, single Red 2.5
Power distribution (0V) PVC, single Black 2.5
Signals (normal) PVC, single Grey 1.0
Signals (IS) PVC, single Blue 1.0
Solenoid signals PVC, single Grey 2.5
Power distribution (240V) PVC, triple
Sheath Black
Live Brown 2.5
Neutral Light Blue 2.5
Earth Yell/Grn 2.5
Protective earth PVC, single Yell/Grn 6
Clean earth PVC, single Light Grn 2.5
IS earth PVC, single Yell/Grn 6

Note: The connection to the S600 computers uses D type connectors with solder bucket connections which take
a maximum wire size of 0.2mm.
All panel wires are terminated in bootlace ferrules, and identified with a computer-printed sleeve. Where
termination of two wires in a single terminal cannot be reasonably avoided, one double ferrule is used for both
wires.
Earth wiring to doors, gland plates and other moveable parts will be 6mm.
S.7 Wire identification
Wires within the panel will be identified using heat shrink labels, using four digits in the form ab-cd indicating
sheet number and wire number. For example, 12-34 indicates wire number 34 on sheet 12 of the panel wiring
diagram. Incoming terminals / isolated repeaters will be identified by client tag number.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 15 of 395 Issue 7

S.8 Accessories
Each panel bay is equipped with one each of the following:
240VAC light, with integral switch
240V roof fitted ventilation fan
240V utility socket
Drawing pocket


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 16 of 395 Issue 7
6 SYS1LM ILA1URLS
6.J Introduction
This chapter specifies those features that are common to the metering system computers. Please refer to later
sections for specific details of each configuration, and to details that are specific to the project.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 17 of 395 Issue 7
6.2 Computer Hardware
S600 Front of Panel View

F1 F2 F3 F4
VEW ALARM ACCEPT
MENU
1 2 3
4 5 6
7 8 9
- 0 . .. .
EXPT D8P PRNT
CLEAR CHNG
LCD Display
Function Keys
Alarm Keys & Light
Vector and Menu Keys
Numeric Keys
Operation Keys
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 18 of 395 Issue 7
6.2.J I Keys
At the top of the Keypad are ranged four yellow Function keys, numbered F1 to F4.
Each F key may be programmed as a shortcut to a frequently used display page.
The Period key (.) is used to program the function of these keys.

6.2.2 Vector and Menu Keys
The directional Vector key is located just below the Function keys, and is used to select the parameters to view
or change.

Use the Vector key to move around the matrix of display cells.
Select Right or Left vector keys to move along the row of data items on either side of the current display, i.e.
increment or decrement the display number after the decimal point on the status line. You can see that the
display wraps round from the last data item of the row, to the first.
The Left key is also used as the delete/backspace key when entering or changing data.
Use the Up or Down vector keys to view above or below the current display i.e. increment or decrement the
display number before the decimal point on the status line.
Note:
When the display moves vertically to view another row, the data item shown is always the first display cell of
that row.
Press the Menu key to move up one level of the display tree. On a data page this key returns the user to the
display parent menu.
Useful information:
Whilst on any menu page, pressing the Up vector key returns the user to the Main Menu.
6.2.3 Alarm Light and Keys
Press View to show the current alarm list in chronological order, the most recent alarm being displayed first.
Details of one alarm will be shown at a time. Use the up and down keys to scroll through the alarms. If viewing
alarms from a data page, the left or right vector keys will return the user to that page.
ALARM LIGHT
Colour Function
Green (solid) Normal operation,
No alarms present

Red (solid) At least one alarm present,
All alarms previously acknowledged

Red (flash) At least one alarm present,
and un-acknowledged

Yellow (flash) Display-keypad fault.
Communications to the P152 CPU module from
the front panel have failed


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 19 of 395 Issue 7
Alarm Page Layout

====================
11/10/1998 10:35:40_
I/O01 DWNSTR DENS
Low
0.0800 kg/m3



Alarm 1 of 11
====================

Key:
Row Description
1 Date and Time stamp of the alarm
Inverse video indicates the alarm is unacknowledged
2 Database object on which the alarm was raised.
3 Alarm descriptor
4 Snapshot value of the object as it went into alarm.
8 Alarm page description

6.2.4 Numeric Keys
The lower part of the Keypad houses the Numeric keys (light green).
The Numeric Keys offer the full number set 0-9, decimal point (period) and a minus key.
Numeric 0 to 9
These are used to enter or change data, and also used to navigate the display matrix.
Minus (-)
Used to enter negative quantities, and also used to define the Default Display.
To assign a default display, press the minus key whilst on the required data display, but not at the data entry or
menu page, and then follow the screen instructions.
Period( . )
Used as a decimal point when entering fractional quantities and in addition used to define hot keys for rapid
access to frequently used displays. This is done by pressing the period sign on the required display, but not at
the data entry or menu level, and then following the screen instructions.
6.2.S Operation Keys
The Operation keys (dark green) are used in conjunction with the Numeric keys to perform a variety of tasks.
The Operation keys are Expt, Clear, Disp, Print, Chng and Enter.
Exponent
Used to enter quantities in Scientific notation.
Where the value to be entered exceeds the space available on the display (20 characters), it is necessary to
express the data in scientific (exponential) terms.
Clear
Used to cancel or exit from the current operation and return to the previous data display. This key is also used to
activate the default display.
Data Pages
Generally each data page will display a single data item, along with its associated descriptor text, units and page
description.
On the bottom line of every data page is the Status/ID line.
On the left hand side is the page reference number e.g. P12.5, followed by the number of associated data pages
which can be traversed using the Left and right vector keys.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 20 of 395 Issue 7
On the right hand side, the character M appears when the unit is in Maintenance mode.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 21 of 395 Issue 7
6.3 Ram Battery
Each S600 flowcomputer is fitted with aback up battery. The back up battery is used to retain thecontents of the
Static RAM on the CPU board, the PC compatible BIOS CMOS memory area and the calendar clock.
The battery fitted is a Ni-MH rechargeable 3.6 V 140mAh unit. to ensure that the battery is fully functional , a
regular load test is performed.
Battery Characteristics

Hold Up Time (without re-charge) 48 Hours
Battery Life 5-7 Years
Hold Up Time (after load test failure) 2 Weeks @ 20 deg C


6.4 Signal Handling
6.4.J Analogue Signals
Analogue signals (e.g pressure, differential pressure and density pressure and temperature) are connected to the
flowcomputers in the form of 4-20mA signals. The signals are terminated by 250R precision resistors internal to
the flowcomputers and selected by internal links.
6.4.2 R1D Signals
Four wire RTD s ( e.g. stream temperature) are connected directly to the flowcomputers. The excitation current
of 1ma is sourced from the flowcomputer.

6.4.3 Density signals
The density signals are in the form of pulse outputs direct from the transmitters and are optically coupled inputs
to the flowcomputers. Pulse input modules are connected to the two condensate densitometers to enable
connection to both stream computers.

6.4.4 1urbine Meters
The turbine meters are Faure Herman type producing current modulated signals. Connection to the
flowcomputer is made using a Daniels P100 pulse conditioning module which converts the current modulated
pulses to voltage and also maintains the line integrity checking.

6.4.S Digital Inputs
Digital inputs are optically coupled to the flowcomputers. The digital inputs share a common 24vdc supply in
(groups of four) which are externally connected.

6.4.6 Valve Status
The motor operated valves are monitored for their open and closed status.
These valve status inputs are interpreted as follows:
Open Limit Switch Closed Limit Switch Status
O/C S/C Open
S/C S/C Moving
S/C O/C Closed
O/C O/C Failed
Where, O/C = Open Circuit and S/C = Short Circuit.
Valves that are detected as failed shall raise an alarm, which is displayed on the supervisory and printed in the
alarm log.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 22 of 395 Issue 7
6.4.7 Illegal flow
If the flowcomputer detecst a flowcondition ahen the input and output valves are closed and the flowcomputer is
not in Maintenance mode, then this will be deemed an illegal flow condition and the illegal flow alarm will be
raised.
6.4.8 Valve Commands
The valves shall be driven by the stream flow computers when in Remote mode. In the case of the flow
computer driving the valve, the output shall be held active for a user defined drive period. If after another user-
defined period the valve has failed to achieve the desired position an alarm shall be raised.

6.4.9 Digital Outputs
Digital and pulse outputs are provided in the form of open collector transmitter outputs. the outputs are grouped
in fours with the transmitter emitters connected to a common ground.

6.4.J0 Analogue Outputs
Four analogue outputs are provided on each flowcomputer. The outputs are internally supplied from 15 volts
with a maximum loop impedance of 650 ohms.
6.S System Communications
6.S.J Lthernet
The gas export metering system flowcomputers, the buy back flowcomputer, the back up gas flowcomputer, the
condensate export metering system flowcomputers and the prover flowcomputers are connected to the duty and
standby supervisories by a unshielded twisted pair Ethernet link. This link forms one part of the dual data
highway.

6.S.2 RS 48S Communications
The second part of the dual data highway is provided in the form of two RS 485 serial buses using Modbus
protocol which connects all computers in addition to the Ethernet link above.

6.S.3 Prover Communications
The prover computer is connected to the two condensate stream flowcomputer via a RS 485 serial link using
Modbus protocol. This link is used for proving purposes only.

6.S.4 PLC Communications
The Modicon PLC is connected to each of the supervisory P.C.s via an RS 232 serial data link. The protocol
used will be Modbus.

6.S.S Chromatograph Communications
The chromatograph is connected directly to each of the gas export metering system flowcomputers using RS
232 serial links running Modbus protocol.
A fourth serial link using Modbus protocol and an RS 485 interface is used to connect the chromatograph
controller to the supervisory computers.
Gas composition data is passed from the supervisory computer to the back up gas stream and the buy back
flowcomputer.

6.S.6 Printer Communications
The supervisory computers are connected to the report printer via an automatic printer switch. Only the duty
supervisory will access the printer. The interface used is parallel.

The alarm printer is connected to the supervisory computer via an automatic printer switch. Only the duty
supervisory will access the printer. The interface used is serial, 9600 baud, eight data bits, one stop bit no parity
check.
Each S600 flowcomputer is configured to provide a serial port connection for printing alarms and report data.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 23 of 395 Issue 7
6.S.7 DCS Communications
Two serial data links are provided to the DCS, (one from each supervisory). The interface is RS 232 and the
protocol is Modbus.
This link shall be used to supply metering data to the DCS and also accept downloading of gas composition
from lab analysis.

6.S.8 Ilowcomputer Reporting
Each of the flowcomputers is configured with a serial port for local printing. If required a local printer will need
to be connected to this port and the following reports may be generated from the computer front panel:
Daily Report
Current Report
Constants Log
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 24 of 395 Issue 7

6.6 Stream Status
The stream status is determined by the flowcomputer and may be any one of the following:
Status Description

UNDEFINED The status task is not running correctly.

MAINT The flowcomputer has been put into Maintenance Mode

DISABLED The stream disable logic has been set by the Supervisory computer

VLV-ILLEGAL One of the monitored valves is indicating an unknown/illegal position

UNHEALTHY
(CONDENSATE STREAM)
There is not a flow path through the meter run AND the measured
Gross volume flowrate is above the low flow cut-off limit (m3/h)

ON-LINE
(CONDENSATE STREAM)
There is a flowpath through the meter run AND the measured Gross
volume flowrate is above the low flow cut-off limit (m3/h)

UNHEALTHY
(GAS STREAM)
There is not a flowpath through the meter run AND the measured
Mass flowrate is above the low flow cut-off limit (t/h)
ON-LINE
(GAS STREAM)
There is a flowpath through the meter run AND the measured Mass
flowrate is above the low flow cut-off limit (t/h)
OFF-LINE There is not a flow path through the meter run AND the measured
Gross volume flowrate is below the low flow cut-off limit.

6.7 Maintenance Mode

The flowcomputer should be put into Maintenance Mode when calculation or calibration tests are to be carried
out.
Entry of Maintenance Mode is only possible if the stream status is Off-Line and one of the inlet valves is
closed..
The flowcomputer does not check the status of the outlet valves for maintenance entry / exit.
To Exit Maintenance Mode the Off-Line interlock checks must be satisfied.
Whilst in Maintenance Mode the following occurs:
1. Alarm digital outputs (except Watchdog) are forced to the no alarm position.
2. Totalisation pulse outputs are inhibited.
3. Analogue outputs are set to the low limit value.
4. Any flow registered is totalised into separate maintenance totalisers.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 25 of 395 Issue 7
6.8 Security System
6.8.J PC Operator Interface
Unauthorised changing of data is prevented using a multiple level security system. Each login level has a
separate password. Each login level can change its own password, and the passwords for all lower levels.
Permissions are:
User
Level
User name Access Level Default
Password
0 Secure Display selection and login.
1 Operator Display selection and login. Change limits, keypad values,
stream commands. Accept alarms
oper
2 Technician As Operator + change scalings tech
3 Engineer As Technician + edit databases, reports, and displays engr
8 System Alderley password level
:

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 26 of 395 Issue 7
6.9 1otals
6.9.J 1otalisation
During normal metering the Supervisory polls totals from each S600 flowcomputer. The supervisory calculates
the difference between the total received on the previous poll and the total received on current poll, and adds
that amount to its own version of the stream total.
Supervisory cumulative totals roll over from 99,999,999 to 0.
Stream and station totals are formed on a cumulative and daily basis. Daily totals for each flowcomputer are
formed independently at the flowcomputer and supervisory computers. The supervisory reports its own
versions of daily totals.
6.9.2 1otaliser Security
Totals in the flowcomputers are stored in battery supported static RAM ensuring they remain unchanged during
power failure. The supervisory totals are stored on the hard drive and remain unchanged during power failure.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 27 of 395 Issue 7
6.J0 Configuration and Constants
Each S600 flowcomputer has a set of Flash containing the core software. The core software consists of a
number of programme modules, each able to perform a particular function - for example, alarm handling. A
particular application is realised by selecting the relevant programme modules, and setting them up to suit the
users requirements.
The S600 configuration determines the selection and set-up of modules for a particular application. Each S600
stores its configuration as a set of files in an area of memory set up as a RAM disc. An internal battery supports
the RAM disc power, so that data is not lost even if the main S600 power is interrupted.
Constants are user-entered values such as transmitter ranges. They are also stored in the RAM disc.

6.JJ Alarms
Each S600 independently raises alarms for its own internal condition and inputs. The Supervisory computer
collects together all flowcomputer alarms to form a single display for the PC, and for printing. Alarms are
grouped as follows:
Group Description
System Internal failure of a computer/transmitter
Input An input is failed
Process An input or variable is outside entered limits

Alarms are automatically accepted at the flowcomputer on transfer to the supervisory.

6.JJ.J Ilowcomputer Alarm System
6.JJ.2 Introduction
The Flowcomputer operates a comprehensive alarm system, a summary of which is detailed below:

1. Visual Indication
Front Panel Display
An alarm indicator LED on the front panel is used to indicate alarm status, as detailed below:
Flashing red - unaccepted alarm is present
Constant red - alarm condition is present, however has been accepted
Constant green - no alarms present
Flashing amber - communications failure to front panel

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 28 of 395 Issue 7

2. Alarm Output
One off relay output, and two open collector digital outputs are used to indicate alarm status.
A number of alarms are assigned to each of these outputs.
If an alarm digital output is in the alarm state when another alarm assigned to that output occurs, the digital
output will drop to the non-alarm state for approximately 0.5 seconds in order to enable annunciation of the
additional alarm.
A latching method is employed which operates as defined below:

NO ALARM Alarm output remains unset
Alarm indicator shows no alarm
ALARM OCCURS Alarm output is set
Alarm indicator shows unaccepted alarm
ALARM IS STILL PRESENT AND IS ACCEPTED
Alarm output remains set
Alarm indicator shows accepted alarm
Printout of alarm ACC
ALARM CLEARS PRIOR TO ACCEPTANCE
Alarm output remains set
Alarm indicator shows unaccepted alarm

ALARM ACCEPTED FOLLOWING CLEARANCE
Alarm output is unset
Alarm indicator shows no alarm
Printout of alarm ACC
Printout of Alarm CLR
ALARM CLEARS FOLLOWING ACCEPTANCE
Alarm output is unset
Alarm indicator shows no alarm
Printout of alarm CLR
ALARM OCCURS HAVING ALREADY BEEN RAISED AND CLEARED WITHOUT ACCEPTANCE
Alarm output remains set
Alarm indicator shows unaccepted alarm

6.JJ.3 Alarm Suppression
Alarms designated as process alarms are inhibited under the following conditions:

Flowcomputer is in Maintenance mode
Flowrate is below low flow cut-off value.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 29 of 395 Issue 7
6.J2 Display Units and formats
The display of units and their formats throughout the system, Operator workstation, Reports and Flow
computers shall be as listed in the following table:

Parameter Units Normal Format
Line Temperature C 12.12
Base / Calibration Temperature C 12.12
Temperature Limits and Scaling C 12
Line Pressure barg 12.123
Base Pressure Bar 1.12345
Pressure Limits and Scaling barg 12
Differential Pressure mBar 123.123
Differential Pressure Limits and Scaling mBar 123
Differential Pressure switch points % 12
Vapour Pressure barg 123.123
Time - HH:MM:SS
Date - DD/MM/YY
Density (Condensate) kg/m
3
123.123
Density Limits (Gas & Condensate) kg/m
3
123
Base Density (Condensate) kg/Sm
3
123.123
Density (Gas) kg/m3 123.123
Base Density (Gas) kg/Sm3 1.123456
Gas Composition mol% 123.1234
Ctlm 1.1234567
Cplm 1.1234567
Ctld 1.1234567
Cpld 1.1234567
Alpha Exponent
Beta Exponent
Meter Frequency Hz 1234.1
Low Flow Cut off Hz 12
K Factor Pls/ m
3
1234.123
Meter Factor 1.123456
Prover Final K Factor Pls/ m
3
1234.1234
Volume Flow Rate m
3
/h 1234.123
Volume Total m
3
123456789.123
Volume Flow Rate Limits m
3
/h 1234
Std Volume Flow Rate Skm
3
/h 1234.123
Std Volume Total Skm
3
123456789.123
Std Volume Total bbl

123456789.123
Mass Flow Rate t

/h 1234.123
Mass Total tonnes

123456789.123
Energy Flow Rate GJ/h 1234.123
Energy Total GJ 123456789.123
Energy Total MBTU 123456789.123
Discharge Coefficient 1.1234567
Velocity of Approach 1.1234567
Expansibility 1.1234567
Isentropic Exponent 1.1234
Reynolds Number Exponent
Orifice Thermal Expansion / C Exponent
Pipe Thermal Expansion / C Exponent
Timeouts s 123
Pipe / Orifice / Prover Dimensions mm 123.123
Corrected Pipe Diameter mm 123.12345
Corrected Orifice Diameter mm 123.12345
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 30 of 395 Issue 7
Ctlp 1.1234567
Cplp 1.1234567
Ctsp 1.1234567
Cpsp 1.1234567
Modulus of Steel /bar Exponent
Thermal expansion / C Exponent
Base Prover Volume m
3
1.1234567
Corrected Prover Volume m
3
1.1234567




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 31 of 395 Issue 7
7 CONDLNSA1L S1RLAM ILOWCOMPU1LRS
The flow computers are Daniel model S600 (General arrangement appended).
7.J General Ieatures

The S600 stream computers are factory configured to provide all the measurement functions for the Helang
liquid turbine meter application.


7.J.J 1urbine Meter Pulse Counting.

Two pulse inputs are provided for liquid turbine meter applications. They will be configured to provide dual
pulse security checks to IP252, 1976 level A. This entails comparing the two pulse trains from the turbine meter
pulse amplifiers which are normally 90 electrical degrees out of phase. If the pulse trains are in-phase an alarm
will be raised and the pulses rejected. The normal ordering of the pulse trains is ABABAB and all correct AB
pairs are counted in the Good Pulse Counter (H/W). If a missing pulse is detected e.g. ABBABA this is
separately counted in the Bad Pulse Counter (H/W). If the flowrate is above the Low Flow Limit then the Bad
Pulse Counter (1) will be incremented. If the flowrate is below the Low Flow Limit the Bad Pulse Counter (1)
will not be incremented, unless configured for no low flow cut-off operation. The Bad Pulse Counter (1) will be
compared against a keypad entered Bad Pulse Threshold and if this is exceeded, an alarm will be raised and Bad
Pulse Counter(2) incremented. The increments to the Bad Pulse Counter (2) may also be configured as a pulse
output to an external counter. The Bad Pulse Counter (1) will be reset to zero under the following conditions:

Acceptance of the alarm.

After 10000 good pulses. (This minimises raising nuisance alarms due to occasional bad pulses at flow
start/stop eventually causing the threshold to be exceeded.)

The Bad Pulse Counter (2) will be held as a non-reset triplicated register.

7.J.2 Meter Iactor Linearisation
The Condensate flowcomputers will be configured to perform Meter Factor linearistaion using 10 entered
values of Meter Factors and flowrates.
This will comprise a two-stage system. The S600 will perform the linearisation and the results will be made
available at the supervisory.
The results will graphically display the curves and the operator can then decide to download the new meter
factors to the stream. The table will be downloaded to the particular flowcomputer and displayed as a graph.
The results of up to 16 single point proves (meter factor, flowrate and date) will be displayed on the same
display.
In the event of a prove result not matching the existing curve, the operator can elect to copy values from the
prove result into the table to form a new curve and download the values to the flowcomputer.
The values will be downloaded from the supervisory computer after a series of prove runs.

7.J.3 Density Handling

The density in use is from one of three sources:-
Density A measured
Density B measured
Density Fallback - an operator entered fixed value.
Each computer accepts pulse inputs from two Solartron densitometers situated on the header. A set of
calibration constants for each densitometer is entered into each flowcomputer in order that measured density
may be calculated.
Using the live temperature and pressure inputs the measured density is corrected for temperature and pressure at
the densitometer.
Live density A is normally selected for use in the calculations; if the density A fails then the live density B is
selected for use. If both density inputs are failed then the fallback density is selected for use. The two densities
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 32 of 395 Issue 7
are checked for a difference in reading and if the difference exceeds a keypad entered limit then a discrepancy
alarm is raised.
The density temperature is compared with the line temperature and if the difference exceeds a keypad entered
limit then an alarm is raised
The selected measured density is then used in conjunction with the thermal expansion coefficient, the
condensate compressibility and the liquid temperature and pressure correction factors to calculate the density at
standard conditions.
The calculated base density is now corrected for line temperature and pressure conditions to produce the density
at the meter.




7.J.4 Low Irequency Cut-off (Hz)
A low flow cut-off point is provided for entry of a frequency in Hz. When the turbine meter input frequency
exceeds this figure, dual pulse checking, flowrate and calculation will be performed - this is the normal
metering condition.
When a turbine frequency is detected below the low flow cut-off, a low flow cut-off alarm will be raised, IP
252/76 pulse checking and flowrate calculations are inhibited. Totalisation is performed at all times.

7.J.S Valve Handling
The condensate system has duplicated valves at the inlet, outlet and prover inlet positions. All valve statuses are
wired in to the flowcomputer.

7.J.6 Condensate 1otals and flowrates
Flowrates will be calculated and totals formed for the following

Flowrate Resolution Total Resolution
Mass t/h xxxxxxx.xxx t xxxxxxxx.xxx
Gross Volume m3/h xxxxxxxx.xxx m3 xxxxxxxx.xxx
Std Volume Skm3/h xxxxxxxx.xxx Skm3 xxxxxxxx.xxx

7.J.7 Average, Maximum and Minimum S Vol Ilowrates
The average standard volume flowrate for the condensate will be computed on a daily basis and printed
on the daily report. The Minimum and Maximum values of standard volume flowrate will be captured
on a daily basis and printed on the daily report.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 33 of 395 Issue 7

7.J.8 Local Printing
The following printout facilities are available:
Configuration:
Constants log report on request.
A display dump is printed on request.
A print out of all possible alarms and their configured alarm group.

Reports:
Day end report is printed automatically at day end, or on request.
Current report is printed on request.

Alarms:
Automatic alarm printouts on occurrence, acceptance and clearance of alarm states.
Automatic status printouts on occurrence of a keypad value or mode change.
All current alarms on request
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 34 of 395 Issue 7

7.2 Iunctions

The functions of the stream flowcomputers are:-

To accept a dual pulse stream representing gross volume flowrate from the turbine meter.

To detect pulse errors in accordance with IP252/76; to count these errors, to raise an alarm on reaching a
settable alarm threshold

To correct pulse errors according to IP252/76 level A.

To accept an analogue input representing line pressure and to convert the reading to engineering units for
display and calculation.

To accept a 4 wire P.R.T. input representing line temperature and to convert the reading to engineering units for
display and calculations.

To accept a 4-20mA input from the sample loop representing density temperature and to convert the reading to
engineering units for display and calculation.

To accept a 4-20mA input from the sample loop representing density pressure and to convert the reading to
engineering units for display and calculation.

To accept two frequency input signals representing density and to accept densitometer constants and hence
calculate line density and mass flowrate and totals.

To allow a densitometer to be selected for use and to provide automatic switching to the second densitometer in
the case of failure.

To provide an analogue (4-20mA) output to the flow control valve.

To provide an analogue (4-20mA) output to the sample loop flow controller.

To provide a digital output to the sample loop flow controller to represent an on-line condition.

To perform calculations as defined in the calculation section.

To display measured and calculated quantities.

To provide a means of operator data entry and inspection.

To accept digital inputs from the each of the inlet block valves and to interpret these signals to represent the
valve status as open, closed, moving or failed.

To accept digital inputs from the outlet block valves and to interpret these signals to represent the valve status
as open, closed, moving or failed.

To accept digital inputs from the prover inlet block valves and to interpret these signals to represent the valve
status as open, closed, moving or failed.

To accept a digital signals from each valve to indicate Local / Remote status.

To issue open and close commands to the inlet, outlet, and prover inlet block valves.

To accept a digital signal representing strainer blocked and to raise an alarm when this signal is open.
.
To communicate with the supervisory computers via a UTP ethernet link to allow bi-directional transfer of
measured and calculated data, alarms, status and configuration.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 35 of 395 Issue 7

To communicate with each supervisory computer via two RS485 serial links to allow bi-directional transfer of
measured and calculated data, alarms, status and configuration.

To provide a digital output representing computer fail.

To provide a pulse output representing good pulses to the prover computer

To store for one month, daily totals, hourly totals and average values of K factor,meter factor, pressure,
temperature and density.

To provide an RS 232 serial port for printing reports.

To calculate flow weighted average values for Presssure, Temperature, Meter Density and Base Density against
volume flow on a aperiod and daily basis.

To perform meter factor linearisation based on 10 enetered values of meter factor and flowrates.

To accept meter factor curve downloaded from the supervisory.

To calculate the average, minimum and maximum values for standard volume flowrate on a daily basis.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 36 of 395 Issue 7

7.3 Input / Output Definition
The following inputs and outputs will be selected for each stream flowcomputer for this project during
configuration.

S600 Conn DPin I/O Description Stm 1 Stm 2
A 1 DAC 1 +ve Flow Control Valve FV 3211 FV 3221
A 14 DAC 1 ve Flow Control Valve FV 3211 FV 3221
A 15 DAC 2 +ve Sample Loop Flow Cont
A 3 DAC 2 ve Sample Loop Flow Cont
A 8 ADC 1 +ve Mtr Pressure PT 3211 PT 3221
A 11 ADC 6 +ve Density Pressure PT 3201 PT 3201
A 24 ADC 7 +ve Density Temperature TE 3201 TE 3201
A 22 ADC 4 +ve Prover V/V1 L/R * MOV 3213 MOV 3223
A 10 ADC 5 +ve Prover V/V 2 L/R * MOV 3214 MOV 3224
A 9 ADC 3 +ve Strainer Blocked *
PDISH
3212
PDISH
3222
B 4 PRT 1 I + Mtr Temp TE 3211 TE 3221
B 1 PRT 1 V + Mtr Temp TE 3211 TE 3221
B 21 PRT 1 V - Mtr Temp TE 3211 TE 3221
B 24 PRT 1 I - Mtr Temp TE 3211 TE 3221
B 9 Density 1 +ve Density 1 QT 3201 QT 3201
B 27 Density 1 -ve Density 1 QT 3201 QT 3201
B 10 Density 2 +ve Density 2 QT 3202 QT 3202
B 28 Density 2 -ve Density 2 QT 3202 QT 3202
B 13 Dig In 1 ve Inlet V/V 1 Open MOV 3211 MOV 3221
B 14 Dig In 2 ve Inlet V/V 1 Closed MOV 3211 MOV 3221
B 15 Dig In 3 ve Inlet V/V 1 L/R MOV 3211 MOV 3221
B 16 Dig In 4 ve Inlet V/V 2 Open MOV 3212 MOV 3222
B 17 Dig In 1-4 +ve Common
B 18 Dig 5 ve Inlet V/V 2 Closed MOV 3212 MOV 3222
B 19 Dig In 6 ve Inlet V/V 2 L/R MOV 3212 MOV 3222
C 19 Dig In 7 ve Outlet V/V 1 Open MOV 3215 MOV 3225
C 18 Dig 8 ve Outlet V/V 1 Closed MOV 3215 MOV 3225
C 17 Dig In 5-8 +ve Common
C 16 Dig In 9 ve Outlet V/V 1 L/R MOV 3215 MOV 3225
C 15 Dig In 10 ve Outlet V/V 2 Open MOV 3216 MOV 3226
C 14 Dig In 11 ve Outlet V/V 2 Closed MOV 3216 MOV 3226
C 13 Dig In12 ve Outlet V/V 2 L/R MOV 3216 MOV 3226
C 12 DigIn 9-12 +ve Common
C 11 Dig In 13 ve Prover V/V 1 Open MOV 3213 MOV 3223
C 10 Dig In 14 ve Prover V/V 1 Closed MOV 3213 MOV 3223
C 9 Dig In 15 ve Prover V/V 2 Open MOV 3214 MOV 3224
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 37 of 395 Issue 7
C 8 Dig In16 ve Prover V/V 2 Closed MOV 3214 MOV 3224
C 7 DigIn 13-16 +ve Common
C 36 Dig Out 1+ve In V/V 1 Open Com MOV 3211 MOV 3221
C 37 Dig Out 2 +ve In V/V 1 Close Com MOV 3211 MOV 3221
C 37 Dig Out 3+ve In V/V 2 Open Com MOV 3212 MOV 3222
C 36 Dig Out 4 +ve In V/V 2 Close Com MOV 3212 MOV 3222
C 35 Dig Out 1-4 -ve Command Common
C 34 Dig Out 5+ve Out V/V 1 Open Com MOV 3215 MOV 3225
C 33 Dig Out 6+ve Out V/V 1 Close Com MOV 3215 MOV 3225
C 32 Dig Out 7+ve Out V/V 2 Open Com MOV 3216 MOV 3226
C 31 Dig Out 8+ve Out V/V 2 Close Com MOV 3216 MOV 3226
C 30 Dig Out 5-8 -ve Command Common
C 29 Dig Out 9+ve Prv V/V 1 Open Com MOV 3213 MOV 3223
C 28 Dig Out 10+ve Prv V/V 1 Close Com MOV 3213 MOV 3223
C 27 Dig Out 11+ve Prv V/V 2 Open Com MOV 3214 MOV 3224
C 26 Dig Out 12+ve Prv V/V 2 Close Com MOV 3214 MOV 3224
C 25 Dig Out 9-12 -ve Command Common
C 4 Pulse 1 in + Turbine A + FT 3211A FT 3221A
C 23 Pulse 1 in - Turbine A - FT 3211A FT 3221A
C 3 Pulse 2 in + Turbine B + FT 3211B FT 3221B
C 22 Pulse 2 in - Turbine B - FT 3211B FT 3221B
C 24 Pulse Out + Prover Pulse Bus
C 5 Pulse Out - Prover Pulse Bus
RJ 45
Network
1 Signal ground Supervisory Computer

2 DTR Supervisory Computer

3 RTS Supervisory Computer

4 Tx Data Supervisory Computer

5 Rx Data Supervisory Computer

6 CTS Supervisory Computer

7 DSR Supervisory Computer

8 DCD Supervisory Computer

RJ 45 Port 3 1 Signal ground Local Printer

4 Tx Data Local Printer

5 Rx Data Local Printer

TB2 Port 5 1 Rx - Prover Slave

2 Rx + Prover Slave

3 Tx - Prover Slave

4 Tx + Prover Slave

TB2 port 6 5 Rx - Supervisory ComputerA

6 Rx + Supervisory ComputerA

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 38 of 395 Issue 7
7 Tx - Supervisory ComputerA

8 Tx + Supervisory ComputerA

TB2 port 7 9 Rx - Supervisory ComputerB

10 Rx + Supervisory ComputerB

11 Tx - Supervisory ComputerB

12 Tx + Supervisory ComputerB

TB 1 1 24 Volt DC +ve 24 V DC Power

TB 1 2 24 Volt DC -ve 0 V DC Power

TB 1 6 N /C Contact Computer Fail Relay

TB 1 7
Common
Contact
Computer Fail Relay

TB 1 8 N/O Contact Computer Fail Relay



Note:
ADCs 3, 4 and 5 are used to monitor digital inputs. This is achieved by connecting the digital input through a
fixed resistor in the panel, if the current detected by the ADC is above 4 mA then the digital input is closed.
Conversely when the current detected by the ADC is less than 3.5 mA the input is open circuit.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 39 of 395 Issue 7

7.4 Calculations

7.4.J Abbreviations Used In Calculations

Symbol Description
AT Area of the rotor (m)
CPLd correction factor for the effect of pressure on the liquid
CPLm correction factor for the effect of pressure on the liquid
CPSm Correction factor for the effects of pressure on the meter housing
CTLd Correction factor for the effects of temperature at densitometer on the liquid
CTLm Correction factor for the effects of temperature at the meter on the liquid
CTSm Correction factor for the effects of temperature on the meter housing
D15.0 Density at standard conditions (15C, zero barg)
D
I
uncorrected measured density
D
T
measured density corrected for temperature
D
TP
measured density corrected for temperature and pressure
e Poisson ratio
E Youngs modulus of elasticity for the material of the spool body
f turbine meter frequency (Hz)
FWV Flow weighted value
K K.Factor (pls/m
3
)
K
0
, - K
21B
are densitometer calibration constants
K0, K1 are liquid specific constants
K2 liquid specific constant (/C)
LinMeter Linear temperature expansion coefficient for the material of the meter housing
(/C)
LinRotor Linear temperature expansion coefficient for the material of the meter housing
(/C)
MF Meter factor
P
CAL
Meter calibration pressure (barG)
P
cal
densitometer calibration pressure in barG
Pd pressure of the liquid at the densitometer (barG)
Pe liquid equilibrium vapour pressure (barG)
Pm pressure of the liquid at the meter (barG)
PV Process variable
qm mass flowrate (t/h)
Q
m
Mass total t
Q
s
Standard volume total Skm3
qv actual volume flowrate (m
3
/h)
qvstd standard volume flowrate (Skm
3
/h)
R Radius of meter housing (m)
RHOden Raw density measured at densitometer
RHOm meter density (kg/m3)
RHO
std
density corrected to standard conditions (kg/m
3
)
Strain Pressure expansion coefficient for the material of the spool body.(/barG)
t Thickness of meter housing (m)
Tau period of the signal from the densitometer (micro-seconds)
T
CAL
Meter calibration temperature (C)
T
cal
densitometer calibration temperature C
Td temperature of the liquid at the densitometer (C)
T
m
Temperature of the liquid at the meter (C)
T
std
Standard temperature (15C)
VCFm meter volume correction factor
pls number of pulses from the turbine meter in the sample period
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 40 of 395 Issue 7
Qm mass total increment
Qv gross observed volume increment (m
3
)
Qvstd standard volume increment (m
3
)

Coefficient of thermal expansion of the liquid (/C)
d compressibility of the liquid at the densitometer (/bar)
m compressibility of the liquid at the meter (/bar)
X Turbine meter flowrate
X
p
Flowrate co-ordinate from linearisation table
Y
p
Meter factor co-ordinate from linearisation table


7.4.2 Base Conditions
The following base conditions are used in the calculations:

Constant Value Units
Base Temperature 15 C
Base Pressure 0 bar g
Calibration temperature 20 C

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 41 of 395 Issue 7

7.4.3 Conversion Iactors
Detailed below are the default conversion factors:
barG to barA
X barA = Y barG + 1.01325

bar to Pa
X Pa = Y bar x 100000

degC to Kelvin
X K = Y degC + 273.15



7.4.4 1otalisation Calculations
Gross Observed Volume Total Increment (m
3
)
CPSm CTSm MF
K
pls
Qv

=


CTSm and CPSm have keypad values of 1.0 and hence are not used when the mode of these items = Keypad

Standard Volume Total Increment (m
3
)

VCFm Qv Qvstd =


Mass Total Increment (t)

001 . 0 = m RHO Qv Qm


7.4.S Ilowrate Calculations
Gross Volume Flowrate (m
3
/h)
CPSm CTSm MF
K
f
qv = 3600

CTSm and CPSm have keypad values of 1.0 and hence are not used when the mode of these items = Keypad
Standard Volume Flowrate (Skm
3
/h)

VCFm qv qvstd =




Mass Flowrate (t/h)

001 . 0 = RHOm qv qm


7.4.6 Measured Density (kg/m
3
)

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 42 of 395 Issue 7
D
I
= K
0
+ K
1
Tau + K
2
Tau
2
D
T
= D
I
( 1+ K
18
( T
d
-T
cal
)) + K
19
( T
d
-T
cal
)
K20 = K20A + K20B (P
d
- P
cal
)
K21 = K21A + K21B (P
d
- P
cal
)
D
TP
= D
T
[1 + K20 (P
d
- P
cal
) ] + K21(P
d
- P
cal
)


7.4.7 Correction Iactor for the Lffect of 1emperature on the Liquid
a) At the Meter:
CTLm = EXP [- (T
m
- T
std
) (1.0 + 0.8 (T - T
std
))]
b) At the Densitometer:
CTLd = EXP [- (T
d
- T
std
) (1.0 + 0.8 (T
d
- T
std
))]



Coefficient of Thermal Expansion of the Liquid (/degC)
The coefficient of thermal expansion for the liquid is calculated from the following equation
( )
2
1 0
2
K
RHO
K
RHO
K
std std
+ + =




7.4.8 Correction Iactor for the Lffect of Pressure on the Liquid
a) At the Meter:
CPLm =
1
1 m(Pm Pe)





b) At the Densitometer:
) ( 1
1
Pe Pd d
CPLd

=




Compressibility (/bar)
This is calculated:
a) at thedensitometer
( ) ( )
( ) ( )
4 -
2
3 -
2
3 -
4 -
2
3 -
2
3 -
10
10
T 0042092 . 0
10
0.87096
+ T x 0.00021592 + 1.62080 - =
: Meter b)At the
10
10
T 0042092 . 0
10
0.87096
+ T x 0.00021592 + 1.62080 - =
x
x
x
x
EXP
x
x
x
x
EXP
std
m
std
m m
std
d
std
d
d
|
|
.
|

\
|
+
|
|
.
|

\
|
+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 43 of 395 Issue 7
7.4.9 C1Sm and CPSm Volume Corrections for Meter Housing Lxpansion
The spool itself will expand and contract due to the effects of both temperature and pressure, both internally and
externally, on the spool material. This correction is dependent upon the calibration conditions under which the
meter was calibrated and upon the composition of the material used to fabricate the spool. The equations used
for correction are described below.

( ) { } [ ] ( ) { } [ ]
CAL L CAL L
T T LinRotor T T LinMeter CTSm + + = 1 1
2



( ) { }
CAL m
P P Strain CPSm + = . 1


( )
[ ]
|
|
.
|

\
|

=
t R AT E
R e
Strain
2 . / 1 .
. 2 . 2
2








Note:

If this correction is not required then the mode of CTSm/CPSm should be set to keypad with a keypad value of
1.0. If the correction is required then the mode of CTSm and CPSm should be set to Calculated, and the
calibration Temperature and Pressure will be updated after each prove, i.e. with the value of proved meter
temperature and proved meter pressure.


Density Correction
Standard Density (kg/m
3
)
CPLd CTLd
RHO
RHO
den
std

=

RHO
std
density corrected to standard conditions (kg/m
3
)
CTLd correction factor for the effect of temperature on the liquid at the densitometer;
CPLd correction factor for the effect of pressure on the liquid at the densitometer;
RHO
den
measured density, at the densitometer (kg/m
3
)

Meter Density (kg/m
3
)

RHO
m
= RHO
std
x VCF
m

RHO
m
Meter density (kg/m
3
).
RHO
std
density corrected to standard conditions (kg/Sm
3
)
VCF
m
Volume correction factor for the fluid at the meter
Volume Correction Factor

VCFm = CTLm x CPLm

CTLm correction factor for the effect of temperature on the liquid at the meter
CPLm correction factor for the effect of pressure on the liquid at the meter





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 44 of 395 Issue 7

7.4.J0 Ilow Weighted Averages
Flow weighted averages are calculated on a period and daily basis for:
Stream Temperature
Stream Pressure
Meter Density
Base Density

The flow weighted average is calculated by



( )


=
v
v
Q
Q PV
FWV



7.4.JJ Meter Iactor Linearisation



( )
( )( )
( )
p
p p
p p p
calc
Y lower +
X lower - X higher
Y lower - Y higher X lower - X
= MF
(
(


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 45 of 395 Issue 7

7.S Displays

The following is representative of the data that will be available as a minimum on the front panel of the flow
computer.
The actual displays will be included when configuration of the computers is completed

Display Item Parameters Security Units
Mass Total Cumulative, daily 0 tonne
Mass Flowrate 0 kg/hour
Std Vol Total Cumulative, daily 0 Sm
3

Std Vol Flowrate 0 Sm
3
/hour
Gross Volume Total Cumulative, daily 0 m3/h
Gross Volume Flowrate 0 m3/h
Stream Pressure Measured, keypad 0,1 Barg
Stream Temperature Measured, keypad 0,1
o
C
K-Factors 1-8 Keypad 2 pls/m3
Flowrates 1-8 Keypad 2 m3/h
K Factor in use Calculated 0 pls/m3
API constants K0,K1 2

Meter Beta Calculated 0 /bar
Densitometer Beta Calculated 0 /bar
Alpha at base conditions Calculated 0
Cpl at meter Calculated 0
Cpl at Densitometer Calculated 0
Ctl at meter Calculated 0
Ctl at Densitometer Calculated 0
Line Density Calculated, keypad 0 kg/m3
Standard Density Calculated, keypad 0,1 kg/m3
Inlet Valves Open, closed, moving, failed 0
Outlet Valves Open, closed, moving, failed 0
Prover Valves Open, closed, moving, failed 0
Outlet Valves Open, closed, moving, failed 0
Time hh:mm 2
Date dd/mm/yyyy 2
Maint Mode Entry/Exit 2
Security various
Diagnostics various
Software Version various



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 46 of 395 Issue 7

7.6 Alarms
The following table lists the alarms raised on the Condensate stream computers.

S600 SYS HOST COLD ST Grp 1
S600 SYS HOST WARM ST Grp 1
S600 SYS HOST BATT FAIL Grp 1
S600 SYS HOST RAM FAIL Grp 1
S600 SYS HOST ROM FAIL Grp 1
S600 SYS HOST RESET Grp 1
S600 SYS HOST TOT RES Grp 1
S600 SYS HOST TOT PART Grp 1
S600 SYS HOST TOT CORR Grp 1
S600 SYS HOST CONF CSUM Grp 1
S600 SYS HOST TOT ROLL OVR Grp 1
S600 SYS HOST TOT ROLL UDR Grp 1
S600 SYS HOST PRINTING ERR Grp 1
S600 PROVER SLAVE LINK MONITOR Grp 3
S600 SLAVE LINK MONITOR Grp 4
S600 PRINTER MONITOR Grp 4
S600 BKGND TASK MONITOR Grp 4
S600 BKGND TASK TSK ERR Grp 4
S600 DIO SCAN TASK MONITOR Grp 4
S600 DIO SCAN TASK TSK ERR Grp 4
S600 DISPLAY TASK MONITOR Grp 4
S600 DISPLAY TASK TSK ERR Grp 4
S600 IO COMMS TASK MONITOR Grp 4
S600 IO COMMS TASK FAIL IO1 Grp 4
S600 IO COMMS TASK FAIL IO2 Grp 4
S600 IO COMMS TASK FAIL IO3 Grp 4
S600 IO COMMS TASK FAIL IO4 Grp 4
S600 IO COMMS TASK FAIL IO5 Grp 4
S600 IO COMMS TASK FAIL IO6 Grp 4
S600 IO COMMS TASK FAIL IO7 Grp 4
S600 IO COMMS TASK TSK ERR Grp 4
S600 IO SCAN TASK MONITOR Grp 4
S600 IO SCAN TASK TSK ERR Grp 4
S600 REPORTS TASK MONITOR Grp 4
S600 REPORTS TASK TSK ERR Grp 4
S600 TOTALS TASK MONITOR Grp 4
S600 TOTALS TASK TSK ERR Grp 4
S600 LIQ KF/MF TASK MONITOR Grp 4
S600 LIQ KF/MF TASK TSK ERR Grp 4
S600 LIQ M CORR TASK MONITOR Grp 4
S600 LIQ M CORR TASK TSK ERR Grp 4
S600 LIQ LIQ CON TASK MONITOR Grp 4
S600 LIQ LIQ CON TASK TSK ERR Grp 4
S600 LIQ TURB TASK MONITOR Grp 4
S600 LIQ TURB TASK TSK ERR Grp 4
S600 LIQ VOL CORR TASK MONITOR Grp 4
S600 LIQ VOL CORR TASK TSK ERR Grp 4
S600 PRV SEQ TASK MONITOR Grp 4
S600 PRV SEQ TASK TSK ERR Grp 4
S600 PRV BIDI TASK MONITOR Grp 4
S600 PRV BIDI TASK TSK ERR Grp 4
S600 DENSITY TASK MONITOR Grp 4
S600 DENSITY TASK TSK ERR Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 47 of 395 Issue 7
S600 STR STATUS TASK MONITOR Grp 4
S600 STR STATUS TASK TSK ERR Grp 4
S600 FWA CALC TASK MONITOR Grp 4
S600 FWA CALC TASK TSK ERR Grp 4
S600 BVM TASK MONITOR Grp 4
S600 BVM TASK TSK ERR Grp 4
S600 STN AVE TASK MONITOR Grp 4
S600 STN AVE TASK TSK ERR Grp 4
S600 DISCREP TASK MONITOR Grp 4
S600 DISCREP TASK TSK ERR Grp 4
S600 CALC TASK MONITOR Grp 4
S600 CALC TASK TSK ERR Grp 4
S600 PID CTL TASK MONITOR Grp 4
S600 PID CTL TASK TSK ERR Grp 4
S600 ALM SUPPRESS TASK MONITOR Grp 4
S600 ALM SUPPRESS TASK TSK ERR Grp 4
S600 BATCH/FSW TASK MONITOR Grp 4
S600 BATCH/FSW TASK TSK ERR Grp 4
S600 LOGICALC TASK MONITOR Grp 4
S600 LOGICALC TASK TSK ERR Grp 4
S600 LIQ COR IO TASK MONITOR Grp 4
S600 LIQ COR IO TASK TSK ERR Grp 4
S600 LIQ COR IF TASK MONITOR Grp 4
S600 LIQ COR IF TASK TSK ERR Grp 4
S600 LIQ COR FLOW TASK MONITOR Grp 4
S600 LIQ COR FLOW TASK TSK ERR Grp 4
S600 PRV CPRV TASK MONITOR Grp 4
S600 PRV CPRV TASK TSK ERR Grp 4
S600 FAULT TASK MONITOR Grp 4
S600 FAULT TASK TSK ERR Grp 4
S600 FLOWTIME TASK MONITOR Grp 4
S600 FLOWTIME TASK TSK ERR Grp 4
S600 SGERG TASK MONITOR Grp 4
S600 SGERG TASK TSK ERR Grp 4
S600 PRV MMPRV TASK MONITOR Grp 4
S600 PRV MMPRV TASK TSK ERR Grp 4
S600 ADC 01 MTR PRS L Grp 2
S600 ADC 01 MTR PRS H Grp 2
S600 ADC 01 MTR PRS DEV ERR Grp 3
S600 ADC 06 DNS PRS L Grp 2
S600 ADC 06 DNS PRS H Grp 2
S600 ADC 06 DNS PRS DEV ERR Grp 3
S600 ADC 07 DNS TMP L Grp 2
S600 ADC 07 DNS TMP H Grp 2
S600 ADC 07 DNS TMP DEV ERR Grp 3
S600 DAC 02 SAMP LOOP DEV ERR Grp 4
S600 FREQ 01 DNS A DEV ERR Grp 2
S600 FREQ 02 DNS B DEV ERR Grp 2
S600 PRT 01 MTR TMP L Grp 2
S600 PRT 01 MTR TMP H Grp 2
S600 PRT 01 MTR TMP DEV ERR Grp 3
S600 PIP 01 TURBINE BAD PULSE Grp 2
S600 PIP 01 TURBINE LINE FAIL Grp 2
S600 POP 01 OVERFLOW Grp 4
S600 POP 01 DEV ERR Grp 4
S600 POP 02 OVERFLOW Grp 4
S600 POP 02 DEV ERR Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 48 of 395 Issue 7
S600 POP 03 OVERFLOW Grp 4
S600 POP 03 DEV ERR Grp 4
S600 POP 04 OVERFLOW Grp 4
S600 POP 04 DEV ERR Grp 4
S600 POP 05 OVERFLOW Grp 4
S600 POP 05 DEV ERR Grp 4
S600 STATUS RAM FAIL Grp 4
S600 STATUS ROM FAIL Grp 4
S600 STATUS PIC FAIL Grp 4
S600 STATUS TPU FAIL Grp 4
S600 STATUS EEPROM FAIL Grp 4
S600 STATUS TASK ERR Grp 4
S600 STATUS CONF ERR Grp 4
S600 STATUS TASK FAIL Grp 4
S600 STATUS WARM ST Grp 4
S600 STATUS DEV ERR Grp 4
S600 STR01 IP2 CALC CONF ERR Grp 4
S600 STR01 IP2 CALC I/P ERR Grp 4
S600 STR01 IP2 CALC O/P ERR Grp 4
S600 STR01 IP2 CALC CALC FAIL Grp 4
S600 STR01 IP2 CALC NO PERMIT Grp 4
S600 STR01 STATUS CALC CONF ERR Grp 4
S600 STR01 STATUS CALC I/P ERR Grp 4
S600 STR01 STATUS CALC O/P ERR Grp 4
S600 STR01 STATUS CALC CALC FAIL Grp 4
S600 STR01 STATUS CALC NO PERMIT Grp 4
S600 STR01 PLS COND CALC CONF ERR Grp 4
S600 STR01 PLS COND CALC I/P ERR Grp 4
S600 STR01 PLS COND CALC O/P ERR Grp 4
S600 STR01 PLS COND CALC CALC FAIL Grp 4
S600 STR01 PLS COND CALC NO PERMIT Grp 4
S600 STR01 TURB INC CALC CONF ERR Grp 4
S600 STR01 TURB INC CALC I/P ERR Grp 4
S600 STR01 TURB INC CALC O/P ERR Grp 4
S600 STR01 TURB INC CALC CALC FAIL Grp 4
S600 STR01 TURB INC CALC NO PERMIT Grp 4
S600 STR01 MAINT CALC CONF ERR Grp 4
S600 STR01 MAINT CALC I/P ERR Grp 4
S600 STR01 MAINT CALC O/P ERR Grp 4
S600 STR01 MAINT CALC CALC FAIL Grp 4
S600 STR01 MAINT CALC NO PERMIT Grp 4
S600 STR01 LFC CALC CONF ERR Grp 4
S600 STR01 LFC CALC I/P ERR Grp 4
S600 STR01 LFC CALC O/P ERR Grp 4
S600 STR01 LFC CALC CALC FAIL Grp 4
S600 STR01 LFC CALC NO PERMIT Grp 4
S600 STR01 PRV VLV 1 CALC CONF ERR Grp 4
S600 STR01 PRV VLV 1 CALC I/P ERR Grp 4
S600 STR01 PRV VLV 1 CALC O/P ERR Grp 4
S600 STR01 PRV VLV 1 CALC CALC FAIL Grp 4
S600 STR01 PRV VLV 1 CALC NO PERMIT Grp 4
S600 STR01 O/L VLV 1 CALC CONF ERR Grp 4
S600 STR01 O/L VLV 1 CALC I/P ERR Grp 4
S600 STR01 O/L VLV 1 CALC O/P ERR Grp 4
S600 STR01 O/L VLV 1 CALC CALC FAIL Grp 4
S600 STR01 O/L VLV 1 CALC NO PERMIT Grp 4
S600 STR01 I/L VLV 1 CALC CONF ERR Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 49 of 395 Issue 7
S600 STR01 I/L VLV 1 CALC I/P ERR Grp 4
S600 STR01 I/L VLV 1 CALC O/P ERR Grp 4
S600 STR01 I/L VLV 1 CALC CALC FAIL Grp 4
S600 STR01 I/L VLV 1 CALC NO PERMIT Grp 4
S600 STR01 DENS.D CALC CONF ERR Grp 4
S600 STR01 DENS.D CALC I/P ERR Grp 4
S600 STR01 DENS.D CALC O/P ERR Grp 4
S600 STR01 DENS.D CALC CALC FAIL Grp 4
S600 STR01 DENS.D CALC NO PERMIT Grp 4
S600 STR01 PROVE.D CALC CONF ERR Grp 4
S600 STR01 PROVE.D CALC I/P ERR Grp 4
S600 STR01 PROVE.D CALC O/P ERR Grp 4
S600 STR01 PROVE.D CALC CALC FAIL Grp 4
S600 STR01 PROVE.D CALC NO PERMIT Grp 4
S600 STR01 MTR CORR
CALC
CONF ERR Grp 4
S600 STR01 MTR CORR
CALC
I/P ERR Grp 4
S600 STR01 MTR CORR
CALC
O/P ERR Grp 4
S600 STR01 MTR CORR
CALC
CALC FAIL Grp 4
S600 STR01 MTR CORR
CALC
NO PERMIT Grp 4
S600 STR01 PRESS.D CALC CONF ERR Grp 4
S600 STR01 PRESS.D CALC I/P ERR Grp 4
S600 STR01 PRESS.D CALC O/P ERR Grp 4
S600 STR01 PRESS.D CALC CALC FAIL Grp 4
S600 STR01 PRESS.D CALC NO PERMIT Grp 4
S600 STR01 TEMP.D CALC CONF ERR Grp 4
S600 STR01 TEMP.D CALC I/P ERR Grp 4
S600 STR01 TEMP.D CALC O/P ERR Grp 4
S600 STR01 TEMP.D CALC CALC FAIL Grp 4
S600 STR01 TEMP.D CALC NO PERMIT Grp 4
S600 STR01 TFWA CALC CONF ERR Grp 4
S600 STR01 TFWA CALC I/P ERR Grp 4
S600 STR01 TFWA CALC O/P ERR Grp 4
S600 STR01 TFWA CALC CALC FAIL Grp 4
S600 STR01 TFWA CALC NO PERMIT Grp 4
S600 STR01 DENSITY CALC CONF ERR Grp 4
S600 STR01 DENSITY CALC I/P ERR Grp 4
S600 STR01 DENSITY CALC O/P ERR Grp 4
S600 STR01 DENSITY CALC CALC FAIL Grp 4
S600 STR01 DENSITY CALC NO PERMIT Grp 4
S600 STR01 UVOL FR L [SUPP]Grp 2
S600 STR01 UVOL FR H [SUPP]Grp 2
S600 STR01 STD DENSITY L [SUPP]Grp 2
S600 STR01 STD DENSITY H [SUPP]Grp 2
S600 STR01 MTR DENSITY L [SUPP]Grp 2
S600 STR01 MTR DENSITY H [SUPP]Grp 2
S600 STR01 OBS DENSITY DSCRP [SUPP]Grp 2
S600 STR01 OBS DENSITY FAIL A [SUPP]Grp 3
S600 STR01 OBS DENSITY FAIL B [SUPP]Grp 3
S600 STR01 M FACTOR L Grp 2
S600 STR01 M FACTOR H Grp 2
S600 STR01 FILTER BLOCKED Grp 2
S600 STR01 I-VLV 1 ILLEGAL Grp 2
S600 STR01 I-VLV 1 MOVE FAIL Grp 2
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 50 of 395 Issue 7
S600 STR01 I-VLV 1 MOVE UNCM Grp 2
S600 STR01 O-VLV 1 ILLEGAL Grp 2
S600 STR01 O-VLV 1 MOVE FAIL Grp 2
S600 STR01 O-VLV 1 MOVE UNCM Grp 2
S600 STR01 P-VLV 1 ILLEGAL Grp 2
S600 STR01 P-VLV 1 MOVE FAIL Grp 2
S600 STR01 P-VLV 1 MOVE UNCM Grp 2
S600 STR01 LOW FLOW
CUTOFF
Grp 2
S600 STR01 ILLEGAL FLOW Grp 2
S600 STR01 I-VLV 2 ILLEGAL Grp 2
S600 STR01 I-VLV 2 MOVE FAIL Grp 2
S600 STR01 I-VLV 2 MOVE UNCM Grp 2
S600 STR01 O-VLV 2 ILLEGAL Grp 2
S600 STR01 O-VLV 2 MOVE FAIL Grp 2
S600 STR01 O-VLV 2 MOVE UNCM Grp 2
S600 STR01 P-VLV 2 ILLEGAL Grp 2
S600 STR01 P-VLV 2 MOVE FAIL Grp 2
S600 STR01 P-VLV 2 MOVE UNCM Grp 2
S600 STR01 TEMP DISCREP Grp 2



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 51 of 395 Issue 7
8 PROVLR COMPU1LR
The prover computer is a Daniel model S600
Automatic proving is carried out in three stages;
The first is to align the valves so the flow passes through the prover and ensure that the required
flowrate has been achieved. (Citect scope)
Second, the local prover sequence is activated to measure the K factor. This can be repeated any
number of times if so desired. (Prover computer scope)
Finally the valves are returned to their original state. (Citect scope)
On completion of a prove, a final prove report is automatically produced and the meter factor is automatically
downloaded to the proved stream. The operator has then to accept / reject the Meter factor if required and an
event is printed recording the action.
8.J General Ieatures
The S600 prover computer will be configured to provide all the required functions for a bi-directional prover
application.

8.2 Proving
The prover takes the form of a bi-directional prover loop fitted with four sphere switches. All four switches are
connected to the S600 prover. Four base volumes are entered which are related to the sphere switches as
follows:

Base Volume
Sphere Switch
(SS)
Hardware Connections
1 1 & 3
SS 1 = Switch Input 1 (A17)
SS 3 = Switch Input 2 (A5)
2 2 & 4
SS 2 = Switch Input 3 (A18)
SS 4 = Switch Input 4 (A6)
3 1 & 4
SS 1 = Switch Input 1 (A17)
SS 4 = Switch Input 4 (A6)
4 2 & 3
SS 2 = Switch Input 3 (A18)
SS 3 = Switch Input 2 (A5)

The prover base volumes entered are the round trip volumes from the prover calibration certificate.
The prover base volume to be used is selected from the front panel of the prover computer or from the
supervisory display.
8.2.J Prover Pulses
The prover computer provides an input to accept pulses from the stream that is being proved. All streams are
connected to the prover pulse bus but only the proving stream ouputs pulses. Only pulses that are considered
good are output to the pulse bus. The output from the stream computer is in the form of an open collector
transistor output that is connected to an optically isolated input at the prover computer.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 52 of 395 Issue 7

8.2.2 Double Chronometry
The prover does not receive sufficient pulses (10,000) during the prove run to meet the API standard. This is
corrected by calculating the exact fraction of a pulse at the end and start of each pass at which the sphere detect
was triggered. The pulse count is then corrected by the addition of these fractions of a pulse.

The double chronometry method employs three counters.

1) The first counter collects the raw meter pulses N1 accumulated between the detector switches.
2) A second counter measures the number of high frequency clock pulses T2 perceived between the detector
switches.
3) A third counter collects the number of high frequency clock pulses T1 perceived between those meter pulses
which immediately follow the actions of the detector switches.
4) The computer calculates the interpolated pulse count N from the measurements of N1, T1 and T2.

2
1
T
T
N1 N' nt' edPulseCou Interpolat =


The proving sequence is automatic once initiated by the operator and requires a minimum of operator input. The
prove sequence will attempt to perform a number (nominally 5 operator changeable) of prover runs within all
preset limits out of a maximum of up to ten runs (operator changeable). At the end of each run a report will be
compiled and printed which gives the results of the trial run. At the end of a set of good runs the trial data will
be averaged to compile the Final proof report which will be printed. The operator will be required to accept or
reject the final K-factor.
Certain parameters need to be operator entered to control the Prover operations as listed below:-

Pipe Diameter-mm
Prover Wall Thickness-mm
Modulus of Elasticity
Expansion factor of prover steel
Number of good runs required-n
Maximum number of runs allowed-n
K-factor variation allowed-%
Stability sample time-secs
Stability timeout-secs
End of run timer-secs
Stream/Prover temperature difference allowed-deg C
Stream/Prover pressure difference allowed-bar
Prover inlet/outlet temperature difference allowed-deg C
Prover inlet/outlet pressure difference allowed bar
Pulse count high limit-n
Pulse count low limit-n
K factor high limit
K factor low limit
Meter factor high limit
Meter factor low limit
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 53 of 395 Issue 7

8.2.3 Local Printing
The following printout facilities are available:
Configuration:
Constants log report on request.
A display dump is printed on request.
A print out of all possible alarms and their configured alarm group.

Reports:
Final Proof report.

Alarms:
Automatic alarm printouts on occurrence, acceptance and clearance of alarm states.
Automatic status printouts on occurrence of a keypad value or mode change.
All current alarms on request.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 54 of 395 Issue 7

8.3 Proving Sequences

An automatic proving sequence may be requested from the PC control screen or initiated from the prover
computer front panel.



8.3.J Sequence Iunction 0: - Idle
Await sequence command to start the sequence, then proceed to the next stage .

8.3.2 Sequence Iunction J: - validate
Verify:
a) the proving stream number is valid
b) the proving stream is flowing
c) telemetry to the proving stream is OK
d) the prove permit state (i.e. keyswitch) is on
If conditions allow a prove to take place then
a) copy the proving stream meter variables into the proving set.
b) initialise proof run data (via initialise command to run control task)
c) determine required proof flowrate from current rate (snapshot) or preset flowrate.
d) save all the FCV settings.
e) proceed to next stage

8.3.3 Sequence Iunction 2: turn proving stream pulses on
Command all on line streams to turn pulses off.
Command proving stream to turn pulses on.
Wait for the pulses to be aligned then proceed to next stage.
Go to the abort stage upon a 60 second timeout.
Go to the abort stage if abort command is issued.
Go to the abort stage if no flow at proving stream.
Go to the abort stage if proving stream telemetry fails.
Goto the abort stage if prove permit state is off.

8.3.4 Sequence Iunction 3: Open prover outlet valve
Issue command to open the prover outlet valve.
Wait for the valve to open then proceed to next stage.
Go to the abort stage if valve fails to move
Go to the abort stage if abort command is issued.
Go to the abort stage if no flow at proving stream.
Go to the abort stage if proving stream telemetry fails.
Go to the abort stage if on line non-proving stream telemetry fails.
Go to the abort stage if prove permit state is off.

8.3.S Sequence Iunction 4: Close non-proving stream prover inlet valves
Check manual operated valve are open.
Issue command to close the prover inlet valve to all non-aligned on line streams.
Wait for valves to close then proceed to next stage.
Go to the abort stage if any valve fails to move
Go to the abort stage if abort command is issued.
Go to the abort stage if no flow at proving stream.
Go to the abort stage if proving stream telemetry fails.
Go to the abort stage if on line non-proving stream telemetry fails.
Go to the abort stage if prove permit state is off.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 55 of 395 Issue 7


8.3.6 Sequence Iunction S: Open proving stream prover inlet valve
Issue command to open prover inlet valve to proving stream.
Wait for valve to open then proceed to next stage.
Go to the abort stage if valve fails to move
Go to the abort stage if abort command is issued.
Go to the abort stage if no flow at proving stream.
Go to the abort stage if proving stream telemetry fails.
Go to the abort stage if on line non-proving stream telemetry fails.
Goto the abort stage if prove permit state is off.

8.3.7 Sequence Iunction 6: Close proving stream outlet valve
Issue command to close proving stream outlet valve.
Wait for valve to close then proceed to next stage.
Go to the abort stage if valve fails to move.
Go to the abort stage if abort command is issued.
Go to the abort stage if no flow at proving stream.
Go to the abort stage if proving stream telemetry fails.
Go to the abort stage if on line non-proving stream telemetry fails.
Goto the abort stage if prove permit state is off.

8.3.8 Sequence Iunction 7: Seat sphere
Issue command to drive 4 way valve to reverse (via seat sphere command to run control task).
Wait for the valve to reach reverse then proceed to next stage.
Go to the abort stage if the valve fails to move to reverse.
Go to the abort stage if abort command is issued.
Go to the abort stage if no flow at proving stream.
Go to the abort stage if proving stream telemetry fails.
Go to the abort stage if on line non-proving stream telemetry fails.
Go to the abort stage if prove permit state is off.
Go to the abort stage if the valves are not correctly aligned.

8.3.9 Sequence Iunction 8: Hold stable temperature, pressure and flowrate
Wait to achieve stability (via stabilise command to run control task) for temperatures, pressure and flowrate rate
of change.
Upon achieving stability, wait for stability to be held for a user configurable time, then proceed to the next
stage.
Go to the abort stage if stability not achieved.
Go to the abort stage if stability not maintained.
Go to the abort stage if abort command is issued.
Go to the abort stage if no flow at proving stream.
Go to the abort stage if proving stream telemetry fails.
Go to the abort stage if on line non-proving stream telemetry fails.
Go to the abort stage if prove permit state is off.
Go to the abort stage if the valves are not correctly aligned.

8.3.J0 Sequence Iunction 9: Perform proof runs
Start the prove runs (via start command to run control task).
Upon achieving stability, wait for stability to be held for a user configurable time, then proceed to the next
stage.
Go to the abort stage if the runs fail e.g. sphere switch timeout.
Go to the abort stage if abort command is issued.
Go to the abort stage if no flow at proving stream.
Go to the abort stage if proving stream telemetry fails.
Go to the abort stage if on line non-proving stream telemetry fails.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 56 of 395 Issue 7
Go to the abort stage if prove permit state is off.
Go to the abort stage if the valves are not correctly aligned.

8.3.JJ Sequence Iunction J0: K factor download
Copy prove K factor, flowrate and frequency into proving stream data points for subsequent telemetry
download. Note that these are not used by the stream metering calculations until commanded separately.
Proceed to the next stage.

8.3.J2 Sequence Iunction JJ: Await reprove command
Proceed to the next stage if terminate command is issued.
Go to the reinitialise stage if continue command is issued.

8.3.J3 Sequence Iunction J2: Seat sphere (at end of prove)
Issue command to drive 4 way valve to reverse (via seat sphere command to run control task).
Wait for the valve to reach reverse then proceed to next stage.
Go to the abort stage if the valve fails to move to reverse.

8.3.J4 Sequence Iunction J3: Open proving stream outlet valve
Check manual operated valves are open.
Issue command to open proving stream header outlet valve.
Wait for valve to open then proceed to next stage.
Go to the abort stage if valve fails to move.
Go to the abort stage if abort command is issued.
Go to the abort stage if proving stream telemetry fails.

8.3.JS Sequence Iunction J4: Close proving stream prover inlet valve
Issue command to close proving stream inlet valve.
Wait for valve to close then proceed to next stage.
Go to the abort stage if valve fails to move.
Go to the abort stage if abort command is issued.
Go to the abort stage if proving stream telemetry fails.

8.3.J6 Sequence Iunction JS: 1urn off pulses.
Command proving stream to turn pulses off.
Wait for the pulses to be turned off then proceed to idle stage.
Go to the abort stage upon a 60 second timeout.

8.3.J7 Sequence Iunction J6: Aborted
Idle, awaiting the abort condition to be rectified.
Go to the idle stage if terminate command is issued.
Return to the aborted stage if continue command is issued.

8.3.J8 Sequence Iunction J7: Reinitialise
Verify:
a) the proving stream number is valid
b) the proving stream is flowing
c) telemetry to the proving stream is OK
d) the prove permit state (i.e. keyswitch) is on
If conditions deny a prove then go to abort stage
If conditions allow a prove to take place then
a) copy the proving stream meter variables into the proving set.
b) initialise proof run data (via initialise command to run control task)
c) proceed to seat sphere stage
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 57 of 395 Issue 7

8.3.J9 Sequence Iunction J8: Re Seat Sphere
Verify after a reprove command:
Issue hardware command to drive 4 way valve to reverse then wait for valve to reach reverse then proceed to
next stage.
If conditions deny a prove then go to abort stage
a) proceed to seat stabilise checks stage

8.3.20 Sequence Iunction J9: Re Check Stability
Verify after a reprove command:
Stability conditions still valid (via stabilise command to run control task) for temperatures, pressure and
flowrate rate of change.
Perform reprove


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 58 of 395 Issue 7
8.4 Prover Connection Schedule
S600 Conn DPin I/O Description Tag No
A 1 DAC 1 +ve Flow Control Valve FV 3203
A 14 DAC 1 ve Flow Control Valve FV 3203
A 8 ADC 1 +ve Inlet Pressure PT 3202
A 21 ADC 2 +ve Outlet Pressure PT 3203
B 4 PRT 1 I + Inlet Temp TE 3202
B 1 PRT 1 V + Inlet Temp TE 3202
B 21 PRT 1 V - Inlet Temp TE 3202
B 24 PRT 1 I - Inlet Temp TE 3202
B 5 PRT 2 I + Outlet Temp TE 3203
B 2 PRT 2 V + Outlet Temp TE 3203
B 22 PRT 2 V - Outlet Temp TE 3203
B 25 PRT 2 I - Outlet Temp TE 3203
B 13 Dig In 1 ve 4 Way V/V Forward MOV 3204
B 14 Dig In 2 ve 4 Way V/V Reverse MOV 3204
B 15 Dig In 3 ve 4 Way V/V L/R MOV 3204
B 16 Dig In 4 ve 4 Way V/V Leak Detect PDS 3204
B 17 Dig In 1-4 +ve Common
B 18 Dig In 5 ve Prv Out V/V 1 Open MOV 3201
B 19 Dig In 6 ve Prv Out V/V 1 Closed MOV 3201
C 19 Dig In 7 ve Prv Out V/V 1 L/R MOV 3201
C 18 Dig 8 ve Prover Available Panel
C 17 Dig In 5-8 +ve Common
C 16 Dig In 9ve Prv Out V/V 2 Open MOV 3202
C 15 Dig In 10 ve Prv Out V/V 2 Closed MOV 3202
C 14 Dig In 11 ve Prv Out V/V 2 L/R MOV 3202
C 13 Dig In 12 ve
C 12 DigIn 9-12 +ve Common
C 36 Dig Out 1+ve 4 Way V/V Fwd Com MOV 3204
C 37 Dig Out 2 +ve 4 Way V/V Rev Com MOV 3204
C 37 Dig Out 3+ve Out V/V 1 Open Com MOV 3201
C 36 Dig Out 4 +ve Out V/V 1 Close Com MOV 3201
C 35 Dig Out 1-4 -ve Command Common
C 34 Dig Out 5+ve Out V/V 2 Open Com MOV 3202
C 33 Dig Out 6 +ve Out V/V 2 Close Com MOV 3202
C 30 Dig Out 5-8 -ve Common
D 1 Pulse 1 In + Raw Pulse Bus
D 14 Pulse 1 In - Raw Pulse Bus
D 17 Switch 1 - Sphere Switch 1 XS 3201
..D 5 Switch 1 - Sphere Switch 2 XS 3203
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 59 of 395 Issue 7
D 18 Switch 1 - Sphere Switch 3 XS 3202
D 6 Switch 1 - Sphere Switch 4 XS 3204
D 4 Switch Comm + Common
RJ 45
Network
1 Signal ground Supervisory Computer
2 DTR Supervisory Computer
3 RTS Supervisory Computer
4 Tx Data Supervisory Computer
5 Rx Data Supervisory Computer
6 CTS Supervisory Computer
7 DSR Supervisory Computer
8 DCD Supervisory Computer
RJ 45 Port 3 1 Signal ground Local Printer
4 Tx Data Local Printer
5 Rx Data Local Printer
TB2 Port 5 1 Rx - Prover Master
2 Rx + Prover Master
3 Tx - Prover Master
4 Tx + Prover Master
5 Rx - Supervisory ComputerA
TB2 port 6 6 Rx + Supervisory ComputerA
7 Tx - Supervisory ComputerA
8 Tx + Supervisory ComputerA
TB2 port 7 9 Rx - Supervisory ComputerB
10 Rx + Supervisory ComputerB
11 Tx - Supervisory ComputerB
12 Tx + Supervisory ComputerB
TB 1 1 24 Volt DC +ve 24 V DC Power
TB 1 2 24 Volt DC -ve 0 V DC Power
TB 1 6 N /C Contact Computer Fail Relay
TB 1 7
Common
Contact
Computer Fail Relay
TB 1 8 N/O Contact Computer Fail Relay


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 60 of 395 Issue 7

8.S Calculations



8.S.J Abbreviations Used in Calculations

Symbol Description

Coefficient of thermal expansion (/degC)

m
compressibility of the liquid at the meter (/bar)

p
compressibility of the liquid at the prover (/bar)

std
standard density of the liquid (kg/m3)
t the prover run flight time (secs)
BV is the calibrated prover volume, for an out and return run (Sm
3
).
BV
run
is the calibrated prover volume, for the out and return trips [ie BV*2] (Sm
3
)
CPLm
fnl
is the correction factor for the effect of pressure on the liquid at the meter, using
the average meter pressure of the consecutive good runs.
CPLm
run


is the correction factor for the effect of pressure on the liquid at the meter, using
the average meter run pressure
CPLp is the correction factor for the effect of pressure on the liquid at the prover, using
the average prover pressure of the consecutive good runs.
CPLp
run
is the correction factor for the effect of pressure on the liquid at the prover, using
the average prover run pressure
CPSp is the correction factor for the effect of pressure on the steel at the prover, using
the average prover pressure of the consecutive good runs.
CPSp
run
is the correction factor for the effect of pressure on the steel at the prover, using
the average prover run pressure
CTLm
run


is correction factor for the effect of temperature on the liquid at the meter, using
the average meter run temperature
CTLp is correction factor for the effect of temperature on the liquid at the prover, using
the average prover temperature of the consecutive good runs.
CTLp
run
is correction factor for the effect of temperature on the liquid at the prover, using
the average prover run temperature
CTSp is the correction factor for the effect of temperature on the steel at the prover,
using the average prover temperature of the consecutive good runs.
CTSp
fnl
is the correction factor for the effect of temperature on the steel at the prover,
using the average prover temperature of the consecutive good runs.
CTSp
run
is the correction factor for the effect of temperature on the steel at the prover,
using the average prover run temperature
CTS
prun
run correction factor for the effect of temperature on the prover
D internal diameter of prover flow tube (mm)
E modulus of elasticity of prover flow tube steel (/bar)
e thermal coefficient of cubic expansion of the prover steel (/degC)
GVFR
FINAL
is the gross volume flowrate for N consecutive good runs (m
3
/h).
GVFR
RUN
is the gross volume flowrate for the run (m
3
/h)
K0.K1,K2 Liquid specific coefficients
K
AVG
is the average K-Factor (pls/m
3
)
KF
fnl
is the final K-Factor (pls/m
3
)
KF
o
original (calibrated )K factor (pls/m
3
)
K
DEV
is the K-Factor deviation (%)
K
run
is the run K-Factor (pls/m
3
).
MF is the meter factor
N the number of consecutive good runs
PC
fnl
is the final pulse count (pls)
PC
run
is the run pulse count (pls).
P
e
equilibrium vapour pressure (barg)
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 61 of 395 Issue 7
Period the sampling interval
P
m
pressure at the meter (barg)
P
p
pressure at the prover (barg)
P
pfnl
final average prover pressure (barg)
P
prun
run average prover pressure (barg)
P
r
reference pressure (barg)
Samples the number of samples taken during the run
t wall thickness of the prover flow tube (mm)
T
base
reference temperature (degC)
T
m
Meter Temperature (degC)
T
p
Prover Temperature (degC)
T
pfinal
final average prover temperature (degC)
T
prun
run average prover temperature (degC)
T
ref
Calibration reference temperature (degC)
X
FINAL
the average value of a relevant variable for the N consecutive good runs
X
inst
the instantaneous sample value of the variable being averaged.
X
NEW
the new sample value
X
LAST
the previous sample value
X
RATE
the rate of the variable
X
RUN
the average value of the variable for a single round trip run.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 62 of 395 Issue 7
8.S.2 Run Average Data
Samples
Xinst
RUN X

=

The sampled variables (X
inst
) are;
prover temperature (average of inlet and outlet),
prover pressure (average of inlet and outlet),
stream temperature,
stream pressure,
pulse count,
flight time,
standard density.

8.S.3 Variable Average Over Consecutive Good Runs
N
X
X
RUN
FINAL

=

The averaged variables are;
prover temperature (average of inlet and outlet),
prover pressure (average of inlet and outlet),
stream temperature,
stream pressure,
pulse count,
flight time,
standard density.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 63 of 395 Issue 7
8.S.4 Stream / Prover Discrepancy Checks
The discrepancy calculation is used as part of a stability check between stream and prover variables
X
DIFF
= X
A
- X
B


X
A
, X
B
are the variables being compared
X
DIFF
is the difference between the variables XA and XB

The checks are performed;
Prover Inlet - Prover Outlet (Temperature and Pressure)
Prover Inlet - Stream (Temperature and Pressure)
Prover Outlet - Stream (Temperature and Pressure)

8.S.S Variable Rate of Change
The rate of change calculation is used as part of a stability check between stream and prover variables
Period
- X X
X
LAST NEW
RATE =


The checks are performed;
Prover Inlet (Temperature and Pressure)
Prover Outlet (Temperature and Pressure)
Stream Flowrate

8.S.6 Run Gross Volume Ilowrate (m
3
/h)
The following calculation is used to determine the run gross volume flowrate

run run
run run run run run
RUN
CPLm x CTLm t x
3600 x CPSp x CTSp x CPLp x CTLp x BV
= GVFR


8.S.7 Iinal Gross Volume Ilowrate (m
3
/h)
The final gross volume flowrate is the average of the flowrates over last n good runs.

