FlowBar High Capacity Slot Diffusers


Model HT (High Throw) Model JT (Jet Throw)

l l

HT and JT 25mm, 38mm or 51mm slot widths Ceiling or Sidewall Applications Modular or Continuous Lengths Curved Sections Corner Pieces Adjustable Discharge Pattern Concealed Fixing Matching Plenum Boxes

l l l l l l l

A!* D!ff-+!'&

T e*e2+ a %-c b!gge* (!c,-*e ,' be f'-&d a, R-+#!& A!* Ma&age%e&,.


R-+#!& A!* Ma&age%e&, ac,!'&a!* A!* D!ff-+!'& &ac'

www.air-diffusion.co.uk

FlowBar High Capacity Slot Diffusers

FlowBar Linear Slot Diffusers

FlowBar is a registered trademark of Air Systems Components, INC,

FlowBar High Capacity Slot Diffusers

Contents
Page Introduction Diffuser Specification Air Patterns Flange Styles Corner Sections Performance Data Standard Fixing Details Dimensions - Diffuser Installation Details Ordering Information - Diffusers Plenum Boxes Dimensions - Plenum Boxes Order Information - Plenum Boxes Page 4 Page 5 Page 6 Page 7 Page 8 Page 9 - 14 Page 15 Page 16 - 17 Page 18 - 20 Page 21 Page 22 Page 23 - 24 Page 25

A!* D!ff-+!'&

FlowBar High Capacity Slot Diffusers

Introduction
Air Diffusions FlowBar is an architecturally designed high capacity linear slot diffuser. It is designed to combine a very high air handling capacity with maximum flexibility and is suitable for either ceiling or sidewall applications. The flexibility of the system can blend into a design or provide contrast with its striking but simple design. FlowBar is a flexible system that can provide straight lines or curves to blend with other architectural elements and enhance the overall concept of the project. FlowBar Key Features Ceiling Mounted High Throw

High capacity single slot diffuser


available in three slot widths of 25mm, 38mm and 51mm.

Surface mounted and plasterframe


border frames available.

Choice of HT (High Throw) series


horizontal or JT (Jet Throw) series vertical air patterns.

Options include:
- Mitred corners, curved, tee and cross piece sections.

Ceiling or Sidewall Applications Modular or Continuous Lengths Curved Sections Corner Pieces Adjustable Discharge Pattern Concealed Fixing Matching Plenum Boxes

Wall Mounted Jet Throw

FlowBar High Capacity Slot Diffusers

Specification Diffuser Model High Throw (HT) Series


Models: - FL-10-HT 25mm slot Models: - FL-15-HT

38mm slot
Models: - FL-20-HT

Integral pattern controllers are 600mm in length allowing the airstream to be directed left and right for horizontal and vertical airflow. Standard slot sizes are
25mm,38mm and 51mm with single section lengths available up to 2400mm.

51mm slot The FlowBar HT series is


primarily designed for ceiling applications and allows the air diffuser to become inconspicuous, whilst fully integrating in to the ceiling system.

Frame styles 66 (surface


mounted) and 22 (plasterframe border) are available as standard. (Other frame/border style options are available)

The FlowBar systems satisfy


both the Architects and Engineers requirements for designing an air distribution system that will maintain optimum room air conditions whilst being efficient yet inconspicuous.

Factory engineered plenum


boxes are supplied to ensure a trouble free installation and that stated catalogue performance data is met.

Specification Diffuser Model Jet Throw (JT) Series


Models:- FL-10-JT

25mm Slot
Models:- FL-15-JT 38mm Slot Models:- FL-20-JT 51mm Slot

Jet Throw pattern controllers allow extended throws in typical high bay applications for heated and/or cooled air. Jet Throw pattern controllers are useful along perimeter walls where heated air can be directed downward. Standard slot sizes are
25mm, 38mm and 51mm with single section lengths available up to 2400mm.

The FlowBar JT series have


Jet Throw pattern flow controllers to allow the airstream to be jetted in a horizontal direction (sidewall mounted) whilst fully integrating into the wall system.

The FlowBar systems


satisfies both the architectural and engineering requirements for design of an air distribution system that will maintain optimum room air conditions whilst becoming an integral component of the architectural concept of the project.

Frame styles 66 (surface


mounted) and 22 (plasterframes) are available as standard (other frame/border styles options are available).

Factory engineered plenum


boxes are supplied to ensure a trouble free installation and that stated catalogue performance data is met

Integral pattern controllers


are 600mm in length allow the airstream to be directed left or right (ceiling application) and up and down (sidewall application)

A!* D!ff-+!'&

FlowBar High Capacity Slot Diffusers

Air Patterns
Model High Throw (HT) Ceiling Mounted

Horizontal Left

Horizontal Right

Vertical

Model Jet Throw (JT) Sidewall Mounted

Horizontal

Upward

Downward

FlowBar High Capacity Slot Diffusers

Flange Styles
Standard Types 66 and 22

Type 66 (Standard) Surface Mounting

Type 22 (Standard) Plaster Frame

Standard Type 22 Plaster Frame Installation


Tape and Fill

Optional H3 Hard Ceiling Clip

Tape and Fill

A!* D!ff-+!'&

FlowBar High Capacity Slot Diffusers

Corner Sections
90 Mitred Corner Multidirection Supply

All dimensions shown are in mm

T
T

90

* Specify Angle
T

Crosspiece

Curved Supply

NB: HT Active Curved Section JT Non Active Dummy Section only


T

B
C * B

* Specify Radius (minimum radius 2.7 metre)

B = Overall width T = Overall length C = Overall Arc length L = Slot width A = 127mm Minimum
90 Mitred Corner Slot/Style Border 66 Border 22 Border 66 Border 22 Width 38mm 38mm 51mm 51mm T 200 200 200 200 B 121 133 146 158 Multidirection Supply Slot/Style Border 66 Border 22 Border 66 Border 22 Width 38mm 38mm 51mm 51mm T 200 200 200 200 B 121 133 146 158

