DATA SHEET PAGE DATE Loflow K15 Sprinkler Series: The Loflow K15 Sprinkler series contain fine

water spray sprinklers (water mist) with automatic quick res-ponse for fixed fire protection of on-shore, Maritime and offshore applications. Loflow K15 sprinkler heads are installed in fully hydraulic designed wet pipe sprinkler systems. Loflow K15 sprinkler systems must be designed and installed in accordance with GW Sprinkler A/S installation manual no.: 715. The Loflow K15 sprinkler are also suitable sprinkler for foam enchanced sprinkler system, deluge systems and local application systems. On-shore Sprinkler Application: Installation, approvals & specifications test. Loflow K15 sprinklers Model C & O are approved by Factory Mutual for fixed sprinkler protection of FM light hazard occupancies. Which involves areas like: Apart-ments, Churches, Clubs, Eaves and Overhangs, Educa-tional Institutions, Drafting Rooms, Hotel Rooms, Hos-pitals, Institutions, Libraries, (except large stock rooms), Museums, (convalescent) Homes, Offices (including data processing areas) Residentials, Restaurant Seating Areas, Theatres and Auditoriums (excluding stages and prosceniums) and Unused Attic Spaces etc. Loflow Model C & O: Model C Corridors, Confined Areas Model O Open spaces Response index: RTI ms-: <50 Drop sizes: DN90 <300 m Water pressure: [6-16] bar K-factor (1xmin-1 x bar -): 15 Installation height: max. 5m Distance between sprinklers: [1.5-3.5]m Distance from wall to sprinkler max: 1.75m Loflow Model S (Shops and storage) Factory Mutual has specification tested Loflow Model S sprinkler to comply with the appropriate section of. The International Maritime Organisation (IMO) Resolution A800 for shop and storage occupancies. Application Model S: Shops & Storage Water pressure: [6-16] bar - Response index: RTI ms : <50 Drop size: Dn90 <300 K-factor: (1 x min. 1 x bar -) 15 Installation height: max 3m Distance between sprinklers: [1.5-3]m Distance from wall to Sprinkler: max.1m Applications:

140015 1 OF 1 - (FEB.2000)

Model O Mark O Bent 110

Model C Mark C Bent 110

Model S Mark S Bent 110

Accessories: All full programme of: Wet alarm valves, Loflow C1: 80,100,150,200mm Flush Rosettes: Single Piece Rosette Two Piece Rosettes, Model ADJ Sprinkler spanner: Model DD Materials: Standard finish: Chrome coated brass Standard corroision protection Electroless nickel plated brass Seawater protection and clean surfaces PTFE + Electroless nickel plated brass Connection: Standard connection: Non standard connection*: *Extended delivery time

BSPT NPT

Nominal Release Temperatures: 57C Orange glass bulb 68C Red glass bulb* 79C Yellow glass bulb 93C Green glass bulb 141C Blue glass bulb (*FM approved temperature)

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 1 of 18

GW SPRINKLER A/S

BUILDING OCCUPANCY FIRE PROTECTION LOW PRESSURE WATER MIST LOFLOWK15

DATA SHEET PAGE DATE LOFLOW K15 Sprinkler Series: The Loflow K15 Sprinkler series contain fine water spray sprinklers (Water mist) with automatch quick response for fixed sprinkler fire protection of maritime, Offshore and On-shore applications. The Loflow K15 Sprinkler heads is installed in fully hydraulic designed wet pipe systems. Loflow K15 sprinkler installations must be designed and installed in accordance with GW Installation manual no.: 715. Loflow K15 sprinklers is also suitable sprinklers for foam enchanced sprinkler systems, Deluge systems and local application systems. Maritime sprinkler applications type approval: Loflow K15 Model C, O & S Sprinklers is type approved for installation occupancies in accordance with the international maritime organisation (IMO) resolution A800 as equivalent sprinkler system to that mentioned in SOLAS chapter II-2 regulation 12 by: United States Coast Guard (USCG) Danish Maritime Authorities Germanischer Lloyds (GL) Bureau Veritas (BV) *American Bureau of Shipping (ABS) *Det Norske Veritas (DNV) *Registro Italiano Navale (RINA) Type Approvals pending *Loflow K15 Model O, C & S Sprinklers are approved in accordance with the EC Council Directive 96/98 on marine equipment.