8.S.8 Run K-Iactor (pls/m
3
)
The following calculation is used to determine the run K-Factor.
run run run run
run run run
run
CPSp x CTSp x CPLp x CTLp x BV
CPLm x CTLm x PC
= K

8.S.9 Iinal K-Iactor (pls/m
3
)
The final K-Factor.is the average of the K factor over last n good runs

8.S.J0 Meter Iactor
The meter factor is the final K factor divided by the original (i.e. factory calibrated) K factor.

o
fnl
KF
KF
MF =





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 64 of 395 Issue 7
8.S.JJ K-Iactor Deviation
The following calculation is used to determine the deviation of a run K-Factor from the average K-Factor.
( )
100
K
K - K
= K
min
min max
x
DEV



8.S.J2 Correction Iactor for the Lffect of 1emperature on the Liquid
The following equations are used to calculate the correction factors for the effect of temperature on the liquid
: ))] ( 8 . 0 0 . 1 )( ( [
: Meter b)At the
))] ( 8 . 0 0 . 1 )( ( [
: Prover At the )
Tref Tm Tref Tm EXP CTLm
Tref Tp Tref Tp EXP CTLp
a
+ =
+ =




8.S.J3 Coefficient of 1hermal Lxpansion of the Liquid (/degC)
The following equation is used to calculate the coefficient of thermal expansion of the liquid
2
1 0
+ + =
2
K
K K
std std


8.S.J4 Correction Iactor for the Lffect of Pressure on the Liquid
The following equations are used to calculate the correction factors for the effect of temperature on the liquid
( )
( ) e m m
e p p
P P
CPLm
P P
CPLp
1
1
: Meter b)At the
- - 1
1

: Prover a)At the

=
=


8.S.JS Compressibility Iactor API (Base Density 638 -J074 kg/m
3
)
The following equations are used to calculate the compressibility of the liquid
( ) ( )
( ) ( )
4 -
2
3 -
2
3 -
4 -
2
3 -
2
3 -
10
10
T 0042092 . 0
10
0.87096
+ T x 0.00021592 + 1.62080 - =
: Meter b)At the
10
10
T 0042092 . 0
10
0.87096
+ T x 0.00021592 + 1.62080 - =
: Prover a)At the
x
x
x
x
EXP
x
x
x
x
EXP
std
m
std
m m
std
p
std
p p
|
|
.
|

\
|
+
|
|
.
|

\
|
+


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 65 of 395 Issue 7
8.S.J6 Correction Iactor Ior 1he Lffect Of Pressure On 1he Prover Steel
The following equation is used to calculate the correction factor for the effect of pressure on the prover steel:
a) Run
Et D Pp CPSp run run / Pr) ( 1 + =
b) Final
Et D Pp CPSpfnl fnl / Pr) ( 1 + =

Correction Factor For The Effect Of Temperature On The Prover Steel
The following equation is used to calculate the correction factor for the effect of pressure on the prover steel:
a) Run:
) ( 1 Tref Tprun e CTSprun + =
b) Final:
) ( 1 Tref Tpfnl e CTSpfnl + =

8.S.J7 Corrected Prover Base Volume (m
3
)
The following calculation is used to determine the prover base volume corrected to observed temperature and
pressure.
CPSp x CTSp x CPLp x CTLp x BV = BV
CORR





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 66 of 395 Issue 7
8.6 Displays
The following is representative of the data that will be available on the front panel of the meter computer.
PROVER IO Parameters Units

Sphere switch 1 Clear / set
Sphere switch 2 Clear / set
Sphere switch 3 Clear / set
Sphere switch 4 Clear / set
Pulse count between selected sphere switches
Flight time between selected sphere switches secs

O/L Pressure measured barg

O/L Temperature measured
o
C

I/L Pressure measured barg


I/L Temperature measured
o
C

SEQUENCE CTL Parameters Units

control Start, terminate, abort, continue
stream number Modbus address to poll for stream data
run stage index current sequence
run abort index current abort reason
Final K factor Avg K factor on consecutive good runs. Pls/m
3

Final flowrate Avg flowrate on consecutive good runs. m
3
/hr
Final frequency Avg pulse Freq on consecutive good runs. Hz
Final meter factor Avg meter factor on consecutive good runs.
stage index current sequence
stage previous index The last sequence stage index value prior to a change
of index.


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 67 of 395 Issue 7

RUN CTL Parameters Units

control Init/seat sphere/stabilise/start runs/terminate
stability override Enabled/disabled
base vol index select which sphere switches to use
trial number current trial
stability status current status
base vol in use current base volume selected (only updated after
INITIALISATION stage)
m
3

calculation abort index current abort reason
permit status Supervisory interlock status

CONSTANTS Parameters Units

Reference pressure from prover calib cert barg
Reference temperature from prover calib cert
o
C
pipe diameter from prover calib cert mm
modulus of elasticity from prover calib cert
wall thickness from prover calib cert mm
tube coefficient from prover calib cert
Base volume 1 from prover calib cert m
3

Base volume 2 from prover calib cert m
3

Base volume 3 from prover calib cert m
3

Base volume 4 from prover calib cert m
3

Pre switch 1 volume Used for sphere switch timeouts (wrt GVOL F/R).
Set = 0.0 to disable
m
3

Pre switch 2 volume Used for sphere switch timeouts (wrt GVOL F/R).
Set = 0.0 to disable
m
3

Stability wait time Time to wait before starting stability checks secs
Stability hold time Time to maintain stable conditions secs
Run delay time Delay between end and start of next run. secs
4 way turn around time Not used. secs
Required no. runs Enter minimum consecutive runs required
Maximum no. runs Enter maximum number of runs to achieve required
number of consecutive runs stated

K Factor tolerance Enter Tolernace required for consecutive good proof
runs.
%
Temperature rate of change Used for Stability tests
o
C/sec
Pressure rate of change Used for Stability tests barg/sec

Temperature band Used for Stability tests
o
C
Pressure band Used for Stability tests barg

Flowrate rate of change Used for Stability tests m
3
/hr/
sec
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 68 of 395 Issue 7

STREAM DATA Parameters Units

Meter pressure barg
Meter temperature
o
C
Meter vapour pressure barg

Meter std density kg/m
3

Meter gross vol f/r m
3
/hr
Meter K factor Pls/m
3

Meter.K0
Meter K1
Meter K2
Meter CTSm
Meter CPSm

HALF RUN DATA Parameters Units

Pulses
Flight time secs

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 69 of 395 Issue 7

FULL RUN DATA Parameters Units

Run Pulses
Run Flight time secs
Avg meter pressure barg
Avg meter temperature
o
C
Avg meter vapour press barg

Avg meter std. Density kg/m
3

Avg prover pressure barg
Avg prover temperature
o
C
Avg meter CTSm

Avg meter CPSm

Run K Factor Pls/m
3
Avg pulse frequency Hz
Run CPSp
Run CTSp
Run beta (meter)
Run beta (prover)
Run CPLp
Run CPLm
Run alpha
Run CTLp
Run CTLm
Run corrected volume m
3

Run flowrate m
3
/hr
Run meter correction factor

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 70 of 395 Issue 7


FINAL DATA Parameters Units

Pulses
Flight time secs
meter pressure barg
meter temperature
o
C
meter vapour press barg

meter std. Density kg/m
3

prover pressure barg
prover temperature
o
C
meter CTSm

meter CPSm

K Factor Pls/m
3
pulse frequency Hz
CPSp
CTSp
beta (meter)
beta (prover)
CPLp
CPLm
alpha
CTLp
CPLm
corrected volume m
3

corr. vol flowrate m
3
/hr
meter correction factor
Repeatability %
Meter factor


FINAL DATA
Parameters Units

4 way valve status Illegal/forward/reverse/moving
4 way valve sealed Clear/set
Prover outlet valve status Illegal/open/closed/moving




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 71 of 395 Issue 7
Alarms
The alarms below can be raisedby the Prover computer.

S600 SYS HOST COLD ST Grp 1
S600 SYS HOST WARM ST Grp 1
S600 PROVER MASTER LINK RX FAIL Grp 3
S600 PRINTER MONITOR Grp 4
S600 BKGND TASK MONITOR Grp 4
S600 BKGND TASK TSK ERR Grp 4
S600 DIO SCAN TASK MONITOR Grp 4
S600 DIO SCAN TASK TSK ERR Grp 4
S600 DISPLAY TASK MONITOR Grp 4
S600 DISPLAY TASK TSK ERR Grp 4
S600 IO COMMS TASK MONITOR Grp 4
S600 IO COMMS TASK FAIL IO1 Grp 4
S600 IO COMMS TASK FAIL IO2 Grp 4
S600 IO COMMS TASK FAIL IO3 Grp 4
S600 IO COMMS TASK FAIL IO4 Grp 4
S600 IO COMMS TASK FAIL IO5 Grp 4
S600 IO COMMS TASK FAIL IO6 Grp 4
S600 IO COMMS TASK FAIL IO7 Grp 4
S600 IO COMMS TASK TSK ERR Grp 4
S600 IO SCAN TASK MONITOR Grp 4
S600 IO SCAN TASK TSK ERR Grp 4
S600 REPORTS TASK MONITOR Grp 4
S600 REPORTS TASK TSK ERR Grp 4
S600 TOTALS TASK MONITOR Grp 4
S600 TOTALS TASK TSK ERR Grp 4
S600 LIQ KF/MF TASK MONITOR Grp 4
S600 LIQ KF/MF TASK TSK ERR Grp 4
S600 LIQ M CORR TASK MONITOR Grp 4
S600 LIQ M CORR TASK TSK ERR Grp 4
S600 LIQ LIQ CON TASK MONITOR Grp 4
S600 LIQ LIQ CON TASK TSK ERR Grp 4
S600 LIQ TURB TASK MONITOR Grp 4
S600 LIQ TURB TASK TSK ERR Grp 4
S600 LIQ VOL CORR TASK MONITOR Grp 4
S600 LIQ VOL CORR TASK TSK ERR Grp 4
S600 PRV SEQ TASK MONITOR Grp 4
S600 PRV SEQ TASK TSK ERR Grp 4
S600 PRV BIDI TASK MONITOR Grp 4
S600 PRV BIDI TASK TSK ERR Grp 4
S600 DENSITY TASK MONITOR Grp 4
S600 DENSITY TASK TSK ERR Grp 4
S600 STR STATUS TASK MONITOR Grp 4
S600 STR STATUS TASK TSK ERR Grp 4
S600 FWA CALC TASK MONITOR Grp 4
S600 FWA CALC TASK TSK ERR Grp 4
S600 BVM TASK MONITOR Grp 4
S600 BVM TASK TSK ERR Grp 4
S600 STN AVE TASK MONITOR Grp 4
S600 STN AVE TASK TSK ERR Grp 4
S600 DISCREP TASK MONITOR Grp 4
S600 DISCREP TASK TSK ERR Grp 4
S600 CALC TASK MONITOR Grp 4
S600 CALC TASK TSK ERR Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 72 of 395 Issue 7
S600 PID CTL TASK MONITOR Grp 4
S600 PID CTL TASK TSK ERR Grp 4
S600 ALM SUPPRESS TASK MONITOR Grp 4
S600 ALM SUPPRESS TASK TSK ERR Grp 4
S600 BATCH/FSW TASK MONITOR Grp 4
S600 BATCH/FSW TASK TSK ERR Grp 4
S600 CALIB TASK MONITOR Grp 4
S600 CALIB TASK TSK ERR Grp 4
S600 LOGICALC TASK MONITOR Grp 4
S600 LOGICALC TASK TSK ERR Grp 4
S600 LIQ COR IO TASK MONITOR Grp 4
S600 LIQ COR IO TASK TSK ERR Grp 4
S600 LIQ COR IF TASK MONITOR Grp 4
S600 LIQ COR IF TASK TSK ERR Grp 4
S600 LIQ COR FLOW TASK MONITOR Grp 4
S600 LIQ COR FLOW TASK TSK ERR Grp 4
S600 PRV CPRV TASK MONITOR Grp 4
S600 PRV CPRV TASK TSK ERR Grp 4
S600 FAULT TASK MONITOR Grp 4
S600 FAULT TASK TSK ERR Grp 4
S600 FLOWTIME TASK MONITOR Grp 4
S600 FLOWTIME TASK TSK ERR Grp 4
S600 SGERG TASK MONITOR Grp 4
S600 SGERG TASK TSK ERR Grp 4
S600 PRV MMPRV TASK MONITOR Grp 4
S600 PRV MMPRV TASK TSK ERR Grp 4
S600 ADC 01 IN PRS L Grp 2
S600 ADC 01 IN PRS H Grp 2
S600 ADC 01 IN PRS DEV ERR Grp 3
S600 ADC 02 OUT PRS L Grp 2
S600 ADC 02 OUT PRS H Grp 2
S600 ADC 02 OUT PRS DEV ERR Grp 3
S600 PRT 01 IN TMP L Grp 2
S600 PRT 01 IN TMP H Grp 2
S600 PRT 01 IN TMP DEV ERR Grp 3
S600 PRT 02 OUT TMP L Grp 2
S600 PRT 02 OUT TMP H Grp 2
S600 PRT 02 OUT TMP DEV ERR Grp 3
S600 STATUS RAM FAIL Grp 4
S600 STATUS ROM FAIL Grp 4
S600 STATUS PIC FAIL Grp 4
S600 STATUS TPU FAIL Grp 4
S600 STATUS EEPROM FAIL Grp 4
S600 STATUS TASK ERR Grp 4
S600 STATUS CONF ERR Grp 4
S600 STATUS TASK FAIL Grp 4
S600 STATUS WARM ST Grp 4
S600 STATUS DEV ERR Grp 4
S600 STATUS RAM FAIL Grp 4
S600 STATUS ROM FAIL Grp 4
S600 STATUS PIC FAIL Grp 4
S600 STATUS TPU FAIL Grp 4
S600 STATUS EEPROM FAIL Grp 4
S600 STATUS TASK ERR Grp 4
S600 STATUS CONF ERR Grp 4
S600 STATUS TASK FAIL Grp 4
S600 STATUS WARM ST Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 73 of 395 Issue 7
S600 STATUS DEV ERR Grp 4
S600 STN01 FBAL CALC CONF ERR Grp 4
S600 STN01 FBAL CALC I/P ERR Grp 4
S600 STN01 FBAL CALC O/P ERR Grp 4
S600 STN01 FBAL CALC CALC FAIL Grp 4
S600 STN01 FBAL CALC NO PERMIT Grp 4
S600 STN01 FBAL FCVS CALC CONF ERR Grp 4
S600 STN01 FBAL FCVS CALC I/P ERR Grp 4
S600 STN01 FBAL FCVS CALC O/P ERR Grp 4
S600 STN01 FBAL FCVS CALC CALC FAIL Grp 4
S600 STN01 FBAL FCVS CALC NO PERMIT Grp 4
S600 STN01 SEQ S.CTRL CALC CONF ERR Grp 4
S600 STN01 SEQ S.CTRL CALC I/P ERR Grp 4
S600 STN01 SEQ S.CTRL CALC O/P ERR Grp 4
S600 STN01 SEQ S.CTRL CALC CALC FAIL Grp 4
S600 STN01 SEQ S.CTRL CALC NO PERMIT Grp 4
S600 STN01 SEQ S.VAR CALC CONF ERR Grp 4
S600 STN01 SEQ S.VAR CALC I/P ERR Grp 4
S600 STN01 SEQ S.VAR CALC O/P ERR Grp 4
S600 STN01 SEQ S.VAR CALC CALC FAIL Grp 4
S600 STN01 SEQ S.VAR CALC NO PERMIT Grp 4
S600 STN01 SEQ M.STAT CALC CONF ERR Grp 4
S600 STN01 SEQ M.STAT CALC I/P ERR Grp 4
S600 STN01 SEQ M.STAT CALC O/P ERR Grp 4
S600 STN01 SEQ M.STAT CALC CALC FAIL Grp 4
S600 STN01 SEQ M.STAT CALC NO PERMIT Grp 4
S600 STN01 SEQ CTL ABT 1 Grp 2
S600 PRV01 PID MF CALC CONF ERR Grp 4
S600 PRV01 PID MF CALC I/P ERR Grp 4
S600 PRV01 PID MF CALC O/P ERR Grp 4
S600 PRV01 PID MF CALC CALC FAIL Grp 4
S600 PRV01 PID MF CALC NO PERMIT Grp 4
S600 PRV01 RUN CTL CALC CONF ERR Grp 4
S600 PRV01 RUN CTL CALC I/P ERR Grp 4
S600 PRV01 RUN CTL CALC O/P ERR Grp 4
S600 PRV01 RUN CTL CALC CALC FAIL Grp 4
S600 PRV01 RUN CTL CALC NO PERMIT Grp 4
S600 PRV01 RUN PAR CALC CONF ERR Grp 4
S600 PRV01 RUN PAR CALC I/P ERR Grp 4
S600 PRV01 RUN PAR CALC O/P ERR Grp 4
S600 PRV01 RUN PAR CALC CALC FAIL Grp 4
S600 PRV01 RUN PAR CALC NO PERMIT Grp 4
S600 PRV01 STAB PAR CALC CONF ERR Grp 4
S600 PRV01 STAB PAR CALC I/P ERR Grp 4
S600 PRV01 STAB PAR CALC O/P ERR Grp 4
S600 PRV01 STAB PAR CALC CALC FAIL Grp 4
S600 PRV01 STAB PAR CALC NO PERMIT Grp 4
S600 PRV01 RAW IO CALC CONF ERR Grp 4
S600 PRV01 RAW IO CALC I/P ERR Grp 4
S600 PRV01 RAW IO CALC O/P ERR Grp 4
S600 PRV01 RAW IO CALC CALC FAIL Grp 4
S600 PRV01 RAW IO CALC NO PERMIT Grp 4
S600 PRV01 PRV VARS CALC CONF ERR Grp 4
S600 PRV01 PRV VARS CALC I/P ERR Grp 4
S600 PRV01 PRV VARS CALC O/P ERR Grp 4
S600 PRV01 PRV VARS CALC CALC FAIL Grp 4
S600 PRV01 PRV VARS CALC NO PERMIT Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 74 of 395 Issue 7
S600 PRV01 MTR VARS CALC CONF ERR Grp 4
S600 PRV01 MTR VARS CALC I/P ERR Grp 4
S600 PRV01 MTR VARS CALC O/P ERR Grp 4
S600 PRV01 MTR VARS CALC CALC FAIL Grp 4
S600 PRV01 MTR VARS CALC NO PERMIT Grp 4
S600 PRV01 P.CONST CALC CONF ERR Grp 4
S600 PRV01 P.CONST CALC I/P ERR Grp 4
S600 PRV01 P.CONST CALC O/P ERR Grp 4
S600 PRV01 P.CONST CALC CALC FAIL Grp 4
S600 PRV01 P.CONST CALC NO PERMIT Grp 4
S600 PRV01 PASS CALC CONF ERR Grp 4
S600 PRV01 PASS CALC I/P ERR Grp 4
S600 PRV01 PASS CALC O/P ERR Grp 4
S600 PRV01 PASS CALC CALC FAIL Grp 4
S600 PRV01 PASS CALC NO PERMIT Grp 4
S600 PRV01 RUN CALC CONF ERR Grp 4
S600 PRV01 RUN CALC I/P ERR Grp 4
S600 PRV01 RUN CALC O/P ERR Grp 4
S600 PRV01 RUN CALC CALC FAIL Grp 4
S600 PRV01 RUN CALC NO PERMIT Grp 4
S600 PRV01 PRV AVG CALC CONF ERR Grp 4
S600 PRV01 PRV AVG CALC I/P ERR Grp 4
S600 PRV01 PRV AVG CALC O/P ERR Grp 4
S600 PRV01 PRV AVG CALC CALC FAIL Grp 4
S600 PRV01 PRV AVG CALC NO PERMIT Grp 4
S600 PRV01 PRV ARRY CALC CONF ERR Grp 4
S600 PRV01 PRV ARRY CALC I/P ERR Grp 4
S600 PRV01 PRV ARRY CALC O/P ERR Grp 4
S600 PRV01 PRV ARRY CALC CALC FAIL Grp 4
S600 PRV01 PRV ARRY CALC NO PERMIT Grp 4
S600 PRV01 SEQ CTL CALC CONF ERR Grp 4
S600 PRV01 SEQ CTL CALC I/P ERR Grp 4
S600 PRV01 SEQ CTL CALC O/P ERR Grp 4
S600 PRV01 SEQ CTL CALC CALC FAIL Grp 4
S600 PRV01 SEQ CTL CALC NO PERMIT Grp 4
S600 PRV01 PRV 4WAY CALC CONF ERR Grp 4
S600 PRV01 PRV 4WAY CALC I/P ERR Grp 4
S600 PRV01 PRV 4WAY CALC O/P ERR Grp 4
S600 PRV01 PRV 4WAY CALC CALC FAIL Grp 4
S600 PRV01 PRV 4WAY CALC NO PERMIT Grp 4
S600 PRV01 I/L VLV CALC CONF ERR Grp 4
S600 PRV01 I/L VLV CALC I/P ERR Grp 4
S600 PRV01 I/L VLV CALC O/P ERR Grp 4
S600 PRV01 I/L VLV CALC CALC FAIL Grp 4
S600 PRV01 I/L VLV CALC NO PERMIT Grp 4
S600 PRV01 O/L VLV CALC CONF ERR Grp 4
S600 PRV01 O/L VLV CALC I/P ERR Grp 4
S600 PRV01 O/L VLV CALC O/P ERR Grp 4
S600 PRV01 O/L VLV CALC CALC FAIL Grp 4
S600 PRV01 O/L VLV CALC NO PERMIT Grp 4
S600 PRV01 RTRIP K.FACTOR L Grp 2
S600 PRV01 RTRIP K.FACTOR H Grp 2
S600 PRV01 P.4WAY VLV ILLEGAL Grp 2
S600 PRV01 P.4WAY VLV SEAL FAIL Grp 2
S600 PRV01 P.4WAY VLV MOVE FAIL Grp 2
S600 PRV01 P.4WAY VLV MOVE UNCM Grp 2
S600 PRV01 P.O/L VLV 1 ILLEGAL Grp 2
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 75 of 395 Issue 7
S600 PRV01 P.O/L VLV 1 MOVE FAIL Grp 2
S600 PRV01 P.O/L VLV 1 MOVE UNCM Grp 2
S600 PRV01 P.O/L VLV 2 ILLEGAL Grp 2
S600 PRV01 P.O/L VLV 2 MOVE FAIL Grp 2
S600 PRV01 P.O/L VLV 2 MOVE UNCM Grp 2
S600 PRV01 O/L VLV 2 CALC CONF ERR Grp 4
S600 PRV01 O/L VLV 2 CALC I/P ERR Grp 4
S600 PRV01 O/L VLV 2 CALC O/P ERR Grp 4
S600 PRV01 O/L VLV 2 CALC CALC FAIL Grp 4
S600 PRV01 O/L VLV 2 CALC NO PERMIT Grp 4



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 76 of 395 Issue 7
8.6.J Prover Abort Alarm Codes
The S600 prover has one alarm entitled prove abort. The reason for the prove abort alarm is coded and shown
on the front panel and also via Modbus.
Tabled below are the codes for both the Prove Sequence Abort Index and the Run Control Abort Index.
Sequence Abort Index
Code Description
0 Normal
1 Operator Abort
2 Invalid stream number
3 Telemetry fail to proving stream
4 Run task Busy
5 No flow at meter
6 Run Control Aborted
7 Illegal Pulses
8 Telemetry Fail
9 Non Proving Stream Inlet valve not closed
10 Proving Stream Inlet valve not opened
11 Proving Stream Outlet valve not closed
12 Prover inlet valve not open
13 Prover outlet valve not open
14 Prover in Maintenance mode
15 Flow Balance Timeout
16 Flow Balance No Non Proving stream on line
17 Flow Balance No Non Proving stream in auto
18 Flow Balance Hold Fail

Bi-directional Run Abort Index
Code Description
0 Normal
1 Operator requested
2 4 Way command timeout
3 First SS timeout. Check pre-switch volume
4 Second SS timeout. . Check pre-switch volume
5 Stability Wait (temperature / pressure / flowrate stability not achieved)
6 Stability Hold (stability lost during hold stage at start of prove
7 Average calculation error - number of samples exceeds 30,000
8 Not used
9 Full Calc - An error occurred when performing a full run calculation. See
Calculation Abort Index.
10 Runs Exceeded
11 Sphere switch error
12 Pulse Interpolation Module - Lock Lost
13 Prover I/O board failed to respond
14 Null Data - Invalid half run data. Check half run flight time < TINY or half run
pulse count < TINY
15 Base Volume changed during proof run
16 KF Range - Check FULL K FACTOR and limits on FULL RUN operator menu
17 4 way valve moved

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 77 of 395 Issue 7

Calculation Abort Index
Code Calculation Description
0 No errors No calc errors
1 CTSP Calc fails if ctsp is < 0.5 or > 1.5
2 CPSP Calc fails if modulus of elastisity * wall thickness is 0, or
cpsp is < 0.5 or > 1.5
3 Beta for the prover No longer supported - pre v1.0 only
4 Beta for the meter No longer supported - pre v1.0 only
5 CPLP CPL calculation error
6 CPLM CPL calculation error
7 Alpha No longer supported - pre v1.0 only
8 CTLP CTL calculation error - calc fails when denisty < TINY
(alpha calculation)
9 CTLM CTL calculation error - calc fails when denisty < TINY
(alpha calculation)
10 Corrected Prover volume Not used
11 Meter correction factor Calc fails if (ctlm * ctlp) < TINY 12 K Factor Calc fails if
kf is less than kf low limit or greater than kf high limit
13 Meter Factor Calc fails if proved kf or stream kf < TINY



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 78 of 395 Issue 7
9 GAS S1RLAM ILOWCOMPU1LR

The S600 stream computers are factory configured to provide all the measurement functions for the Helang gas
orifice metering application.

9.J General Ieatures
9.J.J DP Cell Handling
The flowcomputer will accept analogue signals from four separate differential pressure cells connected across
the same orifice plate. The cells are arranged in two pairs of low and high cells designated pay and check.
If the differences between the pay and check cells exceed operator entered limits then an alarm is raised.
If failure of the in use pay cell is detected, the matching check cell is selected for use.
Switchover points are provided (operator changeable) to enable switching to take place between the high and
low DP cells depending on the percentage reading of the low range cell. The low to high and high to low switch
points will normally be set at 95% and 90% of the low cell range to prevent multiple switchovers occurring.
When the DP in use is within +/- 5% of the changeover value the difference between the two readings will be
compared against a keypad entered discrepancy. If this value is exceeded a cell discrepancy alarm will be
raised.

9.J.2 Low Ilow Cut-off
An operator settable low flow cut-off point is provided for entry of a percentage of the low DP cell range. When
the gas DP exceeds this figure, the flowcomputer will calculate flowrates and totalisation will be performed -
this is the normal metering condition.
When a gas DP is measured below the low flow cut-off, a low flow alarm will be raised, limit alarms are
suppressed and flowrate calculations and totalisation are inhibited.

9.J.3 DP Cell Operation
Assuming no flow conditions to start with, when the DP measured from the low cell exceeds the low flow cut
off value, the DP from this cell will be used to perform the flowrate calculations. When the DP reading from the
low cell reaches within 5% of the low to high switchover point the readings from the low and high DP cells are
compared. If the discrepancy limit is exceeded an alarm is raised.
The reading from the high cell is now selected for use in the calculations.
As the DP continues to rise, the DP measurement from the high cell will continue to be used. If the range of the
high cell is exceeded the cell fail alarm will be raised and the keypad DP value (usually 0) will be selected for
use.
When the DP is in the high range, the reading from the low cell will exceed the normal range, an alarm will not
be raised under these circumstances.

If the High range cell is in use and the DP is falling, when the value reaches 5% of the changeover value the
reading from the high and low cells will be compared to the cell discrepancy limit and an alarm raised if this is
exceeded. When the reading from the High DP cell falls to the value equal to the switch down point the low DP
cell reading will be selected for use.
If the falling DP from the high cell reaches the switchover point and the low cell is failed the reading from the
high cell will continue to be used.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 79 of 395 Issue 7

9.J.4 Density Handling

A Solartron 7812 densitometer installed downstream of the orifice plate will be connected to each flow
computer. The densitometer calibration constants will be operator entered in to the flowcomputer and density
will be calculated according to the Solartron calculation using these constants and the period measured from the
densitometer.
A correction is made to the density using the gas temperature measurement taken from the line transmitter.

A second density calculation will be performed according to AGA-8 1994 report using the upstream meter
temperature and pressure and the gas composition data. The gas composition data is measured by the
chromatograph and transferred to the export gas stream computer from the supervisory.
In the event of failure of the communications link to the supervisory computer, the gas export stream polls data
directly from the chromatograph for use. A set of default gas compositions is also stored in the export gas
streams and in the event of failure of the chromatograph the default data will automatically be selected for use
in the AGA 8 calculations.
The density from the densitometer is normally selected for use. An operator entered discrepancy limit is
provided and the difference between the two density values is compared with this limit on every machine cycle.
If the densitometer input is detected to have failed then the AGA -8 calculated density is automatically selected
for use. If the AGA -8 calculated density is outside limits then the keypad density is selected for use.







































Correct
Measured
Density to
Upstream
conditions
Hi Lo Alarm Checks
Measured
Density A
Downstream
Density
Keypad

Upstream
Keypad
Value
Gas
Composition
AGA 8
Calculated
Upstream
Density
Discrepancy
Checking
In Use Stream Density
Options of Measured, AGA 8 & Keypad With
auto switching to AGA 8 fail & Keypad- fail
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 80 of 395 Issue 7

9.J.S Gas 1otals/Ilowrates
Gas flowrates will be calculated and totals formed for the following gas compositions.

Gas Composition Mass Std Volume Energy
Total
C1-C4
C5+
C1,C2,C3,iC4,nC4,C5+,CO2,
N2


9.J.6 Units
The following units will be used

Flowrate Resolution Total Resolution
Mass t/h xxxxxxxx.xxx t xxxxxxxx.xxx
Std Volume Skm3/h
Skm3/d
MMScf/d
xxxxxxxx.xxx Skm3 xxxxxxxx.xxx
Std Volume xxxxxxxx.xxx bbl xxxxxxxx.xxx
Energy GJ/h xxxxxxxx.xxx GJ xxxxxxxx.xxx
Energy MBtu xxxxxxxx.xxx

9.J.7 Component Mass 1otals
Mass totals are to be formed for individual gas components of C1, C2, C3, iC4, nC4, C5+, CO2 and N2. The
mass totals will be formed in tonnes. The component mass totals will be summated on a daily basis.
Component mass totals are also formed for C1-C4 in tonnes and C5+ in kg.
9.J.8 CJ C4 Standard Volume Ilowrate
The standard volume flowrate for components C1 C4 will be calculated in units of MMSCF/d .

9.J.9 Daily Standard Volume Ilowrate
The daily standard volume flowrate for the gas mixture will be calculated.

9.J.J0 Average, Maximum and Minimum S Vol Ilowrates
The average, maximum and minimum standard volume flowrate for the gas mixture will be computed on a daily
basis.

9.J.JJ CS+ Liquid 1otals
The volume of Condensate and Natural Gas Liquid, C5+, in Gas Stream shall be calculated in accordance with
GPA Standard 8173-94.
The period, daily and weekly gas totals for C5+ in the gas export and gas back up systems will be calculated.
The resultant totals will represent the liquid totals in barrels at 60 F at 1 atm.
The C5+ total will be made up of components nC5, iC5, neoC5, and C6+
The C6+ component is the summation of the C6, C7, C8, C9 and C10 components.

The C5+ total will be calculated by taking the mass of iC5, nC5, neoC5 and C6+ and dividing by the relevant
liquid standard density in kg/m
3
to produce the standard volume in m
3
.
The liquid densities of nC5, iC5, and neoC5 are 631.05, 624.54 and 596.7 respectively at standard conditions of
15 C and 1.01325 bara .
Standard densities for nC5 and iC5 are according to GPA Standard 2145-00 Revision 2 and GPSA Engineering
Data Book (11
th
Edition 1998).
Standard density for neoC5 is according to GPSA Engineering Data Book (11
th
Edition 1998).
The liquid standard densities of nC5, iC5 and neoC5 will be hard coded to the calculations and passed to the
supervisory for display purposes.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 81 of 395 Issue 7
The component mass of C5+ shall be obtained by multiplying mol% x mol mass of C6+. The mol mass of
C6+(obtained from laboratory analysis) shall be manually entered.
The standard density for the C6+ component will be a keypad entered value derived from laboratory analysis.
The resulting totals in Sm
3
will be passed to the supervisory for display purposes as individual values. The sum
of C5+in Sm
3
will be calculated and also passed to the supervisory for display purposes.
The total for C5+ in Sm
3
will be added to the current, hourly, daily and weekly reports

The resultant standard volumes for nC5, iC5, neoC5, and C6+ will be converted to barrels at 60 F by
multiplication by a conversion factor.
The conversion factors of nC5, iC5, and neoC5 are 6.295, 6.295 and 6.296 respectively according to ASTM D-
1250:IP200, table 52.
The conversion factors of nC5, iC5 and neoC5 will be hard coded to the calculations and passed to the
supervisory for display purposes.

The conversion factor for the C6+ component will be a keypad entered value according to ASTM D-
1250:IP200, table 52 based upon the standard density figure for C6+ obtained from laboratory analysis.

The resultant totals in barrels for nC5, iC5, neoC5, and C6+ will then be summated to form the C5+ total in
barrels at 60 F.

The C5+ total will be formed on a cumulative, hourly, daily and weekly basis and added to the current, hourly,
daily and weekly reports.
Note that two daily totals will be formed to fit in with the two base times on the system, one total 06:00 to 06:00
and the second total 24:00 to 24:00.






The following data is to be passed to the supervisory for display purposes.

Component Mass (kg) Liquid Density
(Kg/m
3
)
Liquid Volume
(Sm
3
)
Conversion
factor m
3
at 15
C bbl at 60 F
Liquid Volume
(bbl)
nc5
ic5
neoC5
C6+
C5+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 82 of 395 Issue 7

9.J.J2 Gas Composition Measurement

The gas composition data is measured by the chromatograph and transferred to the export gas stream computer
from the supervisory. The supervisory computer then allows enhancement of the lumped C6+ component for
individual fractions up to C10. Additional gas components can also be added and in this event the analysis is re-
normalised to 100%.
In the event of failure of the communications link to the supervisory computer, the gas export stream polls data
directly from the chromatograph for use. A set of default gas compositions is also stored in the export gas
streams and in the event of failure of the chromatograph the default data will automatically be selected for use
in the AGA 8 calculations.





























The following components are available for composition entry:
Nitrogen - N
2
n - Pentane - nC5
Carbon Dioxide - CO
2
i - Pentane - iC5
Hydrogen Sulphide - H
2
S NeoPentane - NeoC5 *
Water - H
2
O Hexane - C6
Helium - He Heptane - C7
Methane - C1 Octane - C8
Ethane - C2 Nonane - C9
Propane - C3 Decane - C10
n - Butane - nC4 Oxygen - O
2

i - Butane - iC4 Carbon Monoxide - CO
Argon - Ar Hydrogen - H
2

* NeoPentane value is added to i - Pentane value for the purposes of AGA8 calculation.
Note: If the sum of all the components mol% (Component Total) is outside the operator entered limits (default
values 99.9% - 100.1%), the new data will be rejected and a component error alarm raised.
Supervisory
Download
Supervisory /
Stream
Composition
Stream composition
Manual switch
Direct
Chromatograph
Link
Chromat Data
In Use Gas Composition
Auto switch after 15 mins lost
supervisory comms
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 83 of 395 Issue 7
9.J.J3 Alarms & Lvents
The following alarms and events are typically raised on this input.

Alarms MOLE SELECT - K_COMP : Compontent total outside limits
Events Each Mode change of ACCEPTANCE COMMAND (IDLE to ACCEPTING)
etc

9.J.J4 Local Printing
The following printout facilities are available:
Configuration:
Constants log report on request.
A display dump is printed on request.
A print out of all possible alarms and their configured alarm group.

Reports:
Day end report is printed automatically at day end, or on request.
Current report is printed on request.

Alarms:
Automatic alarm printouts on occurrence, acceptance and clearance of alarm states.
Automatic status printouts on occurrence of a keypad value or mode change.
All current alarms on request.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 84 of 395 Issue 7

9.2 Iunctions
The functions of the gas stream flowcomputers are:-

To accept two analogue (4-20mA) signals from two DP cells representing a high differential pressure input, one
to be used as pay meter and the second to be used if the pay meter fails.

To accept two analogue (4-20mA) signals from two DP cells representing a low differential pressure input, one
to be used as pay meter and the second to be used if the pay meter fails.

To accept an analogue (4-20mA) signal from a transmitter representing static pressure upstream of the orifice.

To accept a 4 wire P.R.T. signal from a temperature transmitter representing temperature downstream of the
orifice.

To accept a frequency input signal representing density and to accept densitometer constants and hence
calculate line density and mass flowrate and totals.

To correct the measured density and measured density to upstream conditions.

To display measured and calculated quantities.

To provide a means of operator data entry and inspection.

To accept digital inputs from two inlet block valves and to interpret these signals to represent the valves status
as open, closed, moving or failed.

To accept digital inputs from two outlet block valves and to interpret these signals to represent the valves status
as open, closed, moving or failed

To accept digital inputs from each valve representing Local or Remote status.

To accept gas composition data from the duty supervisory and to use this data to perform a density calculation
according to AGA -8 1994 report and standard density and mass based calorific value calculations according to
ISO 6976 1995.

To maintain an alarm system, report alarms on the front panel display and to transfer alarm information to the
duty supervisory computer.

To provide a digital output representing computer fail.

To perform secure totalisation of mass, standard volume, and energy of the total gas flow on a cumulative basis.

To perform secure totalisation of mass, standard volume, and energy of the C1-C4 gas composition on a
cumulative basis.

To perform secure totalisation of mass, and standard volume of the C5+ gas composition on a daily and
cumulative basis.

To perform secure totalisation of C5 + in barrels using keypad entered liquid densities and conversion factors

To perform calculations to an accuracy of at least +/- 0.001%

To communicate with the supervisory computer via a UTP ethernet link, and RS 485 serial link to allow bi-
directional transfer of measured and calculated data, alarms, status and configuration.

To calculate flow weighted averages for Pressure, Temperature, Upstream Density, Base Density,
Calorific Value, Relative Density and Differential Pressure against mass total increment on a period and daily
basis.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 85 of 395 Issue 7

To switch status to on-line if isolation valves are open and DP is above low flow cut off.
To switch status to off-line if DP is below low flow cut off.

To switch to Maintenance mode if selected by operator.

To calculate gas component totals on a daily basis.

To calculate the average, maximum and minimum standard volume flowrate on a daily basis.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 86 of 395 Issue 7

9.3 Input / Output Definition


S600 Conn DPin I/O Description Stm 1 Stm 2 Stm 3
A 8 ADC 1 +ve Mtr Pressure PT 2612 PT 2622 PT 2632
A 21 ADC 2 +ve DP Low Cell (Pay) FT 2611 FT 2621 FT 2631
A 9 ADC 3 +ve DP High Cell (Pay) FT 2612 FT 2622 FT 2632
A 22 ADC 4 +ve DP High Cell (Check) FT 2613 FT 2623 FT 2633
A 10 ADC 5 +ve DP Low Cell (Check) FT 2614 FT 2624 FT 2634
A 20 ADC Ground
B 4 PRT 1 I + Mtr Temp TE 2612 TE 2622 TE 2632
B 1 PRT 1 V + Mtr Temp TE 2612 TE 2622 TE 2632
B 21 PRT 1 V - Mtr Temp TE 2612 TE 2622 TE 2632
B 24 PRT 1 I - Mtr Temp TE 2612 TE 2622 TE 2632
B 9 Density 1 +ve Density QT 2611 QT 2621 QT 2631
B 27 Density 1 -ve Density QT 2611 QT 2621 QT 2631
B 13 Dig In 1 ve Inlet V/V 1 Open MOV 2611 MOV 2621 MOV 2631
B 14 Dig In 2 ve Inlet V/V 1 Closed MOV 2611 MOV 2621 MOV 2631
B 15 Dig In 3 ve Inlet V/V 1 L/R MOV 2611 MOV 2621 MOV 2631
B 16 Dig In 4 ve
B 17 Dig In 1-4 +ve
B 18 Dig 5 ve Inlet V/V 2 Open MOV 2612 MOV 2622 MOV 2632
B 19 Dig In 6 ve Inlet V/V 2 Closed MOV 2612 MOV 2622 MOV 2632
C 19 Dig In 7 ve Inlet V/V 2 L/R MOV 2612 MOV 2622 MOV 2632
C 18 Dig 8 ve
C 17 Dig In 5-8 +ve
C 16 Dig In 9 ve Outlet V/V 1 Open MOV 2613 MOV 2623 MOV 2633
C 15 Dig In 10 ve Outlet V/V 1 Closed MOV 2613 MOV 2623 MOV 2633
C 14 Dig In 11 ve Outlet V/V 1 L/R MOV 2613 MOV 2623 MOV 2633
C 13 Dig In12 ve
C 12 DigIn 9-12 +ve
C 11 Dig In 13 ve Outlet V/V 2 Open MOV 2614 MOV 2624 MOV 2634
C 10 Dig In 14 ve Outlet V/V 2 Closed MOV 2614 MOV 2624 MOV 2634
C 9 Dig In 15 ve Outlet V/V 2 L/R MOV 2614 MOV 2624 MOV 2634
C 8 Dig In 16 ve
C 7 Dig In 13-16 +
C 36 Dig Out 1+ve Inlet V/V 1 Open Com MOV 2611 MOV 2621 MOV 2631
C 37 Dig Out 2 +ve Inlet V/V1 Close Com MOV 2611 MOV 2621 MOV 2631
C 37 Dig 3+ve Inlet V/V 2 Open Com MOV 2612 MOV 2622 MOV 2632
C 36 Dig Out 4 +ve Inlet V/V 2 Close Com MOV 2612 MOV 2622 MOV 2632
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 87 of 395 Issue 7
C 35 Dig Out 1-4 -ve Command Common
C 34 Dig Ou 5+ve Outlet V/V 1 Open Com MOV 2613 MOV 2623 MOV 2633
C 33 Dig Out 6+ve
Outlet V/V 1 Close
Comm
MOV 2613 MOV 2623 MOV 2633
C 32 Dig Out 7+ve
Outlet V/V 2 Open
Comm
MOV 2614 MOV 2624 MOV 2634
C 31 Dig Out 8 +ve
Outlet V/V 2 Close
Comm
MOV 2614 MOV 2624 MOV 2634
C 30 Dig Out 5-8 -ve Command Common

RJ 45
Network
1 Signal ground Supervisory Computer

2 DTR Supervisory Computer

3 RTS Supervisory Computer

4 Tx Data Supervisory Computer

5 Rx Data Supervisory Computer

6 CTS Supervisory Computer

7 DSR Supervisory Computer

8 DCD Supervisory Computer

RJ 45 Port 3 1 Signal ground Local Printer

4 Tx Data Local Printer

5 Rx Data Local Printer

RJ 45 Port 4 1 Signal ground Chromatograph

4 Tx Data Chromatograph

5 Rx Data Chromatograph

TB2 Port 6 5 Rx - Supervisory ComputerA

6 Rx + Supervisory ComputerA

7 Tx - Supervisory ComputerA

8 Tx + Supervisory ComputerA

TB2 Port 7 9 Rx - Supervisory ComputerB

10 Rx + Supervisory ComputerB

11 Tx - Supervisory ComputerB

12 Tx + Supervisory ComputerB

TB 1 1 24 Volt DC +ve 24 V DC Power

TB 1 2 24 Volt DC -ve 0 V DC Power

TB 1 6 N /C Contact Computer Fail Relay

TB 1 7
Common
Contact
Computer Fail Relay

TB 1 8 N/O Contact Computer Fail Relay



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 88 of 395 Issue 7

9.4 Calculations
9.4.J Abbreviations used in Calculations

Symbol Description

Viscosity in Cp
A Reynolds number term
B,C,D,E,A
1
,A
2
Coefficients
bj 1 - z for component j (except He & Co2)
C Discharge coefficient
d Orifice diameter at meter conditions, mm
D Pipe diameter at meter conditions, mm
d
u
Orifice diameter at 20C,mm
D
u
Pipe diameter at 20C, mm
E Velocity of approach factor
Eo Orifice expansion coefficient, ppm/C
E
p
Pipe expansion coefficient, ppm/C
FWV Flow weighted value
H
i
Component heating value of component j, MJ/Kg
K Mass flowrate K-factor
k Isentropic exponent
L1, L2 Upstream/downstream tapping length
M Molecular weight of gas
M
2
Downstream dam height
MF
i
Molecular fraction of component i
M
j
Mol mass of component j kg/kg-mol
MW
mix
Molecular Weight of total components
P Measured line pressure, bar a
P
base
Base pressure
P
d
Downstream pressure bar a
PL Permanent pressure loss, bar
PV Process variable
q
e
Energy flowrate GJ/h
Q
e
Energy total GJ
Q
e(C1-C4)
Energy total C1-C4 GJ
Q
e(C5+G)
Energy total C5+G GJ
q
m
Mass flowrate (t/hr)
Q
m
Mass total t
Q
m(C1-C4)
Mass total C1-C4 t
Q
m(C5+G)
Mass total C5+G t
Q
mj
Mass of component j
q
s
Standard volume flowrate, Skm3/hr
Q
s
Standard volume total Skm3
Q
s(C1-C4)
Standard volume total C1-C4 Skm3
Q
s(C5+G)
Standard volume total C5+G Skm3
Q
sj
Standard volume of component j
q
v
Gross volume flowrate m3/h
R Gas constant = 8.314510 J/molK
RD Calculated relative density of gas mixture
Rdj Ideal relative density, component j
T Temperature, C
T
babs
Base temperature absolute
Td Measured downstream temperature,C
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 89 of 395 Issue 7
Tu Calculated upstream temperature,C
W Wobbe index
Xj Composition mole fraction, component j
Z Compressibility at line conditions
Zair Compressibility of air at std. conditions (constant, 0.99958)
Z
bi
Base compressibility of component
Z
i
Component compressibility
Zmix Compressibility of gas mix from ISO6976
P Differential pressure, mbar
Q
m
Mass total increment
W Permanent pressure loss

C x E

Diameter ratio

Expansibility factor

Raw measured density, Kg/m
3

air
Base density of air, kg/m3

stdj
Base density of component jKg/m3

c
Temperature corrected density, Kg/m
3

o
Density at orifice conditions, Kg/m3

t
Pressure and temperatur corrected density, Kg/m
3




9.4.2 Base Conditions
The base conditions for temperature and pressure are 15C and 1.01325 bar a respectively.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 90 of 395 Issue 7

9.4.3 Mass Ilowrate, q
m


Mass flowrate is related to differential pressure according to the following equation:-

x P K = q
u m




The mass flowrate K-factor is represented by the following equation:-


K
3600 x 2
4
x
10
x
d
E C = K
f
5 - 2





9.4.4 Corrections for orifice and pipe expansion

Corrections for orifice and pipe expansion are given by:-

o u
E 20) (T [1 d d + =

p u
E 20) (T [1 D D + =

9.4.S Diameter ratio,

The diameter ratio is defined as:-

D
d
=


9.4.6 Lxpansibility factor,

P x
K
10
x P
) 0.35 + (0.41 - 1 =
-3
4






9.4.7 Velocity of approach factor, L
The velocity of approach factor is defined by:-


2 / 1 4
) 1 (

= E








Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 91 of 395 Issue 7

9.4.8 Reynolds' Number, R
ed

Reynolds number is calculated:-

(

x D x
10
x 4
x
3600 x
K
q
= R
6
f
m
ed



9.4.9 Discharge coefficient, C

( )
( )( )
( )
C = 0.5961 + 0.0261 - 0.
+
10
Re
0.0188 A
10
Re
+ e e A

(1 - )

M M
2 8
0.7
6
D
.5
0.
6
D
L L
4
4

216
0 000521 0 0063
0 043 0 080 0123 1 011
0031 08
3
3
10 1 7 1
2 2
11 1 3
. .
. . . .
. ' . '
. .

(
+ +

(
+




The following calculations are repeated iteratively until successive estimates of mass flow agree within the
convergence limit:
(

x D x
10
x 4
x
3600 x
K
q
=
Re
6
f
m
D


8 . 0
Re
. 19000
|
|
.
|

\
|
=
D
A



D
L L
4 . 25
'
2 1
= =


=
1
' . 2
'
2
2
L
M

( )
( )( )
( )
C = 0.5961 + 0.0261 - 0.
+
10
Re
0.0188 A
10
Re
+ e e A

(1 - )

M M
2 8
0.7
6
D
.5
0.
6
D
L L
4
4

216
0 000521 0 0063
0 043 0 080 0123 1 011
0031 08
3
3
10 1 7 1
2 2
11 1 3
. .
. . . .
. ' . '
. .

(
+ +

(
+



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 92 of 395 Issue 7
K = C E d x 10
4
2 x 3600 K
orif
2 -5
m



m u
q = K P x

9.4.J0 Upstream 1emperature, 1
u

Upstream temperature is calculated from the downstream using:-

15 . 273 } { * ) 15 . 273 (
)
1
(
+ =

k
k
d
d u
P
P
T T

9.4.JJ Downstream pressure


1000
W
P =
Pd





and
3
2
2
10 * *
) * * 1 (
) * * 1 (
P
E C
E C
W
+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 93 of 395 Issue 7

9.4.J2 Standard volume flowrate, q
s


Standard volume flowrate is given by:-

b
m
s
q
= q



9.4.J3 Lnergy Ilowrate, q
e


Energy flowrate is given by:-
CV x q = q
m e



9.4.J4 Gross Volume Ilowrate, q
v


Gross Volume flowrate is calculated by:

1000 *
o
m
v
q
q

=


9.4.JS Calorific Value, CV
calc

Calorific value is calculated by ISO6976, Rev 1995

Z
CV
=
CV
mix
ideal
calc



Where
CV
ideal
= x
j
H
j in MJ/kg

x
j
= Composite mole fraction for component j
H
j
= Superior ideal calorific value for component j from ISO 6976 table 5

9.4.J6 Cumulative Mass, Standard Volume Gross Volume & Lnergy 1otals
Cumulative totals are integrated from flowrates as follows:-

Mass = S
m
_ q
m
.dt, t

Std Vol = S
s
_ q
s
.dt, kSm
3


Energy = S
e
_ q
e
.dt, GJ

G Vol = S
v
_ q
v
.dt, m
3


Where S
m
, S
s
S
e
& S
v
are pulse significance factors which allow the totaliser units to be defined.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 94 of 395 Issue 7

9.4.J7 Measured Density
Measured density is the primary source of density for each meter tube.
Density is measured from a Solartron 7812 transducer and calculated using the transducer calibration constants.


2
2 1 0 t K t K K + + =

Where,
K0, K1, K2 = Calibration Constants
t = period time in microseconds
= measured density

The density is now corrected for temperature effects using the temperature at the densitometer

) 20 ( 19 )) 20 ( 18 1 ( + + = T K T K
t



Where,

t
= Density corrected for temperature
K18, K19 = Calibration Constants
T = Densitometer temperature
20 = Calibration temperature


The density is now corrected for user gas /calibration gas offset data

)}
273
(
4
3
1 {
+

+
+ =
o
s
c
t
t c
T
G
R
K
K



Where,

c
= Corrected density
K3, K4 = Calibration constants
R
c
= Gas SG/ratio specific heats at calibration temp
G
s
= Gas SG/ratio specific heats at standard conditions
T
o
= Temperature measured at orifice
9.4.J8 Density at Orifice
The density is corrected for orifice conditions

k
c u
p P
P
1
(
(


=






Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 95 of 395 Issue 7

9.4.J9 AGA 8 Calculated Density
Gas Density is calculated from gas composition data with compressibility determined using AGA8 (report
1994).






9.4.20 Base Density,
b

Base density is calculated using the keypad entered base density of air and the gas mixture relative density
calculated from ISO 6976.

air b
RD =

9.4.2J Mass total of Components CJ-C4
The total mass for components C1-C4 is calculated by the sum of the total mass multiplied by the component
molecular weight and the mass fraction and dividing by the total molecular weight.

j j mix
M X MW =

Where:
X
j
= Component Mol Fraction = Component Mol % x 0.01
M
j
= Component Mol Mass from ISO 6976 Table 1
m j mj
Q Mf Q =


mix
j
j
MW
M Xj
Mf

=

4
1
) 4 1 (
C
C
mj C C m
Q Q

9.4.22 Mass total of Component CS+
The mass of component C5+ is calculated by subtracting the mass for C1-C4 from the total mass


) 4 1 ( ) 5 ( C C m C m
Q Qm Q
+
=

9.4.23 Std Volume total of Components CJ-C4
The standard volume total for components C1-C4 is calculated by summing the component std volumes.

stdj
mj
sj
Q
Q

=


R x
T
x Z
P x M
=
u
t



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 96 of 395 Issue 7
and the base volume of each component is calculated by


Z R
M
j
stdj

=
15 . 288
325 . 101


Where:
Z = Component compressibility from ISO 6976 Table 2
R = Gas constant = 8.314510 J/mol K

4
1
) 4 1 (
C
C
sj C C s
Q Q


9.4.24 Std Volume total Components CS+
The std volume total for component C5+is calculated by subtracting the std volume total for C1-C4 from the
overall std volume total.


) 4 1 ( ) 5 ( C C s C s
Q Qs Q
+
=


9.4.2S Lnergy 1otal of Gas CJ-C4(GJ)
The energy total of the separated gas C1-C4 will be calculated:

j mj Ej
H Q Q =

Where:
H
j
= Component Heating Value from ISO 6976 table 4 in MJ/kg

4
1
) 4 1 (
C
C
ej C C e
Q Q



9.4.26 Lnergy 1otal of Gas CS+

The heat contents of the gas components C5 and higher shall be calculated using the following formula

) 4 1 ( ) 5 ( C C e C e
Q Qe Q
+
=




9.4.27 Lnergy of Gas (Mbtu)
The energy for C1-C4 is converted to MBtu

05512 . 1
) 4 1 (
4 1
C C e
C eMBtuC
Q
Q

=





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 97 of 395 Issue 7

and for (C5+G )

05512 . 1
) 5 (
5
+
+
=
C e
eMBtuC
Q
Q



Values for composition calculations shall be obtained from the following table.

Component Hi(MJ/kg)
6976 table 4
Molar Mass
6976 table1
Zi
6976 table 2
Nitrogen (N2) 0.0000 28.0135 0.999700
Carbon Dioxide
(CO2) 0.0000 44.01 0.994400
Hydrogen Sulphide
(H2S) 16.5000 34.082 0.990000
Water (H2O) 2.4700 18.0153 0.945000
Helium (He) 0.0000 4.0026 1.000500
Methane (C1) 55.5740 16.043 0.998000
Ethane (C2) 51.9500 30.07 0.991500
Propane (C3) 50.3700 44.097 0.982100
iso Butane (iC4) 49.3900 58.123 0.968000
normal Butane
(nC4) 49.5500 58.123 0.965000
iso Pentane (iC5) 48.9500 72.15 0.948000
normal Pentane
(nC5) 49.0400 72.15 0.937000
2,2
Dimethylpropane
(neoC5) 48.7500 72.15 0.955000
Hexane (C6) 48.7200 86.177 0.913000
Heptane (C7) 48.4700 100.204 0.866000
Octane (C8) 48.2900 114.231 0.802000
Nonane (C9) 48.1500 128.258 0.710000
Decane (C10) 48.0400 142.285 0.584000
Oxygen (O2) 0.0000 31.9988 0.999200
Carbon Monoxide
(CO) 10.1000 28.01 0.999500
Hydrogen (H) 141.9500 2.0159 1.000600


9.4.28 Ilow Weighted Averages
Flow weighted averages are calculated on a period and daily basis for:
Pressure
Temperature
Upstream Density
Base Density
Calorific Value
Relative Density
Differential Pressure

( )


=
m
m
Q
Q PV
FWV
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 98 of 395 Issue 7


9.S CS+Liquid Calculations
9.S.J Symbols table
The following table defines all the symbols used in the calculations.
9.S.2 Constants
The following constants will be hard coded in the calculations.

Component Liquid Density (kg/m
3
) Volume Correction Factor (m
3
at 15 C bbl at 60 F)
nC5 631.05 6.295
iC5 624.54 6.295
neoC5 596.7 6.296

9.S.3 Calculation of C6+mass (kg)


(C10) (C9) (C8) (C7) (C6) ) (C6
W W W W W W + + + + =
+



9.S.4 Calculation of nCS Standard Volume (Sm
3
)


Symbol Description Type Units
W
(nC5)
Mass of component nC5 kg
W
(iC5)
Mass of component iC5 kg
W
(neoC5)
Mass of component neoC5 kg
W
(C6)
Mass of component C6 kg
W
(C7)
Mass of component C7 kg
W
(C8)
Mass of component C8 kg
W
(C9)
Mass of component C9 kg
W
(C10)
Mass of component C10 kg
W
(C6+)
Mass of component C6+ kg

(nC5)
Liquid Density of Component nC5 kg/m
3

(iC5)
Liquid Density of Component iC5 kg/m
3

(neoC5)
Liquid Density of Component neoC5 kg/m
3

(C6+)
Liquid Density of Component C6+ (keypad entered) kg/m
3

VCF
(nC5)
Volume Correction Factor nC5
VCF
(iC5)
Volume Correction Factor iC5
VCF
(neoC5)
Volume Correction Factor neoC5
VCF
(C6+)
Volume Correction Factor C6+ (keypad entered)
V
(m3nC5)
Volume in Sm
3
of component nC5 Sm
3

V
(m3iC5)
Volume in Sm
3
of component iC5 Sm
3

V
(m3neoC5)
Volume in Sm
3
of component neoC5 Sm
3

V
(m3C6+)
Volume in Sm
3
of component C6+ Sm
3

V
(m3C5+)
Volume in Sm
3
of component C5+ Sm
3

V
(bblnC5)
Volume in bbl of component nC5 bbl
V
(bbliC5)
Volume in bbl of component iC5 bbl
V
(bblneoC5)
Volume in bbl of component neoC5 bbl
V
(bblC6+)
Volume in bbl of component C6+ bbl
V
(bblC5+)
Volume in bbl of component C5+ bbl

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 99 of 395 Issue 7
) 5 (
) 5 (
) 5 3 (
nC
nC
nC m
W
V

=

9.S.S Calculation of iCS Standard Volume (Sm
3
)


) 5 (
) 5 (
) 5 3 (
iC
iC
iC m
W
V

=
9.S.6 Calculation of neoCS Standard Volume (Sm
3
)


) 5 (
) 5 (
) 5 3 (
neoC
neoC
neoC m
W
V

=
9.S.7 Calculation of C6+ Standard Volume (Sm
3
)


) 6 (
) 6 (
) 6 3 (
+
+
+
=
C
C
C m
W
V



9.S.8 Calculation of CS+ Standard Volume (Sm
3
)

) 6 3 ( ) 5 3 ( ) 5 3 ( ) 5 3 ( ) 5 3 ( + +
+ + + =
C m neoC m iC m nC m C m
V V V V V


9.S.9 Calculation of nCS Standard Volume (bbl)

) 5 ( ) 5 3 ( ) 5 ln ( nC nC m C bb
VCF V V =

9.S.J0 Calculation of iCS Standard Volume (bbl)

) 5 ( ) 5 3 ( ) 5 ( iC iC m bbliC
VCF V V =




9.S.JJ Calculation of neoCS Standard Volume (bbl)

) 5 ( ) 5 3 ( ) 5 ln ( neoC neoC m eoC bb
VCF V V =
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 100 of 395 Issue 7


9.S.J2 Calculation of C6+ Standard Volume (bbl)

) 6 ( ) 6 3 ( ) 6 ln ( + + +
=
nC nC m C bb
VCF V V


9.S.J3 Calculation of CS+ Standard Volume (bbl)

) 6 ( ) 5 ln ( ) 5 ( ) 5 ln ( ) 5 ( + +
+ + + =
bblC eoC bb bbliC C bb bblC
V V V V V











Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 101 of 395 Issue 7

9.6 Displays
The following is representative of the data that will be available as a minimum on the front panel of the flow
computer.
The actual displays will be included when configuration of the computers is completed

Display Item Parameters Units
Mass Total Cumulative, daily tonne
Mass Flowrate t/h
Std Vol Total Cumulative, daily Sm
3

Std Vol Flowrate Sm
3
/h
Energy Total Cumulative, daily MJ, MBTU
Energy Flowrate MJ/h
Mass Total C1-C4 Cumulative, daily tonne
Std Vol Total C1-C4 Cumulative, daily Sm3
Energy Total C1-C4 Cumulative, daily MJ, MBTU
Mass Total C5+ Cumulative, daily tonne
Std Vol Total C5+ Cumulative, daily Sm3
Std Vol Total C5+ Cumulative, daily bbl
Low Differential Pressure Measured, keypad mBar
High Differential Pressure Pay Cell measured mBar
High Differential Pressure Check Cell measured mBar
Differential Pressure In use, discrepancy, sw up, sw down mBar
Stream Temperature Downstream
o
C
Stream Temperature Upstream
o
C

Stream Pressure Upstream barg
Pipe Diameter Reference Conditions mm
Pipe Diameter Operating Conditions mm
Orifice Diameter Reference Conditions mm
Orifice Diameter Operating Conditions mm
Beta Operating Conditions
Viscosity Keypad entered Cp
Isentropic Exponent Keypad entered
Discharge Coefficient Calculated
Reynolds Number Calculated
Expansibility Calculated
Velocity of approach coef Calculated
Compressibility In-use, calc (AGA 8) and keypad
Density In-use, measured, calc (AGA 8) and keypad kg/ m
3

Standard Density Air Keypad kg/ m
3

Calorific Value In-use, calc (ISO 6976) and keypad MJ/ kg
AGA 8 Variables, constants and results
Gas Compositional Data mol %

Meter Status On-line, Off-line, Maintenance, Illegal,
Unhealthy

Time hh:mm
Date dd/mm/yyyy
Maint Mode Entry/Exit
Security various
Diagnostics various
Software Version various


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 102 of 395 Issue 7

9.7 Alarms
The alarms below are raised by the gas export flow computers.

S600 SYS HOST COLD ST Grp 1
S600 SYS HOST WARM ST Grp 1
S600 SYS HOST BATT FAIL Grp 1
S600 SYS HOST TOT RES Grp 1
S600 SYS HOST TOT PART Grp 1
S600 SLAVE LINK MONITOR Grp 4
S600 PRINTER MONITOR Grp 4
S600 BKGND TASK MONITOR Grp 4
S600 BKGND TASK TSK ERR Grp 4
S600 DIO SCAN TASK MONITOR Grp 4
S600 DIO SCAN TASK TSK ERR Grp 4
S600 DISPLAY TASK MONITOR Grp 4
S600 DISPLAY TASK TSK ERR Grp 4
S600 IO COMMS TASK MONITOR Grp 4
S600 IO COMMS TASK FAIL IO1 Grp 4
S600 IO COMMS TASK FAIL IO2 Grp 4
S600 IO COMMS TASK FAIL IO3 Grp 4
S600 IO COMMS TASK FAIL IO4 Grp 4
S600 IO COMMS TASK FAIL IO5 Grp 4
S600 IO COMMS TASK FAIL IO6 Grp 4
S600 IO COMMS TASK FAIL IO7 Grp 4
S600 IO COMMS TASK TSK ERR Grp 4
S600 IO SCAN TASK MONITOR Grp 4
S600 IO SCAN TASK TSK ERR Grp 4
S600 REPORTS TASK MONITOR Grp 4
S600 REPORTS TASK TSK ERR Grp 4
S600 TOTALS TASK MONITOR Grp 4
S600 TOTALS TASK TSK ERR Grp 4
S600 GAS COMPRESS TASK MONITOR Grp 4
S600 GAS COMPRESS TASK TSK ERR Grp 4
S600 GAS CV TASK MONITOR Grp 4
S600 GAS CV TASK TSK ERR Grp 4
S600 GAS CORRECT TASK MONITOR Grp 4
S600 GAS CORRECT TASK TSK ERR Grp 4
S600 GAS DP COND TASK MONITOR Grp 4
S600 GAS DP COND TASK TSK ERR Grp 4
S600 GAS DP INC TASK MONITOR Grp 4
S600 GAS DP INC TASK TSK ERR Grp 4
S600 GAS DP FLOW TASK MONITOR Grp 4
S600 GAS DP FLOW TASK TSK ERR Grp 4
S600 GAS CHROMAT TASK MONITOR Grp 4
S600 GAS CHROMAT TASK TSK ERR Grp 4
S600 GAS DENS COPY TASK MONITOR Grp 4
S600 GAS DENS COPY TASK TSK ERR Grp 4
S600 DENSITY TASK MONITOR Grp 4
S600 DENSITY TASK TSK ERR Grp 4
S600 STR STATUS TASK MONITOR Grp 4
S600 STR STATUS TASK TSK ERR Grp 4
S600 FWA CALC TASK CONF ERR Grp 4
S600 FWA CALC TASK ZERO DIV Grp 4
S600 FWA CALC TASK TSK OFLOW Grp 4
S600 FWA CALC TASK MONITOR Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 103 of 395 Issue 7
S600 FWA CALC TASK CALC FAIL Grp 4
S600 FWA CALC TASK TSK ERR Grp 4
S600 BVM TASK MONITOR Grp 4
S600 BVM TASK TSK ERR Grp 4
S600 DISCREP TASK MONITOR Grp 4
S600 DISCREP TASK TSK ERR Grp 4
S600 CALC TASK MONITOR Grp 4
S600 CALC TASK TSK ERR Grp 4
S600 ALM SUPPRESS TASK MONITOR Grp 4
S600 ALM SUPPRESS TASK TSK ERR Grp 4
S600 AGA8FULL TASK MONITOR Grp 4
S600 AGA8FULL TASK TSK ERR Grp 4
S600 CALIB TASK MONITOR Grp 4
S600 CALIB TASK TSK ERR Grp 4
S600 LOGICALC TASK MONITOR Grp 4
S600 LOGICALC TASK TSK ERR Grp 4
S600 FAULT TASK MONITOR Grp 4
S600 FAULT TASK TSK ERR Grp 4
S600 FLOWTIME TASK MONITOR Grp 4
S600 FLOWTIME TASK TSK ERR Grp 4
S600 SGERG TASK MONITOR Grp 4
S600 SGERG TASK TSK ERR Grp 4
S600 ADC 01 UP PRESS L Grp 2
S600 ADC 01 UP PRESS H Grp 2
S600 ADC 01 UP PRESS DEV ERR Grp 3
S600 ADC 02 LO DP PAY DEV ERR Grp 3
S600 ADC 03 HI DP PAY DEV ERR Grp 3
S600 ADC 04 HI DP CHK DEV ERR Grp 3
S600 ADC 05 LO DP CHK DEV ERR Grp 3
S600 PRT 01 DN TMP L Grp 2
S600 PRT 01 DN TMP H Grp 2
S600 PRT 01 DN TMP DEV ERR Grp 3
S600 STATUS RAM FAIL Grp 4
S600 STATUS ROM FAIL Grp 4
S600 STATUS PIC FAIL Grp 4
S600 STATUS TPU FAIL Grp 4
S600 STATUS EEPROM FAIL Grp 4
S600 STATUS TASK ERR Grp 4
S600 STATUS CONF ERR Grp 4
S600 STATUS TASK FAIL Grp 4
S600 STATUS WARM ST Grp 4
S600 STATUS DEV ERR Grp 4
S600 STR01 DP STACK CALC CONF ERR Grp 4
S600 STR01 DP STACK CALC I/P ERR Grp 4
S600 STR01 DP STACK CALC O/P ERR Grp 4
S600 STR01 DP STACK CALC CALC FAIL Grp 4
S600 STR01 DP STACK CALC NO PERMIT Grp 4
S600 STR01 DOWN/UP CALC CONF ERR Grp 4
S600 STR01 DOWN/UP CALC I/P ERR Grp 4
S600 STR01 DOWN/UP CALC O/P ERR Grp 4
S600 STR01 DOWN/UP CALC CALC FAIL Grp 4
S600 STR01 DOWN/UP CALC NO PERMIT Grp 4
S600 STR01 GAS INC CALC CONF ERR Grp 4
S600 STR01 GAS INC CALC I/P ERR Grp 4
S600 STR01 GAS INC CALC O/P ERR Grp 4
S600 STR01 GAS INC CALC CALC FAIL Grp 4
S600 STR01 GAS INC CALC NO PERMIT Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 104 of 395 Issue 7
S600 STR01 PIPE COR CALC CONF ERR Grp 4
S600 STR01 PIPE COR CALC I/P ERR Grp 4
S600 STR01 PIPE COR CALC O/P ERR Grp 4
S600 STR01 PIPE COR CALC CALC FAIL Grp 4
S600 STR01 PIPE COR CALC NO PERMIT Grp 4
S600 STR01 STATUS CALC CONF ERR Grp 4
S600 STR01 STATUS CALC I/P ERR Grp 4
S600 STR01 STATUS CALC O/P ERR Grp 4
S600 STR01 STATUS CALC CALC FAIL Grp 4
S600 STR01 STATUS CALC NO PERMIT Grp 4
S600 STR01 LFC CALC CONF ERR Grp 4
S600 STR01 LFC CALC I/P ERR Grp 4
S600 STR01 LFC CALC O/P ERR Grp 4
S600 STR01 LFC CALC CALC FAIL Grp 4
S600 STR01 LFC CALC NO PERMIT Grp 4
S600 STR01 MAINT CALC CONF ERR Grp 4
S600 STR01 MAINT CALC I/P ERR Grp 4
S600 STR01 MAINT CALC O/P ERR Grp 4
S600 STR01 MAINT CALC CALC FAIL Grp 4
S600 STR01 MAINT CALC NO PERMIT Grp 4
S600 STR01 CHROM.P CALC CONF ERR Grp 4
S600 STR01 CHROM.P CALC I/P ERR Grp 4
S600 STR01 CHROM.P CALC O/P ERR Grp 4
S600 STR01 CHROM.P CALC CALC FAIL Grp 4
S600 STR01 CHROM.P CALC NO PERMIT Grp 4
S600 STR01 CHROM.S CALC CONF ERR Grp 4
S600 STR01 CHROM.S CALC I/P ERR Grp 4
S600 STR01 CHROM.S CALC O/P ERR Grp 4
S600 STR01 CHROM.S CALC CALC FAIL Grp 4
S600 STR01 CHROM.S CALC NO PERMIT Grp 4
S600 STR01 CHROM.T CALC CONF ERR Grp 4
S600 STR01 CHROM.T CALC I/P ERR Grp 4
S600 STR01 CHROM.T CALC O/P ERR Grp 4
S600 STR01 CHROM.T CALC CALC FAIL Grp 4
S600 STR01 CHROM.T CALC NO PERMIT Grp 4
S600 STR01 I/L VLV CALC CONF ERR Grp 4
S600 STR01 I/L VLV CALC I/P ERR Grp 4
S600 STR01 I/L VLV CALC O/P ERR Grp 4
S600 STR01 I/L VLV CALC CALC FAIL Grp 4
S600 STR01 I/L VLV CALC NO PERMIT Grp 4
S600 STR01 O/L VLV CALC CONF ERR Grp 4
S600 STR01 O/L VLV CALC I/P ERR Grp 4
S600 STR01 O/L VLV CALC O/P ERR Grp 4
S600 STR01 O/L VLV CALC CALC FAIL Grp 4
S600 STR01 O/L VLV CALC NO PERMIT Grp 4
S600 STR01 AGA8 CALC CONF ERR Grp 4
S600 STR01 AGA8 CALC I/P ERR Grp 4
S600 STR01 AGA8 CALC O/P ERR Grp 4
S600 STR01 AGA8 CALC CALC FAIL Grp 4
S600 STR01 AGA8 CALC NO PERMIT Grp 4
S600 STR01 ISO5167 CALC CONF ERR Grp 4
S600 STR01 ISO5167 CALC I/P ERR Grp 4
S600 STR01 ISO5167 CALC O/P ERR Grp 4
S600 STR01 ISO5167 CALC CALC FAIL Grp 4
S600 STR01 ISO5167 CALC NO PERMIT Grp 4
S600 STR01 ISO6976 CALC CONF ERR Grp 4
S600 STR01 ISO6976 CALC I/P ERR Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 105 of 395 Issue 7
S600 STR01 ISO6976 CALC O/P ERR Grp 4
S600 STR01 ISO6976 CALC CALC FAIL Grp 4
S600 STR01 ISO6976 CALC NO PERMIT Grp 4
S600 STR01 DENSITY CALC CONF ERR Grp 4
S600 STR01 DENSITY CALC I/P ERR Grp 4
S600 STR01 DENSITY CALC O/P ERR Grp 4
S600 STR01 DENSITY CALC CALC FAIL Grp 4
S600 STR01 DENSITY CALC NO PERMIT Grp 4
S600 STR01 TFWA CALC CONF ERR Grp 4
S600 STR01 TFWA CALC I/P ERR Grp 4
S600 STR01 TFWA CALC O/P ERR Grp 4
S600 STR01 TFWA CALC CALC FAIL Grp 4
S600 STR01 MASS FR L [SUPP]Grp 2
S600 STR01 MASS FR H [SUPP]Grp 2
S600 STR01 STD DENS L Grp 2
S600 STR01 STD DENS H Grp 2
S600 STR01 DWNSTR DENS FAIL A Grp 2
S600 STR01 REAL CV L Grp 2
S600 STR01 REAL CV H Grp 2
S600 STR01 INLET VLV 1 ILLEGAL Grp 2
S600 STR01 INLET VLV 1 MOVE FAIL Grp 2
S600 STR01 INLET VLV 1 MOVE UNCM Grp 2
S600 STR01 OUTLET VLV 1 ILLEGAL Grp 2
S600 STR01 OUTLET VLV 1 MOVE FAIL Grp 2
S600 STR01 OUTLET VLV 1 MOVE UNCM Grp 2
S600 STR01 MOLE SELECT K_COMP Grp 4
S600 STR01 MOLE SELECT ADDNLS Grp 4
S600 STR01 MOLE SELECT SPLITS Grp 4
S600 STR01 MOLE SELECT DL COMP Grp 4
S600 STR01 MOLE SELECT USER COMP Grp 4
S600 STR01 CHROM TELEM RX FAIL Grp 2
S600 STR01 CHROM TELEM CONFIG Grp 4
S600 STR01 CHROM TELEM CRITICAL Grp 4
S600 STR01 CHROM TELEM NCRITICAL Grp 4
S600 STR01 CHROM TELEM MOLE LO Grp 4
S600 STR01 CHROM TELEM MOLE HI Grp 4
S600 STR01 CHROM TELEM MOLE DV Grp 4
S600 STR01 CHROM TELEM REP TOUT Grp 4
S600 STR01 DP CELL L [SUPP]Grp 2
S600 STR01 DP CELL H [SUPP]Grp 2
S600 STR01 DP CELL DISCREP [SUPP]Grp 2
S600 STR01 I/L VLV CALC 2 CONF ERR Grp 4
S600 STR01 I/L VLV CALC 2 I/P ERR Grp 4
S600 STR01 I/L VLV CALC 2 O/P ERR Grp 4
S600 STR01 I/L VLV CALC 2 CALC FAIL Grp 4
S600 STR01 O/L VLV CALC 2 CONF ERR Grp 4
S600 STR01 O/L VLV CALC 2 I/P ERR Grp 4
S600 STR01 O/L VLV CALC 2 O/P ERR Grp 4
S600 STR01 O/L VLV CALC 2 CALC FAIL Grp 4
S600 STR01 INLET VLV 2 ILLEGAL Grp 2
S600 STR01 INLET VLV 2 MOVE FAIL Grp 2
S600 STR01 INLET VLV 2 MOVE UNCM Grp 2
S600 STR01 OUTLET VLV 2 ILLEGAL Grp 2
S600 STR01 OUTLET VLV 2 MOVE FAIL Grp 2
S600 STR01 OUTLET VLV 2 MOVE UNCM Grp 2
S600 STR01 DP LO CHK DISCREPANCY Grp 2
S600 STR01 DP HI CHK DISCREPANCY Grp 2
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 106 of 395 Issue 7
S600 STR01 DENSITY DISCREPANCY Grp 2
S600 STR01 LOW FLOW ALARM Grp 2
S600 STR01 ILLEGAL FLOW Grp 2
S600 STR01 DENSITY INUSE L Grp 2
S600 STR01 DENSITY INUSE H Grp 2


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 107 of 395 Issue 7
J0 BACK-UP GAS ILOWCOMPU1LR
A single S600 flowcomputer will be supplied as a back up gas computer for the three gas export streams. The
flowcomputer will be configured as a multi stream device receiving signals from the back-up flow transmitter,
back up pressure transmitter and back up temperature transmitter on each meter run.
Flowing gas density will be calculated using AGA8 from gas chromatograph composition.

J0.J General Ieatures
See Section 9.1Gas Export flowcomputer


J0.J.J Local Printing
The following printout facilities are available:
Configuration:
Constants log report on request.
A display dump is printed on request.
A print out of all possible alarms and their configured alarm group.

Reports:
Day end report is printed automatically at day end, or on request.
Current report is printed on request.

Alarms:
Automatic alarm printouts on occurrence, acceptance and clearance of alarm states.
Automatic status printouts on occurrence of a keypad value or mode change.
All current alarms on request.

J0.2 Iunctions
See Section 9.2 Gas Export flowcomputer
J0.3 Input / Output Definition
The following inputs and outputs will be configured for the back-up computer.