All above configurations available with Type 66 (Surface) and Type 22 (Plaster) flanges.
Crosspiece Slot/Style Border 66 Border 22 Border 66 Border 22 Width 38mm 38mm 51mm 51mm T 400 Not 400 Not B A 120 140 Available 146 127 Available

L B

FlowBar High Capacity Slot Diffusers

FlowBar Slot Diffuser Performance Data - High Throw (HT)


FlowBar with Continuous Slot Plenum - High Throw (HT) - Data based on active section 1200 long FL-10
25mm Slot Width 1 - Slot

Air Flow, l/s-m 36 Static Pressure, Pa 7 NC (Noise Criteria) < 10 Throw, m 1.5 - 2.5 - 4.3

58 18 16 2.8 - 4 - 5.5

79 101 122 34 55 81 26 33 39 3.8 - 4.5 - 6.5 4.3 - 5.3 - 7.3 4.5 - 5.8 - 8.3

144 112 44 5.3 - 6 - 8.8

165 148 49 5.5 - 6.8 - 9.5

FL-15
38mm Slot Width 1 - Slot

Air Flow, l/s-m Static Pressure, Pa NC (Noise Criteria) Throw, m

43 8 <10 1.8 - 3 - 5

65 18 14 3 - 4.3 - 5.8

86 32 24 4 - 5 - 6.8

108 129 51 73 31 37 4.3 - 5.5 - 7.5 5 - 5.8 - 8.3

151 173 99 129 42 48 5.3 - 6.5 - 8.8 5.5 - 6.8 - 9.8

FL-20
51mm Slot Width 1 - Slot

Air Flow, l/s-m Static Pressure, Pa NC (Noise Criteria) Throw, m

43 5 <10 1.5 - 2.8 - 5

72 14 11 2.8 - 4.3 - 6

101 28 22 4 - 5.3 - 7.3

129 46 30 5 - 5.8 - 8.3

158 68 36 5.3 - 6.5 - 9.3

187 95 41 5.8 - 7 - 10

216 127 46 6 - 7.5 - 10.8

Table A. NC Correction for Length Length, mm 600 1200 Supply 3 0 Return 0 +3

1800 +2 +5

2400 +3 +6

3000 +5 +8

Table B. Correction Multiplier for Length Length, mm 600 1200 2400 Throw Correction 0.72 1 1.5

3000 1.7

3600 1.8

All pressures are given in Pascal (Pa) Pressure loss data assumes a duct velocity less than 4 m/sec in the inlet duct Isothermal throw values are given for terminal velocities of .8, .5, and .3 m/sec. Throw data are based on active sections 1200mm active section. For a 600mm section, the throw values are 0.72 times those shown. For a 3000mm continuous length, the throw values are 1.7 times those shown, 1.8 for 3600mm units. Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10 -12 Watts, for a 1200mm section. (See Table A for other lengths.) For supply units used as a return, add 3 NC.

The tests were conducted with no Plenum effect for pressure or sound. Throw values for High Throw units are based on a 1-way discharge from the slot. Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slots.

A!* D!ff-+!'&

FlowBar High Capacity Slot Diffusers

FlowBar Slot Diffuser Performance Data - High Throw (HT)


FlowBar with Air Diffusion Plenum Box - High Throw (HT)

FL-10 with 150mm inlet 12 Air Flow, l/s 2 Total Pressure, Pa Length 2 Pa Pressure, Static 600mm < 10 NC (Noise Criteria) 0.3 - 0.5 - 1.8 Throw, m 19 Air Flow, l/s 2 Pa Pressure, Total 25mm Length 1 Pa Pressure, Static Slot 1200mm Width < 10 NC (Noise Criteria) 0.3 - 0.5 - 1.8 Throw, m 24 Air Flow, l/s 2 Total Pressure, Pa Length 1 Static Pressure, Pa 1500mm < 10 NC (Noise Criteria) 0.3 - 0.5 - 2.3 Throw, m

24 8 7 < 10 1 - 1.8 - 3 38 7 4 < 10 1 - 1.8 - 4 47 9 4 < 10 1 - 2.3 - 4.3

47 35 32 18 28 16 20 <10 1.8 - 2.8 - 3.8 2.5 - 3 - 4.3 76 57 28 16 18 10 16 <10 2.8 - 4 - 5.5 1.8 - 3 - 5 94 71 34 19 18 10 18 <10 2.3 - 3.3 - 5.5 3 - 4.3 - 6

59 50 44 28 2.8 - 3.3 - 5 94 44 28 24 3.3 - 4.3 - 6 118 53 28 26 3.8 - 5 - 7

83 71 98 72 86 63 40 35 3 - 3.8 - 5.5 3.3 - 4 - 5.8 132 113 87 64 55 40 37 31 4 - 5 - 6.8 4.3 - 5.3 - 7.3 165 142 104 77 55 40 38 33 4.3 - 5.5 - 7.5 5 - 5.8 - 8.3

FL-15 with 150mm inlet 33 19 Air Flow, l/s 13 4 Total Pressure, Pa Length 11 4 Pa Pressure, Static 600mm < 10 < 10 NC (Noise Criteria) 0.5 - 1.5 - 2.8 1.5 - 2.5 - 3.8 Throw, m 57 38 Air Flow, l/s 38mm 14 6 Total Pressure, Pa Slot Length 8 4 Pa Pressure, Static Width 1200mm < 10 < 10 NC (Noise Criteria) 1 - Slot 1.8 - 3 - 5 1 - 1.8 - 4 Throw, m 66 42 Air Flow, l/s 15 6 Total Pressure, Pa Length 7 3 Pa Pressure, Static 1500mm < 10 < 10 NC (Noise Criteria) 1.8 - 3 - 5.3 1 - 1.8 - 4 Throw, m

