PM130 PLUS Powermeter Series PM130P/PM130EH

Installation and Operation Manual

0.2 Class BG0425 Rev. A1

LIMITED WARRANTY
The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or parts from date of dispatch from the distributor. In all cases, this warranty is valid for 36 months from the date of production. This warranty is on a return to factory basis. The manufacturer does not accept liability for any damage caused by instrument malfunction. The manufacturer accepts no responsibility for the suitability of the instrument to the application for which it was purchased. Failure to install, set up or operate the instrument according to the instructions herein will void the warranty. Only a duly authorized representative of the manufacturer may open your instrument. The unit should only be opened in a fully anti-static environment. Failure to do so may damage the electronic components and will void the warranty. The greatest care has been taken to manufacture and calibrate your instrument. However, these instructions do not cover all possible contingencies that may arise during installation, operation or maintenance, and all details and variations of this equipment are not covered by these instructions. For additional information regarding installation, operation or maintenance of this instrument, contact the manufacturer or your local representative or distributor.

WARNING
Read the instructions in this manual before performing performing installation and take note of the following precautions: Ensure that all incoming AC power and other power sources sources are turned OFF before performing any work on the instrument. Failure to do so may result in serious or even fatal injury and/or equipment damage. Before connecting the instrument to the power source, source, check the labels on the back of the instrument to ensure that your instrument is equipped with the appropriate power supply voltage, voltage, input voltages and currents. Under no circumstances should the instrument be connected to a power source if it is damaged. To prevent potential fire or shock hazard, do not expose the instrument to rain or moisture. moisture. The secondary of an external current transformer must never be allowed to be open circuit when the primary is energized. An open circuit can cause high voltages, possibly resulting in equipment damage, fire and even serious or fatal injury. injury. Ensure that the current transformer wiring is secured using an external strain relief to reduce mechanical strain on the screw terminals, terminals, if necessary. Only qualified personnel familiar with the instrument and its associated electrical equipment equipment must perform setup procedures. Do not open the instrument under any circumstances when it is connected to a power source. source. Do not use the instrument for primary protection functions where failure of the device can cause cause fire, injury or death. The instrument can only be used for secondary protection if needed. Read this manual thoroughly before connecting the device to the current carrying input ut circuits. During operation of the device, hazardous voltages are present on inp terminals. terminals. Failure to observe precautions can result in serious or even fatal injury or damage to equipment.

All trademarks are property of their respective owners. Copyright 2007

PM130 PLUS Powermeters Series

Quick Start Guide


This section can be used by a licensed electrician to install and perform basic PM130 PLUS Powermeter setup. For more detailed PM130 PLUS setup and use instructions, see the installation and operation manual following chapters. This quick start guide will assist you to have the unit running for the first time. During the operation of the Powermeter, hazardous voltages are present in the input terminals. Failure to observe precautions can result in serious or even fatal injury, or damage to equipment. For complete and accurate in-depth instructions, refer to the following chapters in this manual.

1.

Installing the PM130 PLUS


Mounting the PM130 PLUS Unit
To mount the PM130 PLUS: PLUS: 1. Position the PM130 PLUS unit in the square or round cutout. If two PLM130 PLUS are positioned side by side, take care of proper interval between them. 2. Attach the PM130 PLUS unit using washers and nuts. Make sure that the unit is securely attached into the wall or cabinet fixture.

Mounting the PM130 PLUS (Square or Round Cut-out)

PM130 PLUS Powermeters Series

Mounting two PM130 PLUS side by side

2.

Connecting the PM130 PLUS


To connect the PM130 PLUS: PLUS: 1. Ensure that all incoming power sources are OFF. 2. Check that you have the appropriate power supply. 3. Connect to the external CT by passing the external CT wire through the meter CT core. Observe the arrow that indicates the current direction. In case of a retrofit application where each external CT ends with two wires: Pass one wire through the meter CT core. Connect the wire to one of the meter termination screws. Connect the second wire from the external CT to the termination screw.

4. Connect the measured voltage inputs 5. 6. Connect COM1 RS-485 communication port Connect the Power Supply inputs using 1.5 mm /14AWG-dedicated wires.
2

Common Wiring Mode: 4LL3 or 4L-n3

PM130 PLUS Powermeters Series

CT wiring To assemble Option module: module: 7. Assemble the 4DI/2DO module. 8. Assemble the 4AO module. 9. Assemble the TOU module. 10. Assemble the ETH module

Assembling module 11. Power the PM130 PLUS unit on. 12. Perform device diagnostics. 13. Configure the device through the PM-130 unit front panel displays.

3.

Configuring the PM-130


1. Install the PAS application software on your PC. 2. Configure the PAS database. 3. Configure the communications settings. 4. Set up the meter on your PC using the PAS application software.

PM130 PLUS Powermeters Series

5. Configure your security settings through the Authorization dialog box. 6. Configure Summary Energy and TOU registers. 7. Configure the Modbus point mapping. 8. Change the 32-bit register format. 9. Configure DNP3. 10. Configure remote access. 11. Upgrade your firmware if a new version is available. 12 At this stage, the PM-130 should be ready for operation.

PM130 PLUS Powermeters Series

Table of Contents
Chapter 1 General Information ............................................. 10
1.1 1.2
1.2.1 1.2.2 1.2.3 1.2.4

Features ............................................................................................ 11 Available Options ................................................................................ 12


Digital I/O Option ........................................................................................... 12 Analog Output Option .................................................................................... 12 Ethernet Communication Port Option .............................................................. 12 TOU - Battery-Operated Clock Unit Option ...................................................... 12

1.3
1.3.1 1.3.2 1.3.3

Customized Options ............................................................................ 13


Device Resolution........................................................................................... 13 Energy Rollover .............................................................................................. 13 Display Options .............................................................................................. 13

Chapter 2 Installation ............................................................ 15


2.1 2.2 2.3
2.3.1 2.3.2

Site Requirements .............................................................................. 15 Package Contents ............................................................................... 15 Mechanical Installation........................................................................ 16


Panel Mounting .............................................................................................. 17 DIN Rail Mounting .......................................................................................... 18

2.4
2.4.1 2.4.2 2.4.3 2.4.4 2.4.5

Electrical Installation ........................................................................... 19


Typical Installation ......................................................................................... 19 Terminals....................................................................................................... 20 Power Source Connection ............................................................................... 20 Current Input Connection ............................................................................... 20 Wiring Diagrams ............................................................................................ 21

2.5
2.5.1 2.5.2 2.5.3

I/O Connections ................................................................................. 26


4DI/2DO Module ............................................................................................ 26 4AO Module - Analog Outputs ........................................................................ 27 TOU RTC and 4 Digital Inputs ...................................................................... 28

2.6
2.6.1 2.6.2

Communications Connections .............................................................. 29


COM1 RS-485 Connection............................................................................... 30 COM2 Ethernet Connection............................................................................. 31

Chapter 3 Display Operations ................................................ 32


3.1
3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.1.6

Indicators and Controls ....................................................................... 32


Device Diagnostics ......................................................................................... 32 Numeric LED Display ...................................................................................... 32 Load Bar Graph .............................................................................................. 33 Energy Pulse LED ........................................................................................... 33 Port Activity LEDs ........................................................................................... 33 Navigation Buttons ......................................................................................... 33

3.2
3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 3.2.7

Data Display....................................................................................... 34
Display Features ............................................................................................ 34 Navigation Buttons ......................................................................................... 35 Simple Reset of Accumulated Data ................................................................. 36 Common Measurements Display ..................................................................... 36 Min/Max and Maximum Demand Display ......................................................... 37 Harmonics Display.......................................................................................... 38 Energy Display ............................................................................................... 39

3.3
3.3.1 3.3.2 3.3.3

Status Display .................................................................................... 41


Pulse and Time Counters ................................................................................ 43 Alarm Display ................................................................................................. 43 Diagnostics Display ........................................................................................ 43

PM130 PLUS Powermeters Series

3.4
3.4.1 3.4.2 3.4.3 3.4.4 3.4.5

Using the Menus ................................................................................ 44


Navigation Buttons ......................................................................................... 44 Selecting Menus ............................................................................................. 44 Entering the Password ................................................................................... 45 Selecting a Menu Entry................................................................................... 47 Viewing and Changing Setup Items ................................................................ 47

3.5
3.5.1 3.5.2 3.5.3 3.5.4 3.5.5 3.5.6 3.5.7 3.5.8 3.5.9 3.5.10 3.5.11 3.5.12 3.5.13

Menu Operations ................................................................................ 48


Basic Device Settings ..................................................................................... 48 Device Options ............................................................................................... 49 Communication Ports ..................................................................................... 51 Network Address ............................................................................................ 52 Digital Input Setup ......................................................................................... 53 Relay Output Setup ........................................................................................ 55 Counters Setup .............................................................................................. 57 Alarm/Control Setpoints Setup ........................................................................ 58 Analog Outputs Setup .................................................................................... 60 Display Setup ............................................................................................... 61 Meter Security .............................................................................................. 63 Setting the Device Clock ............................................................................... 64 Resetting Accumulators and Maximum Demands ........................................... 65

Chapter 4 PAS Application Software ..................................... 67


4.1 4.2
4.2.1 4.2.2

Configuring the Database .................................................................... 67 Setting up Communications ................................................................. 68


Communicating through a Serial Port .............................................................. 69 Communicating through the Internet .............................................................. 70

4.3
4.3.1 4.3.2

Setting Up the Meter .......................................................................... 71


Downloading Setup to the Meter .................................................................... 72 Uploading a Setup from the Meter .................................................................. 73

4.4 4.5
4.5.1 4.5.2

Authorization...................................................................................... 73 Configuring Communications in the Meter ............................................ 73


Setting Up Communication Ports .................................................................... 73 Setting Up Ethernet........................................................................................ 75

4.6
4.6.1 4.6.2 4.6.3 4.6.4 4.6.5 4.6.6 4.6.7 4.6.8

General Meter Setup ........................................................................... 76


Basic Meter Setup .......................................................................................... 76 Device Options ............................................................................................... 78 Local Settings ................................................................................................ 80 Using Digital Inputs ........................................................................................ 81 Using Relay Outputs ....................................................................................... 83 Programming Analog Outputs ......................................................................... 84 Using Counters .............................................................................................. 87 Using Control Setpoints .................................................................................. 88

4.7
4.7.1 4.7.2 4.7.3

Configuring Summary Energy and TOU Registers ................................. 90


Setting up Total and Tariff Registers ............................................................... 91 Configuring the Daily Tariff Schedule .............................................................. 92 Configuring the Season Tariff Schedule ........................................................... 93

4.8
4.8.1 4.8.2

Configuring Communication Protocols .................................................. 94


Configuring Modbus ....................................................................................... 95 Configuring DNP3........................................................................................... 96

4.9
4.9.1 4.9.2 4.9.3 4.9.4

Remote Device Control ....................................................................... 98


Remote Relay Control..................................................................................... 98 Device Diagnostics ......................................................................................... 99 Resetting Accumulators ................................................................................ 100 Updating the Clock ....................................................................................... 101

4.10
4.10.1

Administration ................................................................................ 101


Changing a Password ................................................................................. 101

4.11 4.12

Upgrading Device Firmware ............................................................ 102 Monitoring Your Meters ................................................................... 104

PM130 PLUS Powermeters Series

4.12.1 4.12.2 4.12.3

Viewing Real-time Data .............................................................................. 104 Viewing Min/Max Log ................................................................................. 104 Viewing Harmonic Spectrum and Synthesized Waveforms ........................... 105

Appendix A Appendix B Appendix C Appendix E

Technical Specifications ................................... 109 Analog Output Parameters ............................... 116 Setpoint Triggers and Actions .......................... 118 Data Scales ....................................................... 127

Appendix D Parameters for Data Monitoring ...................... 120 Appendix F Device Diagnostic Codes ................................... 128

PM130 PLUS Powermeters Series

Chapter 1General Information

Chapter 1 General Information

The PM130 PLUS Powermeter series is a compact, multi-function, threephase AC powermeter specially designed to meet the requirements of users ranging from electrical panel builders to substation operators. The PM130 PLUS Powermeter Series comprises of two types of models: PM130P: PM130P the basic model which offers standard voltage, current, power and frequency measurements, and control capabilities. PM130EH: PM130EH has all the features of the basic model plus energy measurements and harmonic analysis capabilities.

The PM130 PLUS Powermeter Series units includes: A bright 3-row LED display enabling easy reading of local meters. A standard RS-485 communication port and a second optional Ethernet port . These ports allow local and remote automatic meter readings and setup through the supplemental communication or user data acquisition software. Different communication options for remote communications with the meter. These options enable LAN and Internet communication with the unit.