S600 Conn DPin I/O Description Tag No
A 8 ADC 1 +ve Stm 1 Mtr Pressure PT 2615
A 21 ADC 2 +ve Stm 1High DP FT 2615
A 9 ADC 3 +ve Stm 2 Mtr Pressure PT 2625
A 22 ADC 4 +ve Stm 2 High DP FT 2625
A 10 ADC 5 +ve Stm 3 Mtr Pressure PT 2635
A 11 ADC 6 +ve Stm 3High DP FT 2635
B 4 PRT 1 I + Stm 1 Mtr Temp TE 2615
B 1 PRT 1 V + Stm 1Mtr Temp TE 2615
B 21 PRT 1 V - Stm 1Mtr Temp TE 2615
B 24 PRT 1 I - Stm 1Mtr Temp TE 2615
B 5 PRT 2 I + Stm 2 Mtr Temp TE 2625
B 2 PRT 2 V + Stm 2 Mtr Temp TE 2625
B 22 PRT 2 V - Stm 2 Mtr Temp TE 2625
B 25 PRT 2 I - Stm 2 Mtr Temp TE 2625
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 108 of 395 Issue 7
B 6 PRT 3 I + Stm 3 Mtr Temp TE 2635
B 3 PRT 3 V + Stm 3 Mtr Temp TE 2635
B 23 PRT 3 V - Stm 3 Mtr Temp TE 2635
B 26 PRT 3 I - Stm 3 Mtr Temp TE 2635
RJ 45
Network
1 Signal ground Supervisory Computer
2 DTR Supervisory Computer
3 RTS Supervisory Computer
4 Tx Data Supervisory Computer
5 Rx Data Supervisory Computer
6 CTS Supervisory Computer
7 DSR Supervisory Computer
8 DCD Supervisory Computer
RJ 45 Port 3 1 Signal ground Local Printer
4 Tx Data Local Printer
5 Rx Data Local Printer
TB2 Port 6 5 Rx - Supervisory ComputerA
6 Rx + Supervisory ComputerA
7 Tx - Supervisory ComputerA
8 Tx + Supervisory ComputerA
TB2 Port 7 9 Rx - Supervisory ComputerB
10 Rx + Supervisory ComputerB
11 Tx - Supervisory ComputerB
12 Tx + Supervisory ComputerB
TB 1 1 24 Volt DC +ve 24 V DC Power
TB 1 2 24 Volt DC -ve 0 V DC Power
TB 1 6 N /C Contact Computer Fail Relay
TB 1 7
Common
Contact
Computer Fail Relay
TB 1 8 N/O Contact Computer Fail Relay



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 109 of 395 Issue 7

J0.4 Calculations
The major calculations performed by the back up gas computer are mass flowrate according to ISO 5167, and
AGA 8 density calculations. These are performed for each stream. Standard volume and energy calculations are
also performed for each stream.
For details of calculations, see section 9.4 gas export flowcomputer and calculation flowchart appended.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 110 of 395 Issue 7

J0.S Displays
The following is representative of the data that will be available as a minimum on the front panel of the flow
computer.
The actual displays will be included when configuration of the computers is completed

Display Item Parameters Units
Stream 1 Mass Total Cumulative, daily tonne
Stream 1 Mass Flowrate t/h
Stream 1 Std Vol Total Cumulative, daily Sm
3

Stream 1 Std Vol Flowrate Sm
3
/h
Stream 1 Energy Total Cumulative, daily MJ, MBTU
Stream 1 Energy Flowrate MJ/h
Stream 1 Mass Total C1-C4 Cumulative, daily tonne
Stream 1Std Vol Total C1-C4 Cumulative, daily Sm3
Stream 1Energy Total C1-C4 Cumulative, daily MJ, MBTU
Stream 1 Mass Total C5+ Cumulative, daily tonne
Stream 1 Std Vol Total C5+ Cumulative, daily Sm3
Stream 1 Std Vol Total C5+ Cumulative, daily bbl
Stream 2 Mass Total Cumulative, daily tonne
Stream 2 Mass Flowrate t/h
Stream 2 Std Vol Total Cumulative, daily Sm
3

Stream 2 Std Vol Flowrate Sm
3
/h
Stream 2 Energy Total Cumulative, daily MJ
Stream 2 Energy Flowrate MJ/h
Stream 2 Mass Total C1-C4 Cumulative, daily tonne
Stream 2Std Vol Total C1-C4 Cumulative, daily Sm3
Stream 2Energy Total C1-C4 Cumulative, daily MJ
Stream 2 Mass Total C5+ Cumulative, daily tonne
Stream 2 Std Vol Total C5+ Cumulative, daily Sm3
Stream 2 Std Vol Total C5+ Cumulative, daily bbl
Stream 3 Mass Total Cumulative, daily tonne
Stream 3 Mass Flowrate t/h
Stream 3 Std Vol Total Cumulative, daily Sm
3

Stream 3 Std Vol Flowrate Sm
3
/h
Stream 3 Energy Total Cumulative, daily MJ
Stream 3 Energy Flowrate MJ/h
Stream 3 Mass Total C1-C4 Cumulative, daily tonne
Stream 3Std Vol Total C1-C4 Cumulative, daily Sm3
Stream 3Energy Total C1-C4 Cumulative, daily MJ
Stream 3 Mass Total C5+ Cumulative, daily tonne
Stream 3 Std Vol Total C5+ Cumulative, daily Sm3
Stream 3 Std Vol Total C5+ Cumulative, daily bbl
Differential Pressure Streams 1,2,3 Measured, keypad mBar
Differential Pressure Streams 1,2,3 In use, mBar
Stream Temperature Streams 1,2,3 Downstream
o
C
Stream Temperature Streams 1,2,3 Upstream
o
C

Stream Pressure Streams 1,2,3 Upstream barg
Pipe Diameter Streams 1,2,3 Reference Conditions mm
Pipe Diameter Streams 1,2,3 Operating Conditions mm
Orifice Diameter Streams 1,2,3 Reference Conditions mm
Orifice Diameter Streams 1,2,3 Operating Conditions mm
Beta Streams 1,2,3 Operating Conditions
Viscosity Streams 1,2,3 Keypad entered Cp
Isentropic Exponent Streams 1,2,3 Keypad entered
Discharge Coefficient Streams 1,2,3 Calculated
Reynolds Number Streams 1,2,3 Calculated
Expansibility Streams 1,2,3 Calculated
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 111 of 395 Issue 7
Velocity of approach coef Streams 1,2,3 Calculated
Compressibility Streams 1,2,3 In-use, calc (AGA 8) and keypad
Density Streams 1,2,3 In-use, calc (AGA 8) and keypad kg/ m
3

Standard Density Air Keypad kg/ m
3

Calorific Value Streams 1,2,3 In-use, calc (ISO 6976) and
keypad
MJ/ m
3

AGA 8 Streams 1,2,3 Variables, constants and results
Gas Compositional Data mol %

Meter Status Streams 1,2,3 On-line, Off-line, Maintenance,
Illegal, Unhealthy

Time hh:mm
Date dd/mm/yyyy
Maint Mode Streams 1,2,3 Entry/Exit
Security various
Diagnostics various
Software Version various

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 112 of 395 Issue 7


J0.6 Alarms
The Back up gas flowcomputer will raise the following alarms.
S600 SYS HOST COLD ST Grp 1
S600 SYS HOST WARM ST Grp 1
S600 SYS HOST BATT FAIL Grp 1
S600 SYS HOST TOT RES Grp 1
S600 SYS HOST TOT PART Grp 1
S600 SLAVE LINK MONITOR Grp 4
S600 BKGND TASK MONITOR Grp 4
S600 BKGND TASK TSK ERR Grp 4
S600 DIO SCAN TASK MONITOR Grp 4
S600 DIO SCAN TASK TSK ERR Grp 4
S600 DISPLAY TASK MONITOR Grp 4
S600 DISPLAY TASK TSK ERR Grp 4
S600 IO COMMS TASK MONITOR Grp 4
S600 IO COMMS TASK FAIL IO1 Grp 4
S600 IO COMMS TASK FAIL IO2 Grp 4
S600 IO COMMS TASK FAIL IO3 Grp 4
S600 IO COMMS TASK FAIL IO4 Grp 4
S600 IO COMMS TASK FAIL IO5 Grp 4
S600 IO COMMS TASK FAIL IO6 Grp 4
S600 IO COMMS TASK FAIL IO7 Grp 4
S600 IO COMMS TASK TSK ERR Grp 4
S600 IO SCAN TASK MONITOR Grp 4
S600 IO SCAN TASK TSK ERR Grp 4
S600 REPORTS TASK MONITOR Grp 4
S600 REPORTS TASK TSK ERR Grp 4
S600 TOTALS TASK MONITOR Grp 4
S600 TOTALS TASK TSK ERR Grp 4
S600 GAS COMPRESS TASK MONITOR Grp 4
S600 GAS COMPRESS TASK TSK ERR Grp 4
S600 GAS CV TASK MONITOR Grp 4
S600 GAS CV TASK TSK ERR Grp 4
S600 GAS CORRECT TASK MONITOR Grp 4
S600 GAS CORRECT TASK TSK ERR Grp 4
S600 GAS DP COND TASK MONITOR Grp 4
S600 GAS DP COND TASK TSK ERR Grp 4
S600 GAS DP INC TASK MONITOR Grp 4
S600 GAS DP INC TASK TSK ERR Grp 4
S600 GAS DP FLOW TASK MONITOR Grp 4
S600 GAS DP FLOW TASK TSK ERR Grp 4
S600 GAS CHROMAT TASK MONITOR Grp 4
S600 GAS CHROMAT TASK TSK ERR Grp 4
S600 GAS DENS COPY TASK MONITOR Grp 4
S600 GAS DENS COPY TASK TSK ERR Grp 4
S600 DENSITY TASK MONITOR Grp 4
S600 DENSITY TASK TSK ERR Grp 4
S600 STR STATUS TASK MONITOR Grp 4
S600 STR STATUS TASK TSK ERR Grp 4
S600 DISCREP TASK MONITOR Grp 4
S600 DISCREP TASK TSK ERR Grp 4
S600 CALC TASK MONITOR Grp 4
S600 CALC TASK TSK ERR Grp 4
S600 PID CTL TASK MONITOR Grp 4
S600 PID CTL TASK TSK ERR Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 113 of 395 Issue 7
S600 ALM SUPPRESS TASK MONITOR Grp 4
S600 ALM SUPPRESS TASK TSK ERR Grp 4
S600 AGA8FULL TASK MONITOR Grp 4
S600 AGA8FULL TASK TSK ERR Grp 4
S600 CALIB TASK MONITOR Grp 4
S600 CALIB TASK TSK ERR Grp 4
S600 LOGICALC TASK MONITOR Grp 4
S600 LOGICALC TASK TSK ERR Grp 4
S600 FAULT TASK MONITOR Grp 4
S600 FAULT TASK TSK ERR Grp 4
S600 FLOWTIME TASK MONITOR Grp 4
S600 FLOWTIME TASK TSK ERR Grp 4
S600 SGERG TASK MONITOR Grp 4
S600 SGERG TASK TSK ERR Grp 4
S600 ADC 01 STR01 PRS L Grp 2
S600 ADC 01 STR01 PRS H Grp 2
S600 ADC 01 STR01 PRS DEV ERR Grp 3
S600 ADC 02 STR01 DP DEV ERR Grp 3
S600 ADC 03 STR02 PRS L Grp 2
S600 ADC 03 STR02 PRS H Grp 2
S600 ADC 03 STR02 PRS DEV ERR Grp 3
S600 ADC 02 STR02 DP DEV ERR Grp 3
S600 ADC 05 STR03 PRS L Grp 2
S600 ADC 05 STR03 PRS H Grp 2
S600 ADC 05 STR03 PRS DEV ERR Grp 3
S600 ADC 02 STR03 DP DEV ERR Grp 3
S600 PRT 01 STR01 TMP L Grp 2
S600 PRT 01 STR01 TMP H Grp 2
S600 PRT 01 STR01 TMP DEV ERR Grp 3
S600 PRT 02 STR02 TMP L Grp 2
S600 PRT 02 STR02 TMP H Grp 2
S600 PRT 02 STR02 TMP DEV ERR Grp 3
S600 PRT 03 STR03 TMP L Grp 2
S600 PRT 03 STR03 TMP H Grp 2
S600 PRT 03 STR03 TMP DEV ERR Grp 3
S600 STATUS RAM FAIL Grp 4
S600 STATUS ROM FAIL Grp 4
S600 STATUS PIC FAIL Grp 4
S600 STATUS TPU FAIL Grp 4
S600 STATUS EEPROM FAIL Grp 4
S600 STATUS TASK ERR Grp 4
S600 STATUS CONF ERR Grp 4
S600 STATUS TASK FAIL Grp 4
S600 STATUS WARM ST Grp 4
S600 STATUS DEV ERR Grp 4
S600 STR01 DP STACK CALC CONF ERR Grp 4
S600 STR01 DP STACK CALC I/P ERR Grp 4
S600 STR01 DP STACK CALC O/P ERR Grp 4
S600 STR01 DP STACK CALC CALC FAIL Grp 4
S600 STR01 DP STACK CALC NO PERMIT Grp 4
S600 STR01 DOWN/UP CALC CONF ERR Grp 4
S600 STR01 DOWN/UP CALC I/P ERR Grp 4
S600 STR01 DOWN/UP CALC O/P ERR Grp 4
S600 STR01 DOWN/UP CALC CALC FAIL Grp 4
S600 STR01 DOWN/UP CALC NO PERMIT Grp 4
S600 STR01 GAS INC CALC CONF ERR Grp 4
S600 STR01 GAS INC CALC I/P ERR Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 114 of 395 Issue 7
S600 STR01 GAS INC CALC O/P ERR Grp 4
S600 STR01 GAS INC CALC CALC FAIL Grp 4
S600 STR01 GAS INC CALC NO PERMIT Grp 4
S600 STR01 PIPE COR CALC CONF ERR Grp 4
S600 STR01 PIPE COR CALC I/P ERR Grp 4
S600 STR01 PIPE COR CALC O/P ERR Grp 4
S600 STR01 PIPE COR CALC CALC FAIL Grp 4
S600 STR01 PIPE COR CALC NO PERMIT Grp 4
S600 STR01 STATUS CALC CONF ERR Grp 4
S600 STR01 STATUS CALC I/P ERR Grp 4
S600 STR01 STATUS CALC O/P ERR Grp 4
S600 STR01 STATUS CALC CALC FAIL Grp 4
S600 STR01 STATUS CALC NO PERMIT Grp 4
S600 STR01 LFC CALC CONF ERR Grp 4
S600 STR01 LFC CALC I/P ERR Grp 4
S600 STR01 LFC CALC O/P ERR Grp 4
S600 STR01 LFC CALC CALC FAIL Grp 4
S600 STR01 LFC CALC NO PERMIT Grp 4
S600 STR01 MAINT CALC CONF ERR Grp 4
S600 STR01 MAINT CALC I/P ERR Grp 4
S600 STR01 MAINT CALC O/P ERR Grp 4
S600 STR01 MAINT CALC CALC FAIL Grp 4
S600 STR01 MAINT CALC NO PERMIT Grp 4
S600 STR01 CHROM.P CALC CONF ERR Grp 4
S600 STR01 CHROM.P CALC I/P ERR Grp 4
S600 STR01 CHROM.P CALC O/P ERR Grp 4
S600 STR01 CHROM.P CALC CALC FAIL Grp 4
S600 STR01 CHROM.P CALC NO PERMIT Grp 4
S600 STR01 CHROM.S CALC CONF ERR Grp 4
S600 STR01 CHROM.S CALC I/P ERR Grp 4
S600 STR01 CHROM.S CALC O/P ERR Grp 4
S600 STR01 CHROM.S CALC CALC FAIL Grp 4
S600 STR01 CHROM.S CALC NO PERMIT Grp 4
S600 STR01 CHROM.T CALC CONF ERR Grp 4
S600 STR01 CHROM.T CALC I/P ERR Grp 4
S600 STR01 CHROM.T CALC O/P ERR Grp 4
S600 STR01 CHROM.T CALC CALC FAIL Grp 4
S600 STR01 CHROM.T CALC NO PERMIT Grp 4
S600 STR01 AGA8 CALC CONF ERR Grp 4
S600 STR01 AGA8 CALC I/P ERR Grp 4
S600 STR01 AGA8 CALC O/P ERR Grp 4
S600 STR01 AGA8 CALC CALC FAIL Grp 4
S600 STR01 AGA8 CALC NO PERMIT Grp 4
S600 STR01 ISO5167 CALC CONF ERR Grp 4
S600 STR01 ISO5167 CALC I/P ERR Grp 4
S600 STR01 ISO5167 CALC O/P ERR Grp 4
S600 STR01 ISO5167 CALC CALC FAIL Grp 4
S600 STR01 ISO5167 CALC NO PERMIT Grp 4
S600 STR01 ISO6976 CALC CONF ERR Grp 4
S600 STR01 ISO6976 CALC I/P ERR Grp 4
S600 STR01 ISO6976 CALC O/P ERR Grp 4
S600 STR01 ISO6976 CALC CALC FAIL Grp 4
S600 STR01 ISO6976 CALC NO PERMIT Grp 4
S600 STR01 TFWA CALC CONF ERR Grp 4
S600 STR01 TFWA CALC I/P ERR Grp 4
S600 STR01 TFWA CALC O/P ERR Grp 4
S600 STR01 TFWA CALC CALC FAIL Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 115 of 395 Issue 7
S600 STR01 TFWA CALC NO PERMIT Grp 4
S600 STR01 MASS FR L [SUPP]Grp 2
S600 STR01 MASS FR H [SUPP]Grp 2
S600 STR01 UPSTR DENS L [SUPP]Grp 2
S600 STR01 UPSTR DENS H [SUPP]Grp 2
S600 STR01 STD DENS L Grp 2
S600 STR01 STD DENS H Grp 2
S600 STR01 REAL RDENS L Grp 2
S600 STR01 REAL RDENS H Grp 2
S600 STR01 REAL CV L Grp 2
S600 STR01 REAL CV H Grp 2
S600 STR01 DP CELL L Grp 2
S600 STR01 DP CELL H [SUPP]Grp 2
S600 STR02 DP STACK CALC CONF ERR Grp 4
S600 STR02 DP STACK CALC I/P ERR Grp 4
S600 STR02 DP STACK CALC O/P ERR Grp 4
S600 STR02 DP STACK CALC CALC FAIL Grp 4
S600 STR02 DP STACK CALC NO PERMIT Grp 4
S600 STR02 DOWN/UP CALC CONF ERR Grp 4
S600 STR02 DOWN/UP CALC I/P ERR Grp 4
S600 STR02 DOWN/UP CALC O/P ERR Grp 4
S600 STR02 DOWN/UP CALC CALC FAIL Grp 4
S600 STR02 DOWN/UP CALC NO PERMIT Grp 4
S600 STR02 GAS INC CALC CONF ERR Grp 4
S600 STR02 GAS INC CALC I/P ERR Grp 4
S600 STR02 GAS INC CALC O/P ERR Grp 4
S600 STR02 GAS INC CALC CALC FAIL Grp 4
S600 STR02 GAS INC CALC NO PERMIT Grp 4
S600 STR02 PIPE COR CALC CONF ERR Grp 4
S600 STR02 PIPE COR CALC I/P ERR Grp 4
S600 STR02 PIPE COR CALC O/P ERR Grp 4
S600 STR02 PIPE COR CALC CALC FAIL Grp 4
S600 STR02 PIPE COR CALC NO PERMIT Grp 4
S600 STR02 STATUS CALC CONF ERR Grp 4
S600 STR02 STATUS CALC I/P ERR Grp 4
S600 STR02 STATUS CALC O/P ERR Grp 4
S600 STR02 STATUS CALC CALC FAIL Grp 4
S600 STR02 STATUS CALC NO PERMIT Grp 4
S600 STR02 LFC CALC CONF ERR Grp 4
S600 STR02 LFC CALC I/P ERR Grp 4
S600 STR02 LFC CALC O/P ERR Grp 4
S600 STR02 LFC CALC CALC FAIL Grp 4
S600 STR02 LFC CALC NO PERMIT Grp 4
S600 STR02 MAINT CALC CONF ERR Grp 4
S600 STR02 MAINT CALC I/P ERR Grp 4
S600 STR02 MAINT CALC O/P ERR Grp 4
S600 STR02 MAINT CALC CALC FAIL Grp 4
S600 STR02 MAINT CALC NO PERMIT Grp 4
S600 STR02 CHROM.P CALC CONF ERR Grp 4
S600 STR02 CHROM.P CALC I/P ERR Grp 4
S600 STR02 CHROM.P CALC O/P ERR Grp 4
S600 STR02 CHROM.P CALC CALC FAIL Grp 4
S600 STR02 CHROM.P CALC NO PERMIT Grp 4
S600 STR02 CHROM.S CALC CONF ERR Grp 4
S600 STR02 CHROM.S CALC I/P ERR Grp 4
S600 STR02 CHROM.S CALC O/P ERR Grp 4
S600 STR02 CHROM.S CALC CALC FAIL Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 116 of 395 Issue 7
S600 STR02 CHROM.S CALC NO PERMIT Grp 4
S600 STR02 CHROM.T CALC CONF ERR Grp 4
S600 STR02 CHROM.T CALC I/P ERR Grp 4
S600 STR02 CHROM.T CALC O/P ERR Grp 4
S600 STR02 CHROM.T CALC CALC FAIL Grp 4
S600 STR02 CHROM.T CALC NO PERMIT Grp 4
S600 STR02 AGA8 CALC CONF ERR Grp 4
S600 STR02 AGA8 CALC I/P ERR Grp 4
S600 STR02 AGA8 CALC O/P ERR Grp 4
S600 STR02 AGA8 CALC CALC FAIL Grp 4
S600 STR02 AGA8 CALC NO PERMIT Grp 4
S600 STR02 ISO5167 CALC CONF ERR Grp 4
S600 STR02 ISO5167 CALC I/P ERR Grp 4
S600 STR02 ISO5167 CALC O/P ERR Grp 4
S600 STR02 ISO5167 CALC CALC FAIL Grp 4
S600 STR02 ISO5167 CALC NO PERMIT Grp 4
S600 STR02 ISO6976 CALC CONF ERR Grp 4
S600 STR02 ISO6976 CALC I/P ERR Grp 4
S600 STR02 ISO6976 CALC O/P ERR Grp 4
S600 STR02 ISO6976 CALC CALC FAIL Grp 4
S600 STR02 ISO6976 CALC NO PERMIT Grp 4
S600 STR02 TFWA CALC CONF ERR Grp 4
S600 STR02 TFWA CALC I/P ERR Grp 4
S600 STR02 TFWA CALC O/P ERR Grp 4
S600 STR02 TFWA CALC CALC FAIL Grp 4
S600 STR02 TFWA CALC NO PERMIT Grp 4
S600 STR02 MASS FR L [SUPP]Grp 2
S600 STR02 MASS FR H [SUPP]Grp 2
S600 STR02 UPSTR DENS L [SUPP]Grp 2
S600 STR02 UPSTR DENS H [SUPP]Grp 2
S600 STR02 STD DENS L Grp 2
S600 STR02 STD DENS H Grp 2
S600 STR02 REAL RDENS L Grp 2
S600 STR02 REAL RDENS H Grp 2
S600 STR02 REAL CV L Grp 2
S600 STR02 REAL CV H Grp 2
S600 STR02 DP CELL L Grp 2
S600 STR02 DP CELL H [SUPP]Grp 2
S600 STR03 DP STACK CALC CONF ERR Grp 4
S600 STR03 DP STACK CALC I/P ERR Grp 4
S600 STR03 DP STACK CALC O/P ERR Grp 4
S600 STR03 DP STACK CALC CALC FAIL Grp 4
S600 STR03 DP STACK CALC NO PERMIT Grp 4
S600 STR03 DOWN/UP CALC CONF ERR Grp 4
S600 STR03 DOWN/UP CALC I/P ERR Grp 4
S600 STR03 DOWN/UP CALC O/P ERR Grp 4
S600 STR03 DOWN/UP CALC CALC FAIL Grp 4
S600 STR03 DOWN/UP CALC NO PERMIT Grp 4
S600 STR03 GAS INC CALC CONF ERR Grp 4
S600 STR03 GAS INC CALC I/P ERR Grp 4
S600 STR03 GAS INC CALC O/P ERR Grp 4
S600 STR03 GAS INC CALC CALC FAIL Grp 4
S600 STR03 GAS INC CALC NO PERMIT Grp 4
S600 STR03 PIPE COR CALC CONF ERR Grp 4
S600 STR03 PIPE COR CALC I/P ERR Grp 4
S600 STR03 PIPE COR CALC O/P ERR Grp 4
S600 STR03 PIPE COR CALC CALC FAIL Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 117 of 395 Issue 7
S600 STR03 PIPE COR CALC NO PERMIT Grp 4
S600 STR03 STATUS CALC CONF ERR Grp 4
S600 STR03 STATUS CALC I/P ERR Grp 4
S600 STR03 STATUS CALC O/P ERR Grp 4
S600 STR03 STATUS CALC CALC FAIL Grp 4
S600 STR03 STATUS CALC NO PERMIT Grp 4
S600 STR03 LFC CALC CONF ERR Grp 4
S600 STR03 LFC CALC I/P ERR Grp 4
S600 STR03 LFC CALC O/P ERR Grp 4
S600 STR03 LFC CALC CALC FAIL Grp 4
S600 STR03 LFC CALC NO PERMIT Grp 4
S600 STR03 MAINT CALC CONF ERR Grp 4
S600 STR03 MAINT CALC I/P ERR Grp 4
S600 STR03 MAINT CALC O/P ERR Grp 4
S600 STR03 MAINT CALC CALC FAIL Grp 4
S600 STR03 MAINT CALC NO PERMIT Grp 4
S600 STR03 CHROM.P CALC CONF ERR Grp 4
S600 STR03 CHROM.P CALC I/P ERR Grp 4
S600 STR03 CHROM.P CALC O/P ERR Grp 4
S600 STR03 CHROM.P CALC CALC FAIL Grp 4
S600 STR03 CHROM.P CALC NO PERMIT Grp 4
S600 STR03 CHROM.S CALC CONF ERR Grp 4
S600 STR03 CHROM.S CALC I/P ERR Grp 4
S600 STR03 CHROM.S CALC O/P ERR Grp 4
S600 STR03 CHROM.S CALC CALC FAIL Grp 4
S600 STR03 CHROM.S CALC NO PERMIT Grp 4
S600 STR03 CHROM.T CALC CONF ERR Grp 4
S600 STR03 CHROM.T CALC I/P ERR Grp 4
S600 STR03 CHROM.T CALC O/P ERR Grp 4
S600 STR03 CHROM.T CALC CALC FAIL Grp 4
S600 STR03 CHROM.T CALC NO PERMIT Grp 4
S600 STR03 AGA8 CALC CONF ERR Grp 4
S600 STR03 AGA8 CALC I/P ERR Grp 4
S600 STR03 AGA8 CALC O/P ERR Grp 4
S600 STR03 AGA8 CALC CALC FAIL Grp 4
S600 STR03 AGA8 CALC NO PERMIT Grp 4
S600 STR03 ISO5167 CALC CONF ERR Grp 4
S600 STR03 ISO5167 CALC I/P ERR Grp 4
S600 STR03 ISO5167 CALC O/P ERR Grp 4
S600 STR03 ISO5167 CALC CALC FAIL Grp 4
S600 STR03 ISO5167 CALC NO PERMIT Grp 4
S600 STR03 ISO6976 CALC CONF ERR Grp 4
S600 STR03 ISO6976 CALC I/P ERR Grp 4
S600 STR03 ISO6976 CALC O/P ERR Grp 4
S600 STR03 ISO6976 CALC CALC FAIL Grp 4
S600 STR03 ISO6976 CALC NO PERMIT Grp 4
S600 STR03 TFWA CALC CONF ERR Grp 4
S600 STR03 TFWA CALC I/P ERR Grp 4
S600 STR03 TFWA CALC O/P ERR Grp 4
S600 STR03 TFWA CALC CALC FAIL Grp 4
S600 STR03 TFWA CALC NO PERMIT Grp 4
S600 STR03 MASS FR L [SUPP]Grp 2
S600 STR03 MASS FR H [SUPP]Grp 2
S600 STR03 UPSTR DENS L [SUPP]Grp 2
S600 STR03 UPSTR DENS H [SUPP]Grp 2
S600 STR03 STD DENS L Grp 2
S600 STR03 STD DENS H Grp 2
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 118 of 395 Issue 7
S600 STR03 REAL RDENS L Grp 2
S600 STR03 REAL RDENS H Grp 2
S600 STR03 REAL CV L Grp 2
S600 STR03 REAL CV H Grp 2
S600 STR03 DP CELL L Grp 2
S600 STR03 DP CELL H [SUPP]Grp 2
S600 STR01 LOW FLOW ALARM Grp 2
S600 STR02 LOW FLOW ALARM Grp 2
S600 STR03 LOW FLOW ALARM Grp 2



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 119 of 395 Issue 7
JJ BUY BACK GAS ILOWCOMPU1LR

A single S600 will be supplied configured to perform the necessary gas orifice calculations required to cover the
buy back gas measurements.
The computer will be interfaced to a low and high differential pressure transmitter, pressure transmitter and
temperature transmitter.
Gas composition for density calculation will be downloaded directly from the supervisory computer.

JJ.J General Ieatures
The Buy Back flowcomputer is configured as a single orifice gas stream to measure and totalise the gas
imported to the system during a black start condition. This is effectively gas import rather than gas export.

JJ.J.J DP Cell Handling

The flowcomputer will accept two analogue signals from two separate differential pressure cells connected
across the same orifice plate. One of the cells is designated high range and the other cell is the low range cell.
Switchover points are provided (operator changeable) to enable switching to take place between the DP cells
depending on the percentage reading of the low range cell. The low to high and high to low switch points will
normally be set at 95% and 90% of the low scale range to prevent multiple switchovers occurring. When the DP
in use is within +/- 5% of the changeover value the difference between the two readings will be compared
against a keypad entered discrepancy. If this value is exceeded a cell discrepancy alarm will be raised.

JJ.J.2 Low Ilow Cut-off
An operator settable low flow cut-off point is provided for entry of a percentage of the low DP cell range. When
the gas DP exceeds this figure, the flowcomputer will calculate flowrates and totalisation will be performed -
this is the normal metering condition.
When a gas DP is measured below the low flow cut-off, a low flow alarm will be raised, and flowrate
calculations and totalisation are inhibited.

JJ.J.3 Density

A density calculation will be performed according to AGA-8 1994 report using the upstream meter temperature
and pressure and the gas composition data. The gas composition data is manually entered.


JJ.J.4 Local Printing
The following printout facilities are available:
Configuration:
Constants log report on request.
A display dump is printed on request.
A print out of all possible alarms and their configured alarm group.

Reports:
Day end report is printed automatically at day end, or on request.
Current report is printed on request.

Alarms:
Automatic alarm printouts on occurrence, acceptance and clearance of alarm states.
Automatic status printouts on occurrence of a keypad value or mode change.
All current alarms on request.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 120 of 395 Issue 7
JJ.2 Iunctions
The functions of the gas stream flowcomputers are:-

To accept one analogue (4-20mA) signal from a DP cell representing a high differential pressure input.

To accept a analogue (4-20mA) signal from a DP cell representing a low differential pressure input.

To accept a analogue (4-20mA) signal from a transmitter representing static pressure downstream of the orifice.

To accept a analogue (4-20mA) signal from a temperature transmitter representing temperature downstream of
the orifice.

To display measured and calculated quantities.

To provide a means of operator data entry and inspection.

To accept manually entered gas composition data and to use this data to perform a density calculation according
to AGA -8 1994 report and also a base density and calorific value calculation according to ISO 6976 1995.

To maintain an alarm system, report alarms on the front panel display and to transfer alarm information to the
duty supervisory computer.

To provide a digital output representing computer fail.

To perform secure totalisation of mass, standard volume, and energy of the total gas flow on a daily and
cumulative basis.

To perform calculations to an accuracy of at least +/- 0.001%

To communicate with the supervisory computer via a thin wire ethernet link, and RS 485 serial link to allow bi-
directional transfer of measured and calculated data, alarms, status and configuration.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 121 of 395 Issue 7

JJ.3 Input / Output Definition

S600 Conn DPin I/O Description Tag No
A 8 ADC 1 +ve Meter Pressure PT 6001
A 21 ADC 2 +ve Low Diff Pressure FT 6001A
A 9 ADC 3 +ve High Diff Pressure FT 6001B
A 22 ADC 4 +ve Meter Temp TT 6001
A 20 ADC Ground
RJ 45
Network
1 Signal ground Supervisory Computer
2 DTR Supervisory Computer
3 RTS Supervisory Computer
4 Tx Data Supervisory Computer
5 Rx Data Supervisory Computer
6 CTS Supervisory Computer
7 DSR Supervisory Computer
8 DCD Supervisory Computer
RJ 45 Port 3 1 Signal ground Local Printer
4 Tx Data Local Printer
5 Rx Data Local Printer
TB2 Port 6 5 Rx - Supervisory ComputerA
6 Rx + Supervisory ComputerA
7 Tx - Supervisory ComputerA
8 Tx + Supervisory ComputerA
TB2 Port 7 9 Rx - Supervisory ComputerB
10 Rx + Supervisory ComputerB
11 Tx - Supervisory ComputerB
12 Tx + Supervisory ComputerB
TB 1 1 24 Volt DC +ve 24 V DC Power
TB 1 2 24 Volt DC -ve 0 V DC Power
TB 1 6 N /C Contact Computer Fail Relay
TB 1 7
Common
Contact
Computer Fail Relay
TB 1 8 N/O Contact Computer Fail Relay

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 122 of 395 Issue 7

JJ.4 Calculations
The buy back flowcomputer will compute mass flow according to ISO 5167, line and base density calculations
according to AGA 8 and calorific value and base density calculations according to ISO 6976.
For details of these calculations please refer to section 9.4 of the export gas flowcomputer and calculation
flowchart appended.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 123 of 395 Issue 7

JJ.S Displays
The following is representative of the data that will be available as a minimum on the front panel of the flow
computer.
The actual displays will be included when configuration of the computers is completed

Display Item Parameters Units
Mass Total Cumulative, daily tonne
Mass Flowrate t/h
Std Vol Total Cumulative, daily Sm
3

Std Vol Flowrate Sm
3
/h
Energy Total Cumulative, daily MJ, BTU
Energy Flowrate MJ/h
Low Differential Pressure Measured, keypad mBar
High Differential Pressure Measured, keypad mBar
Differential Pressure In use, discrepancy, sw up, sw down mBar
Stream Temperature Downstream
o
C
Stream Temperature Upstream
o
C

Stream Pressure Upstream barg
Pipe Diameter Reference Conditions mm
Pipe Diameter Operating Conditions mm
Orifice Diameter Reference Conditions mm
Orifice Diameter Operating Conditions mm
Beta Operating Conditions
Viscosity Keypad entered Cp
Isentropic Exponent Keypad entered
Discharge Coefficient Calculated
Reynolds Number Calculated
Expansibility Calculated
Velocity of approach coef Calculated
Compressibility In-use, calc (AGA 8) and keypad
Density In-use, calc (AGA 8) and keypad kg/ m
3

Standard Density Air Keypad kg/ m
3

Calorific Value In-use, calc (ISO 6976) and keypad MJ/ m
3

AGA 8 Variables, constants and results
Gas Compositional Data mol %

Meter Status On-line, Off-line, Maintenance, Illegal,
Unhealthy

Time hh:mm
Date dd/mm/yyyy
Maint Mode Entry/Exit
Security various
Diagnostics various
Software Version various

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 124 of 395 Issue 7


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 125 of 395 Issue 7

JJ.6 Alarms
The alarms below are raised by the buy back gas flow computer.

S600 SYS HOST COLD ST Grp 1
S600 SYS HOST WARM ST Grp 1
S600 SYS HOST BATT FAIL Grp 1
S600 SYS HOST TOT RES Grp 1
S600 SYS HOST TOT PART Grp 1
S600 PRINTER MONITOR Grp 4
S600 BKGND TASK MONITOR Grp 4
S600 BKGND TASK TSK ERR Grp 4
S600 DIO SCAN TASK MONITOR Grp 4
S600 DIO SCAN TASK TSK ERR Grp 4
S600 DISPLAY TASK MONITOR Grp 4
S600 DISPLAY TASK TSK ERR Grp 4
S600 IO COMMS TASK MONITOR Grp 4
S600 IO COMMS TASK FAIL IO1 Grp 4
S600 IO COMMS TASK FAIL IO2 Grp 4
S600 IO COMMS TASK FAIL IO3 Grp 4
S600 IO COMMS TASK FAIL IO4 Grp 4
S600 IO COMMS TASK FAIL IO5 Grp 4
S600 IO COMMS TASK FAIL IO6 Grp 4
S600 IO COMMS TASK FAIL IO7 Grp 4
S600 IO COMMS TASK TSK ERR Grp 4
S600 IO SCAN TASK MONITOR Grp 4
S600 IO SCAN TASK TSK ERR Grp 4
S600 REPORTS TASK MONITOR Grp 4
S600 REPORTS TASK TSK ERR Grp 4
S600 TOTALS TASK MONITOR Grp 4
S600 TOTALS TASK TSK ERR Grp 4
S600 GAS COMPRESS TASK MONITOR Grp 4
S600 GAS COMPRESS TASK TSK ERR Grp 4
S600 GAS CV TASK MONITOR Grp 4
S600 GAS CV TASK TSK ERR Grp 4
S600 GAS CORRECT TASK MONITOR Grp 4
S600 GAS CORRECT TASK TSK ERR Grp 4
S600 GAS DP COND TASK MONITOR Grp 4
S600 GAS DP COND TASK TSK ERR Grp 4
S600 GAS DP INC TASK MONITOR Grp 4
S600 GAS DP INC TASK TSK ERR Grp 4
S600 GAS DP FLOW TASK MONITOR Grp 4
S600 GAS DP FLOW TASK TSK ERR Grp 4
S600 GAS PTZ TASK MONITOR Grp 4
S600 GAS PTZ TASK TSK ERR Grp 4
S600 GAS CHROMAT TASK MONITOR Grp 4
S600 GAS CHROMAT TASK TSK ERR Grp 4
S600 GAS TURB INCTASK MONITOR Grp 4
S600 GAS TURB INCTASK TSK ERR Grp 4
S600 GAS DENS COPY TASK MONITOR Grp 4
S600 GAS DENS COPY TASK TSK ERR Grp 4
S600 LIQ KF/MF TASK MONITOR Grp 4
S600 LIQ KF/MF TASK TSK ERR Grp 4
S600 LIQ M CORR TASK MONITOR Grp 4
S600 LIQ M CORR TASK TSK ERR Grp 4
S600 LIQ LIQ CON TASK MONITOR Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 126 of 395 Issue 7
S600 LIQ LIQ CON TASK TSK ERR Grp 4
S600 LIQ TURB TASK MONITOR Grp 4
S600 LIQ TURB TASK TSK ERR Grp 4
S600 LIQ VOL CORR TASK MONITOR Grp 4
S600 LIQ VOL CORR TASK TSK ERR Grp 4
S600 PRV SEQ TASK MONITOR Grp 4
S600 PRV SEQ TASK TSK ERR Grp 4
S600 PRV BIDI TASK MONITOR Grp 4
S600 PRV BIDI TASK TSK ERR Grp 4
S600 ULT CONTROL TASK MONITOR Grp 4
S600 ULT CONTROL TASK TSK ERR Grp 4
S600 ULT FLOWRATE TASK MONITOR Grp 4
S600 ULT FLOWRATE TASK TSK ERR Grp 4
S600 STN SUM FLOW TASK MONITOR Grp 4
S600 STN SUM FLOW TASK TSK ERR Grp 4
S600 DENSITY TASK MONITOR Grp 4
S600 DENSITY TASK TSK ERR Grp 4
S600 STR STATUS TASK MONITOR Grp 4
S600 STR STATUS TASK TSK ERR Grp 4
S600 FWA CALC TASK MONITOR Grp 4
S600 FWA CALC TASK TSK ERR Grp 4
S600 BVM TASK MONITOR Grp 4
S600 BVM TASK TSK ERR Grp 4
S600 STN AVE TASK MONITOR Grp 4
S600 STN AVE TASK TSK ERR Grp 4
S600 DISCREP TASK MONITOR Grp 4
S600 DISCREP TASK TSK ERR Grp 4
S600 CALC TASK MONITOR Grp 4
S600 CALC TASK TSK ERR Grp 4
S600 PID CTL TASK MONITOR Grp 4
S600 PID CTL TASK TSK ERR Grp 4
S600 ALM SUPPRESS TASK MONITOR Grp 4
S600 ALM SUPPRESS TASK TSK ERR Grp 4
S600 BATCH/FSW TASK MONITOR Grp 4
S600 BATCH/FSW TASK TSK ERR Grp 4
S600 AGA8FULL TASK MONITOR Grp 4
S600 AGA8FULL TASK TSK ERR Grp 4
S600 CALIB TASK MONITOR Grp 4
S600 CALIB TASK TSK ERR Grp 4
S600 US LIQ TASK MONITOR Grp 4
S600 US LIQ TASK TSK ERR Grp 4
S600 SAMPLER TASK MONITOR Grp 4
S600 SAMPLER TASK TSK ERR Grp 4
S600 LOGICALC TASK MONITOR Grp 4
S600 LOGICALC TASK TSK ERR Grp 4
S600 LIQ COR IO TASK MONITOR Grp 4
S600 LIQ COR IO TASK TSK ERR Grp 4
S600 LIQ COR IF TASK MONITOR Grp 4
S600 LIQ COR IF TASK TSK ERR Grp 4
S600 LIQ COR FLOW TASK MONITOR Grp 4
S600 LIQ COR FLOW TASK TSK ERR Grp 4
S600 PRV CPRV TASK MONITOR Grp 4
S600 PRV CPRV TASK TSK ERR Grp 4
S600 FAULT TASK MONITOR Grp 4
S600 FAULT TASK TSK ERR Grp 4
S600 FLOWTIME TASK MONITOR Grp 4
S600 FLOWTIME TASK TSK ERR Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 127 of 395 Issue 7
S600 SGERG TASK MONITOR Grp 4
S600 SGERG TASK TSK ERR Grp 4
S600 PRV MMPRV TASK MONITOR Grp 4
S600 PRV MMPRV TASK TSK ERR Grp 4
S600 ADC 01 PRS L Grp 2
S600 ADC 01 PRS H Grp 2
S600 ADC 01 PRS DEV ERR Grp 3
S600 ADC 02 DP LO DEV ERR Grp 3
S600 ADC 03 DP HI DEV ERR Grp 3
S600 ADC 04 TMP L Grp 2
S600 ADC 04 TMP H Grp 2
S600 ADC 04 TMP DEV ERR Grp 3
S600 STATUS RAM FAIL Grp 4
S600 STATUS ROM FAIL Grp 4
S600 STATUS PIC FAIL Grp 4
S600 STATUS TPU FAIL Grp 4
S600 STATUS EEPROM FAIL Grp 4
S600 STATUS TASK ERR Grp 4
S600 STATUS CONF ERR Grp 4
S600 STATUS TASK FAIL Grp 4
S600 STATUS WARM ST Grp 4
S600 STATUS DEV ERR Grp 4
S600 STR01 DP STACK CALC CONF ERR Grp 4
S600 STR01 DP STACK CALC I/P ERR Grp 4
S600 STR01 DP STACK CALC O/P ERR Grp 4
S600 STR01 DP STACK CALC CALC FAIL Grp 4
S600 STR01 DP STACK CALC NO PERMIT Grp 4
S600 STR01 DOWN/UP CALC CONF ERR Grp 4
S600 STR01 DOWN/UP CALC I/P ERR Grp 4
S600 STR01 DOWN/UP CALC O/P ERR Grp 4
S600 STR01 DOWN/UP CALC CALC FAIL Grp 4
S600 STR01 DOWN/UP CALC NO PERMIT Grp 4
S600 STR01 GAS INC CALC CONF ERR Grp 4
S600 STR01 GAS INC CALC I/P ERR Grp 4
S600 STR01 GAS INC CALC O/P ERR Grp 4
S600 STR01 GAS INC CALC CALC FAIL Grp 4
S600 STR01 GAS INC CALC NO PERMIT Grp 4
S600 STR01 PIPE COR CALC CONF ERR Grp 4
S600 STR01 PIPE COR CALC I/P ERR Grp 4
S600 STR01 PIPE COR CALC O/P ERR Grp 4
S600 STR01 PIPE COR CALC CALC FAIL Grp 4
S600 STR01 PIPE COR CALC NO PERMIT Grp 4
S600 STR01 STATUS CALC CONF ERR Grp 4
S600 STR01 STATUS CALC I/P ERR Grp 4
S600 STR01 STATUS CALC O/P ERR Grp 4
S600 STR01 STATUS CALC CALC FAIL Grp 4
S600 STR01 STATUS CALC NO PERMIT Grp 4
S600 STR01 LFC CALC CONF ERR Grp 4
S600 STR01 LFC CALC I/P ERR Grp 4
S600 STR01 LFC CALC O/P ERR Grp 4
S600 STR01 LFC CALC CALC FAIL Grp 4
S600 STR01 LFC CALC NO PERMIT Grp 4
S600 STR01 MAINT CALC CONF ERR Grp 4
S600 STR01 MAINT CALC I/P ERR Grp 4
S600 STR01 MAINT CALC O/P ERR Grp 4
S600 STR01 MAINT CALC CALC FAIL Grp 4
S600 STR01 MAINT CALC NO PERMIT Grp 4
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 128 of 395 Issue 7
S600 STR01 CHROM.P CALC CONF ERR Grp 4
S600 STR01 CHROM.P CALC I/P ERR Grp 4
S600 STR01 CHROM.P CALC O/P ERR Grp 4
S600 STR01 CHROM.P CALC CALC FAIL Grp 4
S600 STR01 CHROM.P CALC NO PERMIT Grp 4
S600 STR01 CHROM.S CALC CONF ERR Grp 4
S600 STR01 CHROM.S CALC I/P ERR Grp 4
S600 STR01 CHROM.S CALC O/P ERR Grp 4
S600 STR01 CHROM.S CALC CALC FAIL Grp 4
S600 STR01 CHROM.S CALC NO PERMIT Grp 4
S600 STR01 CHROM.T CALC CONF ERR Grp 4
S600 STR01 CHROM.T CALC I/P ERR Grp 4
S600 STR01 CHROM.T CALC O/P ERR Grp 4
S600 STR01 CHROM.T CALC CALC FAIL Grp 4
S600 STR01 CHROM.T CALC NO PERMIT Grp 4
S600 STR01 I/L VLV CALC CONF ERR Grp 4
S600 STR01 I/L VLV CALC I/P ERR Grp 4
S600 STR01 I/L VLV CALC O/P ERR Grp 4
S600 STR01 I/L VLV CALC CALC FAIL Grp 4
S600 STR01 I/L VLV CALC NO PERMIT Grp 4
S600 STR01 O/L VLV CALC CONF ERR Grp 4
S600 STR01 O/L VLV CALC I/P ERR Grp 4
S600 STR01 O/L VLV CALC O/P ERR Grp 4
S600 STR01 O/L VLV CALC CALC FAIL Grp 4
S600 STR01 O/L VLV CALC NO PERMIT Grp 4
S600 STR01 AGA8 CALC CONF ERR Grp 4
S600 STR01 AGA8 CALC I/P ERR Grp 4
S600 STR01 AGA8 CALC O/P ERR Grp 4
S600 STR01 AGA8 CALC CALC FAIL Grp 4
S600 STR01 AGA8 CALC NO PERMIT Grp 4
S600 STR01 ISO5167 CALC CONF ERR Grp 4
S600 STR01 ISO5167 CALC I/P ERR Grp 4
S600 STR01 ISO5167 CALC O/P ERR Grp 4
S600 STR01 ISO5167 CALC CALC FAIL Grp 4
S600 STR01 ISO5167 CALC NO PERMIT Grp 4
S600 STR01 ISO6976 CALC CONF ERR Grp 4
S600 STR01 ISO6976 CALC I/P ERR Grp 4
S600 STR01 ISO6976 CALC O/P ERR Grp 4
S600 STR01 ISO6976 CALC CALC FAIL Grp 4
S600 STR01 ISO6976 CALC NO PERMIT Grp 4
S600 STR01 MASS FR L [SUPP]Grp 2
S600 STR01 MASS FR H [SUPP]Grp 2
S600 STR01 UPSTR DENS L [SUPP]Grp 2
S600 STR01 UPSTR DENS H [SUPP]Grp 2
S600 STR01 STD DENS L Grp 2
S600 STR01 STD DENS H Grp 2
S600 STR01 REAL RDENS L Grp 2
S600 STR01 REAL RDENS H Grp 2
S600 STR01 REAL CV L Grp 2
S600 STR01 REAL CV H Grp 2
S600 STR01 DP CELL L [SUPP]Grp 2
S600 STR01 DP CELL H [SUPP]Grp 2
S600 STR01 DP CELL DISCREP [SUPP]Grp 2
S600 STR01 DP LOW FLOW ENTRY Grp 2

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 129 of 395 Issue 7
J2 SUPLRVISORY COMPU1LRS
The supervisory functions of the metering system are provided by two IBM compatible personal computers
configured in duty stand-by mode. The P.C.s share a single 21 colour monitor and keyboard. The P.C.s will
be mounted in the centre section of the metering panel c/w the monitor and keyboard.

J2.J Hardware Specification
The computers supplied will be AMC-500 4U high rack mounting computers with the following specifications.
AMC Single board computer fitted with Pentium III @ 866 MHz
200 Watt ATX Power Supply Unit with built in UPS
14 Slot Passive Backplane
512 MB Ram expandable to 1024 MB
IBM 18 GB SCSI hard disk drive
ASUS 52X CD ROM drive
12/24 GB DDS-3 DAT drive incorporated
3.5 Floppy disk drive incorporated
Two 9-pin serial port RS 232
Four 9-pin serial port RS232 /485
Two PS/2 connectors for keyboard and mouse (Mini-DIN)
One 15-pin VGA connector
10/100Mb Ethernet Network Interface Card





The monitor supplied will be Hewlett Packard 21 high resolution Colour monitor.

A Cherry keyboard with integral tracker ball will be installed in a drawer in the front of the metering panel.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 130 of 395 Issue 7

J2.2 General Ieatures
The operating system installed on the supervisory computers will be Windows NT.
The operator interface and graphics package providing data displays and operator control access will be Citect
V5.
A printer will be connected to the supervisory computers to provide station reports and second printer is
connected to log alarm printouts.
J2.2.J 1otalisation
The supervisory computer forms the following totals:
station totals for all streams
daily totals for all streams
station daily totals for gas streams
station daily totals for condensate streams
weekly totals for all streams
station weekly totals for gas streams
station weekly totals for condensate streams


The station totals are based on the stream total increments. The following sequence of operations is carried out:
read stream cumulative total
subtract previous cycle stream cumulative total to form increment
check validity of increment (detects stream reset, change of stream computer, change of duty)
add increment to all supervisory totals (cumulative, batch etc.)
store stream cumulative total reading to act as previous value for the next cycle
This procedure enables the supervisory to maintain valid stream totals if the stream computer is reset - or even
changed out.

The daily mass, std volume and energy totals accrued by the buy back gas computer will be subtracted from the
station daily totals at the end of the metering day resulting in Net totals for the day. The totals will be printed on
the daily reports.

J2.2.2 1rending
The station computer provides a trending function for the following data :
Gas Export Streams 1-3:
Standard volume flowrate Mass flowrate Energy flowrate
Pressure Temperature Line density Standard density
Gross Heating Value Specific gravity Differential pressure

Gas station values of
Std volume flowrate Mass flowrate Energy flowrate

Condensate Export Streams 1, 2
Standard volume flowrate Mass flowrate Pressure
Temperature Line density Standard density

Condensate station values of
Std volume flowrate Mass flowrate

The values will be stored at five minute intervals for periods of three months.
The resultant data may be displayed with a selectable time axis of one hour, one day, six hours, one week or one
month.
The data can be transferred to the internally mounted DAT drive using NTbackup.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 131 of 395 Issue 7

J2.2.3 Gas composition processing
The supervisory computer receives the gas mol% for components C1, C2, C3, iC4, nC4, iC5, nC5, neoC5, C6+, N2
and CO2 from the chromatograph controller.
The supervisory computer uses three sets of user-entered gas composition data:
a) A C6+ split, enabling the C6+ composition received from the chromatograph to be distributed into C6,
C7, C8, C9 and C10+
b) Mole % of additional components that the chromatograph cannot detect: He, O
2
, CO, H
2
O, Ar, H
2
S and
H
2

c) A default composition to be used if the chromatograph fails
When a new composition is received, the supervisory computer scales the received component values so that the
total composition, with the additional components as entered, is 100%. It then divides the C6+ in the
proportions entered. Finally, it downloads the processed composition to the gas export and back up
flowcomputers. The supervisory computer determines whether the chromatograph has failed. If no valid
analysis (a valid analysis is one that has a un-normalised total within the high / low limits) is received the
supervisory computer sets the chromatograph status to Failed and takes no action. If no valid analysis is
received by the stream computers for a 15 minute period (keypad entered), the export stream computers
automatically poll the chromatograph controller for data. If the stream computers receive no data from the
chromatograph then the default gas composition is selected for use.
Default data may also be selected manually.

J2.2.4 Gas Ilow Scheduling
An automatic flow scheduling system is provided to control the gas export streams. The gas export streams
normally operate with the outlet isolation valves in the closed position and the inlet isolation valves open. The
flow scheduling will act only on the outlet isolation valves.
In the case of no-flow conditions the last stream on line will always be left open.
The operator will be able to inhibit the flow scheduling if required.
Each stream shall be considered available for flow scheduling if the following conditions apply:
No flow on stream
Outlet valve(s) closed
Outlet valve(s) in remote control
Each stream shall be considered unavailable for flow scheduling if the following conditions apply:
Outlet valve(s) in local control
Stream in Maintenance mode
Input alarm e.g. ADC fail exists on stream
The operator will enter the required flowrate and the supervisory computer will automatically open / close the
available streams to keep the correct number of streams on-line in accordance with the flowrate.
Alarms will be generated if the flow is too low for a single stream or too high for the number of streams
available.
An alarm will be generated when the flow has reached a switchover point to open /close a stream and another
alarm will be generated when that switch over is performed.


J2.2.S Data Comparison
The supervisory computer will compare the difference between standard volume flowrates on each on-line gas
export stream and the corresponding standard volume flowrate on the back up stream with an operator entered
difference value and raise an alarm if this value is exceeded.

When more than one gas export stream is on line, the supervisory computer will compare values of
Differential Pressure
Pressure
Temperature
Density
Base Density

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 132 of 395 Issue 7
for a difference between each stream. There will be an operator entered time set for each parameter, and alarms
will be raised if the difference calculated exceeds a operator entered deviation for the timeout period..

J2.2.6 Sampling
Sampling outputs are provided for Gas Export and Condensate Export systems.
The Gas sampler is Time proportional and the Condensate sampler is flow proportional.
Condensate Sampler
At the start of a sampling run the supervisory calculates the number of grabs required to fill the sampling can,
assuming that the container is initially empty. During the sample run, the sampler output is normally driven at a
rate proportional to the appropriate station gross volume flowrate - subject to its entered maximum operating
frequency.
The supervisory stores a count of the number of sampler pulses (grabs) since the batch start. If the number of
grabs is such that a container is calculated to be more than 80% full, a warning alarm is raised. The sampler
output is automatically changed to the alternative can on receipt of the 90% full signal, and sampling continues
to the second can. If the container is calculated to be 100% full, sampling is inhibited.
The condensate sampler serves two sample cans, each fitted with 10%,70% and 90% full digital input signals.
The can in use may be selected from the supervisory screen (for start up purposes). The can in use is
automatically switched from 1 to 2 and 2 to 1 upon receipt of the appropiate 90% full signal by hardwire
interlocks.

Gas Sampler
The gas sampler outputs a pulse at an operator entered time period.
Analogue inputs are accepted representing %age can full for the gas sampler.
The operator can perform the following operations via the PC:
reset the grab counter and start sampling (one operation)
inhibit sampling
restart sampling having inhibited it



J2.2.7 Proving
The supervisory computer will allow control and monitoring of the automatic proving.





J2.3 Meter Iactor Linearisation
J2.3.J Normal Metering
The stream flowcomputer accepts a set of ten meter factors and frequency inputs to be entered from the turbine
meter calibration report. The action of linearisation may be enabled / disabled from the supervisory screen.
When disabled, the flowcomputer uses the keypad entered meter factor for all input frequencies.
When linearisation is enabled, the flowcomputer calculates the meter factor based on the input frequency.
If the input frequency does not exactly match the table entries then interpolation is performed using the two
nearest entries.
When the input frequency is below the lowest table entry then the meter factor selected is the one belonging to
the lowest frequency value.
When the input frequency is above the highest table entry then the meter factor selected is the one belonging to
the highest frequency value.
The feature is provided to enter all frequency and meter factor points at the S600 or the supervisory screens.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 133 of 395 Issue 7
J2.3.2 New Linearisation Curve
The last sixteen accepted meter factors that have been downloaded to the stream after successful proves will be
saved and presented to the operator for selection. The operator will select eight values which will then be
displayed on the MF curve as shown below in conceptual form. When satisfied with the values, the operator
may then download the selected values to the stream.

The operator would normally accept the Meter-factor. Reasons for not doing so might include knowledge of
operational problems beyond the Prover Computer's ability to detect them.
f MF
11-Apr-02 1:33:25 PM 11 1.0434
12-Apr-02 11:15:19 AM 12 1.0554
12-Apr-02 9:23:58 AM 25 1.0276
12-Apr-02 11:15:00 AM 25 0.9978
13-Apr-02 5:45:12 PM 30 1.0094
13-Apr-02 10:46:00 PM 49 1.0116
14-Apr-02 9:52:40 AM 52 0.9550
14-Apr-02 3:10:30 PM 73 1.0803
17-Apr-02 7:07:10 PM 74 1.0132
17-Apr-02 4:15:00 AM 76 1.0960
18-Apr-02 11:59:00 PM 76 0.9482
18-Apr-02 7:45:00 PM 81 1.0307
22-Apr-02 8:30:20 AM 81 1.0246
22-Apr-02 4:45:40 PM 82 0.9158
25-Apr-02 12:57:00 PM 83 0.9530
26-Apr-02 11:04:00 AM 83 1.0437
Date/time
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
0.9000
0.9500
1.0000
1.0500
1.1000
0 5 10
frequency
M
F
Series1
PLOT DOWNLOAD
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 134 of 395 Issue 7

J2.3.3 Duty Standby Operation
To provide redundancy in the supervisory computer system two PCs are used, one is nominated as a primary
server and the second as a secondary server. Both are connected to the flowcomputers via UTP ethernet and
Modbus serial links.
Only the primary server normally communicates with the stream flowcomputers.
A further communication link between the PCs allows for update of the secondary server from the primary
server.
If communication with the primary server is interrupted, the standby server assumes that the primary server has
failed and takes over as the primary server.
When the primary server is returned to service it reads the stream flowcomputer data from the standby server
and then resumes the role of the primary server.
The standby server automatically reverts to its former role.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 135 of 395 Issue 7

J2.4 Iunctions
The functions of the Supervisory computers include:-

To communicate with the condensate and gas stream flowcomputers via a Ethernet link to allow bi-directional
transfer of measured and calculated data, alarms, and status.

To communicate with the condensate and gas stream flowcomputers via a RS 485 serial link to allow bi-
directional transfer of measured and calculated data, alarms, and status.

To communicate with the gas chromatograph controller using Modbus RTU protocol to capture gas analysis,
and analysis reports.

To transfer the gas compositional data to the export, buy back and back up gas flowcomputers.

To provide display of all alarms relating to the metering systems.

To provide an audible alarm which will sound until alarm is acknowledged.

To provide a security system using passwords to control data entry.

To monitor a security keyswitch input to control access to a higher security level for report editing

To provide a comparison of standard volume totals from the gas export flowcomputer against the
back-up flowcomputer.

To form station totals for mass, standard volume and energy for the gas export and condensate metering.

To calculate and store flow weighted average values for gas and condensate metering systems.

To display and print fiscal metering and proving reports to the report printer.

To allow selection of any fiscal metering report and to copy on demand all the values in the report to a 3.5
floppy in the form of an IBM compatible ASCII file with an end of file marker.

To display and print alarm data and status changes to the alarm printer.

To provide remote manual operation of each motor operated valve in the gas and condensate metering systems.

To allow control of the prover computer.

To provide automatic alignment of the condensate streams valves for proving purposes.

To provide control and display of a time proportional pulse output for the gas sampler.

To provide control and display of a flow proportional pulse output for the condensate sampler.

To provide automatic flow scheduling system to control the gas export flowcomputers.

To provide a serial interface to the plant DCS for data transfer.

To provide user friendly operator interface to allow easy data inspection and entry and control.

To provide a RS 485 serial interface to a PLC to supply sampler pulse outputs for the condensate and gas
samplers.

To provide historic storage of daily, periodic and prove reports. The daily and periodic reports will be stored for
90 days.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 136 of 395 Issue 7
To store weekly reports for 52 weeks.
The facility will be provided to view the history and print out the reports.

To store trending data at five minute intervals for 90 days.

To monitor a digital input connected to the PLC representing condensate sample loop low flow condition and to
raise an alarm accordingly.

To provide reports and display dumps to a laser colour printer on the Ethernet link.

To transfer the daily mass total for the Condensate system automatically to the off- line metering PC.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 137 of 395 Issue 7

J2.S Input / Output Definition

9 way D Comms Port 1
Pin no: Signal Tag/Service
1
2 Tx Data Alarm Printer
3 Rx Data Alarm Printer
4
5 Signal ground Alarm Printer
6
7
8
9
9 way D Comms Port 2 RS232
Pin no: Signal Tag/Service
1
2 Tx Data Chromatograph Controller
3 Rx Data Chromatograph Controller
4
5 Signal ground Chromatograph Controller
6
7
8
9
25 Way D Comms Port 3 RS 232
Pin no: Signal Tag/Service
1
2 Tx Data DCS
3 Rx Data DCS
4
5 Signal ground DCS
6
7
8
9

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 138 of 395 Issue 7

9 way D Comms Port 4 RS 485
Pin no: Signal Tag/Service
1
2 Tx Data Flowcomputers
3 Rx Data Flowcomputers
4
5 Signal ground Flowcomputers
6
7
8
9
9 way D Comms Port 5 RS485
Pin no: Signal Tag/Service
1
2 Tx Data
3 Rx Data
4
5 Signal ground
6
7
8
9
25 Way D Comms Port 6 RS 485
Pin no: Signal Tag/Service
1
2 Tx Data
3 Rx Data
4
5 Signal ground
6
7
8
9

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 139 of 395 Issue 7

J2.6 Calculations

J2.6.J Symbols used in Calculations
Symbol Description Units
V
c
sampler container volume l
V
g
sampler grab volume cc
V
i
sampler volume interval m
3
V
plan
sampler planned batch volume m
3

s
i
Entered split proportion for C6+ tail component i mol%
x(C6+) Normalised mole % of named component mol%
X
i
Mol fraction of component
x
i
Normalised mole % of component i mol%
y
i
Entered mole % of user component mol%
z
i
Indicated mole % of component from chromatograph mol%

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 140 of 395 Issue 7

J2.6.2 Gas component normalisation
Received components from the chromatograph - including C6+ - are normalised, and adjusted to make space for
user entered components:
i
i
i
i
z
z
y
x

=
100

User entered components are entered in the normalised composition without modification:
x y
j i
=
Normalised C6+ is distributed according to the entered split, which is itself normalised:
( )
x
x C s
s
k
i
i
=
+

6




J2.6.3 Sampler Calculation
The volume required to be metered representing a sample pulse output is calculated thus;-


V
V
V
i
plan
c
=
V
g



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 141 of 395 Issue 7

J2.7 Displays
The displays provided for the system data will be:

Gas Export Station Overview
Condensate Export Station Overview
Prover Overview
Cumulative Station Totals
Daily & Previous Day Station Totals
Weekly & Previous Week Station Totals
Back Up Gas Totals
Buy Back Gas Totals
Station Alarm Limits
Station Reports Control
Gas Chromatograph Raw Data
Gas Chromatograph Additional Components
Gas Chromatograph In-Use Data
Gas Chromatograph Default Data
Condensate Composition Data
Current Flow weighted Data
Previous Flow weighted Data
Gas Sampler
Condensate Sampler
Prover Control / Status
Prover Configuration Data
Prover I/O Scalings
Prover Trial Run Data
Prover Final Data
Gas Stream Process Data (1 per stream)
Gas Stream Calculation Data (1 per stream)
Gas Stream Default Data (1 per stream)
Gas Stream Density Constants (1 per stream)
Gas Stream I/O (1 per stream)
Gas Stream Alarm Limits (1 per stream)
Back Up Gas Stream Process Data
Back Up Gas Stream Calculation Data
Back Up Gas Stream Default Data
Back Up Gas Stream I/O
Back Up Gas Stream Alarm Limits
Buy Back Gas Stream Process Data
Buy Back Gas Stream Calculation Data
Buy Back Gas Stream Default Data
Buy Back Gas Stream I/O
Buy Back Gas Stream Alarm Limits
Condensate Stream Process Data (1 per stream)
Condensate Stream Calculation Data (1 per stream)
Condensate Stream Default Data (1 per stream)
Condensate Stream Density Constants (1 per stream)
Condensate Stream I/O (1 per stream)
Condensate Stream Alarm Limits (1 per stream)
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 142 of 395 Issue 7

J2.7.J Mimics
Mimics will be provided using the following colour schemes.
MOV status indication

Status Indication
Open green symbol
Closed red symbol
Moving symbol LHS red, RHS green
Failed red flashing
Alarm symbol backlit with flashing yellow


Sampler Mimics

Status Indication
Operating red outline
Not operating green outline
Alarm yellow flash outline
Container % full proportional white fill

Prover Mimic

Status Indication
Proving red symbol outline
Idle green symbol outline
Not available amber symbol outline
Alarm condition yellow flashing outline



J2.8 MMI Display Details
The PC runs Citect V5 software, which allows data from any stream computer to be obtained via the network
and displayed.
The Citect software runs a menu system very similar to standard windows explorer
The latest alarm in the system is listed as a single line of alarm text below the main title, full alarms may be
viewed by using the alarm page.


Displays are accessed from the main menu by clicking on the required button e.g condensate streams displays
the condensate overview page

A set of identical displays is provided for each metering stream.
The stream displays provide a further navigation aid in the top banner of the screen where it is possible to
switch to the same displayed data for a different stream
Where data can be changed, this is identified by a box appearing around the data when the mouse pointer is
moved to the data. When the mouse pointer is moved to a changeable data field and the left button is clicked, if
the operator is logged in at the required level, a calculator window opens allowing selection and entry of the
new value.
J2.8.J Display Iormats
The main overview displays follow. The complete set of as built display formats for the Supervisory screens are
provided as screen dumps on a CD attached to this document

J2.8.2 Keypad Data
Keypad data isd identified on the displays by printing an asterisk * next to the data in keypad mode.
A
l
d
e
r
l
e
y


C
o
n
t
r
o
l
s


k
:
\
1
6
1
4

h
e
l
a
n
g


g
a
s

&

c
o
n
d
e
n
s
a
t
e
\
d
o
c
u
m
e
n
t
s
\
f
d
s
a
s
b
u
i
l
t
f
i
n
a
l
2
.
d
o
c


M
1
9
1
4

H
e
l
a
n
g

M
e
t
e
r
i
n
g



P
a
g
e

1
4
3

o
f

3
9
5

I
s
s
u
e

7

A
l
d
e
r
l
e
y


C
o
n
t
r
o
l
s


k
:
\
1
6
1
4

h
e
l
a
n
g


g
a
s

&

c
o
n
d
e
n
s
a
t
e
\
d
o
c
u
m
e
n
t
s
\
f
d
s
a
s
b
u
i
l
t
f
i
n
a
l
2
.
d
o
c


M
1
9
1
4

H
e
l
a
n
g

M
e
t
e
r
i
n
g



P
a
g
e

1
4
4

o
f

3
9
5

I
s
s
u
e

7

A
l
d
e
r
l
e
y


C
o
n
t
r
o
l
s


k
:
\
1
6
1
4

h
e
l
a
n
g


g
a
s

&

c
o
n
d
e
n
s
a
t
e
\
d
o
c
u
m
e
n
t
s
\
f
d
s
a
s
b
u
i
l
t
f
i
n
a
l
2
.
d
o
c


M
1
9
1
4

H
e
l
a
n
g

M
e
t
e
r
i
n
g



P
a
g
e

1
4
5

o
f

3
9
5

I
s
s
u
e

7

A
l
d
e
r
l
e
y


C
o
n
t
r
o
l
s


k
:
\
1
6
1
4

h
e
l
a
n
g


g
a
s

&

c
o
n
d
e
n
s
a
t
e
\
d
o
c
u
m
e
n
t
s
\
f
d
s
a
s
b
u
i
l
t
f
i
n
a
l
2
.
d
o
c