47 26 22 16 2.5 - 3 - 4.3 76 25 14 12 2.8 - 4 - 5.5 90 28 13 12 2.8 - 4.3 - 6

104 90 76 61 128 96 68 45 109 81 57 38 46 40 33 25 3.3 - 4.3 - 6 3.8 - 4.5 - 6.5 2.8 - 3.8 - 5 3.3 - 4 - 5.5 151 132 113 94 99 76 56 39 57 44 32 22 38 33 27 20 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8 4 - 5 - 6.8 3.3 - 4.3 - 6 184 160 137 113 116 88 64 44 55 42 30 21 39 33 27 20 3.3 - 5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.8 - 8.3 5 - 6 - 8.5

FL-20 with 200mm inlet Air Flow, l/s Total Pressure, Pa Length 600mm Static Pressure, Pa NC (Noise Criteria) Throw, m Air Flow, l/s 51mm Total Pressure, Pa Length Slot Static Pressure, Pa Width 1200mm NC (Noise Criteria) 1 - Slot Throw, m Air Flow, l/s Total Pressure, Pa Length Static Pressure, Pa 1500mm NC (Noise Criteria) Throw, m

24 4 4 < 10 0.5 - 1.5 - 3 42 4 3 < 10 1 - 1.8 - 4 47 4 2 < 10 0.5 - 1.5 - 4

40 11 10 < 10 1.8 - 2.8 - 4 71 11 8 < 10 2.3 - 3.3 - 5.5 78 10 6 < 10 1.8 - 3 - 5.5

57 22 20 12 2.5 - 3.3 - 5 99 21 16 20 3 - 4.5 - 6.5 109 19 12 19 3 - 4.5 - 6.8

123 106 90 73 104 78 56 37 95 71 51 34 40 35 28 21 4-5-7 3.3 - 4.3 - 6 3.8 - 4.5 - 6.8 3 - 4 - 5.5 212 184 156 127 97 73 52 35 71 54 38 26 48 42 36 29 5 - 6 - 8.5 5.5 - 6.8 - 9.5 4 - 5.3 - 7.3 4.5 - 5.5 - 8 231 201 170 139 85 64 46 31 54 41 29 20 47 42 36 28 4 - 5.3 - 7.5 4.5 - 5.8 - 8.3 5.3 - 6.5 - 9.3 5.5 - 7 - 9.8

10

FlowBar High Capacity Slot Diffusers

FlowBar Slot Diffuser Performance Data - High Throw (HT)


FlowBar with Air Diffusion Plenum Box - High Throw (HT) FL-10 with 200mm inlet 94 83 71 59 47 35 24 Air Flow, l/s 117 90 66 46 29 16 7 Pressure, Pa Length 112 86 63 44 28 16 7 Static Pressure, Pa 600mm 44 40 34 27 19 < 10 < 10 NC (Noise Criteria) 3.8 - 4.3 - 6 3.3 - 4 - 5.8 1.8 - 2.8 - 3.8 2.5 - 3 - 4.3 2.8 - 3.3 - 5 3 - 3.8 - 5.5 1 - 1.8 - 3 Throw, m 146 127 109 90 71 52 33 Air Flow, l/s 25mm 80 60 44 30 19 10 4 Total Pressure, Pa Slot Length 67 51 37 25 16 8 3 Static Pressure, Pa Width 1200mm 40 35 29 22 13 10 < 10 < Criteria) (Noise NC 1 - Slot 0.5 - 1.5 - 3.3 1.8 - 2.8 - 4.5 2.5 - 3.8 - 5.5 3 - 4.3 - 6 3.8 - 4.5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 7.5 Throw, m 179 156 132 109 85 61 38 Air Flow, l/s 83 63 45 30 19 10 4 Total Pressure, Pa Length 65 49 35 24 15 8 3 Static Pressure, Pa 1500mm 40 35 29 22 13 < 10 < 10 NC (Noise Criteria) 5 - 6 - 8.5 0.5 - 1.5 - 3.8 1.8 - 2.8 - 5 2.8 - 4 - 5.8 3.3 - 4.5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8 Throw, m FL-15 with 200mm inlet 33 19 Air Flow, l/s 12 4 Pressure, Pa Length 11 4 Static Pressure, Pa 600mm < 10 < 10 NC (Noise Criteria) 0.5 - 1.5 - 2.8 1.5 - 2.5 - 3.8 Throw, m 61 38 Air Flow, l/s 38mm 12 4 Total Pressure, Pa Slot Length 9 4 Static Pressure, Pa Width 1200mm 10 < 10 < Criteria) (Noise NC 1 - Slot 2.3 - 3 - 5 1 - 1.8 - 4 Throw, m 71 42 Air Flow, l/s 11 4 Total Pressure, Pa Length 8 3 Static Pressure, Pa 1500mm < 10 < 10 NC (Noise Criteria) 2.3 - 3.3 - 5.5 1 - 1.8 - 4 Throw, m FL-20 with 300mm inlet Air Flow, l/s Total Pressure, Pa Length Static Pressure, Pa 600mm NC (Noise Criteria) Throw, m Air Flow, l/s 51mm Total Pressure, Pa Slot Length Static Pressure, Pa Width 1200mm NC (Noise Criteria) 1 - Slot Throw, m Air Flow, l/s Pressure, Pa Length 1500mm Pressure, Pa NC (Noise Criteria) Throw, m
All pressures are given in Pascal (Pa) Isothermal throw values are given for terminal velocities of .8, .5, and .3 m/sec. Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10 -12 Watts.

