Contents
Page Introduction Diffuser Specification Air Patterns Flange Styles Corner Sections Performance Data Standard Fixing Details Dimensions - Diffuser Installation Details Ordering Information - Diffusers Plenum Boxes Dimensions - Plenum Boxes Order Information - Plenum Boxes Page 4 Page 5 Page 6 Page 7 Page 8 Page 9 - 14 Page 15 Page 16 - 17 Page 18 - 20 Page 21 Page 22 Page 23 - 24 Page 25
A!* D!ff-+!'&
Introduction
Air Diffusions FlowBar is an architecturally designed high capacity linear slot diffuser. It is designed to combine a very high air handling capacity with maximum flexibility and is suitable for either ceiling or sidewall applications. The flexibility of the system can blend into a design or provide contrast with its striking but simple design. FlowBar is a flexible system that can provide straight lines or curves to blend with other architectural elements and enhance the overall concept of the project. FlowBar Key Features Ceiling Mounted High Throw
Options include:
- Mitred corners, curved, tee and cross piece sections.
Ceiling or Sidewall Applications Modular or Continuous Lengths Curved Sections Corner Pieces Adjustable Discharge Pattern Concealed Fixing Matching Plenum Boxes
38mm slot
Models: - FL-20-HT
Integral pattern controllers are 600mm in length allowing the airstream to be directed left and right for horizontal and vertical airflow. Standard slot sizes are
25mm,38mm and 51mm with single section lengths available up to 2400mm.
25mm Slot
Models:- FL-15-JT 38mm Slot Models:- FL-20-JT 51mm Slot
Jet Throw pattern controllers allow extended throws in typical high bay applications for heated and/or cooled air. Jet Throw pattern controllers are useful along perimeter walls where heated air can be directed downward. Standard slot sizes are
25mm, 38mm and 51mm with single section lengths available up to 2400mm.
A!* D!ff-+!'&
Air Patterns
Model High Throw (HT) Ceiling Mounted
Horizontal Left
Horizontal Right
Vertical
Horizontal
Upward
Downward
Flange Styles
Standard Types 66 and 22
A!* D!ff-+!'&
Corner Sections
90 Mitred Corner Multidirection Supply
T
T
90
* Specify Angle
T
Crosspiece
Curved Supply
B
C * B
B = Overall width T = Overall length C = Overall Arc length L = Slot width A = 127mm Minimum
90 Mitred Corner Slot/Style Border 66 Border 22 Border 66 Border 22 Width 38mm 38mm 51mm 51mm T 200 200 200 200 B 121 133 146 158 Multidirection Supply Slot/Style Border 66 Border 22 Border 66 Border 22 Width 38mm 38mm 51mm 51mm T 200 200 200 200 B 121 133 146 158
All above configurations available with Type 66 (Surface) and Type 22 (Plaster) flanges.
Crosspiece Slot/Style Border 66 Border 22 Border 66 Border 22 Width 38mm 38mm 51mm 51mm T 400 Not 400 Not B A 120 140 Available 146 127 Available
L B
Air Flow, l/s-m 36 Static Pressure, Pa 7 NC (Noise Criteria) < 10 Throw, m 1.5 - 2.5 - 4.3
58 18 16 2.8 - 4 - 5.5
79 101 122 34 55 81 26 33 39 3.8 - 4.5 - 6.5 4.3 - 5.3 - 7.3 4.5 - 5.8 - 8.3
FL-15
38mm Slot Width 1 - Slot
43 8 <10 1.8 - 3 - 5
65 18 14 3 - 4.3 - 5.8
86 32 24 4 - 5 - 6.8
FL-20
51mm Slot Width 1 - Slot
72 14 11 2.8 - 4.3 - 6
187 95 41 5.8 - 7 - 10
1800 +2 +5
2400 +3 +6
3000 +5 +8
Table B. Correction Multiplier for Length Length, mm 600 1200 2400 Throw Correction 0.72 1 1.5
3000 1.7
3600 1.8
All pressures are given in Pascal (Pa) Pressure loss data assumes a duct velocity less than 4 m/sec in the inlet duct Isothermal throw values are given for terminal velocities of .8, .5, and .3 m/sec. Throw data are based on active sections 1200mm active section. For a 600mm section, the throw values are 0.72 times those shown. For a 3000mm continuous length, the throw values are 1.7 times those shown, 1.8 for 3600mm units. Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10 -12 Watts, for a 1200mm section. (See Table A for other lengths.) For supply units used as a return, add 3 NC.