M
1
9
1
4

H
e
l
a
n
g

M
e
t
e
r
i
n
g



P
a
g
e

1
4
6

o
f

3
9
5

I
s
s
u
e

7
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 147 of 395 Issue 7







Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 148 of 395 Issue 7
J2.9 Alarms
TAG NAME DESCRIPTION
GAS1ALMSYS1CLDSTRT S600GAS1 Computer Has Cold Started
GAS1ALMSYS1WARMSTRT S600GAS1 Computer Has Warm Started
GAS1ALMSYS1TOTALL S600GAS1 All Tri registers have Failed
GAS1ALMSYS1TOTPRT S600GAS1 One Tri register does not agree
GAS1ALMADC02FAIL S600GAS1 Low Pay DP Cell has Failed
GAS1ALMADC05FAIL S600GAS1 Check Low DP Cell has Failed
GAS1ALMADC03FAIL S600GAS1 High Pay DP Cell has Failed
GAS1ALMADC04FAIL S600GAS1 Check High DP Cell has Failed
GAS1ALMADC01FAIL S600GAS1 Pressure Cell has Failed
GAS1ALMPRT01FAIL S600GAS1 Temperature Cell has Failed
GAS1ALMDNS1OAFAIL S600GAS1 Densitometer Fail
GAS1ALMADC01HI S600GAS1 Meter Pressure High
GAS1ALMADC01LO S600GAS1 Meter Pressure Low
GAS1ALMPRT01HI S600GAS1 Meter Temperature High
GAS1ALMPRT01LO S600GAS1 Meter Temperature Low
GAS1ALMDPCHI S600GAS1 Differential Pressure High
GAS1ALMDPCLO S600GAS1 Differential Pressure Low
GAS1ALMDNS1UPHI S600GAS1 Density High
GAS1ALMDNS1UPLO S600GAS1 Density Low
GAS1ALMDNS1BHI S600GAS1 Base Density High
GAS1ALMDNS1BLO S600GAS1 Base Density Low
GAS1ALMCV_1RHI S600GAS1 Calorific Value High
GAS1ALMCV_1RLO S600GAS1 Calorific Value Low
GAS1ALMQM_1HI S600GAS1 Mass Flowrate High
GAS1ALMQM_1LO S600GAS1 Mass Flowrate Low
GAS1ALMOLT1FAIL S600GAS1 No Outlet Valve 1 Status Detected
GAS1ALMILT1FAIL S600GAS1 No Inlet Valve 1 Status Detected
GAS1ALMFLW1LOCO S600GAS1 DP < Low Flow Limit
GAS1ALMFLW1ILGL S600GAS1 Illegal Flow
GAS1ALMDNSDSCRP S600GAS1 Density Discrepancy
GAS1ALMSYS1BATTFAIL S600GAS1 Ram Battery Support Failed
GAS1ALMDPLODSCRP S600GAS1 DP Low Discrepancy
GAS1ALMDPHIDSCRP S600GAS1 DP High Discrepancy
GAS1ALMOLT2FAIL S600GAS1 No Outlet Valve 2 Status Detected
GAS1ALMILT2FAIL S600GAS1 No Inlet Valve 2 Status Detected
GAS1ALMILT1VLVMVFAIL S600GAS1 Inlet Valve 1 Move Fail
GAS1ALMILT1UNCMD S600GAS1 No Inlet Valve 1 Uncommanded Move
GAS1ALMOLT1VLVMVFAIL S600GAS1 Outlet Valve 1 Move Fail
GAS1ALMOLT1UNCMD S600GAS1 No Outlet Valve 1 Uncommanded Move
GAS1ALMILT2VLVMVFAIL S600GAS1 Inlet Valve 2 Move Fail
GAS1ALMILT2UNCMD S600GAS1 Inlet Valve 2 Uncommanded Move
GAS1ALMOLT2VLVMVFAIL S600GAS1 Outlet Valve 2 Move Fail
GAS1ALMOLT2UNCMD S600GAS1 Outlet Valve 2 Uncommanded Move
GAS1SW_1ALM S600GAS1 Stream Software Fault
GAS1ALMDPCDSCRP S600GAS1 Differential Pressure Discrepancy
GAS1ALMCHR1RX S600GAS1 Chromat Comms Receive Fail
GAS2ALMSYS1CLDSTRT S600GAS2 Computer Has Cold Started
GAS2ALMSYS1WARMSTRT S600GAS2 Computer Has Warm Started
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 149 of 395 Issue 7
GAS2ALMSYS1TOTALL S600GAS2 All Tri registers have Failed
GAS2ALMSYS1TOTPRT S600GAS2 One Tri register does not agree
GAS2ALMADC02FAIL S600GAS2 Low Pay DP Cell has Failed
GAS2ALMADC05FAIL S600GAS2 Check Low DP Cell has Failed
GAS2ALMADC03FAIL S600GAS2 High Pay DP Cell has Failed
GAS2ALMADC04FAIL S600GAS2 Check High DP Cell has Failed
GAS2ALMADC01FAIL S600GAS2 Pressure Cell has Failed
GAS2ALMPRT01FAIL S600GAS2 Temperature Cell has Failed
GAS2ALMDNS1OAFAIL S600GAS2 Densitometer Fail
GAS2ALMADC01HI S600GAS2 Meter Pressure High
GAS2ALMADC01LO S600GAS2 Meter Pressure Low
GAS2ALMPRT01HI S600GAS2 Meter Temperature High
GAS2ALMPRT01LO S600GAS2 Meter Temperature Low
GAS2ALMDPCHI S600GAS2 Differential Pressure High
GAS2ALMDPCLO S600GAS2 Differential Pressure Low
GAS2ALMDNS1UPHI S600GAS2 Density High
GAS2ALMDNS1UPLO S600GAS2 Density Low
GAS2ALMDNS1BHI S600GAS2 Base Density High
GAS2ALMDNS1BLO S600GAS2 Base Density Low
GAS2ALMCV_1RHI S600GAS2 Calorific Value High
GAS2ALMCV_1RLO S600GAS2 Calorific Value Low
GAS2ALMQM_1HI S600GAS2 Mass Flowrate High
GAS2ALMQM_1LO S600GAS2 Mass Flowrate Low
GAS2ALMOLT1FAIL S600GAS2 No Outlet Valve 1 Status Detected
GAS2ALMILT1FAIL S600GAS2 No Inlet Valve 1 Status Detected
GAS2ALMFLW1LOCO S600GAS2 DP < Low Flow Limit
GAS2ALMFLW1ILGL S600GAS2 Illegal Flow
GAS2ALMDNSDSCRP S600GAS2 Density Discrepancy
GAS2ALMSYS1BATTFAIL S600GAS2 Ram Battery Support Failed
GAS2ALMDPLODSCRP S600GAS2 DP Low Discrepancy
GAS2ALMDPHIDSCRP S600GAS2 DP High Discrepancy
GAS2ALMOLT2FAIL S600GAS2 No Outlet Valve 2 Status Detected
GAS2ALMILT2FAIL S600GAS2 No Inlet Valve 2 Status Detected
GAS2ALMILT1VLVMVFAIL S600GAS2 Inlet Valve 1 Move Fail
GAS2ALMILT1UNCMD S600GAS2 No Inlet Valve 1 Uncommanded Move
GAS2ALMOLT1VLVMVFAIL S600GAS2 Outlet Valve 1 Move Fail
GAS2ALMOLT1UNCMD S600GAS2 No Outlet Valve 1 Uncommanded Move
GAS2ALMILT2VLVMVFAIL S600GAS2 Inlet Valve 2 Move Fail
GAS2ALMILT2UNCMD S600GAS2 Inlet Valve 2 Uncommanded Move
GAS2ALMOLT2VLVMVFAIL S600GAS2 Outlet Valve 2 Move Fail
GAS2ALMOLT2UNCMD S600GAS2 Outlet Valve 2 Uncommanded Move
GAS2SW_1ALM S600GAS2 Stream Software Fault
GAS2ALMDPCDSCRP S600GAS2 Differential Pressure Discrepancy
GAS2ALMCHR1RX S600GAS2 Chromat Comms Receive Fail
GAS3ALMSYS1CLDSTRT S600GAS3 Computer Has Cold Started
GAS3ALMSYS1WARMSTRT S600GAS3 Computer Has Warm Started
GAS3ALMSYS1TOTALL S600GAS3 All Tri registers have Failed
GAS3ALMSYS1TOTPRT S600GAS3 One Tri register does not agree
GAS3ALMADC02FAIL S600GAS3 Low Pay DP Cell has Failed
GAS3ALMADC05FAIL S600GAS3 Check Low DP Cell has Failed
GAS3ALMADC03FAIL S600GAS3 High Pay DP Cell has Failed
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 150 of 395 Issue 7
GAS3ALMADC04FAIL S600GAS3 Check High DP Cell has Failed
GAS3ALMADC01FAIL S600GAS3 Pressure Cell has Failed
GAS3ALMPRT01FAIL S600GAS3 Temperature Cell has Failed
GAS3ALMDNS1OAFAIL S600GAS3 Densitometer Fail
GAS3ALMADC01HI S600GAS3 Meter Pressure High
GAS3ALMADC01LO S600GAS3 Meter Pressure Low
GAS3ALMPRT01HI S600GAS3 Meter Temperature High
GAS3ALMPRT01LO S600GAS3 Meter Temperature Low
GAS3ALMDPCHI S600GAS3 Differential Pressure High
GAS3ALMDPCLO S600GAS3 Differential Pressure Low
GAS3ALMDNS1UPHI S600GAS3 Density High
GAS3ALMDNS1UPLO S600GAS3 Density Low
GAS3ALMDNS1BHI S600GAS3 Base Density High
GAS3ALMDNS1BLO S600GAS3 Base Density Low
GAS3ALMCV_1RHI S600GAS3 Calorific Value High
GAS3ALMCV_1RLO S600GAS3 Calorific Value Low
GAS3ALMQM_1HI S600GAS3 Mass Flowrate High
GAS3ALMQM_1LO S600GAS3 Mass Flowrate Low
GAS3ALMOLT1FAIL S600GAS3 No Outlet Valve 1 Status Detected
GAS3ALMILT1FAIL S600GAS3 No Inlet Valve 1 Status Detected
GAS3ALMFLW1LOCO S600GAS3 DP < Low Flow Limit
GAS3ALMFLW1ILGL S600GAS3 Illegal Flow
GAS3ALMDNSDSCRP S600GAS3 Density Discrepancy
GAS3ALMSYS1BATTFAIL S600GAS3 Ram Battery Support Failed
GAS3ALMDPLODSCRP S600GAS3 DP Low Discrepancy
GAS3ALMDPHIDSCRP S600GAS3 DP High Discrepancy
GAS3ALMOLT2FAIL S600GAS3 No Outlet Valve 2 Status Detected
GAS3ALMILT2FAIL S600GAS3 No Inlet Valve 2 Status Detected
GAS3ALMILT1VLVMVFAIL S600GAS3 Inlet Valve 1 Move Fail
GAS3ALMILT1UNCMD S600GAS3 No Inlet Valve 1 Uncommanded Move
GAS3ALMOLT1VLVMVFAIL S600GAS3 Outlet Valve 1 Move Fail
GAS3ALMOLT1UNCMD S600GAS3 No Outlet Valve 1 Uncommanded Move
GAS3ALMILT2VLVMVFAIL S600GAS3 Inlet Valve 2 Move Fail
GAS3ALMILT2UNCMD S600GAS3 Inlet Valve 2 Uncommanded Move
GAS3ALMOLT2VLVMVFAIL S600GAS3 Outlet Valve 2 Move Fail
GAS3ALMOLT2UNCMD S600GAS3 Outlet Valve 2 Uncommanded Move
GAS3SW_1ALM S600GAS3 Stream Software Fault
GAS3ALMDPCDSCRP S600GAS3 Differential Pressure Discrepancy
GAS3ALMCHR1RX S600GAS3 Chromat Comms Receive Fail
BAK1CLDSTART S600BAK1 Computer Has Cold Started
BAK1WRMSTART S600BAK1 Computer Has Warm Started
BAK1TRIREGALL S600BAK1 All Tri registers have failed
BAK1TRIREGPRT S600BAK1 One Tri register does not agree
BAK1DPCFAIL S600BAK1 DP Cell Fail
BAK1ADC1FAIL S600BAK1 Pressure Fail
BAK1PRT1FAIL S600BAK1 Temperature Fail
BAK1ADC1HI S600BAK1 Pressure High
BAK1ADC1LO S600BAK1 Pressure Low
BAK1PRT1HI S600BAK1 Temperature High
BAK1PRT1LO S600BAK1 Temperature Low
BAK1DPCHI S600BAK1 DP Cell High
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 151 of 395 Issue 7
BAK1DPCLO S600BAK1 DP Cell Low
BAK1DNSHI S600BAK1 Meter Density High
BAK1DNSLO S600BAK1 Meter Density Low
BAK1DNSBHI S600BAK1 Base Density High
BAK1DNSBLO S600BAK1 Base Density Low
BAK1DNS1RELHI S600BAK1 Relative Density High
BAK1DNS1RELLO S600BAK1 Relative Density Low
BAK1CVHI S600BAK1 Calorific Value High
BAK1CVLO S600BAK1 Calorific Value Low
BAK1QMHI S600BAK1 Mass Flowrate High
BAK1QMLO S600BAK1 Mass Flowrate Low
BAK1FLWLOCO S600BAK1 Gas DP < Low Flow Cutoff
BAK1BATTFAIL S600BAK1 Ram Support Battery Fail
BAK2DPCFAIL S600BAK1 DP Cell Fail
BAK2ADC1FAIL S600BAK1 Pressure Fail
BAK2PRT1FAIL S600BAK1 Temperature Fail
BAK2ADC1HI S600BAK1 Pressure High
BAK2ADC1LO S600BAK1 Pressure Low
BAK2PRT1HI S600BAK1 Temperature High
BAK2PRT1LO S600BAK1 Temperature Low
BAK2DPCHI S600BAK1 DP Cell High
BAK2DPCLO S600BAK1 DP Cell Low
BAK2DNSHI S600BAK1 Meter Density High
BAK2DNSLO S600BAK1 Meter Density Low
BAK2DNSBHI S600BAK1 Base Density High
BAK2DNSBLO S600BAK1 Base Density Low
BAK2DNS1RELHI S600BAK1 Relative Density High
BAK2DNS1RELLO S600BAK1 Relative Density Low
BAK2CVHI S600BAK1 Calorific Value High
BAK2CVLO S600BAK1 Calorific Value Low
BAK2QMHI S600BAK1 Mass Flowrate High
BAK2QMLO S600BAK1 Mass Flowrate Low
BAK2FLWLOCO S600BAK1 Gas DP < Low Flow Cutoff
BAK3DPCFAIL S600BAK1 DP Cell Fail
BAK3ADC1FAIL S600BAK1 Pressure Fail
BAK3PRT1FAIL S600BAK1 Temperature Fail
BAK3ADC1HI S600BAK1 Pressure High
BAK3ADC1LO S600BAK1 Pressure Low
BAK3PRT1HI S600BAK1 Temperature High
BAK3PRT1LO S600BAK1 Temperature Low
BAK3DPCHI S600BAK1 DP Cell High
BAK3DPCLO S600BAK1 DP Cell Low
BAK3DNSHI S600BAK1 Meter Density High
BAK3DNSLO S600BAK1 Meter Density Low
BAK3DNSBHI S600BAK1 Base Density High
BAK3DNSBLO S600BAK1 Base Density Low
BAK3DNS1RELHI S600BAK1 Relative Density High
BAK3DNS1RELLO S600BAK1 Relative Density Low
BAK3CVHI S600BAK1 Calorific Value High
BAK3CVLO S600BAK1 Calorific Value Low
BAK3QMHI S600BAK1 Mass Flowrate High
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 152 of 395 Issue 7
BAK3QMLO S600BAK1 Mass Flowrate Low
BAK3FLWLOCO S600BAK1 Gas DP < Low Flow Cutoff
BAK1SW_1ALM S600BAK1 Stream Software Fault
BAK1ALMDPC1HI S600BAK1 DP Cell High
BAK1ALMDPC1LO S600BAK1 DP Cell Low
BAK2ALMDPC1HI S600BAK1 DP Cell High
BAK2ALMDPC1LO S600BAK1 DP Cell Low
BAK3ALMDPC1HI S600BAK1 DP Cell High
BAK3ALMDPC1LO S600BAK1 DP Cell Low
BUY1CLDSTART S600BUY1 Computer Has Cold Started
BUY1WRMSTART S600BUY1 Computer Has Warm Started
BUY1TRIREGALL S600BUY1 All Tri registers have failed
BUY1TRIREGPRT S600BUY1 One Tri register does not agree
BUY1LODPCFAIL S600BUY1 Low DP Cell has failed
BUY1HIDPCFAIL S600BUY1 High DP Cell has failed
BUY1PRSFAIL S600BUY1 Pressure Cell has failed
BUY1TMPFAIL S600BUY1 Temperature Cell has failed
BUY1PRSHI S600BUY1 Meter Pressure High
BUY1PRSLO S600BUY1 Meter Pressure Low
BUY1TMPHI S600BUY1 Meter Temperature High
BUY1TMPHI S600BUY1 Meter Temperature Low
BUY1DPCHI S600BUY1 Differential Pressure High
BUY1DPCLO S600BUY1 Differential Pressure Low
BUY1DPCDSCRP S600BUY1 Differential Pressure Discrepancy
BUY1DNSHI S600BUY1 Density High
BUY1DNSLO S600BUY1 Density Low
BUY1DNSBHI S600BUY1 Base Density High
BUY1DNSBLO S600BUY1 Base Density Low
BUY1DNSRELHI S600BUY1 Relative Density High
BUY1DNSRELLO S600BUY1 Relative Density Low
BUY1CVHI S600BUY1 Calorific Value High
BUY1CVLO S600BUY1 Calorific Value Low
BUY1QMHI S600BUY1 Mass Flowrate High
BUY1QMLO S600BUY1 Mass Flowrate Low
BUY1FLWLO S600BUY1 Flow Below Low Flow Cutoff
BUY1SW_1ALM S600BUY1 Stream Software Fault
CND1ALMSYS1CLDSTRT S600CND1 Cold Start
CND1ALMSYS1WARMSTRT S600CND1 Warm Start
CND1ALMSYS1BATTFAIL S600CND1 Battery Fail
CND1ALMSYS1RAMFAIL S600CND1 Ram Fail
CND1ALMSYS1ROMFAIL S600CND1 Rom Fail
CND1ALMSYS1RESET S600CND1 S600 Reset
CND1ALMSYS1TOTRST S600CND1 Totals Reset
CND1ALMSYS1TOTPRT S600CND1 Totals Partial Fail
CND1ALMSYS1TOTCORR S600CND1 Totals Corrupted
CND1ALMSYS1CONFCSUM S600CND1 Config Checksum Error
CND1ALMSYS1TOTROLLO S600CND1 Totals Rollover
CND1ALMSYS1TOTROLLU S600CND1 Totals Rollunder
CND1ALMSYS1PRNTERR S600CND1 Printer Error
CND1ALMSYS1PRVCOMMSERR S600CND1 Prover Comms Error
CND1ALMADC01FAIL S600CND1 Meter Pressure Fail
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 153 of 395 Issue 7
CND1ALMADC01HI S600CND1 Meter Pressure High
CND1ALMADC01LO S600CND1 Meter Pressure Low
CND1ALMADC06FAIL S600CND1 Density Pressure Fail
CND1ALMADC06HI S600CND1 Density Pressure High
CND1ALMADC06LO S600CND1 Density Pressure Low
CND1ALMADC07FAIL S600CND1 Density Temperature Fail
CND1ALMADC07HI S600CND1 Density Temperature High
CND1ALMADC07LO S600CND1 Density Temperature Low
CND1ALMPRT01FAIL S600CND1 Meter Temperature Fail
CND1ALMPRT01HI S600CND1 Meter Temperature High
CND1ALMPRT01LO S600CND1 Meter Temperature Low
CND1ALMFRQ01FAIL S600CND1 Density A Fail
CND1ALMFRQ02FAIL S600CND1 Density B Fail
CND1ALMTRB01FAIL S600CND1 Turbine Fail
CND1ALMTRB01BADPLS S600CND1 Turbine Bad Pulses
CND1ALMQV_1HI S600CND1 Uvol Flowrate High
CND1ALMQV_1LO S600CND1 Uvol Flowrate Low
CND1ALMDNS1HI S600CND1 Meter Density High
CND1ALMDNS1LO S600CND1 Meter Density Low
CND1ALMDNS1BHI S600CND1 Standard Density High
CND1ALMDNS1BLO S600CND1 Standard Density Low
CND1ALMDNS1OHI S600CND1 Observed Density High
CND1ALMDNS1OLO S600CND1 Observed Density Low
CND1ALMDNS1OAFAIL S600CND1 Observed Density A Fail
CND1ALMDNS1OBFAIL S600CND1 Observed Density B Fail
CND1ALMMF_1HI S600CND1 Meter Factor High
CND1ALMMF_1LO S600CND1 Meter Factor Low
CND1ALMSTRAINER S600CND1 Strainer Blocked
CND1ALMILT1VLV S600CND1 No Inlet Valve 1 Status Detected
CND1ALMILT1VLVMVFAIL S600CND1 Inlet Valve 1 Move Fail
CND1ALMILT1UNCMD S600CND1 Inlet Valve 1 Uncommanded Move
CND1ALMOLT1VLV S600CND1 No Outlet Valve 1 Status Detected
CND1ALMOLT1VLVMVFAIL S600CND1 Outlet Valve 1 Move Fail
CND1ALMOLT1UNCMD S600CND1 Outlet Valve 1 Uncommanded Move
CND1ALMPLT1VLV S600CND1 No Prover Valve 1 Status Detected
CND1ALMPLT1VLVMVFAIL S600CND1 Prover Valve 1 Move Fail
CND1ALMPLT1UNCMD S600CND1 Prover Valve 1 Uncommanded Move
CND1ALMFLW1LOCO S600CND1 Low Flow Cutoff
CND1ALMFLW1ILGL S600CND1 Illegal Flow
CND1ALMILT2VLV S600CND1 No Inlet Valve 2 Status Detected
CND1ALMILT2VLVMVFAIL S600CND1 Inlet Valve 2 Move Fail
CND1ALMILT2UNCMD S600CND1 Inlet Valve 2 Uncommanded Move
CND1ALMOLT2VLV S600CND1 No Outlet Valve 2 Status Detected
CND1ALMOLT2VLVMVFAIL S600CND1 Outlet Valve 2 Move Fail
CND1ALMOLT2UNCMD S600CND1 Outlet Valve 2 Uncommanded Move
CND1ALMPLT2VLV S600CND1 No Prover Valve 2 Status Detected
CND1ALMPLT2VLVMVFAIL S600CND1 Prover Valve 2 Move Fail
CND1ALMPLT2UNCMD S600CND1 Prover Valve 2 Uncommanded Move
CND1SW_1ALM S600CND1 Stream Software Fault
CND1ALMTMP1DSCRP S600CND1 Temperature Discrepancy
CND1ALMDNS1DSCRP S600CND1 Density Discrepancy
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 154 of 395 Issue 7
CND1ALMDNS1ODSCRP S600CND1 Densitometer Discrepancy
CND2ALMSYS1CLDSTRT S600CND2 Cold Start
CND2ALMSYS1WARMSTRT S600CND2 Warm Start
CND2ALMSYS1BATTFAIL S600CND2 Battery Fail
CND2ALMSYS1RAMFAIL S600CND2 Ram Fail
CND2ALMSYS1ROMFAIL S600CND2 Rom Fail
CND2ALMSYS1RESET S600CND2 S600 Reset
CND2ALMSYS1TOTRST S600CND2 Totals Reset
CND2ALMSYS1TOTPRT S600CND2 Totals Partial Fail
CND2ALMSYS1TOTCORR S600CND2 Totals Corrupted
CND2ALMSYS1CONFCSUM S600CND2 Config Checksum Error
CND2ALMSYS1TOTROLLO S600CND2 Totals Rollover
CND2ALMSYS1TOTROLLU S600CND2 Totals Rollunder
CND2ALMSYS1PRNTERR S600CND2 Printer Error
CND2ALMSYS1PRVCOMMSERR S600CND2 Prover Comms Error
CND2ALMADC01FAIL S600CND2 Meter Pressure Fail
CND2ALMADC01HI S600CND2 Meter Pressure High
CND2ALMADC01LO S600CND2 Meter Pressure Low
CND2ALMADC06FAIL S600CND2 Density Pressure Fail
CND2ALMADC06HI S600CND2 Density Pressure High
CND2ALMADC06LO S600CND2 Density Pressure Low
CND2ALMADC07FAIL S600CND2 Density Temperature Fail
CND2ALMADC07HI S600CND2 Density Temperature High
CND2ALMADC07LO S600CND2 Density Temperature Low
CND2ALMPRT01FAIL S600CND2 Meter Temperature Fail
CND2ALMPRT01HI S600CND2 Meter Temperature High
CND2ALMPRT01LO S600CND2 Meter Temperature Low
CND2ALMFRQ01FAIL S600CND2 Density A Fail
CND2ALMFRQ02FAIL S600CND2 Density B Fail
CND2ALMTRB01FAIL S600CND2 Turbine Fail
CND2ALMTRB01BADPLS S600CND2 Turbine Bad Pulses
CND2ALMQV_1HI S600CND2 Uvol Flowrate High
CND2ALMQV_1LO S600CND2 Uvol Flowrate Low
CND2ALMDNS1HI S600CND2 Meter Density High
CND2ALMDNS1LO S600CND2 Meter Density Low
CND2ALMDNS1BHI S600CND2 Standard Density High
CND2ALMDNS1BLO S600CND2 Standard Density Low
CND2ALMDNS1OHI S600CND2 Observed Density High
CND2ALMDNS1OLO S600CND2 Observed Density Low
CND2ALMDNS1OAFAIL S600CND2 Observed Density A Fail
CND2ALMDNS1OBFAIL S600CND2 Observed Density B Fail
CND2ALMMF_1HI S600CND2 Meter Factor High
CND2ALMMF_1LO S600CND2 Meter Factor Low
CND2ALMSTRAINER S600CND2 Strainer Blocked
CND2ALMILT1VLV S600CND2 No Inlet Valve 1 Status Detected
CND2ALMILT1VLVMVFAIL S600CND2 Inlet Valve 1 Move Fail
CND2ALMILT1UNCMD S600CND2 Inlet Valve 1 Uncommanded Move
CND2ALMOLT1VLV S600CND2 No Outlet Valve 1 Status Detected
CND2ALMOLT1VLVMVFAIL S600CND2 Outlet Valve 1 Move Fail
CND2ALMOLT1UNCMD S600CND2 Outlet Valve 1 Uncommanded Move
CND2ALMPLT1VLV S600CND2 No Prover Valve 1 Status Detected
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 155 of 395 Issue 7
CND2ALMPLT1VLVMVFAIL S600CND2 Prover Valve 1 Move Fail
CND2ALMPLT1UNCMD S600CND2 Prover Valve 1 Uncommanded Move
CND2ALMFLW1LOCO S600CND2 Low Flow Cutoff
CND2ALMFLW1ILGL S600CND2 Illegal Flow
CND2ALMILT2VLV S600CND2 No Inlet Valve 2 Status Detected
CND2ALMILT2VLVMVFAIL S600CND2 Inlet Valve 2 Move Fail
CND2ALMILT2UNCMD S600CND2 Inlet Valve 2 Uncommanded Move
CND2ALMOLT2VLV S600CND2 No Outlet Valve 2 Status Detected
CND2ALMOLT2VLVMVFAIL S600CND2 Outlet Valve 2 Move Fail
CND2ALMOLT2UNCMD S600CND2 Outlet Valve 2 Uncommanded Move
CND2ALMPLT2VLV S600CND2 No Prover Valve 2 Status Detected
CND2ALMPLT2VLVMVFAIL S600CND2 Prover Valve 2 Move Fail
CND2ALMPLT2UNCMD S600CND2 Prover Valve 2 Uncommanded Move
CND2SW_1ALM S600CND2 Stream Software Fault
CND2ALMTMP1DSCRP S600CND2 Temperature Discrepancy
CND2ALMDNS1DSCRP S600CND2 Density Discrepancy
CND2ALMDNS1ODSCRP S600CND2 Densitometer Discrepancy
PRV1CLDSTART S600PRV1 Computer Has Cold Started
PRV1WRMSTART S600PRV1 Computer Has Warm Started
PRV1PRSILTFAIL S600PRV1 Inlet Pressure Fail
PRV1PRSOLTFAIL S600PRV1 Outlet Pressure Fail
PRV1TMPILTFAIL S600PRV1 Inlet Temperature Fail
PRV1TMPOLTFAIL S600PRV1 Outlet Temperature Fail
PRV1ABORT S600PRV1 Prover has Aborted
PRV1KFHI S600PRV1 K Factor High
PRV1KFLO S600PRV1 K Factor Low
PRV1PRSILTHI S600PRV1 Inlet Pressure High
PRV1PRSILTLO S600PRV1 Inlet Pressure Low
PRV1PRSOLTHI S600PRV1 Outlet Pressure High
PRV1PRSOLTLO S600PRV1 Outlet Pressure Low
PRV1TMPILTHI S600PRV1 Inlet Temperature High
PRV1TMPILTLO S600PRV1 Inlet Temperature Low
PRV1TMPOLTHI S600PRV1 Outlet Temperature High
PRV1TMPOLTLO S600PRV1 Outlet Temperature Low
PRV1OLT1FAIL S600PRV1 No status detected from Outlet Valve 1
PRV1OLT2FAIL S600PRV1 No status detected from Outlet Valve 2
PRV1ALMOLT1VLVMVFAIL S600PRV1 Outlet Valve 1 Move Fail
PRV1ALMOLT2VLVMVFAIL S600PRV1 Outlet Valve 2 Move Fail
PRV1ALMOLT1UNCMD S600PRV1 Outlet Valve 1 Uncommanded Move
PRV1ALMOLT2UNCMD S600PRV1 Outlet Valve 2 Uncommanded Move
PRV14WVFAIL S600PRV1 No status detected from 4 Way Valve
PRV14WVSEALFAIL S600PRV1 4 Way Valve Seal Fail
PRV1SW_1ALM S600PRV1 Stream Software Fault
PRV1STR1COMMSFAIL S600PRV1 Comms To Stream Fail
PRV1ALM4WV1MVFAIL S600PRV1 4 Way Valve Move Fail
PRV1ALM4WV1UNCMD S600PRV1 4 Way Valve Uncommanded Move
QSDIFF1 STATION std. vol. flowrate diff stream 1/backup
QSDIFF2 STATION std. vol. flowrate diff stream 2/backup
QSDIFF3 STATION std. vol. flowrate diff stream 3/backup
DPC1DIFF12 STATION Gas DP diff between 1 & 2
PRS1DIFF12 STATION Gas Prs diff between 1 & 2
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 156 of 395 Issue 7
TMP1DIFF12 STATION Gas Tmp diff between 1 & 2
DNS1DIFF12 STATION Gas Dns diff between 1 & 2
DNS1BDIFF12 STATION Gas Base dns diff between 1 & 2
DPC1DIFF13 STATION Gas DP diff between 1 & 3
PRS1DIFF13 STATION Gas Prs diff between 1 & 3
TMP1DIFF13 STATION Gas Tmp diff between 1 & 3
DNS1DIFF13 STATION Gas Dns diff between 1 & 3
DNS1BDIFF13 STATION Gas Base dns diff between 1 & 3
DPC1DIFF23 STATION Gas DP diff between 2 & 3
PRS1DIFF23 STATION Gas Prs diff between 2 & 3
TMP1DIFF23 STATION Gas Tmp diff between 2 & 3
DNS1DIFF23 STATION Gas Dns diff between 2 & 3
DNS1BDIFF23 STATION Gas Base dns diff between 2 & 3
FlowSched STATION Cannot close a stream
FlowSched STATION Cannot open a stream
S600GAS1 STATION S600GAS1 UTP - IOSERVER1 comms fail
S600GAS1_2 STATION S600GAS1 UTP - IOSERVER2 comms fail
S600GAS1_3 STATION S600GAS1 Serial - IOSERVER1 comms fail
S600GAS1_4 STATION S600GAS1 Serial - IOSERVER2 comms fail
S600GAS2 STATION S600GAS2 UTP - IOSERVER1 comms fail
S600GAS2_2 STATION S600GAS2 UTP - IOSERVER2 comms fail
S600GAS2_3 STATION S600GAS2 Serial - IOSERVER1 comms fail
S600GAS2_4 STATION S600GAS2 Serial - IOSERVER2 comms fail
S600GAS3 STATION S600GAS3 UTP - IOSERVER1 comms fail
S600GAS3_2 STATION S600GAS3 UTP - IOSERVER2 comms fail
S600GAS3_3 STATION S600GAS3 Serial - IOSERVER1 comms fail
S600GAS3_4 STATION S600GAS3 Serial - IOSERVER2 comms fail
S600CND1 STATION S600CND1 UTP - IOSERVER1 comms fail
S600CND1_2 STATION S600CND1 UTP - IOSERVER2 comms fail
S600CND1_3 STATION S600CND1 Serial - IOSERVER1 comms fail
S600CND1_4 STATION S600CND1 Serial - IOSERVER2 comms fail
S600CND2 STATION S600CND2 UTP - IOSERVER1 comms fail
S600CND2_2 STATION S600CND2 UTP - IOSERVER2 comms fail
S600CND2_3 STATION S600CND2 Serial - IOSERVER1 comms fail
S600CND2_4 STATION S600CND2 Serial - IOSERVER2 comms fail
S600PRV1 STATION S600PRV1 UTP - IOSERVER1 comms fail
S600PRV1_2 STATION S600PRV1 UTP - IOSERVER2 comms fail
S600PRV1_3 STATION S600PRV1 Serial - IOSERVER1 comms fail
S600PRV1_4 STATION S600PRV1 Serial - IOSERVER2 comms fail
S600BUY1 STATION S600BUY1 UTP - IOSERVER1 comms fail
S600BUY1_2 STATION S600BUY1 UTP - IOSERVER2 comms fail
S600BUY1_3 STATION S600BUY1 Serial - IOSERVER1 comms fail
S600BUY1_4 STATION S600BUY1 Serial - IOSERVER2 comms fail
S600BAK1 STATION S600BAK1 UTP - IOSERVER1 comms fail
S600BAK1_2 STATION S600BAK1 UTP - IOSERVER2 comms fail
S600BAK1_3 STATION S600BAK1 Serial - IOSERVER1 comms fail
S600BAK1_4 STATION S600BAK1 Serial - IOSERVER2 comms fail
PLC STATION PLC - IOSERVER1 comms fail
PLC2 STATION PLC - IOSERVER2 comms fail
OGC_LIVE STATION CHROMAT - IOSERVER1 comms fail
OGC_LIVE2 STATION CHROMAT - IOSERVER2 comms fail
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 157 of 395 Issue 7
SERVER STATION STANBDY SERVER comms fail
SMP1PLC_LEVEL PLC Gas Can Level High
GASSAMPCANFULL2 STATION Gas Sampler Can Full
CNDSAMPCANFULL2 STATION Cond. Sampler Can Full
OGCALARM1 STATION Chromatograph Alarm 1
OGCALARM2 STATION Chromatograph Alarm 2
GASSAMPCANFULL1 STATION Gas Sampler Can Level > 80%
CNDSAMPCANFULL1 STATION Cond. Sampler Can Level > 80%
PLC10001 PLC Condensate Sample Loop Flow Low
PLC10002 PLC Metering Panel Cooling Fan Failure
PLC10003 PLC DC PSU 1 Failure
PLC10004 PLC DC PSU 2 Failure
PLC10005 PLC Security Keyswitch
PLC10006 PLC Alarm Printer Failure
PLC10007 PLC Report Printer Failure
PLC10008 PLC Condensate DUTY can 10% full
PLC10009 PLC Condensate DUTY can 70% full
PLC10010 PLC Condensate DUTY can 90% full
PLC10011 PLC Condensate STANDBY can 10% full
PLC10012 PLC Condensate STANDBY can 70% full
PLC10013 PLC Condensate STANDBY can 90% full






Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 158 of 395 Issue 7
J2.J0 Printing and Reports
The supervisory computer prints the following reports:
Report Produced Condensate
System
Gas System
Weekly report Automatically & On demand
Daily reports (06:00 and
24:00)
Automatically & On demand
Periodic reports Automatically & On demand
Current reports On demand
Prove report Automatically & On demand
Constant Log On demand
Configuration Report On demand
Event & Alarm Report Automatically
Gas Chromat Analysis Automatically



Two day end times are incorporated in both the Gas and Condensate systems. The daily reports are
printed automatically at both day end times and on demand by operator.
The day end times may be changed by the user - although it should be noted that new time only takes
effect after the next scheduled report. Default report time values are:
Item Value
Gas day end times 06:00 & 24:00
Condensate day end times 06:00 & 24.00

Periodic reports may be printed at any interval in hours that divides exactly into 24 (1,2,3,4,6,8,12).
The default periodic reporting interval will be 2h.

Printed alarm messages occupy one line of eighty characters with the following fields
Field Characters Format / Example
date 8 DD/MM/YY
time 8 hh:mm:ss
alarm group 2 01
alarm message 16 tagname and failure
alarm type 7 failure / warning / high / low
alarm clarification 29 stream temperature low
event type 3 set / acc / clr

J2.J0.J Keypad Data
Keypad data is identified on reports by printing an asterisk * next to the keypad value.

J2.J0.2 Saving Reports
Daily reports are to be stored on the system hard drive for a period of 90 days.
It will be possible to any of the stored reports for printing
It will be possible to select a report and copy it to a 3
1
/2
floppy disc as an ASCII file suitable for direct
import into an Excel spreadsheet.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 159 of 395 Issue 7
J2.J0.3 Screen Dumps
The operator will be able to manually select any display screen on the system and send the contents to
the report printer.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 160 of 395 Issue 7

J2.JJ Report Iormats
J2.JJ.J Condensate System Current Report


Helang Central Platform
Condensate Export Metering System
Current Report EOD 1 Current Data at 30/06/02 02:47:32

Cumulative Totals
STREAM 1 STREAM 2 STATION


Mass t 0.000 128.213 128.213
Std Volume Sm 0.000 157.426 157.426
Std Volume bbl 0.000 990179.719 990179.719
Gross Volume m 0.000 161.543 61.543

Current Day Totals

Mass t 0.000 128.375 128.375
Std Volume Sm 0.000 157.426 157.426
Std Volume bbl 0.000 990179.719 990179.719
Gross Volume m 0.000 161.747 161.747

Current Process Data

Stream Status Maintenance On-Line

Mass t/h 0.000 181.109 0.000
Std Volume Sm/h 0.000 257.489 0.000
Gross Volume m/h 0.000 259.049 0.000
Pressure barg 34.000* 2.073
Temperature C 44.00* 20.01
Meter Density kg/m 1007.552 699.166
Base Density kg/Sm 1023.191 703.398
K factor pls/m 1010.000 1000.000
M factor 1.000000 1.000000

Flow Weighted Data
Current Day

Pressure barg 0.000 10.828
Temperature C 0.00 21.68
Meter Density kg/m 0.000 728.377
Base Density kg/Sm 0.000 733.123
Std Volume Sm
3
/d 123.123 123.123

Previous Day

Pressure barg 0.000 0.000
Temperature C 0.00 0.00
Meter Density kg/m 0.000 0.000
Base Density kg/Sm 0.000 0.000
Std Volume Sm
3
/d 123.123 123.123


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 161 of 395 Issue 7
J2.JJ.2 Condensate System Period Report


Helang Central Platform
Condensate Export Metering System
Period Report EOD 1 Current Data at 30/06/02 04:02:35

Cumulative Totals
STREAM STREAM 2 STATION

Mass 0.000 128.213 128.213
Std Volume Sm 0.000 157.426 157.426
Std Volume bbl 0.000 990179.719 990179.719
Gross Volume m 0.000 161.543 161.543

Period Totals

Mass t 0.000 0.000 0.000
Std Volume Sm 0.000 0.000 0.000
Std Volume bbl 0.000 0.000 0.000
Gross Volume m 0.000 0.000 0.000


Current Process Data

Stream Status On-Line On-Line

Mass t/h 140.747 152.720 0.000
Std Volume Sm/h 140.524 216.927 0.000
Gross Volume m/h 141.026 218.484 0.000
Pressure barg 1.113 0.817
Temperature C 20.86 20.77
Meter Density kg/m 998.017 699.045
Base Density kg/Sm 1001.585 704.058
K factor pls/m 1010.000 1000.000
M factor 1.000000 1.000000

Flow Weighted Data
Current Period

Pressure barg 0.889 4.193
Temperature C 20.45 20.81
Meter Density kg/m 998.034 708.396
Base Density kg/m 1001.356 713.084
Std Volume Sm
3
/d 123.123 123.123

Previous Period

Pressure barg 7.264 2.947
Temperature C 25.74 23.24
Meter Density kg/m 818.793 795.514
Base Density kg/Sm
3
828.153 935.921
Std Volume Sm
3
/d 123.123 123.123

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 162 of 395 Issue 7
J2.JJ.3 Condensate Daily Report

Helang Central Platform
Condensate Export Metering System
Daily Report Current Data at 29/06/02 00:00:39

Cumulative Totals
STREAM 1 STREAM 2 STATION

Mass t 771.780 468.299 1240.079
Std Volume Sm 1125.688 583.880 1709.568
Gross Volume m 1001.056 587.076 1588.132
Std Volume bbl 7080364.281 3672494.596 10752858.880


Daily Totals

Mass t 0.718 0.000 0.718
Std Volume Sm 0.907 0.000 0.907
Gross Volume m 0.930 0.000 0.930
Std Volume bbl 5704.858 0.000 5704.858


Current Process Data

Stream Status Valves Illeg Valves Illeg

Mass t/h 0.000 0.000 0.000
Std Volume Sm/h 0.000 0.000 0.000
Gross Volume m/h 0.000 0.000 0.000
Pressure barg 34.000* 36.000*
Temperature C 44.00* 46.00*
Meter Density kg/m 771.518 793.679
Base Density kg/Sm 791.411 814.437
K factor pls/m 100.000 1000.000
M factor 1.000000 1.000000

Flow Weighted Data
Current Day

Pressure barg 0.000 0.000
Temperature C 0.00 0.00
Meter Density kg/m 0.000 0.000
Base Density kg/Sm 0.000 0.000
Std Volume Sm
3
/d 123.123 123.123

Previous Day

Pressure barg 0.000 0.000
Temperature C 0.00 0.00
Meter Density kg/m 0.000 0.000
Base Density kg/Sm 0.000 0.000
Std Volume Sm
3
/d 123.123 123.123

Std Volume flowrates

Daily Average Sm
3
/d 123456.123 123456.123
Daily Minimum Sm
3
/d 123456.123 123456.123
Daily Maximum Sm
3
/d 123456.123 123456.123
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 163 of 395 Issue 7
J2.JJ.4 Condensate Weekly Report

Helang Central Platform
Condensate Export Metering System
Weekly Report EOD 1 Current Data at 09/06/02 17:02:50

Cumulative Totals
STREAM 1 STREAM 2 STATION

Mass t 123.123 123.123 123.123
Std Volume Sm 123.123 123.123 123.123
Std Volume bbl 123.123 123.123 123.123
Gross Volume m 123.123 123.123 123.123

Weekly Totals

Mass 123.123 123.123 123.123
Std Volume Sm 123.123 123.123 123.123
Std Volume bbl 123.123 123.123 123.123
Gross Volume m 123.123 123.123 123.123


Current Process Data

Stream Status Valves Illeg Valves Illeg

Mass t/h 0.00 0.000 428.192
Std Volume Sm/h 0.000 0.000 462.457
Gross Volume m/h 0.000 0.000 464.921
Pressure barg 1.144 3.011
Temperature C 15.58 100.00*
Meter Density kg/m 925.600 871.600
Base Density kg/Sm 925.879 925.879
K factor pls/m 1000.000 1589.000
M factor pls/m 1.000000 1.016372

Flow Weighted Data
Current Week

Pressure barg 0.000 0.000
Temperature C 0.00 0.00
Meter Density kg/m 0.000 0.000
Base Density kg/Sm 0.000 0.000
Std Volume Sm
3
/d 123.123 123.123

Previous Week

Pressure barg 0.000 0.000
Temperature C 0.00 0.00
Meter Density kg/m 0.000 0.000
Base Density kg/Sm
3
0.000 0.000
Std Volume Sm
3
/d 123.123 123.123


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 164 of 395 Issue 7
J2.JJ.S Iinal Prove Report

Helang Central Condensate Metering System Final Prove Report

Proved Stream STREAM 2
Base Volume 3
Prove Ending 30/06/02 03:03:51

Stream Prover Stream Corrected
Run Temp Pressure Temp Pressure Flowrate Volume K-Factor

(C) (Bar g) (C) (Bar g) (m/h) (m)

1 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
2 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
3 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
4 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
5 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
6 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
7 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
8 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
9 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
10 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
11 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
12 0.00 0.000 0.00 0.000 0.000 0.000000 0.000

Cplm Ctlm Cplp Ctlp Ctsp Cpsp Pulses

1 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
2 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
3 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
4 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
5 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
6 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
7 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
8 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
9 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
10 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
11 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
12 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000


Average Stream Temperature C 0.000 Base Volume 1 (m) 0.554975
Average Stream Pressure Bar g 0.000 Base Volume 2 (m) 0.549786
Average Prover Temperature C 0.000 Base Volume 3 (m) 0.568116
Average Prover Pressure Bar g 0.000 Base Volume 4 (m) 0.536642
Average Stream Base Density kg/Sm 0.000
Average Prover Flowrate m/h 0.000

Youngs Modulus Bar 3.12e+007
Internal Diameter mm 182.6260
Wall Thickness mm 18.2880
Temperature Expansion Coeff /C 0.000123


Number of runs required 5
K-Factor Repeatability Limit 0.050
Current K-Factor pls/m 1000.000

Calculated New K-Factor pls/m 0.0000
Calculated New M-Factor 0.000000


Repeatability % 0.000
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 165 of 395 Issue 7
J2.JJ.6 Gas Current Report
Helang Central Platform
Gas Export Metering System
Current Report Current Data at 29/06/02 04:35:35

Cumulative Totals
STREAM 1 STREAM 2 STREAM 3 STATION

Mass t 163.640 0.000 22.746 186.386
Std Volume Skm 213.630 0.000 7.830 221.460
Energy GJ 8495.724 0.000 402.676 8898.400

Mass (C1-C4) t 159.869 0.000 4.956 164.825
Mass (C5+) t 0.000 0.000 3.257 3.257
Std Vol (C1-C4) Skm 221.529 0.000 6.59 228.125
Std Vol (C5+) Skm 0.000 0.000 1.235 1.235
Energy (C1-C4) GJ 8811.053 0.000 271.577 9082.630
Energy (C1-C4) Mbtu 8350.759 0.000 257.390 8608.149
Energy (C5+) GJ 0.000 0.000 131.099 131.099
Energy (C5+) Mbtu 0.000 0.000 124.250 124.250

Current Day Totals

Mass t 163.640 0.000 22.746 186.386
Std Volume Skm 213.630 0.000 7.830 221.460
Energy GJ 8495.724 0.000 402.676 8898.400

Mass (C1-C4) t 159.869 0.000 4.956 164.825
Mass (C5+) t 0.000 0.000 3.257 3.257
Std Vol (C1-C4) Skm 221.529 0.000 6.595 228.125
Std Vol (C5+) Skm 0.000 0.000 1.235 1.235
Energy (C1-C4) GJ 8811.053 0.000 271.577 9082.630
Energy (C1-C4) Mbtu 8350.759 0.000 257.390 8608.149
Energy (C5+) GJ 0.000 0.000 131.099 131.099
Energy (C5+) Mbtu 0.000 0.000 124.250 124.250

Current Process Data

Stream Status Valves Illeg Off-Line Valves Illeg

Mass t/h 0.000 0.000 0.000 0.000
Std Volume Skm/h 0.000 0.000 0.000 0.000
Energy GJ/h 0.000 0.000 0.00 0.000
Pressure barg 100.000* 100.000* 100.000*
Temperature C 30.82 31.43 31.24
Upstr. Density kg/m 79.9929 124.9570 0.0000
Base Density kg/Sm 0.721678 1.270731 0.712228
CV MJ/kg 39.773 9.877 38.600
Relative Density 0.588928 1.036985 0.581216
Diff Press mbar 0.000* 0.000* 0.000*

Flow Weighted Data
Current Day

Pressure barg 100.000 0.000 0.000
Temperature C 30.82 0.00 0.00
Upstr. Density kg/m 75.4258 0.0000 0.0000
Base Density kg/Sm 0.721101 0.000000 0.000000
CV MJ/kg 39.701 0.000 0.000
Relative Density 0.588457 0.000000 0.000000
Diff Press mbar 6000.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123

Previous Day

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
CV MJ/Sm 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 166 of 395 Issue 7
Gas Period Report
Helang Central Platform
Gas Export Metering System
Period Report EOD 1 Current Data at 29/06/02 18:00:36

Cumulative Totals
STREAM 1 STREAM 2 STREAM 3 STATION

Mass t 14.940 1438.824 12.341 1466.105
Std Vol Skm 18.949 1817.787 15.652 1852.388
Energy GJ 797.080 76090.130 658.406 77545.616

Mass (C1-C4) t 13.324 1274.903 11.006 1299.233
Mass (C5+) t 1.616 163.174 1.335 166.125
Std Vol (C1-C4) Skm 18.367 1756.034 15.172 1789.572
Std Vol (C5+) Skm 0.582 63.499 0.480 64.562
Energy (C1-C4) GJ 733.625 70189.661 606.002 71529.288
Energy (C1-C4) MBtu 695.300 66522.918 574.344 67792.562
Energy (C5+) GJ 63.455 5865.535 52.404 5981.394
Energy (C5+) MBtu 60.140 5559.116 49.666 5668.923

Period Totals

Mass t 0.000 0.000 0.000 0.000
Std Vol Skm 0.000 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000 0.000

Mass (C1-C4) t 0.000 0.000 0.000 0.000
Mass (C5+) t 0.000 0.000 0.000 0.000
Std Vol (C1-C4) Skm 0.000 0.000 0.000 0.000
Std Vol (C5+) Skm 0.000 0.000 0.000 0.000
Energy (C1-C4) GJ 0.000 0.000 0.000 0.000
Energy (C1-C4) MBtu 0.000 0.000 0.000 0.000
Energy (C5+) GJ 0.000 0.000 0.000 0.000
Energy (C5+) MBtu 0.000 0.000 0.000 0.000


Current Process Data

Stream Status Valves Illeg Off-Line Valves Illeg

Mass t/h 0.000 0.000 0.000 0.000
Std Volume Skm/h 0.000 0.000 0.000 0.000
Energy GJ/h 0.000 0.000 0.000 0.000
Pressure barg 100.000* 100.000* 100.000*
Temperature C 30.84 31.43 31.24
Upstr. Density kg/m 91.6810 476.6290 0.0000
Base Density kg/Sm 0.788450 1.927152 0.712228
CV MJ/kg 42.064 56.178 38.600
Relative Density 0.643417 1.572659 0.581216
Diff Press mbar 0.000* 0.000* 0.000*

Flow Weighted Data
Current Period

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123

Previous Period

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 167 of 395 Issue 7
Component Mass Totals

Period Totals

Mass (C1) t 123.123 123.123 123.123
Mass (C2) t 123.123 123.123 123.123
Mass (C3) t 123.123 123.123 123.123
Mass (iC4) t 123.123 123.123 123.123
Mass (nC4) t 123.123 123.123 123.123
Mass (CO2) t 123.123 123.123 123.123
Mass (N2) t 123.123 123.123 123.123
Mass (C5+) t 123.123 123.123 123.123




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 168 of 395 Issue 7

J2.JJ.7 Gas Daily Report
Helang Central Platform
Gas Export Metering System
Daily Report EOD 2 Current Data at 29/06/02 00:00:41
Cumulative Totals
STREAM 1 STREAM 2 STREAM 3 STATION

Mass t 0.000 0.000 0.000 0.000
Std Vol Skm 0.000 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000 0.000
Mass (C1-C4) t 0.000 0.000 0.000 0.000
Mass (C5+) t 0.000 0.000 0.000 0.000
Std Vol (C1-C4) Skm 0.000 0.000 0.000 0.000
Std Vol (C5+) Skm 0.000 0.000 0.000 0.000
Energy (C1-C4) GJ 0.000 0.000 0.000 0.000
Energy (C1-C4) Mbtu 0.000 0.000 0.000 0.000
Energy (C5+) GJ 0.000 0.000 0.000 0.000
Energy (C5+) Mbtu 0.000 0.000 0.000 0.000

Daily Totals

Mass t 0.000 0.000 0.000 0.000
Std Vol Skm 0.000 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000 0.000
Mass (C1-C4) t 0.000 0.000 0.000 0.000
Mass (C5+) t 0.000 0.000 0.000 0.000
Std Vol (C1-C4) Skm 0.000 0.000 0.000 0.000
Std Vol (C5+) Skm 0.000 0.000 0.000 0.000
Energy (C1-C4) GJ 0.000 0.000 0.000 0.000
Energy (C1-C4) Mbtu 0.000 0.000 0.000 0.000
Energy (C5+) GJ 0.000 0.000 0.000 0.000
Energy (C5+) Mbtu 0.000 0.000 0.000 0.000

BuyBack Adjustment Mass t Std Vol Skm Energy GJ
Station 0.000 0.000 0.000
BuyBack 0.000 0.000 0.000
Net 0.000 0.000 0.000

Current Process Data

Stream Status Valves Illeg Off-Line Valves Illeg

Mass t/h 0.000 0.000 0.000 0.000
Std Volume Skm/h 0.000 0.000 0.000 0.000
Energy GJ/h 0.000 0.000 0.000 0.000
Pressure barg 100.000* 100.000* 100.000*
Temperature C 30.83 31.44 31.26
Upstr. Density kg/m 91.8444 0.0000 0.0000
Base Density kg/Sm 0.788450 0.712228 0.712228
CV MJ/kg 42.064 38.600 38.600
Relative Density 0.643417 0.581216 0.581216
Diff Press mbar 0.000* 0.000* 0.000*

Flow Weighted Data
Current Day

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 0.000 0.000 0.000

Previous Day

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 169 of 395 Issue 7
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 0.000 0.000 0.000

Component Mass Totals

Mass (C1) t 123.123 123.123 123.123
Mass (C2) t 123.123 123.123 123.123
Mass (C3) t 123.123 123.123 123.123
Mass (iC4) t 123.123 123.123 123.123
Mass (nC4) t 123.123 123.123 123.123
Mass (CO2) t 123.123 123.123 123.123
Mass (N2) t 123.123 123.123 123.123
Mass (C5+) t 123.123 123.123 123.123

Std Volume Flowrates

Daily Average Skm
3
/d 123456.123 123456.123 123456.123
Daily Minimum Skm
3
/d 123456.123 123456.123 123456.123
Daily Maximum Skm
3
/d 123456.123 123456.123 123456.123

C1-C4 Rate MMSCF/d 123456.123 123456.123 123456.123



J2.JJ.8 Mass Component 1otals Daily Report


Helang Central Platform
Gas Export Metering System
Mass Component Totals Daily Report EOD 2 Current Data at 29/06/02 00:00:41


Totals Daily Mass
t
Methane C1 123456.123
Ethane C2 123456.123
Propane C3 123456.123
I-Butane iC4 123456.123
N-Butane nC4 123456.123
Carbon Dioxide CO2 123456.123
Nitrogen N2 123456.123
Pentanes+ C5+ 123456.123

TOTAL MASS 123456.123

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 170 of 395 Issue 7


J2.JJ.9 Gas Weekly Report
Helang Central Platform
Gas Export Metering System
Weekly Report EOD 1 Current Data at 05/06/02 18:51:37

Cumulative Totals
STREAM 1 STREAM 2 STREAM 3 STATION

Mass t 14159.968 4693.475 13629.232 32482.675
Std Vol Skm 32557.967 5894.558 16026.500 54479.025
Energy GJ 1348546.964 246289.255 721753.793 2316590.012

Mass (C1-C4) t 23798.063 4585.097 11951.002 40334.161
Mass (C5+) t 2523.092 704.652 2274.322 5502.066
Std Vol (C1-C4) Skm 32920.916 6249.855 15940.210 55110.981
Std Vol (C5+) Skm 1243.416 423.200 871.936 2538.551
Energy (C1-C4) GJ 632998.599 252040.189 655074.881 1540113.669
Energy (C1-C4) Mbtu 599930.434 238873.483 620853.439 1459657.356
Energy (C5+) GJ 50882.362 26290.464 98891.679 176064.506
Energy (C5+) MBtu 48224.242 24917.037 93725.528 166866.808


Weekly Totals

Mass t 14159.891 2516.541 5560.147 22236.579
Std Vol Skm 32557.880 2927.846 6348.776 41834.502
Energy GJ 1348542.922 128731.965 293303.215 1770578.102

Mass (C1-C4) t 23798.124 2082.101 4590.083 30470.308
Mass (C5+) t 2523.079 434.440 969.979 3927.498
Std Vol (C1-C4) Skm 1170.461 2748.574 6045.586 9964.621
Std Vol (C5+) Skm 58.368 179.786 305.336 543.490
Energy (C1-C4) GJ 632995.127 113981.302 251192.489 998168.918
Energy (C1-C4) Mbtu 599927.143 108026.861 238070.067 946024.071
Energy (C5+) GJ 50881.792 14751.260 42106.212 107739.264
Energy (C5+) MBtu 48223.702 13980.647 39906.562 102110.911


Current Process Data

Stream Status Valves Illeg Off-Line Valves Illeg

Mass t/h 0.000 0.000 0.000 0.000
Std Volume Sm/h 0000 0.000 0.000 0.000
Energy GJ/h 0.000 0.000 0.000 0.000
Pressure barg 100.000* 100.000* 100.000*
Temperature C 15.79 16.19 16.19
Meter Density kg/m 930.700 930.800 930.800
Base Density kg/Sm 925.879 925.879 925.879
CV Mj/kg 123.123 123.123 123.123
Relative Density 1.123456 1.123456 1.123456


Flow Weighted Data
Current WK

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123

Previous Week

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm3 0.000000 0.000000 0.000000
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 171 of 395 Issue 7
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123

Component Mass Totals

Weekly Totals

Mass (C1) t 123.123 123.123 123.123
Mass (C2) t 123.123 123.123 123.123
Mass (C3) t 123.123 123.123 123.123
Mass (iC4) t 123.123 123.123 123.123
Mass (nC4) t 123.123 123.123 123.123
Mass (CO2) t 123.123 123.123 123.123
Mass (N2) t 123.123 123.123 123.123
Mass (C5+) t 123.123 123.123 123.123

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 172 of 395 Issue 7
J2.JJ.J0 Back Up Gas Current Report

Helang Central Platform
Backup Gas Metering System
Current Report Current Data at 26/06/02 07:24:34

Cumulative Totals
STREAM 1 STREAM 2 STREAM 3


Mass t 0.000 0.000 0.000
Std Vol Skm 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000

Mass (C1-C4) t 1971.425 0.000 0.000
Mass (C5+) t 217.767 0.000 0.000
Std Vol (C1-C4) Skm 2810.508 0.000 0.000
Std Vol (C5+) Skm 0.000 0.000 0.000
Energy (C1-C4) GJ 109069.568 0.000 0.000
Energy (C1-C4) Mbtu 103371.719 0.000 0.000
Energy (C5+) GJ 3439.172 0.000 0.000
Energy (C5+) Mbtu 3259.508 0.000 0.000


Current Day Totals

Mass t 0.000 0.000 0.000
Std Vol Skm 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000

Mass (C1-C4) t 1971.425 0.000 0.000
Mass (C5+) t 217.767 0.000 0.000
Std Vol (C1-C4) Skm 2810.508 0.000 0.000
Std Vol (C5+) Skm 146.440 0.000 0.000
Energy (C1-C4) GJ 109069.568 0.000 0.000
Energy (C1-C4) Mbtu 103371.719 0.000 0.000
Energy (C5+) GJ 3439.172 0.000 0.000
Energy (C5+) Mbtu 3259.508 0.000 0.000

Current Process Data

Stream Status Off-Line Off-Line Off-Line

Mass t/h 0.000 0.000 0.000
Std Vol Skm/h 0.000 0.000 0.000
Energy GJ/h 0.000 0.000 0.000
Pressure barg 100.000* 100.000* 100.000*
Temperature C 100.00* 100.00* 100.00*
Upstr. Density kg/m 60.0869 60.0869 60.0869
Base Density kg/Sm 0.740355 0.740355 0.740355
CV MJ/kg 38.049 38.049 38.049
Relative Density 0.604170 0.604170 0.604170
Diff Press mbar 0.000* 0.000* 0.000*


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 173 of 395 Issue 7
J2.JJ.JJ Buy Back Gas Current Report

Buy Back Gas Metering System
Current Report Current Data at 19/06/02 09:04:07

Cumulative Totals
STREAM 1

Mass t 2245.947
Std Volume Skm 2962.674
Energy GJ 112729.582

Current Day Totals

Mass t 2245.947
Std Volume Skm 2962.674
Energy GJ 112729.582

Current Process Data

Stream Status Off-Line

Mass t/h 0.000
Std Volume Skm/h 0.000
Energy GJ/h 0.000
Pressure barg 100.000*
Temperature C 100.00*
Upstr. Density kg/m 60.0869
Base Density kg/Sm 0.740355
CV MJ/kg 38.049
Relative Density 0.604170
Diff Press mbar 0.000*




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 174 of 395 Issue 7

J2.JJ.J2 Constants Log
A constant log may be produced on demand for each computer listing the values of all constants held in
the computer.

Helang Central Platform
Gas Export Stream 1
Constant Log Report at 30/11/2002 20:03:54


Gas Export 1 Base Density High Limit 1.0000000 kg/m3
Gas Export 1 Base Density Keypad 0.8400000 kg/m3
Gas Export 1 Base Density Low Limit 0.5000000 kg/m3
Gas Export 1 Base Pressure 0.0000000 barg
Gas Export 1 Base Temperature 15.0000000 Deg C
Gas Export 1 Calorific Value High Limit 42.0000000 MJ/kg
Gas Export 1 Calorific Value Keypad 48.0000000 MJ/kg
Gas Export 1 Calorific Value Low Limit 35.0000000 MJ/kg
Gas Export 1 Densitometer 1 Const Calib Temp 20.0000000 Deg C
Gas Export 1 Density Const G 5.0000000e-001
Gas Export 1 Density Const K0 -4.2144810e+001
Gas Export 1 Density Const K1 -2.7510340e-001
Gas Export 1 Density Const K18 -1.9000000e-005
Gas Export 1 Density Const K19 2.2900000e-004
Gas Export 1 Density Const K2 7.0545060e-004
Gas Export 1 Density Const K3 8.0000000e+002
Gas Export 1 Density Const K4 7.9800000e+001
Gas Export 1 Density Const R 2.3600000e-003
Gas Export 1 Density Expansion Coefficient 0.7692310
Gas Export 1 Density Of Air 1.2254100
Gas Export 1 Density Keypad 110.0000000 kg/m3
Gas Export 1 Density Mode KEYPAD
Gas Export 1 DP Pay Low Input High Limit 102.0000000 mbar
Gas Export 1 DP Pay Low Input High Scale 280.0000000 mbar
Gas Export 1 DP Pay Low Input Keypad 0.0000000 mbar
Gas Export 1 DP Pay Low Input Low Limit -2.0000000 mbar
Gas Export 1 DP Pay Low Input Low Scale 0.0000000 mbar
Gas Export 1 DP Pay High Input High Limit 102.0000000 mbar
Gas Export 1 DP Pay High Input High Scale 625.0000000 mbar
Gas Export 1 DP Pay High Input Keypad 0.0000000 mbar
Gas Export 1 DP Pay Low Input Low Limit -2.0000000 mbar
Gas Export 1 DP Pay Low Input Low Scale 0.0000000 mbar
Gas Export 1 DP Check High Input High Limit 102.0000000 mbar
Gas Export 1 DP Check High Input High Scale 625.0000000 mbar
Gas Export 1 DP Check High Input Keypad 100.0000000 mbar
Gas Export 1 DP Check High Input Low Limit -2.0000000 mbar
Gas Export 1 DP Check High Input Low Scale 0.0000000 mbar
Gas Export 1 DP Check Low Input High Limit 102.0000000 mbar
Gas Export 1 DP Check Low Input High Scale 280.0000000 mbar
Gas Export 1 DP Check Low Input Keypad 100.0000000 mbar
Gas Export 1 DP Check Low Input Low Limit -2.0000000 mbar
Gas Export 1 DP Check Low Input Low Scale 0.0000000 mbar
Gas Export 1 DP Stack Low Cutoff 1.0000000 mbar
Gas Export 1 DP Stack Discrepancy 10.0000000 mbar
Gas Export 1 DP Stack Discrepancy Timeout 5.0000000 secs
Gas Export 1 DP Stack High Pay/Check Discrepancy 0.0000000 mbar
Gas Export 1 DP Stack High Limit 600.0000000 mbar
Gas Export 1 DP Stack Keypad 0.0000000 mbar
Gas Export 1 DP Stack Low Pay/Check Discrepancy 0.0000000 mbar
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 175 of 395 Issue 7
Gas Export 1 DP Stack Low Limit 5.0000000 mbar
Gas Export 1 DP Stack Mode KEYPAD
Gas Export 1 DP Stack Switch Down 90.0000000 mbar
Gas Export 1 DP Stack Switch Up 95.0000000 mbar
Gas Export 1 Energy GJ -> MBtu 1.0551200
Gas Export 1 Isentropic Exponent 1.3000000
Gas Export 1 Low Flow Cutoff 5.0000000 t/h
Gas Export 1 Maintenance Mode Status CLEAR
Gas Export 1 DP Discrepancy Limit 100.0000000 mbar
Gas Export 1 Upstream Density High Limit 1000.0000000 kg/m3
Gas Export 1 Upstream Density Keypad 105.0000000 kg/m3
Gas Export 1 Upstream Density Low Limit 0.0000000 kg/m3
Gas Export 1 Upstream Density Mode PTZ
Gas Export 1 Orifice Diameter 180.0000000 mm
Gas Export 1 Orifice Calib Temperature 20.0000000 Deg C
Gas Export 1 Orifice Expansion Constant 0.0000160
Gas Export 1 Pipe Diameter 300.0000000 mm
Gas Export 1 Pipe Calib Temperature 20.0000000 Deg C
Gas Export 1 Pipe Temperature Expansion 0.0000110
Gas Export 1 Pressure High Limit 119.0000000 barg
Gas Export 1 Pressure High Scale 120.0000000 barg
Gas Export 1 Pressure Keypad 100.0000000 barg
Gas Export 1 Pressure Low Limit 0.0000000 barg
Gas Export 1 Pressure Low Scale 0.0000000 barg
Gas Export 1 Pressure Mode KEYPAD
Gas Export 1 Std Vol Skm3 -> bbl 0.1589873
Gas Export 1 Temperature Expansion Coefficient -0.2307690
Gas Export 1 Temperature High Limit 40.0000000 Deg C
Gas Export 1 Temperature Keypad 100.0000000 Deg C
Gas Export 1 Temperature Low Limit 0.0000000 Deg C
Gas Export 1 Temperature Mode KEYPAD
Gas Export 1 Upstream Density High Limit 200.0000000 kg/m3
Gas Export 1 Upstream Density Low Limit 0.2000000 kg/m3
Gas Export 1 Mass Flowrate High Limit 1300.0000000 t/h
Gas Export 1 Mass Flowrate Low Limit 0.0000000 t/h
Gas Export 1 Viscosity 0.0171000


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 176 of 395 Issue 7
Helang Central Platform
Prover Computer
Constant Log Report at 30/11/2002 20:05:08


Prover Base Volume 1 0.5549750 Sm3
Prover Base Volume 2 0.5497860 Sm3
Prover Base Volume 3 0.5681160 Sm3
Prover Base Volume 4 0.5366420 Sm3
Prover Base Volume Index 2.0000000
Prover Elasticity 30000000.0000000
Prover Inlet Pressure High Limit 102.0000000 barg
Prover Inlet Pressure Low Limit -2.0000000 barg
Prover Inlet Temperature High Limit 102.0000000 Deg C
Prover Inlet Temperature Low Limit -2.0000000 Deg C
Prover Input Pressure Keypad 25.0000000 barg
Prover Input Pressure Mode KEYPAD
Prover Input Temperature Keypad 40.0000000 Deg C
Prover Input Temperature Mode KEYPAD
Prover K Factor Repeatability 1.0000000 %
Prover Key Switch Status CLEAR
Prover Maximum Runs 12.0000000
Prover Meter Factor High Limit 1.1000000
Prover Meter Factor Low Limit 0.5000000
Prover Outlet Pressure High Limit 102.0000000 barg
Prover Outlet Pressure Low Limit -2.0000000 barg
Prover Outlet Temperature High Limit 102.0000000 Deg C
Prover Outlet Temperature Low Limit -2.0000000 Deg C
Prover Output Pressure Keypad 25.0000000 barg
Prover Output Pressure Mode KEYPAD
Prover Output Temperature Keypad 40.0000000 Deg C
Prover Output Temperature Mode KEYPAD
Prover Pipe Diameter 182.6260000 mm
Prover Run Time Delay 5.0000000 sec
Prover Runs Required 5.0000000
Prover Stability Flow Rate Of Change 10.0000000 m3/h
Prover Stability Hold Time 10.0000000
Prover Stability Overide SET
Prover Stability Pressure Band 0.5000000 barg
Prover Stability Pressure Rate Of Change 0.0500000 barg/sec
Prover Stability Temperature Band 1.0000000 Deg C
Prover Stability Temperature Rate Of Change 0.1000000 Deg C/sec
Prover Stability Wait Time 60.0000000 sec
Prover Stream No 1.0000000
Prover Tube Coefficient 1.0000000e-004
Prover Wall Thickness 18.2880000 mm



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 177 of 395 Issue 7

J2.JJ.J3 Alarms and Lvents Report
A list of alarms and events will be automatically printed at end of day for both the gas and condensate
metering systems. Each alarm and event will be identified with the stream number and will contain
details of the alarm / event and the time of occurrence.


Helang Central Gas Export Metering
Alarms and Events Report

Alarms and Events Report Print Date: 12/05/2000 06:00:00


Alarms List:
1999/12/26 18:00:59 Gas01Pressure High [123.123] Raised
1999/12/26 18:01:04 Gas01Pressure High [123.123] Accepted
1999/12/26 18:00:47 BackupGas01Pressure High [123.123] Raised


Events List:

2000/01/25 22:08:14 DP_1USED:MODE KEYPAD
2000/01/25 22:12:32DP_1KPAD:VALUE [5.000000E+01]-.[0.000000E+00]



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 178 of 395 Issue 7


J2.JJ.J4 Gas Maintenance report
This report is printed on exit from maintenance mode.



Helang Central Platform Backup Stream 1
Maintenance Report
Current Data at 29/06/02
04:55:38


Current Stream Status Unknown

Totals On Entry to Maintenance

Cumulative Daily Maintenance

Mass t 32.293 32.293 0.000
Standard Volume Skm 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000

Totals on Exit from Maintenance

Cumulative Daily Maintenance

Mass t 32.293 32.293 0.000
Standard Volume Skm 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000


J2.JJ.JS Condensate Maintenance Report

Helang Central Platform Condensate Export
Stream 1

Maintenance Report
Current Data at 29/06/02
03:27:25


Current Stream Status Valves Illegal

Totals On Entry to Maintenance Cumulative Daily Maintenance

Mass t 771.801 0.021 0.000
Standard Volume Sm 1125.715 0.027 0.000
Volume m 1001.084 0.028 0.000

Totals on Exit from Maintenance

Cumulative Daily Maintenance

Mass t 771.801 0.021 148.730
Standard Volume Sm 1125.715 0.027 187.931
Volume m 1001.084 0.028 192.776



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 179 of 395 Issue 7
J2.JJ.J6 Gas Chromatograph Analysis Report


CHROMATOGRAPH A 2601 30/06/02 03:05:55

Stream analysed: 1 - analysis cycle at 27/ 6/ 2 20: 8 (dd/mm/yy hh:mm)

Analysis cycle
time:
123 secs
Calibration cycle
time:
123 secs

Component Mole% Weight% Response
Factor
Response
Factor


C6+ 47/35/17 0.0000 0.2329 15248800.0000 35.4800
Propane 0.0000 0.0944 0.9925 34.8829
i-Butane 2.4280 0.0000 0.9880 32.0295
n-Butane 3.2392 0.0078 0.9873 31.4905
neo-Pentane 0.0000 0.0000 77116.1016 0.0000
i-Pentane 0.0000 0.0000 63457.6016 0.6783
n-Pentane 0.0000 0.0000 60013.5000 0.8312
Nitrogen 88.5635 99.5490 0.9927 43.0788
Methane 0.0000 0.0000 0.9920 38.8894
Carbon Dioxide 1.2871 0.0228 0.9935 19.6092
Ethane 4.4823 0.1387 0.9923 99.2222
Invalid code:0 0.0000 0.0000 0.0000 0.0000
Invalid code:0 0.0000 0.0000 0.0000 0.0000
Invalid code:0 0.0000 0.0000 0.0000 0.0000
Invalid code:0 0.0000 0.0000 0.0000 0.0000
Invalid code:0 0.0000 0.0000 0.0000 0.0000

Units Primary results
Dry inferior CV MJ/kg 0.2545
Dry superior CV MJ/kg 0.2809
Saturated inferior
CV
MJ/kg 0.2629
Saturated superior
CV
MJ/kg 0.2761
Real relative
density
0.9691
Real density kg/m 0.0000
Wobbe index
inferior
MJ/m 1.1876
Wobbe index
superior
MJ/m 0.2853
Compressibility Z 0.9997
Unnormalised sum
of mole%
493030016.0000
Molar mass 28.0709





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 180 of 395 Issue 7
J3 COMMUNICA1IONS
J3.J Chromatograph Communications

The chromatograph port provided uses RS232 interface at 9600 baud, using seven data bits, one stop
bit and odd parity and implements Modbus ASCII protocol.

The flowomputers provide communications to the Daniels 2350 Gas Chromatograph Controller..
The Chromatograph protocol is a limited implementation of Modbus ASCII framing with the
supervisory acting as a MASTER device. All transactions are initiated by the supervisory computer.

Modbus specifies a set of function codes, the subset available within this implementation is as shown
below, with those actually used marked *
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 181 of 395 Issue 7
Code Description

01 Not supported
02 Computer reads input status
03* Computer reads multiple registers
04 Not supported
05 Computer writes single coil to
06 Computer writes single register to
07 Not supported
08 Comms Loopback test, only diagnostic code 0 supported
09 Not supported
10 Not supported
11 Not supported
12 Not supported
13 Not supported
14 Not supported
15 Computer writes multiple coils
16* Computer writes multiple registers
17-21 Not supported
22- Not supported

All unused codes are correctly handled as defined in the specification. As Modbus is only specified to
handle 16 bit integers, the following extension is necessary to allow transfer of floating point real
variables.

- Functions 03 and 16 may be used to read & write single precision real variables.

- FP Reals must reside within register range 7000-7999.

- Each FP Real register consists of 4 bytes organised to IEEE format as follows:-

7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0
s| EXP------------------- -| MANTISSA--------- --------------------------- -------------------|
First Byte Second Byte Third Byte
Fourth Byte

Note that as the data is packaged to Modbus ASCII format 8 bytes will actually be transmitted for each
variable.

The controller address on each modbus link will be 01

The physical characteristics of the Modbus interface will be:-

RS232, 9600 Baud, 7 data, Odd parity, 1 start, 1 stop.

MODBUS registers

The MODBUS registers that will be used from the 2350 controllers are detailed below:-
16 Bit Integers
3001 .. 3016 Component codes (current component table)
3017 .. 3032 as above
3033 Analysis elapsed time (1/30th secs)
3034 Stream last analysed
3035 8 bit stream mask - bit 0 indicates that the component table is used with
stream 1

bit 7 indicates that the component table is used with stream 8
3036 Current month number
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 182 of 395 Issue 7
3037 Current day
3038 Current Year (2 digits, e.g. 99,00,01 etc)
3039 Current Hour
3040 Current Minute
3041 Start of Cycle Month
3042 " day
3043 " year (2 digits, e.g. 99,00,01 etc)
3044 " hour
3045 " minute
3046 Alarm status bits - see ref.[1] for meanings.
3047 as above.
3058 New data flag, set to 1 when data is available
3059 Analysis / Calibration flag
1 = last completed run was an analysis run
0 = last completed run was a calibration run
3061 Stream last analysed


32 Bit integers
5001 Analysis cycle time ( in 1/30 second units)
5002 Calibration cycle time ( in 1/30 second units )


32 bit Real Numbers
7001..7016 Mole % results
7017..7032 Weight % results
7033 Dry superior CV }
7034 Saturated superior CV }
7035 Real Relative density } primary results
7036 Compressibility Z }
7037 Wobbe index superior }
7038 Unnormalised sum of mole % values
7039 Molar mass of the gas mixture
7087 Dry inferior CV }
7088 Sat inferior CV }
7089 Wobbe index inferior }
7090 Real Density Kg/m3 }
7095..7110 Response Factor 1..16 used on last run.
7111 Dry superior CV }
7112 Saturated superior CV }
7113 Dry inferior CV }
7114 Saturated inferior CV }
7115 Compressibility Z } primary results from last calibration.
7116 Real Relative density }
7117 Real Density Kg/m3 }
7118 Wobbe index superior }
7119 Wobbe index inferior }
7120 Molar mass }
7121 Un-normalised sum }
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 183 of 395 Issue 7

Modbus Register Gas Component
7001 C6+
7002 C3
7003 IC4
7004 NC4
7005 IC5
7006 NC5
7007 N2
7008 C1
7009 CO2
7010 C2
70?? NeoC5


J3.J.J Alarm Status Bits
Registers 3046 and 3047 contain the following alarm information.


Bit Register 3046 Register 3047
0 Spare Power Fail
1 Spare Response Factor % Deviation
2 Analogue/Digital Convertor 1 low Pre-amp Failure
3 Analogue/Digital Convertor 1 high Adjust Pre-amp
4 Analogue/Digital Convertor 2 low Spare
5 Analogue/Digital Convertor 2 high Spare
6 Spare Spare
7 Spare Spare
8 Digital/Analogue Convertor 1 low Spare
9 Digital/Analogue Convertor 1 high Spare
10 Digital/Analogue Convertor 2 low Spare
11 Digital/Analogue Convertor 2 high Spare
12 Digital/Analogue Convertor 3 low Spare
13 Digital/Analogue Convertor 3 high Spare
14 Analyser Failure Spare
15 Checksum Failure Spare
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 184 of 395 Issue 7

J3.J.2 Component codes

The following lists the component codeswhich are used in Modbus registers 3001..3032

Code Component Name Code Component Name
100 Methane 126 Air
101 Ethane 127 i-Butene
102 Propane 128 Butene-1
103 i-Butane 129 C4=1
104 n-Butane 130 Trans-2-butene
105 i-Pentane 131 CIS-2-Butene
106 n-Pentane 132 Butenes
107 neo-Pentane 133 Butanes
108 C6+ 47/35/17 134 1,3-Butadiene
109 C6+ 50/50/00 135 1,2-Butadiene
110 C6+ 50/25/25 136 Ethylene oxide
111 C6+ 57/28/14 137 1-Pentene
112 Hydrogen 138 not used
113 Helium 139 n-Hexane
114 Nitrogen 140 H2S
115 Carbon Monoxide 141 CS2
116 Oxygen 142 Not used
117 Carbon Dioxide 143 Sulphur dioxide
118 N2O 144 Water
119 n-Nonane 145 n-Heptane
120 n-Octane 146 Argon
121 Ethylene 147 C3+
122 Acetylene 148 C4+
123 Propylene 149 C5+
124 Propadiene 150 User defined component, index # 1
125 n-Decane 151..
165
User defined components, indices 215


J3.2 Analyser Control.
The analyser controller provides register 9030 to enable status to be read and controlled.

The mode values READ from register 9030 are:
0 - idle
1 - in automatic sequencing mode.
2 - running in single stream mode
3 - calibrating.
4 - warm starting, running confidence tests.

The commands WRITTEN to register 9030 are:
0 - Halt at the end of the current analysis
1 - start automatic sequencing mode
2 - start a normal calibration, on first calibration stream
3 - run single analysis on stream 1, then halt
4 - run continually on stream 1.
5 - run a single analysis on stream 2,then halt
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 185 of 395 Issue 7
6 - run continually on stream 2.
7 - run a single analysis on stream 3, then halt
8 - run continually on stream 3.
9 - run a single analysis on stream 4, then halt
10 - run continually on stream 4.
11 - run a single analysis on stream 5, then halt
12 - run continually on stream 5.

Commands 1..12 above are with 60 secs purge.

Adding 20 to any command means 'no purge', if relevant.
These writes are done using Modbus functions 6 or 16.
Except for commands 0 and 2, the analyser must be idle.
If a command fails because the GC was not idle, or because the code is invalid, or the stream is not
used, a Modbus exception "illegal data value" will be returned.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 186 of 395 Issue 7

J3.3 Modbus Communications
A Modbus port is configured on each supervisory computer for connection to the DCS.
The main Data transfer is metering data from the supervisory to the DCS, condensate compositions will
be downloaded from the DCS to the supervisory computers.

The transport layer of the protocol is configured as follows:
Protocol Modbus RTU (subset)
Link security Read / Write
Alderley computer is Slave ID 1
Hardware format RS-232
Handshaking Xon Xoff
Baud rate 9600
Data bits 8
Parity None
Start bits 1
Stop bits 1

Please refer to the rest of this section for details of the way in which the Modbus protocol with
Alderley Controls Ltd extensions allows this interface to transport data in a variety of formats,
including 32 and 64 bit.
Data may be polled via the serial link at any time. The Modbus codes supported are:
Code Description
01 Master read group of logic coils from Flow Computer
02 Master read input status from Flow Computer
03 Master read multiple registers from Flow Computer
04 Unused
05 Master write single coil to Flow Computer
06 Master write single register to Flow Computer
07 Unused
08 Link Test (limited support - see note)
09 15 Unused
16 Master write multiple registers
17 22 Unused

All unused codes are correctly handled as defined in PI-MBUS-300. Function code 08 fully supports
diagnostic code 00, and provides limited support for diagnostic code 02. As the master devices are not
permitted to write data, codes 05, 06, and 16 are ignored.
J3.3.J Iloating point formats
As most data is in engineering units, the 16-bit integers normally provided by Modbus are inadequate
to represent it. The implementation therefore has facilities to map data to Modbus using IEEE 754 floating
point formats
Each high precision data point maps to a group of distinct Modbus points. The flow computers freeze
data occupying multiple 16-bit registers during each multiple read command (function code 03). This
ensures that registers read using one multiple read command are coherent. It is the responsibility of the
clients computer system to reassemble received 16-bit registers into 32-bit or 64-bit data as appropriate.
On no account should registers read in separate multiple read commands be assembled together.
Floating point data are grouped within the Modbus address space according to type, as follows:
40,001 - 42,000 16-bit integers
43,001 - 47,000 32-bit floats
47,001 - 49,999 64-bit floats (doubles)

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 187 of 395 Issue 7
J3.3.2 Double precision format
This format can represent numbers up to about 10
308
to a resolution of approximately sixteen digits. It
consists of a sign bit, 11-bit exponent offset by 1023 and 52-bit mantissa with implicit leading 1 - that
is:
7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0
S|EXP | MANTISSA
FIRST BYTE SECOND BYTE THIRD BYTE FOURTH BYTE
7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0
MANTISSA
FIFTH BYTE SIXTH BYTE SEVENTH BYTE EIGTH BYTE

The first and second bytes are mapped to a lower numbered Modbus register, the third and fourth to the
next (logically distinct) Modbus register in sequence, and so on to a total of four registers.
J3.3.3 Single precision format
This format can represent numbers up to about 10
38
to a resolution of approximately seven digits. It
consists of a sign bit, 8-bit exponent offset by 126 and a 23-bit mantissa with implicit leading 1, that is:
7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0 7-6-5-4-3-2-1-0
S|EXP | MANTISSA
FIRST BYTE SECOND BYTE THIRD BYTE FOURTH BYTE

The first and second bytes are mapped to a lower numbered Modbus register, and the third and fourth
to the next (logically distinct) Modbus register in sequence.
J3.3.4 Iloating point examples
The following block consists of three numbers: zero, -1, and 100.1, in that order as single precision
floating point values:

43001 0x0000
43002 0x0000
43003 0xBF80
43004 0x0000
43005 0x42C8
43006 0x3333

The same numbers, in the same order, are represented as double precision floating point values thus:

47001 0x0000
47002 0x0000
47003 0x0000
47004 0x0000
47005 0xBFF0
47006 0x0000
47007 0x0000
47008 0x0000
47007 0x4059
47008 0x0666
47009 0x6666
47010 0x6667

Note that single and double precision numbers are, by Alderley convention, stored in separate address
ranges.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 188 of 395 Issue 7
J3.3.S DCS Modbus Registers

Process Data

Description of Data Register Function
Gas Stream 1 Differential Pressure 43001 F03
Gas Stream 1 Pressure 43003 F03
Gas Stream 1 Temperature 43005 F03
Gas Stream 1 Line Density 43007 F03
Gas Stream 1 Base Density 43009 F03
Gas Stream 1 Calorific Value 43011 F03
Gas Stream 1 Mass Flowrate 43013 F03
Gas Stream 1 Standard Volume Flowrate 43015 F03
Gas Stream 1 Energy Flowrate 43017 F03

Gas Stream 2 Differential Pressure 43019 F03
Gas Stream 2 Pressure 43021 F03
Gas Stream 2 Temperature 43023 F03
Gas Stream 2 Line Density 43025 F03
Gas Stream 2 Base Density 43027 F03
Gas Stream 2 Calorific Value 43029 F03
Gas Stream 2 Mass Flowrate 43031 F03
Gas Stream 2 Standard Volume Flowrate 43033 F03
Gas Stream 2 Energy Flowrate 43035 F03

Gas Stream 3 Differential Pressure 43037 F03
Gas Stream 3 Pressure 43039 F03
Gas Stream 3 Temperature 43041 F03
Gas Stream 3 Line Density 43043 F03
Gas Stream 3 Base Density 43045 F03
Gas Stream 3 Calorific Value 43047 F03
Gas Stream 3 Mass Flowrate 43049 F03
Gas Stream 3 Standard Volume Flowrate 43051 F03
Gas Stream 3 Energy Flowrate 43053 F03

Gas Station Mass Flowrate 43055 F03
Gas Station Standard Volume Flowrate 43057 F03
Gas Station Energy Flowrate 43059 F03

Back Up Gas Stream 1 Differential Pressure 43061 F03
Back Up Gas Stream 1 Pressure 43063 F03
Back Up Gas Stream 1 Temperature 43065 F03
Back Up Gas Stream 1 Line Density 43067 F03
Back Up Gas Stream 1 Base Density 43069 F03
Back Up Gas Stream 1 Calorific Value 43071 F03
Back Up Gas Stream 1 Mass Flowrate 43073 F03
Back Up Gas Stream 1 Standard Volume Flowrate 43075 F03
Back Up Gas Stream 1 Energy Flowrate 43079 F03

Back Up Gas Stream 2 Differential Pressure 43081 F03
Back Up Gas Stream 2 Pressure 43083 F03
Back Up Gas Stream 2 Temperature 43085 F03
Back Up Gas Stream 2 Line Density 43087 F03
Back Up Gas Stream 2 Base Density 43089 F03
Back Up Gas Stream 2 Calorific Value 43091 F03
Back Up Gas Stream 2 Mass Flowrate 43093 F03
Back Up Gas Stream 2 Standard Volume Flowrate 43095 F03
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 189 of 395 Issue 7
Back Up Gas Stream 2 Energy Flowrate 43097 F03

Back Up Gas Stream 3 Differential Pressure 43099 F03
Back Up Gas Stream 3 Pressure 43101 F03
Back Up Gas Stream 3 Temperature 43103 F03
Back Up Gas Stream 3 Line Density 43105 F03
Back Up Gas Stream 3 Base Density 43107 F03
Back Up Gas Stream 3 Calorific Value 43109 F03
Back Up Gas Stream 3 Mass Flowrate 43111 F03
Back Up Gas Stream 3 Standard Volume Flowrate 43113 F03
Back Up Gas Stream 3 Energy Flowrate 43115 F03

Buy Back Gas Stream Differential Pressure 43117 F03
Buy Back Gas Stream Pressure 43119 F03
Buy Back Gas Stream Temperature 43121 F03
Buy Back Gas Stream Line Density 43123 F03
Buy Back Gas Stream Base Density 43125 F03
Buy Back Gas Stream Calorific Value 43127 F03
Buy Back Gas Stream Mass Flowrate 43129 F03
Buy Back Gas Stream Standard Volume Flowrate 43131 F03
Buy Back Gas Stream Energy Flowrate 43133 F03

Condensate Stream 1 Pressure 43135 F03
Condensate Stream 1 Temperature 43137 F03
Condensate Stream 1 Line Density 43139 F03
Condensate Stream 1 Base Density 43141 F03
Condensate Stream 1 Gross Volume Flowrate 43143 F03
Condensate Stream 1 Standard Volume Flowrate 43145 F03
Condensate Stream 1 Mass Flowrate 43147 F03

Condensate Stream 2 Pressure 43149 F03
Condensate Stream 2 Temperature 43151 F03
Condensate Stream 2 Line Density 43153 F03
Condensate Stream 2 Base Density 43155 F03
Condensate Stream 2 Gross Volume Flowrate 43157 F03
Condensate Stream 2 Standard Volume Flowrate 43159 F03
Condensate Stream 2 Mass Flowrate 43161 F03

Condensate Station Gross Volume Flowrate 43163 F03
Condensate Station 2 Standard Volume Flowrate 43165 F03
Condensate Station 2 Mass Flowrate 43167 F03

Condensate Stream 1 Status 43169 F03
Condensate Stream 2 Status 43171 F03
Prover Status 43173 F03
Gas Stream 1 Status 43175 F03
Gas Stream 2 Status 43177 F03
Gas Stream 3 Status 43179 F03
Buy Back Gas Stream Status 43181 F03
Back Up Gas Stream Status 43183 F03




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 190 of 395 Issue 7


Stream / Prover Status Definitions
The stream and prover statuses are represented in the Modbus registers as follows:

Status Modbus Value
On-Line 0
Off-Line 1
Disabled 2
Maintenance 3
Proving 4
By-Pass 5
Batch 6
Back Flow 7
Spare 8
Valves Illegal 9
Unhealthy 10
Telemetry Fail 11




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 191 of 395 Issue 7

Totals

Description of Data Register Function
Gas Stream 1 Cumulative Mass Total 47001 F03
Gas Stream 1 Cumulative Standard Volume Total 47005 F03
Gas Stream 1 Cumulative Energy Total 47009 F03

Gas Stream 2 Cumulative Mass Total 47013 F03
Gas Stream 2 Cumulative Standard Volume Total 47017 F03
Gas Stream 2 Cumulative Energy Total 47021 F03

Gas Stream 3 Cumulative Mass Total 47025 F03
Gas Stream 3 Cumulative Standard Volume Total 47029 F03
Gas Stream 3 Cumulative Energy Total 47037 F03

Back Up Gas Stream 1 Cumulative Mass Total 47041 F03
Back Up Gas Stream 1 Cumulative Standard Volume Total 47045 F03
Back Up Gas Stream 1 Cumulative Energy Total 47049 F03
Back Up Gas Stream 2 Cumulative Mass Total 47053 F03
Back Up Gas Stream 2 Cumulative Standard Volume Total 47057 F03
Back Up Gas Stream 2 Cumulative Energy Total 47061 F03
Back Up Gas Stream 3 Cumulative Mass Total 47065 F03
Back Up Gas Stream 3 Cumulative Standard Volume Total 47069 F03
Back Up Gas Stream 3 Cumulative Energy Total 47073 F03

Buy Back Cumulative Mass Total 47077 F03
Buy Back Cumulative Standard Volume Total 47081 F03
Buy Back Cumulative Energy Total 47085 F03

Gas Station Cumulative Mass Total 47089 F03
Gas Station Cumulative Standard Volume Total 47093 F03
Gas Station Cumulative Energy Total 47097 F03

Condensate Stream 1 Cumulative Gross Volume Total 47101 F03
Condensate Stream 1 Cumulative Standard Volume Total 47105 F03
Condensate Stream 1 Cumulative Mass Total 47109 F03

Condensate Stream 2 Cumulative Gross Volume Total 47103 F03
Condensate Stream 2 Cumulative Standard Volume Total 47107 F03
Condensate Stream 2 Cumulative Mass Total 47111 F03

Condensate Station Cumulative Gross Volume Total 47115 F03
Condensate Station Cumulative Standard Volume Total 47119 F03
Condensate Station Cumulative Mass Total 47123 F03



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 192 of 395 Issue 7
J3.3.6 Digital Status Signals
Digital status signals are represented as single bits where 1 represents a true condition or alarm
condition.
For the local remote signals 0 =Local, 1 =Remote

For the valve status:

Status Modbus Value
Illegal 0
Open 1
Closed 2
Moving Open 3
Moving Closed 4
Closed / leak 5
Forward 6
Reverse 7
Moving Forward 8
Moving Reverse 9
Forward / leak 10
Reverse /leak 11

In the table above,
Bits 0-5 refer to a stream MOV and bit 0 and bits 6-11 refer to the 4-way valve.