47 24 22 14 2.5 - 3 - 4.3 85 22 18 15 3 - 4.3 - 5.8 99 21 16 14 3 - 4.5 - 6.5

76 61 61 40 57 38 32 24 2.8 - 3.8 - 5 3.3 - 4 - 5.5 132 109 54 36 44 30 32 24 3.8 - 4.5 - 6.8 4.3 - 5.3 - 7.3 156 127 53 35 39 26 31 24 4 - 5.3 - 7.3 4.5 - 5.5 - 8

90 86 81 38 3.3 - 4.3 - 6 156 75 61 38 4.5 - 5.5 - 8 184 74 55 37 5 - 6 - 8.5

104 115 109 45 3.8 - 4.5 - 6.5 179 99 81 43 5 - 6 - 8.5 212 99 73 43 5.5 - 6.8 - 9.5

24 4 4 < 10 0.5 - 1.5 - 3 42 3 3 < 10 1 - 1.8 - 4 47 3 2 < 10 0.5 - 1.5 - 4

42 12 11 < 10 1.8 - 2.8 - 4.3 78 10 10 < 10 2.5 - 3.8 - 5.5 90 9 8 < 10 2.5 - 3.8 - 6

61 24 24 < 10 2.8 - 3.8 - 5 113 22 20 13 3.3 - 5 - 6.8 132 20 18 15 3.8 - 5.3 - 7.3

137 118 99 80 121 90 63 41 119 88 62 41 32 27 20 13 4.3 - 5.3 - 7.3 4-5-7 3.3 - 4 - 5.8 3.8 - 4.5 - 6.5 255 219 184 149 110 82 57 37 103 76 54 35 43 37 31 23 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10 5 - 6 - 8.5 4.5 - 5.5 - 8 302 260 217 175 103 76 53 34 92 68 48 31 45 39 33 25 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10.3 6.5 - 8 - 11 5 - 6 - 8.5
Throw values for High Throw units are based on a 1-way discharge from the slot. Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slots.

The tests were conducted with the FlowBar and plenums as a composite assembly. Plenums not provided by Air Diffusion may demonstrate performance variations from data published by Air Diffusion. Air Diffusion cannot validate performance if a factory engineered plenum is not provided.

A!* D!ff-+!'& 11

FlowBar High Capacity Slot Diffusers

FlowBar Slot Diffusers Performance Data - Jet Throw (JT)


FlowBar with Continuous Slot Plenum - Jet Throw (JT) - Data based on active section 1200 long

FL-10
25mm Slot Width 1 - Slot

Air Flow, l/s-m Static Pressure, Pa NC (Noise Criteria) Throw, m

31 2 < 10 0.5 - 1 - 2.3

62 7 < 10 1.3 - 2.3 - 4

93 15 17 2.3 - 3 - 5.8

124 155 27 42 24 28 2.8 - 4 - 6.8 3.3 - 5.3 - 7.3

186 61 32 4 - 5.8 - 8

217 83 36 4.5 - 6 - 8.8

FL-15
38mm Slot Width 1 - Slot

Air Flow, l/s-m 46 93 139 Static Pressure, Pa 2 8 18 NC (Noise Criteria) <10 <10 13 Throw, m 0.5 - 1.3 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8

186 31 22 3 - 4.5 - 8

232 49 28 3.8 - 5.5 - 9.3

279 325 70 95 34 40 4.5 - 6.8 - 9.8 5.3 - 7.5 - 10.8

FL-20
51mm Slot Width 1 - Slot

Air Flow, l/s-m Static Pressure, Pa NC (Noise Criteria) Throw, m

54 1 <10 0.3 - 1 - 2.3

116 7 18 1.5 - 2.5 - 4.5

178 15 24 2.5 - 3.8 - 7

240 28 28 3 - 5 - 9.3

302 44 32 4 - 6 - 10.3

364 64 37 5 - 7.3 - 11.3

426 88 40 5.5 - 8.5 - 12.3

Table A. NC Correction for Length Length, mm 600 1200 Supply -3 0 Return 0 +3

1800 +2 +5

2400 +3 +6

3000 +5 +8

Table B. Correction Multiplier for Length Length, mm 600 1200 2400 Throw Correction 0.72 1 1.5

3000 1.7

3600 1.8

All pressures are given in Pascal (Pa) Pressure loss data assumes a duct velocity less than 4 m/sec in the inlet duct Isothermal throw values are given for terminal velocities of .8, .5, and .3 m/sec. Throw data are based on active sections 1200mm active section. For a 600mm section, the throw values are 0.72 times those shown. For a 3000mm continuous length, the throw values are 1.7 times those shown, 1.8 for 3600mm units. Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10 -12 Watts, for a 1200mm section. (See Table A for other lengths.) For supply units used as a return, add 3 NC.

The tests were conducted with no Plenum effect for pressure or sound. Throw values for Jet Throw units are based on the pattern controller set at 0 discharge vertical flow. Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slots.

12

FlowBar High Capacity Slot Diffusers

FlowBar Slot Diffusers Performance Data - Jet Throw (JT)


FlowBar with Diffuser Plenum Box - Jet Throw (JT)

FL-10 with 200mm inlet Air Flow, l/s Total Pressure, Pa Length Static Pressure, Pa 600mm NC (Noise Criteria) Throw, m Air Flow, l/s Total Pressure, Pa 25mm Length Slot Static Pressure, Pa 1200mm Width NC (Noise Criteria) Throw, m Air Flow, l/s Total Pressure, Pa Length Static Pressure, Pa 1500mm NC (Noise Criteria) Throw, m

24 3 3 < 10 0.5 - 1 - 1.8 47 4 3 < 10 1 - 1.3 - 2.5 52 4 2 < 10 1 - 1.3 - 2.5

45 66 87 109 11 23 41 63 10 21 36 56 < 10 16 23 29 1.3 - 1.8 - 3.3 1.5 - 2.5 - 4.3 2.3 - 3.3 - 5 2.8 - 4 - 5.5 83 118 153 189 12 25 41 63 8 17 28 42 < 10 18 25 30 1.5 - 2.3 - 4.3 2.3 - 3 - 5.8 2.8 - 4 - 6.8 3.3 - 5.3 - 7.3 92 132 172 212 11 23 40 60 6 13 23 34 < 10 17 24 29 1.5 - 2.3 - 4.3 2.3 - 3 - 6 2.8 - 4 - 7 3.3 - 5.3 - 8

