Dynasty has upgraded their UPS line and replaced all but one of their UPS series batteries with
their new High Max Rate Series (MR). The case length and width for their new MR series remain
the same as their now discontinued batteries. Therefore, replacement banks are a perfect fit.
The case heights on the new MR series batteries are slightly less due to changes in the terminals.
Capacities are increased on each type and all of the MR series are rated as fire retardant (FR).
We have prepared a reference chart below to aid in selecting replacements. All specifications
and ratings are also included in this document. Product specification sheets for the discontinued
batteries are available upon request at sales@dcbattery.com
UPS12-100
Discontinued, updated
&
and replaced by
UPS12-100FR Dynasty part number UPS12-100MR
UPS12-140
Discontinued, updated
&
and replaced by
UPS12-140FR Dynasty part number UPS12-150MR
UPS12-170
Discontinued, updated
&
and replaced by
UPS12-170FR Dynasty part number UPS12-210MR
UPS12-200
Discontinued, updated
&
and replaced by
UPS12-200
Dynasty part number UPS12-300MR
UPS12-270
Discontinued, updated
&
and replaced by
UPS12-270FR Dynasty part number UPS12-300MR
UPS12-310
Discontinued, updated
&
and replaced by
UPS12-310FR Dynasty part number UPS12-350MR
UPS12-370
Discontinued, updated
&
and replaced by
UPS12-370FR Dynasty part number UPS12-400MR
UPS12-475
Discontinued, updated
&
and replaced by
UPS12-475FR Dynasty part number UPS12-490MR
UPS12-530
Discontinued, updated
&
and replaced by
UPS12-530FR Dynasty part number UPS12-540MR
UPS6-620
Is not discontinued;
UPS6-620FR
&
Available in FR only
UPS6-620FR

Capacity is
increased

Case dimensions are


the same

Terminals
unchanged

Case Length and Width Terminals change


Capacity is
are the same; Height is
to threaded
increased
slightly shorter
inserts
Case Length and Width Terminals change
Capacity is
are the same; Height is
to threaded
increased
slightly shorter
inserts
Case Length and Width Terminals change
Capacity is
are the same; Height is
to threaded
increased
slightly shorter
inserts
Case Length and Width Terminals change
Capacity is
are the same; Height is
to threaded
increased
slightly shorter
inserts
Case Length and Width Terminals change
Capacity is
are the same; Height is
to threaded
increased
slightly shorter
inserts
Case Length and Width Terminals change
Capacity is
are the same; Height is
to threaded
increased
slightly shorter
inserts
Case Length and Width Terminals change
Capacity is
are the same; Height is
to threaded
increased
slightly shorter
inserts
Case Length and Width Terminals change
Capacity is
are the same; Height is
to threaded
increased
slightly shorter
inserts
Capacity is
unchanged

Case dimensions are


the same

Terminals
unchange

UPS
41-9027

Valve Regulated Lead Acid Battery


Designed for UPS Standby Power Applications.

FEATURES & BENEFITS


Absorbent Glass Mat (AGM)
technology for efficient gas
recombination of up to 99% and
freedom from electrolyte maintenance.

Proprietary Fixed Orifice Plate Pasting


technology applying active materials
on both sides of the grid for consistent
cell-to-cell performance, higher
capacity and uniform grid protection.

3 Year Warranty (refer Dynasty warranty


card, 41-9026)

Thermally welded case-to-cover bond


to eliminate leakage.

Patented Long Life Alloy having the


lowest calcium levels in the industry minimizing grid growth, reducing
gassing, and extending battery life.

Can be operated in any orientation.


Upright, side or end mounting
recommended.

10 year design life @ 25C

Not restricted for air transport Complies with IATA/ICAO Special


Provisions A67.

Patented UL Recognized Flamearresting vents in each cell for safety


and long life.
Designed with the same recombination,
thermal runaway prevention, gassing
and flame retardant characteristics of
the Bellcore 4228 compliant Dynasty
Telecom products.
Flame retardant polypropylene case
and cover compliant with UL 1778

TECHNICAL DATA

Not restricted for surface transport Classified as non-hazardous material


as related to DOT-CFR Title 49 parts
171-189.
Not restricted for water transport Classified as non-hazardous material
per IMDG Amendment 27.

Watts Per Cell @ 77F (25C)


1.67 Volts per Cell - Operating Time to End Point Voltage (in minutes)
10
15
20
30
40
45
50
60
117
91
75
57
47
43
39
35

90
24

Weight
lbs
21

Weight
kg
10

51

36

27.3

12.4

73

52

40

18

Model
UPS12-100MR

Voltage
12

5
172

UPS12-150MR

12

288

192

148

120

89

71

65

60

UPS12-210MR

12

376

257

206

170

125

101

92

85

UPS12-300MR

12

550

382

300

244

179

144

131

121

105

76

58.4

26.5

UPS12-350MR

12

620

440

350

290

217

171

155

141

122

87

67.4

30.5

UPS12-400MR

12

720

505

400

325

237

189

172

158

136

98

75.8

34.4

UPS12-490MR

12

773

590

488

412

317

256

236

218

189

136

100

45

UPS12-540MR

12

868

654

537

450

344

277

252

230

198

139

100

45

UPS6-620MR

940

750

620

525

410

333

309

285

245

173

72

33

Available Through: DC Battery Specialists 160 NW 73 St. Miami, FL 33150 Phone 305.758.5041
www.dcbattery.com e-mail: sales@dcbattery.com