Both models are suitable for mounting on both 4-inch round and 92x92mm square cutouts.

10

PM130 PLUS Powermeters Series

Chapter 1General Information

1.1 Features
The PM130 PLUS Powermeter Series includes the following features and functionalities: 3 voltage inputs and 3 current transformer-isolated AC inputs for direct connection to power line or via potential and current transformers A multi-function 3-phase meter (true RMS, volts, amps, power, power factor, neutral current, voltage, and current unbalance, frequency) An embedded harmonic analyzer, voltage and current THD, current TDD and K-Factor, up to 40th order harmonic (PM130EH) Voltage and current harmonic spectrum and angles (PM130EH) An Ampere/Volt demand meter Class 0.2 four-quadrant energy meter; three-phase total and per phase energy measurements; active, reactive and apparent energy counters (PM130EH) Time-of-Use, 4 totalization and tariff energy/demand registers x 4 tariffs, 4 seasons x 4 types of days, 8 tariff changes per day, easy programmable tariff schedule (PM130EH with a battery-operated clock unit) Embedded programmable controller; 16 control setpoints; programmable thresholds and delays; relay output control (see the Order Options section); 1-cycle response time Easy to read 3-row (2x4 characters + 1x5 characters) bright LED display, adjustable update time and brightness, auto-scroll option with adjustable page exposition time, auto-return to a default page LED bar graph showing percent load with respect to user-definable nominal load current 25/50/60/400 Hz measurement capabilities Internal clock with a 30-second backup; optional battery-backed clock unit with 6-month retention time, see the Order Options section Standard 2-wire RS-485 communication port; Modbus RTU, DNP3, and proprietary ASCII communication protocols Optional second communication port, see the Order Options section Easy-to-upgrade field device firmware through the communication port.

PM130 PLUS Powermeters Series

11

Chapter 1General Information

1.2 Available Options


The PM130 can be provided with an optional single expansion module from the following list: Digital I/O Analog outputs Ethernet communication port TOU - Battery-operated clock unit

1.2.1

Digital I/O Option


The PM130 digital I/O expansion module provides: 4 dry contact digital inputs (DI) to monitor external contacts, and receive pulses from energy, water, and gas meters Programmable de-bounce time; 1-ms scan time. 2 electro-mechanical or solid-state relay outputs (RO) for alarms and controls, and for output energy pulses; unlatched, latched and pulse operations, failsafe operation for alarm notifications; programmable pulse width; direct remote relay control through communications; 1-cycle update time.

1.2.2

Analog Output Option


The PM130 analog output (AO) expansion module provides: 4 optically isolated analog outputs with an internal power supply; options for 0-20mA, 4-20mA, 0-1mA, and 1mA output; 1-cycle update time.

1.2.3

Ethernet Communication Port Option


A second COM2 communication port can be ordered as an expansion module. COM2 communication port option available: Ethernet 10/100BaseT Communication protocols available: Modbus/TCP and DNP3/TCP.

1.2.4

TOU - Battery-Operated Clock Unit Option


The PM130 TOU module provides: An optional precise internal clock with a backup battery can be ordered, as an alternate power source for the clock meter to maintain the current time and date for at least 36 months while the main power is missing. The TOU option is only available in the presence of the battery backup unit. 4 dry contact digital inputs (DI) for monitoring external contacts, and receiving pulses from energy, water and gas meters; programmable debounce time; 1-ms scan time.

12

PM130 PLUS Powermeters Series

Chapter 1General Information

1.3 Customized Options


Presentation of data on the front display and via communications can be customized to best suit the user application.

1.3.1

Device Resolution
A low or high-resolution option can be selected for the presentation of voltage, current, and power for use in high and low power applications. See Measurement Units for more information.

1.3.2

Energy Rollover
The energy rollover limit can be changed in the meter to provide 4-digit to 9digit energy resolution. See Device Options in Chapter 3 for details. The meter display is capable of showing full 9-digit energy counters using two LED windows.

1.3.3

Display Options
Different display options are available for customization to be used in dark or non-safe locations, or in places that are hardly accessible for observation. See Display Setup in Chapter 3 for more information.

Table 1: Measured and Displayed Parameters


Parameter 1-cycle Real-time Measurements RMS Voltage per phase RMS Current per phase kW per phase kvar per phase kVA per phase Power Factor per phase Total kW Total kvar Total kVA Frequency Neutral Current Total Power Factor Voltage & Current unbalance 1-sec Average Measurements RMS Voltage per phase RMS Current per phase kW per phase kvar per phase kVA per phase Power Factor per phase Total kW Total kvar Total kVA Total Power Factor Frequency Neutral Current Voltage & Current unbalance Amps & Volt Demands Ampere & Volt Demand per phase Ampere Maximum Demand per phase Voltage Maximum Demand per phase Power Demands EH Display Comm. Analog Pulse Alarm

PM130 PLUS Powermeters Series

13

Chapter 1General Information

Parameter kW Accumulated Demand Import & Export kvar Accumulated Demand Import & Export kVA Accumulated Demand kW Demand Import & Export kvar Demand Import & Export kVA Demand kW Sliding Demand Import & Export kvar Sliding Demand Import & Export kVA Sliding Demand kW Predicted Demand Import & Export kvar Predicted Demand Import & Export kVA Predicted Demand kW Maximum Demand Import kW Maximum Demand Export kvar Maximum Demand Import kvar Maximum Demand Export kVA Maximum Demand Total Energy EH Total kWh Import & Export Total kvarh Import & Export Total kvarh Net Total kVAh Energy per Phase EH kWh Import per phase kvarh Import per phase kVAh per phase TOU Registers EH 4 TOU energy registers (kWh and kvarh import & export, kVAh, 4 pulse sources) 4 TOU maximum demand registers 4 tariffs, 4 seasons x 4 types of day Harmonic Measurements EH Voltage THD per phase Current THD per phase Current TDD per phase K-factor per phase Voltage harmonics per phase up to order 40 Current harmonics per phase up to order 40 Voltage harmonic angles up to order 40 Current harmonic angles up to order 40 Fundamental Component EH Voltage and Current per phase kW, PF per phase kvar, KVA per phase Total kW, PF Total kvar, KVA Min/Max Logging Min/Max A, V, total kW, kvar, kVA, PF Min/Max Frequency, Neutral current Phase Rotation Voltage and Current Phase Angles Day and Time Pulse Counters Digital Inputs (optional) Relay Outputs (optional) Remote Relay Control (optional) Alarm Triggers/Setpoints Self-diagnostics

Display Comm. Analog Pulse

Alarm

14

PM130 PLUS Powermeters Series

Chapter 2Installation

Chapter 2 Installation
This chapter discusses the following types of physical installations for the PM130 PLUS Powermeter: Mechanical Installation Electrical Installation I/O Connections COM Port Connections.

2.1 Site Requirements


See Technical Specifications in Appendix A for more details

Environmental conditions: as specified in Technical Specifications in Appendix A Electrical requirements: as specified in Technical Specifications in Appendix A

2.2 Package Contents


The PM130 PLUS Powermeter package contains the following items: PM130 PLUS Powermeter unit Technical Documentation hardcopy Technical Documentation CD Optional accessories (depending on the options ordered, if any) Flat screwdriver Cables

PM130 PLUS Powermeters Series

15

Chapter 2Installation

2.3 Mechanical Installation


Refer to the figures provided in this section to properly perform the mechanical installation.

Figure 2-1. Dimensions

16

PM130 PLUS Powermeters Series

Chapter 2Installation

2.3.1 Panel Mounting


To mount the meter in cutout (ANSI 4" round or DIN 92x92mm square cutout): 1. Position the meter in the cutout. 2. Affix the meter using washers and nuts. (Add short text on Panel Mounting, a heading should always have text)

Figure 2-2. Mounting

PM130 PLUS Powermeters Series

17

Chapter 2Installation

2.3.2 DIN Rail Mounting


The PM130 can be mounted on a 35-mm DIN rail.

Figure 2-3. Dimensions

Figure 2-4. DIN Rail Mounting

18

PM130 PLUS Powermeters Series

Chapter 2Installation

2.4 Electrical Installation


Before installing, ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.

2.4.1

Typical Installation

Figure 2-5. Typical Installation Diagram

PM130 PLUS Powermeters Series

19

Chapter 2Installation

2.4.2

Terminals

Figure 2-6. Terminals - Rear View

2.4.3

Power Source Connection


Before connecting your meter to the power source, check the label on the back of the device to ensure that it is equipped with the appropriate power supply. The power source can be a dedicated fuse, or a monitored voltage if it is within the instrument power supply range. To connect an AC power supply: 1. 2. Connect the Line wire to terminal L/+. Connect the Neutral wire to terminal N/-.

To connect to a DC power supply: 1. Connect the positive wire to terminal L/+ Connect the negative wire to terminal N/-.

2.

2.4.4

Current Input Connection


The PM130 does not have current terminals. To connect to the external CT, pass the external CT wire through the meter CT core, see Figure 2-7 for details and observe the arrow that indicates the current direction. In case of a retrofit application where each external CT ends with two wires: 1. Pass one wire through the meter CT core. Connect the wire to one of the meter termination screws.

2.

20

PM130 PLUS Powermeters Series

Chapter 2Installation

3.

Connect the second wire from the external CT to the termination screw to close the loop.

Figure 2-7. Current Input Connection

2.4.5

Wiring Diagrams
For AC input ratings, see Technical Specifications in Appendix A for more details. Table 2 presents the available wiring configurations in the meter. For more details, see Basic Device Settings in Chapter 3.

Table 2: Wiring Configurations


Wiring Configuration 3-wire 2-element Direct connection using 2 CTs 4-wire Wye 3-element direct connection using 3 CTs 4-wire Wye 3-element connection using 3 PTs, 3 CTs 3-wire 2-element Open Delta connection using 2 PTs, 2 CTs 4-wire Wye 2 -element connection using 2 PTs, 3 CTs 3-wire 2 -element Open Delta connection using 2 PTs, 3 CTs 4-wire 3-element Delta direct connection using 3 CTs 3-wire 2-element Broken Delta connection using 2 PTs, 3 CTs Setup Code 3dir2 4Ln3 or 4LL3 4Ln3 or 4LL3 3OP2 3Ln3 or 3LL3 3OP3 4Ln3 or 4LL3 3bLn3 or 3bLL3 Figure 2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15

PM130 PLUS Powermeters Series

21

Chapter 2Installation

Figure 2-8. 3-Wire 2-Element Direct Connection Using 2 CTs - Wiring Mode = 3dir2

Figure 2-9. 4-Wire Wye 3-Element Direct Connection Using 3 CTs - Wiring Mode = 4LL3 or 4Ln3

22

PM130 PLUS Powermeters Series

Chapter 2Installation

Figure 2-10. 4-Wire Wye 3-Element Connection Using 3 PTs, 3 CTs - Wiring Mode = 4LL3 or 4Ln3

Figure 2-11. 3-Wire 2-Element Open Delta Connection Using 2 PTs, 2 CTs - Wiring Mode = 3OP2

PM130 PLUS Powermeters Series

23

Chapter 2Installation

This configuration provides accurate power measurements only if the voltages are balanced. Figure 2-12. 4-Wire Wye 2-Element Connection Using 2 PTs, 3 CTs - Wiring Mode = 3LL3 or 3Ln3

Figure 2-13. 3-Wire Open 2-Element Delta Connection Using 2 PTs, 3 CTs - Wiring Mode = 3OP3

24

PM130 PLUS Powermeters Series

Chapter 2Installation

Figure 2-14. 4-Wire 3-Element Delta Direct Connection Using 3 CTs - Wiring Mode = 4LL3 or 4Ln3

Figure 2-15. 3-Wire 2-Element Broken Delta Connection Using 2 PTs, 3 CTs - Wiring Mode = 3bLn3 or 3bLL3

PM130 PLUS Powermeters Series

25

Chapter 2Installation

2.5 I/O Connections


Before I/O Module installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.

Figure 2-16. Module with Cover Before Module Assembly For I/O ratings, see Technical Specifications in Appendix A.

2.5.1

4DI/2DO Module

Figure 2-17. 4DI/2DO Module Assembly

2.5.1.1 Relay Outputs


There are two relay outputs provided for energy pulsing, alarms, or remote control.

Figure 2-18. Relay Output Connection

26

PM130 PLUS Powermeters Series

Chapter 2Installation

2.5.1.2 Digital Inputs


Four optically isolated status inputs are provided for status monitoring, pulse counting, external power demand period, and time synchronization.