130 90 80 34 3.3 - 4.3 - 6 224 88 60 34 4 - 5.8 - 8 252 85 48 33 4 - 6 - 8.5

151 121 108 39 3.8 - 4.5 - 6.8 260 119 80 38 4.5 - 6 - 8.5 293 114 65 37 4.5 - 6.5 - 9.3

FL-15 with 200mm inlet Air Flow, l/s 28 52 76 99 123 146 170 Total Pressure, Pa 3 11 24 42 64 91 122 Length 2 7 14 24 37 52 70 600mm Static Pressure, Pa NC (Noise Criteria) < 10 < 10 < 10 16 24 31 37 Throw, m 0.3 - 1 - 1.5 1 - 1.5 - 2.8 1.5 - 2.3 - 4.3 1.8 - 2.8 - 5.3 2.3 - 3.3 - 5.8 2.8 - 4 - 6.5 3 - 4.5 - 7 Air Flow, l/s 57 85 113 142 170 198 227 38mm Total Pressure, Pa 8 17 31 48 70 95 124 Slot Length Static Pressure, Pa 2 4 8 12 18 24 31 Width 1200mm NC (Noise Criteria) < 10 < 10 < 10 < 10 16 22 27 1 - Slot Throw, m 0.5 - 1.3 - 2.3 1.3 - 1.5 - 3.3 1.5 - 2.3 - 4.5 1.8 - 2.8 - 5.5 2.3 - 3.3 - 6.8 2.5 - 4 - 7.5 3 - 4.5 - 8 Air Flow, l/s 66 94 123 151 179 208 236 Total Pressure, Pa 10 20 33 50 71 95 122 Length Static Pressure, Pa 2 3 6 9 13 17 22 1500mm (Noise Criteria) < 10 < 10 < 10 < 10 12 17 22 Throw, m 0.5 - 1.3 - 2.5 1.3 - 1.5 - 3.3 1.5 - 2.3 - 4.3 1.8 - 2.8 - 5.3 2.3 - 3 - 6.5 2.5 - 3.8 - 7.3 2.8 - 4.3 - 8.3

FL-20 with 200mm inlet Air Flow, l/s 33 66 99 132 165 Total Pressure, Pa 2 8 18 33 51 Length Static Pressure, Pa 1 6 13 23 36 600mm NC (Noise Criteria) < 10 < 10 14 21 27 Throw, m 0.3 - 0.5 - 1.5 1 - 1.5 - 3 1.5 - 2.3 - 4.5 2.3 - 3 - 6 2.5 - 3.8 - 7 Air Flow, l/s 66 113 160 208 255 51mm Total Pressure, Pa 4 12 23 39 58 Length Slot Static Pressure, Pa 1 4 8 14 21 Width 1200mm NC (Noise Criteria) < 10 12 21 27 32 1 - Slot Throw, m 0.3 - 1 - 2.3 1.3 - 1.8 - 3.8 1.8 - 2.8 - 5.3 2.3 - 3.3 - 6.8 2.8 - 4.3 - 8.3 Air Flow, l/s 71 123 175 227 278 Total Pressure, Pa 4 12 24 40 61 Length Static Pressure, Pa 1 3 6 11 16 1500mm NC (Noise Criteria) < 10 13 21 27 32 Throw, m 0.3 - 1 - 2.3 1 - 1.8 - 3.8 1.8 - 2.5 - 5.3 2.3 - 3.3 - 6.8 2.8 - 4 - 8.3

198 231 74 100 51 70 33 38 3 - 4.5 - 7.5 3.8 - 5.3 - 8.3 302 349 82 110 30 40 36 40 3.3 - 5 - 9.3 3.8 - 5.8 - 10 330 382 85 114 23 30 36 40 3 - 5 - 9.5 3.8 - 5.5 - 10.3

A!* D!ff-+!'& 13

FlowBar High Capacity Slot Diffusers

FlowBar Slot Diffusers Performance Data - Jet Throw (JT)


FlowBar with Air Diffusion Plenum Box - Jet Throw (JT) FL-10 with 250mm inlet Air Flow, l/s Total Pressure, Pa Length Static Pressure, Pa 600mm NC (Noise Criteria) Throw, m Air Flow, l/s Total Pressure, Pa 25mm Length Slot Static Pressure, Pa 1200mm Width NC (Noise Criteria) Throw, m Air Flow, l/s Total Pressure, Pa Length Static Pressure, Pa 1500mm NC (Noise Criteria) Throw, m 24 3 3 < 10 0.5 - 1 - 1.8 47 3 3 < 10 1 - 1.3 - 2.5 52 3 2 < 10 1 - 1.3 - 2.5 45 66 87 109 130 151 10 22 38 59 84 114 10 21 36 56 80 108 < 10 16 22 28 33 38 1.3 - 1.8 - 3.3 1.5 - 2.5 - 4.3 2.3 - 3.3 - 5 2.8 - 4 - 5.5 3.3 - 4.3 - 6 3.8 - 4.5 - 6.8 85 123 160 198 236 274 10 21 37 56 79 107 9 18 31 47 66 89 < 10 18 25 30 35 39 1.5 - 2.3 - 4.5 2.3 - 3.3 - 5.8 2.8 - 4.3 - 6.8 3.8 - 5.3 - 7.5 4.3 - 5.8 - 8.3 5 - 6.5 - 8.8 99 146 193 241 288 335 10 21 37 58 82 112 7 16 28 44 63 85 < 10 19 26 31 35 40 1.5 - 2.5 - 5 2.5 - 3.3 - 6.5 3 - 4.5 - 7.3 4 - 5.8 - 8.3 4.5 - 6.5 - 9.3 5.5 - 7 - 9.8