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 193 of 395 Issue 7


Description of Data Register Function
Gas Stream 1 MOV 2611 Status 43185 F03
Gas Stream 1 MOV 2612 Status 43187 F03
Gas Stream 1 MOV 2613 Status 43189 F03
Gas Stream 1 MOV 2614 Status 43191 F03

Gas Stream 2 MOV 2621 Status 43193 F03
Gas Stream 2 MOV 2622 Status 43195 F03
Gas Stream 2 MOV 2623 Status 43197 F03
Gas Stream 2 MOV 2624 Status 43199 F03

Gas Stream 3 MOV 2631 Status 43201 F03
Gas Stream 3 MOV 2632 Status 43203 F03
Gas Stream 3 MOV 2633 Status 43205 F03
Gas Stream 3 MOV 2634 Status 43207 F03

Condensate Stream 1 MOV 3211 Status 43209 F03
Condensate Stream 1 MOV 3212 Status 43211 F03
Condensate Stream 1 MOV 3213 Status 43213 F03
Condensate Stream 1 MOV 3214 Status 43215 F03
Condensate Stream 1 MOV 3215 Status 43217 F03
Condensate Stream 1 MOV 3216 Status 43219 F03

Condensate Stream 2 MOV 3221 Status 43221 F03
Condensate Stream 2 MOV 3222 Status 43223 F03
Condensate Stream 2 MOV 3223 Status 43225 F03
Condensate Stream 2 MOV 3224 Status 43227 F03
Condensate Stream 2 MOV 3225 Status 43229 F03
Condensate Stream 2 MOV 3226 Status 43231 F03

Prover 4 Way MOV 3204 Status 43231 F03
Prover Outlet Valve MOV 3201 Status 43233 F03
Prover Outlet Valve MOV 3202 Status 43235 F03

Local /Remote signals

Description of Data Register Function
Gas Stream 1 MOV 2611 Local/Remote 10001 F03
Gas Stream 1 MOV 2612 Local/Remote 10002 F03
Gas Stream 1 MOV 2613 Local/Remote 10003 F03
Gas Stream 1 MOV 2614 Local/Remote 10004 F03
Gas Stream 2 MOV 2621 Local/Remote 10005 F03
Gas Stream 2 MOV 2622 Local/Remote 10006 F03
Gas Stream 2 MOV 2623 Local/Remote 10007 F03
Gas Stream 2 MOV 2624 Local/Remote 10008 F03
Gas Stream 3 MOV 2631 Local/Remote 10009 F03
Gas Stream 3 MOV 2632 Local/Remote 10010 F03
Gas Stream 3 MOV 2633 Local/Remote 10011 F03
Gas Stream 3 MOV 2634 Local/Remote 10012 F03
Condensate Stream 1 MOV 3211 Local/Remote 10013 F03
Condensate Stream 1 MOV 3212 Local/Remote 10014 F03
Condensate Stream 1 MOV 3213 Local/Remote 10015 F03
Condensate Stream 1 MOV 3214 Local/Remote 10016 F03
Condensate Stream 1 MOV 3215 Local/Remote 10017 F03
Condensate Stream 1 MOV 3216 Local/Remote 10018 F03
Condensate Stream 2 MOV 3221 Local/Remote 10019 F03
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 194 of 395 Issue 7
Condensate Stream 2 MOV 3222 Local/Remote 10020 F03
Condensate Stream 2 MOV 3223 Local/Remote 10021 F03
Condensate Stream 2 MOV 3224 Local/Remote 10022 F03
Condensate Stream 2 MOV 3225 Local/Remote 10023 F03
Condensate Stream 2 MOV 3226 Local/Remote 10024 F03
Prover 4 Way MOV 3204 Local / Remote 10025 F03
Prover Outlet MOV3201 Local/Remote 10026 F03
Prover Outlet MOV3202 Local/Remote 10027 F03
Condensate Sample loop Low Flow 10028 F03
Metering Panel Fan Failure 10029 F03

Gas Stream 1 Process Alarm 10030 F03
Gas Stream 1 Input Alarm 10031 F03
Gas Stream 1 System Alarm 10032 F03

Gas Stream 2 Process Alarm 10033 F03
Gas Stream 2 Input Alarm 10034 F03
Gas Stream 2 System Alarm 10035 F03

Gas Stream 3 Process Alarm 10036 F03
Gas Stream 3 Input Alarm 10037 F03
Gas Stream 3 System Alarm 10038 F03

Buy Back Gas Stream Process Alarm 10039 F03
Buy Back Gas Stream Input Alarm 10040 F03
Buy Back Gas Stream System Alarm 10041 F03

Back Up Gas Stream Process Alarm 10042 F03
Back Up Gas Stream Input Alarm 10043 F03
Back Up Gas Stream System Alarm 10044 F03

Condensate Stream 1 Process Alarm 10045 F03
Condensate Stream 1 Input Alarm 10046 F03
Condensate Stream 1 System Alarm 10047 F03

Condensate Stream 2 Process Alarm 10048 F03
Condensate Stream 2 Input Alarm 10049 F03
Condensate Stream 2 System Alarm 10050 F03

Prover Computer Process Alarm 10051 F03
Prover Computer Input Alarm 10052 F03
Prover Computer System Alarm 10053 F03





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 195 of 395 Issue 7
J4 PLC
A Modicon Momentum PLC will be supplied fitted in the metering panel to accept the digital inputs for
the supervisory computer and supply the sample pulse outputs. The PLC will be connected to the
supervisory computers via a single RS 485 serial link.
The cards supplied are:

Momentum Processor 171CCS76000 1
I/O Base Module (16 Digins,16 Digouts) 107ADM35010 1
Connectors 170XTS00100

The signals to be handled are:
Digital Inputs
Condensate Sample loop low flow
Metering Panel Cooling Fan failure
DC PSU 1 failure
DC PSU 2 failure
Security key switch
Alarm Printer failure
Report Printer failure

Condensate sample can 1 10% full
Condensate sample can 1 70% full
Condensate sample can 1 90% full
Condensate sample can 2 10% full
Condensate sample can 2 70% full
Condensate sample can 2 90% full


Digital Outputs

Condensate Sampler Pulse Output
Condensate Sample Can Changeover
Condensate sample Can 1 select
Gas Sampler Pulse Output


Analogue Inputs

Gas Export Sample can percentage full signal


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 196 of 395 Issue 7
J4.J PLC Connection Schedule
PLC
Module
No. 1
Module
type:
170-ADM-350-10-Digital
Input/Digital Output

Terminal
row
Terminal
No.
Tag No. Description PLC
addr.
MODBUS
addr.
1 1 FSL-3204 Condensate Sample Loop Flow
Low
100001 10001
1 2 Metering Panel Cooling Fan
Failure
100002 10002
1 3 DC PSU 1 Failure 100003 10003
1 4 DC PSU 2 Failure 100004 10004
1 5 Security Keyswitch 100005 10005
1 6 Alarm Printer Failure 100006 10006
1 7 Report Printer Failure 100007 10007
1 8 #1 Condensate Can 10% full 100008 10008
1 9 #1 Condensate Can 70% full 100009 10009
1 10 #1 Condensate Can 90% full 100010 10010
1 11 #2 Condensate Can 10% full 100011 10011
1 12 #2 Condensate Can 70% full 100012 10012
1 13 #2 Condensate Can 90% full 100013 10013
1 14 SpareDig.In 100014 10014
1 15 SpareDig.In 100015 10015
1 16 SpareDig.In 100016 10016
2 1 XMP 3201 Condensate Sampler Pulse
Output
000001 00001
2 2 XMP 2601 Gas Sampler Pulse Output 000002 00002
2 3 Condensate Sample Pump
Running
000003 00003
2 4 Condensate Sample Can #1
selected
000004 00004
2 5 Condensate Sample Can #2
selected
000005 00005
2 6 Start standby Condensate
Sample Pump
000006 00006
2 7 SpareDig.Out 000007 00007
2 8 SpareDig.Out 000008 00008
2 9 SpareDig.Out 000009 00009
2 10 SpareDig.Out 000010 00010
2 11 SpareDig.Out 000011 00011
2 12 Spare DigOut 000012 00012
2 13 SpareDig.Out 000013 00013
2 14 SpareDig.Out 000014 00014
2 15 SpareDig.Out 000015 00015
2 16 SpareDig.Out 000016 00016
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 197 of 395 Issue 7

PLC
Module
No. 2
Module
type:
170-AAI-030-00-Analogue Input

Channel Tag No. Description PLC
addr.
MODBUS
addr.
1 Gas Sample Can Percentage Full 300001 40013
2 Spare An.In 300002
3 Spare An.In 300003
4 Spare An.In 300004
5 Spare An.In 300005
6 Spare An.In 300006
7 Spare An.In 300007
8 Spare An.In 300008

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 198 of 395 Issue 7

Modbus
Addresses

Tag No. Description MODBUS
addr.
Data
Type
Condensate Run 10020 BOOL
Condensate System Running 00020 BOOL
Condensate Pulse time (mS) 40025 INT
Condensate Minimum Interval time (mS) 40026 INT
Condensate Requested Count 40015 REAL
Condensate Sample Count 40017 REAL
Condensate Reset 10021 BOOL
Condensate Sample Can #1 select 10024 BOOL
Condensate Sample Can #2 select 10025 BOOL

Gas Run 10022 BOOL
Gas System Running 00022 BOOL
Gas Pulse time (mS) 40030 INT
Gas Minimum Interval time (mS) 40031 INT
Gas Requested Count 40019 REAL
Gas Sample Count 40021 REAL
Gas Sample Can Percentage Full 40013 REAL
Gas Reset 10023 BOOL


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 199 of 395 Issue 7
JS SAMPLL LOOP P& ID CON1ROLLLR
A three term, proportional, integral and derivative controller is mounted on the front of the metering
panel and is used to control the flow in the condensate sample loop in accordance with the flow in the
main condensate metering run.
The flow controller is a Eurotherm 2604.
An analogue input is provided from a flow measurement device in the sample loop that is used as the
process variable.
The controller set point is provided by an analogue output representing gross volume flowrate from
each of the condensate S600 flowcomputers. The Eurotherm controller automatically selects the on-line
S600 analogue output as the set point.
A 4-20mA output is provided from the controller to the flow control valve situated in the sample loop.

Configuration of the controller parameters is performed from the front panel of the controller.
A dual 5 digit display and a 2 line LCD panel are incorporated in the front of the controller.


Sample Loop Flow Controller Block Diagram










































PV
DP
Multiplier
PID
Analogue
Output
4-20mA
High
Select
Range
Range
Str 1 Flow
4-20mA
Str 2 Flow
4-20mA
Sample loop flow FT 3204
FV 3204
0.19884
Variable set point
Process variable
F/rate =0.2 x DP
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 200 of 395 Issue 7


JS.J Connection Schedule


Controller Terminal Service
4-20mA Input 1 V+ Sample Loop Flow Transmitter FT 3204 analoge input
4-20mA Input 1 V- Sample Loop Flow Transmitter FT 3204 analoge input
4-20mA Input 2 1C Condensate Stream 1 G Vol Flowrate DAC2
4-20mA Input 2 1D Condensate Stream 1 G Vol Flowrate DAC2
4-20mA Input 3 3C Condensate Stream 2 G Vol Flowrate DAC2
4-20mA Input 3 3D Condensate Stream 2 G Vol Flowrate DAC2
4-20mA Output 4A Sample Loop Flow Control Valve FV 3204
4-20mA Output4B Sample Loop Flow Control Valve FV 3204

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 201 of 395 Issue 7
J6 VALIDA1ION SYS1LM
A stand-alone validation system is supplied installed on a desk top P.C. to be housed in the control
room. The PC has access to the system report printer via the automatic printer switch.

J6.J
In order to avoid mismeasurement introduced by poor instrument performance it is necessary to ensure
the highest level of 'Instrument Management'. KIMS ensures effective instrument management.
KIMS is a Windows based software tool which facilitates short and long term logging, trending,
scheduling and archiving of critical data generated whilst performing necessary instrument calibration
routines.
Not concerned solely with instrumentation, KIMS is also used to record critical data associated with
computational and calibrating devices utilised during calibration routines such as flow computers,
PLC's, dead weight testers, resistive devices, etc.
A fully self contained package, KIMS significantly reduces the arduous documentation and
recording activities invariably associated with efficient management of critical instrumentation (and
associated test equipment).
On completion of calibration routines and associated data collection, collating and logging exercises
KIMS allows the user to print a fully formatted and detailed report and calibration certificates.
Calibration data archives allows the instant recall of previously stored data and calibration routines
facilitating long term monitoring and data trending of critical instrumentation.
The scheduling of instrument maintenance and calibration routines is one of the many main functions
of KIMS. The Scheduler facility alerts personnel of the imminent approach of critical
instrumentation re-calibration and / or maintenance routines.
KIMS Test equipment management facility allows personnel to quickly define calibration routine
equipment requirements, availability, and operational status. This facility ensures efficiency in
preparatory tasks associated with critical instrument calibration routines.


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 202 of 395 Issue 7
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 203 of 395 Issue 7
J7 OII-LINL ML1LRING P.C.
The SK10 Sales Agreement outlines a requirement for the offline re-calculation of the condensate
liquid stream gas heat content and liquid volume every 14 days. This shall be achieved by installing an
off-line metering PC and associated software connected to the metering system LAN. The off-line
calculations will be performed on historical daily mass totals provided by the Metering Supervisory
Computer System. Mole% composition data is provided from the laboratory analysis of a product
sample and this data is then used to produce adjusted reports. The purpose of this PC will be to perform
the off-line calculations based on the composition of the liquid sample.
A single desktop personal computer will be connected to the metering system LAN via UTP CAT5
cabling. The existing network laser printer will be utilised for report printing.
The Metering Supervisory Computer will be modified to provide a database of historic hourly mass
flow values for the previous 90-day period. This data will be available via the network to the offline
calculation software. The provided software will then calculate, for the requested period (normally 14
days), the individual component mass totals based upon the entered laboratory composition data. From
these interim values, and provided physical component constants, the daily gas components Heat
Content and the liquid component volume of the condensate shall be calculated.
A report will be produced for each day within the requested period, a totalised report shall also be
produced for this requested period (normally bi-weekly). The reports (both of the same format) shall
contain the following data.
Total daily mass
Mole% of Components N2, CO2, C1, C2, C3, iC4, nC4, iC5, nC5, neo-C5 and C6+.
Mass of Components C1, C2, C3, iC4, nC4, iC5, nC5, neo-C5 and C6+.
Heating value of C1, C2, C3 and C4 components.
Liquid volume of C5+ components.
The daily and period (normally bi-weekly) totalised reports generated shall be stored on the Metering
Supervisory Computers for a period of 90 days.
Data from the laboratory analysis will be provided in electronic format on floppy disk for updating the
daily reports and creating the periodic report on the offline system. The format of the template and
data on this disk will be defined by mutual agreement prior to development. The template will also be
used to enter the laboratory determined density and volume conversion factor (see extract table from
GPA Standard 8173-94, page 2 Schedule H).
Provision will be made within the software to manually enter composition for any period. All values
that are manually entered will be highlighted on subsequent reports based upon the information.
In normal operation the operator will receive a composition disk from the laboratory and insert this into
the offline calculation computer. The data from the composition disk shall be downloaded to the
calculation software. From within the application the operator will select the range of dates to which
the data is to be applied and request data is printed. Reports will be printed on the network laser
printer.
If no disk is inserted the user will be prompted to ask if he wants to use previous data for composition,
if he accepts the reports will be generated using the data from the previous disk.
The application will include a facility for manual entry of composition data, if data is entered in this
way this will be identified on the report.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 204 of 395 Issue 7

J7.J Iunctions
The functions of the Off-Line metering PC include:

To provide operator interface for data entry and display

To accept composition data entry from laboratory analysis via 3floppy disc

To provide the facility for manual entry of laboratory data

To communicate with the metering system supervisory PC via the network and receive
condensate daily mass totals (06:00 and 24:00)

To calculate the daily mass totals, heat content and standard volume on a component basis for
a specified period based on the laboratory analysis data.

To compile and print reports on the system printer

J7.2 Laboratory Data
The laboratory data will be entered in to the Off line metering PC either manually or via a pre-
formatted floppy disc.
The data on the floppy disc shall be in the form of a comma separated variable file as follows:
Date of analysis DD/MM/YY,
Mol % of C1 component 123.1234,
Mol % of C2 component 123.1234,
Mol % of C3 component 123.1234,
Mol % of iC4 component 123.1234,
Mol % of nC4 component 123.1234,
Mol % of iC5 component 123.1234,
Mol % of nC5 component 123.1234,
Mol % of neoC5 component 123.1234,,
Mol % of C6+ components 123.1234,
Density of iC5 (kg/m3) 123.123,
Density of nC5 (kg/m3) 123.123,
Density of neoC5 (kg/m3) 123.123,
Density of C6+ (kg/m3) 123.123
Volume conversion factor iC5 (m3 to bbl) 1.123,
Volume conversion factor nC5 (m3 to bbl) 1.123,
Volume conversion factor neoC5 (m3 to bbl) 1.123,
Volume conversion factor C6+ (m3 to bbl) 1.123,
Mol mass of component C6+ (kg/kg-mol) 1.123,
Heating Value C6+ (Mj/kg) 123.123,

Notes:
Densities for iC5, nC5 and neo C5 are at standard conditions of 15
o
C and 1.01325 bara. Standard
density for Isopentane and n-Pentane is retrieved from GPA Standard 2145-00. Standard density for
Neopentane is retrieved from GPSA Engineering Data Book (11
th
Edition 1998).
Density of C6+ is to be derived from laboratory analysis (every 3 to 6 months) by using flash
separation and gas chromatography method and calculated by GPA Standard 2186-02.
Conversion factors for iC5, nC5 and neoC5 for volume from m
3
at 15
o
C, 1.01325 bara to Barrel at 60
o
F at one atmosphere pressure (ASTM D-1250: IP200, Table 52)
Conversion factor far C6+ volume shall be determined based on density of Hexane Plus using (ASTM
D-1250: IP200, Table 52)
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 205 of 395 Issue 7

J7.3 Condensate Calculations

J7.3.J Symbols Used in Calculations

Symbol Description
MW
mix
Total molecular weight
X
j
Component Mol fraction
M
j
Component Mol mass
Q
mj
Component mass total
Q
m
Daily mass total of mixture
Q
m(C1-C4)
Daily mass total for C1-C4
Q
Ej
Component energy total
H
j
Component mass based CV
Q
Ej(C1-C4)
Daily energy total for C1-C4
Q
e MMBtuC1-C4
Daily energy total for C1-C4 in MMBtu
Q
S(C5+)
Daily standard volume total C5+

j
Component base density
Q
mjiC5
iC5 mass total
Q
mjnC5
nC5 mass total
Q
mjneoC5
neo C5 mass total
Q
mjC6+
C6+ mass total

iC5
iC5 base density

nC5
nC 5 base density

neoC5
neo C5 base density

C6+
C6+ base density

The gross heating value of the liquid components C1-C4 is to be calculated when the
composition is known.
J7.3.2 Mass total of Components CJ-C4
The daily total mass for components C1-C4 is calculated by the sum of the total mass
multiplied by the component molecular weight and the mass fraction and dividing by the total
molecular weight.
j j mix
M X MW =
Where:
X
j
= Component Mol Fraction = Component Mol % x 0.01
M
j
= Component Mol Mass
m j mj
Q Mf Q =

mix
j
j
MW
M Xj
Mf

=

4
1
) 4 1 (
C
C
mj C C m
Q Q

J7.3.3 Lnergy 1otal of Liquid CJ-C4(GJ)
The energy total of the separated gas C1-C4 will be calculated:
j mj Ej
H Q Q =
Where:
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 206 of 395 Issue 7
H
j
= Component Heating Value table following this section

4
1
) 4 1 (
C
C
Ej C C E
Q Q


The Gross Heating Values (Mass Based) of the individual components shall be taken from the
values specified in the following table:
Component Hj(MJ/kg) Mj(kg/kg-mol)
Methane 55.575 16.043
Ethane 51.950 30.070
Propane 50.368 44.097
n-Butane 49.546 58.123
Isobutane 49.388 58.123
n-Pentane N/A 72.150
Isopentane N/A 72.150
Neopentane N/A 72.150
Hexane Plus N/A (Note)
Nitrogen N/A 28.0134
Carbon N/A 44.010
Dioxide

Note: The figures for Hexane Plus shall be obtained by sampling and analysis in
accordance with flash separation and gas chromatograph method.
J7.3.4 Lnergy of Liquid (MMbtu)
The energy for C1-C4 liquid is converted to MMBtu
12 . 1055
) 4 1 (
4 1
C C Ej
C eMMBtuC
Q
Q

=



J7.3.S Std Volume total of Components CS+
The standard volume is calculated by dividing the mass totals of each by the base density of
each component
The following calculations are performed for components, nC5, iC5, neo C5 and C6+
j j mix
M X MW =
Where:
X
j
= Component Mol Fraction = Component Mol % x 0.01
M
j
= Component Mol Mass
1000 =
m j mj
Q Mf Q

mix
j
j
MW
M Xj
Mf

=

and,
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 207 of 395 Issue 7

+
+
=
6
5
) 5 (
C
ic
j
mj
C s
Q
Q



=
+
+
+ + +
6
6
5
5
5
5
5
5
C
mC
neoC
mneoC
nC
mnC
iC
miC
Q Q Q Q





The volume of Condensate and Natural Gas Liquid, C5+ in Liquid Stream shall be calculated
and tabulated as below.

Components Mass (kg) (note 4) Density
kg/m
3

(note 1)
volume in
m
3


Factor
(note 2)
Vc in
Barrel
(note 5)
Isopentane 624.35

6.295

n-Pentane
631.00 6.295
Neopentane 596.70 6.296
Hexane
Plus
(liquid)

(note 3)

Note 1: At standard conditions of 15
o
C and 1.01325 bara. Standard component density to be retrieved
from GPA Standard 2145-92.
Note 2: Conversion factor for volume from m
3
at 15
o
C, 1.01325 bara to barrel at 60
o
F at one
atmosphere pressure (ASTM D-2150)
Note 3: Density to be measured/calculated by laboratory analysis.
Note 4: Component mass of Liquid Stream shall be provided by incorporating the data from
laboratory analysis of sample. .
Note 5: V
c
equal to volume of Condensate and Natural Gas Liquid in barrel.
J7.4 Reports
At operator request a daily report will be printed for each day of the period covered by the
laboratory analysis. A daily report is compiled for each reporting period 06:00 to 06:00 and
24:00 to 24:00. The reports will be stored on the PC hard drive for a period of up to ninety
days and the facility will be provided to select stored reports for printing. The reports will be
printed on the existing system printer.
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 208 of 395 Issue 7

J7.4.J Report Iormat
Helang Central Platform
Condensate Export Metering System
Corrected Daily Report for DD/MM/YY
Base Time : 06:00


Laboratory Data

Mol % C1 123.123
Mol % C2 123.123
Mol % C3 123.123
Mol % iC4 123.123
Mol % nC4 123.123
Mol % iC5 123.123
Mol % nC5 123.123
Mol % neoC5 123.123
Mol % C6+ 123.123
Density iC5 (kg/m3) 123.123
Density nC5 (kg/m3) 123.123
Density neoC5
(kg/m3)
123.123
Density C6+ (kg/m3) 123.123
VCF iC5 (m3 to bbl) 1.123
VCF nC5 (m3 to bbl) 1.123
VCF neoC5 (m3 to
bbl)
1.123
VCF C6+ (m3 to bbl) 1.123
Mol mass C6+ (kg/kg-mol) 1.123
Heating Value C6+ (MJ/kg) 123.123

Measured Mass Total
t
123456.123

Calculated Data
Mass
t
Std Volume
Sm3
Std Volume
bbl
Energy
MJ
Energy
MMBTU

C1 123.123 123.123 123.123 123.123 123.123
C2 123.123 123.123 123.123 123.123 123.123
C3 123.123 123.123 123.123 123.123 123.123
iC4 123.123 123.123 123.123 123.123 123.123
nC4 123.123 123.123 123.123 123.123 123.123
iC5 123.123 123.123 123.123 123.123 123.123
nC5 123.123 123.123 123.123 123.123 123.123
neoC5 123.123 123.123 123.123 123.123 123.123
C6+ 123.123 123.123 123.123 123.123 123.123

Total C1-C4 123.123 123.123 123.123 123.123 123.123
Total C5+ 123.123 123.123 123.123 123.123 123.123





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 209 of 395 Issue 7
J8 APPLNDIX

J8.J Ilowcomputer Specification
Note:
Every care has been taken to ensure that the data, specifications and descriptions contained in this
section are accurate but the Company accepts no liability for errors or omissions. Specifications are
likely to change without notice.

Analogue Signal Level: 0-5.125V, 0-22 mA.
Conversion Method: Integrating charge balance, 16 bit method
Resolution Accuracy: +/- 0.005% of FSD at 23 Deg C (Voltage Inputs)
+/- 0.02% of FSD at 23 Deg C (Current Inputs)
Conversion Time: <100 msec per channel
PRT Signal Level: Pt 100 to IEC 751, 4 wire connection, 1mA current source
Measuring Range: -100 Deg C to +200 Deg C
resolution 0.01 Deg C
Resolution:
Accuracy:
+/- 0.1 Deg C
Digital Signal Level: 12V - 30V, opto-isolated
Frequency Signal Level: 3V min pk-pk to 10KHz.
Current Limit: 3mA.
Frequency Range: 0 Hz-10KHz

Flowmeter Signal Level: 3.5-12V
Frequency Range: 0-10Khz
Security Monitoring IP 252/76 (ISO 6551), level A or B
Power Voltage Range: 20-32 V dc, 24 watts nominal
Isolation: Three way galvanically isolated from input to computer,
supply and earth. 240V Flash

Output Specifications
Analogue Signal Level: 0-21mA
Resolution: 12 bit
Accuracy: +/- 0.1% at 23 Deg C
Loop Resistance: 650R max with internal supply, 470-1000R
max with external 24V dc supply
Digital Signal Level: Open collector, 36V max, 100mA max
Frequency Range: dc-2Hz
RAW Pulse Output Signal Level: Open collector, 24 V max, 100mA max
Frequency Range: 0-5KHz
Programmable Pulse Signal Level: Open collector, 36 V max, 100mA max
Frequency Range: dc-500Hz
Alarm Signal Level: C/O relay contact, 30V, 500mA
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 210 of 395 Issue 7
Communications Interface
Serial Ports Interface Standard: RS232, 422, 485.
Baud Rate: 57.6K baud max
Data Protocol: MODBUS RTU/ASCII, ASCII
LAN Interface Type: Ethernet 10baseT
Data Rate: 10 Mb/sec
Computer
Computer Processor: 50Mhz 80486DX2/50 (208 Pin
SQFP)
Memory: 8 Mb DRAM
512K SRAM, battery backed.
4 Mb Flash
Clock: Battery- supported calendar clock
Health Monitor: Hardware watchdog, metering task
software watchdog
Operating System: Wind V2.5
VX Works 5.3.1
System Language: C
Mechanical
Dimensions Front Panel: 85mm (width) x 269mm (height) x
28mm (deep)
Case Depth: 280 mm (+ 50 mm for connectors)
Panel Cut-out: 65 mm x 257 mm (both with +/-
1mm tolerance)
Max Panel Thickness: 10 mm
Weight: 4.3 Kg approx, with single I/O board
configuration.
Construction Structure: Painted, spot welded steel outer case,
plastic front panel.
Access: Allow 300mm clearance directly
behind case for maintenance
Mounting: Self attaches to the panel cut out by
rod operated cams from the rear,
tensioned by two concealed screw-
operated tensioning bars
Display Type: Back lit LCD, 8 lines of 20 characters
Alarm/Status: 3 colour LED, green, amber, red



J8.2 S600 Connection Schedules
J8.2.J Gas/Condensate Ilowcomputer
The following lists all available I/O
Connection schedules for each application are shown in the main body of the manual.
Connector A: Analogue Inputs and Outputs
Connector Type 25 Way D Male

D Pin Signal Tag/Service D Pin Signal Tag/Service
1 DAC 1 Supply +ve 8 ADC 1 +ve
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 211 of 395 Issue 7
14 DAC 1 Output 21 ADC 2 +ve
2 DAC 1 Ground 9 ADC 3 +ve
15 DAC 2 Supply +ve 22 ADC 4 +ve
3 DAC 2 Output 10 ADC 5 +ve
16 DAC 2 Ground 20 Ground
4 DAC 3 Supply +ve 11 ADC 6 +ve
17 DAC 3 Output 24 ADC 7 +ve
5 DAC 3 Ground 12 ADC 8 +ve
18 DAC 4 Supply +ve 25 ADC 9 +ve
6 DAC 4 Output 13 ADC 10 +ve
19 DAC 4 Ground 23 Ground
7

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 212 of 395 Issue 7

Connector B: ADC, PRT , Digital inputs, Pulse inputs and outputs
Connector type 37 Way D Male

D pin Signal Tag/Service D Pin Signal Tag/Service
4 PRT 1 I + 8 ADC 11 +ve
1 PRT 1 V + 7 ADC 12 +ve
21 PRT 1 V - 20 Ground
24 PRT 1 I - 30 Pulse Output 1 +ve
5 PRT 1 2 + 31 Pulse Output 2 +ve
2 PRT 2 V + 32 Pulse Output 3 +ve
22 PRT 2 V - 33 Pulse Output 4 +ve
25 PRT 2 I - 35 Pulse 1-4 Common -ve
6 PRT 3 I + 34 Pulse Output 5 +ve
3 PRT 3 V + 12 Pulse Output 5 ve
23 PRT 3 V - 9 Density Input 1 +ve
26 PRT 3 I - 27 Density Input 1 ve
13 Digital Input 1 ve 10 Density Input 2 +ve
14 Digital Input 2 ve 28 Density Input 2 -ve
15 Digital Input 3 ve 11 Density Input 3 +ve
16 Digital Input 4 ve 29 Density Input 3 -ve
17 Dig In 1-4Common+ve 36 Digital Output 1+ve
18 Digital Input 5 ve 37 Digital Output 2 +ve
19 Digital Input 6 ve

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 213 of 395 Issue 7

Connector C: Digital inputs and outputs, Dual pulse inputs.
Connector type 37 Way D Female

D pin Signal Tag/Service D Pin Signal Tag/Service
19 Digital Input 7 ve 37 Digital Output 3+ve
18 Digital Input 8 ve 36 Digital Output 4 +ve
17 Dig In 5-8 Common +ve 35 Dig Out 1-4 Common -ve
16 Digital Input 9 ve 34 Digital Output 5+ve
15 Digital Input 10 ve 33 Digital Output 6+ve
14 Digital Input 11 ve 32 Digital Output 7+ve
13 Digital Input 12 ve 31 Digital Output 8 +ve
12 Dig In 9-12 Common +ve 30 Dig Out 5-8 Common -ve
11 Digital Input 13 ve 29 Digital Output 9+ve
10 Digital Input 14 ve 28 Digital Output 10+ve
9 Digital Input 15 ve 27 Digital Output 11+ve
8 Digital Input 16 ve 26 Digital Output 12 +ve
7 Dig In 13-16 Common
+ve
25 Dig Out 9-12 Common -ve
6 Not Connected 4 Dual Pulse Ch 1+ve
24 Raw Pulse Output +ve 23 Dual Pulse Ch 1-ve
5 Raw Pulse Output ve 3 Dual Pulse Ch 2+ve
22 Dual Pulse Ch 2-ve
2 Dual Pulse Ch 3+ve
21 Dual Pulse Ch 3-ve
1 Dual Pulse Ch 4+ve
20 Dual Pulse Ch 4-ve

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 214 of 395 Issue 7
Power and Communications


Plug In Terminal Connector TB 1
Pin no: Signal Tag/Service
1 24 Volt DC Input +ve 24 V DC Power
2 24 Volt DC Input -ve 0 V DC Power
3 24 Volt DC Output +ve
4 15 Volt DC Output +ve
5 DC Output -ve
6 N /C Contact Computer Fail Relay
7 Common Contact Computer Fail Relay
8 N/O Contact Computer Fail Relay
15 Way D Connector Comms Ports 1 & 2
Pin no: Signal Tag/Service
1 Ground
2 Front panel Tx
3 Ground
4 Speaker
5 Not Connected
6 Tx
7 RTS
8 Ground
9 Front panel Rx
10 Front panel CTS
11 Ground
12 Not Connected
13 Not Connected
14 Rx
15 CTS

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 215 of 395 Issue 7
Communications 2

RJ 45 Comms Port 3 RS 232
Pin no: Signal Tag/Service
1 Signal ground
2 DTR
3 RTS
4 Tx Data
5 Rx Data
6 CTS
7 DSR
8 DCD
RJ 45 Comms Port 4 RS232
Pin no: Signal Tag/Service
1 Signal ground
2 DTR
3 RTS
4 Tx Data
5 Rx Data
6 CTS
7 DSR
8 DCD
RJ 45 Network
Pin no: Signal Tag/Service
1 Signal ground
2 DTR
3 RTS
4 Tx Data
5 Rx Data
6 CTS
7 DSR
8 DCD

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 216 of 395 Issue 7

Terminal Block 2 Comms Port 5 RS 422/485
Pin no: Signal Tag/Service
1 Rx - Prover Tx-
2 Rx + Prover Tx+
3 Tx - Prover Rx-
4 Tx + Prover Rx+
Terminal Block 2 Comms Port 6 RS 422/485
Pin no: Signal Tag/Service
5 Rx -
6 Rx +
7 Tx -
8 Tx +
Terminal Block 2 Comms Port 7 RS 422/485
Pin no: Signal Tag/Service
9 Rx -
10 Rx +
11 Tx -
12 Tx +
13 Computer Ground


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 217 of 395 Issue 7
J8.2.2 Prover Computer

Connector A: Analogue Inputs and Outputs
Connector Type 25 Way D Male

DPin Signal Tag/Service DPin Signal Tag/Service
1 DAC 1 Supply +ve 8 ADC 1 +ve
14 DAC 1 Output 21 ADC 2 +ve
2 DAC 1 Ground 9 ADC 3 +ve
15 DAC 2 Supply +ve 22 ADC 4 +ve
3 DAC 2 Output 10 ADC 5 +ve
16 DAC 2 Ground 20 Ground
4 DAC 3 Supply +ve 11 ADC 6 +ve
17 DAC 3 Output 24 ADC 7 +ve
5 DAC 3 Ground 12 ADC 8 +ve
18 DAC 4 Supply +ve 25 ADC 9 +ve
6 DAC 4 Output 13 ADC 10 +ve
19 DAC 4 Ground 23 Ground
7


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 218 of 395 Issue 7

Connector B: ADC, PRT , Digital inputs, Pulse inputs and outputs
Connector type 37 Way D Male

Dpin Signal Tag/Service DPin Signal Tag/Service
4 PRT 1 I + 8 ADC 11 +ve
1 PRT 1 V + 7 ADC 12 +ve
21 PRT 1 V - 20 Ground
24 PRT 1 I - 30 Pulse Output 1 +ve
5 PRT 1 2 + 31 Pulse Output 2 +ve
2 PRT 2 V + 32 Pulse Output 3 +ve
22 PRT 2 V - 33 Pulse Output 4 +ve
25 PRT 2 I - 35 Pulse 1-4 Common ve
6 PRT 3 I + 34 Pulse Output 5 +ve
3 PRT 3 V + 12 Pulse Output 5 ve
23 PRT 3 V - 9 Density Input 1 +ve
26 PRT 3 I - 27 Density Input 1 -ve
13 Digital Input 1 ve 10 Density Input 2 +ve
14 Digital Input 2 ve 28 Density Input 2 -ve
15 Digital Input 3 ve 11 Density Input 3 +ve
16 Digital Input 4 ve 29 Density Input 3 -ve
17 Dig In 1-4Common+ve 36 Digital Output 1+ve
18 Digital Input 5 ve 37 Digital Output 2 +ve
19 Digital Input 6 ve

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 219 of 395 Issue 7

Connector C: Digital inputs and outputs, Dual pulse inputs.
Connector type 37 Way D Female

Dpin Signal Tag/Service DPin Signal Tag/Service
19 Digital Input 7 ve 37 Digital Output 3+ve
18 Digital Input 8 ve 36 Digital Output 4 +ve
17 Dig In 5-8 Common +ve 35 Dig Out 1-4 Common -ve
16 Digital Input 9 ve 34 Digital Output 5+ve
15 Digital Input 10 ve 33 Digital Output 6+ve
14 Digital Input 11 ve 32 Digital Output 7+ve
13 Digital Input 12 ve 31 Digital Output 8 +ve
12 Dig In 9-12 Common +ve 30 Dig Out 5-8 Common -ve
11 Digital Input 13 ve 29 Digital Output 9+ve
10 Digital Input 14 ve 28 Digital Output 10+ve
9 Digital Input 15 ve 27 Digital Output 11+ve
8 Digital Input 16 ve 26 Digital Output 12 +ve
7 Dig In 13-16 Common +ve 25 Dig Out 9-12 Common -ve
6 Not Connected 4 Dual Pulse Ch 1+ve
24 Raw Pulse Output +ve 23 Dual Pulse Ch 1-ve
5 Raw Pulse Output ve 3 Dual Pulse Ch 2+ve
22 Dual Pulse Ch 2-ve
2 Dual Pulse Ch 3+ve
21 Dual Pulse Ch 3-ve
1 Dual Pulse Ch 4+ve
20 Dual Pulse Ch 4-ve

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 220 of 395 Issue 7

Connector D: Analogue Inputs and Outputs
Connector Type 25 Way D Male

DPin Signal Tag/Service DPin Signal Tag/Service
1 Raw Pulse Input 1+ve 17 Detector Sw 1 -ve
14 Raw Pulse Input 1-ve 5 Detector Sw 2 -ve
2 Raw Pulse Input 2+ve 18 Detector Sw 3 -ve
15 Raw Pulse Input 2-ve 6 Detector Sw 4 -ve
3 Raw Pulse Input 3+ve 4 Common +ve
16 Raw Pulse Input 3-ve 11 Raw Pulse O/P+ve
8 Phase Lock Loop Input+ 23 Raw Pulse O/P-ve
20 Phase Lock Loop Input- 12 Ground
9 Density 1+ve 13 Ground
21 Density 1-ve 19 Ground
10 Density 1+ve 24 Ground
22 Density 1-ve 25 Ground
7


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 221 of 395 Issue 7

Connector E: Digital inputs, Pulse outputs
Connector type 37 Way D Male

Dpin Signal Tag/Service DPin Signal Tag/Service
13 Dig In 1-ve 31 Pulse Output 1+ve
14 Dig In 2-ve 32 Pulse Output 2+ve
15 Dig In 3-ve 33 Pulse Output 3+ve
16 Dig In 4-ve 34 Pulse Output 4+ve
17 Digin 1-4 Comm + 35 Pulse Common -ve
18 Dig In 5-ve 36 Dig Out 1 +ve
19 Dig In 6-ve 37 Dig Out 2 +ve
1 Dig In 17-ve 20 Dig In 25 -ve
2 Dig In 18-ve 21 Dig In 26 -ve
3 Dig In 19-ve 22 Dig In 27 -ve
4 Dig In 20-ve 23 Dig In 28 -ve
5 Digin 17-20 Comm + 24 Digin 25-28 Comm +
6 Dig In 21-ve 25 Dig In 29 -ve
7 Dig In 22-ve 26 Dig In 30 -ve
8 Dig In 23-ve 27 Dig In 31 -ve
9 Dig In 24-ve 28 Dig In 32 -ve
10 Digin 21-24 Comm + 29 Digin 29-32 Comm +
11
12

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 222 of 395 Issue 7

Connector F: Digital inputs and outputs, Dual pulse inputs.
Connector type 37 Way D Female

Dpin Signal Tag/Service DPin Signal Tag/Service
19 Dig In 7-ve 37 Digital Output 3+ve
18 Dig In 8-ve 36 Digital Output 4 +ve
17 Dig In 5-8 Common +ve 35 Dig Out 1-4 Common -ve
16 Digital Input 9 ve 34 Digital Output 5+ve
15 Digital Input 10 ve 33 Digital Output 6+ve
14 Digital Input 11 ve 32 Digital Output 7+ve
13 Digital Input 12 ve 31 Digital Output 8 +ve
12 Dig In 9-12 Common +ve 30 Dig Out 5-8 Common -ve
11 Digital Input 13 ve 29 Digital Output 9+ve
10 Digital Input 14 ve 28 Digital Output 10+ve
9 Digital Input 15 ve 27 Digital Output 11+ve
8 Digital Input 16 ve 26 Digital Output 12 +ve
7 Dig In 13-16 Common +ve 25 Dig Out 9-12 Common -ve
4 Dual Pulse Channel 1 +ve 24 Phase Loop Lock O/p +ve
23 Dual Pulse Channel 1 -ve 5 Phase Loop Lock O/p -ve
3 Dual Pulse Channel 2 +ve
22 Dual Pulse Channel 2 -ve
2 Dual Pulse Channel 3 +ve
21 Dual Pulse Channel 3 -ve
1 Dual Pulse Channel 4 +ve
20 Dual Pulse Channel 4 -ve



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 223 of 395 Issue 7

Power and Communications



Plug In Terminal Connector TB 1
Pin no: Signal Tag/Service
1 24 Volt DC Input +ve 24 V DC Power
2 24 Volt DC Input -ve 0 V DC Power
3 24 Volt DC Output +ve
4 15 Volt DC Output +ve
5 DC Output -ve
6 N /C Contact Computer Fail Relay
7 Common Contact Computer Fail Relay
8 N/O Contact Computer Fail Relay
15 Way D Connector Comms Ports 1 & 2
Pin no: Signal Tag/Service
1 Ground
2 Front panel Tx
3 Ground
4 Speaker
5 Not Connected
6 Tx
7 RTS
8 Ground
9 Front panel Rx
10 Front panel CTS
11 Ground
12 Not Connected
13 Not Connected
14 Rx
15 CTS


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 224 of 395 Issue 7
Communications 2

RJ 45 Comms Port 3 RS 232
Pin no: Signal Tag/Service
1 Signal ground
2 DTR
3 RTS
4 Tx Data
5 Rx Data
6 CTS
7 DSR
8 DCD
RJ 45 Comms Port 4 RS232
Pin no: Signal Tag/Service
1 Signal ground
2 DTR
3 RTS
4 Tx Data
5 Rx Data
6 CTS
7 DSR
8 DCD
RJ 45 Network
Pin no: Signal Tag/Service
1 Signal ground
2 DTR
3 RTS
4 Tx Data
5 Rx Data
6 CTS
7 DSR
8 DCD


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 225 of 395 Issue 7

Terminal Block 2 Comms Port 5 RS 422/485
Pin no: Signal Tag/Service
1 Rx - Streams Tx-
2 Rx + Streams Tx+
3 Tx - Streams Rx-
4 Tx + Streams Rx+
Terminal Block 2 Comms Port 6 RS 422/485
Pin no: Signal Tag/Service
5 Rx -
6 Rx +
7 Tx -
8 Tx +
Terminal Block 2 Comms Port 7 RS 422/485
Pin no: Signal Tag/Service
9 Rx -
10 Rx +
11 Tx -
12 Tx +
13 Computer Ground


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 226 of 395 Issue 7
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 227 of 395 Issue 7
J9 AS- BUIL1 RLPOR1S
Helang Central Platform
Condensate Export Metering System
Current Report EOD 1 Current Data at 30/06/02 02:47:32

Cumulative Totals
STREAM 1 STREAM 2 STATION


Mass t 0.000 128.213 128.213
Std Volume Sm 0.000 157.426 157.426
Std Volume bbl 0.000 990179.719 990179.719
Gross Volume m 0.000 161.543 61.543

Current Day Totals

Mass t 0.000 128.375 128.375
Std Volume Sm 0.000 157.426 157.426
Std Volume bbl 0.000 990179.719 990179.719
Gross Volume m 0.000 161.747 161.747

Current Process Data

Stream Status Maintenance On-Line

Mass t/h 0.000 181.109 0.000
Std Volume Sm/h 0.000 257.489 0.000
Gross Volume m/h 0.000 259.049 0.000
Pressure barg 34.000* 2.073
Temperature C 44.00* 20.01
Meter Density kg/m 1007.552 699.166
Base Density kg/Sm 1023.191 703.398
K factor pls/m 1010.000 1000.000
M factor 1.000000 1.000000

Flow Weighted Data
Current Day

Pressure barg 0.000 10.828
Temperature C 0.00 21.68
Meter Density kg/m 0.000 728.377
Base Density kg/Sm 0.000 733.123
Std Volume Sm
3
/d 123.123 123.123

Previous Day

Pressure barg 0.000 0.000
Temperature C 0.00 0.00
Meter Density kg/m 0.000 0.000
Base Density kg/Sm 0.000 0.000
Std Volume Sm
3
/d 123.123 123.123


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 228 of 395 Issue 7



Helang Central Platform
Condensate Export Metering System
Period Report EOD 1 Current Data at 30/06/02 04:02:35

Cumulative Totals
STREAM STREAM 2 STATION

Mass 0.000 128.213 128.213
Std Volume Sm 0.000 157.426 157.426
Std Volume bbl 0.000 990179.719 990179.719
Gross Volume m 0.000 161.543 161.543

Period Totals

Mass t 0.000 0.000 0.000
Std Volume Sm 0.000 0.000 0.000
Std Volume bbl 0.000 0.000 0.000
Gross Volume m 0.000 0.000 0.000


Current Process Data

Stream Status On-Line On-Line

Mass t/h 140.747 152.720 0.000
Std Volume Sm/h 140.524 216.927 0.000
Gross Volume m/h 141.026 218.484 0.000
Pressure barg 1.113 0.817
Temperature C 20.86 20.77
Meter Density kg/m 998.017 699.045
Base Density kg/Sm 1001.585 704.058
K factor pls/m 1010.000 1000.000
M factor 1.000000 1.000000

Flow Weighted Data
Current Period

Pressure barg 0.889 4.193
Temperature C 20.45 20.81
Meter Density kg/m 998.034 708.396
Base Density kg/m 1001.356 713.084
Std Volume Sm
3
/d 123.123 123.123

Previous Period

Pressure barg 7.264 2.947
Temperature C 25.74 23.24
Meter Density kg/m 818.793 795.514
Base Density kg/Sm
3
828.153 935.921
Std Volume Sm
3
/d 123.123 123.123

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 229 of 395 Issue 7

Helang Central Platform
Condensate Export Metering System
Daily Report Current Data at 29/06/02 00:00:39

Cumulative Totals
STREAM 1 STREAM 2 STATION

Mass t 771.780 468.299 1240.079
Std Volume Sm 1125.688 583.880 1709.568
Gross Volume m 1001.056 587.076 1588.132
Std Volume bbl 7080364.281 3672494.596 10752858.880


Daily Totals

Mass t 0.718 0.000 0.718
Std Volume Sm 0.907 0.000 0.907
Gross Volume m 0.930 0.000 0.930
Std Volume bbl 5704.858 0.000 5704.858


Current Process Data

Stream Status Valves Illeg Valves Illeg

Mass t/h 0.000 0.000 0.000
Std Volume Sm/h 0.000 0.000 0.000
Gross Volume m/h 0.000 0.000 0.000
Pressure barg 34.000* 36.000*
Temperature C 44.00* 46.00*
Meter Density kg/m 771.518 793.679
Base Density kg/Sm 791.411 814.437
K factor pls/m 100.000 1000.000
M factor 1.000000 1.000000

Flow Weighted Data
Current Day

Pressure barg 0.000 0.000
Temperature C 0.00 0.00
Meter Density kg/m 0.000 0.000
Base Density kg/Sm 0.000 0.000
Std Volume Sm
3
/d 123.123 123.123

Previous Day

Pressure barg 0.000 0.000
Temperature C 0.00 0.00
Meter Density kg/m 0.000 0.000
Base Density kg/Sm 0.000 0.000
Std Volume Sm
3
/d 123.123 123.123

Std Volume flowrates

Daily Average Sm
3
/d 123456.123 123456.123
Daily Minimum Sm
3
/d 123456.123 123456.123
Daily Maximum Sm
3
/d 123456.123 123456.123
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 230 of 395 Issue 7


Helang Central Platform
Condensate Export Metering System
Weekly Report EOD 1 Current Data at 09/06/02 17:02:50

Cumulative Totals
STREAM 1 STREAM 2 STATION

Mass t 123.123 123.123 123.123
Std Volume Sm 123.123 123.123 123.123
Std Volume bbl 123.123 123.123 123.123
Gross Volume m 123.123 123.123 123.123

Weekly Totals

Mass 123.123 123.123 123.123
Std Volume Sm 123.123 123.123 123.123
Std Volume bbl 123.123 123.123 123.123
Gross Volume m 123.123 123.123 123.123


Current Process Data

Stream Status Valves Illeg Valves Illeg

Mass t/h 0.00 0.000 428.192
Std Volume Sm/h 0.000 0.000 462.457
Gross Volume m/h 0.000 0.000 464.921
Pressure barg 1.144 3.011
Temperature C 15.58 100.00*
Meter Density kg/m 925.600 871.600
Base Density kg/Sm 925.879 925.879
K factor pls/m 1000.000 1589.000
M factor pls/m 1.000000 1.016372

Flow Weighted Data
Current Week

Pressure barg 0.000 0.000
Temperature C 0.00 0.00
Meter Density kg/m 0.000 0.000
Base Density kg/Sm 0.000 0.000
Std Volume Sm
3
/d 123.123 123.123

Previous Week

Pressure barg 0.000 0.000
Temperature C 0.00 0.00
Meter Density kg/m 0.000 0.000
Base Density kg/Sm
3
0.000 0.000
Std Volume Sm
3
/d 123.123 123.123


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 231 of 395 Issue 7


Helang Central Condensate Metering System Final Prove Report

Proved Stream STREAM 2
Base Volume 3
Prove Ending 30/06/02 03:03:51

Stream Prover Stream Corrected
Run Temp Pressure Temp Pressure Flowrate Volume K-Factor

(C) (Bar g) (C) (Bar g) (m/h) (m)

1 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
2 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
3 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
4 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
5 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
6 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
7 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
8 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
9 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
10 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
11 0.00 0.000 0.00 0.000 0.000 0.000000 0.000
12 0.00 0.000 0.00 0.000 0.000 0.000000 0.000

Cplm Ctlm Cplp Ctlp Ctsp Cpsp Pulses

1 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
2 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
3 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
4 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
5 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
6 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
7 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
8 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
9 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
10 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
11 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000
12 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000


Average Stream Temperature C 0.000 Base Volume 1 (m) 0.554975
Average Stream Pressure Bar g 0.000 Base Volume 2 (m) 0.549786
Average Prover Temperature C 0.000 Base Volume 3 (m) 0.568116
Average Prover Pressure Bar g 0.000 Base Volume 4 (m) 0.536642
Average Stream Base Density kg/Sm 0.000
Average Prover Flowrate m/h 0.000

Youngs Modulus Bar 3.12e+007
Internal Diameter mm 182.6260
Wall Thickness mm 18.2880
Temperature Expansion Coeff /C 0.000123


Number of runs required 5
K-Factor Repeatability Limit 0.050
Current K-Factor pls/m 1000.000

Calculated New K-Factor pls/m 0.0000
Calculated New M-Factor 0.000000


Repeatability % 0.000
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 232 of 395 Issue 7
Helang Central Platform
Gas Export Metering System
Current Report Current Data at 29/06/02 04:35:35

Cumulative Totals
STREAM 1 STREAM 2 STREAM 3 STATION

Mass t 163.640 0.000 22.746 186.386
Std Volume Skm 213.630 0.000 7.830 221.460
Energy GJ 8495.724 0.000 402.676 8898.400

Mass (C1-C4) t 159.869 0.000 4.956 164.825
Mass (C5+) t 0.000 0.000 3.257 3.257
Std Vol (C1-C4) Skm 221.529 0.000 6.59 228.125
Std Vol (C5+) Skm 0.000 0.000 1.235 1.235
Energy (C1-C4) GJ 8811.053 0.000 271.577 9082.630
Energy (C1-C4) Mbtu 8350.759 0.000 257.390 8608.149
Energy (C5+) GJ 0.000 0.000 131.099 131.099
Energy (C5+) Mbtu 0.000 0.000 124.250 124.250

Current Day Totals

Mass t 163.640 0.000 22.746 186.386
Std Volume Skm 213.630 0.000 7.830 221.460
Energy GJ 8495.724 0.000 402.676 8898.400

Mass (C1-C4) t 159.869 0.000 4.956 164.825
Mass (C5+) t 0.000 0.000 3.257 3.257
Std Vol (C1-C4) Skm 221.529 0.000 6.595 228.125
Std Vol (C5+) Skm 0.000 0.000 1.235 1.235
Energy (C1-C4) GJ 8811.053 0.000 271.577 9082.630
Energy (C1-C4) Mbtu 8350.759 0.000 257.390 8608.149
Energy (C5+) GJ 0.000 0.000 131.099 131.099
Energy (C5+) Mbtu 0.000 0.000 124.250 124.250

Current Process Data

Stream Status Valves Illeg Off-Line Valves Illeg

Mass t/h 0.000 0.000 0.000 0.000
Std Volume Skm/h 0.000 0.000 0.000 0.000
Energy GJ/h 0.000 0.000 0.00 0.000
Pressure barg 100.000* 100.000* 100.000*
Temperature C 30.82 31.43 31.24
Upstr. Density kg/m 79.9929 124.9570 0.0000
Base Density kg/Sm 0.721678 1.270731 0.712228
CV MJ/kg 39.773 9.877 38.600
Relative Density 0.588928 1.036985 0.581216
Diff Press mbar 0.000* 0.000* 0.000*

Flow Weighted Data
Current Day

Pressure barg 100.000 0.000 0.000
Temperature C 30.82 0.00 0.00
Upstr. Density kg/m 75.4258 0.0000 0.0000
Base Density kg/Sm 0.721101 0.000000 0.000000
CV MJ/kg 39.701 0.000 0.000
Relative Density 0.588457 0.000000 0.000000
Diff Press mbar 6000.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123

Previous Day

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
CV MJ/Sm 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 233 of 395 Issue 7

Helang Central Platform
Gas Export Metering System
Period Report EOD 1 Current Data at 29/06/02 18:00:36

Cumulative Totals
STREAM 1 STREAM 2 STREAM 3 STATION

Mass t 14.940 1438.824 12.341 1466.105
Std Vol Skm 18.949 1817.787 15.652 1852.388
Energy GJ 797.080 76090.130 658.406 77545.616

Mass (C1-C4) t 13.324 1274.903 11.006 1299.233
Mass (C5+) kg 1616.123 163174.146 1335.342 166125.610
Std Vol (C1-C4) Skm 18.367 1756.034 15.172 1789.572
Std Vol (C5+) Skm 0.582 63.499 0.480 64.562
Liq StdVol (C5+) Sm
3
5662.608 0.000 5718.349
Liq StdVol (C5+) bbl 35648.243 0.000 35998.092
Energy (C1-C4) GJ 733.625 70189.661 606.002 71529.288
Energy (C1-C4) MBtu 695.300 66522.918 574.344 67792.562
Energy (C5+) GJ 63.455 5865.535 52.404 5981.394
Energy (C5+) MBtu 60.140 5559.116 49.666 5668.923

Period Totals

Mass t 0.000 0.000 0.000 0.000
Std Vol Skm 0.000 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000 0.000

Mass (C1-C4) t 0.000 0.000 0.000 0.000
Mass (C5+) kg 0.000 0.000 0.000 0.000
Std Vol (C1-C4) Skm 0.000 0.000 0.000 0.000
Std Vol (C5+) Skm 0.000 0.000 0.000 0.000
Liq StdVol (C5+) Sm
3
0.000 0.000 0.000
Liq StdVol (C5+) bbl 0.000 0.000 0.000
Energy (C1-C4) GJ 0.000 0.000 0.000 0.000
Energy (C1-C4) MBtu 0.000 0.000 0.000 0.000
Energy (C5+) GJ 0.000 0.000 0.000 0.000
Energy (C5+) MBtu 0.000 0.000 0.000 0.000


Current Process Data

Stream Status Valves Illeg Off-Line Valves Illeg

Mass t/h 0.000 0.000 0.000 0.000
Std Volume Skm/h 0.000 0.000 0.000 0.000
Energy GJ/h 0.000 0.000 0.000 0.000
Pressure barg 100.000* 100.000* 100.000*
Temperature C 30.84 31.43 31.24
Upstr. Density kg/m 91.6810 476.6290 0.0000
Base Density kg/Sm 0.788450 1.927152 0.712228
CV MJ/kg 42.064 56.178 38.600
Relative Density 0.643417 1.572659 0.581216
Diff Press mbar 0.000* 0.000* 0.000*

Flow Weighted Data
Current Period

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123

Previous Period

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 234 of 395 Issue 7
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123
Component Mass Totals

Period Totals

Mass (C1) t 123.123 123.123 123.123
Mass (C2) t 123.123 123.123 123.123
Mass (C3) t 123.123 123.123 123.123
Mass (iC4) t 123.123 123.123 123.123
Mass (nC4) t 123.123 123.123 123.123
Mass (CO2) t 123.123 123.123 123.123
Mass (N2) t 123.123 123.123 123.123
Mass (C5+) kg 123.123 123.123 123.123




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 235 of 395 Issue 7

Helang Central Platform
Gas Export Metering System
Daily Report EOD 2 Current Data at 29/06/02 00:00:41
Cumulative Totals
STREAM 1 STREAM 2 STREAM 3 STATION

Mass t 0.000 0.000 0.000 0.000
Std Vol Skm 0.000 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000 0.000
Mass (C1-C4) t 0.000 0.000 0.000 0.000
Mass (C5+) kg 0.000 0.000 0.000 0.000
Std Vol (C1-C4) Skm 0.000 0.000 0.000 0.000
Std Vol (C5+) Skm 0.000 0.000 0.000 0.000
Liq StdVol (C5+) Sm
3
0.000 0.000 0.000
Liq StdVol (C5+) bbl 0.000 0.000 0.000
Energy (C1-C4) GJ 0.000 0.000 0.000 0.000
Energy (C1-C4) Mbtu 0.000 0.000 0.000 0.000
Energy (C5+) GJ 0.000 0.000 0.000 0.000
Energy (C5+) Mbtu 0.000 0.000 0.000 0.000

Daily Totals

Mass t 0.000 0.000 0.000 0.000
Std Vol Skm 0.000 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000 0.000
Mass (C1-C4) t 0.000 0.000 0.000 0.000
Mass (C5+) t 0.000 0.000 0.000 0.000
Std Vol (C1-C4) Skm 0.000 0.000 0.000 0.000
Std Vol (C5+) Skm 0.000 0.000 0.000 0.000
Liq StdVol (C5+) Sm
3
0.000 0.000 0.000
Liq StdVol (C5+) bbl 0.000 0.000 0.000
Energy (C1-C4) GJ 0.000 0.000 0.000 0.000
Energy (C1-C4) Mbtu 0.000 0.000 0.000 0.000
Energy (C5+) GJ 0.000 0.000 0.000 0.000
Energy (C5+) Mbtu 0.000 0.000 0.000 0.000

BuyBack Adjustment Mass t Std Vol Skm Energy GJ
Station 0.000 0.000 0.000
BuyBack 0.000 0.000 0.000
Net 0.000 0.000 0.000

Current Process Data

Stream Status Valves Illeg Off-Line Valves Illeg

Mass t/h 0.000 0.000 0.000 0.000
Std Volume Skm/h 0.000 0.000 0.000 0.000
Energy GJ/h 0.000 0.000 0.000 0.000
Pressure barg 100.000* 100.000* 100.000*
Temperature C 30.83 31.44 31.26
Upstr. Density kg/m 91.8444 0.0000 0.0000
Base Density kg/Sm 0.788450 0.712228 0.712228
CV MJ/kg 42.064 38.600 38.600
Relative Density 0.643417 0.581216 0.581216
Diff Press mbar 0.000* 0.000* 0.000*

Flow Weighted Data
Current Day

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 0.000 0.000 0.000

Previous Day

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 236 of 395 Issue 7
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 0.000 0.000 0.000

Component Mass Totals

Mass (C1) t 123.123 123.123 123.123
Mass (C2) t 123.123 123.123 123.123
Mass (C3) t 123.123 123.123 123.123
Mass (iC4) t 123.123 123.123 123.123
Mass (nC4) t 123.123 123.123 123.123
Mass (CO2) t 123.123 123.123 123.123
Mass (N2) t 123.123 123.123 123.123
Mass (C5+) kg 123.123 123.123 123.123

Std Volume Flowrates

Daily Average Skm
3
/d 123456.123 123456.123 123456.123
Daily Minimum Skm
3
/d 123456.123 123456.123 123456.123
Daily Maximum Skm
3
/d 123456.123 123456.123 123456.123

C1-C4 Rate MMSCF/d 123456.123 123456.123 123456.123



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 237 of 395 Issue 7



Helang Central Platform
Gas Export Metering System
Mass Component Totals Daily Report EOD 2 Current Data at 29/06/02 00:00:41


Totals Daily Mass
t
Methane C1 123456.123
Ethane C2 123456.123
Propane C3 123456.123
I-Butane iC4 123456.123
N-Butane nC4 123456.123
Carbon Dioxide CO2 123456.123
Nitrogen N2 123456.123
Pentanes+ C5+ kg 123456.123

TOTAL MASS 123456.123

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 238 of 395 Issue 7



Helang Central Platform
Gas Export Metering System
Weekly Report EOD 1 Current Data at 05/06/02 18:51:37

Cumulative Totals
STREAM 1 STREAM 2 STREAM 3 STATION

Mass t 14159.968 4693.475 13629.232 32482.675
Std Vol Skm 32557.967 5894.558 16026.500 54479.025
Energy GJ 1348546.964 246289.255 721753.793 2316590.012

Mass (C1-C4) t 23798.063 4585.097 11951.002 40334.161
Mass (C5+) kg 2523.092 704.652 2274.322 5502.066
Std Vol (C1-C4) Skm 32920.916 6249.855 15940.210 55110.981
Std Vol (C5+) Skm 1243.416 423.200 871.936 2538.551
Liq StdVol (C5+) Sm
3
345.786 556.392 153.965
Liq StdVol (C5+) bbl 3156.438 4679.332 1236. 960
Energy (C1-C4) GJ 632998.599 252040.189 655074.881 1540113.669
Energy (C1-C4) Mbtu 599930.434 238873.483 620853.439 1459657.356
Energy (C5+) GJ 50882.362 26290.464 98891.679 176064.506
Energy (C5+) MBtu 48224.242 24917.037 93725.528 166866.808


Weekly Totals

Mass t 14159.891 2516.541 5560.147 22236.579
Std Vol Skm 32557.880 2927.846 6348.776 41834.502
Energy GJ 1348542.922 128731.965 293303.215 1770578.102

Mass (C1-C4) t 23798.124 2082.101 4590.083 30470.308
Mass (C5+) kg 2523.079 434.440 969.979 3927.498
Std Vol (C1-C4) Skm 1170.461 2748.574 6045.586 9964.621
Std Vol (C5+) Skm 58.368 179.786 305.336 543.490
Liq StdVol (C5+) Sm
3
189.478 345.966 191.576
Liq StdVol (C5+) bbl 1192.85 1978.758 1206.011
Energy (C1-C4) GJ 632995.127 113981.302 251192.489 998168.918
Energy (C1-C4) Mbtu 599927.143 108026.861 238070.067 946024.071
Energy (C5+) GJ 50881.792 14751.260 42106.212 107739.264
Energy (C5+) MBtu 48223.702 13980.647 39906.562 102110.911


Current Process Data

Stream Status Valves Illeg Off-Line Valves Illeg

Mass t/h 0.000 0.000 0.000 0.000
Std Volume Sm/h 0000 0.000 0.000 0.000
Energy GJ/h 0.000 0.000 0.000 0.000
Pressure barg 100.000* 100.000* 100.000*
Temperature C 15.79 16.19 16.19
Meter Density kg/m 930.700 930.800 930.800
Base Density kg/Sm 925.879 925.879 925.879
CV Mj/kg 123.123 123.123 123.123
Relative Density 1.123456 1.123456 1.123456


Flow Weighted Data
Current WK

Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm 0.000000 0.000000 0.000000
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123

Previous Week

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 239 of 395 Issue 7
Pressure barg 0.000 0.000 0.000
Temperature C 0.00 0.00 0.00
Upstr. Density kg/m 0.0000 0.0000 0.0000
Base Density kg/Sm3 0.000000 0.000000 0.000000
CV MJ/kg 0.000 0.000 0.000
Relative Density 0.000000 0.000000 0.000000
Diff Press mbar 0.000 0.000 0.000
Std Volume Skm
3
/d 123456.123 123456.123 123456.123

Component Mass Totals

Weekly Totals

Mass (C1) t 123.123 123.123 123.123
Mass (C2) t 123.123 123.123 123.123
Mass (C3) t 123.123 123.123 123.123
Mass (iC4) t 123.123 123.123 123.123
Mass (nC4) t 123.123 123.123 123.123
Mass (CO2) t 123.123 123.123 123.123
Mass (N2) t 123.123 123.123 123.123
Mass (C5+) kg 123.123 123.123 123.123

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 240 of 395 Issue 7

Helang Central Platform
Backup Gas Metering System
Current Report Current Data at 26/06/02 07:24:34

Cumulative Totals
STREAM 1 STREAM 2 STREAM 3


Mass t 0.000 0.000 0.000
Std Vol Skm 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000

Mass (C1-C4) t 1971.425 0.000 0.000
Mass (C5+) kg 217.767 0.000 0.000
Std Vol (C1-C4) Skm 2810.508 0.000 0.000
Std Vol (C5+) Skm 0.000 0.000 0.000
Liq StdVol (C5+) Sm
3
123.123 123.123 123.123
Liq StdVol (C5+) bbl 123.123 123.123 123.123
Energy (C1-C4) GJ 109069.568 0.000 0.000
Energy (C1-C4) Mbtu 103371.719 0.000 0.000
Energy (C5+) GJ 3439.172 0.000 0.000
Energy (C5+) Mbtu 3259.508 0.000 0.000


Current Day Totals

Mass t 0.000 0.000 0.000
Std Vol Skm 0.000 0.000 0.000
Energy GJ 0.000 0.000 0.000

Mass (C1-C4) t 1971.425 0.000 0.000
Mass (C5+) t 217.767 0.000 0.000
Std Vol (C1-C4) Skm 2810.508 0.000 0.000
Std Vol (C5+) Skm 146.440 0.000 0.000
Liq StdVol (C5+) Sm
3
123.123 123.123 123.123
Liq StdVol (C5+) bbl 123.123 123.123 123.123
Energy (C1-C4) GJ 109069.568 0.000 0.000
Energy (C1-C4) Mbtu 103371.719 0.000 0.000
Energy (C5+) GJ 3439.172 0.000 0.000
Energy (C5+) Mbtu 3259.508 0.000 0.000

Current Process Data

Stream Status Off-Line Off-Line Off-Line

Mass t/h 0.000 0.000 0.000
Std Vol Skm/h 0.000 0.000 0.000
Energy GJ/h 0.000 0.000 0.000
Pressure barg 100.000* 100.000* 100.000*
Temperature C 100.00* 100.00* 100.00*
Upstr. Density kg/m 60.0869 60.0869 60.0869
Base Density kg/Sm 0.740355 0.740355 0.740355
CV MJ/kg 38.049 38.049 38.049
Relative Density 0.604170 0.604170 0.604170
Diff Press mbar 0.000* 0.000* 0.000*


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 241 of 395 Issue 7


Buy Back Gas Metering System
Current Report Current Data at 19/06/02 09:04:07

Cumulative Totals
STREAM 1

Mass t 2245.947
Std Volume Skm 2962.674
Energy GJ 112729.582

Current Day Totals

Mass t 2245.947
Std Volume Skm 2962.674
Energy GJ 112729.582

Current Process Data

Stream Status Off-Line

Mass t/h 0.000
Std Volume Skm/h 0.000
Energy GJ/h 0.000
Pressure barg 100.000*
Temperature C 100.00*
Upstr. Density kg/m 60.0869
Base Density kg/Sm 0.740355
CV MJ/kg 38.049
Relative Density 0.604170
Diff Press mbar 0.000*



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 242 of 395 Issue 7
Helang Central Platform
Condensate Export Metering System
Corrected Daily Report for DD/MM/YY
Base Time : 06:00


Laboratory Data

Mol % C1 123.123
Mol % C2 123.123
Mol % C3 123.123
Mol % iC4 123.123
Mol % nC4 123.123
Mol % iC5 123.123
Mol % nC5 123.123
Mol % neoC5 123.123
Mol % C6+ 123.123
Density iC5 (kg/m3) 123.123
Density nC5 (kg/m3) 123.123
Density neoC5
(kg/m3)
123.123
Density C6+ (kg/m3) 123.123
VCF iC5 (m3 to bbl) 1.123
VCF nC5 (m3 to bbl) 1.123
VCF neoC5 (m3 to
bbl)
1.123
VCF C6+ (m3 to bbl) 1.123
Mol mass C6+ (kg/kg-mol) 1.123
Heating Value C6+ (MJ/kg) 123.123

Measured Mass Total
t
123456.123

Calculated Data
Mass
t
Std Volume
Sm3
Std Volume
bbl
Energy
MJ
Energy
MMBTU

C1 123.123 123.123 123.123 123.123 123.123
C2 123.123 123.123 123.123 123.123 123.123
C3 123.123 123.123 123.123 123.123 123.123
iC4 123.123 123.123 123.123 123.123 123.123
nC4 123.123 123.123 123.123 123.123 123.123
iC5 123.123 123.123 123.123 123.123 123.123
nC5 123.123 123.123 123.123 123.123 123.123
neoC5 123.123 123.123 123.123 123.123 123.123
C6+ 123.123 123.123 123.123 123.123 123.123

Total C1-C4 123.123 123.123 123.123 123.123 123.123
Total C5+ 123.123 123.123 123.123 123.123 123.123





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 243 of 395 Issue 7
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 244 of 395 Issue 7
20 AS-BUIL1 DISPLAYS
20.J S600 Gas Lxport
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 245 of 395 Issue 7
MENU: FLOW RATES|STREAM 1|STR01 UVOL FR
+--------------------+
|STR01 UVOL FR |
| 0.000 m3/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: FLOW RATES|STREAM 1|STR01 CVOL FR
+--------------------+ +--------------------+ +--------------------+
|STR01 CVOL FR | |STR01 CVOL FR | |STR01 CVOL FR C1-C4 |
| 0.000 Skm3/h | | | |MMSCF/d |
| | |MMSCF/d | | |
|Skm3/d | | 0.00 | | 0.000 |
| 0.00 | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 CVOL BASE 1 FR| |STR01 CVOL BASE 1 FR| |STR01 CVOL BASE 2 FR|
| | | | | |
|Cur Day Max | |Prev Day Max | |Cur Day Max |
| 0.000 | | 0.000 | | 0.000 |
| | | | | |
|Cur Day Min | |Prev Day Min | |Cur Day Min |
| 0.000 | | 0.000 | | 0.000 |

+--------------------+ +--------------------+ +--------------------+
+--------------------+
|STR01 CVOL BASE 2 FR|
| |
|Prev Day Max |
| 0.000 |
| |
|Prev Day Min |
| 0.000 |
+--------------------+

MENU: FLOW RATES|STREAM 1|STR01 MASS FR
+--------------------+
|STR01 MASS FR |
| 0.000 t/h |
|Limits (H/L) |
| |
| 1300.00 t/h |
| 0.00 t/h |
| |
+--------------------+

MENU: FLOW RATES|STREAM 1|STR01 ENERGY FR
+--------------------+
|STR01 ENERGY FR |
| 0.000 GJ/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: TOTALS|STREAM 1|STR01 UVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 UVOL | |STR01 UVOL MAINT | |STR01 UVOL HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
| | |Previous Period: | |Previous Period: |
| | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 246 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |

|STR01 UVOL DAILY | |STR01 UVOL HOURLY B2| |STR01 UVOL DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 CVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |CUMULATIVE TOTAL | |MAINTENANCE TOTAL |
|STR01 CVOL | |STR01 CVOL | |STR01 CVOL MAINT |
| | | | | |
| | | | |Current Period: |
| 0.000 Skm3 | | 0.000 | | 0.000 Skm3 |
| | |bbl | |Previous Period: |
| | | | | 0.000 Skm3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 1 | |BASETIME 2 |
|STR01 CVOL HOURLY | |STR01 CVOL DAILY | |STR01 CVOL HOURLY B2|
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|BASETIME 2 |
|STR01 CVOL DAILY B2 |
| |
|Current Period: |
| 0.000 Skm3 |
|Previous Period: |
| 0.000 Skm3 |
+--------------------+