Figure 2-19. Digital Input Connection

2.5.2

4AO Module - Analog Outputs


The 4AO module has four optically isolated analog outputs with an internal power supply and current output options of 0-20 mA and 4-20 mA (current loop load of up to 500 Ohm), 0-1 mA and 1 mA (current loop load of 10 kOhm).

Figure 2-20. Analog Output Connection

PM130 PLUS Powermeters Series

27

Chapter 2Installation

2.5.3

TOU RTC and 4 Digital Inputs


The TOU provides a battery-operated real time clock (RTC) with four optically isolated inputs for status monitoring, time synchronization, pulse counting, and external power demand period.

2.5.3.1 Digital Inputs

Figure 2-21. TOU Digital Input Connection

2.5.3.2 TOU Battery Replacement

WARNING!
Only qualified personnel familiar with the instrument and its associated electrical equipment must perform the RTC battery backup replacement. To replace the CR1632 RTC battery: 1. Remove the TOU module from the PM130 PLUS compartment Open the TOU MODULE case by applying a flat screwdriver at three snap-in slit (1, 2 and 3), as shown in Figure 2-22. Remove the old battery by lifting up the battery holder retractable tab. Place the new CR1632 battery into the battery holder while holding up the battery holder retractable tab in such a way that the (+) battery pole is toward

2.

3.

4.

28

PM130 PLUS Powermeters Series

Chapter 2Installation

the battery holder, as shown in Figure 2-22.

Figure 2-22. TOU RTC Battery Replacement

2.6 Communications Connections


Before installing the Communication Module, ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment. Several communication options are available for the PM130: COM1: COM1 RS-485 COM2: COM2 Ethernet 10/100BaseT

A connection to the Ethernet connector is made through a cable adaptor provided with your meter. A full description of the communication protocols is found in the PM130 protocol guides that come with your meter.

PM130 PLUS Powermeters Series

29

Chapter 2Installation

2.6.1

COM1 RS-485 Connection

Figure 2-23. COM1 RS-485 2-Wire Connection The connector is removable with a captured-wire and 3 terminals.

30

PM130 PLUS Powermeters Series

Chapter 2Installation

2.6.2

COM2 Ethernet Connection

Figure 2-24. COM2 Ethernet Connection

PM130 PLUS Powermeters Series

31

Chapter 3Display Operations

Chapter 3 Display Operations


This chapter provides PM130 PLUS Power meter series front panel information, default settings, and operating procedures.

Figure 3-1: PM130 PLUS Unit

3.1 Indicators and Controls


3.1.1 Device Diagnostics
After applying power to the meter, a one-digit start-up diagnostic code is shown for 1 second on all LEDs. Code 8 indicates a normal power-up sequence. You can observe the list of device diagnostic codes recorded during restart and meter operation via the Status Display. When the meter records a diagnostic message, the diagnostic i LED flashes until you reset the device diagnostics via the Status Display. The diagnostic LED can be disabled or enabled via the Display Setup menu.

3.1.2

Numeric LED Display


The meter has a simple user interface that allows you to view numerous measurement parameters by scrolling through different display pages. The numeric LED display shows up to three parameters at a time. Small rectangular or round LEDs at the right and below the display indicate the displayed parameters and their measurement units. The display layout may change depending on the meter type and mode of operation.

32

PM130 PLUS Powermeters Series

Chapter 3Display Operations

There are three modes of display operation: Data display Status display Programming mode display.

3.1.3

Load Bar Graph


The load bar graph displays the amount, in percent (40% to 110%), of the present current load with respect to user-defined nominal load current. The reference nominal current can be set up in amps through the Display Setup menu. If it is set to 0 (default), the current load is referenced to the specified CT primary current.

3.1.4

Energy Pulse LED


The PM130EH has a red Energy Pulse LED. It flashes at a constant rate when a load is applied to the meter. There are two modes of LED operation: Normal mode: mode the LED pulses indicate imported Wh at a rate of 1,000 pulses per kWh Test mode: mode the LED pulses indicate either imported Wh, or imported (inductive) varh at a rate of 10,000 pulses per kWh/kvarh The energy test mode can be enabled through the Device Options menu. When in test mode, the energy and demand accumulators do not account for consumed energy.

3.1.5

Port Activity LEDs


The meter has two green LEDs RX and TX, which indicate activity on the COM1 communication port. The LEDs flash when the port is receiving or transmitting data.

3.1.6

Navigation Buttons
The PM130 is provided with six push buttons that are normally used to navigate between different measurement displays. In programming mode, the buttons access the device setup menus where the default factory-set device settings can be changed.

PM130 PLUS Powermeters Series

33

Chapter 3Display Operations

3.2 Data Display


In data mode, the display is normally updated once every second. You can adjust the display update rate via the Display Setup menu.

3.2.1

Display Features

3.2.1.1 Measurement Units


The PM130 has a selectable resolution for volts, amps and powers presented on the front display and via communications. See Device Options in Chapter 3 for information on selecting the data resolution in the PM130. Low Resolution Option Currents are displayed in whole amperes below 10,000 A, and in kilo amperes above 10,000 A. Measurement units for voltage and power depend on the voltage connection scheme: For direct wiring (PT=1) or wiring via PT with the PT ratio up to and including 4.0, voltages are displayed in volts, and power in kilowatts. For the PT ratio above 4.0, voltages are displayed in kilovolts with three decimal places, and power in megawatts with three decimal places.

High Resolution Option Currents are displayed in amperes with up to two decimal places below 10,000 A, and in kilo amperes above 10,000 A. Measurement units for voltage and power depend on the voltage connection scheme: When direct wiring is used (PT=1), voltages are displayed in volts with one decimal place, and power in kilowatts with three decimal places. When wiring via PT is used with the PT ratio up to and including 4.0, voltages are displayed in volts, and power in whole kilowatts. For the PT ratio above 4.0, voltages are displayed in kilovolts with three decimal places, and power in megawatts with three decimal places.

The small round Kilo and Mega LEDs light up showing the appropriate measurement units for a displayed page.

3.2.1.2 Primary and Secondary Volts


Volts can be displayed in primary (default) or secondary units. The volts display mode can be changed through the Display Setup menu.

3.2.1.3 Phase Power Readings


In configurations with the neutral wire, in addition to total three-phase powers, the meter can show per-phase power readings. By default, they are disabled. See Display Setup on how to enable per-phase power readings in your meter.

34

PM130 PLUS Powermeters Series

Chapter 3Display Operations

3.2.1.4 Fundamental Component


The PM130EH can display total displacement power factor and active power for the fundamental component if it is enabled through the Display Setup menu. When phase power readings are allowed, the PM130EH also displays perphase displacement power factor and active power for the fundamental component.

3.2.1.5 Auto Return


If no buttons are pressed for 30 seconds while the display Auto Return option is enabled, the display automatically returns to the main screen from any other measurement display. The Auto Return option can be enabled through the Display Setup menu.

3.2.1.6 Auto Scroll


If no buttons are pressed for 30 seconds while in the common measurements display, and the Auto Scroll option is enabled in the meter, the display automatically scrolls through all available pages. The scroll interval can be adjusted through the Display Setup menu. To stop auto scrolling, press briefly the UP or DOWN button.

3.2.1.7 Brightness
The PM130 display has a 3-level adjustable brightness. It is normally preset at the factory to the highest level. You can adjust the display through the Display Setup menu.

3.2.2

Navigation Buttons

Figure 3-2: Navigation Buttons In Data Display mode, the navigation buttons function as follows. The MAX/MIN button switches to the Min/Max and Maximum Demands display pages. When briefly pressed again, it switches back to the common measurements display. The H/ESC button in the PM130EH switches between the Total Harmonics and Individual Harmonics pages. When briefly pressed once again, it switches back to the common measurements display. The UP and DOWN arrow buttons, labeled by arrowheads, scroll forwards and backwards through the display pages. Pressed briefly, they move one page forward or backward. If you hold down the button, the display pages are scrolled at a rate of twice per second. Pressing both the UP and DOWN arrow buttons together will return you to the first page within the current display.

PM130 PLUS Powermeters Series

35

Chapter 3Display Operations

The SELECT button operates once it is released. The button has two functions: When pressed briefly, it switches to programming mode. When pressed together with the ENTER button for more than 5 seconds, it resets Min/Max registers, maximum demands, or energies depending on the currently displayed page. If the meter is password protected and a simple reset of data from the display is not allowed, the action has no effect. The ENERGY button switches to the Energy display in the PM130EH. In the PM130P, the button is not operational. If TOU registers are configured in the meter, you can repeatedly press this button to scroll through all available TOU registers. When briefly pressed once again, it switches back to the common measurements display:

3.2.3

Simple Reset of Accumulated Data


You can reset the Min/Max registers, maximum demands and energies from the data display mode without accessing the reset menu. This is accomplished by using the simple two-button reset option if the meter is not password protected or the meter security is overridden by the twobutton reset mode setting, see Display Setup: 1. Select a display page where the data you want to reset is displayed: Min/Max log: log select a Min/Max page from the Min/Max Display Ampere and volt maximum demands: demands select the Ampere or Volt maximum demand page from the Min/Max Display. Power maximum demands: demands select the power maximum demand page from the Min/Max Display. Total and phase energies: energies select a total energy, or phase energy page from the Energy Display. 2. While holding the SELECT button down, press and hold the ENTER button for about 5 seconds. The displayed data is reset to zero.

3.2.4

Common Measurements Display


Scroll through pages with the UP and DOWN arrow buttons.

Table 3: Common Measurements (Main Display)


1 L 2 P 3 V12 V23 V31 V1 V2 V3 I1 I2 I3 Line-to-line volts

Line-to-neutral volts (in 4LN3, 3LN3, 3BLN3 configurations) Amps

36

PM130 PLUS Powermeters Series

Chapter 3Display Operations

kVA/MVA PF kW/MW In Hz kvar/Mvar Ph.L1 PF kW/MW kVA/MVA Ph.L1 kvar/Mvar Ph.L2 PF kW/MW kVA/MVA Ph.L2 kvar/Mvar Ph.L3 PF kW/MW kVA/MVA Ph.L3 kvar/Mvar H01 PF kW/MW H1.L1 PF kW/MW H1.L2 PF kW/MW H1.L3 PF kW/MW U.Unb V% unb

Total VA Total PF Total W Neutral current Frequency Total var Phase L1 powers (if enabled) Phase L1 powers (if enabled) Phase L2 powers (if enabled) Phase L2 powers (if enabled) Phase L3 powers (if enabled) Phase L3 powers (if enabled) Fundamental total powers (PM130EH, if enabled) Fundamental phase L1 powers (PM130EH, if enabled) Fundamental phase L2 powers (PM130EH, if enabled) Fundamental phase L3 powers (PM130EH, if enabled)

10

11

12

13

14

15

16

Voltage unbalance, percent

17

C.Unb I% unb Current unbalance, percent

3.2.5

Min/Max and Maximum Demand Display

Figure 3-3: MAX/MIN Button 1. Press the MAX/MIN button. The MIN, MIN MAX, MAX or MAX DMD LED is illuminated when in the MIN/MAX display.

PM130 PLUS Powermeters Series

37

Chapter 3Display Operations

2.

Use the UP and DOWN arrow buttons to scroll through the Min/Max and Max. Demand pages.

Note that Volts readings are line-to-neutral in 4LN3, 3LN3 and 3BLN3 wiring modes, and line-to-line in other modes.

Table 4: Min/Max and Maximum Demands


1 MIN V1/V12 V2/V23 V3/V31 I1 I2 I3 kVA/MVA PF kW/MW In Hz kvar/Mvar V1/V12 V2/V23 V3/V31 I1 I2 I3 kVA/MVA PF kW/MW In Hz kvar/Mvar V1/V12 V2/V23 V3/V31 I1 I2 I3 kVA/MVA PF kW/MW Minimum volts

MIN

Minimum amps

MIN

Minimum total VA Minimum total PF (absolute) Minimum total W Minimum neutral current Minimum frequency Minimum total var Minimum volts

MIN

MAX

MAX

Maximum amps

MAX

Maximum total VA Maximum total PF (absolute) Maximum total W Maximum neutral current Maximum frequency Maximum total var Maximum volt demands

MAX

MAX DMD MAX DMD MAX DMD

10

Maximum ampere demands

11

Maximum VA demand PF at maximum VA demand Maximum W demand

3.2.6

Harmonics Display

Figure 3-4: H/ESC Button 1. Press the H/ESC button in the PM130EH. The THD/TDD LED is illuminated.

38

PM130 PLUS Powermeters Series

Chapter 3Display Operations

2.

