750-60
Performance Specification
Capacity: Cf Factor: Cavitation: Rangeability: Bearing Friction: See Technical Data Sheet 0.9 See Technical Data Sheet 500:1 No friction from slip-type bearings 2 1/2" and 4" Female American National Fire Hose Connection (Section Thread NFPA -194-1974) Male American National Fire Hose Connection (Section Thread NFPA -194-1974) Determined by components as high as 720 psi maximum 150 psid continuous, 225 psid intermittent* 125 psid maximum 32 to 160 degrees F*
Control systems are fully piped at the factory and the Cla-Val Fire Hydrant Pressure Relief Valve is shipped complete, ready for installation.
Material Specification
Body: Liner: Liner Retainer: 316L Stainless Steel Natural Rubber, 65 durometer (standard) Viton, EPDM, Nitrile, Silicone (available) 316 Stainless Steel
Design Specification
Sizes: End Detail Inlet:
Pilot
Body: Spring Cover: Wetted Parts: ASTM B62 Bronze* ASTM B62 Bronze* Bronze/Stainless Steel*, Buna-N
Accessories
Shut-off Isolation Valve: "Y" Strainer: Control Piping: Control Fittings: Brass* Bronze* Copper* Brass*
Operating Pressure:
*Standard natural rubber 65 durometer in water service. Temperature range depends on liner material. Higher differential pressure ratings available.
3B 3A
2 B
INLET
OUTLET
Basic Components
1 2 3 100-42FH Roll Seal (Main Valve) X43 "Y" Strainer RCBP Pressure Relief Control w/ Built in Restrictor
Optional
B CK2 (Isolation Valve)
Purchase Specification
Valve and control system shall maintain inlet pressure at a predetermined set point; shall open as pressure starts to increase above the set point, and close as pressure falls below the set point. Control valve shall be constructed of two parts: an 316L stainless steel body and an elastomeric liner or control element. Minimum rangeability shall be 500:1 based on capacity at flowing pressure conditions. Cf shall be greater than or equal to 0.9. Valve and control system shall be similar in all respects to Cla-Val Fire Hydrant Pressure Relief Valve as manufactured by Cla-Val, Newport Beach, California.
CLA-VAL
PO Box 1325 Newport Beach CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441
CLA-VAL CANADA
4687 Christie Drive Beamsville, Ontario Canada L0R 1B4 Phone: 905-563-4963 Fax: 905-563-4040
E-750-60 (R-3/2011)
COPYRIGHT CLA-VAL 2011 Printed in USA Specifications subject to change without notice.