MENU: TOTALS|STREAM 1|STR01 MASS
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 MASS | |STR01 MASS MAINT | |STR01 MASS HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
| | |Previous Period: | |Previous Period: |
| | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR01 MASS DAILY | |STR01 MASS HOURLY B2| |STR01 MASS DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 ENERGY
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 ENERGY | |STR01 ENERGY MAINT | |STR01 ENERGY HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
| | |Previous Period: | |Previous Period: |
| | | 0.000 GJ | | 0.000 GJ |
+--------------------+ +--------------------+ +--------------------+





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 247 of 395 Issue 7


+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR01 ENERGY DAILY | |STR01 ENERGY HOURLY | |STR01 ENERGY DAILY 2|
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 MASS COMP
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |CUMULATIVE TOTAL | |CUMULATIVE TOTAL |
|STR01 MASS C1-C4 | |STR01 MASS C1 | |STR01 MASS C2 |
| | | | | |
|tonne | |tonne | |tonne |
| 0.000 | | 0.000 | | 0.000 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |CUMULATIVE TOTAL | |CUMULATIVE TOTAL |
|STR01 MASS C3 | |STR01 MASS IC4 | |STR01 MASS NC4 |
| | | | | |
|tonne | |tonne | |tonne |
| 0.000 | | 0.000 | | 0.000 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |CUMULATIVE TOTAL | |CUMULATIVE TOTAL |
|STR01 MASS C5+ | |STR01 MASS CO2 | |STR01 MASS N2 |
| | | | | |
|tonne | |tonne | |tonne |
| 0.000 | | 0.000 | | 0.000 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 SVOL COMP
+--------------------+ +--------------------+
|CUMULATIVE TOTAL | |CUMULATIVE TOTAL |
|STR01 SVOL C1-C4 | |STR01 SVOL C5+ |
| | | |
|Skm3 | |Skm3 |
| 0.000 | | 0.000 |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 EGY COMP
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |CUMULATIVE TOTAL | |CUMULATIVE TOTAL |
|STR01 EGY C1-C4 | |STR01 EGY C5+ | |STR01 EGY C1-C4 |
| | | | | |
|GJ | |GJ | |MBtu |
| 0.000 | | 0.000 | | 0.000 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|CUMULATIVE TOTAL |
|STR01 EGY C5+ |
| |
|MBtu |
| 0.000 |
| |
| |
+--------------------+





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 248 of 395 Issue 7

MENU: OPERATOR|STREAM 1|COMPOSITION|SPV/KEYPAD MOLES
+--------------------+ +--------------------+ +--------------------+
|USE SPV/STR DATA | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|Status: | |NITROGEN | |H2S |
|SPV | | 0.0000 % | | 0.0000 % |
| | | | | |
| | |CO2 | |H2O |
| | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|HELIUM | |ETHANE | |N_BUTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|METHANE | |PROPANE | |I_BUTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|N_PENTANE | |NEO_PENTANE | |HEPTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|I_PENTANE | |HEXANE | |OCTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|NONANE | |OXYGEN | |HYDROGEN |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|DECANE | |CO | |BENZENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|TOLUENE | |C6_PLUS | |TOTAL |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|ARGON | |CX_PLUS | | |
| 0.0000 % | | 0.0000 % | | |
+--------------------+ +--------------------+ +--------------------+
MENU: OPERATOR|STREAM 1|COMPOSITION|CHROMAT MOLES
+--------------------+ +--------------------+ +--------------------+
|CHROMAT MOLES | |CHROMAT MOLES | |CHROMAT MOLES |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CHROMAT MOLES | |CHROMAT MOLES | |CHROMAT MOLES |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CHROMAT MOLES | |CHROMAT MOLES | |CHROMAT MOLES |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 249 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+
|CHROMAT MOLES | |CHROMAT MOLES | |CHROMAT MOLES |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|CHROMAT MOLES | |CHROMAT MOLES |
| | | |
|C6_PLUS | |TOTAL |
| 0.0000 % | | 0.0000 % |
| | | |
|CX_PLUS | | |
| 0.0000 % | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|COMPOSITION|SELECTED MOLES
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES |
| | | |
|C6_PLUS | |TOTAL |
| 0.0000 % | | 0.0000 % |
| | | |
|CX_PLUS | | |
| 0.0000 % | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|COMPOSITION|SPLITS
+--------------------+ +--------------------+ +--------------------+
|MOLE SPLITS | |MOLE SPLITS | |MOLE SPLITS |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 96.0000 % | | 1.0000 % | | 1.0000 % |
| | | | | |
|HEPTANE | |NONANE | | |
| 1.0000 % | | 1.0000 % | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 250 of 395 Issue 7
MENU: OPERATOR|STREAM 1|COMPOSITION|COMMAND
+--------------------+ +--------------------+ +--------------------+
|MOLE SELECT | |ACCEPTANCE COMMAND | |SPV CHR TIMEOUT |
| | | | | |
|Status: | |Status: | |Value: |
|KEYPAD | |IDLE | | 15 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|COMPOSITION|DEBUG
+--------------------+ +--------------------+ +--------------------+
|TELEM STAGE | |TELEM POLL DELAY | |TELEM RESET DELAY 1 |
| | | | | |
|Value: | |Value: | |Value: |
| 2 | | 2 | | 15 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|TELEM RESET DELAY 2 |
| |
|Value: |
| 30 |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|STREAM SETUP
+--------------------+ +--------------------+ +--------------------+
|STR01 STREAM TYPE | |STR01 NAME | |STR01 METER LOCATION|
| | | | | |
|Status: | |Value: | |Value: |
|GAS DP | |GAS DP | |LINE 1 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 STD TEMP | |STR01 STD PRESS | |STR01 LF CUT OFF |
| | | | | |
|Value: | |Value: | |Value: |
| 15.00000000 Deg.C | | 0.00000000 barg | | 5.00000000 t/h |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|STR01 FLOW DIRECTION|
| |
|Status: |
|FORWARD |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|STREAM STATUS
+--------------------+ +--------------------+ +--------------------+
|STR01 STATUS | |STR01 DISABLE | |STR01 LOW FLOW STAT |
| | | | | |
|Status: | |Status: | |Status: |
|ILLEGAL-V | |CLEAR | |SET |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+






Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 251 of 395 Issue 7
MENU: OPERATOR|STREAM 1|METER SETUP
+--------------------+ +--------------------+ +--------------------+
|STR01 TEMP EXP COEFF| |STR01 DENS EXP COEFF| |STR01 CALIB PIPE DIA|
| | | | | |
|Value: | |Value: | |Value: |
| -0.23076900 | | 0.76923100 | | 300.00000000 mm |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 PIPE MATERIAL | |STR01 PIPE TEMP EXP | |STR01 PIPE CALIB TEM|
| | | | | |
|Status: | |Value: | |Value: |
|USER | | 0.00001100 | | 20.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 CALIB ORIF DIA| |STR01 ORIF MATERIAL | |STR01 ORIF EXP CONST|
| | | | | |
|Value: | |Status: | |Value: |
| 180.00000000 mm | |USER | | 0.00001600 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 ORIF CALIB TEM| |STR01 ISENTROPIC EXP| |STR01 VISCOSITY |
| | | | | |
|Value: | |Value: | |Value: |
| 20.00000000 Deg.C | | 1.30000000 | | 0.01710000 cP |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|DENS OF AIR | |STR01 DOWN/UP CORREC|
| | | |
|Value: | |Status: |
| 1.22541000 kg/m3 | |EXTENDED |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|METERING IO
+--------------------+ +--------------------+ +--------------------+
|STR01 METER TEMP | |STR01 METER TEMP | |STR01 METER PRESSURE|
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 100.00 barg |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 METER PRESSURE| |DP Stack 1 | |DP Stack 1 |
| | |STR01 DP STACK | |STR01 DP STACK |
|Keypad Value: | |In Use DP Value: | | |
| 100.00 barg | | 0.000 mbar | |Keypad Value: |
|Mode Status: | |NO CELL SELECTED | | 0.000 mbar |
|KEYPAD-F | |mode Status: | |Measured Value: |
| | |KEYPAD-F | | 0.000 mbar |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
|Limits (H/L) | | | | |
| | |Switch up point: | |Discrepancy: |
| 600.00 mbar | | 95.000 % | | 10.000 % |
| 5.00 mbar | |Switch down point: | |Discrepancy timout: |
| | | 90.000 % | | 5.000 s |
+--------------------+ +--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 252 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
| | | | | |
|Check DP Value: | |Low DP Cut Off: | |DP Cell type: |
| 20.000 mbar | | 10.000 mbar | |LO-HI-HI |
|Live/Check: | | | |Cut off mode: |
|LIVE | | | |NORMAL |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|CALCULATED DATA
+--------------------+ +--------------------+ +--------------------+
|STR01 DOWNSTR PRESS | |STR01 RECOVERED PRES| |STR01 UPSTREAM TEMP |
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|CALCULATED | |CALCULATED | |CALCULATED |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 DOWNSTREAM TEM| |STR01 PRESS LOSS | |STR01 CORR PIPE DIAM|
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 100.000000 Deg.C | | 0.000000 mbar | | 300.264000 mm |
| | | | | |
| | |Mode Status: | |Mode Status: |
| | |CALCULATED | |CALCULATED |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 CORR ORIF DIAM| |STR01 UPSTR COMPRESS| |STR01 STD COMPRESS |
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 180.230400 mm | | 0.000000 | | 0.000000 |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|CALCULATED | |COMPRESS | |COMPRESS |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 UPSTREAM DENS | |STR01 STANDARD DENS | |STR01 STANDARD DENS |
| | | | | |
|In Use Value: | |In Use Value: | |Keypad Value: |
| 0.000000 | | 0.712228 kg/m3 | | 0.848463 kg/m3 |
| | | | | |
|Mode Status: | |Mode Status: | | |
|KEYPAD-F | |CV | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 STANDARD DENS | |STR01 REAL RDENS | |STR01 REAL RDENS |
| | | | | |
|Limits (H/L) | |In Use Value: | |Keypad Value: |
| | | 0.581216 | | 0.500000 |
| 1.00 kg/m3 | | | | |
| 0.50 kg/m3 | |Mode Status: | |Mode Status: |
| | |CV | |CV |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 REAL CV | |STR01 REAL CV | |STR01 REAL CV |
| | | | | |
|In Use Value: | |Keypad Value: | |Limits (H/L) |
| 38.599754 MJ/Sm3 | | 40.000000 MJ/Sm3 | | |
| | | | | 42.00 MJ/Sm3 |
|Mode Status: | | | | 35.00 MJ/Sm3 |
|CV | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|STR01 BETA | |STR01 REYNOLDS NO |
| | | |
|In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 253 of 395 Issue 7
MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 PRESS
+--------------------+ +--------------------+ +--------------------+
|PRESS BASE 1 | |PRESS BASE 1 | |PRESS BASE 1 PREV |
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 barg | | 0.00000000 barg | | 0.00000000 barg |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 barg | | | | 0.00000000 barg |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PRESS BASE 1 PREV | |PRESS BASE 2 | |PRESS BASE 2 |
| | | | | |
|HOURLY | |NOT USED | |WEEKLY 2 |
| 0.00000000 barg | | 0.00000000 barg | | 0.00000000 barg |
| | | | | |
| | |DAILY 2 | | |
| | | 0.00000000 barg | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|PRESS BASE 2 PREV | |PRESS BASE 2 PREV |
| | | |
|NOT USED | |WEEKLY 2 |
| 0.00000000 barg | | 0.00000000 barg |
| | | |
|DAILY 2 | | |
| 0.00000000 barg | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 TEMP
+--------------------+ +--------------------+ +--------------------+
|TEMP BASE 1 | |TEMP BASE 1 | |TEMP BASE 1 PREV |
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 Deg.C | | 0.00000000 Deg.C | | 0.00000000 Deg.C |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 Deg.C | | | | 0.00000000 Deg.C |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|TEMP BASE 1 PREV | |TEMP BASE 2 | |TEMP BASE 2 |
| | | | | |
|HOURLY | |NOT USED | |WEEKLY 2 |
| 0.00000000 Deg.C | | 0.00000000 Deg.C | | 0.00000000 Deg.C |
| | | | | |
| | |DAILY 2 | | |
| | | 0.00000000 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|TEMP BASE 2 PREV | |TEMP BASE 2 PREV |
| | | |
|NOT USED | |WEEKLY 2 |
| 0.00000000 Deg.C | | 0.00000000 Deg.C |
| | | |
|DAILY 2 | | |
| 0.00000000 Deg.C | | |
+--------------------+ +--------------------+
MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 STD DENS
+--------------------+ +--------------------+ +--------------------+
|STD DENS BASE 1 | |STD DENS BASE 1 | |STD DENS BASE 1 PREV|
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 kg/m3 | | | | 0.00000000 kg/m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STD DENS BASE 1 PREV| |STD DENS BASE 2 | |STD DENS BASE 2 |
| | | | | |
|HOURLY | |DAILY | |HOURLY |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | | | |
| | |DAILY 2 | | |
| | | 0.00000000 kg/m3 | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 254 of 395 Issue 7
+--------------------+ +--------------------+
|STD DENS BASE 2 PREV| |STD DENS BASE 2 PREV|
| | | |
|NOT USED | |WEEKLY 2 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | |
|DAILY 2 | | |
| 0.00000000 kg/m3 | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 DP STACK
+--------------------+ +--------------------+ +--------------------+
|DP BASE 1 | |DP BASE 1 | |DP BASE 1 PREV |
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 mbar | | 0.00000000 mbar | | 0.00000000 mbar |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 mbar | | | | 0.00000000 mbar |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP BASE 1 PREV | |DP BASE 2 | |DP BASE 2 |
| | | | | |
|HOURLY | |NOT USED | |WEEKLY 2 |
| 0.00000000 mbar | | 0.00000000 mbar | | 0.00000000 mbar |
| | | | | |
| | |DAILY 2 | | |
| | | 0.00000000 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|DP BASE 2 PREV | |DP BASE 2 PREV |
| | | |
|NOT USED | |WEEKLY 2 |
| 0.00000000 mbar | | 0.00000000 mbar |
| | | |
|DAILY 2 | | |
| 0.00000000 mbar | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 REL DENS
+--------------------+ +--------------------+ +--------------------+
|REL DENS BASE 1 | |REL DENS BASE 1 | |REL DENS BASE 1 PREV|
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 | | | | 0.00000000 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|REL DENS BASE 1 PREV| |REL DENS BASE 2 | |REL DENS BASE 2 |
| | | | | |
|HOURLY | |NOT USED | |WEEKLY 2 |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
| | |DAILY 2 | | |
| | | 0.00000000 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|REL DENS BASE 2 PREV| |REL DENS BASE 2 PREV|
| | | |
|NOT USED | |WEEKLY 2 |
| 0.00000000 | | 0.00000000 |
| | | |
|DAILY 2 | | |
| 0.00000000 | | |
+--------------------+ +--------------------+









Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 255 of 395 Issue 7
MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 CV
+--------------------+ +--------------------+ +--------------------+

|CV BASE 1 | |CV BASE 1 | |CV BASE 1 PREV |
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 MJ/Sm3 | | 0.00000000 MJ/Sm3 | | 0.00000000 MJ/Sm3 |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 MJ/Sm3 | | | | 0.00000000 MJ/Sm3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CV BASE 1 PREV | |CV BASE 2 | |CV BASE 2 |
| | | | | |
|HOURLY | |NOT USED | |WEEKLY 2 |
| 0.00000000 MJ/Sm3 | | 0.00000000 MJ/Sm3 | | 0.00000000 MJ/Sm3 |
| | | | | |
| | |DAILY 2 | | |
| | | 0.00000000 MJ/Sm3 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|CV BASE 2 PREV | |CV BASE 2 PREV |
| | | |
|NOT USED | |WEEKLY 2 |
| 0.00000000 MJ/Sm3 | | 0.00000000 MJ/Sm3 |
| | | |
|DAILY 2 | | |
| 0.00000000 MJ/Sm3 | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 UPSTR DENS
+--------------------+ +--------------------+ +--------------------+
|UPSTR DENS BASE 1 | |UPSTR DENS BASE 1 | |UPSTR DENS BASE 1 PR|V
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 kg/m3 | | | | 0.00000000 kg/m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTR DENS BASE 1 PR|V |UPSTR DENS BASE 2 | |UPSTR DENS BASE 2 |
| | | | | |
|HOURLY | |NOT USED | |WEEKLY 2 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | | | |
| | |DAILY 2 | | |
| | | 0.00000000 kg/m3 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|UPSTR DENS BASE 2 PR|V |UPSTR DENS BASE 2 PR|V
| | | |
|NOT USED | |WEEKLY 2 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | |
|DAILY 2 | | |
| 0.00000000 kg/m3 | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 CVOL FR
+--------------------+ +--------------------+ +--------------------+
|CVOL FR BASE 1 | |CVOL FR BASE 1 | |CVOL FR BASE 1 PREV |
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 | | | | 0.00000000 |
+--------------------+ +--------------------+ +--------------------+







Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 256 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+
|CVOL FR BASE 1 PREV | |CVOL FR BASE 2 | |CVOL FR BASE 2 |
| | | | | |
|HOURLY | |NOT USED | |WEEKLY 2 |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
| | |DAILY 2 | | |
| | | 0.00000000 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|CVOL FR BASE 2 PREV | |CVOL FR BASE 2 PREV |
| | | |
|NOT USED | |WEEKLY 2 |
| 0.00000000 | | 0.00000000 |
| | | |
|DAILY 2 | | |
| 0.00000000 | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 METHOD
+--------------------+
|STR01 METHOD |
| |
|Status: |
|FWA |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|INLET VALVE 1
+--------------------+ +--------------------+ +--------------------+
|I-VLV 1 POSN | |I-VLV 1 TRAVEL TIME | |I-VLV 1 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|I-VLV 1 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|OUTLET VALVE 1
+--------------------+ +--------------------+ +--------------------+
|O-VLV 1 POSN | |O-VLV 1 TRAVEL TIME | |O-VLV 1 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|O-VLV 1 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+







Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 257 of 395 Issue 7
MENU: OPERATOR|STREAM 1|VALVES|INLET VALVE 2
+--------------------+ +--------------------+ +--------------------+
|I-VLV 2 POSN | |I-VLV 2 TRAVEL TIME | |I-VLV 2 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|I-VLV 2 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|OUTLET VALVE 2
+--------------------+ +--------------------+ +--------------------+
|O-VLV 2 POSN | |O-VLV 2 TRAVEL TIME | |O-VLV 2 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|O-VLV 2 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+
MENU: OPERATOR|STREAM 1|DENSITOMETERS|DENSITOMETER A
+--------------------+ +--------------------+ +--------------------+
|DENS A TYPE | |MTR TEMP | |MTR TEMP |
| | | | | |
|Status: | |In Use Value: | |Keypad Value: |
|SOL 1794 | | 100.00 Deg.C | | 100.00 Deg.C |
| | | | |Mode Status: |
| | | | |KEYPAD-F |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|MTR PRESSURE | |MTR PRESSURE | |DENS A PERIOD |
| | | | | |
|In Use Value: | |Keypad Value: | |Period |
| 100.00 barg | | 100.00 barg | | 0.000000 uS |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DENS A LIVE/CHECK | |DENS A CHECK PERIOD | |DENS A CONSTANTS |
| | | | | |
|Status: | |Value: | |SOLK0 |
|LIVE | | 0.01000000 uS | | 9.904493000E+02 |
| | | | | |
| | | | |SOLK1 |
| | | | |-4.332491000E+00 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DENS A CONSTANTS | |DENS A CONSTANTS | |DENS A CONSTANTS |
| | | | | |
|SOLK2 | |SOLK19 | |SOLR |
| 4.694431000E-03 | | 3.010000000E-04 | | .0 |
| | | | | |
|SOLK18 | |SOLG | |SOLK3 |
|-1.840000000E-05 | | .0 | | 4.660000000E+02 |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 258 of 395 Issue 7
+--------------------+ +--------------------+
|DENS A CONSTANTS | |DENS CONST ACC |
| | | |
|SOLK4 | |Status: |
| 7.990000000E+01 | |IDLE |
| | | |
|SOLTcal | | |
| 2.000000000E+01 | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|DENSITOMETERS|UPSTREAM DENSITY
+--------------------+ +--------------------+ +--------------------+
|INUSE CORRECTED DENS| |INUSE DENSITY | |INUSE DENSITY |
| | | | | |
|In Use Value: | |Dens A Value: | |Limits (H/L) |
| 0.000000 | | 0.000 kg/m3 | | |
| | | | | 1000.000000 |
|Mode Status: | |AGA8 Value: | | 0.000000 |
|KEYPAD-F | | 0.000000 kg/m3 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|RELATIVE DENSITY |
| |
|In Use Value: |
| 0.581216 |
| |
|Mode Status: |
|CV |
+--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 01 - MTR PRS
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 1 | |ADC Channel 1 | |ADC Channel 1 |
|MTR PRS | |MTR PRS | |MTR PRS |
| | | | | |
|In Use Value: | |Keypad Value: | |Limits (H/L) |
| 100.000 barg | | 100.000 barg | | |
|Mode Status: | |Measured Value: | | 119.00 barg |
|KEYPAD-F | | -29.998 barg | | 0.00 barg |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 1 | |ADC Channel 1 |
|MTR PRS | |MTR PRS |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 2.66852032E-04 mA | | 120.000 barg |
| | | 0.000 barg |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 02 - LO DP P
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 2 | |ADC Channel 2 | |ADC Channel 2 |
|LO DP PAY | |LO DP PAY | |LO DP PAY |
| | | | | |
|In Use Value: | |Keypad Value: | |Current: |
| 0.000 mbar | | 0.000 mbar | | 2.22886360E-04 mA |
|Mode Status: | |Measured Value: | | |
|KEYPAD | | -69.996 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|ADC Channel 2 |
|LO DP PAY |
|HIGH AND LOW SCALE |
| |
| 280.000 mbar |
| 0.000 mbar |
| |
+--------------------+







Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 259 of 395 Issue 7
MENU: PLANT I/O|ANALOG INPUTS|ADC 03 - HI DP P
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 3 | |ADC Channel 3 | |ADC Channel 3 |
|HI DP PAY | |HI DP PAY | |HI DP PAY |
| | | | | |
|In Use Value: | |Keypad Value: | |Current: |
| 0.000 mbar | | 0.000 mbar | | 1.28011176E-04 mA |
|Mode Status: | |Measured Value: | | |
|KEYPAD | | -156.245 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|ADC Channel 3 |
|HI DP PAY |
|HIGH AND LOW SCALE |
| |
| 625.000 mbar |
| 0.000 mbar |
| |
+--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 04 - HI DP C
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 4 | |ADC Channel 4 | |ADC Channel 4 |
|HI DP CHK | |HI DP CHK | |HI DP CHK |
| | | | | |
|In Use Value: | |Keypad Value: | |Current: |
| 0.000 mbar | | 0.000 mbar | | 3.20207590E-04 mA |
|Mode Status: | |Measured Value: | | |
|KEYPAD | | -156.237 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|ADC Channel 4 |
|HI DP CHK |
|HIGH AND LOW SCALE |
| |
| 625.000 mbar |
| 0.000 mbar |
| |
+--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 05 - LO DP C
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 5 | |ADC Channel 5 | |ADC Channel 5 |
|LO DP CHK | |LO DP CHK | |LO DP CHK |
| | | | | |
|In Use Value: | |Keypad Value: | |Current: |
| 100.000 mbar | | 100.000 mbar | | 6.13697484E-05 mA |
|Mode Status: | |Measured Value: | | |
|KEYPAD | | -69.999 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|ADC Channel 5 |
|LO DP CHK |
|HIGH AND LOW SCALE |
| |
| 280.000 mbar |
| 0.000 mbar |
| |
+--------------------+

MENU: PLANT I/O|ANALOG INPUTS|DISCREPANCY
+--------------------+
|DP DISCREPANCY PAY-C|K
|LOW CELL |
| 0.00 |
|mbar |
|HIGH CELL |
| 0.00 |
|mbar |
+--------------------+






Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 260 of 395 Issue 7
MENU: PLANT I/O|PRT/RTD INPUTS|PRT 01 - MTR TMP
+--------------------+ +--------------------+ +--------------------+
|PRT Input 1 | |PRT Input 1 | |PRT Input 1 |
|MTR TMP | |MTR TMP | |MTR TMP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 Deg.C | | 100.000 Deg.C | | 40.00 Deg.C |
|Mode Status: | |Measured Value: | | 0.00 Deg.C |
|KEYPAD-F | | -100.627 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|PRT Channel 1 |
|MTR TMP |
| |
|Resistance: |
| 0.000 ohms |
| |
| |
+--------------------+

MENU: PLANT I/O|FREQUENCY INPUTS|FREQ 01 - DNS A
+--------------------+
|FREQ Input 1 |
|DNS A |
| |
|Period: |
| 0.000 uS |
| |
| |
+--------------------+

MENU: PLANT I/O|DIGITAL I/OS|DIGITAL IO 01
+--------------------+
|Discrete I/O 1 |
|I/O01 DIO 01 |
| |
|Input Status: |
|0000000000000000 |
|Output Status: |
|0000000000000000 |
+--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 01 - DAC01
+--------------------+ +--------------------+
|DAC Channel 1 | |DAC Channel 1 |
|I/O01 DAC 01 | |I/O01 DAC 01 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 02 - DAC02
+--------------------+ +--------------------+
|DAC Channel 2 | |DAC Channel 2 |
|I/O01 DAC 02 | |I/O01 DAC 02 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 03 - DAC03
+--------------------+ +--------------------+
|DAC Channel 3 | |DAC Channel 3 |
|I/O01 DAC 03 | |I/O01 DAC 03 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 261 of 395 Issue 7
MENU: PLANT I/O|ANALOG OUTPUTS|DAC 04 - DAC04
+--------------------+ +--------------------+
|DAC Channel 4 | |DAC Channel 4 |
|I/O01 DAC 04 | |I/O01 DAC 04 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|UNIT SETUP|CONVERSIONS
+--------------------+ +--------------------+
|Conversions | |Conversions |
| | | |
|GJ -> MMBtu | |Skm3 -> MMSCF |
| | | |
|Value: | |Value: |
| 1.0551200 | | 0.8772016 |
| | | |
+--------------------+ +--------------------+
MENU: SYSTEM SETTINGS|UNIT SETUP|SETUP
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS MASS UNITS | |GAS MASS FR UNITS | |GAS GROSS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|tonne | |t/h | |m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS GROSS FR UNITS | |GAS NETT UNITS | |GAS NETT FR UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|m3/h | |Skm3 | |Skm3/h |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS ENGY UNITS | |GAS ENGY FR UNITS | |PRESS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|GJ | |GJ/h | |barg |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DP UNITS | |TEMP UNITS | |DENS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mbar | |Deg.C | |kg/m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|K-FACTOR UNITS | |CV MASS UNITS | |CV VOL UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|pls/m3 | |MJ/kg | |MJ/Sm3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DYN VISC UNITS | |KIN VISC UNITS | |FREQ UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|cP | |cSt | |Hz |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 262 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|LENGTH UNITS | |PERIOD UNITS | |PERCENT UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mm | |uS | |% |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DIAM UNITS | |AREA UNITS | |VEL UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mm | |mm2 | |m/s |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|Unit Setup |
|TIME UNITS |
| |
|Selected Unit: |
|s |
| |
| |
+--------------------+

MENU: SYSTEM SETTINGS|REPORT SETUP
+--------------------+ +--------------------+ +--------------------+
|REPORT CONTROL | |REPORT CONTROL | |BASETIME 1 |
|WEEK START | |MONTH START | | |
| | | | | |
|SUNDAY | |FIRST | | 6 |
| | | | | |
| | | | |O-CLOCK |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|BASETIME 2 |
| |
| |
| 0 |
| |
|O-CLOCK |
| |
+--------------------+

MENU: SYSTEM SETTINGS|ALARM SETUP
+--------------------+ +--------------------+
|ALARM CONTROL | |ALARM CONTROL |
|ALARM MODE | |ALARM ENABLE |
| | | |
|LATCHED | |YES |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|MAINTENANCE MODE
+--------------------+ +--------------------+
| | | |
|SYSTEM MAINT ENAB | |STR01 MAINT MODE |
| | | |
|SET | |CLEAR |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+







Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 263 of 395 Issue 7
MENU: SYSTEM SETTINGS|SYSTEM STATUS
+--------------------+
| |
|SYSTEM RUN MODE |
| |
|NORMAL |
| |
| |
| |
+--------------------+

MENU: SYSTEM SETTINGS|SOFTWARMENU
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|CONFIG NAME | |CONFIG FORMAT | |CONFIG VERSION |
| | | | | |
|Helang - Gas ExpCV | |5 | |299 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|CONFIG CREATED | |CONFIG LAST EDITED | |CONFIG STRUCTURE |
| | | | | |
|28 Nov 2001. 11:16 | |09 Apr 2003. 15:08 | |CSUM d0f9 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|NMI CONSTANTS | |FILE CSUM | |REGISTRATION CODE |
| | | | | |
|AAAA-1111 | |AAAA | |1.3dMAKAWGG20011024P|
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|APPLICATION SW | |PC SETUP PACKAGE | |MAIN BOARD ID |
| | | | | |
|03.24a Jul 19 2002 | |1.3 | |00:A0:D8:FE:0D:89 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 HW_REV | |I/O01 MOD_STRIKE | |I/O01 BOARD SERNO |
| | | | | |
|REV 04 | |MOD E | |SN 06968 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 FIRST CALIB | |I/O01 LAST CALIB | |I/O01 SW VERSION |
| | | | | |
|09052003 | |09052003 | |01.01.16.00 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|VERSION CONTROL |
|I/O01 BOARD ID |
| |
|1.1.1.1.1.2.0 |
| |
| |
| |
+--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 264 of 395 Issue 7
MENU: TECH/ENGINEER|DISPLAY SETUP
+--------------------+
|Display Setup |
| |
|DEF DISP : |
| |
|DISPLAY T/O: 300 s |
|LOGOUT T/O: 20 s |
|IDENT T/O: 120 s |
+--------------------+

MENU: TECH/ENGINEER|CONTRAST
+--------------------+
| |
| |
|CONTRAST : 8 |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|DATE & TIME
+--------------------+ +--------------------+
|Current Date & Time | |Date and Time Format|
| | | |
|07/02/1980 02:32:19 | | |
| | | |
| | |DD MM YYYY |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|DISPLAY TEST
+--------------------+
| |
| |
|DISPLAY TEST |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|SECURITY
+--------------------+ +--------------------+
|Security Setup | |PC Setup Link |
| | | |
|Current Level: | |DISABLED |
|SECURITY : 9 | | |
| | | |
|Front Panel Keypad: | | |
|ENABLED | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 01
+--------------------+ +--------------------+ +--------------------+

|COM1 - DISPLAY | |COM1 - DISPLAY | |COM1 - DISPLAY |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM1 - DISPLAY |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
| |
+--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 265 of 395 Issue 7
MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 02
+--------------------+ +--------------------+ +--------------------+
|COM2 - PC LINK | |COM2 - PC LINK | |COM2 - PC LINK |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 38400 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM2 - PC LINK |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 03
+--------------------+ +--------------------+ +--------------------+
|COM3 | |COM3 | |COM3 |
| | |GOOD_TX : 500 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 38 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM3 |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 04
+--------------------+ +--------------------+ +--------------------+
|COM4 | |COM4 | |COM4 |
| | |GOOD_TX : 21 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 7 |
|HEALTHY | |BAD_RX : 21 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM4 |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 05
+--------------------+ +--------------------+ +--------------------+
|COM5 | |COM5 | |COM5 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+






Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 266 of 395 Issue 7
+--------------------+
|COM5 |
| |
|HANDSHAKE NONE |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 06
+--------------------+ +--------------------+ +--------------------+
|COM6 | |COM6 | |COM6 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM6 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 07
+--------------------+ +--------------------+ +--------------------+
|COM7 | |COM7 | |COM7 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM7 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 08
+--------------------+ +--------------------+ +--------------------+
|COM8 - IO | |COM8 - IO | |COM8 - IO |
| | |GOOD_TX : 246 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 38400 |
| | |GOOD_RX : 245 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM8 - IO |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
| |
+--------------------+







Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 267 of 395 Issue 7
MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|MODBUS ADDRESS
+--------------------+
|FLOW COMPUTER |
|SLAVE ADDRESS |
|1 |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|CHROMAT LINK
+--------------------+
|CHROMAT LINK |
| |
|Port: |
|PORT 4 |
|Protocol: |
|ASCII SERIAL |

| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 03
+--------------------+ +--------------------+
|COMMS TASK 03 | |COMMS TASK 03 |
| | | |
|Port: | |Address: |
|PORT 6 | |0 |
|Protocol: | | |
|MODBUS TCP | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|SLAVE LINK
+--------------------+ +--------------------+
|SLAVE LINK | |SLAVE LINK |
| | | |
|Port: | |Address: |
|PORT 4 | |0 |
|Protocol: | | |
|MODBUS TCP | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 06
+--------------------+ +--------------------+
|COMMS TASK 06 | |COMMS TASK 06 |
| | | |
|Port: | |Address: |
|PORT 6 | |0 |
|Protocol: | | |
|RTU SERIAL | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 07
+--------------------+ +--------------------+
|COMMS TASK 07 | |COMMS TASK 07 |
| | | |
|Port: | |Address: |
|PORT 7 | |0 |
|Protocol: | | |
|RTU SERIAL | | |
| | | |
+--------------------+ +--------------------+
MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|PRINTER
+--------------------+
|PRINTER |
| |
|Port: |
|PORT 3 |
| |
| |
| |
+--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 268 of 395 Issue 7
MENU: CALCULATIONS|STREAM 1|DOWN/UP CORR|INPUTS
+--------------------+ +--------------------+ +--------------------+
|DOWNSTREAM DENSITY | |DOWNSTREAM DENSITY | |METER TEMP |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 113.000000 kg/m3 | | 113.000000 kg/m3 | | 100.00 Deg.C |
| | | | | |
| | | | | |
| | | | | |

+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|METER TEMP | |DP Stack 1 | |DP Stack 1 |
| | |STR01 DP STACK | |STR01 DP STACK |
|Keypad Value: | |In Use DP Value: | | |
| 100.00 Deg.C | | 0.000 mbar | |Keypad Value: |
|Mode Status: | |NO CELL SELECTED | | 0.000 mbar |
|KEYPAD-F | |mode Status: | |Measured Value: |
| | |KEYPAD-F | | 0.000 mbar |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
|Limits (H/L) | | | | |
| | |Switch up point: | |Discrepancy: |
| 600.00 mbar | | 95.000 % | | 10.000 % |
| 5.00 mbar | |Switch down point: | |Discrepancy timout: |
| | | 90.000 % | | 5.000 s |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
| | | | | |
|Check DP Value: | |Low DP Cut Off: | |DP Cell type: |
| 20.000 mbar | | 10.000 mbar | |LO-HI-HI |
|Live/Check: | | | |Cut off mode: |
|LIVE | | | |NORMAL |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|METER PRESSURE | |METER PRESSURE | |PRESSURE LOSS |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 barg | | 100.00 barg | | 0.000000 mbar |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|TEMP EXP CONSTANT | |DENS EXP CONSTANT | |TEMP MEAS POINT |
| | | | | |
|Value: | |Value: | |Status: |
| -0.23076900 | | 0.76923100 | |DOWNSTREAM |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|PRESS MEAS POINT | |CORRECTION TYPE |
| | | |
|Status: | |Status: |
|UPSTREAM | |EXTENDED |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|DOWN/UP CORR|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|DOWNSTREAM PRESSURE | |RECOVERED PRESSURE | |UPSTREAM TEMP |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
|In Use Value: | |In Use Value: | |In Use Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 269 of 395 Issue 7
+--------------------+
|UPSTREAM DENSITY |
| |
|Calculated Value: |
| 113.000000 kg/m3 |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|PIPE CORRECTION|INPUTS
+--------------------+ +--------------------+ +--------------------+
|CALIB PIPE DIAM | |CALIB ORIFICE DIAM | |PIPE CALIB TEMP |
| | | | | |
|Value: | |Value: | |Value: |
| 300.00000000 mm | | 180.00000000 mm | | 20.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|ORIFICE CALIB TEMP | |PIPE EXP CONSTANT | |ORIFICE EXP CONSTANT|
| | | | | |
|Value: | |Value: | |Value: |
| 20.00000000 Deg.C | | 0.00001100 | | 0.00001600 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM TEMP | |PIPE MATERIAL | |ORIFICE MATERIAL |
| | | | | |
|In Use Value: | |Status: | |Status: |
| 100.000000 Deg.C | |USER | |USER |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|PIPE CORRECTION|OUTPUTS
+--------------------+ +--------------------+
|CORRECTED PIPE DIAM | |CORRECTED ORIF DIAM |
| | | |
|Calculated Value: | |Calculated Value: |
| 300.264000 mm | | 180.230400 mm |
|In Use Value: | |In Use Value: |
| 300.264000 mm | | 180.230400 mm |
| | | |
+--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|AGA 8|INPUTS
+--------------------+ +--------------------+ +--------------------+
|AGA8 METHOD | |UPSTREAM PRESS | |UPSTREAM TEMP |
| | | | | |
|Status: | |In Use Value: | |In Use Value: |
|DETAIL | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STANDARD PRESS | |STANDARD TEMP | |INUSE COMPOSITION |
| | | | | |
|Value: | |Value: | |NITROGEN |
| 0.00000000 barg | | 15.00000000 Deg.C | | 0.00000000 % |
| | | | | |
| | | | |CO2 |
| | | | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+







Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 270 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|H2S | |HELIUM | |ETHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|H2O | |METHANE | |PROPANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|N_BUTANE | |N_PENTANE | |NEO_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|I_BUTANE | |I_PENTANE | |HEXANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|HEPTANE | |NONANE | |OXYGEN |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|OCTANE | |DECANE | |CO |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|HYDROGEN | |TOLUENE | |C6_PLUS |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|BENZENE | |ARGON | |CX_PLUS |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|AGA 8|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |AGA8 CALC DENSITY | |UPSTREAM DENSITY |
| | | | | |
|Calculated Value: | |Limits (H/L) | |DISCREPANCY |
| 0.000000 kg/m3 | | | | 0.00 |
| | | 100.000000 kg/m3 | |kg/m3 |
| | | 0.200000 kg/m3 | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Zf | |Zb | |MOLECULAR WEIGHT |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STANDARD DENSITY | |STANDARD DENSITY | |STANDARD DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 0.848463 kg/m3 | | |
|In Use Value: | | | | 1.00 kg/m3 |
| 0.712228 kg/m3 | | | | 0.50 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|Zs | |Zs |
| | | |
|Calculated Value: | |Keypad Value: |
| 0.000000 | | 1.000000 |
|In Use Value: | |Mode Status: |
| 0.000000 | |COMPRESS |
| | | |
+--------------------+ +--------------------+


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 271 of 395 Issue 7
MENU: CALCULATIONS|STREAM 1|ISO5167|INPUTS
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
|In Use DP Value: | | | |Limits (H/L) |
| 0.000 mbar | |Keypad Value: | | |
|NO CELL SELECTED | | 0.000 mbar | | 600.00 mbar |
|mode Status: | |Measured Value: | | 5.00 mbar |
|KEYPAD-F | | 0.000 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
| | | | | |
|Switch up point: | |Discrepancy: | |Check DP Value: |
| 95.000 % | | 10.000 % | | 20.000 mbar |
|Switch down point: | |Discrepancy timout: | |Live/Check: |
| 90.000 % | | 5.000 s | |LIVE |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |UPSTREAM PRESSURE |
|STR01 DP STACK | |STR01 DP STACK | | |
| | | | |In Use Value: |
|Low DP Cut Off: | |DP Cell type: | | 100.000000 barg |
| 10.000 mbar | |LO-HI-HI | | |
| | |Cut off mode: | | |
| | |NORMAL | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |VISCOSITY | |CORR PIPE DIAM |
| | | | | |
|In Use Value: | |Value: | |In Use Value: |
| 0.000000 | | 0.01710000 cP | | 300.264000 mm |
| | | | | |
|MODE | | | | |
|KEYPAD-F | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CORR ORIFICE DIAM | |ISENTROPIC EXPONENT | |DP TAP TYPE |
| | | | | |
|In Use Value: | |Value: | |Status: |
| 180.230400 mm | | 1.30000000 | |FLANGE |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|LF CUT OFF STATUS | |DOWNSTREAM PRESSURE | |CALC TYPE |

| | | | | |
|Status: | |In Use Value: | |Status: |
|SET | | 100.000000 barg | |1998 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|ISO5167|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|MASS FLOWRATE | |MASS FLOWRATE | |PRESSURE LOSS |
| | | | | |
|Calculated Value: | |Limits (H/L) | |Calculated Value: |
| 0.000000 t/h | | | | 0.000000 mbar |
|In Use Value: | | 1300.00 t/h | |In Use Value: |
| 0.000000 t/h | | 0.00 t/h | | 0.000000 mbar |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BETA | |REYNOLDS NUMBER | |EXPANSION FACTOR |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 272 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+
|DISCHARGE COEFF | |FLOW COEFFICIENT | |VEL OF APPROACH FAC |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|ISO6976|INPUTS
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |COMPOSITION TYPE | |REFERENCE CONDITIONS|
| | | | | |
|C6_PLUS | |Status: | |Status: |
| 0.00000000 % | |MOL % | |15/15 DEG |
| | | | | |
|CX_PLUS | | | | |
| 0.00000000 % | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|ISO6976|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|STD COMPRESS (Zs) | |STD COMPRESS (Zs) | |IDEAL REL DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 0.997817 | | 1.000000 | | 0.580191 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 0.000000 | |COMPRESS | | 0.580191 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|IDEAL REL DENSITY | |IDEAL STD DENSITY | |IDEAL STD DENSITY |
| | | | | |
|Keypad Value: | |Calculated Value: | |Keypad Value: |
| 0.500000 | | 0.710673 kg/m3 | | 0.750000 kg/m3 |
|Mode Status: | |In Use Value: | |Mode Status: |
|CV | | 0.710673 kg/m3 | |CALCULATED |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 273 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+
|IDEAL CALORIFIC VAL | |IDEAL CALORIFIC VAL | |REAL REL DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 38.515472 MJ/Sm3 | | 40.000000 MJ/Sm3 | | 0.581216 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 38.515472 MJ/Sm3 | |CALCULATED | | 0.581216 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|REAL REL DENSITY | |REAL STD DENSITY | |REAL STD DENSITY |
| | | | | |
|Keypad Value: | |Calculated Value: | |Keypad Value: |
| 0.500000 | | 0.712228 kg/m3 | | 0.848463 kg/m3 |
| | |In Use Value: | | |
| | | 0.712228 kg/m3 | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|REAL STD DENSITY | |REAL CALORIFIC VALUE| |REAL CALORIFIC VALUE|
| | | | | |
|Limits (H/L) | |Calculated Value: | |Keypad Value: |
| | | 38.599754 MJ/Sm3 | | 40.000000 MJ/Sm3 |
| 1.00 kg/m3 | |In Use Value: | | |
| 0.50 kg/m3 | | 38.599754 MJ/Sm3 | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|REAL CALORIFIC VALUE|
| |
|Limits (H/L) |
| |
| 42.00 MJ/Sm3 |
| 35.00 MJ/Sm3 |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|MASS CV|INPUTS
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |

| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 274 of 395 Issue 7
+--------------------+
|INUSE COMPOSITION |
| |
|C6_PLUS |
| 0.00000000 % |
| |
|CX_PLUS |
| 0.00000000 % |
+--------------------+

MENU: CALCULATIONS|STREAM 1|MASS CV|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|IDEAL CV (MASS) | |IDEAL CV (MASS) | |IDEAL CV (MASS) |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 MJ/kg | | 50.489000 MJ/kg | | |
|In Use Value: | |Mode Status: | | 52.49 MJ/kg |
| 0.000000 MJ/kg | |CALCULATED | | 48.49 MJ/kg |
| | | | | |
+--------------------+ +--------------------+ +--------------------+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 275 of 395 Issue 7
20.2 Gas Back Up
MENU: FLOW RATES|STREAM 1|STR01 UVOL FR
+--------------------+
|STR01 UVOL FR |
| 0.000 m3/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: FLOW RATES|STREAM 1|STR01 CVOL FR
+--------------------+ +--------------------+ +--------------------+
|STR01 CVOL FR | |STR01 CVOL FR C1-C4 | |STR01 CVOL BASE 1 FR|
| 0.000 Skm3/h | |MMSCF/d | | |
| | | | |Cur Day Max |
| | | 0.000 | | 0.000 |
| | | | | |
| | | | |Cur Day Min |
| | | | | 0.000 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 CVOL BASE 1 FR| |STR01 CVOL BASE 2 FR| |STR01 CVOL BASE 2 FR|
| | | | | |
|Prev Day Max | |Cur Day Max | |Prev Day Max |
| 0.000 | | 0.000 | | 0.000 |
| | | | | |
|Prev Day Min | |Cur Day Min | |Prev Day Min |
| 0.000 | | 0.000 | | 0.000 |

+--------------------+ +--------------------+ +--------------------+

MENU: FLOW RATES|STREAM 1|STR01 MASS FR
+--------------------+
|STR01 MASS FR |
| 0.000 t/h |
|Limits (H/L) |
| |
| 950.00 t/h |
| -5.00 t/h |
| |
+--------------------+

MENU: FLOW RATES|STREAM 1|STR01 ENERGY FR
+--------------------+
|STR01 ENERGY FR |
| 0.000 GJ/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: FLOW RATES|STREAM 2|STR02 UVOL FR
+--------------------+
|STR02 UVOL FR |
| 0.000 m3/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: FLOW RATES|STREAM 2|STR02 CVOL FR
+--------------------+ +--------------------+ +--------------------+

|STR02 CVOL FR | |STR02 CVOL FR C1-C4 | |STR02 CVOL BASE 1 FR|
| 0.000 Skm3/h | |MMSCF/d | | |
| | | | |Cur Day Max |
| | | 0.000 | | 0.000 |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 276 of 395 Issue 7
| | | | |Cur Day Min |
| | | | | 0.000 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 CVOL BASE 1 FR| |STR02 CVOL BASE 2 FR| |STR02 CVOL BASE 2 FR|
| | | | | |
|Prev Day Max | |Cur Day Max | |Prev Day Max |
| 0.000 | | 0.000 | | 0.000 |
| | | | | |
|Prev Day Min | |Cur Day Min | |Prev Day Min |
| 0.000 | | 0.000 | | 0.000 |
+--------------------+ +--------------------+ +--------------------+

MENU: FLOW RATES|STREAM 2|STR02 MASS FR
+--------------------+
|STR02 MASS FR |
| 0.000 t/h |
|Limits (H/L) |
| |
| 950.00 t/h |
| -5.00 t/h |
| |
+--------------------+

MENU: FLOW RATES|STREAM 2|STR02 ENERGY FR
+--------------------+
|STR02 ENERGY FR |
| 0.000 GJ/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: FLOW RATES|STREAM 3|STR03 UVOL FR
+--------------------+
|STR03 UVOL FR |
| 0.000 m3/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: FLOW RATES|STREAM 3|STR03 CVOL FR
+--------------------+ +--------------------+ +--------------------+
|STR03 CVOL FR | |STR03 CVOL FR C1-C4 | |STR03 CVOL BASE 1 FR|
| 0.000 Skm3/h | |MMSCF/d | | |
| | | | |Cur Day Max |
| | | 0.000 | | 0.000 |
| | | | | |
| | | | |Cur Day Min |
| | | | | 0.000 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 CVOL BASE 1 FR| |STR03 CVOL BASE 2 FR| |STR03 CVOL BASE 2 FR|
| | | | | |
|Prev Day Max | |Cur Day Max | |Prev Day Max |
| 0.000 | | 0.000 | | 0.000 |
| | | | | |
|Prev Day Min | |Cur Day Min | |Prev Day Min |
| 0.000 | | 0.000 | | 0.000 |
+--------------------+ +--------------------+ +--------------------+

MENU: FLOW RATES|STREAM 3|STR03 MASS FR
+--------------------+
|STR03 MASS FR |
| 0.000 t/h |
|Limits (H/L) |
| |
| 950.00 t/h |
| -5.00 t/h |
| |
+--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 277 of 395 Issue 7



MENU: FLOW RATES|STREAM 3|STR03 ENERGY FR
+--------------------+
|STR03 ENERGY FR |
| 0.000 GJ/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: TOTALS|STREAM 1|STR01 UVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 UVOL | |STR01 UVOL MAINT | |STR01 UVOL HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
| | |Previous Period: | |Previous Period: |
| | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR01 UVOL DAILY | |STR01 UVOL HOURLY B2| |STR01 UVOL DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 CVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 CVOL | |STR01 CVOL MAINT | |STR01 CVOL HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
| | |Previous Period: | |Previous Period: |

| | | 0.000 Skm3 | | 0.000 Skm3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR01 CVOL DAILY | |STR01 CVOL HOURLY B2| |STR01 CVOL DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 MASS
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 MASS | |STR01 MASS MAINT | |STR01 MASS HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
| | |Previous Period: | |Previous Period: |
| | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR01 MASS DAILY | |STR01 MASS HOURLY B2| |STR01 MASS DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 278 of 395 Issue 7



MENU: TOTALS|STREAM 1|STR01 ENERGY
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 ENERGY | |STR01 ENERGY MAINT | |STR01 ENERGY HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
| | |Previous Period: | |Previous Period: |
| | | 0.000 GJ | | 0.000 GJ |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR01 ENERGY DAILY | |STR01 ENERGY HOURLY | |STR01 ENERGY DAILY B|
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 MASS COMP
+--------------------+ +--------------------+ +--------------------+
|STR01 MASS C1 C4 | |STR01 MASS C1 | |STR01 MASS C2 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|tonne | |tonne | |tonne |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 MASS C3 | |STR01 MASS IC4 | |STR01 MASS NC4 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|tonne | |tonne | |tonne |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 MASS C5+ | |STR01 MASS CO2 | |STR01 MASS N2 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|tonne | |tonne | |tonne |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 SVOL COMP
+--------------------+ +--------------------+
|STR01 CVOL C1 C4 | |STR01 CVOL C5+ |
| | | |
| 0.000 | | 0.000 |
|Skm3 | |Skm3 |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 ENERGY COM
+--------------------+ +--------------------+ +--------------------+
|STR01 ENERGY C1 C4 | |STR01 ENERGY C5+ | |STR01 ENERGY C1 C4 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|GJ | |GJ | |MBtu |

| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 279 of 395 Issue 7



+--------------------+
|STR01 ENERGY C5+ |
| |
| 0.000 |
|MBtu |
| |
| |
| |
+--------------------+

MENU: TOTALS|STREAM 2|STR02 UVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR02 UVOL | |STR02 UVOL MAINT | |STR02 UVOL HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
| | |Previous Period: | |Previous Period: |
| | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR02 UVOL DAILY | |STR02 UVOL HOURLY B2| |STR02 UVOL DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 2|STR02 CVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR02 CVOL | |STR02 CVOL MAINT | |STR02 CVOL HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
| | |Previous Period: | |Previous Period: |
| | | 0.000 Skm3 | | 0.000 Skm3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR02 CVOL DAILY | |STR02 CVOL HOURLY B2| |STR02 CVOL DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 2|STR02 MASS
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR02 MASS | |STR02 MASS MAINT | |STR02 MASS HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
| | |Previous Period: | |Previous Period: |
| | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR02 MASS DAILY | |STR02 MASS HOURLY B2| |STR02 MASS DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 280 of 395 Issue 7



MENU: TOTALS|STREAM 2|STR02 ENERGY
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR02 ENERGY | |STR02 ENERGY MAINT | |STR02 ENERGY HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
| | |Previous Period: | |Previous Period: |
| | | 0.000 GJ | | 0.000 GJ |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR02 ENERGY DAILY | |STR02 ENERGY HOURLY | |STR02 ENERGY DAILY B|
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 2|STR02 MASS COMP
+--------------------+ +--------------------+ +--------------------+
|STR02 MASS C1 C4 | |STR02 MASS C1 | |STR02 MASS C2 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|tonne | |tonne | |tonne |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 MASS C3 | |STR02 MASS IC4 | |STR02 MASS NC4 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|tonne | |tonne | |tonne |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 MASS C5+ | |STR02 MASS CO2 | |STR02 MASS N2 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|tonne | |tonne | |tonne |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 2|STR02 SVOL COMP
+--------------------+ +--------------------+
|STR02 CVOL C1 C4 | |STR02 CVOL C5+ |
| | | |
| 0.000 | | 0.000 |
|Skm3 | |Skm3 |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: TOTALS|STREAM 2|STR02 ENERGY COM
+--------------------+ +--------------------+ +--------------------+
|STR02 ENERGY C1 C4 | |STR02 ENERGY C5+ | |STR02 ENERGY C1 C4 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|GJ | |GJ | |MBtu |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 281 of 395 Issue 7



+--------------------+
|STR02 ENERGY C5+ |
| |
| 0.000 |
|MBtu |
| |
| |
| |
+--------------------+

MENU: TOTALS|STREAM 3|STR03 UVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR03 UVOL | |STR03 UVOL MAINT | |STR03 UVOL HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
| | |Previous Period: | |Previous Period: |
| | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR03 UVOL DAILY | |STR03 UVOL HOURLY B2| |STR03 UVOL DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 3|STR03 CVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR03 CVOL | |STR03 CVOL MAINT | |STR03 CVOL HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
| | |Previous Period: | |Previous Period: |
| | | 0.000 Skm3 | | 0.000 Skm3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR03 CVOL DAILY | |STR03 CVOL HOURLY B2| |STR03 CVOL DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 3|STR03 MASS
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR03 MASS | |STR03 MASS MAINT | |STR03 MASS HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
| | |Previous Period: | |Previous Period: |
| | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR03 MASS DAILY | |STR03 MASS HOURLY B2| |STR03 MASS DAILY B2 |
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 282 of 395 Issue 7



MENU: TOTALS|STREAM 3|STR03 ENERGY
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR03 ENERGY | |STR03 ENERGY MAINT | |STR03 ENERGY HOURLY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
| | |Previous Period: | |Previous Period: |
| | | 0.000 GJ | | 0.000 GJ |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR03 ENERGY DAILY | |STR03 ENERGY HOURLY | |STR03 ENERGY DAILY B|
| | | | | |
|Current Period: | |Current Period: | |Current Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
|Previous Period: | |Previous Period: | |Previous Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 3|STR03 MASS COMP
+--------------------+ +--------------------+ +--------------------+
|STR03 MASS C1 C4 | |STR03 MASS C1 | |STR03 MASS C2 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|tonne | |tonne | |tonne |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 MASS C3 | |STR03 MASS IC4 | |STR03 MASS NC4 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|tonne | |tonne | |tonne |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 MASS C5+ | |STR03 MASS CO2 | |STR03 MASS N2 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|tonne | |tonne | |tonne |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 3|STR03 SVOL COMP
+--------------------+ +--------------------+
|STR03 CVOL C1 C4 | |STR03 CVOL C5+ |
| | | |
| 0.000 | | 0.000 |
|Skm3 | |Skm3 |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: TOTALS|STREAM 3|STR03 ENERGY COM
+--------------------+ +--------------------+ +--------------------+
|STR03 ENERGY C1 C4 | |STR03 ENERGY C5+ | |STR03 ENERGY C1 C4 |
| | | | | |
| 0.000 | | 0.000 | | 0.000 |
|GJ | |GJ | |MBtu |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 283 of 395 Issue 7



+--------------------+
|STR03 ENERGY C5+ |
| |
| 0.000 |
|MBtu |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|COMPOSITION|SPV/KEYPAD MOLES
+--------------------+ +--------------------+ +--------------------+
|USE SPV/STR DATA | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|Status: | |NITROGEN | |H2S |
|SPV | | 0.0000 % | | 0.0000 % |
| | | | | |
| | |CO2 | |H2O |
| | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|HELIUM | |ETHANE | |N_BUTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|METHANE | |PROPANE | |I_BUTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|N_PENTANE | |NEO_PENTANE | |HEPTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|I_PENTANE | |HEXANE | |OCTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|NONANE | |OXYGEN | |HYDROGEN |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|DECANE | |CO | |BENZENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|TOLUENE | |C6_PLUS | |TOTAL |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|ARGON | |CX_PLUS | | |
| 0.0000 % | | 0.0000 % | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|COMPOSITION|SELECTED MOLES
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 284 of 395 Issue 7
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES |
| | | |
|C6_PLUS | |TOTAL |
| 0.0000 % | | 0.0000 % |
| | | |
|CX_PLUS | | |
| 0.0000 % | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|COMPOSITION|COMMAND
+--------------------+ +--------------------+
|MOLE SELECT | |ACCEPTANCE COMMAND |
| | | |
|Status: | |Status: |
|KEYPAD | |IDLE |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|STREAM SETUP
+--------------------+ +--------------------+ +--------------------+
|STR01 STREAM TYPE | |STR01 NAME | |STR01 METER LOCATION|
| | | | | |
|Status: | |Value: | |Value: |
|GAS DP | |GAS DP | |LINE 1 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 STD TEMP | |STR01 STD PRESS | |STR01 LF CUT OFF |
| | | | | |
|Value: | |Value: | |Value: |
| 15.00000000 Deg.C | | 0.00000000 barg | | 5.00000000 t/h |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|STR01 FLOW DIRECTION|
| |
|Status: |
|FORWARD |
| |
| |
| |
+--------------------+






Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 285 of 395 Issue 7



MENU: OPERATOR|STREAM 1|STREAM STATUS
+--------------------+ +--------------------+ +--------------------+
|STR01 STATUS | |STR01 DISABLE | |STR01 LOW FLOW STAT |
| | | | | |
|Status: | |Status: | |Status: |
|OFF-LINE | |CLEAR | |SET |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|METER SETUP
+--------------------+ +--------------------+ +--------------------+
|STR01 TEMP EXP COEFF| |STR01 DENS EXP COEFF| |STR01 CALIB PIPE DIA|
| | | | | |
|Value: | |Value: | |Value: |
| -0.23076900 | | 0.76923100 | | 300.00000000 mm |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 PIPE MATERIAL | |STR01 PIPE TEMP EXP | |STR01 PIPE CALIB TEM|
| | | | | |
|Status: | |Value: | |Value: |
|USER | | 0.00001100 | | 20.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 CALIB ORIF DIA| |STR01 ORIF MATERIAL | |STR01 ORIF EXP CONST|
| | | | | |
|Value: | |Status: | |Value: |
| 200.00000000 mm | |USER | | 0.00001600 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 ORIF CALIB TEM| |STR01 ISENTROPIC EXP| |STR01 VISCOSITY |
| | | | | |
|Value: | |Value: | |Value: |
| 20.00000000 Deg.C | | 1.30000000 | | 0.01710000 cP |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|DENS OF AIR | |STR01 DOWN/UP CORREC|
| | | |
|Value: | |Status: |
| 1.22550000 kg/m3 | |EXTENDED |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+
MENU: OPERATOR|STREAM 1|METERING IO
+--------------------+ +--------------------+ +--------------------+
|STR01 METER TEMP | |STR01 METER TEMP | |STR01 METER PRESSURE|
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 100.00 barg |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 METER PRESSURE| |DP Stack 1 | |DP Stack 1 |
| | |STR01 DP STACK | |STR01 DP STACK |
|Keypad Value: | |In Use DP Value: | | |
| 100.00 barg | | 0.000 mbar | |Keypad Value: |
|Mode Status: | |NO CELL SELECTED | | 0.000 mbar |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 286 of 395 Issue 7
|KEYPAD-F | |mode Status: | |Measured Value: |
| | |KEYPAD-F | | 0.000 mbar |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
|Limits (H/L) | | | | |
| | |Switch up point: | |Discrepancy: |
| 95.00 mbar | | 95.000 % | | 10.000 % |
| 5.00 mbar | |Switch down point: | |Discrepancy timout: |
| | | 90.000 % | | 5.000 s |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
| | | | | |
|Check DP Value: | |Low DP Cut Off: | |DP Cell type: |
| 20.000 mbar | | 10.000 mbar | |SINGLE |
|Live/Check: | | | |Cut off mode: |
|LIVE | | | |NORMAL |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|CALCULATED DATA
+--------------------+ +--------------------+ +--------------------+
|STR01 DOWNSTR PRESS | |STR01 RECOVERED PRES| |STR01 UPSTREAM TEMP |
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|CALCULATED | |CALCULATED | |CALCULATED |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 DOWNSTREAM TEM| |STR01 PRESS LOSS | |STR01 CORR PIPE DIAM|
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 100.000000 Deg.C | | 0.000000 mbar | | 300.264000 mm |
| | | | | |
| | |Mode Status: | |Mode Status: |
| | |CALCULATED | |CALCULATED |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 CORR ORIF DIAM| |STR01 UPSTR COMPRESS| |STR01 STD COMPRESS |
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 200.256000 mm | | 0.000000 | | 0.000000 |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|CALCULATED | |COMPRESS | |COMPRESS |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 UPSTREAM DENS | |STR01 UPSTREAM DENS | |STR01 UPSTREAM DENS |
| | | | | |
|In Use Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | |
| | | | | 100.00 kg/m3 |
| | | | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 STANDARD DENS | |STR01 STANDARD DENS | |STR01 STANDARD DENS |
| | | | | |
|In Use Value: | |Keypad Value: | |Limits (H/L) |
| 0.712228 kg/m3 | | 10.000000 kg/m3 | | |
| | | | | 100.00 kg/m3 |
| | | | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 REAL RDENS | |STR01 CV (MASS) | |STR01 CV (MASS) |
| | | | | |
|In Use Value: | |In Use Value: | |Keypad Value: |
| 0.581216 | | 0.000000 MJ/kg | | 50.100000 MJ/kg |
| | | | | |
|Mode Status: | | | | |
|CV | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 287 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+


+--------------------+ +--------------------+
|STR01 BETA | |STR01 REYNOLDS NO |
| | | |
|In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 2|COMPOSITION|SPV/KEYPAD MOLES
+--------------------+ +--------------------+ +--------------------+
|USE SPV/STR DATA | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|Status: | |NITROGEN | |H2S |
|SPV | | 0.0000 % | | 0.0000 % |
| | | | | |
| | |CO2 | |H2O |
| | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|HELIUM | |ETHANE | |N_BUTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|METHANE | |PROPANE | |I_BUTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|N_PENTANE | |NEO_PENTANE | |HEPTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|I_PENTANE | |HEXANE | |OCTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|NONANE | |OXYGEN | |HYDROGEN |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|DECANE | |CO | |BENZENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|TOLUENE | |C6_PLUS | |TOTAL |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|ARGON | |CX_PLUS | | |
| 0.0000 % | | 0.0000 % | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 2|COMPOSITION|SELECTED MOLES
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 288 of 395 Issue 7
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES |
| | | |
|C6_PLUS | |TOTAL |
| 0.0000 % | | 0.0000 % |
| | | |
|CX_PLUS | | |
| 0.0000 % | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 2|COMPOSITION|COMMAND
+--------------------+ +--------------------+
|MOLE SELECT | |ACCEPTANCE COMMAND |
| | | |
|Status: | |Status: |
|KEYPAD | |IDLE |

| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 2|STREAM SETUP
+--------------------+ +--------------------+ +--------------------+
|STR02 STREAM TYPE | |STR02 NAME | |STR02 METER LOCATION|
| | | | | |
|Status: | |Value: | |Value: |
|GAS DP | |GAS DP | |LINE 1 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 STD TEMP | |STR02 STD PRESS | |STR02 LF CUT OFF |
| | | | | |
|Value: | |Value: | |Value: |
| 15.00000000 Deg.C | | 0.00000000 barg | | 5.00000000 t/h |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|STR02 FLOW DIRECTION|
| |
|Status: |
|FORWARD |
| |
| |
| |
+--------------------+





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 289 of 395 Issue 7



MENU: OPERATOR|STREAM 2|STREAM STATUS
+--------------------+ +--------------------+ +--------------------+
|STR02 STATUS | |STR02 DISABLE | |STR02 LOW FLOW STAT |
| | | | | |
|Status: | |Status: | |Status: |
|OFF-LINE | |CLEAR | |SET |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 2|METER SETUP
+--------------------+ +--------------------+ +--------------------+
|STR02 TEMP EXP COEFF| |STR02 DENS EXP COEFF| |STR02 CALIB PIPE DIA|
| | | | | |
|Value: | |Value: | |Value: |
| -0.23076900 | | 0.76923100 | | 300.00000000 mm |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 PIPE MATERIAL | |STR02 PIPE TEMP EXP | |STR02 PIPE CALIB TEM|
| | | | | |
|Status: | |Value: | |Value: |
|USER | | 0.00001100 | | 20.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 CALIB ORIF DIA| |STR02 ORIF MATERIAL | |STR02 ORIF EXP CONST|
| | | | | |
|Value: | |Status: | |Value: |
| 200.00000000 mm | |USER | | 0.00001600 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 ORIF CALIB TEM| |STR02 ISENTROPIC EXP| |STR02 VISCOSITY |
| | | | | |
|Value: | |Value: | |Value: |
| 20.00000000 Deg.C | | 1.30000000 | | 0.01710000 cP |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|DENS OF AIR | |STR02 DOWN/UP CORREC|
| | | |
|Value: | |Status: |
| 1.22550000 kg/m3 | |EXTENDED |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+
MENU: OPERATOR|STREAM 2|METERING IO
+--------------------+ +--------------------+ +--------------------+
|STR02 METER TEMP | |STR02 METER TEMP | |STR02 METER PRESSURE|
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 100.00 barg |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 METER PRESSURE| |DP Stack 2 | |DP Stack 2 |
| | |STR02 DP STACK | |STR02 DP STACK |
|Keypad Value: | |In Use DP Value: | | |
| 100.00 barg | | 0.000 mbar | |Keypad Value: |
|Mode Status: | |NO CELL SELECTED | | 0.000 mbar |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 290 of 395 Issue 7
|KEYPAD-F | |mode Status: | |Measured Value: |
| | |KEYPAD-F | | 0.000 mbar |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 2 | |DP Stack 2 | |DP Stack 2 |
|STR02 DP STACK | |STR02 DP STACK | |STR02 DP STACK |
|Limits (H/L) | | | | |
| | |Switch up point: | |Discrepancy: |
| 95.00 mbar | | 95.000 % | | 10.000 % |
| 5.00 mbar | |Switch down point: | |Discrepancy timout: |
| | | 90.000 % | | 5.000 s |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 2 | |DP Stack 2 | |DP Stack 2 |
|STR02 DP STACK | |STR02 DP STACK | |STR02 DP STACK |
| | | | | |
|Check DP Value: | |Low DP Cut Off: | |DP Cell type: |
| 20.000 mbar | | 10.000 mbar | |SINGLE |
|Live/Check: | | | |Cut off mode: |
|LIVE | | | |NORMAL |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 2|CALCULATED DATA
+--------------------+ +--------------------+ +--------------------+
|STR02 DOWNSTR PRESS | |STR02 RECOVERED PRES| |STR02 UPSTREAM TEMP |
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|CALCULATED | |CALCULATED | |CALCULATED |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 DOWNSTREAM TEM| |STR02 PRESS LOSS | |STR02 CORR PIPE DIAM|
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 100.000000 Deg.C | | 0.000000 mbar | | 300.264000 mm |
| | | | | |
| | |Mode Status: | |Mode Status: |
| | |CALCULATED | |CALCULATED |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 CORR ORIF DIAM| |STR02 UPSTR COMPRESS| |STR02 STD COMPRESS |
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 200.256000 mm | | 0.000000 | | 0.000000 |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|CALCULATED | |COMPRESS | |COMPRESS |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 UPSTREAM DENS | |STR02 UPSTREAM DENS | |STR02 UPSTREAM DENS |
| | | | | |
|In Use Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | |
| | | | | 100.00 kg/m3 |
| | | | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR02 STANDARD DENS | |STR02 STANDARD DENS | |STR02 STANDARD DENS |
| | | | | |
|In Use Value: | |Keypad Value: | |Limits (H/L) |
| 0.712228 kg/m3 | | 10.000000 kg/m3 | | |
| | | | | 100.00 kg/m3 |
|Mode Status: | | | | 0.20 kg/m3 |
|CV | | | | |
+--------------------+ +--------------------+ +--------------------+

+--------------------+ +--------------------+ +--------------------+
|STR02 REAL RDENS | |STR02 CV (MASS) | |STR02 CV (MASS) |
| | | | | |
|In Use Value: | |In Use Value: | |Keypad Value: |
| 0.581216 | | 0.000000 MJ/kg | | 50.200000 MJ/kg |
| | | | | |
|Mode Status: | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 291 of 395 Issue 7
|CV | | | | |
+--------------------+ +--------------------+ +--------------------+

+--------------------+ +--------------------+
|STR02 BETA | |STR02 REYNOLDS NO |
| | | |
|In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 3|COMPOSITION|SPV/KEYPAD MOLES
+--------------------+ +--------------------+ +--------------------+
|USE SPV/STR DATA | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|Status: | |NITROGEN | |H2S |
|SPV | | 0.0000 % | | 0.0000 % |
| | | | | |
| | |CO2 | |H2O |
| | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|HELIUM | |ETHANE | |N_BUTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|METHANE | |PROPANE | |I_BUTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|N_PENTANE | |NEO_PENTANE | |HEPTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|I_PENTANE | |HEXANE | |OCTANE |

| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|NONANE | |OXYGEN | |HYDROGEN |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|DECANE | |CO | |BENZENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|TOLUENE | |C6_PLUS | |TOTAL |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|ARGON | |CX_PLUS | | |
| 0.0000 % | | 0.0000 % | | |
+--------------------+ +--------------------+ +--------------------+
MENU: OPERATOR|STREAM 3|COMPOSITION|SELECTED MOLES
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 292 of 395 Issue 7
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES |
| | | |
|C6_PLUS | |TOTAL |
| 0.0000 % | | 0.0000 % |
| | | |
|CX_PLUS | | |
| 0.0000 % | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 3|COMPOSITION|COMMAND
+--------------------+ +--------------------+
|MOLE SELECT | |ACCEPTANCE COMMAND |
| | | |
|Status: | |Status: |
|KEYPAD | |IDLE |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 3|STREAM SETUP
+--------------------+ +--------------------+ +--------------------+
|STR03 STREAM TYPE | |STR03 NAME | |STR03 METER LOCATION|
| | | | | |
|Status: | |Value: | |Value: |
|GAS DP | |GAS DP | |LINE 1 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 STD TEMP | |STR03 STD PRESS | |STR03 LF CUT OFF |
| | | | | |
|Value: | |Value: | |Value: |
| 15.00000000 Deg.C | | 0.00000000 barg | | 5.00000000 t/h |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|STR03 FLOW DIRECTION|
| |
|Status: |
|FORWARD |
| |
| |
| |
+--------------------+






Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 293 of 395 Issue 7



MENU: OPERATOR|STREAM 3|STREAM STATUS
+--------------------+ +--------------------+ +--------------------+
|STR03 STATUS | |STR03 DISABLE | |STR03 LOW FLOW STAT |
| | | | | |
|Status: | |Status: | |Status: |
|OFF-LINE | |CLEAR | |SET |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 3|METER SETUP
+--------------------+ +--------------------+ +--------------------+
|STR03 TEMP EXP COEFF| |STR03 DENS EXP COEFF| |STR03 CALIB PIPE DIA|
| | | | | |
|Value: | |Value: | |Value: |
| -0.23076900 | | 0.76923100 | | 300.00000000 mm |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 PIPE MATERIAL | |STR03 PIPE TEMP EXP | |STR03 PIPE CALIB TEM|
| | | | | |
|Status: | |Value: | |Value: |
|USER | | 0.00001100 | | 20.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 CALIB ORIF DIA| |STR03 ORIF MATERIAL | |STR03 ORIF EXP CONST|
| | | | | |
|Value: | |Status: | |Value: |
| 200.00000000 mm | |USER | | 0.00001600 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 ORIF CALIB TEM| |STR03 ISENTROPIC EXP| |STR03 VISCOSITY |
| | | | | |
|Value: | |Value: | |Value: |
| 20.00000000 Deg.C | | 1.30000000 | | 0.01710000 cP |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|DENS OF AIR | |STR03 DOWN/UP CORREC|
| | | |
|Value: | |Status: |
| 1.22550000 kg/m3 | |EXTENDED |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+
MENU: OPERATOR|STREAM 3|METERING IO
+--------------------+ +--------------------+ +--------------------+
|STR03 METER TEMP | |STR03 METER TEMP | |STR03 METER PRESSURE|
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 100.00 barg |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 METER PRESSURE| |DP Stack 3 | |DP Stack 3 |
| | |STR03 DP STACK | |STR03 DP STACK |
|Keypad Value: | |In Use DP Value: | | |
| 100.00 barg | | 0.000 mbar | |Keypad Value: |
|Mode Status: | |NO CELL SELECTED | | 0.000 mbar |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 294 of 395 Issue 7
|KEYPAD-F | |mode Status: | |Measured Value: |
| | |KEYPAD-F | | 0.000 mbar |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 3 | |DP Stack 3 | |DP Stack 3 |
|STR03 DP STACK | |STR03 DP STACK | |STR03 DP STACK |
|Limits (H/L) | | | | |
| | |Switch up point: | |Discrepancy: |
| 95.00 mbar | | 95.000 % | | 10.000 % |
| 5.00 mbar | |Switch down point: | |Discrepancy timout: |
| | | 90.000 % | | 5.000 s |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 3 | |DP Stack 3 | |DP Stack 3 |

|STR03 DP STACK | |STR03 DP STACK | |STR03 DP STACK |
| | | | | |
|Check DP Value: | |Low DP Cut Off: | |DP Cell type: |
| 20.000 mbar | | 10.000 mbar | |SINGLE |
|Live/Check: | | | |Cut off mode: |
|LIVE | | | |NORMAL |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 3|CALCULATED DATA
+--------------------+ +--------------------+ +--------------------+
|STR03 DOWNSTR PRESS | |STR03 RECOVERED PRES| |STR03 UPSTREAM TEMP |
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|CALCULATED | |CALCULATED | |CALCULATED |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 DOWNSTREAM TEM| |STR03 PRESS LOSS | |STR03 PRESS LOSS |
| | | | | |
|In Use Value: | |In Use Value: | |Keypad Value: |
| 100.000000 Deg.C | | 0.000000 mbar | | 0.000000 mbar |
| | | | | |
| | |Mode Status: | |Mode Status: |
| | |CALCULATED | |CALCULATED |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 CORR PIPE DIAM| |STR03 CORR ORIF DIAM| |STR03 UPSTR COMPRESS|
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 300.264000 mm | | 200.256000 mm | | 0.000000 |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|CALCULATED | |CALCULATED | |COMPRESS |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 STD COMPRESS | |STR03 UPSTREAM DENS | |STR03 UPSTREAM DENS |
| | | | | |
|In Use Value: | |In Use Value: | |Keypad Value: |
| 0.000000 | | 0.000000 kg/m3 | | 50.000000 kg/m3 |
| | | | | |
|Mode Status: | | | | |
|COMPRESS | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 UPSTREAM DENS | |STR03 STANDARD DENS | |STR03 STANDARD DENS |
| | | | | |
|Limits (H/L) | |In Use Value: | |Keypad Value: |
| | | 0.712228 kg/m3 | | 10.000000 kg/m3 |
| 100.00 kg/m3 | | | | |
| 0.20 kg/m3 | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR03 STANDARD DENS | |STR03 REAL RDENS | |STR03 CV (MASS) |
| | | | | |
|Limits (H/L) | |In Use Value: | |In Use Value: |
| | | 0.581216 | | 0.000000 MJ/kg |
| 100.00 kg/m3 | | | | |
| 0.20 kg/m3 | |Mode Status: | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 295 of 395 Issue 7
| | |CV | | |
+--------------------+ +--------------------+ +--------------------+

+--------------------+ +--------------------+ +--------------------+
|STR03 CV (MASS) | |STR03 BETA | |STR03 REYNOLDS NO |
| | | | | |
|Keypad Value: | |In Use Value: | |In Use Value: |
| 50.300000 MJ/kg | | 0.000000 | | 0.000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 01 - STR01 P
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 1 | |ADC Channel 1 | |ADC Channel 1 |
|STR01 PRS | |STR01 PRS | |STR01 PRS |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 barg | | 100.000 barg | | 102.00 barg |
|Mode Status: | |Measured Value: | | -2.00 barg |
|KEYPAD-F | | -24.998 barg | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 1 | |ADC Channel 1 |
|STR01 PRS | |STR01 PRS |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 3.02877073E-04 mA | | 100.000 barg |
| | | 0.000 barg |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 02 - STR01 D
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 2 | |ADC Channel 2 | |ADC Channel 2 |
|STR01 DP | |STR01 DP | |STR01 DP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 0.000 mbar | | 0.000 mbar | | 102.00 mbar |
|Mode Status: | |Measured Value: | | -2.00 mbar |
|KEYPAD | | -24.998 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 2 | |ADC Channel 2 |
|STR01 DP | |STR01 DP |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 2.70933728E-04 mA | | 100.000 mbar |
| | | 0.000 mbar |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 03 - STR02 P
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 3 | |ADC Channel 3 | |ADC Channel 3 |
|STR02 PRS | |STR02 PRS | |STR02 PRS |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 barg | | 100.000 barg | | 102.00 barg |
|Mode Status: | |Measured Value: | | -2.00 barg |
|KEYPAD-F | | -24.999 barg | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 3 | |ADC Channel 3 |
|STR02 PRS | |STR02 PRS |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 1.38678777E-04 mA | | 100.000 barg |
| | | 0.000 barg |
| | | |
+--------------------+ +--------------------+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 296 of 395 Issue 7