Use the UP and DOWN arrow buttons to scroll through total harmonics measurements. Press the H/ESC button again to move to the individual harmonics.

3.

Note that voltage harmonics readings are line-to-neutral in the 4LN3, 3LN3, 3BLN3 wiring modes, and line-to-line in all other modes.

Table 5: Total Harmonics


1 thd. 2 thd. 3 tdd. 4 HF V1/V12 THD V2/V23 THD V3/V31 THD I1 THD I2 THD I3 THD I1 TDD I2 TDD I3 TDD I1 K-Factor I2 K-Factor I3 K-Factor Voltage THD

Current THD

Current TDD

Current K-Factor

Table 6: Individual Voltage Harmonics


1 3. 2 5. 19 39. V1/V12 HD% V2/V23 HD% V3/V31 HD% V1/V12 HD% V2/V23 HD% V3/V31 HD% V1/V12 HD% V2/V23 HD% V3/V31 HD% Order 3 harmonic distortion

Order 5 harmonic distortion

Order 39 harmonic distortion

Table 7: Individual Current Harmonics


1 3. 2 5. 19 39. I1 HD% I2 HD% I3 HD% I1 HD% I2 HD% I3 HD% I1 HD% I2 HD% I3 HD% Order 3 harmonic distortion

Order 5 harmonic distortion

Order 39 harmonic distortion

3.2.7

Energy Display

Figure 3-5: Energy Button 1. Press the ENERGY button.

PM130 PLUS Powermeters Series

39

Chapter 3Display Operations

The kVAh, kvarh, or kWh LED is illuminated. 2. If TOU registers are configured in the meter, press the button again to scroll through all active TOU registers. Use the UP and DOWN arrow buttons to scroll through energy pages.

3.

Along with total energies, per phase energy accumulators are displayed if phase energy calculation is enabled in the Device Options menu.

Table 8: Total and Phase Energies


1 Ac.i 1234 56789 rE.i 1234 56789 AP. 1234 56789 Ac.E 1234 56789 rE.E 1234 56789 Ac.i 1 1234 56789 rE.i 1 1234 56789 AP. 1 1234 56789 Ac.i 2 1234 56789 rE.i 2 1234 56789 AP. 2 1234 56789 Ac.i 3 1234 56789 rE.i 3 1234 56789 AP. 3 1234 56789 Total kWh import

Total kvarh import

Total kVAh

Total kWh export

Total kvarh export

Phase L1 kWh import

Phase L1 kvarh import

Phase L1 kVAh

Phase L2 kWh import

10

Phase L2 kvarh import

11

Phase L2 kVAh

12

Phase L3 kWh import

13

Phase L3 kvarh import

14

Phase L3 kVAh

40

PM130 PLUS Powermeters Series

Chapter 3Display Operations

Table 9: TOU Energy Register 1


1 r1.t1 1234 56789 r1.t2 1234 56789 r1.t4 1234 56789 Tariff 1 reading kWh Tariff 2 reading kWh Tariff 4 reading kWh

Table 10: TOU Energy Register 4


1 r4.t1 1234 56789 r4.t2 1234 56789 r4.t4 1234 56789 Tariff 1 reading kWh Tariff 2 reading kWh Tariff 4 reading kWh

3.3 Status Display


The meter has a separate status information display accessible through the primary device menu. For information on navigating in the menus, see Using the Menus. The Status Display shows rarely used information that is especially helpful for troubleshooting or when connecting the meter to an external equipment. To access the Status Display: 1. From the Data Display menu, press the SELECT button to access the primary device menu. The StA window is highlighted. 3. Press ENTER to access the Status Display. Use the UP and DOWN arrow buttons to scroll through the status pages.

4.

PM130 PLUS Powermeters Series

41

Chapter 3Display Operations

Figure 3-6: Status Display To exit the Status Display: 1. 2. Press ESC to return to the primary device menu. Press ESC to return to the Data display.

Table 11: Status Display Parameters


1 PhS rot POS/nEG/Err V1 angle V2 angle V3 angle I1 angle I2 angle I3 angle rEL 1.2 00 St.In 1.2.3.4 0000 Cnt.1 <hour> 12345 Cnt.2 <hour> 12345 Cnt.3 <hour> 12345 Cnt.4 <hour> 12345 Alar SP.<Setpoint Number> <Alarm Trigger > diAG <Diagnostic Code> <Diagnostic Message> SEr.n 1 Phase rotation order

2 A. 3 A. 4

Voltage angles (180, referenced to V1) Current angles (180, referenced to V1) Relay status (with a digital I/O module) Status inputs (with a digital I/O module) Counter #1 value (a time counter in 0.1 hour units) Counter #2 value (a time counter in 0.1 hour units) Counter #3 value (a time counter in 0.1 hour units) Counter #4 value (a time counter in 0.1 hour units) Setpoint alarms (see Alarm Display below)

10

11

Device diagnostics (see Diagnostics Display below) Device serial number

12

42

PM130 PLUS Powermeters Series

Chapter 3Display Operations

23456 13 SoFt 11. 01.01 Firmware version number

3.3.1

Pulse and Time Counters


The 5-digit meter counters count setpoint events, external pulses, or setpoint operation time. Time counters have the hour label in the middle window and display the setpoint operation time at a 0.1-hour resolution. See Using Time Counters in Chapter 4 for information on programming time counters. You can clear a counter using the simple two-button reset option if the meter is not password protected, or if the meter security is overridden by the two-button reset mode setting (see Display Setup). To clear a counter: counter: 1. Select a counter page. 2. While holding the SELECT button, press and hold the ENTER button for about 5 seconds. The displayed data is reset to zero.

3.3.2

Alarm Display
The alarm display shows a list of operated alarm setpoints along with the alarm trigger labels if there are alarms recorded during meter operation. Use the UP and DOWN arrow buttons to scroll through the alarm list. The setpoint status is latched into a non-volatile register, which is not affected by loss of power and may only be cleared via communications or from the meter display. To clear alarms: 1. 2. Select an alarm page. While holding the SELECT button, press and hold the ENTER button for about 5 seconds until the alarm code is reset to none.

3.3.3

Diagnostics Display
The diagnostics display shows a list of the device diagnostic codes recorded as a result of the meter self-test diagnostics during start-up and operation. When there are recorded diagnostic messages, the i diagnostic LED on the front display briefly flashes two times to indicate that the meter may require servicing. The diagnostic LED can be disabled or enabled via the Display Setup menu. Use the UP and DOWN arrow buttons to scroll through the diagnostic message list. See Device Diagnostic Codes in Appendix F for the list of diagnostic codes and their meanings.

PM130 PLUS Powermeters Series

43

Chapter 3Display Operations

Frequent hardware failures may be the result of excessive electrical noise in the region of the device. If the meter continuously resets itself, contact your local distributor. A configuration reset may also be a result of the legal changes in the meter configuration when other configuration data is affected by the changes. The diagnostics codes are stored in a non-volatile register, which is not affected by loss of power and may be cleared via communications (see Device Diagnostics in Chapter 4) or from the meter display. To clear the meter diagnostics: 1. Select a diagnostics page. 2. While holding the SELECT button, press and hold the ENTER button for about 5 seconds until the diagnostic message is reset to none. none

3.4 Using the Menus


3.4.1 Navigation Buttons

Figure 3-7: Navigation Buttons The PM130 has a menu-driven setup. To access the menus, press and release the SELECT button. The SELECT button selects (highlights) an active window in which you can select or change a required menu item. The button operates once it is briefly pressed and released. The UP and DOWN arrow buttons scroll through menu items in the highlighted window forwards and backwards. It allows changing a highlighted item when entering numbers. The ENTER button confirms the selection of a menu item or a number in the highlighted window, thus allowing to access a submenu or to store a changed item. The ESC button is Escape leaving the highlighted item unchanged or returning to the upper level menu.

3.4.2

Selecting Menus
To access the meter menus, press and release the SELECT button. The primary meter menu is displayed as shown in Figure 3-8. The menu has three entries: StA: StA Status Display entry (see the Status Display section) OPS: PS Main setup menu entry allowing to review setup options CHG: CHG Main setup menu entry allowing to change setups

44

PM130 PLUS Powermeters Series

Chapter 3Display Operations

Figure 3-8: Menu Entries To access the Status Display: 1. If the StA window is not highlighted, use the SELECT button to activate it. Press the ENTER button to access the Status Display

2.

To review the meter setup options: 1. 2. Press the SELECT button to activate the OPS window. Press the ENTER button to access the main menu.

To change the meter meter setup, or to clear the accumulated values: 1. 2. Press the SELECT button to activate the CHG window. Press the ENTER button to access the main menu.

3.4.3

Entering the Password


The Setup Change menu can be secured by a four-digit user password. The meter is primarily shipped with the password preset to 0 and password protection disabled. You can change the password and enable password protection through the Access Control menu (see the Meter Security section). If authorization is not required, just press the ENTER button to move to the Main menu; otherwise you should enter a correct password to be authorized to access the meter setup.

Figure 3-9: Meter Setup To access the password: 1. 2. 3. 4. Adjust the first digit with the UP and DOWN arrow buttons. Press the SELECT button to advance to the next digit. Adjust the remaining password digits in the same manner. Press ENTER to confirm the password.

PM130 PLUS Powermeters Series

45

Chapter 3Display Operations

If the password entered is correct, move to the Main menu, otherwise return to the previous menu. Selecting the OPS or CHG entry moves you to the Main menu that is represented by two entries: the upper window displays a secondary menu list the bottom item acts as an assisting exit window.

46

PM130 PLUS Powermeters Series

Chapter 3Display Operations

3.4.4

Selecting a Menu Entry


To select a menu entry from the menu list: 1. Highlight the upper item by pressing the SELECT button.

Figure 3-10: Selecting a Menu Entry 2. Scroll through the menu list by pressing briefly the UP and DOWN arrow buttons until the required menu entry appears. Press the ENTER button.

3.

3.4.5

Viewing and Changing Setup Items


A second level menu normally consists of three items: the upper static window - indicates the menu name the middle window - represents a list of setup parameters you can scroll through the lower item - shows the present parameter value.

To select a parameter you want to to view or change: 1. Highlight the middle window by pressing the SELECT button.

Figure 3-11: Selecting a Parameter 2. Scroll through the parameter list with the UP and DOWN buttons until the required parameter name appears.

To change the selected parameter: 1. Press the SELECT button to highlight the lower item.

Figure 3-12: Changing a Parameter

PM130 PLUS Powermeters Series

47

Chapter 3Display Operations

2.

Adjust the number to the required value with the UP and DOWN arrow buttons if a number represents the parameter. When briefly pressed, the button increments or decrements the number by one. When the button is pressed continuously, the number is changed approximately twice per second.

3.

If a name represents the parameter, select the required option with the UP and DOWN arrow buttons. To store your new selection, press the ENTER button. To leave the parameter unchanged, press the ESC button. Return to the parameter list to select another parameter or return to the main menu. Press ESC to exit the menu.

4. 5. 6.

7.

3.5 Menu Operations


3.5.1 Basic Device Settings

Figure 3-13: Basic Device Settings The Basic Device Settings menu allows you to configure the basic meter settings that define the general operating characteristics of the device. To access the Basic Device Settings menu: menu: 1. Select the baSc entry from the main menu. Press the ENTER button.

2.

To select a setup option: 1. Press the SELECT button to activate the middle window. 2. Use the UP and DOWN arrow buttons to scroll to the required option. To change the option: 1. Press the SELECT button to activate the lower window. 2. Use the UP and DOWN arrow buttons to select the required option. 3. Press ENTER to confirm your changes and to store your new setting or press ESC to discard changes.

48

PM130 PLUS Powermeters Series

Chapter 3Display Operations

To exit the menu, press ESC.

Table 12 lists the Basic Device Settings options.

Table 12: Available Options


Label ConF Parameter Wiring connection (configuration) mode PT ratio Options See Basic Default 4Ln3 Description The wiring connection of the device The phase potential transformers primary to secondary ratio PT Ratio multiplication factor. Used in extra high voltage networks to accommodate the PT ratio for 500 kV and higher networks. The primary rating of the phase current transformer The length of the demand period for power demand calculations. If the external synchronization is selected, a pulse front on the digital input DI1 denotes the start of the demand interval. The number of blocks to be averaged for sliding window demands The length of the demand period for ampere, volt and THD demand calculations The nominal line frequency The maximum demand load current (0 = CT primary)

Meter Setup
in Chapter 4 1.0-6500.0 1.0

Pt

Pt.F

PT Ratio multiplier

1, 10

Ct d.P

CT primary current Power block demand period EH

1-50000 A 1, 2, 5, 10, 15, 20, 30, 60 min, E=external sync

5A 30 min

nd.P

The number of blocks in 1-15 the sliding window EH Ampere and volt demand period Nominal frequency Maximum demand load current 0-1800 sec

Ad.P

900 sec

Freq LoAd

50,60,25, 400 Hz 0-50000 A

60 Hz 0

Always specify the wiring mode and transformer ratings prior to setting up setpoints and analog outputs. The maximum value for the product of the phase CT primary current and PT ratio is 57,500,000. If the product is greater, power readings are zeroed.