140016 1 OF 1 - (FEB.2000)

Model O Mark O Bent 110

Model C Mark C Bent 110

Model S Mark S Bent 110

Accessories: A full programme of: Alarm valves for maritime Loflow installations Rosettes: Single piece & two piece rosettes Flexible sprinkler connection pipes Alarm gongs and sprinkler spanners etc. Materials Chrome coated brass fresh water installations ENP nickel plated brass Sea water installations Nedox Nickel PTFE plated Sea water installations For further informations please see data sheet no.: 14711 Connections: Male thread BSPT or NPT, with or without PTFE sealing tape.
SOLAS Occupancy Model K15-O X X X X Model K15-C X X X X Model K15-S

General Loflow K15 Nozzle Parameters: Drop sizes: Dn90 Response index ms- Water pressure bar: <300m <50 (Quick Response) [6-16]

Nominal release temperatures: 57C - Orange glass bulb 68C - Red glass bulb 79C - Yellow glass bulb D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc 93C - Green glass bulb 141C - Blue glass bulb

1.Control Stations 2. Stairways 3.Corridors 4.Accommodation areas minor fire risks 5. Accommodation areas X X X moderate risks 6.Accommodation areas X X X greater risks 7.Sanitary spaces X X X 8. Storerooms etc. X 9.Storage, X Page 2 of 18 shops For further informations please see GW data sheet no.: 14711

GW SPRINKLER A/S

MARINE OCCUPANCY SPRINKLER FIRE PROTECTION LOW PRESSURE WATER MIST LOFLOW K15

DATA SHEET PAGE DATE -

14711 1 OF 2 C

Maritime Installation of LOFLOW K15 Sprinklers LOFLOW K15 Sprinklers must be installed in pendent position. LOFLOW K15 Systems must be designed and installed in accordance with SOLAS Regulation II-2/12, with the exception of water density less than 5 litre/min.m2. LOFLOW Sprinkler systems must be hydraulically calculated with Hazen- Williams formulary, to provide the recommended minimum water pressure on the last nozzle to operate in the system. Solas and NFPA 750 require the systems toParameters have standing charge of fresh water. Occupancy Classification LOFLOW Sprinkler Type
K15-O K15-C
2

K15-S

(1) Control Stations Sprinkler Spacing: max. 3.5m max. 12/15m Table 1: Applications as Classified in SOLAS Regulation II-2/26.2.2: max. 2m Distance to Wall: max. 1.5m Water Pressure: Locations: Ceiling Height: Sprinkler Spacing: Distance to Wall: Water Pressure Stairways Width: Ceiling Height: Sprinkler Spacing: Distance to Wall: Water Pressure: Corridor Width: Ceiling Height: Sprinkler Spacing: Distance to Wall: Water Pressure Locations: Ceiling Height: min. 6/8 bar min. 6 bar small rooms* all max. 2.5m max. 5m max. 3.5m max. 3.5m max. 1.5m max. 0.8m min. 6 bar min. 6 bar >1.6 bar < 1.6m max. 5m max. 2.5m max. 3.5m max. 3.5m max. 1.5m max. 0.8m min. 6 bar min. 6 bar > 1.6 bar < 1.6m max. 5m max. 2.5m max. 3.5m max. 12/15m2 max. 2m max. 1.5m min. 6/8 bar min. 6 bar small rooms all max. 2.5m max. 5m max. 3.5m max. 12/15m2 max. 2m max. 1.5m min. 6/8 bar min. 6 bar small rooms* all sizes max. 2.5m max. 5m max. 3.5m max. 12/15m2 max. 2m* max. 1.5m min. 6/8 bar min. 6 bar small rooms all sizes max. 2.5m max. 5m Page 3 of 18 max. 3.5m max. 12/15m2 max. 2m max. 1.5m min. 6/8 bar min. 6 bar small rooms* all sizes