The tests were conducted with no Plenum effect for pressure or sound. Throw values for High Throw units are based on a 1-way discharge from the slot. Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slots.
A!* D!ff-+!'&
FL-10 with 150mm inlet 12 Air Flow, l/s 2 Total Pressure, Pa Length 2 Pa Pressure, Static 600mm < 10 NC (Noise Criteria) 0.3 - 0.5 - 1.8 Throw, m 19 Air Flow, l/s 2 Pa Pressure, Total 25mm Length 1 Pa Pressure, Static Slot 1200mm Width < 10 NC (Noise Criteria) 0.3 - 0.5 - 1.8 Throw, m 24 Air Flow, l/s 2 Total Pressure, Pa Length 1 Static Pressure, Pa 1500mm < 10 NC (Noise Criteria) 0.3 - 0.5 - 2.3 Throw, m
47 35 32 18 28 16 20 <10 1.8 - 2.8 - 3.8 2.5 - 3 - 4.3 76 57 28 16 18 10 16 <10 2.8 - 4 - 5.5 1.8 - 3 - 5 94 71 34 19 18 10 18 <10 2.3 - 3.3 - 5.5 3 - 4.3 - 6
83 71 98 72 86 63 40 35 3 - 3.8 - 5.5 3.3 - 4 - 5.8 132 113 87 64 55 40 37 31 4 - 5 - 6.8 4.3 - 5.3 - 7.3 165 142 104 77 55 40 38 33 4.3 - 5.5 - 7.5 5 - 5.8 - 8.3
FL-15 with 150mm inlet 33 19 Air Flow, l/s 13 4 Total Pressure, Pa Length 11 4 Pa Pressure, Static 600mm < 10 < 10 NC (Noise Criteria) 0.5 - 1.5 - 2.8 1.5 - 2.5 - 3.8 Throw, m 57 38 Air Flow, l/s 38mm 14 6 Total Pressure, Pa Slot Length 8 4 Pa Pressure, Static Width 1200mm < 10 < 10 NC (Noise Criteria) 1 - Slot 1.8 - 3 - 5 1 - 1.8 - 4 Throw, m 66 42 Air Flow, l/s 15 6 Total Pressure, Pa Length 7 3 Pa Pressure, Static 1500mm < 10 < 10 NC (Noise Criteria) 1.8 - 3 - 5.3 1 - 1.8 - 4 Throw, m
104 90 76 61 128 96 68 45 109 81 57 38 46 40 33 25 3.3 - 4.3 - 6 3.8 - 4.5 - 6.5 2.8 - 3.8 - 5 3.3 - 4 - 5.5 151 132 113 94 99 76 56 39 57 44 32 22 38 33 27 20 4.3 - 5.3 - 7.3 4.5 - 5.5 - 8 4 - 5 - 6.8 3.3 - 4.3 - 6 184 160 137 113 116 88 64 44 55 42 30 21 39 33 27 20 3.3 - 5 - 6.8 4.3 - 5.3 - 7.3 4.5 - 5.8 - 8.3 5 - 6 - 8.5
FL-20 with 200mm inlet Air Flow, l/s Total Pressure, Pa Length 600mm Static Pressure, Pa NC (Noise Criteria) Throw, m Air Flow, l/s 51mm Total Pressure, Pa Length Slot Static Pressure, Pa Width 1200mm NC (Noise Criteria) 1 - Slot Throw, m Air Flow, l/s Total Pressure, Pa Length Static Pressure, Pa 1500mm NC (Noise Criteria) Throw, m
40 11 10 < 10 1.8 - 2.8 - 4 71 11 8 < 10 2.3 - 3.3 - 5.5 78 10 6 < 10 1.8 - 3 - 5.5
123 106 90 73 104 78 56 37 95 71 51 34 40 35 28 21 4-5-7 3.3 - 4.3 - 6 3.8 - 4.5 - 6.8 3 - 4 - 5.5 212 184 156 127 97 73 52 35 71 54 38 26 48 42 36 29 5 - 6 - 8.5 5.5 - 6.8 - 9.5 4 - 5.3 - 7.3 4.5 - 5.5 - 8 231 201 170 139 85 64 46 31 54 41 29 20 47 42 36 28 4 - 5.3 - 7.5 4.5 - 5.8 - 8.3 5.3 - 6.5 - 9.3 5.5 - 7 - 9.8
10