3.5.2

Device Options

Figure 3-14: Device Options The Device Options menu allows changing user-configurable device options or putting the meter into energy test mode.

PM130 PLUS Powermeters Series

49

Chapter 3Display Operations

To access the Device Options menu: 1. Select the OPtS entry from the main menu. Press the ENTER button.

2.

To select a setup option: 1. 2. Press the SELECT button to activate the middle window. Use the UP and DOWN arrow buttons to scroll to the required option.

To change the option: 1. 2. 3. Press the SELECT button to activate the lower window. Use the UP and DOWN arrow buttons to select the required option. Press ENTER to confirm changes and to store new settings or press ESC to discard changes.

To exit the menu, press ESC.

Table 13 lists available options.

Table 13: Available Device Options


Label P.cAL Parameter Power calculation mode Options Default Description The method used for calculating reactive and apparent powers. See

rEAc (reactive power), Reactive nAct (non-active power)

Power Calculation Modes in Chapter 4


The value at which energy counters roll over to zero

roLL

Energy roll value EH

10.E4=10,000 10.E5=100,000 10.E6=1,000,000 10.E7=10,000,000 10.E8=100,000,000 10.E9=1,000,000,000 diS = disabled En = enabled 1.5-5.0%

10.E8

Ph.En U.Str

Phase energy option EH Starting voltage

Disabled 1.5

Enables phase energy calculations The device starting voltage in percent of FS (120V or 400V) The maximum voltage scale allowed. See Data Scales in Appendix E

U.ScL

Voltage scale, secondary volts

10-828 V

144 V

C.ScL

Current scale, 1.0-10.0 A secondary amps Device resolution Lo Hi

2 CT The maximum current secondary scale allowed. See Data Scales in Appendix E Lo The voltage, current and power resolution on the front display (see Measurement Units in Chapter 3) and in communications (see the appropriate section in the communication guides)

rESL

50

PM130 PLUS Powermeters Series

Chapter 3Display Operations

Label tESt

Parameter Energy test mode EH

Options OFF = disabled Ac.Ei = Wh pulses rE.Ei = varh pulses

Default Disabled

Description Setting this option puts the meter into the energy test mode

3.5.3

Communication Ports

Figure 3-15: Communication Ports Options The Communication Ports Options menus allow you to configure parameters for communication ports COM1 and COM2. To access the menu: 1. Select Prt.1 for COM1 or Prt.2 for COM2 from the main menu 2. Press the ENTER button. To select a setup option: 1. Press the SELECT button to activate the middle window. 2. Use the UP and DOWN arrow buttons to scroll to the required option. To change the option: 1. Press the SELECT button to activate the lower window. 2. Use the UP and DOWN arrow buttons to select the required option. 3. Press ENTER to confirm changes and to store new settings or press ESC to discard changes. 4. Press ESC to exit the menu.

Table 14 and Table 15 list COM port settings.

Table 14: COM1 Settings


Label Prot Parameter Options Default Modbus RTU Description The communications protocol supported by the port

Communications ASCII = SATEC ASCII protocol rtu = Modbus RTU dnP3 = DNP3 Port interface Device address 485 = RS-485 SATEC ASCII: 0-99 Modbus RTU: 1-247 DNP3: 065532 300-115200 bps

rS Addr

RS-485 1 Device network address The port baud rate 7E data format should not be used with the Modbus RTU and DNP3 protocols

bAud dAtA

Baud rate

9600 bps 8N

Data format and 7E, 8N, 8E parity

PM130 PLUS Powermeters Series

51

Chapter 3Display Operations

Table 15: COM2 Settings


Label Prot Parameter Options Default Modbus/TCP Description The communications protocol supported by the port Not changeable; automatically detected by the meter Device network address

Communications rtu = Modbus/TCP protocol1 dnP3 = DNP3/TCP Port interface Eth.= Ethernet

rS

Eth.

Addr

Device address

Modbus: 1-247 DNP3: 065532

3.5.4

Network Address

Figure 3-16: Network Address The Network Address entry appears only if the meter is ordered with the optional optional Ethernet module. The Network Address menu allows you to configure the device IP address and the default gateway address for the Ethernet port. To access the Network Address menu: 1. Select nEt from the main menu. 2. Press the ENTER button. To change the the IP Address and Default Gateway: 1. To change the device IP address, select the A entry in the upper window using the UP and DOWN arrow buttons. To change the default gateway address, select the G entry. Press the SELECT button to activate the first address digit. Use the UP and DOWN arrow buttons to adjust the digit. Press the SELECT button to advance to the next digit.

2. 2. 3. 4.

Selecting the DNP3 protocol on the Ethernet port launches the DNP3/TCP server along with the Modbus/TCP server. This allows simultaneous connections on both TCP ports. Selecting the Modbus protocol for the port disables the DNP3/TCP server.

52

PM130 PLUS Powermeters Series

Chapter 3Display Operations

5. 6.

Adjust the remaining address digits. Press ENTER to confirm the new setting or press ESC to discard changes. Press ESC to exit the menu.

7.

3.5.5

Digital Input Setup

Figure 3-17: Digital Input Setup The Digital Input Setup option appears only if the meter is ordered with the optional digital I/O module. To access the Digital Input Setup menu: 1. Select the dinP entry from the main menu. 2. Press the ENTER button. 3. Use the UP and DOWN arrow buttons to scroll to the required digital input. To select a digital input parameter: 1. Press the SELECT button to activate the middle window. 2. Use the UP and DOWN arrow buttons to scroll to the required parameter. To change the parameter value: 1. Press the SELECT button to activate the lower window. 2. Use the UP and DOWN arrow buttons to select the required value. 3. Press ENTER to confirm the new parameter setting or press ESC to discard changes. 4. You are returned to the middle window to select and configure another parameter or confirm the settings and exit the menu.

PM130 PLUS Powermeters Series

53

Chapter 3Display Operations

To store your new settings: 1. Press the ENTER button when the middle window is highlighted. 2. You are returned to the upper window to select another digital input or exit the menu. 3. press ESC to exit the menu.

Table 16 lists available digital setup options.

Table 16: Available Digital Setup Options


Label PuLS Parameter Pulse input mode Options PLS.A = Pulse mode PLS.C = KYZ mode Default PLS.A Description In pulse mode, either leading, or trailing edge of the input pulse is recognized as an event. In KYZ mode, both leading and trailing edges of the input pulse are recognized as separate events. For the normal polarity, the open to closed transition is considered a pulse. For the inverting polarity, the closed to open transition is considered a pulse. It has no meaning in KYZ mode where both transitions are used. The amount of time while the state of the digital input should not change to be recognized as a new state. Too low debounce time could produce multiple events on the input change.

Polr

Pulse polarity

nor = Normal (N.O.) InS = Inverting (N.C.)

nor

dbnc

Debounce time

1-100 ms

10 ms

54

PM130 PLUS Powermeters Series

Chapter 3Display Operations

3.5.6

Relay Output Setup

Figure 3-18: Relay Output Setup The Relay Output Setup entry appears only if the meter is ordered with the optional digital I/O module. To access the Relay Output Setup menu: 1. Select the rEL entry from the main menu. Press the ENTER ENTER button. Use the UP and DOWN arrow buttons to scroll to the required relay.

2. 3.

To select a relay parameter: 1. 2. Press the SELECT button to activate the middle window. Use the UP and DOWN arrow buttons to scroll to the required parameter.

PM130 PLUS Powermeters Series

55

Chapter 3Display Operations

To change the parameter parameter value: 1. 2. 3. Press the SELECT button to activate the lower window. Use the UP and DOWN arrow buttons to select the required value. Press ENTER to confirm the new parameter setting or press ESC to discard changes. You are returned to the middle window to select and configure another parameter or confirm the settings. Exit the menu.

4.

5.

To store your new settings: 1. 2. Press the ENTER button when the middle window is highlighted. You are returned to the upper window to select another relay or exit the menu. Press ESC to exit the menu.

3.

Table 17 lists available relay options.

Table 17: Available Digital Input Options


Label tYPE Parameter Operation mode Options UnLt = Unlatched Ltch = Latched PLS.A = Pulse PLS.C = KYZ pulse Default UnLt Description See Using Relay Outputs in

Chapter 4

Polr

Polarity

nor = Normal (N.O.) nor InS = Inverting (N.C.) 20-1000 ms 100 ms

See Using Relay Outputs in Chapter 4 The actual pulse width is a multiple of the 1-cycle time rounded to the nearest bigger value. The pause time between pulses is equal to the pulse width. Links a pulse relay to the internal energy pulse source. The relay must be set into either pulse, or KYZ mode.

PuLS

Pulse width

Src

Pulse source

nonE Ac.Ei = kWh IMP Ac.EE = kWh EXP rE.Ei = kvarh IMP rE.EE = kvarh EXP rE.Et = kvarh TOT AP.Et = kVAh 0.1-1000.0

NONE

Unit

Pulse rate, kWh/Pulse

1.0 kWh/Pulse

Defines the pulse weight in kWh units per pulse

56

PM130 PLUS Powermeters Series

Chapter 3Display Operations

3.5.7

Counters Setup

Figure 3-19: Counters Setup The Counters Setup entry appears only if the meter is ordered with the optional digital I/O module. The PM130 has four six-digit counters that can count pulses delivered through the device digital inputs with a programmable scale factor. The Counters Setup menu allows linking digital inputs to the counters and defining a pulse multiplier for each counter. To access the Counters Setup menu: 1. Select the Cnt entry from the main menu. 2. Press the ENTER button. 3. Use the UP and DOWN arrow buttons to scroll to the required counter. To select a counter parameter: 1. Press the SELECT button to activate the middle window. 2. Use the UP and DOWN arrow buttons to scroll to the required parameter. To change the parameter value: 1. Press the SELECT button to activate the lower window. 2. Use the UP and DOWN arrow buttons to select the required value. 3. Press ENTER to confirm the new parameter setting or press ESC to discard changes. 4. You are returned to the middle window to select and configure another parameter, or confirm the settings. 5. Exit the menu. To store your new settings: 1. When the middle window is highlighted, press the ENTER button. 2. You are returned to the upper window to select another counter or exit the menu. 3. Press ESC to exit the menu.

PM130 PLUS Powermeters Series

57

Chapter 3Display Operations

Table 18 lists available counter options.

Table 18: Available Counter Options


Label InP Parameter Pulse source input Options Default Description Links a digital input to the counter

None = disabled None di.1 = DI1 di.2 = DI2 di.3 = DI3 di.4 = DI4 1-9999 1

SCAL

Multiplier

The value added to the counter when a pulse is detected on the pulse source input

3.5.8

Alarm/Control Setpoints Setup

Figure 3-20: Alarm/Control Setpoints Setup

58

PM130 PLUS Powermeters Series

Chapter 3Display Operations

The PM130 provides 16 alarm/control setpoints with programmable operate and release delays. See Using Control Setpoints in Chapter 4 for more information on setpoints operation. To access the setpoint setup menu: 1. Select the SEtP entry from the main menu. Press the ENTER button.

2.

3. Use the UP and DOWN arrow buttons to scroll to the required setpoint. To select select a setpoint parameter: 1. 2. Press the SELECT button to activate the middle window. Use the UP and DOWN arrow buttons to scroll to the required parameter.

To change the parameter value: 1. 2. 3. Press the SELECT button to activate the lower window. Use the UP and DOWN arrow buttons to select the required value. Press ENTER to confirm the new parameter setting or press ESC to discard changes. You are returned to the middle window to select and configure another parameter or confirm the setpoint settings. Exit the menu.

4.

5.

To store your new setpoint settings after you configured all setpoint parameters: 1. 2. Press the ENTER button when the middle window is highlighted. You are returned to the upper window to select another setpoint or to exit the menu.

3. Press ESC to exit the menu.

Table 19 lists available setpoint options. For a list of available setpoint triggers and actions, see the Using Control Setpoints section in Chapter 4.