(2) Stairways

(3) Corridors

(6) Accommodations Spaces minor fire risk

Sprinkler Spacing: Distance to Wall: Water Pressure: Locations: Ceiling Height: (8) Accommodation spaces Sprinkler Spacing: greater fire risk Distance to Wall: Water Pressure Locations: D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Ceiling Height: (9) Sanitary & Similar Spaces Sprinkler Spacing: Distance to Wall: Water Pressure Locations:

(7) Accommodation spaces moderate fire risk

max. 3.5m max. 1.5m min. 6 bar all sizes max. 5m max. 3.5m max. 1.5m min. 6 bar all sizes max. 5m

Sprinklers to be installed symmetrically Max. 4m x 3m rooms, min. 6 bar pressure Max. 5m x 3m rooms, min 8 bar pressure INSTALLATION GUIDE LINES GW SPRINKLER A/S FOR LOFLOW K15-O, K15-C & K15-S

DATA SHEET PAGE DATE -

14711 2 OF 2 C

Installation and Maintenance: LOFLOW K15 Sprinklers have small orifices when compared with traditional sprinklers. To minimise the risk of blocked sprinkler nozzle during operation, the sprinkler pipes must be flushed with fresh clean water through each branch pipe end. To avoid dirt in pipes before the sprinklers are installed. CAUTION: After the pipes have been flushed and the pipe plug removed, the inside pipe sucked threads must be cleaned for any sealing materials, before the LOFLOW sprinklers are installed. LOFLOW sprinkler must always be installed in pendent position using special purpose System Sprinkler materiel Pipe system material Extinguishing agent spanner from GW Sprinkler A/S. Brass natural Galvanized steel pipes Fresh water
Cu-alloys pipes Plastic (See note 1) Sprinkler Pipes and Components: Galvanised steel pipes Fresh water Brass/Cu-alloy pipes Sprinkler pipes must match hydraulic calculations, internal pressures and authority Wet Pipe Systems Brass ENP SS303, 304 pipes demands and recommendations. Sprinkler material must match materials of pipes and CuNi pipes Fresh & Seawater SS316, SMO254 etc. quality of extinguishing, table 2. Plastic pipes (see note 1) CuNi pipes Fresh & Seawater Stainless steel AISI316 SS316, SMO254 etc. Plastic pipes (see note 1) Brass natural Cu-alloys pipes Fresh water Brass chrome D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Dry Pipe Systems Brass ENP Brass/Cu-alloy pipes Fresh & Seawater Page 4 of 18 SS303, 304 pipes Stainless steel AISI316 CuNi pipes Fresh & Seawater Stainless steel pipes Brass chrome

The materials of sprinkler system components such as valves, flow switches, pumps etc. must match authority demands, water flow, system pressure, pipe materials and extinguishing agent. Please see also LOFLOW Sprinkler Installation Guideline No.: 715 for Maritime Installations. Galvanised Pipes and Fittings: NFPA 750 does not allow the use of galvanised pipes and fittings downstream the system strainer. USCG requires a strainer downstream of all fittings that are of materials other than these shown in NFPA (1996), table 2-3.3.1. Table 3 Components Material:

be used installations or Installations.

Note 1: Plastic pipes are not to in maritime ordinary hazard

GW SPRINKLER A/S

INSTALLATION GUIDELINES FOR LOFLOW K15-O, K15-C & K15-S

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 5 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 6 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 7 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 8 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 9 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 10 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 11 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 12 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 13 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 14 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 15 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 16 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 17 of 18

D:\Rulesandregs\Fire\Water Mist\Gwsprinkler.doc Page 18 of 18