MENU: PLANT I/O|ANALOG INPUTS|ADC 04 - STR02 D
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 4 | |ADC Channel 4 | |ADC Channel 4 |
|STR02 DP | |STR02 DP | |STR02 DP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 0.000 mbar | | 0.000 mbar | | 102.00 mbar |
|Mode Status: | |Measured Value: | | -2.00 mbar |
|KEYPAD | | -24.998 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 4 | |ADC Channel 4 |
|STR02 DP | |STR02 DP |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 3.29546951E-04 mA | | 100.000 mbar |
| | | 0.000 mbar |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 05 - STR03 P
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 5 | |ADC Channel 5 | |ADC Channel 5 |
|STR03 PRS | |STR03 PRS | |STR03 PRS |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 barg | | 100.000 barg | | 102.00 barg |
|Mode Status: | |Measured Value: | | -2.00 barg |
|KEYPAD-F | | -24.999 barg | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 5 | |ADC Channel 5 |
|STR03 PRS | |STR03 PRS |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 8.27157492E-05 mA | | 100.000 barg |
| | | 0.000 barg |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 06 - STR03 D
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 6 | |ADC Channel 6 | |ADC Channel 6 |
|STR03 DP | |STR03 DP | |STR03 DP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 0.000 mbar | | 0.000 mbar | | 102.00 mbar |
|Mode Status: | |Measured Value: | | -2.00 mbar |
|KEYPAD | | -24.998 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 6 | |ADC Channel 6 |
|STR03 DP | |STR03 DP |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 2.93845660E-04 mA | | 100.000 mbar |
| | | 0.000 mbar |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|PRT/RTD INPUTS|PRT 01 - STR01 T
+--------------------+ +--------------------+ +--------------------+
|PRT Input 1 | |PRT Input 1 | |PRT Input 1 |
|STR01 TMP | |STR01 TMP | |STR01 TMP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 Deg.C | | 100.000 Deg.C | | 102.00 Deg.C |
|Mode Status: | |Measured Value: | | -2.00 Deg.C |
|KEYPAD-F | | -100.627 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 297 of 395 Issue 7



+--------------------+
|PRT Channel 1 |
|STR01 TMP |
| |
|Resistance: |
| 0.000 ohms |
| |
| |
+--------------------+

MENU: PLANT I/O|PRT/RTD INPUTS|PRT 02 - STR02 T
+--------------------+ +--------------------+ +--------------------+
|PRT Input 2 | |PRT Input 2 | |PRT Input 2 |
|STR02 TMP | |STR02 TMP | |STR02 TMP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 Deg.C | | 100.000 Deg.C | | 102.00 Deg.C |
|Mode Status: | |Measured Value: | | -2.00 Deg.C |
|KEYPAD-F | | -100.627 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|PRT Channel 2 |
|STR02 TMP |
| |
|Resistance: |
| 0.000 ohms |
| |
| |
+--------------------+

MENU: PLANT I/O|PRT/RTD INPUTS|PRT 03 - STR03 T
+--------------------+ +--------------------+ +--------------------+
|PRT Input 3 | |PRT Input 3 | |PRT Input 3 |
|STR03 TMP | |STR03 TMP | |STR03 TMP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 Deg.C | | 100.000 Deg.C | | 102.00 Deg.C |
|Mode Status: | |Measured Value: | | -2.00 Deg.C |
|KEYPAD-F | | 311.204 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|PRT Channel 3 |
|STR03 TMP |
| |
|Resistance: |
| 85567.391 ohms |
| |
| |
+--------------------+

MENU: PLANT I/O|DIGITAL I/OS|DIGITAL IO 01
+--------------------+
|Discrete I/O 1 |
|I/O01 DIO 01 |
| |
|Input Status: |

|0000000000000000 |
|Output Status: |
|0000000000000000 |
+--------------------+

MENU: SYSTEM SETTINGS|UNIT SETUP|CONVERSIONS
+--------------------+ +--------------------+
|Conversions | |Conversions |
| | | |
|GJ -> MBtu | |Sm3/h -> MMSCF/d |
| | | |
|Value: | |Value: |
| 1.0551200 | | 0.8772016 |
| | | |
+--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 298 of 395 Issue 7




MENU: SYSTEM SETTINGS|UNIT SETUP|SETUP
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS MASS UNITS | |GAS MASS FR UNITS | |GAS GROSS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|tonne | |t/h | |m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS GROSS FR UNITS | |GAS NETT UNITS | |GAS NETT FR UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|m3/h | |Skm3 | |Skm3/h |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS ENGY UNITS | |GAS ENGY FR UNITS | |PRESS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|GJ | |GJ/h | |barg |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DP UNITS | |TEMP UNITS | |DENS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mbar | |Deg.C | |kg/m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|CV MASS UNITS | |CV VOL UNITS | |DYN VISC UNITS |

| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|MJ/kg | |MJ/Sm3 | |cP |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|FREQ UNITS | |LENGTH UNITS | |PERIOD UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|Hz | |mm | |uS |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|PERCENT UNITS | |DIAM UNITS | |AREA UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|% | |mm | |mm2 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|Unit Setup | |Unit Setup |
|VEL UNITS | |TIME UNITS |
| | | |
|Selected Unit: | |Selected Unit: |
|m/s | |s |
| | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 299 of 395 Issue 7
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|REPORT SETUP
+--------------------+ +--------------------+ +--------------------+
|REPORT CONTROL | |REPORT CONTROL | |BASETIME 1 |
|WEEK START | |MONTH START | | |
| | | | | |
|SUNDAY | |FIRST | | 6 |
| | | | | |
| | | | |O-CLOCK |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|ALARM SETUP
+--------------------+ +--------------------+
|ALARM CONTROL | |ALARM CONTROL |
|ALARM MODE | |ALARM ENABLE |
| | | |
|LATCHED | |YES |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|MAINTENANCE MODE
+--------------------+ +--------------------+ +--------------------+
| | | | | |
|SYSTEM MAINT ENAB | |STR01 MAINT MODE | |STR02 MAINT MODE |
| | | | | |
|SET | |CLEAR | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
| |
|STR03 MAINT MODE |
| |
|CLEAR |
| |
| |
| |
+--------------------+

MENU: SYSTEM SETTINGS|SYSTEM STATUS
+--------------------+
| |
|SYSTEM RUN MODE |
| |
|NORMAL |
| |
| |
| |
+--------------------+

MENU: SYSTEM SETTINGS|SOFTWARE VERSION
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|CONFIG NAME | |CONFIG FORMAT | |CONFIG VERSION |
| | | | | |
|Helang - BUG_CV | |5 | |101 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|CONFIG CREATED | |CONFIG LAST EDITED | |CONFIG STRUCTURE |
| | | | | |
|17 Jan 2002. 13:05 | |08 Apr 2003. 18:52 | |CSUM 5a04 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 300 of 395 Issue 7



+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|NMI CONSTANTS | |FILE CSUM | |REGISTRATION CODE |
| | | | | |
|AAAA-1111 | |AAAA | |1.3dMAKAWGG20011024P|
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|APPLICATION SW | |PC SETUP PACKAGE | |MAIN BOARD ID |
| | | | | |
|03.24a Jul 19 2002 | |1.3 | |00:A0:D8:FE:0D:89 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 HW_REV | |I/O01 MOD_STRIKE | |I/O01 BOARD SERNO |
| | | | | |
|REV 04 | |MOD E | |SN 06968 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 FIRST CALIB | |I/O01 LAST CALIB | |I/O01 SW VERSION |
| | | | | |
|09052003 | |09052003 | |01.01.16.00 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|VERSION CONTROL |
|I/O01 BOARD ID |
| |
|1.1.1.1.1.2.0 |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|DISPLAY SETUP
+--------------------+
|Display Setup |
| |
|DEF DISP : |
| |
|DISPLAY T/O: 300 s |
|LOGOUT T/O: 20 s |
|IDENT T/O: 120 s |
+--------------------+

MENU: TECH/ENGINEER|CONTRAST
+--------------------+
| |
| |
|CONTRAST : 8 |
| |
| |
| |
| |
+--------------------+






Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 301 of 395 Issue 7



MENU: TECH/ENGINEER|DATE & TIME
+--------------------+ +--------------------+
|Current Date & Time | |Date and Time Format|
| | | |
|07/02/1980 02:50:31 | | |
| | | |
| | |DD MM YYYY |

| | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|DISPLAY TEST
+--------------------+
| |
| |
|DISPLAY TEST |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|SECURITY
+--------------------+ +--------------------+
|Security Setup | |PC Setup Link |
| | | |
|Current Level: | |DISABLED |
|SECURITY : 9 | | |
| | | |
|Front Panel Keypad: | | |
|ENABLED | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 01
+--------------------+ +--------------------+ +--------------------+
|COM1 - DISPLAY | |COM1 - DISPLAY | |COM1 - DISPLAY |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM1 - DISPLAY |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 02
+--------------------+ +--------------------+ +--------------------+
|COM2 - PC LINK | |COM2 - PC LINK | |COM2 - PC LINK |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 38400 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM2 - PC LINK |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 302 of 395 Issue 7



MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 03
+--------------------+ +--------------------+ +--------------------+
|COM3 | |COM3 | |COM3 |
| | |GOOD_TX : 3664 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 290 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM3 |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |

| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 04
+--------------------+ +--------------------+ +--------------------+
|COM4 | |COM4 | |COM4 |
| | |GOOD_TX : 135 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 7 |
|HEALTHY | |BAD_RX : 135 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY EVEN |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM4 |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 05
+--------------------+ +--------------------+ +--------------------+
|COM5 | |COM5 | |COM5 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM5 |
| |
|HANDSHAKE NONE |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 06
+--------------------+ +--------------------+ +--------------------+
|COM6 | |COM6 | |COM6 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 303 of 395 Issue 7



+--------------------+
|COM6 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 07
+--------------------+ +--------------------+ +--------------------+
|COM7 | |COM7 | |COM7 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM7 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 08
+--------------------+ +--------------------+ +--------------------+
|COM8 - IO | |COM8 - IO | |COM8 - IO |
| | |GOOD_TX : 3083 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 38400 |
| | |GOOD_RX : 3083 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM8 - IO |
| |

|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|MODBUS ADDRESS
+--------------------+
|FLOW COMPUTER |
|SLAVE ADDRESS |
|1 |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 03
+--------------------+ +--------------------+
|COMMS TASK 03 | |COMMS TASK 03 |
| | | |
|Port: | |Address: |
|PORT 6 | |11 |
|Protocol: | | |
|MODBUS TCP | | |
| | | |
+--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 304 of 395 Issue 7



MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|SLAVE LINK
+--------------------+ +--------------------+
|SLAVE LINK | |SLAVE LINK |
| | | |
|Port: | |Address: |
|PORT 4 | |11 |
|Protocol: | | |
|MODBUS TCP | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 06
+--------------------+ +--------------------+
|COMMS TASK 06 | |COMMS TASK 06 |
| | | |
|Port: | |Address: |
|PORT 6 | |11 |
|Protocol: | | |
|RTU SERIAL | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 07
+--------------------+ +--------------------+
|COMMS TASK 07 | |COMMS TASK 07 |
| | | |
|Port: | |Address: |
|PORT 7 | |11 |
|Protocol: | | |
|RTU SERIAL | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|PRINTER
+--------------------+
|PRINTER |
| |
|Port: |
|PORT 3 |
| |
| |

| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|DOWN/UP CORR|INPUTS
+--------------------+ +--------------------+ +--------------------+
|METER TEMP | |METER TEMP | |DP Stack 1 |
| | | | |STR01 DP STACK |
|In Use Value: | |Keypad Value: | |In Use DP Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 0.000 mbar |
| | |Mode Status: | |NO CELL SELECTED |
| | |KEYPAD-F | |mode Status: |
| | | | |KEYPAD-F |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
| | |Limits (H/L) | | |
|Keypad Value: | | | |Switch up point: |
| 0.000 mbar | | 95.00 mbar | | 95.000 % |
|Measured Value: | | 5.00 mbar | |Switch down point: |
| 0.000 mbar | | | | 90.000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
| | | | | |
|Discrepancy: | |Check DP Value: | |Low DP Cut Off: |
| 10.000 % | | 20.000 mbar | | 10.000 mbar |
|Discrepancy timout: | |Live/Check: | | |
| 5.000 s | |LIVE | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 305 of 395 Issue 7



+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |METER PRESSURE | |METER PRESSURE |
|STR01 DP STACK | | | | |
| | |In Use Value: | |Keypad Value: |
|DP Cell type: | | 100.00 barg | | 100.00 barg |
|SINGLE | | | |Mode Status: |
|Cut off mode: | | | |KEYPAD-F |
|NORMAL | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PRESSURE LOSS | |TEMP EXP CONSTANT | |DENS EXP CONSTANT |
| | | | | |
|In Use Value: | |Value: | |Value: |
| 0.000000 mbar | | -0.23076900 | | 0.76923100 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|TEMP MEAS POINT | |PRESS MEAS POINT | |CORRECTION TYPE |
| | | | | |
|Status: | |Status: | |Status: |
|DOWNSTREAM | |UPSTREAM | |EXTENDED |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|DOWN/UP CORR|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|DOWNSTREAM PRESSURE | |RECOVERED PRESSURE | |UPSTREAM TEMP |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
|In Use Value: | |In Use Value: | |In Use Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |UPSTREAM DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 50.000000 kg/m3 | | 50.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
| 0.000000 kg/m3 | |COMPRESS | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|PIPE CORRECTION|INPUTS
+--------------------+ +--------------------+ +--------------------+
|CALIB PIPE DIAM | |CALIB ORIFICE DIAM | |PIPE CALIB TEMP |
| | | | | |
|Value: | |Value: | |Value: |
| 300.00000000 mm | | 200.00000000 mm | | 20.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|ORIFICE CALIB TEMP | |PIPE EXP CONSTANT | |ORIFICE EXP CONSTANT|
| | | | | |
|Value: | |Value: | |Value: |
| 20.00000000 Deg.C | | 0.00001100 | | 0.00001600 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM TEMP | |UPSTREAM TEMP | |PIPE MATERIAL |
| | | | | |
|In Use Value: | |Keypad Value: | |Status: |
| 100.000000 Deg.C | | 50.000000 Deg.C | |USER |
| | |Mode Status: | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 306 of 395 Issue 7
| | |CALCULATED | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|ORIFICE MATERIAL |
| |
|Status: |
|USER |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|PIPE CORRECTION|OUTPUTS
+--------------------+ +--------------------+
|CORRECTED PIPE DIAM | |CORRECTED ORIF DIAM |
| | | |
|Calculated Value: | |Calculated Value: |
| 300.264000 mm | | 200.256000 mm |
|In Use Value: | |In Use Value: |
| 300.264000 mm | | 200.256000 mm |
| | | |
+--------------------+ +--------------------+
MENU: CALCULATIONS|STREAM 1|AGA 8|INPUTS
+--------------------+ +--------------------+ +--------------------+
|AGA8 METHOD | |UPSTREAM PRESS | |UPSTREAM TEMP |
| | | | | |
|Status: | |In Use Value: | |In Use Value: |
|DETAIL | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STANDARD PRESS | |STANDARD TEMP | |INUSE COMPOSITION |
| | | | | |

|Value: | |Value: | |NITROGEN |
| 0.00000000 barg | | 15.00000000 Deg.C | | 0.00000000 % |
| | | | | |
| | | | |CO2 |
| | | | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|H2S | |HELIUM | |ETHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|H2O | |METHANE | |PROPANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|N_BUTANE | |N_PENTANE | |NEO_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|I_BUTANE | |I_PENTANE | |HEXANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|HEPTANE | |NONANE | |OXYGEN |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|OCTANE | |DECANE | |CO |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|HYDROGEN | |TOLUENE | |C6_PLUS |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 307 of 395 Issue 7
|BENZENE | |ARGON | |CX_PLUS |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
MENU: CALCULATIONS|STREAM 1|AGA 8|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |UPSTREAM DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
| 0.000000 kg/m3 | |COMPRESS | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Zf | |Zb | |MOLECULAR WEIGHT |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STANDARD DENSITY | |STANDARD DENSITY | |STANDARD DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 10.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
| 0.712228 kg/m3 | |CV | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|Zs | |Zs |
| | | |
|Calculated Value: | |Keypad Value: |
| 0.000000 | | 1.000000 |
|In Use Value: | |Mode Status: |
| 0.000000 | |COMPRESS |
| | | |
+--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|ISO5167|INPUTS
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
|In Use DP Value: | | | |Limits (H/L) |
| 0.000 mbar | |Keypad Value: | | |
|NO CELL SELECTED | | 0.000 mbar | | 95.00 mbar |
|mode Status: | |Measured Value: | | 5.00 mbar |
|KEYPAD-F | | 0.000 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
| | | | | |
|Switch up point: | |Discrepancy: | |Check DP Value: |
| 95.000 % | | 10.000 % | | 20.000 mbar |
|Switch down point: | |Discrepancy timout: | |Live/Check: |
| 90.000 % | | 5.000 s | |LIVE |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |UPSTREAM PRESSURE |
|STR01 DP STACK | |STR01 DP STACK | | |
| | | | |In Use Value: |
|Low DP Cut Off: | |DP Cell type: | | 100.000000 barg |
| 10.000 mbar | |SINGLE | | |
| | |Cut off mode: | | |
| | |NORMAL | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |VISCOSITY |
| | | | | |
|In Use Value: | |Keypad Value: | |Value: |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | 0.01710000 cP |
| | |Mode Status: | | |
| | |COMPRESS | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 308 of 395 Issue 7
| | | | | |
+--------------------+ +--------------------+ +--------------------+

+--------------------+ +--------------------+ +--------------------+
|CORR PIPE DIAM | |CORR ORIFICE DIAM | |ISENTROPIC EXPONENT |
| | | | | |
|In Use Value: | |In Use Value: | |Value: |
| 300.264000 mm | | 200.256000 mm | | 1.30000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP TAP TYPE | |LF CUT OFF STATUS | |DOWNSTREAM PRESSURE |
| | | | | |
|Status: | |Status: | |In Use Value: |
|FLANGE | |SET | | 100.000000 barg |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|CALC TYPE |
| |
|Status: |
|1998 |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|ISO5167|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|MASS FLOWRATE | |MASS FLOWRATE | |PRESSURE LOSS |
| | | | | |
|Calculated Value: | |Limits (H/L) | |Calculated Value: |
| 0.000000 t/h | | | | 0.000000 mbar |
|In Use Value: | | 950.00 t/h | |In Use Value: |
| 0.000000 t/h | | -5.00 t/h | | 0.000000 mbar |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BETA | |REYNOLDS NUMBER | |EXPANSION FACTOR |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DISCHARGE COEFF | |FLOW COEFFICIENT | |VEL OF APPROACH FAC |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|PID PV COEFF |
| |
|Calculated Value: |
| 0.000000 |
|In Use Value: |
| 0.000000 |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|ISO6976|INPUTS
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 309 of 395 Issue 7
|CO2 | |H2O | |METHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |CV CALC TABLE | |COMPOSITION TYPE |
| | | | | |
|C6_PLUS | |Status: | |Status: |
| 0.00000000 % | |ISO6976 1995 | |VOL % |
| | | | | |
|CX_PLUS | | | | |
| 0.00000000 % | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|REFERENCE CONDITIONS|
| |
|Status: |
|15/15 DEG |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|ISO6976|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|STD COMPRESS (Zs) | |STD COMPRESS (Zs) | |IDEAL REL DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 0.997817 | | 1.000000 | | 0.580191 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 0.000000 | |COMPRESS | | 0.580191 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|IDEAL REL DENSITY | |IDEAL STD DENSITY | |IDEAL STD DENSITY |
| | | | | |
|Keypad Value: | |Calculated Value: | |Keypad Value: |
| 0.500000 | | 0.710673 kg/m3 | | 0.750000 kg/m3 |
|Mode Status: | |In Use Value: | |Mode Status: |
|CV | | 0.710673 kg/m3 | |CALCULATED |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|IDEAL CALORIFIC VAL | |IDEAL CALORIFIC VAL | |REAL REL DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 38.515472 MJ/Sm3 | | 40.000000 MJ/Sm3 | | 0.581216 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 38.515472 MJ/Sm3 | |CALCULATED | | 0.581216 |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 310 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+


+--------------------+ +--------------------+ +--------------------+
|REAL REL DENSITY | |REAL REL DENSITY | |REAL STD DENSITY |
| | | | | |
|Keypad Value: | |Limits (H/L) | |Calculated Value: |
| 0.500000 | | | | 0.712228 kg/m3 |
| | | 1.50 | |In Use Value: |
| | | 0.40 | | 0.712228 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|REAL STD DENSITY | |REAL STD DENSITY | |REAL CALORIFIC VALUE|
| | | | | |
|Keypad Value: | |Limits (H/L) | |Calculated Value: |
| 10.000000 kg/m3 | | | | 38.599754 MJ/Sm3 |
|Mode Status: | | 100.00 kg/m3 | |In Use Value: |
| | | 0.20 kg/m3 | | 38.599754 MJ/Sm3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|REAL CALORIFIC VALUE| |REAL CALORIFIC VALUE|
| | | |
|Keypad Value: | |Limits (H/L) |
| 40.000000 MJ/Sm3 | | |
| | | 0.00 MJ/Sm3 |
| | | 0.00 MJ/Sm3 |
| | | |
+--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|MASS CV|INPUTS
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|INUSE COMPOSITION |
| |
|C6_PLUS |
| 0.00000000 % |
| |
|CX_PLUS |
| 0.00000000 % |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 311 of 395 Issue 7
+--------------------+


MENU: CALCULATIONS|STREAM 1|MASS CV|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|IDEAL CV (MASS) | |IDEAL CV (MASS) | |IDEAL CV (MASS) |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 MJ/kg | | 50.100000 MJ/kg | | |
|In Use Value: | |Mode Status: | | 52.51 MJ/kg |
| 0.000000 MJ/kg | |CALCULATED | | 48.10 MJ/kg |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 2|DOWN/UP CORR|INPUTS
+--------------------+ +--------------------+ +--------------------+
|METER TEMP | |METER TEMP | |DP Stack 2 |
| | | | |STR02 DP STACK |
|In Use Value: | |Keypad Value: | |In Use DP Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 0.000 mbar |
| | |Mode Status: | |NO CELL SELECTED |
| | |KEYPAD-F | |mode Status: |
| | | | |KEYPAD-F |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 2 | |DP Stack 2 | |DP Stack 2 |
|STR02 DP STACK | |STR02 DP STACK | |STR02 DP STACK |
| | |Limits (H/L) | | |
|Keypad Value: | | | |Switch up point: |
| 0.000 mbar | | 95.00 mbar | | 95.000 % |
|Measured Value: | | 5.00 mbar | |Switch down point: |
| 0.000 mbar | | | | 90.000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 2 | |DP Stack 2 | |DP Stack 2 |
|STR02 DP STACK | |STR02 DP STACK | |STR02 DP STACK |
| | | | | |
|Discrepancy: | |Check DP Value: | |Low DP Cut Off: |
| 10.000 % | | 20.000 mbar | | 10.000 mbar |
|Discrepancy timout: | |Live/Check: | | |
| 5.000 s | |LIVE | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 2 | |METER PRESSURE | |METER PRESSURE |
|STR02 DP STACK | | | | |
| | |In Use Value: | |Keypad Value: |
|DP Cell type: | | 100.00 barg | | 100.00 barg |
|SINGLE | | | |Mode Status: |
|Cut off mode: | | | |KEYPAD-F |
|NORMAL | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PRESSURE LOSS | |TEMP EXP CONSTANT | |DENS EXP CONSTANT |
| | | | | |
|In Use Value: | |Value: | |Value: |
| 0.000000 mbar | | -0.23076900 | | 0.76923100 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|TEMP MEAS POINT | |PRESS MEAS POINT | |CORRECTION TYPE |
| | | | | |
|Status: | |Status: | |Status: |
|DOWNSTREAM | |UPSTREAM | |EXTENDED |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
MENU: CALCULATIONS|STREAM 2|DOWN/UP CORR|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|DOWNSTREAM PRESSURE | |RECOVERED PRESSURE | |UPSTREAM TEMP |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
|In Use Value: | |In Use Value: | |In Use Value: |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 312 of 395 Issue 7
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |UPSTREAM DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
| 0.000000 kg/m3 | |COMPRESS | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 2|PIPE CORRECTION|INPUTS
+--------------------+ +--------------------+ +--------------------+
|CALIB PIPE DIAM | |CALIB ORIFICE DIAM | |PIPE CALIB TEMP |
| | | | | |
|Value: | |Value: | |Value: |
| 300.00000000 mm | | 200.00000000 mm | | 20.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|ORIFICE CALIB TEMP | |PIPE EXP CONSTANT | |ORIFICE EXP CONSTANT|
| | | | | |
|Value: | |Value: | |Value: |
| 20.00000000 Deg.C | | 0.00001100 | | 0.00001600 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM TEMP | |PIPE MATERIAL | |ORIFICE MATERIAL |
| | | | | |
|In Use Value: | |Status: | |Status: |
| 100.000000 Deg.C | |USER | |USER |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 2|PIPE CORRECTION|OUTPUTS
+--------------------+ +--------------------+
|CORRECTED PIPE DIAM | |CORRECTED ORIF DIAM |
| | | |
|Calculated Value: | |Calculated Value: |
| 300.264000 mm | | 200.256000 mm |
|In Use Value: | |In Use Value: |
| 300.264000 mm | | 200.256000 mm |
| | | |
+--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 2|AGA 8|INPUTS
+--------------------+ +--------------------+ +--------------------+
|AGA8 METHOD | |UPSTREAM PRESS | |UPSTREAM TEMP |
| | | | | |
|Status: | |In Use Value: | |In Use Value: |
|DETAIL | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STANDARD PRESS | |STANDARD TEMP | |INUSE COMPOSITION |
| | | | | |
|Value: | |Value: | |NITROGEN |
| 0.00000000 barg | | 15.00000000 Deg.C | | 0.00000000 % |
| | | | | |
| | | | |CO2 |
| | | | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 313 of 395 Issue 7



+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|H2S | |HELIUM | |ETHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|H2O | |METHANE | |PROPANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|N_BUTANE | |N_PENTANE | |NEO_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|I_BUTANE | |I_PENTANE | |HEXANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|HEPTANE | |NONANE | |OXYGEN |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|OCTANE | |DECANE | |CO |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|HYDROGEN | |TOLUENE | |C6_PLUS |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|BENZENE | |ARGON | |CX_PLUS |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 2|AGA 8|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |UPSTREAM DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
| 0.000000 kg/m3 | |COMPRESS | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Zf | |Zb | |MOLECULAR WEIGHT |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STANDARD DENSITY | |STANDARD DENSITY | |STANDARD DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 10.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
| 0.712228 kg/m3 | |CV | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|Zs | |Zs |
| | | |
|Calculated Value: | |Keypad Value: |
| 0.000000 | | 1.000000 |
|In Use Value: | |Mode Status: |
| 0.000000 | |COMPRESS |
| | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 314 of 395 Issue 7
+--------------------+ +--------------------+


MENU: CALCULATIONS|STREAM 2|ISO5167|INPUTS
+--------------------+ +--------------------+ +--------------------+
|DP Stack 2 | |DP Stack 2 | |DP Stack 2 |
|STR02 DP STACK | |STR02 DP STACK | |STR02 DP STACK |
|In Use DP Value: | | | |Limits (H/L) |
| 0.000 mbar | |Keypad Value: | | |
|NO CELL SELECTED | | 0.000 mbar | | 95.00 mbar |
|mode Status: | |Measured Value: | | 5.00 mbar |
|KEYPAD-F | | 0.000 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 2 | |DP Stack 2 | |DP Stack 2 |
|STR02 DP STACK | |STR02 DP STACK | |STR02 DP STACK |
| | | | | |
|Switch up point: | |Discrepancy: | |Check DP Value: |
| 95.000 % | | 10.000 % | | 20.000 mbar |
|Switch down point: | |Discrepancy timout: | |Live/Check: |
| 90.000 % | | 5.000 s | |LIVE |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 2 | |DP Stack 2 | |UPSTREAM PRESSURE |
|STR02 DP STACK | |STR02 DP STACK | | |
| | | | |In Use Value: |
|Low DP Cut Off: | |DP Cell type: | | 100.000000 barg |
| 10.000 mbar | |SINGLE | | |
| | |Cut off mode: | | |
| | |NORMAL | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |VISCOSITY |
| | | | | |
|In Use Value: | |Keypad Value: | |Value: |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | 0.01710000 cP |
| | |Mode Status: | | |
| | |COMPRESS | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CORR PIPE DIAM | |CORR ORIFICE DIAM | |ISENTROPIC EXPONENT |
| | | | | |
|In Use Value: | |In Use Value: | |Value: |
| 300.264000 mm | | 200.256000 mm | | 1.30000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP TAP TYPE | |LF CUT OFF STATUS | |DOWNSTREAM PRESSURE |
| | | | | |
|Status: | |Status: | |In Use Value: |
|FLANGE | |SET | | 100.000000 barg |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|CALC TYPE |
| |
|Status: |
|1998 |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 2|ISO5167|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|MASS FLOWRATE | |MASS FLOWRATE | |PRESSURE LOSS |
| | | | | |
|Calculated Value: | |Limits (H/L) | |Calculated Value: |
| 0.000000 t/h | | | | 0.000000 mbar |
|In Use Value: | | 950.00 t/h | |In Use Value: |
| 0.000000 t/h | | -5.00 t/h | | 0.000000 mbar |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 315 of 395 Issue 7
| | | | | |
+--------------------+ +--------------------+ +--------------------+

+--------------------+ +--------------------+ +--------------------+
|BETA | |REYNOLDS NUMBER | |EXPANSION FACTOR |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DISCHARGE COEFF | |FLOW COEFFICIENT | |VEL OF APPROACH FAC |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|PID PV COEFF |
| |
|Calculated Value: |
| 0.000000 |
|In Use Value: |
| 0.000000 |

| |
+--------------------+

MENU: CALCULATIONS|STREAM 2|ISO6976|INPUTS
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |CV CALC TABLE | |COMPOSITION TYPE |

| | | | | |
|C6_PLUS | |Status: | |Status: |
| 0.00000000 % | |ISO6976 1995 | |VOL % |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 316 of 395 Issue 7
|CX_PLUS | | | | |
| 0.00000000 % | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|REFERENCE CONDITIONS|
| |
|Status: |
|15/15 DEG |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 2|ISO6976|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|STD COMPRESS (Zs) | |STD COMPRESS (Zs) | |IDEAL REL DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 0.997817 | | 1.000000 | | 0.580191 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 0.000000 | |COMPRESS | | 0.580191 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|IDEAL REL DENSITY | |IDEAL STD DENSITY | |IDEAL STD DENSITY |
| | | | | |
|Keypad Value: | |Calculated Value: | |Keypad Value: |
| 0.500000 | | 0.710673 kg/m3 | | 0.750000 kg/m3 |
|Mode Status: | |In Use Value: | |Mode Status: |
|CV | | 0.710673 kg/m3 | |CALCULATED |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|IDEAL CALORIFIC VAL | |IDEAL CALORIFIC VAL | |REAL REL DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 38.515472 MJ/Sm3 | | 40.000000 MJ/Sm3 | | 0.581216 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 38.515472 MJ/Sm3 | |CALCULATED | | 0.581216 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|REAL REL DENSITY | |REAL REL DENSITY | |REAL STD DENSITY |
| | | | | |
|Keypad Value: | |Limits (H/L) | |Calculated Value: |
| 0.500000 | | | | 0.712228 kg/m3 |
| | | 1.50 | |In Use Value: |
| | | 0.40 | | 0.712228 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|REAL STD DENSITY | |REAL STD DENSITY | |REAL CALORIFIC VALUE|
| | | | | |
|Keypad Value: | |Limits (H/L) | |Calculated Value: |
| 10.000000 kg/m3 | | | | 38.599754 MJ/Sm3 |
| | | 100.00 kg/m3 | |In Use Value: |
| | | 0.20 kg/m3 | | 38.599754 MJ/Sm3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|REAL CALORIFIC VALUE| |REAL CALORIFIC VALUE|
| | | |
|Keypad Value: | |Limits (H/L) |
| 40.000000 MJ/Sm3 | | |
| | | 0.00 MJ/Sm3 |
| | | 0.00 MJ/Sm3 |
| | | |
+--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 2|MASS CV|INPUTS
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 317 of 395 Issue 7
|CO2 | |H2O | |METHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|INUSE COMPOSITION |
| |
|C6_PLUS |
| 0.00000000 % |
| |
|CX_PLUS |
| 0.00000000 % |
+--------------------+

MENU: CALCULATIONS|STREAM 2|MASS CV|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|IDEAL CV (MASS) | |IDEAL CV (MASS) | |IDEAL CV (MASS) |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 MJ/kg | | 50.200000 MJ/kg | | |
|In Use Value: | |Mode Status: | | 52.52 MJ/kg |
| 0.000000 MJ/kg | |CALCULATED | | 48.20 MJ/kg |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 3|DOWN/UP CORR|INPUTS
+--------------------+ +--------------------+ +--------------------+
|METER TEMP | |METER TEMP | |DP Stack 3 |
| | | | |STR03 DP STACK |
|In Use Value: | |Keypad Value: | |In Use DP Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 0.000 mbar |
| | |Mode Status: | |NO CELL SELECTED |
| | |KEYPAD-F | |mode Status: |
| | | | |KEYPAD-F |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 3 | |DP Stack 3 | |DP Stack 3 |
|STR03 DP STACK | |STR03 DP STACK | |STR03 DP STACK |
| | |Limits (H/L) | | |
|Keypad Value: | | | |Switch up point: |
| 0.000 mbar | | 95.00 mbar | | 95.000 % |
|Measured Value: | | 5.00 mbar | |Switch down point: |
| 0.000 mbar | | | | 90.000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 3 | |DP Stack 3 | |DP Stack 3 |
|STR03 DP STACK | |STR03 DP STACK | |STR03 DP STACK |
| | | | | |
|Discrepancy: | |Check DP Value: | |Low DP Cut Off: |
| 10.000 % | | 20.000 mbar | | 10.000 mbar |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 318 of 395 Issue 7
|Discrepancy timout: | |Live/Check: | | |
| 5.000 s | |LIVE | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 3 | |METER PRESSURE | |METER PRESSURE |
|STR03 DP STACK | | | | |
| | |In Use Value: | |Keypad Value: |
|DP Cell type: | | 100.00 barg | | 100.00 barg |
|SINGLE | | | |Mode Status: |
|Cut off mode: | | | |KEYPAD-F |
|NORMAL | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PRESSURE LOSS | |TEMP EXP CONSTANT | |DENS EXP CONSTANT |
| | | | | |
|In Use Value: | |Value: | |Value: |
| 0.000000 mbar | | -0.23076900 | | 0.76923100 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|TEMP MEAS POINT | |PRESS MEAS POINT | |CORRECTION TYPE |
| | | | | |
|Status: | |Status: | |Status: |
|DOWNSTREAM | |UPSTREAM | |EXTENDED |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 3|DOWN/UP CORR|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|DOWNSTREAM PRESSURE | |RECOVERED PRESSURE | |UPSTREAM TEMP |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
|In Use Value: | |In Use Value: | |In Use Value: |
| 100.000000 barg | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |UPSTREAM DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
| 0.000000 kg/m3 | |COMPRESS | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 3|PIPE CORRECTION|INPUTS
+--------------------+ +--------------------+ +--------------------+
|CALIB PIPE DIAM | |CALIB ORIFICE DIAM | |PIPE CALIB TEMP |
| | | | | |
|Value: | |Value: | |Value: |
| 300.00000000 mm | | 200.00000000 mm | | 20.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|ORIFICE CALIB TEMP | |PIPE EXP CONSTANT | |ORIFICE EXP CONSTANT|
| | | | | |
|Value: | |Value: | |Value: |
| 20.00000000 Deg.C | | 0.00001100 | | 0.00001600 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM TEMP | |PIPE MATERIAL | |ORIFICE MATERIAL |
| | | | | |
|In Use Value: | |Status: | |Status: |
| 100.000000 Deg.C | |USER | |USER |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 319 of 395 Issue 7
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
MENU: CALCULATIONS|STREAM 3|PIPE CORRECTION|OUTPUTS
+--------------------+ +--------------------+
|CORRECTED PIPE DIAM | |CORRECTED ORIF DIAM |
| | | |
|Calculated Value: | |Calculated Value: |
| 300.264000 mm | | 200.256000 mm |
|In Use Value: | |In Use Value: |
| 300.264000 mm | | 200.256000 mm |
| | | |
+--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 3|AGA 8|INPUTS
+--------------------+ +--------------------+ +--------------------+
|AGA8 METHOD | |UPSTREAM PRESS | |UPSTREAM TEMP |
| | | | | |
|Status: | |In Use Value: | |In Use Value: |
|DETAIL | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STANDARD PRESS | |STANDARD TEMP | |INUSE COMPOSITION |
| | | | | |
|Value: | |Value: | |NITROGEN |
| 0.00000000 barg | | 15.00000000 Deg.C | | 0.00000000 % |
| | | | | |
| | | | |CO2 |
| | | | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|H2S | |HELIUM | |ETHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|H2O | |METHANE | |PROPANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|N_BUTANE | |N_PENTANE | |NEO_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|I_BUTANE | |I_PENTANE | |HEXANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|HEPTANE | |NONANE | |OXYGEN |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|OCTANE | |DECANE | |CO |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|HYDROGEN | |TOLUENE | |C6_PLUS |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|BENZENE | |ARGON | |CX_PLUS |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
MENU: CALCULATIONS|STREAM 3|AGA 8|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |UPSTREAM DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 320 of 395 Issue 7
| 0.000000 kg/m3 | |COMPRESS | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Zf | |Zb | |MOLECULAR WEIGHT |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STANDARD DENSITY | |STANDARD DENSITY | |STANDARD DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 10.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
| 0.712228 kg/m3 | |CV | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|Zs | |Zs |
| | | |
|Calculated Value: | |Keypad Value: |
| 0.000000 | | 1.000000 |
|In Use Value: | |Mode Status: |
| 0.000000 | |COMPRESS |
| | | |
+--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 3|ISO5167|INPUTS
+--------------------+ +--------------------+ +--------------------+
|DP Stack 3 | |DP Stack 3 | |DP Stack 3 |
|STR03 DP STACK | |STR03 DP STACK | |STR03 DP STACK |
|In Use DP Value: | | | |Limits (H/L) |
| 0.000 mbar | |Keypad Value: | | |
|NO CELL SELECTED | | 0.000 mbar | | 95.00 mbar |
|mode Status: | |Measured Value: | | 5.00 mbar |
|KEYPAD-F | | 0.000 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 3 | |DP Stack 3 | |DP Stack 3 |
|STR03 DP STACK | |STR03 DP STACK | |STR03 DP STACK |
| | | | | |
|Switch up point: | |Discrepancy: | |Check DP Value: |
| 95.000 % | | 10.000 % | | 20.000 mbar |
|Switch down point: | |Discrepancy timout: | |Live/Check: |
| 90.000 % | | 5.000 s | |LIVE |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 3 | |DP Stack 3 | |UPSTREAM PRESSURE |
|STR03 DP STACK | |STR03 DP STACK | | |
| | | | |In Use Value: |
|Low DP Cut Off: | |DP Cell type: | | 100.000000 barg |
| 10.000 mbar | |SINGLE | | |
| | |Cut off mode: | | |
| | |NORMAL | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |VISCOSITY |
| | | | | |
|In Use Value: | |Keypad Value: | |Value: |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | 0.01710000 cP |
| | |Mode Status: | | |
| | |COMPRESS | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CORR PIPE DIAM | |CORR ORIFICE DIAM | |ISENTROPIC EXPONENT |
| | | | | |
|In Use Value: | |In Use Value: | |Value: |
| 300.264000 mm | | 200.256000 mm | | 1.30000000 |
| | | | | |
| | | | | |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 321 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+


+--------------------+ +--------------------+ +--------------------+
|DP TAP TYPE | |LF CUT OFF STATUS | |DOWNSTREAM PRESSURE |
| | | | | |
|Status: | |Status: | |In Use Value: |
|FLANGE | |SET | | 100.000000 barg |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|CALC TYPE |
| |
|Status: |
|1998 |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 3|ISO5167|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|MASS FLOWRATE | |MASS FLOWRATE | |PRESSURE LOSS |
| | | | | |
|Calculated Value: | |Limits (H/L) | |Calculated Value: |
| 0.000000 t/h | | | | 0.000000 mbar |
|In Use Value: | | 950.00 t/h | |In Use Value: |
| 0.000000 t/h | | -5.00 t/h | | 0.000000 mbar |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BETA | |REYNOLDS NUMBER | |EXPANSION FACTOR |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DISCHARGE COEFF | |FLOW COEFFICIENT | |VEL OF APPROACH FAC |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|PID PV COEFF |
| |
|Calculated Value: |
| 0.000000 |
|In Use Value: |
| 0.000000 |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 3|ISO6976|INPUTS
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 322 of 395 Issue 7
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |CV CALC TABLE | |COMPOSITION TYPE |
| | | | | |
|C6_PLUS | |Status: | |Status: |
| 0.00000000 % | |ISO6976 1995 | |VOL % |
| | | | | |
|CX_PLUS | | | | |
| 0.00000000 % | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|REFERENCE CONDITIONS|
| |
|Status: |
|15/15 DEG |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 3|ISO6976|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|STD COMPRESS (Zs) | |STD COMPRESS (Zs) | |IDEAL REL DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 0.997817 | | 1.000000 | | 0.580191 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 0.000000 | |COMPRESS | | 0.580191 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|IDEAL REL DENSITY | |IDEAL STD DENSITY | |IDEAL STD DENSITY |
| | | | | |
|Keypad Value: | |Calculated Value: | |Keypad Value: |
| 0.500000 | | 0.710673 kg/m3 | | 0.750000 kg/m3 |
|Mode Status: | |In Use Value: | |Mode Status: |
|CV | | 0.710673 kg/m3 | |CALCULATED |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|IDEAL CALORIFIC VAL | |IDEAL CALORIFIC VAL | |REAL REL DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 38.515472 MJ/Sm3 | | 40.000000 MJ/Sm3 | | 0.581216 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 38.515472 MJ/Sm3 | |CALCULATED | | 0.581216 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|REAL REL DENSITY | |REAL REL DENSITY | |REAL STD DENSITY |
| | | | | |
|Keypad Value: | |Limits (H/L) | |Calculated Value: |
| 0.500000 | | | | 0.712228 kg/m3 |
| | | 1.50 | |In Use Value: |
| | | 0.40 | | 0.712228 kg/m3 |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 323 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+


+--------------------+ +--------------------+ +--------------------+
|REAL STD DENSITY | |REAL STD DENSITY | |REAL CALORIFIC VALUE|
| | | | | |
|Keypad Value: | |Limits (H/L) | |Calculated Value: |
| 10.000000 kg/m3 | | | | 38.599754 MJ/Sm3 |
| | | 100.00 kg/m3 | |In Use Value: |
| | | 0.20 kg/m3 | | 38.599754 MJ/Sm3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|REAL CALORIFIC VALUE| |REAL CALORIFIC VALUE|
| | | |
|Keypad Value: | |Limits (H/L) |
| 40.000000 MJ/Sm3 | | |
| | | 0.00 MJ/Sm3 |
| | | 0.00 MJ/Sm3 |
| | | |
+--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 3|MASS CV|INPUTS
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|INUSE COMPOSITION |
| |
|C6_PLUS |
| 0.00000000 % |
| |
|CX_PLUS |
| 0.00000000 % |
+--------------------+

MENU: CALCULATIONS|STREAM 3|MASS CV|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|IDEAL CV (MASS) | |IDEAL CV (MASS) | |IDEAL CV (MASS) |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 MJ/kg | | 50.300000 MJ/kg | | |
|In Use Value: | |Mode Status: | | 52.53 MJ/kg |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 324 of 395 Issue 7
| 0.000000 MJ/kg | |CALCULATED | | 48.30 MJ/kg |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 325 of 395 Issue 7

20.3 Buy Back Gas

MENU: FLOW RATES|STREAM 1|STR01 UVOL FR
+--------------------+
|STR01 UVOL FR |
| 0.000 m3/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: FLOW RATES|STREAM 1|STR01 CVOL FR
+--------------------+
|STR01 CVOL FR |
| 0.000 Skm3/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: FLOW RATES|STREAM 1|STR01 MASS FR
+--------------------+
|STR01 MASS FR |
| 0.000 t/h |
|Limits (H/L) |
| |
| 950.00 t/h |
| -5.00 t/h |
| |
+--------------------+

MENU: FLOW RATES|STREAM 1|STR01 ENERGY FR
+--------------------+
|STR01 ENERGY FR |
| 0.000 GJ/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: TOTALS|STREAM 1|STR01 UVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 UVOL | |STR01 UVOL MAINT | |STR01 UVOL DAILY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
| | |Previous Period: | |Previous Period: |
| | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|BASETIME 1 |
|STR01 UVOL 2 HOURLY |
| |
|Current Period: |
| 0.000 m3 |
|Previous Period: |
| 0.000 m3 |
+--------------------+

MENU: TOTALS|STREAM 1|STR01 CVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 CVOL | |STR01 CVOL MAINT | |STR01 CVOL DAILY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 Skm3 | | 0.000 Skm3 | | 0.000 Skm3 |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 326 of 395 Issue 7
| | |Previous Period: | |Previous Period: |
| | | 0.000 Skm3 | | 0.000 Skm3 |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 327 of 395 Issue 7

+--------------------+
|BASETIME 1 |
|STR01 CVOL 2 HOURLY |
| |
|Current Period: |
| 0.000 Skm3 |
|Previous Period: |
| 0.000 Skm3 |
+--------------------+

MENU: TOTALS|STREAM 1|STR01 MASS
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 MASS | |STR01 MASS MAINT | |STR01 MASS DAILY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
| | |Previous Period: | |Previous Period: |
| | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|BASETIME 1 |
|STR01 MASS 2 HOURLY |
| |
|Current Period: |
| 0.000 tonne |
|Previous Period: |
| 0.000 tonne |
+--------------------+

MENU: TOTALS|STREAM 1|STR01 ENERGY
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 ENERGY | |STR01 ENERGY MAINT | |STR01 ENERGY DAILY |
| | | | | |
| | |Current Period: | |Current Period: |
| 0.000 GJ | | 0.000 GJ | | 0.000 GJ |
| | |Previous Period: | |Previous Period: |
| | | 0.000 GJ | | 0.000 GJ |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|BASETIME 1 |
|STR01 ENERGY 2 HOURL|
| |
|Current Period: |
| 0.000 GJ |
|Previous Period: |
| 0.000 GJ |
+--------------------+

MENU: OPERATOR|STREAM 1|COMPOSITION|SPV/KEYPAD MOLES
+--------------------+ +--------------------+ +--------------------+
|USE SPV/STR DATA | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|Status: | |NITROGEN | |H2S |
|SPV | | 0.0000 % | | 0.0000 % |
| | | | | |
| | |CO2 | |H2O |
| | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|HELIUM | |ETHANE | |N_BUTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|METHANE | |PROPANE | |I_BUTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 328 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|N_PENTANE | |NEO_PENTANE | |HEPTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|I_PENTANE | |HEXANE | |OCTANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|NONANE | |OXYGEN | |HYDROGEN |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|DECANE | |CO | |BENZENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES | |SPV/KEYPAD MOLES |
| | | | | |
|TOLUENE | |C6_PLUS | |TOTAL |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|ARGON | |CX_PLUS | | |
| 0.0000 % | | 0.0000 % | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|COMPOSITION|SELECTED MOLES
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.2595 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.5956 % | | 0.0000 % | | 96.5222 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 1.8186 % | | 0.1007 % | | 0.2438 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.4596 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES | |SELECTED MOLES |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.0000 % | | 0.0000 % | | 0.0000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|SELECTED MOLES | |SELECTED MOLES |
| | | |
|C6_PLUS | |TOTAL |
| 0.0000 % | | 100.0000 % |
| | | |
|CX_PLUS | | |
| 0.0000 % | | |
+--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 329 of 395 Issue 7

MENU: OPERATOR|STREAM 1|COMPOSITION|COMMAND
+--------------------+ +--------------------+
|MOLE SELECT | |ACCEPTANCE COMMAND |
| | | |
|Status: | |Status: |
|KEYPAD | |IDLE |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|STREAM SETUP
+--------------------+ +--------------------+ +--------------------+
|STR01 STREAM TYPE | |STR01 NAME | |STR01 METER LOCATION|
| | | | | |
|Status: | |Value: | |Value: |
|GAS DP | |GAS DP | |LINE 1 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 STD TEMP | |STR01 STD PRESS | |STR01 LF CUT OFF |
| | | | | |
|Value: | |Value: | |Value: |
| 20.00000000 Deg.C | | 0.00000000 barg | | 5.00000000 t/h |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|STR01 FLOW DIRECTION|
| |
|Status: |
|FORWARD |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|STREAM STATUS
+--------------------+ +--------------------+ +--------------------+
|STR01 STATUS | |STR01 DISABLE | |STR01 LOW FLOW STAT |
| | | | | |
|Status: | |Status: | |Status: |
|OFF-LINE | |CLEAR | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|METER SETUP
+--------------------+ +--------------------+ +--------------------+
|STR01 TEMP EXP COEFF| |STR01 DENS EXP COEFF| |STR01 CALIB PIPE DIA|
| | | | | |
|Value: | |Value: | |Value: |
| -0.23076900 | | 0.76923100 | | 300.00000000 mm |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 PIPE MATERIAL | |STR01 PIPE TEMP EXP | |STR01 PIPE CALIB TEM|
| | | | | |
|Status: | |Value: | |Value: |
|STAINLESS | | 0.00000925 | | 20.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 330 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|STR01 CALIB ORIF DIA| |STR01 ORIF MATERIAL | |STR01 ORIF EXP CONST|
| | | | | |
|Value: | |Status: | |Value: |
| 200.00000000 mm | |STAINLESS | | 0.00000925 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 ORIF CALIB TEM| |STR01 ISENTROPIC EXP| |STR01 VISCOSITY |
| | | | | |
|Value: | |Value: | |Value: |
| 15.00000000 Deg.C | | 1.30000000 | | 0.01710000 cP |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|DENS OF AIR | |STR01 DOWN/UP CORREC|
| | | |
|Value: | |Status: |
| 1.22550000 kg/m3 | |EXTENDED |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+
MENU: OPERATOR|STREAM 1|METERING IO
+--------------------+ +--------------------+ +--------------------+
|STR01 METER TEMP | |STR01 METER TEMP | |STR01 METER PRESSURE|
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 100.00 barg |
| | |Mode Status: | | |
| | |KEYPAD | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 METER PRESSURE| |DP Stack 1 | |DP Stack 1 |
| | |STR01 DP STACK | |STR01 DP STACK |
|Keypad Value: | |In Use DP Value: | | |
| 100.00 barg | | 300.000 mbar | |Keypad Value: |
|Mode Status: | |NO CELL SELECTED | | 300.000 mbar |
|KEYPAD-F | |mode Status: | |Measured Value: |
| | |KEYPAD-F | | 0.000 mbar |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
|Limits (H/L) | | | | |
| | |Switch up point: | |Discrepancy: |
| 600.00 mbar | | 95.000 % | | 10.000 % |
| 5.00 mbar | |Switch down point: | |Discrepancy timout: |
| | | 90.000 % | | 5.000 s |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
| | | | | |
|Check DP Value: | |Low DP Cut Off: | |DP Cell type: |
| 20.000 mbar | | 10.000 mbar | |LO-HI |
|Live/Check: | | | |Cut off mode: |
|LIVE | | | |NORMAL |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|CALCULATED DATA
+--------------------+ +--------------------+ +--------------------+
|STR01 DOWNSTR PRESS | |STR01 RECOVERED PRES| |STR01 UPSTREAM TEMP |
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 99.700000 barg | | 100.000000 barg | | 100.000000 Deg.C |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|CALCULATED | |CALCULATED | |CALCULATED |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 331 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|STR01 PRESS LOSS | |STR01 CORR PIPE DIAM| |STR01 CORR ORIF DIAM|
| | | | | |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 mbar | | 300.222000 mm | | 200.157250 mm |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|CALCULATED | |CALCULATED | |CALCULATED |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 UPSTR COMPRESS| |STR01 UPSTR COMPRESS| |STR01 STD COMPRESS |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 0.944196 | | 1.000000 | | 0.997860 |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|COMPRESS | |COMPRESS | |COMPRESS |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 STD COMPRESS | |STR01 UPSTREAM DENS | |STR01 UPSTREAM DENS |
| | | | | |
|Keypad Value: | |In Use Value: | |Keypad Value: |
| 1.000000 | | 0.000000 kg/m3 | | 50.000000 kg/m3 |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|COMPRESS | |MEASURED | |MEASURED |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 UPSTREAM DENS | |STR01 STANDARD DENS | |STR01 STANDARD DENS |
| | | | | |
|Limits (H/L) | |In Use Value: | |Keypad Value: |
| | | 0.699967 kg/m3 | | 10.000000 kg/m3 |
| 100.00 kg/m3 | | | | |
| 0.20 kg/m3 | |Mode Status: | |Mode Status: |
| | |COMPRESS | |COMPRESS |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 STANDARD DENS | |STR01 REAL RDENS | |STR01 REAL RDENS |
| | | | | |
|Limits (H/L) | |In Use Value: | |Keypad Value: |
| | | 0.581216 | | 0.500000 |
| 100.00 kg/m3 | | | | |
| 0.20 kg/m3 | |Mode Status: | |Mode Status: |
| | |CV | |CV |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 REAL RDENS | |STR01 REAL CV | |STR01 REAL CV |
| | | | | |
|Limits (H/L) | |In Use Value: | |Keypad Value: |
| | | 38.599754 MJ/Sm3 | | 40.000000 MJ/Sm3 |
| 1.50 | | | | |
| 0.40 | |Mode Status: | |Mode Status: |
| | |CV | |CV |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 REAL CV | |STR01 BETA | |STR01 REYNOLDS NO |
| | | | | |
|Limits (H/L) | |In Use Value: | |In Use Value: |
| | | 0.000000 | | 0.000000 |
| 0.00 MJ/Sm3 | | | | |
| 0.00 MJ/Sm3 | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVG DATA|STR01 PRESS
+--------------------+ +--------------------+ +--------------------+
|STR01 FWA PRESS | |STR01 FWA PRESS | |STR01 FWA PRESS |
| | | | | |
|HOURLY | |MAINT | |BASETIME 1 PRD 2 |
| 0.00000000 barg | | 0.00000000 barg | | 0.00000000 barg |
| | | | | |
|BATCH | |BASETIME 1 PRD 1 | |BASETIME 1 PRD 3 |
| 0.00000000 barg | | 0.00000000 barg | | 0.00000000 barg |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 332 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|STR01 FWA PRESS | |STR01 FWA PRESS | |STR01 FWA PRESS |
| | | | | |
|BASETIME 1 PRD 4 | |BASETIME 2 PRD 2 | |BASETIME 2 PRD 4 |
| 0.00000000 barg | | 0.00000000 barg | | 0.00000000 barg |
| | | | | |
|BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 | |BASETIME 3 PRD 1 |
| 0.00000000 barg | | 0.00000000 barg | | 0.00000000 barg |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|STR01 FWA PRESS | |STR01 FWA PRESS |
| | | |
|BASETIME 3 PRD 2 | |BASETIME 3 PRD 4 |
| 0.00000000 barg | | 0.00000000 barg |
| | | |
|BASETIME 3 PRD 3 | | |
| 0.00000000 barg | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVG DATA|STR01 TEMP
+--------------------+ +--------------------+ +--------------------+
|STR01 FWA TEMP | |STR01 FWA TEMP | |STR01 FWA TEMP |
| | | | | |
|HOURLY | |MAINT | |BASETIME 1 PRD 2 |
| 0.00000000 Deg.C | | 0.00000000 Deg.C | | 0.00000000 Deg.C |
| | | | | |
|BATCH | |BASETIME 1 PRD 1 | |BASETIME 1 PRD 3 |
| 0.00000000 Deg.C | | 0.00000000 Deg.C | | 0.00000000 Deg.C |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 FWA TEMP | |STR01 FWA TEMP | |STR01 FWA TEMP |
| | | | | |
|BASETIME 1 PRD 4 | |BASETIME 2 PRD 2 | |BASETIME 2 PRD 4 |
| 0.00000000 Deg.C | | 0.00000000 Deg.C | | 0.00000000 Deg.C |
| | | | | |
|BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 | |BASETIME 3 PRD 1 |
| 0.00000000 Deg.C | | 0.00000000 Deg.C | | 0.00000000 Deg.C |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|STR01 FWA TEMP | |STR01 FWA TEMP |
| | | |
|BASETIME 3 PRD 2 | |BASETIME 3 PRD 4 |
| 0.00000000 Deg.C | | 0.00000000 Deg.C |
| | | |
|BASETIME 3 PRD 3 | | |
| 0.00000000 Deg.C | | |
+--------------------+ +--------------------+
MENU: OPERATOR|STREAM 1|AVG DATA|STR01 STD DENS
+--------------------+ +--------------------+ +--------------------+
|STR01 FWA STD D | |STR01 FWA STD D | |STR01 FWA STD D |
| | | | | |
|HOURLY | |MAINT | |BASETIME 1 PRD 2 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | | | |
|BATCH | |BASETIME 1 PRD 1 | |BASETIME 1 PRD 3 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 FWA STD D | |STR01 FWA STD D | |STR01 FWA STD D |
| | | | | |
|BASETIME 1 PRD 4 | |BASETIME 2 PRD 2 | |BASETIME 2 PRD 4 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | | | |
|BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 | |BASETIME 3 PRD 1 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|STR01 FWA STD D | |STR01 FWA STD D |
| | | |
|BASETIME 3 PRD 2 | |BASETIME 3 PRD 4 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | |
|BASETIME 3 PRD 3 | | |
| 0.00000000 kg/m3 | | |
+--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 333 of 395 Issue 7

MENU: OPERATOR|STREAM 1|AVG DATA|STR01 FLOW
+--------------------+ +--------------------+ +--------------------+
|STR01 FWA FLOW | |STR01 FWA FLOW | |STR01 FWA FLOW |
| | | | | |
|HOURLY | |MAINT | |BASETIME 1 PRD 2 |
| 0.00000000 t/h | | 0.00000000 t/h | | 0.00000000 t/h |
| | | | | |
|BATCH | |BASETIME 1 PRD 1 | |BASETIME 1 PRD 3 |
| 0.00000000 t/h | | 0.00000000 t/h | | 0.00000000 t/h |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 FWA FLOW | |STR01 FWA FLOW | |STR01 FWA FLOW |
| | | | | |
|BASETIME 1 PRD 4 | |BASETIME 2 PRD 2 | |BASETIME 2 PRD 4 |
| 0.00000000 t/h | | 0.00000000 t/h | | 0.00000000 t/h |
| | | | | |
|BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 | |BASETIME 3 PRD 1 |
| 0.00000000 t/h | | 0.00000000 t/h | | 0.00000000 t/h |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|STR01 FWA FLOW | |STR01 FWA FLOW |
| | | |
|BASETIME 3 PRD 2 | |BASETIME 3 PRD 4 |
| 0.00000000 t/h | | 0.00000000 t/h |
| | | |
|BASETIME 3 PRD 3 | | |
| 0.00000000 t/h | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVG DATA|COMMAND
+--------------------+
|STR01 METHOD |
| |
|Status: |
|FWA |
| |
| |
| |
+--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 01 - ADC 01
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 1 | |ADC Channel 1 | |ADC Channel 1 |
|ADC 01 PRS | |ADC 01 PRS | |ADC 01 PRS |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 barg | | 100.000 barg | | 102.00 barg |
|Mode Status: | |Measured Value: | | -2.00 barg |
|KEYPAD-F | | -24.998 barg | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 1 | |ADC Channel 1 |
|ADC 01 PRS | |ADC 01 PRS |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 3.77285149E-04 mA | | 100.000 barg |
| | | 0.000 barg |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 02 - ADC 02
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 2 | |ADC Channel 2 | |ADC Channel 2 |
|ADC 02 DP LO | |ADC 02 DP LO | |ADC 02 DP LO |
| | | | | |
|In Use Value: | |Keypad Value: | |Current: |
| 100.000 mbar | | 100.000 mbar | | 6.51891984E-04 mA |
|Mode Status: | |Measured Value: | | |
|KEYPAD-F | | -24.996 mbar | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 334 of 395 Issue 7

+--------------------+
|ADC Channel 2 |
|ADC 02 DP LO |
|HIGH AND LOW SCALE |
| |
| 100.000 mbar |
| 0.000 mbar |
| |
+--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 03 - ADC 03
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 3 | |ADC Channel 3 | |ADC Channel 3 |
|ADC 03 DP HI | |ADC 03 DP HI | |ADC 03 DP HI |
| | | | | |
|In Use Value: | |Keypad Value: | |Current: |
| 100.000 mbar | | 100.000 mbar | | 4.90568811E-04 mA |
|Mode Status: | |Measured Value: | | |
|KEYPAD-F | | -24.997 mbar | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|ADC Channel 3 |
|ADC 03 DP HI |
|HIGH AND LOW SCALE |
| |
| 100.000 mbar |
| 0.000 mbar |
| |
+--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 04 - ADC04
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 4 | |ADC Channel 4 | |ADC Channel 4 |
|I/O01 ADC 04 | |I/O01 ADC 04 | |I/O01 ADC 04 |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 Deg.C | | 100.000 Deg.C | | 102.00 Deg.C |
|Mode Status: | |Measured Value: | | -2.00 Deg.C |
|KEYPAD | | -24.997 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 4 | |ADC Channel 4 |
|I/O01 ADC 04 | |I/O01 ADC 04 |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 4.22610901E-04 mA | | 100.000 Deg.C |
| | | 0.000 Deg.C |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|DIGITAL I/OS|DIGITAL IO 01
+--------------------+
|Discrete I/O 1 |
|I/O01 DIO 01 |
| |
|Input Status: |
|0000000000000000 |
|Output Status: |
|0000000000000000 |
+--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 01 - DAC01
+--------------------+ +--------------------+
|DAC Channel 1 | |DAC Channel 1 |
|I/O01 DAC 01 | |I/O01 DAC 01 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 335 of 395 Issue 7

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 02 - DAC02
+--------------------+ +--------------------+
|DAC Channel 2 | |DAC Channel 2 |
|I/O01 DAC 02 | |I/O01 DAC 02 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 03 - DAC03
+--------------------+ +--------------------+
|DAC Channel 3 | |DAC Channel 3 |
|I/O01 DAC 03 | |I/O01 DAC 03 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 04 - DAC04
+--------------------+ +--------------------+
|DAC Channel 4 | |DAC Channel 4 |
|I/O01 DAC 04 | |I/O01 DAC 04 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|PULSE OUTPUTS|POP 01 - POP01
+--------------------+
|Pulse Output 1 |
|I/O01 POP 01 |
| |
|Pulse Freq (Hz) |
| 5.000 Hz |
|Grab Size (incs/pls)|
| 10.000 |
+--------------------+

MENU: PLANT I/O|PULSE OUTPUTS|POP 02 - POP02
+--------------------+
|Pulse Output 2 |
|I/O01 POP 02 |
| |
|Pulse Freq (Hz) |
| 5.000 Hz |
|Grab Size (incs/pls)|
| 10.000 |
+--------------------+

MENU: PLANT I/O|PULSE OUTPUTS|POP 03 - POP03
+--------------------+
|Pulse Output 3 |
|I/O01 POP 03 |
| |
|Pulse Freq (Hz) |
| 5.000 Hz |
|Grab Size (incs/pls)|
| 10.000 |
+--------------------+
MENU: PLANT I/O|PULSE OUTPUTS|POP 04 - POP04
+--------------------+
|Pulse Output 4 |
|I/O01 POP 04 |
| |
|Pulse Freq (Hz) |
| 5.000 Hz |
|Grab Size (incs/pls)|
| 10.000 |
+--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 336 of 395 Issue 7
MENU: PLANT I/O|PULSE OUTPUTS|POP 05 - POP05
+--------------------+
|Pulse Output 5 |
|I/O01 POP 05 |
| |
|Pulse Freq (Hz) |
| 5.000 Hz |
|Grab Size (incs/pls)|
| 10.000 |
+--------------------+

MENU: SYSTEM SETTINGS|UNIT SETUP|CONVERSIONS
+--------------------+ +--------------------+ +--------------------+
|Conversion Factor | |Conversion Factor | |Conversion Factor |
|lb - kg | |tonne - US ton | |Bar. press (Bar) |
| | | | | |
|Value: | |Value: | |Value: |
| 0.45359240 | | 1.10231136 | | 1.01325000 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Conversion Factor | |Conversion Factor | |Conversion Factor |
|Bar. press (psi) | |bar - kPa | |bar - psi |
| | | | | |
|Value: | |Value: | |Value: |
| 14.73000000 | | 100.00000000 | | 14.50377439 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Conversion Factor | |Conversion Factor | |Conversion Factor |
|bar - in H2O (@60F) | |Deg.C - K | |m3 - bbl |
| | | | | |
|Value: | |Value: | |Value: |
| 401.86465200 | | 273.15000000 | | 6.28981057 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Conversion Factor | |Conversion Factor | |Conversion Factor |
|m3 - cf | |Btu - J | |cst - mm2s |
| | | | | |
|Value: | |Value: | |Value: |
| 35.31466247 | | 1055.05600000 | | 1.00000000 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
MENU: SYSTEM SETTINGS|UNIT SETUP|SETUP
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|LIQ MASS UNITS | |LIQ MASS FR UNITS | |LIQ GROSS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|tonne | |t/h | |m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|LIQ GROSS FR UNITS | |LIQ NETT UNITS | |LIQ NETT FR UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|m3/h | |Sm3 | |Sm3/h |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS MASS UNITS | |GAS MASS FR UNITS | |GAS GROSS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|tonne | |t/h | |m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 337 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS GROSS FR UNITS | |GAS NETT UNITS | |GAS NETT FR UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|m3/h | |Skm3 | |Skm3/h |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS ENGY UNITS | |GAS ENGY FR UNITS | |PRESS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|GJ | |GJ/h | |barg |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DP UNITS | |TEMP UNITS | |DENS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mbar | |Deg.C | |kg/m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|K-FACTOR UNITS | |CV MASS UNITS | |CV VOL UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|pls/m3 | |MJ/kg | |MJ/Sm3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DYN VISC UNITS | |KIN VISC UNITS | |FREQ UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|cP | |cSt | |Hz |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|LENGTH UNITS | |PERIOD UNITS | |PERCENT UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mm | |uS | |% |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DIAM UNITS | |AREA UNITS | |VEL UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mm | |mm2 | |m/s |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|TIME UNITS | |ROC TEMP UNITS | |ROC PRS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|s | |Deg.C/s | |bar/s |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 338 of 395 Issue 7

MENU: SYSTEM SETTINGS|REPORT SETUP
+--------------------+ +--------------------+ +--------------------+
|REPORT CONTROL | |REPORT CONTROL | |BASETIME 1 |
|WEEK START | |MONTH START | | |
| | | | | |
|SUNDAY | |FIRST | | 6 |
| | | | | |
| | | | |O-CLOCK |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|BASETIME 2 | |BASETIME 3 |
| | | |
| | | |
| 12 | | 18 |
| | | |
|O-CLOCK | |O-CLOCK |
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|ALARM SETUP
+--------------------+ +--------------------+
|ALARM CONTROL | |ALARM CONTROL |
|ALARM MODE | |ALARM ENABLE |
| | | |
|LATCHED | |YES |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|MAINTENANCE MODE
+--------------------+ +--------------------+
| | | |
|SYSTEM MAINT ENAB | |STR01 MAINT MODE |
| | | |
|SET | |CLEAR |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|SYSTEM STATUS
+--------------------+
| |
|SYSTEM RUN MODE |
| |
|NORMAL |
| |
| |
| |
+--------------------+

MENU: SYSTEM SETTINGS|SOFTWARE VERSION
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|CONFIG NAME | |CONFIG FORMAT | |CONFIG VERSION |
| | | | | |
|Helang - Buy Back Ga| |5 | |60 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|CONFIG CREATED | |CONFIG LAST EDITED | |CONFIG STRUCTURE |
| | | | | |
|09 Nov 2001. 08:38 | |15 Jun 2002. 01:01 | |CSUM 4a0d |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 339 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|NMI CONSTANTS | |FILE CSUM | |REGISTRATION CODE |
| | | | | |
|AAAA-1111 | |AAAA | |1.3dMAKAWGG20011024P|
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|APPLICATION SW | |PC SETUP PACKAGE | |MAIN BOARD ID |
| | | | | |
|03.20 May 14 2002 | |1.3 | |00:A0:D8:FE:0E:6B |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 HW_REV | |I/O01 MOD_STRIKE | |I/O01 BOARD SERNO |
| | | | | |
|REV 04 | |MOD D | |SN 07354 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 FIRST CALIB | |I/O01 LAST CALIB | |I/O01 SW VERSION |
| | | | | |
|10082001 | |10082001 | |01.01.16.00 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|VERSION CONTROL |
|I/O01 BOARD ID |
| |
|1.1.1.1.1.2.0 |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|DISPLAY SETUP
+--------------------+
|Display Setup |
| |
|DEF DISP : |
| |
|DISPLAY T/O: 300 s |
|LOGOUT T/O: 20 s |
|IDENT T/O: 120 s |
+--------------------+

MENU: TECH/ENGINEER|CONTRAST
+--------------------+
| |
| |
|CONTRAST : 8 |
| |
| |
| |
| |
+--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 340 of 395 Issue 7

MENU: TECH/ENGINEER|DATE & TIME
+--------------------+ +--------------------+
|Current Date & Time | |Date and Time Format|
| | | |
|03/07/1980 23:46:19 | | |
| | | |
| | |DD MM YYYY |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|DISPLAY TEST
+--------------------+
| |
| |
|DISPLAY TEST |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|SECURITY
+--------------------+ +--------------------+
|Security Setup | |PC Setup Link |
| | | |
|Current Level: | |DISABLED |
|SECURITY : 9 | | |
| | | |
|Front Panel Keypad: | | |
|ENABLED | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 01
+--------------------+ +--------------------+ +--------------------+
|COM1 - DISPLAY | |COM1 - DISPLAY | |COM1 - DISPLAY |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM1 - DISPLAY |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 02
+--------------------+ +--------------------+ +--------------------+
|COM2 - PC LINK | |COM2 - PC LINK | |COM2 - PC LINK |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 38400 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM2 - PC LINK |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 341 of 395 Issue 7


MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 03
+--------------------+ +--------------------+ +--------------------+
|COM3 | |COM3 | |COM3 |
| | |GOOD_TX : 32 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM3 |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 04
+--------------------+ +--------------------+ +--------------------+
|COM4 | |COM4 | |COM4 |
| | |GOOD_TX : 69 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 7 |
|HEALTHY | |BAD_RX : 69 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY EVEN |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM4 |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 05
+--------------------+ +--------------------+ +--------------------+
|COM5 | |COM5 | |COM5 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM5 |
| |
|HANDSHAKE NONE |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 06
+--------------------+ +--------------------+ +--------------------+
|COM6 | |COM6 | |COM6 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 342 of 395 Issue 7

+--------------------+
|COM6 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 07
+--------------------+ +--------------------+ +--------------------+
|COM7 | |COM7 | |COM7 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM7 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 08
+--------------------+ +--------------------+ +--------------------+
|COM8 - IO | |COM8 - IO | |COM8 - IO |
| | |GOOD_TX : 804915 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 38400 |
| | |GOOD_RX : 804914 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM8 - IO |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|MODBUS ADDRESS
+--------------------+
|FLOW COMPUTER |
|SLAVE ADDRESS |
|2 |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 03
+--------------------+ +--------------------+
|COMMS TASK 03 | |COMMS TASK 03 |
| | | |
|Port: | |Address: |
|PORT 6 | |21 |
|Protocol: | | |
|MODBUS TCP | | |
| | | |
+--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 343 of 395 Issue 7

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 04
+--------------------+ +--------------------+
|COMMS TASK 04 | |COMMS TASK 04 |
| | | |
|Port: | |Address: |
|PORT 4 | |21 |
|Protocol: | | |
|MODBUS TCP | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 06
+--------------------+ +--------------------+
|COMMS TASK 06 | |COMMS TASK 06 |
| | | |
|Port: | |Address: |
|PORT 6 | |21 |
|Protocol: | | |
|RTU SERIAL | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 07
+--------------------+ +--------------------+
|COMMS TASK 07 | |COMMS TASK 07 |
| | | |
|Port: | |Address: |
|PORT 7 | |21 |
|Protocol: | | |
|RTU SERIAL | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|PRINTER
+--------------------+
|PRINTER |
| |
|Port: |
|PORT 3 |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|DOWN/UP CORR|INPUTS
+--------------------+ +--------------------+ +--------------------+
|DOWNSTREAM DENSITY | |DOWNSTREAM DENSITY | |METER TEMP |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | 100.00 Deg.C |
| | |Mode Status: | | |
| | |AVERAGE | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|METER TEMP | |DP Stack 1 | |DP Stack 1 |
| | |STR01 DP STACK | |STR01 DP STACK |
|Keypad Value: | |In Use DP Value: | | |
| 100.00 Deg.C | | 300.000 mbar | |Keypad Value: |
|Mode Status: | |NO CELL SELECTED | | 300.000 mbar |
|KEYPAD | |mode Status: | |Measured Value: |
| | |KEYPAD-F | | 0.000 mbar |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
|Limits (H/L) | | | | |
| | |Switch up point: | |Discrepancy: |
| 600.00 mbar | | 95.000 % | | 10.000 % |
| 5.00 mbar | |Switch down point: | |Discrepancy timout: |
| | | 90.000 % | | 5.000 s |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 344 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
| | | | | |
|Check DP Value: | |Low DP Cut Off: | |DP Cell type: |
| 20.000 mbar | | 10.000 mbar | |LO-HI |
|Live/Check: | | | |Cut off mode: |
|LIVE | | | |NORMAL |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|METER PRESSURE | |METER PRESSURE | |PRESSURE LOSS |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 barg | | 100.00 barg | | 0.000000 mbar |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PRESSURE LOSS | |TEMP EXP CONSTANT | |DENS EXP CONSTANT |
| | | | | |
|Keypad Value: | |Value: | |Value: |
| 0.000000 mbar | | -0.23076900 | | 0.76923100 |
|Mode Status: | | | | |
|CALCULATED | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|TEMP MEAS POINT | |PRESS MEAS POINT | |CORRECTION TYPE |
| | | | | |
|Status: | |Status: | |Status: |
|DOWNSTREAM | |UPSTREAM | |EXTENDED |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|DOWN/UP CORR|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|DOWNSTREAM PRESSURE | |DOWNSTREAM PRESSURE | |RECOVERED PRESSURE |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 99.700000 barg | | 10.000000 barg | | 100.000000 barg |
|In Use Value: | |Mode Status: | |In Use Value: |
| 99.700000 barg | |CALCULATED | | 100.000000 barg |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|RECOVERED PRESSURE | |UPSTREAM TEMP | |UPSTREAM TEMP |
| | | | | |
|Keypad Value: | |Calculated Value: | |Keypad Value: |
| 40.000000 barg | | 100.000000 Deg.C | | 50.000000 Deg.C |
|Mode Status: | |In Use Value: | |Mode Status: |
|CALCULATED | | 100.000000 Deg.C | |CALCULATED |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |UPSTREAM DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 0.000000 kg/m3 | | 50.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
| 0.000000 kg/m3 | |MEASURED | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM PRESSURE | |UPSTREAM PRESSURE | |DOWNSTREAM TEMP |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 100.000000 barg | | 50.000000 barg | | 100.000000 Deg.C |
|In Use Value: | |Mode Status: | |In Use Value: |
| 100.000000 barg | |CALCULATED | | 100.000000 Deg.C |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 345 of 395 Issue 7

+--------------------+
|DOWNSTREAM TEMP |
| |
|Keypad Value: |
| 50.000000 Deg.C |
|Mode Status: |
|CALCULATED |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|PIPE CORRECTION|INPUTS
+--------------------+ +--------------------+ +--------------------+
|CALIB PIPE DIAM | |CALIB ORIFICE DIAM | |PIPE CALIB TEMP |
| | | | | |
|Value: | |Value: | |Value: |
| 300.00000000 mm | | 200.00000000 mm | | 20.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|ORIFICE CALIB TEMP | |PIPE EXP CONSTANT | |ORIFICE EXP CONSTANT|
| | | | | |
|Value: | |Value: | |Value: |
| 15.00000000 Deg.C | | 0.00000925 | | 0.00000925 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM TEMP | |UPSTREAM TEMP | |PIPE MATERIAL |
| | | | | |
|In Use Value: | |Keypad Value: | |Status: |
| 100.000000 Deg.C | | 50.000000 Deg.C | |STAINLESS |
| | |Mode Status: | | |
| | |CALCULATED | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|ORIFICE MATERIAL |
| |
|Status: |
|STAINLESS |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|PIPE CORRECTION|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|CORRECTED PIPE DIAM | |CORRECTED PIPE DIAM | |CORRECTED ORIF DIAM |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 300.222000 mm | | 300.000000 mm | | 200.157250 mm |
|In Use Value: | |Mode Status: | |In Use Value: |
| 300.222000 mm | |CALCULATED | | 200.157250 mm |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|CORRECTED ORIF DIAM |
| |
|Keypad Value: |
| 200.000000 mm |
|Mode Status: |
|CALCULATED |
| |
+--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 346 of 395 Issue 7