76 61 61 40 57 38 32 24 2.8 - 3.8 - 5 3.3 - 4 - 5.5 132 109 54 36 44 30 32 24 3.8 - 4.5 - 6.8 4.3 - 5.3 - 7.3 156 127 53 35 39 26 31 24 4 - 5.3 - 7.3 4.5 - 5.5 - 8
104 115 109 45 3.8 - 4.5 - 6.5 179 99 81 43 5 - 6 - 8.5 212 99 73 43 5.5 - 6.8 - 9.5
42 12 11 < 10 1.8 - 2.8 - 4.3 78 10 10 < 10 2.5 - 3.8 - 5.5 90 9 8 < 10 2.5 - 3.8 - 6
61 24 24 < 10 2.8 - 3.8 - 5 113 22 20 13 3.3 - 5 - 6.8 132 20 18 15 3.8 - 5.3 - 7.3
137 118 99 80 121 90 63 41 119 88 62 41 32 27 20 13 4.3 - 5.3 - 7.3 4-5-7 3.3 - 4 - 5.8 3.8 - 4.5 - 6.5 255 219 184 149 110 82 57 37 103 76 54 35 43 37 31 23 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10 5 - 6 - 8.5 4.5 - 5.5 - 8 302 260 217 175 103 76 53 34 92 68 48 31 45 39 33 25 5.5 - 6.8 - 9.5 5.8 - 7.3 - 10.3 6.5 - 8 - 11 5 - 6 - 8.5
Throw values for High Throw units are based on a 1-way discharge from the slot. Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slots.
The tests were conducted with the FlowBar and plenums as a composite assembly. Plenums not provided by Air Diffusion may demonstrate performance variations from data published by Air Diffusion. Air Diffusion cannot validate performance if a factory engineered plenum is not provided.
A!* D!ff-+!'& 11
FL-10
25mm Slot Width 1 - Slot
93 15 17 2.3 - 3 - 5.8
186 61 32 4 - 5.8 - 8
FL-15
38mm Slot Width 1 - Slot
Air Flow, l/s-m 46 93 139 Static Pressure, Pa 2 8 18 NC (Noise Criteria) <10 <10 13 Throw, m 0.5 - 1.3 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8
186 31 22 3 - 4.5 - 8
FL-20
51mm Slot Width 1 - Slot
240 28 28 3 - 5 - 9.3
302 44 32 4 - 6 - 10.3
1800 +2 +5
2400 +3 +6
3000 +5 +8
Table B. Correction Multiplier for Length Length, mm 600 1200 2400 Throw Correction 0.72 1 1.5
3000 1.7
3600 1.8
All pressures are given in Pascal (Pa) Pressure loss data assumes a duct velocity less than 4 m/sec in the inlet duct Isothermal throw values are given for terminal velocities of .8, .5, and .3 m/sec. Throw data are based on active sections 1200mm active section. For a 600mm section, the throw values are 0.72 times those shown. For a 3000mm continuous length, the throw values are 1.7 times those shown, 1.8 for 3600mm units. Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10 -12 Watts, for a 1200mm section. (See Table A for other lengths.) For supply units used as a return, add 3 NC.
The tests were conducted with no Plenum effect for pressure or sound. Throw values for Jet Throw units are based on the pattern controller set at 0 discharge vertical flow. Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slots.