FL-15 with 300mm inlet Air Flow, l/s 28 Total Pressure, Pa 2 Length Static Pressure, Pa 2 600mm NC (Noise Criteria) < 10 Throw, m 0.3 - 1 - 1.5 Air Flow, l/s 57 38mm Total Pressure, Pa 2 Slot Length Static Pressure, Pa 2 Width 1200mm NC (Noise Criteria) < 10 1 - Slot Throw, m 0.5 - 1.3 - 2.3 Air Flow, l/s 66 Total Pressure, Pa 2 Length Static Pressure, Pa 2 1500mm NC (Noise Criteria) < 10 Throw, m 0.5 - 1.3 - 2.5

59 90 120 151 182 212 9 20 37 58 84 115 8 20 35 55 80 110 < 10 < 10 18 27 35 43 1.3 - 1.5 - 3.3 1.5 - 2.5 - 5 2.3 - 3.3 - 5.8 2.8 - 4.3 - 6.8 3.3 - 5.3 - 7.3 4 - 5.5 - 8 113 170 227 283 340 396 9 21 37 58 83 113 8 18 31 49 70 95 < 10 10 21 30 37 45 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8 3.8 - 5.5 - 9.3 4.5 - 6.8 - 9.8 5.3 - 7.5 - 10.8 132 198 264 330 396 463 9 20 35 55 79 107 7 15 27 42 61 83 < 10 10 21 29 36 43 1.5 - 2.5 - 4.5 2.5 - 3.3 - 7 3 - 4.5 - 8.8 4 - 5.8 - 9.8 4.5 - 7 - 10.8 5.5 - 8.3 - 11.5

FL-20 with 300mm inlet Air Flow, l/s 33 76 118 160 203 245 288 Pressure, Pa 2 8 20 36 58 85 117 Length Static Pressure, Pa 1 7 8 34 54 79 108 600mm NC (Noise Criteria) < 10 < 10 < 10 17 25 31 36 Throw, m 0.3 - 0.5 - 1.5 1.3 - 1.8 - 3.3 1.8 - 2.8 - 5.5 2.5 - 3.8 - 6.8 3 - 4.5 - 7.5 3.8 - 5.5 - 8.3 4.3 - 6.5 - 9.3 Air Flow, l/s 66 137 208 278 349 420 491 51mm Total Pressure, Pa 2 8 19 34 54 77 106 Slot Length Static Pressure, Pa 1 6 14 25 40 58 79 Width 1200mm NC (Noise Criteria) < 10 < 10 17 24 31 37 41 1 - Slot Throw, m 0.3 - 1 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8.8 3.8 - 5.8 - 10 4.5 - 6.8 - 11 5.3 - 8 - 12 Air Flow, l/s 71 156 241 326 411 496 580 Total Pressure, Pa 2 8 19 34 54 79 108 Length Static Pressure, Pa 1 5 12 22 35 51 70 1500mm NC (Noise Criteria) < 10 < 10 19 26 32 38 43 Throw, m 0.3 - 1 - 2.3 1.5 - 2.3 - 4.5 2.5 - 3.3 - 7 3 - 5 - 9.5 4 - 6 - 11 5 - 7.3 - 12 5.5 - 8.5 - 12.8
All pressures are given in Pascal (Pa) Isothermal throw values are given for terminal velocities of .8, .5, and .3 m/sec. Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10 -12 Watts. The tests were conducted with the FlowBar and plenums as a composite assembly. Plenums not provided by Air Diffusion may demonstrate performance variations from data published by Air Diffusion. Air Diffusion cannot validate performance if a factory engineered plenum is not provided. Throw values for Jet Throw units are based on the pattern controller set at 0 discharge vertical flow. Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slots.

14

FlowBar High Capacity Slot Diffusers

Standard Fixing Details - High Throw (HT)

Nominal Length W 65 Plenum Length

(minimum)

D + 100

Plenum Retaining Clips

Dimensions FL-10-HT (25mm) W = 70mm Dimensions FL-15-HT (38mm) W = 95mm

Dimensions FL-20-HT (51mm) W = 121mm

Standard Fixing Details - Jet Throw (JT)

Nominal Length

D + 100 (minimum) D

Plenum Length

65

Dimensions FL-10-JT (25mm) W = 78mm Dimensions FL-15-JT (38mm) W = 103mm

Dimensions FL-20-JT (51mm) W = 129mm

Flowbar Border 66 Installation Detail

A!* D!ff-+!'& 15

FlowBar High Capacity Slot Diffusers

Dimension and Details - High Throw (HT)


Model FL - 15 and FL - 20 W Model FL - 15 and FL - 20 W

S Border Type 22

Border Type 66 FL - 10/15/20 - HT Border Type 66 1 Slot (25mm) 1 Slot (38mm) 1 Slot (51mm) F 35 41 48 S 25 38 51 W 70 95 121 H 43 43 43

FL - 10/15/20 - HT Border Type 22 1 Slot (25mm) 1 Slot (38mm) 1 Slot (51mm) F 41 48 54 S 25 38 51 W 70 95 121 H 43 43 43

H3

F F H3 F

FL - 10/15/20 - JT Border Type 66 1 Slot (25mm) 1 Slot (38mm) 1 Slot (51mm) F 35 41 48 S 25 38 51 W 68 95 121 H 43 43 43 O 76 102 127

FL - 10/15/20 - JT Border Type 22 1 Slot (25mm) 1 Slot (38mm) 1 Slot (51mm) F 41 48 54 S 25 38 51 W 70 95 121 H 43 43 43

Border Type 66 Slot Run


FRAME SIZE 27mm 2400 (Max) 2400 (Max) 27

Border Type 22 Slot Run


FRAME SIZE 1.6mm 2400 (Max) 2 2400 (Max)

CEILING OPENING = OVERALL 32mm OVERALL LENGTH

CEILING OPENING = OVERALL LENGTH + 5mm

* Make up pieces manufactured to suit.