Table 19: Available Setpoints Options


Label TriG Parameter Trigger parameter Operate limit Options See Appendix C Description The analog or digital value that is used as an argument in a logical expression The threshold (in primary units) at which the conditional expression would be evaluated to true. Not applicable for digital triggers. The threshold (in primary units) at which the conditional expression would be evaluated to false. Defines the hysteresis for analog triggers. Not applicable for digital triggers.

On

OFF

Release limit

PM130 PLUS Powermeters Series

59

Chapter 3Display Operations

Label On d

Parameter Operate delay

Options 0-999.9 sec

Description The time delay before operation when the operate conditions are fulfilled The time delay before release when the release conditions are fulfilled The action performed when the setpoint expression is evaluated to true (the setpoint is in operated state)

OFFd Act

Release delay Setpoint action

0-999.9 sec See Appendix C

3.5.9

Analog Outputs Setup

Figure 3-21: Analog Outputs Setup The Analog Outputs Setup entry appears only if the meter is ordered with the optional analog output module. See Programming Analog Outputs in Chapter 4 for more information on configuring analog outputs in your meter. To access the Analog Outputs Setup menu: 1. Select the Aout entry from the main menu. 2. Press the ENTER button. 3. Use the UP and DOWN arrow buttons to scroll to the required analog output. To select the analog output option: 1. Press the SELECT SELECT button to activate the middle window. 2. Use the UP and DOWN arrow buttons to scroll to the required parameter.

60

PM130 PLUS Powermeters Series

Chapter 3Display Operations

To change the parameter value: 1. Press the SELECT button to activate the lower window. 2. Use the UP and DOWN arrow buttons to select the required value. 3. Press ENTER to confirm the new parameter setting or press ESC to discard changes. 4. You are returned to the middle window to select and configure another parameter or confirm the settings. 5. Exit the menu. To store your new settings: 1. Press the ENTER button when the middle window is highlighted. 2. You are returned to the upper window to select another analog output or to exit the menu. 3. Press ESC to exit the menu.

Table 20 lists available analog output options. See Analog Output Parameters in Appendix B for a list of the available output parameters.

Table 20: Available Analog Output Options


Label OutP Parameter Output parameter Zero scale Options See Appendix B Description Selects the measured parameter to be transmitted through the analog output channel. Low engineering scale (in primary units) for the analog output corresponding to a lowest (zero) output current (0 or 4 mA) High engineering scale (in primary units) for the analog output corresponding to a highest output current (1 or 20 mA)

Lo

Hi

Full scale

3.5.10 Display Setup

Figure 3-22: Display Setup The Display Setup menu allows configuring options for the meter display, or running the meter Flash Loader. To access the Display Setup menu: 1. Select the diSP entry from the main menu. 2. Press the ENTER ENTER button.

PM130 PLUS Powermeters Series

61

Chapter 3Display Operations

To select a setup option: 1. Press the SELECT button to activate the middle window. 2. Use the UP and DOWN arrow buttons to scroll to the required option. To change the option: 1. Press the SELECT button to activate the lower window. 2. Use the UP and DOWN arrow buttons to select the required option. 3. Press ENTER to confirm your changes and to save the new setting or press ESC to discard changes. 4. Press ESC to exit the menu.

Table 21 lists available options.

Table 21: Display Setup Options


Label UPdt ScrL Parameter Display update rate Options 0.1-10.0 sec Default 1 sec None Description Defines the interval between display updates Defines the scroll interval for the main data display or disables auto scroll Enables automatic return to the main display if no buttons are pressed for 5 minutes Defines the nominal load (100%) level for the bar graph display Selects primary or secondary units for volts display Disables or enables phase powers in the main display Disables or enables fundamental values in the main display

Auto scroll interval None, 2-15 sec Auto return to the main screen diS = disabled, En = Enabled

rEtn

Enabled

bAr

Reference load current for LED bar graph

0-10,000A (0 = CT primary current)

Uolt

Primary/Secondary Pri, SEc volts units Phase powers display mode diS, En

Primary

Ph.P Fund.

Disabled Disabled

Fundamental diS, En component display mode Date order dnY, ndY, Ynd (d=day, n=month, y=year)

dAtE

mm.dd.yy Defines the date order in the RTC display

rSt

Simple reset mode PASS = password protected En = always enabled Brightness Diagnostic LED Flash Loader call 1-3 diS, En N/A

PASS

PASS = the simple reset is not allowed if password protection is enabled En = enables the simple reset buttons regardless of password protection Sets the LED brightness Enables the diagnostic LED Launches the Flash Loader

brGt diAG SoFt.

3 Disabled N/A

62

PM130 PLUS Powermeters Series

Chapter 3Display Operations

3.5.11 Meter Security


The password in your meter is preset to 0 at the factory, and password protection is disabled. The Access Control menu allows changing the user password and enabling or disabling password protection. To access the menu: 1. Select the AccS entry from the main menu. 2. Press the ENTER button.

Figure 3-23: Accs Entry To change the password: 1. Select the PASS entry in the upper window with the UP and DOWN arrow buttons.

Figure 3-24: PASS Entry 2. Press the SELECT button to activate the first password digit. 3. Use the UP and DOWN arrow buttons to adjust the digit. 4. Press the SELECT button to advance to the next digit. 5. Adjust the remaining password digits. 6. Press ENTER to confirm the new password. The new password is effective for both the display and communication ports. To enable or disable password protection: 1. Select CtrL in the upper window using the UP and DOWN arrow buttons.

Figure 3-25: CtrL Entry 2. Press the SELECT button to activate the middle window.

PM130 PLUS Powermeters Series

63

Chapter 3Display Operations

3. Use the UP and DOWN arrow buttons to select the required option. ON enables password protection and OFF disables password protection. 4. Press ENTER ENTER to confirm your new setting, or ESC to discard changes. 5. Press ESC to exit the menu. When password protection is enabled, you are not able to change the device settings through the display or communications unless you provide a correct password. If you cannot provide a proper password, contact your local distributor for the appropriate password to override password protection.

3.5.12 Setting the Device Clock


The Device Clock menu allows setting up the device clock and configuring the local time zone settings. See Daylight Savings Time in Chapter 4 for more information on the Daylight Savings option. To access the Device Clock menu: 1. Select the rtc entry from the main menu. 2. Press the ENTER button. 3. Use the UP and DOWN arrow buttons from the upper window to select a setup option. To change the time, date, or daylight savings setting: 1. Highlight an item you want to change by pressing briefly the SELECT button. When you access the time setup display, the hours and minutes are frozen allowing you to adjust the time.

Figure 3-26: hour and dAtE Entries 2. Adjust the selected item with the UP and DOWN arrow buttons. 3. Highlight the next item to change and adjust in the same manner. 4. Press ENTER to confirm your changes or press ESC to leave the clock settings unchanged. If you confirm the time change while the seconds are highlighted, the seconds are zeroed; otherwise they stay unchanged. 5. Press ESC to exit the menu.

64

PM130 PLUS Powermeters Series

Chapter 3Display Operations

Table 22 lists available options.

Table 22: Hour, Date, and Day Options


Label hour Option Time Format/Range hh.mm.ss Description The time is displayed as hh.mm.ss, where the hours and minutes are shown in the middle window separated by a dot, and the seconds - in the lower window. The date is displayed as per the user definition, where the first two items are shown in the middle window, and the last one - in the lower window. See Display Setup for instructions on how to select the date format. The day of the week is displayed in the lower window. It is set automatically when you change the date.

dAte

Date

YY.MM.DD, MM.DD.YY, DD.MM.YY

dAY

Day of week

Sun = Sunday on = Monday tuE = Tuesday WEd = Wednesday thu = Thursday Fri = Friday Sat = Saturday

dSt

Daylight savings diS = disabled time option En = enabled

When DST is disabled, the RTC operates in standard time only. When enabled, the device automatically updates the time at 2:00 AM at the pre-defined DST switch dates. The date when Daylight Savings Time begins. The DST switch point is specified by the month, week of the month and weekday. By default, DST starts at 2:00 AM on the first Sunday in April of each year. The date when Daylight Savings Time ends. The DST switch point is specified by the month, week of the month and weekday. By default, DST ends at 2:00 AM on the last Sunday in October of each year. The external port receiving the time synchronization pulses. See Time Synchronization Pulses in Chapter 4.

dSt.S

DST start date

Month-weekweekday Week = 1, 2, 3, 4 or L (last week of the month) Month-weekweekday Week = 1, 2, 3, 4 or L (last week of the month) None di.1 = di.2 = di.3 = di.4 =

dSt.E

DST end date

SYnC

Clock synchronization input

DI1 DI2 DI3 DI4

3.5.13 Resetting Accumulators and Maximum Demands


The Reset menu allows separately resetting minimum/maximum log records, maximum demands and counters.

Figure 3-27: Reset Menu

PM130 PLUS Powermeters Series

65

Chapter 3Display Operations

To access the Reset menu: 1. Select the rst entry from the main menu. Press the ENTER button.

2.

To reset the required registers: 1. Highlight the middle window by pressing briefly the SELECT button. 2. Select the required entry by scrolling through the list with the UP and DOWN arrow buttons until the required entry appears. 3. Press the SELECT button briefly to highlight the lower item. 4. Press and hold the ENTER button for 5 seconds. 5. Release the button. The do entry is replaced with done showing the operation is complete.

Table 23 shows the Accumulators and Maximum Demands options.

Table 23: Accumulators and Maximum Demands Options


Label EnrG dnd P.dnd A.dnd Lo.Hi Cnt Cnt1 Cnt4 Description Clears all total energies Clears all maximum demands Clears maximum power demands Clears maximum ampere and volt demands Clears Min/Max log Clears all counters Clears counter #1-#4

66

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

Chapter 4 PAS Application Software


The supplemental PAS software can be used for: Configuring the PM130 through its communication ports Retrieving real-time and recorded data Remote upgrading of the device firmware.

For information on how to install PAS on your PC, see the PAS Getting Started guide supplied on the installation CD.

4.1 Configuring the Database


To communicate with the meters, create a separate site database for each device. All communication and configuration data for the meter is stored in its database. During configuration, store all setups to the site database so that PAS recognizes the properties of the device regardless of whether the device is online or offline. To create a new database for your meter: 1. From the menu, select Tools > Configuration. Configuration The Configuration Configuration dialog box appears. 2. In the Instrument Setup tab, click the Sites button on the right side of the dialog box.

Figure 4-1: Configuration Dialog Box Instrument Setup Tab

PM130 PLUS Powermeters Series

67

Chapter 4PAS Application Software

2. Select the directory where the new database will be stored from the Look in field. By default, the directory is the Sites directory. 3. Enter a site name for your device in the File name field. 4. Click the New button. 5. Click OK. OK 4. Go to the Instrument Setup tab and select PM130 PLUS from the Model drop-down list. PAS automatically selects the appropriate instrument options for your meter. 5. Select a correct CT secondary current (5A or 1A) for your meter. 6. If you have the analog expander connected to the meter, select an appropriate output current option for the analog expander. 5. If you have to add any comments for your meter, type the comments in the Comment field.

4.2 Setting up Communications


It is possible to communicate with the meter via the factory set serial RS-485 COM1 port or via a replaceable COM2 communication module. Depending on what was ordered, your meters COM2 module can be equipped with an RS-232 or RS-422/RS-485 serial interface with an Ethernet port for communication on the Internet, or with a Profibus port. PAS does not support communications through Profibus. To configure PM130 communications: 1. From the menu, select Tools > Configuration. Configuration The Configuration dialog box appears, see Figure 4-1. 2. Go to the Connection tab, see in the Instrument Setup tab, select the type of a connection for your device. 3. Set the device communication address you assigned to the PM130 in the Address field. 3. Select a rate at which PAS updates data on your screen when you continuously poll the device in the PAS Data Monitor from the Sampling Rate field. The communication protocol and port settings in PAS must match the settings made in your device.

68

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

4.2.1

Communicating through a Serial Port


In order to communicate through the serial port, the port has to be configured. To configure a serial port: 1. From the menu select Tools > Configuration. Configuration The Configuration dialog box appears. 2. Click the Connection tab, see Figure 4-4. 3. Go to the Serial Port/Modem Port/Modem area and select a COM port from the Device drop-down list. 4. Click the Configure button. The Serial Port Setup dialog box appears.

Figure 4-2: Serial Port Setup Dialog Box 5. Specify the baud rate from the Baud Rate drop-down list. Choose the same baud rate as you have set in the device. 6. Select a data bit value from the Data Bits drop-down list. Choose the same data format as you have set in the device 7. Select a stop bit value for the port from the Stop Bits drop-down list. 8. Select the type of parity from the Parity drop-down list. 9. Click OK. OK The default settings for the local RS-232 and RS-422/485 ports are 9600 baud, 8 bits with no parity.