12
FL-10 with 200mm inlet Air Flow, l/s Total Pressure, Pa Length Static Pressure, Pa 600mm NC (Noise Criteria) Throw, m Air Flow, l/s Total Pressure, Pa 25mm Length Slot Static Pressure, Pa 1200mm Width NC (Noise Criteria) Throw, m Air Flow, l/s Total Pressure, Pa Length Static Pressure, Pa 1500mm NC (Noise Criteria) Throw, m
45 66 87 109 11 23 41 63 10 21 36 56 < 10 16 23 29 1.3 - 1.8 - 3.3 1.5 - 2.5 - 4.3 2.3 - 3.3 - 5 2.8 - 4 - 5.5 83 118 153 189 12 25 41 63 8 17 28 42 < 10 18 25 30 1.5 - 2.3 - 4.3 2.3 - 3 - 5.8 2.8 - 4 - 6.8 3.3 - 5.3 - 7.3 92 132 172 212 11 23 40 60 6 13 23 34 < 10 17 24 29 1.5 - 2.3 - 4.3 2.3 - 3 - 6 2.8 - 4 - 7 3.3 - 5.3 - 8
151 121 108 39 3.8 - 4.5 - 6.8 260 119 80 38 4.5 - 6 - 8.5 293 114 65 37 4.5 - 6.5 - 9.3
FL-15 with 200mm inlet Air Flow, l/s 28 52 76 99 123 146 170 Total Pressure, Pa 3 11 24 42 64 91 122 Length 2 7 14 24 37 52 70 600mm Static Pressure, Pa NC (Noise Criteria) < 10 < 10 < 10 16 24 31 37 Throw, m 0.3 - 1 - 1.5 1 - 1.5 - 2.8 1.5 - 2.3 - 4.3 1.8 - 2.8 - 5.3 2.3 - 3.3 - 5.8 2.8 - 4 - 6.5 3 - 4.5 - 7 Air Flow, l/s 57 85 113 142 170 198 227 38mm Total Pressure, Pa 8 17 31 48 70 95 124 Slot Length Static Pressure, Pa 2 4 8 12 18 24 31 Width 1200mm NC (Noise Criteria) < 10 < 10 < 10 < 10 16 22 27 1 - Slot Throw, m 0.5 - 1.3 - 2.3 1.3 - 1.5 - 3.3 1.5 - 2.3 - 4.5 1.8 - 2.8 - 5.5 2.3 - 3.3 - 6.8 2.5 - 4 - 7.5 3 - 4.5 - 8 Air Flow, l/s 66 94 123 151 179 208 236 Total Pressure, Pa 10 20 33 50 71 95 122 Length Static Pressure, Pa 2 3 6 9 13 17 22 1500mm (Noise Criteria) < 10 < 10 < 10 < 10 12 17 22 Throw, m 0.5 - 1.3 - 2.5 1.3 - 1.5 - 3.3 1.5 - 2.3 - 4.3 1.8 - 2.8 - 5.3 2.3 - 3 - 6.5 2.5 - 3.8 - 7.3 2.8 - 4.3 - 8.3
FL-20 with 200mm inlet Air Flow, l/s 33 66 99 132 165 Total Pressure, Pa 2 8 18 33 51 Length Static Pressure, Pa 1 6 13 23 36 600mm NC (Noise Criteria) < 10 < 10 14 21 27 Throw, m 0.3 - 0.5 - 1.5 1 - 1.5 - 3 1.5 - 2.3 - 4.5 2.3 - 3 - 6 2.5 - 3.8 - 7 Air Flow, l/s 66 113 160 208 255 51mm Total Pressure, Pa 4 12 23 39 58 Length Slot Static Pressure, Pa 1 4 8 14 21 Width 1200mm NC (Noise Criteria) < 10 12 21 27 32 1 - Slot Throw, m 0.3 - 1 - 2.3 1.3 - 1.8 - 3.8 1.8 - 2.8 - 5.3 2.3 - 3.3 - 6.8 2.8 - 4.3 - 8.3 Air Flow, l/s 71 123 175 227 278 Total Pressure, Pa 4 12 24 40 61 Length Static Pressure, Pa 1 3 6 11 16 1500mm NC (Noise Criteria) < 10 13 21 27 32 Throw, m 0.3 - 1 - 2.3 1 - 1.8 - 3.8 1.8 - 2.5 - 5.3 2.3 - 3.3 - 6.8 2.8 - 4 - 8.3
198 231 74 100 51 70 33 38 3 - 4.5 - 7.5 3.8 - 5.3 - 8.3 302 349 82 110 30 40 36 40 3.3 - 5 - 9.3 3.8 - 5.8 - 10 330 382 85 114 23 30 36 40 3 - 5 - 9.5 3.8 - 5.5 - 10.3