16

Dimension and Details - Jet Throw (JT)

Tape and Skim Plaster

Tape and Skim Plaster

OVERALL LENGTH

FlowBar High Capacity Slot Diffusers

Dimension and Details - End Border Configurations


Border Type 66 Border Type 22

27.5

1.6

Optional Blanking Plates - FBBO Blank-off Optional Blanking: FBBO - 10 (25mm Slot) FBBO - 15 (38mm Slot) FBBO - 20 (51mm Slot)

Optional Blank-off (Painted Black)

A!* D!ff-+!'& 17

FlowBar High Capacity Slot Diffusers

Standard Installation Details - High Throw (HT) Jet Throw (JT)


Standard Installation for Solid (Plaster / Board) Type Ceiling Systems Standard Installation for Suspended Ceiling Systems

Frame Opening Frame (By Others) F Spreader FlowBar Diffuser Hanger Wire Upper Hanger Clip

Pattern Controller

Hard Ceiling Clip H1 / H3

SS1 Spline Support Clip

SS1 Spline Support Clip FlowBar Diffuser Mounting screws 250-mm maximum centres Standard Plenum Box Installation System [High Throw (HT) only]

Optional Support Hangers

Hanger Wire

Upper Hanger Clip NB. Type 22 must be coated with a bonding agent, (typically Thistle Bond) prior to taping and final filling.

FlowBar Diffuser Plenum Clip

18

FlowBar High Capacity Slot Diffusers

Standard Installation Details - High Throw (HT) Jet Throw (JT)


Upper Hanger Clip (UHC) The UHC - Hanger Clip used to suspend the FlowBar assembly from the structure. The clip is designed to utilize standard ceiling hanger wire. UHC is for 1 - slot only and FL - 15, 20.

H1 Hard Ceiling Clip The H1 - Hard Ceiling Clip is used to mount the FlowBar assembly with border type 66 when a standard plaster board ceiling is required.

H3 Hard Ceiling Clip The H3 - Hard Ceiling Clip can be used to mount the Flowbar assembly with border type 22 when a standard plaster board ceiling is required.

H3 16

H3

Tape and Fill

Tape and Fill

Tape and Fill

Tape and Fill

Spline Support Clip The SS1 - Spline Clip is also used to adjoin multiple sections of FlowBar when continuous lengths are desired.

A!* D!ff-+!'& 19

FlowBar High Capacity Slot Diffusers

Standard Installation Details - Jet Throw (JT) only


Bracket Diffuser Assembly Diffuser Installation without Plenum

Mounting Bracket (F6)

Mounting Bracket

FlowBar Spacer

Diffuser Flange

Fixing Screw Ceiling

Concealed Fastening Plenum Installation Attach Hanger Wire/Rods to Plenum Support Brackets

Diffuser Installation with Plenum

Ceiling

Mounting bracket catches in Hemmed Edge of Plenum

Opening

Diffuser flange overlaps ceiling opening Hemmed Edge of Plenum Ceiling opening dimensions for border type 66 Ceiling Opening Width FlowBar Model FL - 10 FL - 15 FL - 20 1 - Slot 77 102 127 Plenum

20

FlowBar High Capacity Slot Diffusers

Ordering Information FlowBar Slot Diffuser


Example Frame I 66 HT I JT No. of Slots I 1 Slot Width I 15 End Flanges I E1 Fix I F6 Frame Finish I 3 Blade Finish l 4

E0 Open end E1 End Border one end E2 End Border two ends EP1 End plate one end EP2 End plate two ends ME Mitred End

3 Standard White RAL 9010 matt. Type 66 Border 4 Standard Black Type 22 Border 6 Other colours available to special order

66 22

Surface mounting Plaster frame

10 15 20

F6 F9 SP H1 H3

U Bracket fixing (JT only) Toggle fix (HT only) Special fixing Hard ceiling clip (Border Type 66) Hard ceiling clip (Border Type 22)

4 Standard Black 6 Other colours available to special order

UHC Upper hanger clip (Border Type 66)

The model described in the example above would be : 66 - HT1 - 15 - E1 - F6 - 3 - 4 Important: please allow for any lighting zones when selecting plenum boxes

Important Note: All orders must be addressed to AIR DIFFUSION, Ruskin Air Management Limited.

A!* D!ff-+!'& 21

FlowBar High Capacity Slot Diffusers

Plenum Boxes
Plenum Boxes Supplied unlined as standard with side entry spigot. Plenum boxes can be supplied internally lined with 6mm class O foam at extra cost. Apply to sales office for price. Specifications Material Standard is a minimum of 0.7mm thick galvanised or zinc coated steel. Construction Plenum boxes are generally fabricated in 3 sections having tray ends, which are either mechanically joined or spot welded to form an airtight seal. Flush ends (no tray indents) are also available. As standard, spigots are side entry and located centrally. All boxes are supplied with plain edges, as standard, (F0 fixing). Standard Installation Method The tray ends of the plenum box incorporate a 15mm indent, on each side to allow for 8mm drop rod fixings, which gives space for holes to be drilled (by others) without disturbing the active section. Installation Options Fixing lugs can be factory fitted if preferred or special fixing methods (by others) may be used. For plenum boxes having flush ends separate hanging brackets/fixing lugs need to be fitted to allow independent support of diffuser and plenum box. Accessories Joggled style plenum boxes or pan adapters. Spigot dampers include; manual quadrant, teleflex operation or cord operated. 6mm thick Class O internal lining. Equalising grids (50% free area perforated mesh). Turning Vanes. Fixing lugs or special fixings (by others). Flush Ends (No Indent). Finish Self finish galvanised or zinc coated steel as standard. Black paint can be applied to internal faces if required. (At extra cost).