PM130 PLUS Powermeters Series

69

Chapter 4PAS Application Software

4.2.1.1 Selecting the Communication Protocol


To select a communication communication protocol: 1. Go to the Serial Port/Modem area on the Connection tab and click the Protocol button. The Protocol Setup dialog box appears.

Figure 4-3: Protocol Setup Dialog Box 2. In the Protocol Protocol Setup dialog box, select the same communications protocol as you have in your meter. The default protocol setting in your meter for all ports excluding the Profibus port is Modbus RTU. For more information on configuring the protocol parameters, refer to the PAS Getting Started guide.

4.2.2

Communicating through the Internet


If you are communicating through the Ethernet port, you should define the IP address of your meter on the network. To configure the IP address of your meter on the network: 1. On the Instrument Instrument Setup tab, select Internet Site under the Communication area. 2. Click on the Connection tab.

70

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

Figure 4-4: Configuration Dialog Box Connection Tab 3. In the Internet area, click on the IP Address option. 4. Enter the IP address of your meter. The default IP address preset at the factory is 192.168.0.203. 5. Select the communications protocol for the TCP port from the Protocol drop-down list. The meter can provide a Modbus/TCP connection on TCP port 502 and a DNP3/TCP connection on port 20000. The host port is set automatically as you select the protocol. 6. Select Modbus RTU for Modbus/TCP or DNP3 for DNP3/TCP. 7. In the Wait for answer field, adjust the time (in seconds) that PAS will have to wait for a connection before announcing an error. 8. Specify the number of retries PAS will use to receive a response from the device if communications fail in the Retries [15] field. 9. Click OK to continue.

4.3 Setting Up the Meter


PAS allows you to prepare the setup data for the meter off-line without the need to have it connected to your PC. To setset-up the meter: 1. Select the device site from the list box on the PAS toolbar. 2. Select the required setup group from the Meter Setup menu. 3. Click on the tab with the setup you want to create or modify. 4. Fill in the boxes with the required configuration data for your device.

PM130 PLUS Powermeters Series

71

Chapter 4PAS Application Software

5. Click on the Save as button to store your new data to the site database. Always set up and store the Basic Setup data to the site database first. PAS uses this data as a reference when arranging other meter setups. To save your setup to another site database: 1. 2. Select the setup from the file pane. Click the OK button.

To reuse setups from another site: 1. Copy the setup to your present site database. 2. Click the Open button. 3. Select the required site database. 4. Click the OK button. The opened setup is copied to your site database. You can also copy all setups from one site database into another site's database. To copy all setups from one site database into another database site 1. Select a device site from the drop-down list on the toolbar from which you want to reproduce setups. 2. Select Copy to... from the Meter Setup menu. 3. Select the site database where to copy the setups. 4. , Click the OK button.

4.3.1

Downloading Setup to the Meter


You can update each setup in your meter one at a time or download all setups together from the site database. To update a particular setup in your device: 1. Click on the OnOn-line button on the PAS toolbar 2. Select a meter site from the drop-down list on the toolbar. 3. Select the required setup group from the Meter Setup menu. 4. Click on the tab of the setup you want to download to the meter. 5. Click Send. Send To download all setups to your device at once: 1. Click the On-line button on the toolbar. 2. Select the device site from the drop-down list on the toolbar. 3. Select Download Setups from the Meter Setup menu.

72

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

4.3.2

Uploading a Setup from the Meter


To upload the setup from the device to the site database: 1. Click on the On-line button on the toolbar. 2. Select the device site from the drop-down list on the toolbar. 3. Select Upload Setups from the Meter Setup menu.

4.4 Authorization
If communications with your device is secured, you are prompted for the password when you send new setup data to the meter.

Figure 4-5: Authorization Required Dialog Box Enter the password and click OK. OK

If your authorization was successful, you are not prompted for the password again until you close the dialog box.

4.5 Configuring Communications in the Meter


This section describes how to configure communication ports in your meter through the PAS application software.

4.5.1

Setting Up Communication Ports


To set up the communication ports: 1. Select the device site from the drop-down list on the PAS toolbar to access the Setup dialog box. 2. Select Communication Setup from the Meter Setup menu. The Communication Setup dialog box appears. 3. Click the Serial Ports Setup tab. 4. Select the required device port from the Port drop-down list.

PM130 PLUS Powermeters Series

73

Chapter 4PAS Application Software

Figure 4-6: Communication Setup Dialog Box Serial Ports Setup Tab 5. Select the required port parameters in the Port Setup area to change the port settings in your meter. 6. Click the Send button. For the available communication options, see Communication Ports in

Chapter 3.
Notes: The meter provides the permanent Modbus TCP server on port 502. Selecting the DNP3 protocol launches the DNP3 TCP server in addition to the Modbus server allowing simultaneous connections on both ports. Selecting the Modbus protocol disables the DNP3 TCP server. When you change the COM2 settings through the Ethernet port, the device port restarts so communications will be temporarily lost. You may need to wait some additional time until PAS restores a connection with your device.

74

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

4.5.2

Setting Up Ethernet
To set up Ethernet: 1. Select the device site from the drop-down list on the PAS toolbar to access the Setup dialog box. 2. Select Communications Setup from the Meter Setup menu. 3. Click on the Network Setup tab.

Table 24 lists the Ethernet options.

Table 24: Ethernet Options


Parameter Device IP Address Network Subnet Mask Network Default Gateway TCP Service Port 502 = Modbus/TCP 20000 = DNP3/TCP Options Default 192.168.0.203 255.255.255.0 192.168.0.1 502

The TCP service port can also be changed trough the COM1 serial port setup. Changing the protocol for the port automatically changes the TCP port for the Ethernet.

Figure 4-7: Communication Setup Dialog Box Network Setup Tab 4. Select the required parameters to change the Ethernet settings in your meter. 5. Click Send. Send

PM130 PLUS Powermeters Series

75

Chapter 4PAS Application Software

Notes: The meter provides the permanent Modbus TCP server on port 502. Selecting the DNP3 TCP service port launches the DNP3 TCP server in addition to the Modbus server allowing simultaneous connections on both ports. Selecting the Modbus TCP port disables the DNP3 TCP server. When you change the device network settings through the Ethernet port, the device port restarts so communication will be temporarily lost. You may need to wait some additional time until PAS restores a connection with your device.

4.6 General Meter Setup


This section describes how to configure the PM130 for your particular environment and application using PAS.

4.6.1

Basic Meter Setup


Before operating your meter, provide the device with basic information about your electrical network. To set basic meter parameters: 1. Select the device site from the drop-down list on the PAS toolbar to access the Setup dialog box. 2. Select General Setup from the Meter Setup menu.

Figure 4-8: General Setup Dialog Box Basic Setup Tab

76

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

Table 25 lists available device configuration options.

Table 25: Device Configuration Options


Parameter Options Default Description

Basic Configuration Wiring mode PT ratio2 PT Ratio multiplier See Table 26. 1.0-6500.0 1, 10 4LN3 1.0 1 The wiring connection of the device The phase potential transformers primary to secondary ratio PT Ratio multiplication factor. Used in extra high voltage networks to accommodate the PT ratio for 500 kV and higher networks. The primary rating of the phase current transformer The nominal secondary line-to-neutral or line-to-line voltage. Used as a reference voltage for the disturbance monitor. The maximum demand load current (0 = CT primary) The nominal line frequency

CT primary current Nominal voltage EH

1-50000 A 10-690 V

5A 120 V

Maximum demand load current Nominal frequency

0-50000 A 50, 60, 25, 400 Hz

0 60 Hz

Demand Setup Power block demand period


EH

1, 2, 5, 10, 15, 20, 30, 60 min, E=external sync

30 min

The length of the demand period for power demand calculations. If the external synchronization is selected, a pulse front on the digital input DI1 denotes the start of the demand interval. The number of blocks to be averaged for sliding window demands The length of the demand period for ampere and volt demand calculations

Number of blocks in 1-15 sliding demand EH Volt/Ampere demand period 0-1800 sec

1 900 sec

Always specify the wiring mode and transformer ratings prior to setting up setpoints and analog outputs. The maximum value for the product of the phase CT primary current and PT ratio is 57,500,000. If the product is greater, power readings are zeroed. Table 26 lists the available wiring modes.

Table 26: Wiring Modes


Wiring Mode 3OP2 4LN3 3DIR2 4LL3 3OP3 3LN3 3LL3 Description 3-wire Open Delta using 2 CTs (2 element) 4-wire Wye using 3 PTs (3 element), line-to-neutral voltage readings 3-wire Direct Connection using 2 CTs (2 element) 4-wire Wye using 3 PTs (3 element), line-to-line voltage readings 3-wire Open Delta using 3 CTs (2 element) 4-wire Wye using 2 PTs (2 element), line-to-neutral voltage readings 4-wire Wye using 2 PTs (2 element), line-to-line voltage readings

PT Ratio is defined as a relation of the potential transformers primary voltage rating to its secondary rating. For example, for the 14,400 V transformers primary rating and 120 V secondary rating, the PT Ratio = 14400/120 = 120.

PM130 PLUS Powermeters Series

77

Chapter 4PAS Application Software

Wiring Mode 3BLN3 3BLL3

Description 3-wire Broken Delta using 2 PTs, 3 CTs (2-element), line-to-neutral voltage readings 3-wire Broken Delta using 2 PTs, 3 CTs (2-element), line-to-line voltage readings

In 4LN3, 3LN3 and 3BLN3 wiring modes, Min/Max volts, volt demands and voltage harmonics represent line-to-neutral voltages; otherwise, they will be line-to-line voltages.

4.6.2

Device Options
The Device Options setup allows you to enable or disable optional calculations and redefine user-selectable device options. To set up the device options: 1. Select the device site from the drop-down list on the PAS toolbar to access the setup dialog box. Select Device Options from the Meter Setup menu.

2.

Table 27 lists available wiring modes:

Table 27: Wiring Modes


Parameter Power Calculation Mode Options S=f(P, Q) (using reactive power), Q=f(S, P) (using non-active power)
EH

Default S=f(P, Q)

Description The method used for calculating reactive and apparent powers (see the Power Calculation Modes section below) The value at which energy counters roll over to zero

Energy Roll Value

1000 kWh 10000 kWh 100000 kWh 1000000 kWh 10000000 kWh 100000000 kWh 1000000000 kWh Disabled, Enabled OFF = disabled Wh pulses varh pulses 1.5-5.0% Low High

10000000

Phase Energy Calculation EH Energy Test Mode


EH

Disabled Disabled

Enables phase energy calculations Setting this option puts the meter into the energy test mode The device starting voltage in percent of FS (120V or 400V) The voltage, current and power resolution on the front display (see Measurement Units in Chapter 3) and in communications (see the appropriate section in the communication guides) The maximum voltage scale allowed, in secondary volts. See Data Scales in Appendix E The maximum current scale allowed, in secondary amps. See Data Scales in Appendix E

Starting Voltage Device Resolution

1.5% Low

Volts Scale, V

10-828 V

144 V

Amps Scale, A

1.0-10.0 A

2 CT secondary

78

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

Figure 4-9: General Setup Dialog Box Device Options Tab Power Calculation Modes The power calculation mode option allows you to change the method for calculating reactive and apparent powers in presence of high harmonics. The options work as follows: When the reactive power calculation mode is selected, active and reactive powers are measured directly and apparent power is calculated as:

S = P 2 + Q2
This mode is recommended for electrical networks with low harmonic distortion, commonly with THD < 5% for volts, and THD < 10% for currents. In networks with high harmonics, the second method is preferable.

When the non-active power calculation mode is selected, active power is measured directly, apparent power is taken as product S = V x I, where V and I are the RMS volts and amps, and reactive power (called non-active power) is calculated as:
N= S2 P2

PM130 PLUS Powermeters Series

79

Chapter 4PAS Application Software

4.6.3

Local Settings
This setup allows you to specify your time zone, daylight savings time, and clock synchronization options. To configure the time zone options for your device: 1. Select the device site from the drop-down list on the PAS toolbar. 2. Select General Setup from the Meter Setup menu. 3. Click on the Local Settings tab.

Figure 4-10: General Setup Dialog Box Local Settings Tab The Local Settings parameters are described in Table 28.

Table 28: Local Settings


Parameter Country Daylight savings time Options Default, or country name Disabled Enabled Default Default Disabled Description Defines calendar setting. The default setting stands for the U.S.A. When DST is disabled, the RTC operates in standard time only. When enabled, the device automatically updates the time at 2:00 AM at the pre-defined DST switch dates.