A!* D!ff-+!'& 13
FL-15 with 300mm inlet Air Flow, l/s 28 Total Pressure, Pa 2 Length Static Pressure, Pa 2 600mm NC (Noise Criteria) < 10 Throw, m 0.3 - 1 - 1.5 Air Flow, l/s 57 38mm Total Pressure, Pa 2 Slot Length Static Pressure, Pa 2 Width 1200mm NC (Noise Criteria) < 10 1 - Slot Throw, m 0.5 - 1.3 - 2.3 Air Flow, l/s 66 Total Pressure, Pa 2 Length Static Pressure, Pa 2 1500mm NC (Noise Criteria) < 10 Throw, m 0.5 - 1.3 - 2.5
59 90 120 151 182 212 9 20 37 58 84 115 8 20 35 55 80 110 < 10 < 10 18 27 35 43 1.3 - 1.5 - 3.3 1.5 - 2.5 - 5 2.3 - 3.3 - 5.8 2.8 - 4.3 - 6.8 3.3 - 5.3 - 7.3 4 - 5.5 - 8 113 170 227 283 340 396 9 21 37 58 83 113 8 18 31 49 70 95 < 10 10 21 30 37 45 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8 3.8 - 5.5 - 9.3 4.5 - 6.8 - 9.8 5.3 - 7.5 - 10.8 132 198 264 330 396 463 9 20 35 55 79 107 7 15 27 42 61 83 < 10 10 21 29 36 43 1.5 - 2.5 - 4.5 2.5 - 3.3 - 7 3 - 4.5 - 8.8 4 - 5.8 - 9.8 4.5 - 7 - 10.8 5.5 - 8.3 - 11.5
FL-20 with 300mm inlet Air Flow, l/s 33 76 118 160 203 245 288 Pressure, Pa 2 8 20 36 58 85 117 Length Static Pressure, Pa 1 7 8 34 54 79 108 600mm NC (Noise Criteria) < 10 < 10 < 10 17 25 31 36 Throw, m 0.3 - 0.5 - 1.5 1.3 - 1.8 - 3.3 1.8 - 2.8 - 5.5 2.5 - 3.8 - 6.8 3 - 4.5 - 7.5 3.8 - 5.5 - 8.3 4.3 - 6.5 - 9.3 Air Flow, l/s 66 137 208 278 349 420 491 51mm Total Pressure, Pa 2 8 19 34 54 77 106 Slot Length Static Pressure, Pa 1 6 14 25 40 58 79 Width 1200mm NC (Noise Criteria) < 10 < 10 17 24 31 37 41 1 - Slot Throw, m 0.3 - 1 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8.8 3.8 - 5.8 - 10 4.5 - 6.8 - 11 5.3 - 8 - 12 Air Flow, l/s 71 156 241 326 411 496 580 Total Pressure, Pa 2 8 19 34 54 79 108 Length Static Pressure, Pa 1 5 12 22 35 51 70 1500mm NC (Noise Criteria) < 10 < 10 19 26 32 38 43 Throw, m 0.3 - 1 - 2.3 1.5 - 2.3 - 4.5 2.5 - 3.3 - 7 3 - 5 - 9.5 4 - 6 - 11 5 - 7.3 - 12 5.5 - 8.5 - 12.8
All pressures are given in Pascal (Pa) Isothermal throw values are given for terminal velocities of .8, .5, and .3 m/sec. Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10dB, re 10 -12 Watts. The tests were conducted with the FlowBar and plenums as a composite assembly. Plenums not provided by Air Diffusion may demonstrate performance variations from data published by Air Diffusion. Air Diffusion cannot validate performance if a factory engineered plenum is not provided. Throw values for Jet Throw units are based on the pattern controller set at 0 discharge vertical flow. Throws listed are for the 1-way air pattern. For divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slots.