MENU: CALCULATIONS|STREAM 1|AGA 8|INPUTS
+--------------------+ +--------------------+ +--------------------+
|AGA8 METHOD | |UPSTREAM PRESS | |UPSTREAM PRESS |
| | | | | |
|Status: | |In Use Value: | |Keypad Value: |
|DETAIL | | 100.000000 barg | | 50.000000 barg |
| | | | |Mode Status: |
| | | | |CALCULATED |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM TEMP | |UPSTREAM TEMP | |STANDARD PRESS |
| | | | | |
|In Use Value: | |Keypad Value: | |Value: |
| 100.000000 Deg.C | | 50.000000 Deg.C | | 0.00000000 barg |
| | |Mode Status: | | |
| | |CALCULATED | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STANDARD TEMP | |SG CHARACTERISTIC | |SG CHARACTERISTIC |
| | | | | |
|Value: | |In Use Value: | |Keypad Value: |
| 20.00000000 Deg.C | | 0.581216 | | 0.500000 |
| | | | |Mode Status: |
| | | | |CV |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|HEATING VALUE | |HEATING VALUE | |INUSE COMPOSITION |
| | | | | |
|In Use Value: | |Keypad Value: | |NITROGEN |
| 38.599754 MJ/Sm3 | | 40.000000 MJ/Sm3 | | 0.25950000 % |
| | |Mode Status: | | |
| | |CV | |CO2 |
| | | | | 0.59560000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|H2S | |HELIUM | |ETHANE |
| 0.00000000 % | | 0.00000000 % | | 1.81860000 % |
| | | | | |
|H2O | |METHANE | |PROPANE |
| 0.00000000 % | | 96.52220000 % | | 0.45960000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|N_BUTANE | |N_PENTANE | |NEO_PENTANE |
| 0.10070000 % | | 0.24380000 % | | 0.00000000 % |
| | | | | |
|I_BUTANE | |I_PENTANE | |HEXANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|HEPTANE | |NONANE | |OXYGEN |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|OCTANE | |DECANE | |CO |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|HYDROGEN | |TOLUENE | |C6_PLUS |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|BENZENE | |ARGON | |CX_PLUS |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 347 of 395 Issue 7

MENU: CALCULATIONS|STREAM 1|AGA 8|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM DENSITY | |UPSTREAM DENSITY | |UPSTREAM DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Limits (H/L) |
| 57.943450 kg/m3 | | 50.000000 kg/m3 | | |
|In Use Value: | |Mode Status: | | 100.00 kg/m3 |
| 0.000000 kg/m3 | |MEASURED | | 0.20 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Zf | |Zf | |Zb |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 0.944196 | | 1.000000 | | 0.997977 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 0.944196 | |COMPRESS | | 0.997977 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Zb | |MOLECULAR WEIGHT | |MOLECULAR WEIGHT |
| | | | | |
|Keypad Value: | |Calculated Value: | |Keypad Value: |
| 1.000000 | | 16.803830 | | 16.000000 |
|Mode Status: | |In Use Value: | |Mode Status: |
|CALCULATED | | 16.803830 | |CALCULATED |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|IDEAL RDENS | |IDEAL RDENS | |STANDARD DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 0.580191 | | 0.500000 | | 0.699967 kg/m3 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 0.580191 | |CV | | 0.699967 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STANDARD DENSITY | |STANDARD DENSITY | |REAL REL DENSITY |
| | | | | |
|Keypad Value: | |Limits (H/L) | |Calculated Value: |
| 10.000000 kg/m3 | | | | 0.581194 |
|Mode Status: | | 100.00 kg/m3 | |In Use Value: |
|COMPRESS | | 0.20 kg/m3 | | 0.581216 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|REAL REL DENSITY | |REAL REL DENSITY | |Zs |
| | | | | |
|Keypad Value: | |Limits (H/L) | |Calculated Value: |
| 0.500000 | | | | 0.997860 |
|Mode Status: | | 1.50 | |In Use Value: |
|CV | | 0.40 | | 0.997860 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|Zs |
| |
|Keypad Value: |
| 1.000000 |
|Mode Status: |
|COMPRESS |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|ISO5167|INPUTS
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
|In Use DP Value: | | | |Limits (H/L) |
| 300.000 mbar | |Keypad Value: | | |
|NO CELL SELECTED | | 300.000 mbar | | 600.00 mbar |
|mode Status: | |Measured Value: | | 5.00 mbar |
|KEYPAD-F | | 0.000 mbar | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 348 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |DP Stack 1 |
|STR01 DP STACK | |STR01 DP STACK | |STR01 DP STACK |
| | | | | |
|Switch up point: | |Discrepancy: | |Check DP Value: |
| 95.000 % | | 10.000 % | | 20.000 mbar |
|Switch down point: | |Discrepancy timout: | |Live/Check: |
| 90.000 % | | 5.000 s | |LIVE |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP Stack 1 | |DP Stack 1 | |UPSTREAM PRESSURE |
|STR01 DP STACK | |STR01 DP STACK | | |
| | | | |In Use Value: |
|Low DP Cut Off: | |DP Cell type: | | 100.000000 barg |
| 10.000 mbar | |LO-HI | | |
| | |Cut off mode: | | |
| | |NORMAL | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|UPSTREAM PRESSURE | |UPSTREAM DENSITY | |UPSTREAM DENSITY |
| | | | | |
|Keypad Value: | |In Use Value: | |Keypad Value: |
| 50.000000 barg | | 0.000000 kg/m3 | | 50.000000 kg/m3 |
|Mode Status: | | | |Mode Status: |
|CALCULATED | | | |MEASURED |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VISCOSITY | |CORR PIPE DIAM | |CORR PIPE DIAM |
| | | | | |
|Value: | |In Use Value: | |Keypad Value: |
| 0.01710000 cP | | 300.222000 mm | | 300.000000 mm |
| | | | |Mode Status: |
| | | | |CALCULATED |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CORR ORIFICE DIAM | |CORR ORIFICE DIAM | |ISENTROPIC EXPONENT |
| | | | | |
|In Use Value: | |Keypad Value: | |Value: |
| 200.157250 mm | | 200.000000 mm | | 1.30000000 |
| | |Mode Status: | | |
| | |CALCULATED | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DP TAP TYPE | |LF CUT OFF STATUS | |DOWNSTREAM PRESSURE |
| | | | | |
|Status: | |Status: | |In Use Value: |
|FLANGE | |CLEAR | | 99.700000 barg |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|DOWNSTREAM PRESSURE | |CALC TYPE |
| | | |
|Keypad Value: | |Status: |
| 10.000000 barg | |1998 |
|Mode Status: | | |
|CALCULATED | | |
| | | |
+--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|ISO5167|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|MASS FLOWRATE | |MASS FLOWRATE | |PRESSURE LOSS |
| | | | | |
|Calculated Value: | |Limits (H/L) | |Calculated Value: |
| 0.000000 t/h | | | | 0.000000 mbar |
|In Use Value: | | 950.00 t/h | |In Use Value: |
| 0.000000 t/h | | -5.00 t/h | | 0.000000 mbar |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 349 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|PRESSURE LOSS | |BETA | |REYNOLDS NUMBER |
| | | | | |
|Keypad Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 mbar | | 0.000000 | | 0.000000 |
|Mode Status: | |In Use Value: | |In Use Value: |
|CALCULATED | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|EXPANSION FACTOR | |DISCHARGE COEFF | |FLOW COEFFICIENT |
| | | | | |
|Calculated Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|In Use Value: | |In Use Value: | |In Use Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FLOW COEFFICIENT | |VEL OF APPROACH FAC | |PID PV COEFF |
| | | | | |
|Keypad Value: | |Calculated Value: | |Calculated Value: |
| 0.000000 | | 0.000000 | | 0.000000 |
|Mode Status: | |In Use Value: | |In Use Value: |
|CALCULATED | | 0.000000 | | 0.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|ISO6976|INPUTS
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NITROGEN | |H2S | |HELIUM |
| 0.25950000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO2 | |H2O | |METHANE |
| 0.59560000 % | | 0.00000000 % | | 96.52220000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|ETHANE | |N_BUTANE | |N_PENTANE |
| 1.81860000 % | | 0.10070000 % | | 0.24380000 % |
| | | | | |
|PROPANE | |I_BUTANE | |I_PENTANE |
| 0.45960000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|NEO_PENTANE | |HEPTANE | |NONANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|HEXANE | |OCTANE | |DECANE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |INUSE COMPOSITION | |INUSE COMPOSITION |
| | | | | |
|OXYGEN | |HYDROGEN | |TOLUENE |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
| | | | | |
|CO | |BENZENE | |ARGON |
| 0.00000000 % | | 0.00000000 % | | 0.00000000 % |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INUSE COMPOSITION | |CV CALC TABLE | |COMPOSITION TYPE |
| | | | | |
|C6_PLUS | |Status: | |Status: |
| 0.00000000 % | |ISO6976 19 | |VOL % |
| | | | | |
|CX_PLUS | | | | |
| 0.00000000 % | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 350 of 395 Issue 7

+--------------------+
|REFERENCE CONDITIONS|
| |
|Status: |
|15/15 DEG |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|ISO6976|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|STD COMPRESS (Zs) | |STD COMPRESS (Zs) | |IDEAL REL DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 0.997817 | | 1.000000 | | 0.580191 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 0.997860 | |COMPRESS | | 0.580191 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|IDEAL REL DENSITY | |IDEAL STD DENSITY | |IDEAL STD DENSITY |
| | | | | |
|Keypad Value: | |Calculated Value: | |Keypad Value: |
| 0.500000 | | 0.710673 kg/m3 | | 0.750000 kg/m3 |
|Mode Status: | |In Use Value: | |Mode Status: |
|CV | | 0.710673 kg/m3 | |CALCULATED |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|IDEAL CALORIFIC VAL | |IDEAL CALORIFIC VAL | |REAL REL DENSITY |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 38.515472 MJ/Sm3 | | 40.000000 MJ/Sm3 | | 0.581216 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 38.515472 MJ/Sm3 | |CALCULATED | | 0.581216 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|REAL REL DENSITY | |REAL REL DENSITY | |REAL STD DENSITY |
| | | | | |
|Keypad Value: | |Limits (H/L) | |Calculated Value: |
| 0.500000 | | | | 0.712228 kg/m3 |
|Mode Status: | | 1.50 | |In Use Value: |
|CV | | 0.40 | | 0.699967 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|REAL STD DENSITY | |REAL STD DENSITY | |REAL CALORIFIC VALUE|
| | | | | |
|Keypad Value: | |Limits (H/L) | |Calculated Value: |
| 10.000000 kg/m3 | | | | 38.599754 MJ/Sm3 |
|Mode Status: | | 100.00 kg/m3 | |In Use Value: |
|COMPRESS | | 0.20 kg/m3 | | 38.599754 MJ/Sm3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|REAL CALORIFIC VALUE| |REAL CALORIFIC VALUE|
| | | |
|Keypad Value: | |Limits (H/L) |
| 40.000000 MJ/Sm3 | | |
|Mode Status: | | 0.00 MJ/Sm3 |
|CV | | 0.00 MJ/Sm3 |
| | | |
+--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 351 of 395 Issue 7
20.4 Lxport Condensate
MENU: FLOW RATES|STREAM 1|STR01 UVOL FR
+--------------------+
|STR01 UVOL FR |
| 0.000 m3/h |
|Limits (H/L) |
| |
| 400.000 m3/h |
| 5.000 m3/h |
| |
+--------------------+

MENU: FLOW RATES|STREAM 1|STR01 CVOL FR
+--------------------+ +--------------------+ +--------------------+
|STR01 CVOL FR | |STR01 CVOL FR | |STR01 CVOL FR |
| 0.000 Sm3/h | | | | |
| | |Cur Day Max | |Prev Day Max |
|Sm3/d | | 0.000 Sm3/h | | 0.000 Sm3/h |
| 0.00 | | | | |
| | |Cur Day Min | |Prev Day Min |
| | | 0.000 Sm3/h | | 0.000 Sm3/h |
+--------------------+ +--------------------+ +--------------------+

MENU: FLOW RATES|STREAM 1|STR01 MASS FR
+--------------------+
|STR01 MASS FR |
| 0.000 t/h |
| |
| |
| |
| |
| |
+--------------------+

MENU: TOTALS|STREAM 1|STR01 UVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 UVOL | |STR01 UVOL MAINT | |STR01 UVOL HOURLY |
| | | | | |
| | |Current Period | |Current Period |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
| | |Previous Period | |Previous Period |
| | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR01 UVOL DAILY | |STR01 UVOL HOURLY | |STR01 UVOL DAILY |
| | | | | |
|Current Period | |Current Period | |Current Period |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
|Previous Period | |Previous Period | |Previous Period |
| 0.000 m3 | | 0.000 m3 | | 0.000 m3 |
+--------------------+ +--------------------+ +--------------------+

MENU: TOTALS|STREAM 1|STR01 CVOL
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |CUMULATIVE TOTAL | |MAINTENANCE TOTAL |
|STR01 CVOL | |STR01 CVOL | |STR01 CVOL MAINT |
| | | | | |
| | | | |Current Period |
| 0.000 Sm3 | | 0.000 | | 0.000 Sm3 |
| | |bbl | |Previous Period |
| | | | | 0.000 Sm3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 1 | |BASETIME 2 |
|STR01 CVOL HOURLY | |STR01 CVOL DAILY | |STR01 CVOL HOURLY |
| | | | | |
|Current Period | |Current Period | |Current Period |
| 0.000 Sm3 | | 0.000 Sm3 | | 0.000 Sm3 |
|Previous Period | |Previous Period | |Previous Period |
| 0.000 Sm3 | | 0.000 Sm3 | | 0.000 Sm3 |
+--------------------+ +--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 352 of 395 Issue 7



+--------------------+
|BASETIME 2 |
|STR01 CVOL DAILY |
| |
|Current Period |
| 0.000 Sm3 |
|Previous Period |
| 0.000 Sm3 |
+--------------------+

MENU: TOTALS|STREAM 1|STR01 MASS
+--------------------+ +--------------------+ +--------------------+
|CUMULATIVE TOTAL | |MAINTENANCE TOTAL | |BASETIME 1 |
|STR01 MASS | |STR01 MASS MAINT | |STR01 MASS HOURLY |
| | | | | |
| | |Current Period | |Current Period |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
| | |Previous Period | |Previous Period |
| | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASETIME 1 | |BASETIME 2 | |BASETIME 2 |
|STR01 MASS DAILY | |STR01 MASS HOURLY | |STR01 MASS DAILY |
| | | | | |
|Current Period | |Current Period | |Current Period |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
|Previous Period | |Previous Period | |Previous Period |
| 0.000 tonne | | 0.000 tonne | | 0.000 tonne |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|PROVED DATA
+--------------------+ +--------------------+ +--------------------+
|STR01 PROVED FR | |STR01 PROVED TEMP | |STR01 PROVED PRESS |
| | | | | |
|Value: | |Value: | |Value: |
| 100.00000000 m3/h | | 15.00000000 Deg.C | | 20.00000000 barg |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 PROVED FREQ | |STR01 PROVED MF | |STR01 PROVED KF |
| | | | | |
|Value: | |Value: | |Value: |
| 100.00000000 Hz | | 1.00000000 | | 1.0000E+03 pls/m3 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 NEW M-FAC ACC | |STR01 TEMP DISCREP | |STR01 PRESS DISCREP |
| | | | | |
|Status: | |Value: | |Value: |
|IDLE | | 10.00000000 Deg.C | | 10.00000000 barg |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|STR01 DENS DISCREP | |STR01 FR DISCREP |
| | | |
|Value: | |Value: |
| 10.00000000 kg/m3 | | 10.00000000 m3/h |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+






Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 353 of 395 Issue 7



MENU: OPERATOR|STREAM 1|SETUP
+--------------------+ +--------------------+ +--------------------+
|STR01 TYPE | |STR01 NAME | |STR01 METER LOCATION|
| | | | | |
|Status: | |Value: | |Value: |
|LIQ TURB | |LIQ TURBINE | |LINE 1 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 BASE TEMP | |STR01 VAPOUR PRESS | |STR01 VAPOUR PRESS |
| | | | | |
|Value: | |In Use Value: | |Keypad Value: |
| 15.00000000 Deg.C | | 0.000000 barg | | 0.000000 barg |
| | | | | |
| | |Mode Status: | |Mode Status: |
| | |KEYPAD | |KEYPAD |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|STR01 LF C/O STATUS | |STR01 LF C/O LIMIT |
| | | |
|Status: | |Value: |
|SET | | 60.00000000 m3/h |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+
MENU: OPERATOR|STREAM 1|STATUS
+--------------------+ +--------------------+ +--------------------+
|STR01 STATUS | |STR01 DISABLE | |STR01 PULSE ENABLE |
| | | | | |
|Status: | |Status: | |Status: |
|ILLEGAL-V | |CLEAR | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|METER SETUP
+--------------------+ +--------------------+ +--------------------+
|STR01 BAD PLS THRESH| |STR01 LOW FREQ C/O | |STR01 ERROR CHK FREQ|
| | | | | |
|Value: | |Value: | |Value: |
| 50.00000000 | | 60.00000000 Hz | | 5.00000000 Hz |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 RESET THRESH | |STR01 KP TURB FREQ | |STR01 TURB LIVE/CHK |
| | | | | |
|Value: | |Value: | |Status: |
| 200000.00000000 | | 0.00000000 Hz | |LIVE |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 TMP EXP CF MTR| |STR01 TMP EXP CF RTR| |STR01 SPOOL RADIUS |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 | | 1.00000000 mm |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 SPOOL WALL T. | |STR01 MTR ROTOR AREA| |STR01 MOD ELASTICITY|
| | | | | |
|Value: | |Value: | |Value: |
| 1.00000000 mm | | 0.00000000 mm2 | | 2100000.00000000 |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 354 of 395 Issue 7
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|METERING I/O
+--------------------+ +--------------------+ +--------------------+
|MTR TEMP | |MTR TEMP | |MTR PRESS |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 100.00 barg |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|MTR PRESS | |PULSE COUNT | |PULSE FREQ |

| | | | | |
|Keypad Value: | |Good Pulse Count: | |Value: |
| 100.00 barg | | 0 | | 0.00000000 Hz |
|Mode Status: | | | | |
|KEYPAD-F | |Bad Pulse Count: | | |
| | | 0 | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|CALCULATED DATA
+--------------------+ +--------------------+ +--------------------+
|STR01 METER-FACTOR | |STR01 METER-FACTOR | |STR01 K-FACTOR |
| | | | | |
|In Use Value: | |Limits (H/L) | |In Use Value: |
| 1.000000 | | | | 1000.000000 pls/m3 |
| | | 1.10 | | |
|MODE | | 0.90 | | |
|CALCULATED | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 K-FACTOR | |STR01 CTSm | |STR01 CTSm |
| | | | | |
|Keypad Value: | |In Use Value: | |Keypad Value: |
| 1000.000000 pls/m3 | | 1.000000 | | 1.000000 |
| | | | | |
| | |Mode Status: | |Mode Status: |
| | |KEYPAD | |KEYPAD |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 CPSm | |STR01 CPSm | |STR01 VCF (CCF) |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 1.000000 | | 1.000000 | | 0.946672 |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|KEYPAD | |KEYPAD | |METER |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|STR01 VCF (CCF) |
| |
|Keypad Value: |
| 1.000000 |
| |
|Mode Status: |
|METER |
+--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 PRESS
+--------------------+ +--------------------+ +--------------------+
|PRESS BASE 1 | |PRESS BASE 1 | |PRESS BASE 1 PREV |
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 barg | | 0.00000000 barg | | 0.00000000 barg |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 barg | | | | 0.00000000 barg |
+--------------------+ +--------------------+ +--------------------+



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 355 of 395 Issue 7




+--------------------+ +--------------------+ +--------------------+
|PRESS BASE 1 PREV | |PRESS BASE 2 | |PRESS BASE 2 |
| | | | | |
|HOURLY | |BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 barg | | 0.00000000 barg | | 0.00000000 barg |
| | | | | |
| | |BASETIME 2 PRD 2 | | |
| | | 0.00000000 barg | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|PRESS BASE 2 PREV | |PRESS BASE 2 PREV |
| | | |
|BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 barg | | 0.00000000 barg |
| | | |
|BASETIME 2 PRD 2 | | |
| 0.00000000 barg | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 TEMP
+--------------------+ +--------------------+ +--------------------+
|TEMP BASE 1 | |TEMP BASE 1 | |TEMP BASE 1 PREV |
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 Deg.C | | 0.00000000 Deg.C | | 0.00000000 Deg.C |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 Deg.C | | | | 0.00000000 Deg.C |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|TEMP BASE 1 PREV | |TEMP BASE 2 | |TEMP BASE 2 |
| | | | | |
|HOURLY | |BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 Deg.C | | 0.00000000 Deg.C | | 0.00000000 Deg.C |
| | | | | |
| | |BASETIME 2 PRD 2 | | |
| | | 0.00000000 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|TEMP BASE 2 PREV | |TEMP BASE 2 PREV |
| | | |
|BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 Deg.C | | 0.00000000 Deg.C |
| | | |
|BASETIME 2 PRD 2 | | |
| 0.00000000 Deg.C | | |
+--------------------+ +--------------------+
MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 STD DENS
+--------------------+ +--------------------+ +--------------------+
|STD DENS BASE 1 | |STD DENS BASE 1 | |STD DENS BASE 1 PREV|
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 kg/m3 | | | | 0.00000000 kg/m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STD DENS BASE 1 PREV| |STD DENS BASE 2 | |STD DENS BASE 2 |
| | | | | |
|HOURLY | |DAILY | |HOURLY |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | | | |
| | |BASETIME 2 PRD 2 | | |
| | | 0.00000000 kg/m3 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|STD DENS BASE 2 PREV| |STD DENS BASE 2 PREV|
| | | |
|BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 356 of 395 Issue 7
|BASETIME 2 PRD 2 | | |
| 0.00000000 kg/m3 | | |
+--------------------+ +--------------------+
MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 MTR DENS
+--------------------+ +--------------------+ +--------------------+
|MTR DENS BASE 1 | |MTR DENS BASE 1 | |MTR DENS BASE 1 PREV|
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | | | |
|WEEKLY | | | |WEEKLY |

| 0.00000000 kg/m3 | | | | 0.00000000 kg/m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|MTR DENS BASE 1 PREV| |MTR DENS BASE 2 | |MTR DENS BASE 2 |
| | | | | |
|HOURLY | |BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | | | |
| | |BASETIME 2 PRD 2 | | |
| | | 0.00000000 kg/m3 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|MTR DENS BASE 2 PREV| |MTR DENS BASE 2 PREV|
| | | |
|BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 kg/m3 | | 0.00000000 kg/m3 |
| | | |
|BASETIME 2 PRD 2 | | |
| 0.00000000 kg/m3 | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 KF
+--------------------+ +--------------------+ +--------------------+
|KF BASE 1 | |KF BASE 1 | |KF BASE 1 PREV |
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 pls/m3 | | 0.00000000 pls/m3 | | 0.00000000 pls/m3 |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 pls/m3 | | | | 0.00000000 pls/m3 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|KF BASE 1 PREV | |KF BASE 2 | |KF BASE 2 |
| | | | | |
|HOURLY | |BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 pls/m3 | | 0.00000000 pls/m3 | | 0.00000000 pls/m3 |
| | | | | |
| | |BASETIME 2 PRD 2 | | |
| | | 0.00000000 pls/m3 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|KF BASE 2 PREV | |KF BASE 2 PREV |
| | | |
|BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 pls/m3 | | 0.00000000 pls/m3 |
| | | |
|BASETIME 2 PRD 2 | | |
| 0.00000000 pls/m3 | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 SVOL
+--------------------+ +--------------------+ +--------------------+
|SVOL BASE 1 | |SVOL BASE 1 | |SVOL BASE 1 PREV |
| | | | | |
|DAILY | |HOURLY | |DAILY |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
|WEEKLY | | | |WEEKLY |
| 0.00000000 | | | | 0.00000000 |
+--------------------+ +--------------------+ +--------------------+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 357 of 395 Issue 7



+--------------------+ +--------------------+ +--------------------+
|SVOL BASE 1 PREV | |SVOL BASE 2 | |SVOL BASE 2 |
| | | | | |
|HOURLY | |BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
| | |BASETIME 2 PRD 2 | | |
| | | 0.00000000 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|SVOL BASE 2 PREV | |SVOL BASE 2 PREV |
| | | |
|BASETIME 2 PRD 1 | |BASETIME 2 PRD 3 |
| 0.00000000 | | 0.00000000 |
| | | |
|BASETIME 2 PRD 2 | | |
| 0.00000000 | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|AVERAGE DATA|STR01 METHOD
+--------------------+
|STR01 METHOD |
| |
|Status: |
|FWA |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|IP2 DATA
+--------------------+ +--------------------+ +--------------------+
|STR01 ALPHA | |STR01 ALPHA | |STR01 BETA |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 0.000718 | | 0.000010 | | 0.000092 |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|METER | |METER | |METER |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 BETA | |STR01 MTR DENSITY | |STR01 MTR DENSITY |
| | | | | |
|Keypad Value: | |In Use Value: | |Keypad Value: |
| 1.000000000E-06 | | 875.499992 kg/m3 | | 900.000000 kg/m3 |
| | | | | |
|Mode Status: | |Mode Status: | |Mode Status: |
|METER | |METER | |METER |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 MTR DENSITY | |STR01 STD DENSITY | |STR01 STD DENSITY |
| | | | | |
|Limits (H/L) | |In Use Value: | |Keypad Value: |
| | | 924.819175 kg/m3 | | 800.000000 kg/m3 |
| 900.00 kg/m3 | | | | |
| 500.00 kg/m3 | |Mode Status: | |Mode Status: |
| | |STD 15 | |STD 15 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STR01 STD DENSITY | |STR01 K0 | |STR01 K1 |
| | | | | |
|Limits (H/L) | |Value: | |Value: |
| | | 613.97230000 | | 0.00000000 |
| 900.00 kg/m3 | | | | |
| 500.00 kg/m3 | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|STR01 K2 |
| |
|Value: |
| 0.00000000 |
| |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 358 of 395 Issue 7
| |
| |
+--------------------+
MENU: OPERATOR|STREAM 1|VALVES|PROVER VALVE 1
+--------------------+ +--------------------+ +--------------------+
|P-VLV 1 POSN | |P-VLV 1 TRAVEL TIME | |P-VLV 1 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|P-VLV 1 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|OUTLET VALVE 1
+--------------------+ +--------------------+ +--------------------+
|O-VLV 1 POSN | |O-VLV 1 TRAVEL TIME | |O-VLV 1 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|O-VLV 1 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|INLET VALVE 1
+--------------------+ +--------------------+ +--------------------+
|I-VLV 1 POSN | |I-VLV 1 TRAVEL TIME | |I-VLV 1 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|I-VLV 1 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|PROVER VALVE 2
+--------------------+ +--------------------+ +--------------------+
|P-VLV 2 POSN | |P-VLV 2 TRAVEL TIME | |P-VLV 2 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 359 of 395 Issue 7



+--------------------+
|P-VLV 2 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|OUTLET VALVE 2
+--------------------+ +--------------------+ +--------------------+
|O-VLV 2 POSN | |O-VLV 2 TRAVEL TIME | |O-VLV 2 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|O-VLV 2 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|INLET VALVE 2
+--------------------+ +--------------------+ +--------------------+
|I-VLV 2 POSN | |I-VLV 2 TRAVEL TIME | |I-VLV 2 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|I-VLV 2 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|DENSITOMETERS|DENSITOMETER A
+--------------------+ +--------------------+ +--------------------+
|DENS A TYPE | |DENS A TEMP | |DENS A TEMP |
| | | | | |
|Status: | |In Use Value: | |Keypad Value: |
|SOL 1762 | | 100.00 Deg.C | | 100.00 Deg.C |
| | | | |Mode Status: |
| | | | |KEYPAD-F |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DENS A PRESSURE | |DENS A PRESSURE | |DENS A PERIOD |
| | | | | |
|In Use Value: | |Keypad Value: | |Period |
| 100.00 barg | | 100.00 barg | | 0.000000 uS |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 360 of 395 Issue 7



+--------------------+ +--------------------+ +--------------------+
|DENS A LIVE/CHECK | |DENS A CHECK PERIOD | |DENS A CONSTANTS |
| | | | | |
|Status: | |Value: | |SOLK0 |
|LIVE | | 0.01000000 uS | |-1.175180000E+03 |
| | | | | |
| | | | |SOLK1 |
| | | | |-2.971830000E-01 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DENS A CONSTANTS | |DENS A CONSTANTS | |DENS A CONSTANTS |
| | | | | |
|SOLK2 | |SOLK19 | |SOLK20B |
| 1.269820000E-03 | | 2.870000000E-02 | |-1.081000000E-06 |
| | | | | |
|SOLK18 | |SOLK20A | |SOLK21A |
| 1.622000000E-06 | | 3.618000000E-05 | | 4.904000000E-02 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|DENS A CONSTANTS | |DENS CONST ACC |
| | | |
|SOLK21B | |Status: |
|-1.465000000E-03 | |IDLE |
| | | |
|SOLTcal | | |
| 2.000000000E+01 | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|DENSITOMETERS|DENSITOMETER B
+--------------------+ +--------------------+ +--------------------+
|DENS B TYPE | |DENS B TEMP | |DENS B TEMP |
| | | | | |
|Status: | |In Use Value: | |Keypad Value: |
|SOL 1762 | | 100.00 Deg.C | | 100.00 Deg.C |
| | | | |Mode Status: |
| | | | |KEYPAD-F |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DENS B PRESSURE | |DENS B PRESSURE | |DENS B PERIOD |
| | | | | |
|In Use Value: | |Keypad Value: | |Period |
| 100.00 barg | | 100.00 barg | | 0.000000 uS |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DENS B LIVE/CHECK | |DENS B CHECK PERIOD | |DENS B CONSTANTS |
| | | | | |
|Status: | |Value: | |SOLK0 |
|LIVE | | 0.01000000 uS | |-1.115740000E+03 |
| | | | | |
| | | | |SOLK1 |
| | | | |-3.158900000E-01 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DENS B CONSTANTS | |DENS B CONSTANTS | |DENS B CONSTANTS |
| | | | | |
|SOLK2 | |SOLK19 | |SOLK20B |
| 1.247680000E-03 | | 2.621000000E-02 | |-1.296000000E-06 |
| | | | | |
|SOLK18 | |SOLK20A | |SOLK21A |
| 5.261000000E-07 | | 6.887000000E-05 | | 9.003000000E-02 |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|DENS B CONSTANTS | |DENS CONST ACC |
| | | |
|SOLK21B | |Status: |
|-1.694000000E-03 | |IDLE |
| | | |
|SOLTcal | | |
| 2.000000000E+01 | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 361 of 395 Issue 7
+--------------------+ +--------------------+


MENU: OPERATOR|STREAM 1|DENSITOMETERS|MEASURED DENS

+--------------------+ +--------------------+ +--------------------+
|OBS DENSITY | |OBS DENSITY | |OBS DENSITY |
| | | | | |
|In Use Value: | |Keypad Value: | |Dens A Value: |
| 875.500000 kg/m3 | | 875.500000 kg/m3 | | 0.000000 kg/m3 |
| | | | |Dens B Value: |
| | | | | 0.000000 kg/m3 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|OBS DENSITY |
| |
|Discrep Limit: |
| 10.000000 kg/m3 |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|LINEAR
+--------------------+ +--------------------+ +--------------------+
|LINEAR PT 1 | |LINEAR PT 2 | |LINEAR PT 3 |
| | | | | |
|Freq: | |Freq: | |Freq: |
| 100.00000000 Hz | | 200.00000000 Hz | | 300.00000000 Hz |
|M Factor Values: | |M Factor Values: | |M Factor Values: |
| 1.00000000 | | 1.10000000 | | 1.20000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|LINEAR PT 4 | |LINEAR PT 5 | |LINEAR PT 6 |
| | | | | |
|Freq: | |Freq: | |Freq: |
| 400.00000000 Hz | | 500.00000000 Hz | | 600.00000000 Hz |
|M Factor Values: | |M Factor Values: | |M Factor Values: |
| 1.30000000 | | 1.40000000 | | 0.15000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|LINEAR PT 7 | |LINEAR PT 8 | |LINEAR PT 9 |
| | | | | |
|Freq: | |Freq: | |Freq: |
| 700.00000000 Hz | | 800.00000000 Hz | | 0.00000000 Hz |
|M Factor Values: | |M Factor Values: | |M Factor Values: |
| 1.60000000 | | 1.70000000 | | 0.00000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|LINEAR ACCEPT |
| |
|Meter Factor: |
|IDLE |
| |
| |
| |
+--------------------+

MENU: OPERATOR|IO BOARD 1|I/O01 PID LOOP 1
+--------------------+ +--------------------+ +--------------------+
|AUTO/MAN MODE | |DIRECTION | |SETPOINT TRACKING |
| | | | | |
|Status: | |Status: | |Status: |
|MANUAL | |REVERSE | |ON |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+




Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 362 of 395 Issue 7



+--------------------+ +--------------------+ +--------------------+
|CLAMPING | |SLEW LIMIT | |RAMP RATE |
| | | | | |
|Status: | |Value: | |Value: |
|ON | | 60.00000000 | | 0.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|MANUAL POSITION | |SETPOINT | |PV RANGE |
| | | | | |
|Value: | |Value: | |Value: |
| 100.00000000 % | | 0.00000000 | | 2000.00000000 |
| | | | | |
| | | | | |
| | | | | |

+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PROPORTIONAL BAND | |INTEGRAL TIME | |DERIVATIVE TIME |
| | | | | |
|Value: | |Value: | |Value: |
| 50.00000000 | | 0.00000000 s | | 0.00000000 s |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|OUTPUT POSITION |
| |
|Value: |
| 100.00000000 % |
| |
| |
| |
+--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 01 - MTR PRS
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 1 | |ADC Channel 1 | |ADC Channel 1 |
|MTR PRS | |MTR PRS | |MTR PRS |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 barg | | 100.000 barg | | 102.00 barg |
|Mode Status: | |Measured Value: | | -2.00 barg |
|KEYPAD-F | | -24.998 barg | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 1 | |ADC Channel 1 |
|MTR PRS | |MTR PRS |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 2.94871512E-04 mA | | 100.000 barg |
| | | 0.000 barg |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 03 - STRAINE
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 3 | |ADC Channel 3 | |ADC Channel 3 |
|STRAINER | |STRAINER | |STRAINER |
| | | | | |
|In Use Value: | |Keypad Value: | |Current: |
| -24.999 | | 100.000 | | 1.24010825E-04 mA |
|Mode Status: | |Measured Value: | | |
|MEASURED | | -24.999 | | |
+--------------------+ +--------------------+ +--------------------+





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 363 of 395 Issue 7



+--------------------+
|ADC Channel 3 |
|STRAINER |
|HIGH AND LOW SCALE |
| |
| 100.000 |
| 0.000 |
| |
+--------------------+


MENU: PLANT I/O|ANALOG INPUTS|ADC 04 - PRV 1 L
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 4 | |ADC Channel 4 | |ADC Channel 4 |
|PRV 1 L/R | |PRV 1 L/R | |PRV 1 L/R |
| | | | | |
|In Use Value: | |Keypad Value: | |Current: |
| -24.998 | | 100.000 | | 3.38886341E-04 mA |
|Mode Status: | |Measured Value: | | |
|MEASURED | | -24.998 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|ADC Channel 4 |
|PRV 1 L/R |
|HIGH AND LOW SCALE |
| |
| 100.000 |
| 0.000 |
| |
+--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 05 - PRV 2 L
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 5 | |ADC Channel 5 | |ADC Channel 5 |
|PRV 2 L/R | |PRV 2 L/R | |PRV 2 L/R |
| | | | | |
|In Use Value: | |Keypad Value: | |Current: |
| -25.000 | | 100.000 | | 4.93626248E-05 mA |
|Mode Status: | |Measured Value: | | |
|MEASURED | | -25.000 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|ADC Channel 5 |
|PRV 2 L/R |
|HIGH AND LOW SCALE |
| |
| 100.000 |
| 0.000 |
| |
+--------------------+

MENU: PLANT I/O|ANALOG INPUTS|ADC 06 - DNS PRS
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 6 | |ADC Channel 6 | |ADC Channel 6 |
|DNS PRS | |DNS PRS | |DNS PRS |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 barg | | 100.000 barg | | 102.00 barg |
|Mode Status: | |Measured Value: | | -2.00 barg |
|KEYPAD-F | | -24.998 barg | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 6 | |ADC Channel 6 |
|DNS PRS | |DNS PRS |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 3.13985045E-04 mA | | 100.000 barg |
| | | 0.000 barg |
| | | |
+--------------------+ +--------------------+



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 364 of 395 Issue 7



MENU: PLANT I/O|ANALOG INPUTS|ADC 07 - DNS TMP
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 7 | |ADC Channel 7 | |ADC Channel 7 |
|DNS TMP | |DNS TMP | |DNS TMP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 Deg.C | | 100.000 Deg.C | | 102.00 Deg.C |
|Mode Status: | |Measured Value: | | -2.00 Deg.C |
|KEYPAD-F | | -24.997 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 7 | |ADC Channel 7 |
|DNS TMP | |DNS TMP |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 4.26665181E-04 mA | | 100.000 Deg.C |
| | | 0.000 Deg.C |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|PRT/RTD INPUTS|PRT 01 - MTR TMP
+--------------------+ +--------------------+ +--------------------+
|PRT Input 1 | |PRT Input 1 | |PRT Input 1 |
|MTR TMP | |MTR TMP | |MTR TMP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 Deg.C | | 100.000 Deg.C | | 102.00 Deg.C |
|Mode Status: | |Measured Value: | | -2.00 Deg.C |
|KEYPAD-F | | 311.204 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|PRT Channel 1 |
|MTR TMP |
| |
|Resistance: |
| 219099.375 ohms |
| |
| |
+--------------------+

MENU: PLANT I/O|FREQUENCY INPUTS|FREQ 01 - DEN A
+--------------------+
|FREQ Input 1 |
|DEN A |
| |
|Period |
| 0.000 uS |
| |
| |
+--------------------+

MENU: PLANT I/O|FREQUENCY INPUTS|FREQ 02 - DEN B
+--------------------+
|FREQ Input 2 |
|DEN B |
| |
|Period |
| 0.000 uS |
| |
| |
+--------------------+

MENU: PLANT I/O|PULSE INPUTS|PIP 01 - PIP01
+--------------------+ +--------------------+
|Pulse Input 1 | |Pulse Input 1 |
|PIP 01 TURBINE | |PIP 01 TURBINE |
| | | |
|Good Pulse Count: | |Frequency: |
| 0 | | 0 Hz |
|Bad Pulse Count: | | |
| 0 | | |
+--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 365 of 395 Issue 7



MENU: PLANT I/O|DIGITAL I/OS|DIGITAL IO 01
+--------------------+
|Discrete I/O 1 |
|I/O01 DIO 01 |
| |
|Input Status: |
|0000000000000000 |
|Output Status: |
|0000000000000000 |
+--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 01 - FCV
+--------------------+ +--------------------+
|DAC Channel 1 | |DAC Channel 1 |
|FCV | |FCV |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 100.000 | | 100.000 |
| | | 0.000 |
| | |% |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 02 - SAMP LO
+--------------------+ +--------------------+
|DAC Channel 2 | |DAC Channel 2 |
|SAMP LOOP | |SAMP LOOP |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 m3/h | | 10000000.000 m3/h |
| | | 0.000 m3/h |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|DISCREP
+--------------------+
|TEMP DISCREP |
| |
|Value: |
| 5.000 Deg.C |
| |
| |
| |
+--------------------+

MENU: SYSTEM SETTINGS|UNIT SETUP|CONVERSIONS
+--------------------+
|Conversions |
| |
|m3 -> bbl |
| |
|Value: |
| 0.1589873 |
| |
+--------------------+

MENU: SYSTEM SETTINGS|UNIT SETUP|SETUP
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|LIQ MASS UNITS | |LIQ MASS FR UNITS | |LIQ GROSS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|tonne | |t/h | |m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|LIQ GROSS FR UNITS | |LIQ NETT UNITS | |LIQ NETT FR UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|m3/h | |Sm3 | |Sm3/h |
| | | | | |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 366 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+


+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS MASS UNITS | |GAS MASS FR UNITS | |GAS GROSS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|tonne | |t/h | |m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS GROSS FR UNITS | |GAS NETT UNITS | |GAS NETT FR UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|m3/h | |Sm3 | |Sm3/h |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS ENGY UNITS | |GAS ENGY FR UNITS | |PRESS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|GJ | |GJ/h | |barg |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DP UNITS | |TEMP UNITS | |DENS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mbar | |Deg.C | |kg/m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|K-FACTOR UNITS | |CV MASS UNITS | |CV VOL UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|pls/m3 | |MJ/kg | |MJ/Sm3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DYN VISC UNITS | |KIN VISC UNITS | |FREQ UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|cP | |cSt | |Hz |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|LENGTH UNITS | |PERIOD UNITS | |PERCENT UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mm | |uS | |% |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DIAM UNITS | |AREA UNITS | |VEL UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mm | |mm2 | |m/s |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 367 of 395 Issue 7



+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|TIME UNITS | |ROC TEMP UNITS | |ROC PRS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|s | |Deg.C/s | |bar/s |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|REPORT SETUP
+--------------------+ +--------------------+ +--------------------+
|REPORT CONTROL | |REPORT CONTROL | |BASETIME 1 |
|WEEK START | |MONTH START | | |
| | | | | |
|SUNDAY | |FIRST | | 6 |
| | | | | |
| | | | |O-CLOCK |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|ALARM SETUP
+--------------------+ +--------------------+
|ALARM CONTROL | |ALARM CONTROL |
|ALARM MODE | |ALARM ENABLE |
| | | |
|LATCHED | |YES |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|MAINTENANCE MODE
+--------------------+ +--------------------+
| | | |
|SYSTEM MAINT ENAB | |STR01 MAINT MODE |
| | | |
|SET | |CLEAR |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|SYSTEM STATUS
+--------------------+
| |
|SYSTEM RUN MODE |
| |
|NORMAL |
| |
| |
| |
+--------------------+

MENU: SYSTEM SETTINGS|SOFTWARE VERSION
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|CONFIG NAME | |CONFIG FORMAT | |CONFIG VERSION |
| | | | | |
|Helang - Oil Cond | |5 | |163 |
|(NEW TABLES) | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|CONFIG CREATED | |CONFIG LAST EDITED | |CONFIG STRUCTURE |
| | | | | |
|14 Dec 2001. 14:10 | |09 Apr 2003. 15:08 | |CSUM ef27 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 368 of 395 Issue 7



+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|NMI CONSTANTS | |FILE CSUM | |REGISTRATION CODE |
| | | | | |
|AAAA-1111 | |AAAA | |1.3dMAKAWGG20011024P|
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|APPLICATION SW | |PC SETUP PACKAGE | |MAIN BOARD ID |
| | | | | |
|03.24a Jul 19 2002 | |1.3 | |00:A0:D8:FE:0D:89 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 HW_REV | |I/O01 MOD_STRIKE | |I/O01 BOARD SERNO |
| | | | | |
|REV 04 | |MOD E | |SN 06968 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 FIRST CALIB | |I/O01 LAST CALIB | |I/O01 SW VERSION |
| | | | | |
|09052003 | |09052003 | |01.01.16.00 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|VERSION CONTROL |
|I/O01 BOARD ID |
| |

|1.1.1.1.1.2.0 |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|DISPLAY SETUP
+--------------------+
|Display Setup |
| |
|DEF DISP : |
| |
|DISPLAY T/O: 300 s |
|LOGOUT T/O: 20 s |
|IDENT T/O: 120 s |
+--------------------+

MENU: TECH/ENGINEER|CONTRAST
+--------------------+
| |
| |
|CONTRAST : 8 |
| |
| |
| |
| |
+--------------------+





Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 369 of 395 Issue 7



MENU: TECH/ENGINEER|DATE & TIME
+--------------------+ +--------------------+
|Current Date & Time | |Date and Time Format|
| | | |
|07/02/1980 03:01:35 | | |
| | | |
| | |DD MM YYYY |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|DISPLAY TEST
+--------------------+
| |
| |
|DISPLAY TEST |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|SECURITY
+--------------------+ +--------------------+
|Security Setup | |PC Setup Link |
| | | |
|Current Level: | |DISABLED |
|SECURITY : 9 | | |
| | | |
|Front Panel Keypad | | |
|ENABLED | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 01
+--------------------+ +--------------------+ +--------------------+
|COM1 - DISPLAY | |COM1 - DISPLAY | |COM1 - DISPLAY |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM1 - DISPLAY |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 02
+--------------------+ +--------------------+ +--------------------+
|COM2 - PC LINK | |COM2 - PC LINK | |COM2 - PC LINK |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 38400 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM2 - PC LINK |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 370 of 395 Issue 7



MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 03
+--------------------+ +--------------------+ +--------------------+
|COM3 | |COM3 | |COM3 |
| | |GOOD_TX : 39 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 2 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM3 |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 04
+--------------------+ +--------------------+ +--------------------+
|COM4 | |COM4 | |COM4 |
| | |GOOD_TX : 135 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 7 |
|HEALTHY | |BAD_RX : 135 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY EVEN |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM4 |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 05
+--------------------+ +--------------------+ +--------------------+
|COM5 | |COM5 | |COM5 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM5 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION ON |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 06
+--------------------+ +--------------------+ +--------------------+
|COM6 | |COM6 | |COM6 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 371 of 395 Issue 7



+--------------------+
|COM6 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 07
+--------------------+ +--------------------+ +--------------------+
|COM7 | |COM7 | |COM7 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM7 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 08
+--------------------+ +--------------------+ +--------------------+
|COM8 - IO | |COM8 - IO | |COM8 - IO |
| | |GOOD_TX : 4298 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 38400 |
| | |GOOD_RX : 4297 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM8 - IO |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|MODBUS ADDRESS
+--------------------+
|FLOW COMPUTER |
|SLAVE ADDRESS |
|1 |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 03
+--------------------+ +--------------------+
|COMMS TASK 03 | |COMMS TASK 03 |
| | | |
|Port: | |Address: |
|PORT 6 | |0 |
|Protocol: | | |
|MODBUS TCP | | |
| | | |
+--------------------+ +--------------------+


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 372 of 395 Issue 7



MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|PROVER SLAVE LIN
+--------------------+ +--------------------+
|PROVER SLAVE LINK | |PROVER SLAVE LINK |
| | | |
|Port: | |Address: |
|PORT 5 | |0 |
|Protocol: | | |
|RTU SERIAL | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|SLAVE LINK
+--------------------+ +--------------------+
|SLAVE LINK | |SLAVE LINK |
| | | |
|Port: | |Address: |
|PORT 4 | |0 |
|Protocol: | | |
|MODBUS TCP | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 06
+--------------------+ +--------------------+
|COMMS TASK 06 | |COMMS TASK 06 |
| | | |
|Port: | |Address: |
|PORT 6 | |0 |
|Protocol: | | |
|RTU SERIAL | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|COMMS TASK 07
+--------------------+ +--------------------+
|COMMS TASK 07 | |COMMS TASK 07 |
| | | |
|Port: | |Address: |
|PORT 7 | |0 |
|Protocol: | | |
|RTU SERIAL | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|PRINTER
+--------------------+
|PRINTER |
| |
|Port: |
|PORT 3 |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|IP2 (NEW TABLES)|INPUTS
+--------------------+ +--------------------+ +--------------------+
|TEMP CORR TABLE | |PRESS CORR TABLE | |TABLE LIMIT MODE |
| | | | | |
|Status: | |Status: | |Status: |
|T53/54_K0 | |11.2.1M | |ALM/CLAMP |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|ROUNDING CONTROL | |BASE TEMP | |K0 |
| | | | | |
|Status: | |Value: | |Value: |
|DISABLED | | 15.00000000 Deg.C | | 613.97230000 |
| | | | | |
| | | | | |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 373 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+


+--------------------+ +--------------------+ +--------------------+
|K1 | |K2 | |RHO MINIMUM |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 | | 600.00000000 kg/m3 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|RHO MAXIMUM | |OBS DENSITY | |OBS DENSITY |
| | | | | |
|Value: | |In Use Value: | |Keypad Value: |
| 950.00000000 kg/m3 | | 875.500000 kg/m3 | | 875.500000 kg/m3 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DENSITY A TEMP | |DENSITY A TEMP | |DENSITY A PRESS |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 100.00 barg |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|DENSITY A PRESS | |VAPOUR PRESS | |VAPOUR PRESS |
| | | | | |
|Keypad Value: | |In Use Value: | |Keypad Value: |
| 100.00 barg | | 0.000000 barg | | 0.000000 barg |
|Mode Status: | | | |Mode Status: |
|KEYPAD-F | | | |KEYPAD |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|MTR TEMP | |MTR TEMP | |MTR PRESS |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 100.00 barg |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|MTR PRESS |
| |
|Keypad Value: |
| 100.00 barg |
|Mode Status: |
|KEYPAD-F |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|IP2 (NEW TABLES)|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|ALPHA | |ALPHA | |BETA |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 0.000718 | | 0.000010 | | 0.000092 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 0.000718 | |METER | | 0.000092 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BETA | |BETAd | |CTL |
| | | | | |
|Keypad Value: | |Inuse Value: | |Calculated Value: |
| 1.000000000E-06 | | 0.000092 | | 0.938009 |
|Mode Status: | | | |In Use Value: |
|METER | | | | 0.938009 |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 374 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+


+--------------------+ +--------------------+ +--------------------+
|CTL | |CTLd | |CPL |
| | | | | |
|Keypad Value: | |Inuse Value: | |Calculated Value: |
| 1.000000 | | 0.938009 | | 1.009235 |
|Mode Status: | | | |In Use Value: |
|METER | | | | 1.009235 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CPL | |CPLd | |VCF |
| | | | | |
|Keypad Value: | |Inuse Value: | |Calculated Value: |
| 1.000000 | | 1.009235 | | 0.946672 |
|Mode Status: | | | |In Use Value: |
|METER | | | | 0.946672 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VCF | |MTR DENSITY | |MTR DENSITY |
| | | | | |
|Keypad Value: | |Calculated Value: | |Keypad Value: |
| 1.000000 | | 0.000000 kg/m3 | | 900.000000 kg/m3 |
|Mode Status: | |In Use Value: | |Mode Status: |
|METER | | 875.499992 kg/m3 | |METER |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|MTR DENSITY | |STD DENSITY | |STD DENSITY |
| | | | | |
|Limits (H/L) | |Calculated Value: | |Keypad Value: |
| | | 924.819175 kg/m3 | | 800.000000 kg/m3 |
| 900.00 kg/m3 | |In Use Value: | |Mode Status: |
| 500.00 kg/m3 | | 924.819175 kg/m3 | |STD 15 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STD DENSITY | |T53 DIAGNOSTIC | |T54 DIAGNOSTIC |
| | | | | |
|Limits (H/L) | |Value: | |Value: |
| | | 77 | | 7 |
| 900.00 kg/m3 | | | | |
| 500.00 kg/m3 | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: CALCULATIONS|STREAM 1|METER CORR|INPUTS
+--------------------+ +--------------------+ +--------------------+
|MTR PRESS | |MTR PRESS | |MTR TEMP |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 barg | | 100.00 barg | | 100.00 Deg.C |
| | |Mode Status: | | |
| | |KEYPAD-F | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|MTR TEMP | |PROVED PRESS | |PROVED TEMP |
| | | | | |
|Keypad Value: | |Value: | |Value: |
| 100.00 Deg.C | | 20.00000000 barg | | 15.00000000 Deg.C |
|Mode Status: | | | | |
|KEYPAD-F | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|METER TEMP EXP COEF | |ROTOR TEMP EXP COEF | |SPOOL RADIUS |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 | | 1.00000000 mm |
| | | | | |
| | | | | |
| | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 375 of 395 Issue 7
+--------------------+ +--------------------+ +--------------------+



+--------------------+ +--------------------+ +--------------------+
|SPOOL WALL THICKNESS| |METER ROTOR AREA | |MODULUS ELASTICITY |
| | | | | |
|Value: | |Value: | |Value: |
| 1.00000000 mm | | 0.00000000 mm2 | | 2100000.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|POISSON RATIO |
| |
|Value: |
| 0.27000000 |
| |
| |
| |
+--------------------+

MENU: CALCULATIONS|STREAM 1|METER CORR|OUTPUTS
+--------------------+ +--------------------+ +--------------------+
|CTSm | |CTSm | |CPSm |
| | | | | |
|Calculated Value: | |Keypad Value: | |Calculated Value: |
| 1.000000 | | 1.000000 | | 1.000066 |
|In Use Value: | |Mode Status: | |In Use Value: |
| 1.000000 | |KEYPAD | | 1.000000 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|CPSm |
| |
|Keypad Value: |
| 1.000000 |
|Mode Status: |
|KEYPAD |
| |
+--------------------+



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 376 of 395 Issue 7
20.S Prover
MENU: OPERATOR|STATION 1|SEQUENCE CTL
+--------------------+ +--------------------+ +--------------------+
|SEQ CTL | |SEQ STREAM NO. | |SEQ STAGE INDEX |
| | | | | |
|Status: | |Value: | |Value: |
|NOT_ACTND | | 0 | | 0 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|SEQ STAGE PREV | |SEQ ABORT INDEX |
| | | |
|Value: | |Value: |
| 0 | | 0 |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|PROVER I/O
+--------------------+ +--------------------+ +--------------------+
|RAW PULSE BUS FREQ | |PRV.I/L PRESS | |PRV.I/L PRESS |
| | | | | |
|Frequency: | |In Use Value: | |Keypad Value: |
| 0 Hz | | 100.00 barg | | 100.00 barg |
| | | | |Mode Status: |
| | | | |KEYPAD |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PRV.O/L PRESS | |PRV.O/L PRESS | |PRV.I/L TEMP |
| | | | | |
|In Use Value: | |Keypad Value: | |In Use Value: |
| 100.00 barg | | 100.00 barg | | 100.00 Deg.C |
| | |Mode Status: | | |
| | |KEYPAD | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PRV.I/L TEMP | |PRV.O/L TEMP | |PRV.O/L TEMP |
| | | | | |
|Keypad Value: | |In Use Value: | |Keypad Value: |
| 100.00 Deg.C | | 100.00 Deg.C | | 100.00 Deg.C |
|Mode Status: | | | |Mode Status: |
|KEYPAD | | | |KEYPAD |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PRV SPHERE SWITCHES | |PIO FLIGHT TIME | |PIO PULSE COUNT |
| | | | | |
|SS1/SS2/SS3/SS4: | |BASE VOL 1/2/3/4: | |BASE VOL 1/2/3/4: |
|CLEAR | | 0.0000 s | | 0.0000 |
|CLEAR | | 0.0000 s | | 0.0000 |
|CLEAR | | 0.0000 s | | 0.0000 |
|CLEAR | | 0.0000 s | | 0.0000 |
+--------------------+ +--------------------+ +--------------------+
MENU: OPERATOR|STREAM 1|SEQ CONTROL
+--------------------+ +--------------------+ +--------------------+
|SEQ CONTROL | |SEQ STREAM NO. | |BASE VOL INDEX: |
| | | | | 1 |
|Status: | |Value: | | |
|NOT_ACTND | | 0 | |BASE VOL INUSE: |
| | | | | 10.00000000 m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|STABILITY OVERRIDE: | |RUN PERMIT | |RUN CONTROL |
|DISABLED | | | | |
| | |Value: | |Status: |
|STABILITY STATUS: | | 0 | |NOT_ACTND |
|CLEAR | | | | |
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 377 of 395 Issue 7
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 378 of 395 Issue 7

MENU: OPERATOR|STREAM 1|SEQ DIAGS
+--------------------+ +--------------------+ +--------------------+
|SEQ STAGE INDEX: | |SEQ ABORT INDEX: | |TRIAL NUMBER |
| 0 | | 0 | | |
|RUN STAGE INDEX: | | | |Value: |
| 0 | |RUN ABORT INDEX: | | 0 |
|TRIAL NUMBER: | | 0 | | |
| 0 | |RUN CALC INDEX: | | |
| | | 0 | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|PROVER CONSTANTS
+--------------------+ +--------------------+ +--------------------+
|REFERENCE PRS | |REFERENCE TMP | |PIPE DIAMETER |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 barg | | 15.00000000 Deg.C | | 182.62600000 mm |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|M.ELASTICITY | |WALL T/NESS | |TUBE COEFF |
| | | | | |
|Value: | |Value: | |Value: |
| 3.000000000E+07 | | 18.28800000 mm | | 0.00010000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|INTERP FACTOR | |BASE VOL 1 | |BASE VOL 2 |
| | | | | |
|Value: | |Value: | |Value: |
| 1.00000000 | | 0.55497500 Sm3 | | 0.54978600 Sm3 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|BASE VOL 3 | |BASE VOL 4 | |PRE SW VOL FWD |
| | | | | |
|Value: | |Value: | |Value: |
| 0.56811600 Sm3 | | 0.53664200 Sm3 | | 0.20000000 Sm3 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PRE SW VOL RVS | |STAB WAIT TIME | |STAB HOLD TIME |
| | | | | |
|Value: | |Value: | |Value: |
| 0.20000000 Sm3 | | 60 | | 10 |
| | |seconds | |seconds |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|RUN DELAY TIME | |REQUIRED RUNS | |MAXIMUM RUNS |
| | | | | |
|Value: | |Value: | |Value: |
| 5 | | 5 | | 12 |
|seconds | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|KF TOLERANCE | |TMP R.O.C. | |PRS R.O.C. |
| | | | | |
|Value: | |Value: | |Value: |
| 1.00000000 % | | 0.10000000 Deg.C/s | | 0.05000000 bar/s |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 379 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|TMP BAND | |PRS BAND | |F/R R.O.C. |
| | | | | |
|Value: | |Value: | |Value: |
| 1.00000000 Deg.C | | 0.50000000 barg | | 10.00000000 |
| | | | |m3/h |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|STREAM DATA
+--------------------+ +--------------------+ +--------------------+
|M.PRS | |M.TMP | |M.VAP PRS |
| | | | | |
|Value: | |Value: | |Value: |
| 20.00000000 barg | | 15.00000000 Deg.C | | 0.01000000 barg |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|M.STD DENS | |M.GVOL F/R | |M.K FACTOR |
| | | | | |
|Value: | |Value: | |Value: |
| 700.00000000 kg/m3 | | 0.00000000 m3/h | | 0.00000000 pls/m3 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|M.K0 | |M.K1 | |M.K2 |
| | | | | |
|Value: | |Value: | |Value: |
| 613.97230000 | | 0.00000000 | | 0.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|M.CTSM | |M.CPSM |
| | | |
|Value: | |Value: |
| 0.00000000 | | 0.00000000 |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|HALF RUN DATA
+--------------------+ +--------------------+
|HALF PULSES | |HALF F/TIME |
| | | |
|Value: | |Value: |
| 0.00000000 | | 0.00000000 s |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: OPERATOR|STREAM 1|FULL RUN DATA
+--------------------+ +--------------------+ +--------------------+
|FULL PULSES | |FULL PULSES | |FULL F/TIME |
| | | | | |
|In Use Value: | |Limits (H/L) | |Value: |
| 0.000000 | | | | 0.00000000 s |
| | | 28000.00 | | |
| | | 2000.00 | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 380 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|FULL M.PRS | |FULL M.TMP | |FULL M.VAP PRS |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 barg | | 0.00000000 Deg.C | | 0.00000000 barg |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FULL M.STD DNS | |FULL P.PRS | |FULL P.TMP |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 kg/m3 | | 0.00000000 barg | | 0.00000000 Deg.C |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FULL M.CTSM | |FULL M.CPSM | |FULL K FACTOR |
| | | | | |
|Value: | |Value: | |In Use Value: |
| 0.00000000 | | 0.00000000 | | 0.000000 pls/m3 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FULL K FACTOR | |FULL FREQ | |FULL CPSP |
| | | | | |
|Limits (H/L) | |Value: | |Value: |
| | | 0.00000000 Hz | | 0.00000000 |
| 14000.00 pls/m3 | | | | |
| 0.00 pls/m3 | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FULL CTSP | |FULL BETAM | |FULL BETAP |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FULL CPLP | |FULL CPLM | |FULL ALPHA |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FULL CTLP | |FULL CTLM | |FULL CORR VOL |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 | | 0.00000000 Sm3 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FULL F/RATE | |FULL MTR FACTOR | |FULL MTR FACTOR |
| | | | | |
|Value: | |In Use Value: | |Limits (H/L) |
| 0.00000000 Sm3/h | | 0.000000 | | |
| | | | | 1.10 |
| | | | | 0.50 |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 381 of 395 Issue 7

MENU: OPERATOR|STREAM 1|FINAL RUN DATA
+--------------------+ +--------------------+ +--------------------+
|FINAL PULSES | |FINAL F/TIME | |FINAL M.PRS |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 s | | 0.00000000 barg |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FINAL M.TMP | |FINAL M.VAP PRS | |FINAL M.STD DNS |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 Deg.C | | 0.00000000 barg | | 0.00000000 kg/m3 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FINAL P.PRS | |FINAL P.TMP | |FINAL M.CTSM |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 barg | | 0.00000000 Deg.C | | 0.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FINAL M.CPSM | |FINAL K FACTOR | |FINAL FREQ |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 pls/m3 | | 0.00000000 Hz |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FINAL CPSP | |FINAL CTSP | |FINAL BETAM |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FINAL BETAP | |FINAL CPLP | |FINAL CPLM |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FINAL ALPHA | |FINAL CTLP | |FINAL CTLM |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 | | 0.00000000 | | 0.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|FINAL CORR VOL | |FINAL F/RATE | |FINAL RPTBLTY |
| | | | | |
|Value: | |Value: | |Value: |
| 0.00000000 Sm3 | | 0.00000000 Sm3/h | | 0.00000000 % |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 382 of 395 Issue 7

+--------------------+
|FINAL M.FAC |
| |
|Value: |
| 0.00000000 |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|4WAY VALVE
+--------------------+ +--------------------+ +--------------------+
|4-WAY POSN | |4-WAY TRAVEL TIME | |4-WAY SETTLE TIME |
| | | | | |
|Status: | |Value: | |Value: |
|ILLEGAL | | 60 | | 30 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|4-WAY TEST TIME | |4-WAY REMOTE | |4-WAY SEALED |
| | | | | |
|Value: | |Status: | |Status: |
| 120 | |CLEAR | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|4-WAY SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|OUTLET VALVE 1
+--------------------+ +--------------------+ +--------------------+
|O-VLV 1 POSN | |O-VLV 1 TRAVEL TIME | |O-VLV 1 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 60 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|O-VLV 1 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|STREAM 1|VALVES|OUTLET VALVE 2
+--------------------+ +--------------------+ +--------------------+
|O-VLV 2 POSN | |O-VLV 2 TEST TIME | |O-VLV 2 REMOTE |
| | | | | |
|Status: | |Value: | |Status: |
|ILLEGAL | | 120 | |CLEAR |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 383 of 395 Issue 7

+--------------------+
|O-VLV 2 SIMULATE |
| |
|Status: |
|DISABLED |
| |
| |
| |
+--------------------+

MENU: OPERATOR|IO BOARD 1|I/O01 PID LOOP 1
+--------------------+ +--------------------+ +--------------------+
|AUTO/MAN MODE | |DIRECTION | |SETPOINT TRACKING |
| | | | | |
|Status: | |Status: | |Status: |
|MANUAL | |REVERSE | |ON |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|CLAMPING | |SLEW LIMIT | |RAMP RATE |
| | | | | |
|Status: | |Value: | |Value: |
|ON | | 60.00000000 | | 0.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|MANUAL POSITION | |SETPOINT | |PV RANGE |
| | | | | |
|Value: | |Value: | |Value: |
| 100.00000000 % | | 0.00000000 | | 2000.00000000 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|PROPORTIONAL BAND | |INTEGRAL TIME | |DERIVATIVE TIME |
| | | | | |
|Value: | |Value: | |Value: |
| 50.00000000 | | 0.00000000 s | | 0.00000000 s |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|OUTPUT POSITION |
| |
|Value: |
| 0.00000000 % |
| |
| |
| |
+--------------------+
MENU: PLANT I/O|ANALOG INPUTS|ADC 01 - IN PRS
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 1 | |ADC Channel 1 | |ADC Channel 1 |
|IN PRS | |IN PRS | |IN PRS |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 barg | | 100.000 barg | | 102.00 barg |
|Mode Status: | |Measured Value: | | -2.00 barg |
|KEYPAD | | -24.998 barg | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 1 | |ADC Channel 1 |
|IN PRS | |IN PRS |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 3.79951467E-04 mA | | 100.000 barg |
| | | 0.000 barg |
| | | |
+--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 384 of 395 Issue 7

MENU: PLANT I/O|ANALOG INPUTS|ADC 02 - OUT PRS
+--------------------+ +--------------------+ +--------------------+
|ADC Channel 2 | |ADC Channel 2 | |ADC Channel 2 |
|OUT PRS | |OUT PRS | |OUT PRS |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 barg | | 100.000 barg | | 102.00 barg |
|Mode Status: | |Measured Value: | | -2.00 barg |
|KEYPAD | | -24.996 barg | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|ADC Channel 2 | |ADC Channel 2 |
|OUT PRS | |OUT PRS |
| | |HIGH AND LOW SCALE |
|Current: | | |
| 6.54558185E-04 mA | | 100.000 barg |
| | | 0.000 barg |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|PRT/RTD INPUTS|PRT 01 - IN TMP
+--------------------+ +--------------------+ +--------------------+
|PRT Input 1 | |PRT Input 1 | |PRT Input 1 |
|IN TMP | |IN TMP | |IN TMP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 Deg.C | | 100.000 Deg.C | | 102.00 Deg.C |
|Mode Status: | |Measured Value: | | -2.00 Deg.C |
|KEYPAD | | 311.204 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|PRT Channel 1 |
|IN TMP |
| |
|Resistance: |
| 17859.359 ohms |
| |
| |
+--------------------+

MENU: PLANT I/O|PRT/RTD INPUTS|PRT 02 - OUT TMP
+--------------------+ +--------------------+ +--------------------+
|PRT Input 2 | |PRT Input 2 | |PRT Input 2 |
|OUT TMP | |OUT TMP | |OUT TMP |
| | | | |Limits (H/L) |
|In Use Value: | |Keypad Value: | | |
| 100.000 Deg.C | | 100.000 Deg.C | | 102.00 Deg.C |
|Mode Status: | |Measured Value: | | -2.00 Deg.C |
|KEYPAD | | -100.627 Deg.C | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|PRT Channel 2 |
|OUT TMP |
| |
|Resistance: |
| 0.000 ohms |
| |
| |
+--------------------+

MENU: PLANT I/O|DIGITAL I/OS|DIGITAL IO 01
+--------------------+
|Discrete I/O 1 |
|I/O01 DIO 01 |
| |
|Input Status: |
|0000000000000000 |
|Output Status: |
|0000000000000000 |
+--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 385 of 395 Issue 7

MENU: PLANT I/O|DIGITAL I/OS|DIGITAL IO 02
+--------------------+
|Discrete I/O 2 |
|I/O02 DIO 01 |
| |
|Input Status: |
|0000000000000000 |
|Output Status: |
|0000000000000000 |
+--------------------+

MENU: PLANT I/O|DIGITAL I/OS|DIGITAL IO 03
+--------------------+
|Discrete I/O 3 |
|I/O02 DIO 02 |
| |
|Input Status: |
|0000000000000000 |
|Output Status: |
|0000000000000000 |
+--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 01 - DAC01
+--------------------+ +--------------------+
|DAC Channel 1 | |DAC Channel 1 |
|I/O01 DAC 01 | |I/O01 DAC 01 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 100.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 02 - DAC02
+--------------------+ +--------------------+
|DAC Channel 2 | |DAC Channel 2 |
|I/O01 DAC 02 | |I/O01 DAC 02 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 03 - DAC03
+--------------------+ +--------------------+
|DAC Channel 3 | |DAC Channel 3 |
|I/O01 DAC 03 | |I/O01 DAC 03 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+

MENU: PLANT I/O|ANALOG OUTPUTS|DAC 04 - DAC04
+--------------------+ +--------------------+
|DAC Channel 4 | |DAC Channel 4 |
|I/O01 DAC 04 | |I/O01 DAC 04 |
| | | |
|Output Value: | |Hi & Lo Scale Values|
| 0.000 | | 10000000.000 |
| | | 0.000 |
| | | |
+--------------------+ +--------------------+
MENU: PLANT I/O|PROVER SWITCHES|PRV 01
+--------------------+
|Prove Control 1 |
| |
| |
|Switch status |
|0000 |
| |
| |
+--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 386 of 395 Issue 7

MENU: SYSTEM SETTINGS|UNIT SETUP|CONVERSIONS
+--------------------+ +--------------------+ +--------------------+
|Conversion Factor | |Conversion Factor | |Conversion Factor |
|lb - kg | |tonne - US ton | |Bar. press (Bar) |
| | | | | |
|Value: | |Value: | |Value: |
| 0.45359240 | | 1.10231136 | | 1.01325000 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Conversion Factor | |Conversion Factor | |Conversion Factor |
|Bar. press (psi) | |bar - kPa | |bar - psi |
| | | | | |
|Value: | |Value: | |Value: |
| 14.73000000 | | 100.00000000 | | 14.50377439 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Conversion Factor | |Conversion Factor | |Conversion Factor |
|bar - in H2O (@60F) | |Deg.C - K | |m3 - bbl |
| | | | | |
|Value: | |Value: | |Value: |
| 401.86465200 | | 273.15000000 | | 6.28981057 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Conversion Factor | |Conversion Factor | |Conversion Factor |
|m3 - cf | |Btu - J | |cst - mm2s |
| | | | | |
|Value: | |Value: | |Value: |
| 35.31466247 | | 1055.05600000 | | 1.00000000 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|UNIT SETUP|SETUP
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|LIQ MASS UNITS | |LIQ MASS FR UNITS | |LIQ GROSS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|tonne | |t/h | |m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|LIQ GROSS FR UNITS | |LIQ NETT UNITS | |LIQ NETT FR UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|m3/h | |Sm3 | |Sm3/h |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS MASS UNITS | |GAS MASS FR UNITS | |GAS GROSS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|tonne | |t/h | |m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS GROSS FR UNITS | |GAS NETT UNITS | |GAS NETT FR UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|m3/h | |Sm3 | |Sm3/h |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 387 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|GAS ENGY UNITS | |GAS ENGY FR UNITS | |PRESS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|GJ | |GJ/h | |barg |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DP UNITS | |TEMP UNITS | |DENS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mbar | |Deg.C | |kg/m3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|K-FACTOR UNITS | |CV MASS UNITS | |CV VOL UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|pls/m3 | |MJ/kg | |MJ/Sm3 |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DYN VISC UNITS | |KIN VISC UNITS | |FREQ UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|cP | |cSt | |Hz |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|LENGTH UNITS | |PERIOD UNITS | |PERCENT UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mm | |uS | |% |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|DIAM UNITS | |AREA UNITS | |VEL UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|mm | |mm2 | |m/s |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|Unit Setup | |Unit Setup | |Unit Setup |
|TIME UNITS | |ROC TEMP UNITS | |ROC PRS UNITS |
| | | | | |
|Selected Unit: | |Selected Unit: | |Selected Unit: |
|s | |Deg.C/s | |bar/s |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|REPORT SETUP
+--------------------+ +--------------------+ +--------------------+
|REPORT CONTROL | |REPORT CONTROL | |BASETIME 1 |
|WEEK START | |MONTH START | | |
| | | | | |
|SUNDAY | |FIRST | | 6 |
| | | | | |
| | | | |O-CLOCK |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 388 of 395 Issue 7

+--------------------+ +--------------------+
|BASETIME 2 | |BASETIME 3 |
| | | |
| | | |
| 12 | | 18 |
| | | |
|O-CLOCK | |O-CLOCK |
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|ALARM SETUP
+--------------------+ +--------------------+
|ALARM CONTROL | |ALARM CONTROL |
|ALARM MODE | |ALARM ENABLE |
| | | |
|LATCHED | |YES |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: SYSTEM SETTINGS|MAINTENANCE MODE
+--------------------+
| |
|SYSTEM MAINT ENAB |
| |
|SET |
| |
| |
| |
+--------------------+

MENU: SYSTEM SETTINGS|SYSTEM STATUS
+--------------------+
| |
|SYSTEM RUN MODE |
| |
|NORMAL |
| |
| |
| |
+--------------------+

MENU: SYSTEM SETTINGS|SOFTWARE VERSION
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|CONFIG NAME | |CONFIG FORMAT | |CONFIG VERSION |
| | | | | |
|Helang - Prover | |5 | |67 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|CONFIG CREATED | |CONFIG LAST EDITED | |CONFIG STRUCTURE |
| | | | | |
|21 Nov 2001. 10:21 | |10 Jun 2002. 17:58 | |CSUM f809 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|NMI CONSTANTS | |FILE CSUM | |REGISTRATION CODE |
| | | | | |
|AAAA-1111 | |AAAA | |1.3dMAKAWGG20011024P|
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 389 of 395 Issue 7

+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|APPLICATION SW | |PC SETUP PACKAGE | |MAIN BOARD ID |
| | | | | |
|03.20 May 14 2002 | |1.3 | |00:A0:D8:FE:0E:6B |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 HW_REV | |I/O01 MOD_STRIKE | |I/O01 BOARD SERNO |
| | | | | |
|REV 04 | |MOD D | |SN 07354 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 FIRST CALIB | |I/O01 LAST CALIB | |I/O01 SW VERSION |
| | | | | |
|10082001 | |10082001 | |01.01.16.00 |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O01 BOARD ID | |I/O02 HW_REV | |I/O02 MOD_STRIKE |
| | | | | |
|1.1.1.1.1.2.0 | |UNAVAILABLE | |UNAVAILABLE |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL | |VERSION CONTROL |
|I/O02 BOARD SERNO | |I/O02 FIRST CALIB | |I/O02 LAST CALIB |
| | | | | |
|UNAVAILABLE | |UNAVAILABLE | |UNAVAILABLE |
| | | | | |
| | | | | |
| | | | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+ +--------------------+
|VERSION CONTROL | |VERSION CONTROL |
|I/O02 SW VERSION | |PRV02 BOARD ID |
| | | |
|UNAVAILABLE | |UNAVAILABLE |
| | | |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|DISPLAY SETUP
+--------------------+
|Display Setup |
| |
|DEF DISP : |
| |
|DISPLAY T/O: 300 s |
|LOGOUT T/O: 20 s |
|IDENT T/O: 120 s |
+--------------------+
MENU: TECH/ENGINEER|CONTRAST
+--------------------+
| |
| |
|CONTRAST : 8 |
| |
| |
| |
| |
+--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 390 of 395 Issue 7

MENU: TECH/ENGINEER|DATE & TIME
+--------------------+ +--------------------+
|Current Date & Time | |Date and Time Format|
| | | |
|04/07/1980 00:12:44 | | |
| | | |
| | |DD MM YYYY |
| | | |
| | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|DISPLAY TEST
+--------------------+
| |
| |
|DISPLAY TEST |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|SECURITY
+--------------------+ +--------------------+
|Security Setup | |PC Setup Link |
| | | |
|Current Level: | |DISABLED |
|SECURITY : 9 | | |
| | | |
|Front Panel Keypad: | | |
|ENABLED | | |
+--------------------+ +--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 01
+--------------------+ +--------------------+ +--------------------+
|COM1 - DISPLAY | |COM1 - DISPLAY | |COM1 - DISPLAY |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM1 - DISPLAY |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 02
+--------------------+ +--------------------+ +--------------------+
|COM2 - PC LINK | |COM2 - PC LINK | |COM2 - PC LINK |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 38400 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM2 - PC LINK |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 391 of 395 Issue 7

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 03
+--------------------+ +--------------------+ +--------------------+
|COM3 | |COM3 | |COM3 |
| | |GOOD_TX : 11 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM3 |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 04
+--------------------+ +--------------------+ +--------------------+
|COM4 | |COM4 | |COM4 |
| | |GOOD_TX : 69 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 9600 |
| | |GOOD_RX : 0 | |DATA BITS 7 |
|HEALTHY | |BAD_RX : 69 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY EVEN |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM4 |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 05
+--------------------+ +--------------------+ +--------------------+
|COM5 | |COM5 | |COM5 |
| | |GOOD_TX : 10 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|RX FAIL | |BAD_RX : 9 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM5 |
| |
|HANDSHAKE NONE |
|DTR CONTROL ON |
|DETERMINATION ON |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 06
+--------------------+ +--------------------+ +--------------------+
|COM6 | |COM6 | |COM6 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 392 of 395 Issue 7

+--------------------+
|COM6 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 07
+--------------------+ +--------------------+ +--------------------+
|COM7 | |COM7 | |COM7 |
| | |GOOD_TX : 0 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 19200 |
| | |GOOD_RX : 0 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 0 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY NONE |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM7 |
| |
|HANDSHAKE HW |
|DTR CONTROL ON |
|DETERMINATION OFF |
| |
|ACCEPT |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|SERIAL PORTS|PORT 08
+--------------------+ +--------------------+ +--------------------+
|COM8 - IO | |COM8 - IO | |COM8 - IO |
| | |GOOD_TX : 808690 | | |
|Link Status | |BAD_TX : 0 | |BAUD RATE 38400 |
| | |GOOD_RX : 808685 | |DATA BITS 8 |
|HEALTHY | |BAD_RX : 4 | |STOP BITS 1 |
| | |CSUM_ERR: 0 | |PARITY ODD |
| | |ADDR_ERR: 0 | | |
+--------------------+ +--------------------+ +--------------------+
+--------------------+
|COM8 - IO |
| |
|HANDSHAKE NONE |
|DTR CONTROL OFF |
|DETERMINATION OFF |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|MODBUS ADDRESS
+--------------------+
|FLOW COMPUTER |
|SLAVE ADDRESS |
|2 |
| |
| |
| |
| |
+--------------------+

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|PROVER MASTER LI
+--------------------+
|PROVER MASTER LINK |
| |
|Port: |
|PORT 5 |
|Protocol: |
|RTU SERIAL |
| |
+--------------------+

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 393 of 395 Issue 7

MENU: TECH/ENGINEER|COMMUNICATIONS|ASSIGNMENT|PRINTER
+--------------------+
|PRINTER |
| |
|Port: |
|PORT 3 |
| |
| |
| |
+--------------------+


Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 394 of 395 Issue 7



Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 395 of 395 Issue 7

Alderley
Controls

k:\1614 helang gas & condensate\documents\fdsasbuiltfinal2.doc
M1914 Helang Metering

Page 396 of 395 Issue 7
2J APPLNDIX
2J.J Supervisory Displays
The Supervisory displays are contained on a CD attached to this document.

2J.2 Calculation Ilowcharts
The following calculation flowcharts are attached:

M1914FL/01 Gas Export Calculation Flowchart

M1914FL/02 Gas Back Up Calculation Flowchart

M1914FL/03 Gas Buy Back Calculation Flowchart

M1914FL/04 Prover Calculation Flowchart