UPS
SPECIFICATIONS
Operating Temperature Range
with temperature compensation

Discharge: -40F (-40C) to +160F (71C)


Charge: -10F (-23C) to +140F (60C)

Nominal Operating Temperature Range

+74F (-23C) to +80F (27C)

Recommended Maximum Charging


Current Limit

C/5 amperes @ 20hr rate

Float Charging Voltage

13.65 1.5 VDC average per 12V unit (6.75 to 6.90 per 6V unit)

Maximum AC Ripple (Charger)

0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.

Self Discharge

Up to 6 months at 25C and then a freshening charge is required. For higher temps,
the time interval will increase. freshening charge is required.
For higher temperatures the time interval will be shorter.
For lower temperatures time interval will decrease equalization charge.

Equalize charge and


cycle service voltage

14.40 to 14.80 VDC average per 12V unit @ 77F (25C) (7.20 to 7.40 VDC per 6V unit.)

Terminal: Flag

0.22 in. clearance hole to accept 0.1875 in. bolt (UPS12-100MR)

Terminal: Inserted

Threaded copper alloy insert terminal to accept


10-32 UNF bolt (UPS12-150MR, UPS12-210MR)
4-20 UNC bolt (UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MR, UPS12-540MR, UPS6-620MR)

Terminal Hardware Annual Retorque

32 in.-lbs (3.48 N-m)(UPS12-100MR)

Terminal Hardware Initial Torque:


Inserted Terminal

40 in.-lbs. (4.5 N-m)(UPS12-100MR)


25 in.-lbs. (2.8 N-m) (UPS12-150MR, UPS12-210MR)
110 in.-lbs. (12.4 N-m) (UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MR, UPS12-540MR, UPS6-620MR)

DIMENSIONS

*All dimensions in millimeters. All dimensions are for reference only. Contact a C&D Representative for complete dimension information.

Available Through: DC Battery Specialists 160 NW 73 St. Miami, FL 33150 Phone 305.758.5041
www.dcbattery.com e-mail: sales@dcbattery.com

UPS
UPS12-100MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
158
168
172
174
179

10
111
115
117
118
119

15
87
90
91
91
92

20
73
75
75
76
76

30
56
57
57
57
58

40
46
47
47
47
47

45
42
43
43
43
43

50
39
40
40
40
40

60
34
35
35
35
35

90
24
24
24
25
25

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.90
1.85
1.80
1.75

.083
51.1
62.8
72.3
80.0

.25
33.0
38.4
42.1
44.3

.50
22.4
25.3
27.1
28.1

.75
18.2
20.5
21.8
22.5

1
14.0
15.6
16.4
16.9

2
6.30
9.10
9.50
9.75

3
6.05
6.60
6.86
7.00

5
3.94
4.29
4.45
4.53

8
2.62
2.85
2.95
3.00

10
2.14
2.33
2.41
2.45

12
1.82
1.98
2.05
2.08

20
1.14
1.24
1.28
1.30

24
0.96
1.05
1.08
1.10

72
0.34
0.37
0.38
0.39

100
0.24
0.26
0.27
0.28

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

UPS12-150MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
270
282
288
292
296

10
182
188
192
196
200

15
141
144
148
150
152

20
115
118
120
122
123

30
86
87
89
90
91

40
69.0
70.0
71.1
71.8
72.5

45
63.0
63.9
64.9
65.3
66.0

50
58.0
58.8
59.5
60.0
60.5

60
49.7
50.4
51.0
51.5
51.8

90
35.0
35.5
36.0
36.3
36.5

20
1.65
1.69
1.73

24
1.39
1.42
1.45

72
0.47
0.48
0.49

50
83.0
84.2
85.0
85.4
86.0

60
71.8
72.8
73.3
73.8
74.2

90
51.0
52.0
52.4
52.6
52.8

20
2.50
2.63
2.67

24
2.10
2.21
2.24

72
0.73
0.76
0.77

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
22.5
23.8
25.2

2
12.5
13.1
13.7

3
8.80
9.20
9.52

5
5.68
5.90
6.05

8
3.76
3.90
4.00

10
3.10
3.21
3.29

12
2.63
2.72
2.78

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

UPS12-210MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
340
366
376
380
392

10
240
252
257
259
261

15
195
201
206
207
209

20
164
168
170
171
172

30
121
123
125
126
127

40
98
99
101
101
102

45
90
91
92
93
93

Constant Power Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
33.0
35.0
36.5

2
18.7
19.5
20.6

3
13.3
13.9
14.5

5
8.60
9.20
9.40

8
5.78
6.10
6.23

10
4.74
5.02
5.09

12
4.02
4.25
4.30

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Available Through: DC Battery Specialists 160 NW 73 St. Miami, FL 33150 Phone 305.758.5041
www.dcbattery.com e-mail: sales@dcbattery.com