14
(minimum)
D + 100
Nominal Length
D + 100 (minimum) D
Plenum Length
65
A!* D!ff-+!'& 15
S Border Type 22
Border Type 66 FL - 10/15/20 - HT Border Type 66 1 Slot (25mm) 1 Slot (38mm) 1 Slot (51mm) F 35 41 48 S 25 38 51 W 70 95 121 H 43 43 43
FL - 10/15/20 - HT Border Type 22 1 Slot (25mm) 1 Slot (38mm) 1 Slot (51mm) F 41 48 54 S 25 38 51 W 70 95 121 H 43 43 43
H3
F F H3 F
FL - 10/15/20 - JT Border Type 66 1 Slot (25mm) 1 Slot (38mm) 1 Slot (51mm) F 35 41 48 S 25 38 51 W 68 95 121 H 43 43 43 O 76 102 127
FL - 10/15/20 - JT Border Type 22 1 Slot (25mm) 1 Slot (38mm) 1 Slot (51mm) F 41 48 54 S 25 38 51 W 70 95 121 H 43 43 43
16
OVERALL LENGTH
27.5
1.6
Optional Blanking Plates - FBBO Blank-off Optional Blanking: FBBO - 10 (25mm Slot) FBBO - 15 (38mm Slot) FBBO - 20 (51mm Slot)
A!* D!ff-+!'& 17
Frame Opening Frame (By Others) F Spreader FlowBar Diffuser Hanger Wire Upper Hanger Clip
Pattern Controller
SS1 Spline Support Clip FlowBar Diffuser Mounting screws 250-mm maximum centres Standard Plenum Box Installation System [High Throw (HT) only]
Hanger Wire
Upper Hanger Clip NB. Type 22 must be coated with a bonding agent, (typically Thistle Bond) prior to taping and final filling.
18
H1 Hard Ceiling Clip The H1 - Hard Ceiling Clip is used to mount the FlowBar assembly with border type 66 when a standard plaster board ceiling is required.
H3 Hard Ceiling Clip The H3 - Hard Ceiling Clip can be used to mount the Flowbar assembly with border type 22 when a standard plaster board ceiling is required.
H3 16
H3
Spline Support Clip The SS1 - Spline Clip is also used to adjoin multiple sections of FlowBar when continuous lengths are desired.
A!* D!ff-+!'& 19
Mounting Bracket
FlowBar Spacer
Diffuser Flange
Concealed Fastening Plenum Installation Attach Hanger Wire/Rods to Plenum Support Brackets
Ceiling
Opening
Diffuser flange overlaps ceiling opening Hemmed Edge of Plenum Ceiling opening dimensions for border type 66 Ceiling Opening Width FlowBar Model FL - 10 FL - 15 FL - 20 1 - Slot 77 102 127 Plenum
20
E0 Open end E1 End Border one end E2 End Border two ends EP1 End plate one end EP2 End plate two ends ME Mitred End
3 Standard White RAL 9010 matt. Type 66 Border 4 Standard Black Type 22 Border 6 Other colours available to special order
66 22
10 15 20
F6 F9 SP H1 H3
U Bracket fixing (JT only) Toggle fix (HT only) Special fixing Hard ceiling clip (Border Type 66) Hard ceiling clip (Border Type 22)
The model described in the example above would be : 66 - HT1 - 15 - E1 - F6 - 3 - 4 Important: please allow for any lighting zones when selecting plenum boxes
Important Note: All orders must be addressed to AIR DIFFUSION, Ruskin Air Management Limited.
A!* D!ff-+!'& 21
Plenum Boxes
Plenum Boxes Supplied unlined as standard with side entry spigot. Plenum boxes can be supplied internally lined with 6mm class O foam at extra cost. Apply to sales office for price. Specifications Material Standard is a minimum of 0.7mm thick galvanised or zinc coated steel. Construction Plenum boxes are generally fabricated in 3 sections having tray ends, which are either mechanically joined or spot welded to form an airtight seal. Flush ends (no tray indents) are also available. As standard, spigots are side entry and located centrally. All boxes are supplied with plain edges, as standard, (F0 fixing). Standard Installation Method The tray ends of the plenum box incorporate a 15mm indent, on each side to allow for 8mm drop rod fixings, which gives space for holes to be drilled (by others) without disturbing the active section. Installation Options Fixing lugs can be factory fitted if preferred or special fixing methods (by others) may be used. For plenum boxes having flush ends separate hanging brackets/fixing lugs need to be fitted to allow independent support of diffuser and plenum box. Accessories Joggled style plenum boxes or pan adapters. Spigot dampers include; manual quadrant, teleflex operation or cord operated. 6mm thick Class O internal lining. Equalising grids (50% free area perforated mesh). Turning Vanes. Fixing lugs or special fixings (by others). Flush Ends (No Indent). Finish Self finish galvanised or zinc coated steel as standard. Black paint can be applied to internal faces if required. (At extra cost).