Pressure Drops and Sound Rating The pressure drop given is for supply grille with damper fully open. When the grille is installed with plenum box, the pressure loss of the box has to be added to the grille. Spigot Velocity m/s 1.5 Pressure Drop Pa* Sound Power Level NR* 2 2.0 4 2.5 6 25 3.0 8 30 3.5 12 35 4.0 16 40

* The figures given are approximate - dependent upon spigot entry conditions

Plenum Box Spigot Volumes (l/s) Spigot Velocity m/s Diameter (mm) 100 125 150 175 200 225 250 275 300 325 350 400 1.5 10 18 25 35 45 58 71 86 103 120 140 185 2.0 15 24 34 46 60 77 95 115 139 160 188 245 2.5 19 30 42 58 75 96 120 145 172 200 235 310 3.0 22 35 51 70 91 117 142 172 208 240 280 370 3.5 26 41 60 82 109 137 170 205 240 280 328 430 4.0 30 47 68 94 121 151 191 230 275 320 375 495

22

FlowBar High Capacity Slot Diffusers

Plenum Box Dimensions


Type PBL-1 65

* Allow D when cord operated


20

damper fitted

8mm hole for support rods

X C W L Cord operated spigot damper L + 30

Order Detail C H Angle Bracket fixing available if required.


-

L
-

W
-

D
-

LH
-

RH
-

X
-

Type PBL-1 for F6 fixing (JT only) * This becomes D if spigot damper fitted 65* 20 8mm hole for support rods

L W L + 30

Order Detail C Boxes shown with Indented Ends. Plain End boxes also available. H
-

L
-

W
-

D
-

LH
-

RH
-

X
-

A!* D!ff-+!'& 23

FlowBar High Capacity Slot Diffusers

Plenum Box Dimensions Continued


Manual Quadrant Control Damper

Model Ref CB CB CB CB CB CB CB CB CB CB

* NDD 100 125 150 160 200 250 300 315 350 355

Open Blade Protrusion (mm)

DW 144 Casing Leakage Class C C C C C

Weight (Kg) 0.56 0.71 0.85 0.91 1.17 1.53 1.92 2.05 2.35 2.40

20.5 45.5 53 70.5 73

C C C C C

* NDD: Nominal duct diameter. Actual sizes are in accordance with BS EN 1506: 1998

24

FlowBar High Capacity Slot Diffusers

Ordering Information Plenum Boxes


Example Model PBL-1 Internal Lining U Spigot Damper N Options 0 Dimensions

Plenum Boxes PBL-1 Linear Plenum Box with either a circular or square side entry spigot PBL-2 Linear Plenum Box having either a circular or square top entry spigot PBL-3 Linear Plenum Box with joggle section having either a circular or square side entry spigot

U Standard Unlined Plenum Box L 6mm Class O Internal Lining.

N Plain spigot no damper. Q Quadrant damper. T Teleflex damper fitted to spigot. C Cord operated damper fitted to spigot.

0 No options. 1 Internal faces painted black. 2 Equalising grid. 3 Fixing lugs fitted to side of plenum. 4 Profile ends on each end of plenum. 5 Hemmed Edge for concealed strap fixing. (JT only) 6 Plenum retaining clips. (HT only)

See example below

Dimensions PBL - 1, PBS - 2, Example Neck Size LxW 1000 x 95 0 Denotes Standard. Plenum Height H 350 Circular Spigot Diameter D 250 OR

Sq. / Rect.Spigot Width x Height CxE 0

Centre Line of Spigot G 0

Important Note: All orders must be addressed to AIR DIFFUSION, Ruskin Air Management Limited.

Note: Redesign may occur which supersedes the information in this brochure. Pease refer to our website for latest information.

A!* D!ff-+!'& 25

FlowBar High Capacity Slot Diffusers

26

FlowBar High Capacity Slot Diffusers

A!* D!ff-+!'& 27

A sample of the many products available from Ruskin Air Management


ac,!'&a!*

A!* D!ff-+!'&

&ac'

A!* D!ff-+!'&

R-+#!& A!* Ma&age%e&, L!%!,ed, S,'-*b*!dge R'ad, B*!dg&'*, , S *'(+ !*e, WV15 5BB E&g$a&d. Te$: 01746 761921 Fa0: 01746 760127 ///.a!*-d!ff-+!'&.c'.-#

T e +,a,e%e&,+ %ade !& , !+ b*'c -*e '* b1 '-* *e(*e+e&,a,!.e+ !& c'&+e)-e&ce 'f a&1 e&)-!*!e+ a*!+!&g '-, 'f , !+ d'c-%e&, a*e g!.e& f'* !&f'*%a,!'& (-*('+e+ '&$1. T e1 a*e &', !&,e&ded ,' a.e a&1 $ega$ effec, a&d , e c'%(a&1 !+ &', ,' be *ega*ded a+ b'-&d , e*eb1. T e c'%(a&1 /!$$ '&$1 acce(, 'b$!ga,!'&+ / !c a*e e0(*e++$1 &eg',!a,ed f'* a&d ag*eed a&d !&c'*('*a,ed !&,' a /*!,,e& ag*ee%e&, %ade /!, !,+ c-+,'%e*+. D-e ,' a ('$!c1 'f c'&,!&-'-+ (*'d-c, de.e$'(%e&, , e +(ec!f!ca,!'& a&d de,a!$+ c'&,a!&ed e*e!& a*e +-b"ec, ,' a$,e*a,!'& /!, '-, (*!'* &',!ce.

Vous aimerez peut-être aussi