UPS
UPS12-300MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
496
530
550
566
580

10
360
373
382
387
391

15
282
294
300
303
306

20
234
240
244
246
248

30
174
177
179
181
183

40
140
142
144
146
147

45
128
130
131
133
134

50
118
120
121
122
123

60
103
104
105
106
107

90
74
75
76
77
78

20
3.60
3.80
3.89

24
3.03
3.18
3.25

72
1.05
1.08
1.10

50
137
140
141
144
145

60
118
120
122
123
125

90
85
86
87
88
89

20
4.40
4.55
4.65

24
3.71
3.83
3.90

72
1.29
1.32
1.34

50
154
156
158
160
161

60
133
135
136
137
138

90
96
97
98
99
100

20
4.77
4.99
5.10

24
4.00
4.18
4.27

72
1.38
1.43
1.46

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
48.4
50.7
52.5

2
27.1
28.3
29.0

3
19.6
20.3
20.6

5
12.6
13.1
13.4

8
8.34
8.81
9.13

10
6.85
7.27
7.50

12
5.80
6.15
6.35

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

UPS12-350MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
540
596
620
640
672

10
410
425
440
455
470

15
327
337
350
360
370

20
274
283
290
298
303

30
205
211
217
219
222

40
164
167
171
173
175

45
149
152
155
157
159

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
53.0
59.0
63.0

2
31.0
33.5
35.1

3
22.1
23.7
24.8

5
14.8
15.6
16.1

8
10.08
10.63
11.00

10
8.34
8.74
9.00

12
7.08
7.42
7.58

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

UPS12-400MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
616
680
720
740
770

10
461
490
505
515
525

15
377
390
400
406
412

20
312
319
325
329
333

30
230
234
237
239
241

40
184
187
189
191
193

45
168
170
172
174
175

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
56.0
62.0
68.0

2
33.0
35.3
38.0

3
23.9
25.3
27.0

5
15.8
16.6
17.6

8
10.8
11.4
11.9

10
8.90
9.44
9.80

12
7.58
8.02
8.30

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Available Through: DC Battery Specialists 160 NW 73 St. Miami, FL 33150 Phone 305.758.5041
www.dcbattery.com e-mail: sales@dcbattery.com

UPS
UPS12-490MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
660
740
773
800
840

10
525
570
590
614
644

15
444
472
488
500
513

20
385
401
412
418
428

30
300
310
317
322
327

40
245
252
256
260
264

45
224
231
236
238
241

50
208
214
218
220
222

60
183
186
189
191
192

90
133
135
136
137
138

20
6.58
6.79
6.96

24
5.53
5.70
5.84

72
1.93
1.99
2.03

50
220
226
230
234
237

60
190
193
198
200
202

90
136
137.5
139
141
143

20
6.35
6.94
7.20
7.35

24
5.35
5.88
6.06
6.17

72
1.85
2.00
2.07
2.11

60
242
243
245
248
250

90
168
170
173
176
178

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
80.9
85.5
90.3

2
47.2
50.9
53.2

3
34.4
36.3
37.8

5
22.5
23.5
24.2

8
15.0
15.5
16.1

10
12.3
12.8
13.2

12
10.5
10.9
11.2

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

UPS12-540MR
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
723
825
868
904
952

10
564
625
654
679
696

15
472
512
537
554
564

20
405
432
450
459
465

30
320
334
344
350
354

40
261
270
277
282
284

45
239
247
252
256
258

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.90
1.85
1.80
1.75

1
75.0
85.0
90.0
95.0

2
44.0
49.5
53.0
56.0

3
32.0
35.8
38.0
39.9

5
21.4
23.4
24.6
25.6

8
14.4
15.8
16.4
16.9

10
11.9
13.0
13.6
13.9

12
10.1
11.1
11.5
11.8

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

UPS6-620MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
840
890
940
950
1000

10
680
720
750
760
790

15
575
600
620
630
650

20
500
520
525
532
550

30
395
405
410
414
420

40
320
332
333
335
340

45
297
306
309
311
315

50
275
280
285
288
290

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.90
1.85
1.80
1.75

.083
250
332
418
454

.25
207
248
288
312

.50
149
174
196
208

.75
122
142
158
166

1
94.0
110
120
123

2
57.7
62.7
68.0
69.5

3
42.0
45.5
48.3
50.0

5
27.9
30.0
31.6
32.4

8
19.0
20.3
21.3
22.0

10
15.8
16.9
17.6
18.2

12
13.5
14.5
15.2
15.6

20
8.70
9.30
9.80
10.0

24
7.31
7.84
8.21
8.38

72
2.51
2.73
2.83
2.87

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.

Available Through: DC Battery Specialists 160 NW 73 St. Miami, FL 33150 Phone 305.758.5041
www.dcbattery.com e-mail: sales@dcbattery.com

100
1.82
1.98
2.05
2.08

DIECUT

Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)