Pressure Drops and Sound Rating The pressure drop given is for supply grille with damper fully open. When the grille is installed with plenum box, the pressure loss of the box has to be added to the grille. Spigot Velocity m/s 1.5 Pressure Drop Pa* Sound Power Level NR* 2 2.0 4 2.5 6 25 3.0 8 30 3.5 12 35 4.0 16 40
* The figures given are approximate - dependent upon spigot entry conditions
Plenum Box Spigot Volumes (l/s) Spigot Velocity m/s Diameter (mm) 100 125 150 175 200 225 250 275 300 325 350 400 1.5 10 18 25 35 45 58 71 86 103 120 140 185 2.0 15 24 34 46 60 77 95 115 139 160 188 245 2.5 19 30 42 58 75 96 120 145 172 200 235 310 3.0 22 35 51 70 91 117 142 172 208 240 280 370 3.5 26 41 60 82 109 137 170 205 240 280 328 430 4.0 30 47 68 94 121 151 191 230 275 320 375 495
22
damper fitted
L
-
W
-
D
-
LH
-
RH
-
X
-
Type PBL-1 for F6 fixing (JT only) * This becomes D if spigot damper fitted 65* 20 8mm hole for support rods
L W L + 30
Order Detail C Boxes shown with Indented Ends. Plain End boxes also available. H
-
L
-
W
-
D
-
LH
-
RH
-
X
-
A!* D!ff-+!'& 23
Model Ref CB CB CB CB CB CB CB CB CB CB
* NDD 100 125 150 160 200 250 300 315 350 355
Weight (Kg) 0.56 0.71 0.85 0.91 1.17 1.53 1.92 2.05 2.35 2.40
C C C C C
* NDD: Nominal duct diameter. Actual sizes are in accordance with BS EN 1506: 1998
24
Plenum Boxes PBL-1 Linear Plenum Box with either a circular or square side entry spigot PBL-2 Linear Plenum Box having either a circular or square top entry spigot PBL-3 Linear Plenum Box with joggle section having either a circular or square side entry spigot
N Plain spigot no damper. Q Quadrant damper. T Teleflex damper fitted to spigot. C Cord operated damper fitted to spigot.
0 No options. 1 Internal faces painted black. 2 Equalising grid. 3 Fixing lugs fitted to side of plenum. 4 Profile ends on each end of plenum. 5 Hemmed Edge for concealed strap fixing. (JT only) 6 Plenum retaining clips. (HT only)
Dimensions PBL - 1, PBS - 2, Example Neck Size LxW 1000 x 95 0 Denotes Standard. Plenum Height H 350 Circular Spigot Diameter D 250 OR
Important Note: All orders must be addressed to AIR DIFFUSION, Ruskin Air Management Limited.
Note: Redesign may occur which supersedes the information in this brochure. Pease refer to our website for latest information.
A!* D!ff-+!'& 25
26
A!* D!ff-+!'& 27
A!* D!ff-+!'&
&ac'
A!* D!ff-+!'&
R-+#!& A!* Ma&age%e&, L!%!,ed, S,'-*b*!dge R'ad, B*!dg&'*, , S *'(+ !*e, WV15 5BB E&g$a&d. Te$: 01746 761921 Fa0: 01746 760127 ///.a!*-d!ff-+!'&.c'.-#
T e +,a,e%e&,+ %ade !& , !+ b*'c -*e '* b1 '-* *e(*e+e&,a,!.e+ !& c'&+e)-e&ce 'f a&1 e&)-!*!e+ a*!+!&g '-, 'f , !+ d'c-%e&, a*e g!.e& f'* !&f'*%a,!'& (-*('+e+ '&$1. T e1 a*e &', !&,e&ded ,' a.e a&1 $ega$ effec, a&d , e c'%(a&1 !+ &', ,' be *ega*ded a+ b'-&d , e*eb1. T e c'%(a&1 /!$$ '&$1 acce(, 'b$!ga,!'&+ / !c a*e e0(*e++$1 &eg',!a,ed f'* a&d ag*eed a&d !&c'*('*a,ed !&,' a /*!,,e& ag*ee%e&, %ade /!, !,+ c-+,'%e*+. D-e ,' a ('$!c1 'f c'&,!&-'-+ (*'d-c, de.e$'(%e&, , e +(ec!f!ca,!'& a&d de,a!$+ c'&,a!&ed e*e!& a*e +-b"ec, ,' a$,e*a,!'& /!, '-, (*!'* &',!ce.