DST start month DST start week DST start weekday

Month-weekFirst The date when Daylight Savings Time weekday Sunday in begins. The DST switch point is specified by the month, week of the Week = 1st, 2nd, 3rd, April month and weekday. By default, DST 4thor Last (last week starts at 2:00 AM on the first Sunday of the month) in April of each year.

80

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

Parameter DST end month DST end week DST end weekday

Options

Default

Description The date when Daylight Savings Time ends. The DST switch point is specified by the month, week of the month and weekday. By default, DST ends at 2:00 AM on the last Sunday in October of each year. The external port receiving the time synchronization pulses

Month-weekLast weekday Sunday in Week = 1st, 2nd, 3rd, October 4thor Last (last week of the month) None DI1, DI2, DI3, DI4 None

Clock synchronization input

4.6.3.1 Daylight Savings Time


The daylight savings time option is enabled in the PM130 by default, and the default daylight savings time change points are preset for the U.S.A. When the daylight savings time is enabled, the meter automatically adjusts the device clock at 02.00 AM when daylight savings time begins/ends. If the daylight savings time option is disabled, you need to manually adjust the device clock for daylight savings time.

4.6.3.2 Time Synchronization Pulses


External time synchronization pulses can be delivered through one of the digital inputs. If a digital input is selected as the time synchronization source, the edge of an external pulse adjusts the device clock at the nearest whole minute. The time accuracy could be affected by the debounce time of the digital input, and by the operation delay of the external relay.

4.6.4

Using Digital Inputs


The meter is provided with two digital inputs that can trigger the alarm/control setpoints to give an alarm on input status change. It can also be linked to the energy/TOU registers to count pulses from external watt meters or gas and water meters. To configure digital inputs in your device: 1. Select the device site from the drop-down list on the PAS toolbar. 2. Select General Setup from the Meter Setup menu. The General Setup dialog box appears. 3. Click on the Digital Inputs tab. 4. Set the Digital Inputs parameters with the options provided in Table 29.

PM130 PLUS Powermeters Series

81

Chapter 4PAS Application Software

Figure 4-11: General Setup Dialog Box Digital Inputs Dialog Box The available digital inputs options are shown in Table 29.

Table 29: Digital Inputs


Parameter Options Default PULSE MODE Description In pulse mode, either leading, or trailing edge of the input pulse is recognized as an event. In KYZ mode, both leading and trailing edges of the input pulse are recognized as separate events. For the normal polarity, the open to closed transition is considered a pulse. For the inverting polarity, the closed to open transition is considered a pulse. It has no meaning in KYZ mode where both transitions are used. The amount of time while the state of the digital input should not change to be recognized as a new state. Too low debounce time could produce multiple events on the input change.

Pulse input mode PULSE MODE, KYZ MODE

Pulse polarity

NORMAL (N.O.), INVERTING (N.C.)

NORMAL

Debounce time

1-100 ms

10 ms

The debounce time is used the same for both digital inputs. If you change the debounce time for one digital input, the same debounce time is automatically assigned to the other.

82

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

4.6.5

Using Relay Outputs


The PM130 is equipped with two relays. Each relay can be operated either locally from the alarm/control setpoints in response to an external event or by a remote command sent through communications. It can also be linked to an internal pulse source to produce energy pulses.

Figure 4-12: General Setup Dialog Box Relay Outputs Tab The available relay outputs options are shown in Table 30:

Table 30: Relay Options


Parameter Operation mode Options UNLATHCED LATCHED PULSE KYZ Default UNLATCHED Description Unlatched mode: the relay goes into its active state when the control setpoint is in active (operated) state, and returns into its non-active state when the setpoint is released. Latched mode: the relay goes into its active state when the control setpoint goes into active state and remains in the active state until it is returned into its non-active state by a remote command. Pulse mode: the relay goes into its active state for the specified time, goes into non-active state for the specified time and remains in the non-active state. KYZ mode: the relay generates transition pulses. The relay changes its output state upon each command and remains in this state until the next command.

PM130 PLUS Powermeters Series

83

Chapter 4PAS Application Software

Parameter Polarity

Options NORMAL (N.O.) INVERTING (N.C.)

Default NORMAL

Description With normal polarity, the relay is normally deenergized in its nonactive state and is energized in its active (operated) state. With inverting polarity, the relay is normally energized in its non-active state and is de-energized in its active (operated) state. It is called failsafe relay operation. The actual pulse width is a multiple of the 1-cycle time rounded to the nearest bigger value. The pause time between pulses is equal to the pulse width. Links a pulse relay to the internal energy pulse source. The relay must be set into either pulse, or KYZ mode.

Pulse width

20-1000 ms

100 ms

Pulse source

NONE kWh IMP kWh EXP kvarh IMP kvarh EXP kvarh TOT kVAh 0.1-1000.0

NONE

Pulse rate, kWh/Pulse

1.0 kWh/Pulse

Defines the pulse weight in kWh units per pulse

4.6.5.1 Generating Energy Pulses through Relay Outputs


To generate energy pulses through a relay output: 1. Set a relay to either pulse, or KYZ mode. 2. Select a polarity (active pulse edge) for energy pulses and a pulse width. 3. Select a source accumulator (type of energy). 4. Select the pulse rate for your output. 3. Store your new setup to the device.

4.6.6

Programming Analog Outputs


The meter can be ordered with two optional analog outputs with options for the following output currents:

0-1mA 1mA 0-20mA 4-20mA

The 0-1mA and 1mA current outputs provide a 100% overload, and actually output currents up to 2 mA and 2mA whenever the output value exceeds the engineering scale set for the 1 mA or 1mA.

84

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

To configure the Analog Outputs in your device: 1. Select General Setup from the Meter Setup menu 2, Click on the Analog Outputs tab. If you are programming your device online, analog outputs are designated as not available if they are not present in the device.

Figure 4-13: General Setup Dialog Box Analog Outputs Tab The available analog output options are described in Table 31.

Table 31: Analog Output Options


Option AO type Range 0-1mA 1mA 0-20mA 4-20mA See Appendix B Description The analog output type. When connected to the meter, shows the actual AO type read from the device. When working off-line, select the analog output option corresponding to your meter. Selects the measured parameter to be transmitted through the analog output channel. Defines the low engineering scale (in primary units) for the analog output corresponding to a lowest (zero) output current (0 or 4 mA) Defines the high engineering scale (in primary units) for the analog output corresponding to a highest output current (1 or 20 mA)

Output parameter Zero scale

Full scale

When you select an output parameter for the analog output channel, the default engineering scales are set automatically. The scales represent the maximum available scales. If the parameter actually covers a lower range, you can change the scales to provide a better resolution on the analog outputs.

PM130 PLUS Powermeters Series

85

Chapter 4PAS Application Software

4.6.6.1 Scaling Non-Directional Analog Outputs


When programming scales for non-directional analog outputs with a 0-1mA, 0-20mA or 4-20mA current option, you can change both zero and full engineering scales for any parameter. The engineering scale need not be symmetrical.

4.6.6.2 Scaling Directional Power Factor


The engineering scale for the signed power factor emulates analog power factor meters. The power factor scale is -0 to +0 and is symmetrical with regard to 1.000 (-1.000 +1.000). The negative power factor is scaled as -1.000 minus the measured value, and non-negative power factor is scaled as +1.000 minus the measured value. To define the entire power factor range from -0 to +0, the default scales are specified as -0.000 to 0.000.

4.6.6.3 Scaling 1mA Analog Outputs


Programming engineering scales for directional 1mA analog outputs depends on whether the output parameter represents unsigned (as volts and amps) or signed (as powers and power factor) values. If the output value is unsigned, you can change both zero and full engineering scales. If the parameter represents a signed (directional) value, you should provide only the engineering scale for the +1 mA output current. The engineering scale for the 0 mA output current is always equal to zero for all values except the signed power factor, for which it is set to 1.000, for more details, see the Scaling Directional Power Factor section above. The device does not allow access to the setting if the parameter is directional. Whenever the sign of the output parameter is changed to negative, the device automatically uses full engineering scale settings for +1 mA with a negative sign.

4.6.6.4 Scaling Analog Outputs for 0-2 mA and 2 mA


The output scales for 0-1 mA and 1 mA analog outputs are programmed for 0 mA and +1 mA regardless of the required output current range. To use the entire output output range of 2 mA or 2 mA, set the analog output scales in your device as follows:

0-2 mA: mA set the 1 mA scale to of the required full scale output for unidirectional parameters, and set the 0 mA scale to the negative full scale and the 1 mA scale to zero for bi-directional parameters. 2 mA: mA set the 1 mA scale to of the required full-scale output for both uni-directional and bi-directional parameters.

For example, to provide the 0 to 2 mA output current range for Volts measured by the meter in the range of 0 to 120V, set the 1 mA scale to 60V; then the 120V reading will be scaled to 2 mA.

86

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

4.6.7

Using Counters
The meter provides four six-digit counters that count different events. To configure the device counters: 1. Select General Setup from the Meter Setup menu. 2. Click on the Pulse/Event Counters tab. 3. Set the Counters parameters with the options provided in Table 32. Each counter is independently linked to any digital input and count input pulses with a programmable scale factor. Each counter can also be incremented in response to any internal or external event, checked and cleared through the Control Setpoints.

Table 32 lists available counters options.

Table 32: Counters Options


Option Pulse Input Multiplier Range None, DI1-DI4 1-9999 Default None 1 Description Links a digital input to the counter The value added to the counter when a pulse is detected on the pulse source input Displays the present counter contents

Counter Value

Figure 4-14: General Setup Dialog Box Pulse/Events Counters

PM130 PLUS Powermeters Series

87

Chapter 4PAS Application Software

You can preset a counter to a required value or clear it through the General Setup dialog box without affecting the counter setup. To preset or clear a counter: 1. Click the Online button on the PAS toolbar before accessing the setup dialog box. 2. Type in the required value into the Counter Value field. 3. Click the Send button.

4.6.8

Using Control Setpoints


The PM130 has an embedded logical controller that runs different actions in response to user-defined internal and external events. Unlike a PLC, the meter uses a simplified programming technique based on setpoints that allows the user to define a logical expression based on measured analog and digital values that produce a required action. The meter provides 16 control setpoints with programmable operate and release delays. Each setpoint evaluates a logical expression with one trigger argument. Whenever an expression is evaluated as true, the setpoint performs a programmable action that can send a command to the output relay, or increment a counter. The logical controller provides very fast response to events. The scan time for all setpoints is 1 cycle time (16.6 ms at 60Hz and 20 ms at 50/400 Hz). To program the setpoints: setpoints: 1. Select General Setup from the Meter Setup menu. 2. Click on the Control/Alarm Setpoints tab. 3. Configure the setpoints according to the valid setpoint values provided in Table 33.

Table 33: Setpoint Options


Option Trigger parameter Operate limit Range See Appendix C Description The trigger parameter that is used as an argument in the logical expression The threshold (in primary units) at which the conditional expression would be evaluated to true. Not applicable for digital triggers. The threshold (in primary units) at which the conditional expression would be evaluated to false. Defines the hysteresis for analog triggers. Not applicable for digital triggers. The time delay before operation when the operate conditions are fulfilled The time delay before release when the release conditions are fulfilled The action performed when the setpoint expression is evaluated to true (the setpoint is in operated state)

Release limit

Operate delay 0.1-999.9 sec Release delay Action 0.1-999.9 sec See Appendix C

88

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

Figure 4-15: General Setup Dialog Box Control/Alarm Setpoints Tab

4.6.8.1 Using Numeric Triggers


For numeric (analog) triggers, a setpoint allows you to specify two thresholds for each trigger to provide hysteresis (dead band) for setpoint operations. The Operate Limit defines the operating threshold, and the second Release Limit defines the release threshold for the trigger. The trigger thresholds are specified in primary units. If you do not want to use hysteresis for the trigger, set the Release Limit to the same value as the Operate Limit.

4.6.8.2 Using Binary Triggers


Binary (digital) triggers like digital inputs and relays are tested for ON/CLOSED or OFF/OPEN status. In the PM130, the binary events are level-sensitive events. An event is asserted all the time while the corresponding condition exists.

4.6.8.3 Delaying Setpoint Operations


Two optional delays can be added to each setpoint to extend monitoring setpoint triggers for a longer time before reaching a decision on whether the expected event occurred or not. When a delay is specified, the logical controller changes the setpoint status only if all conditions are asserted for a period of at least as long as the delay time.

PM130 PLUS Powermeters Series

89

Chapter 4PAS Application Software

4.6.8.4 Using Setpoint Events and Actions


When a setpoint status changes, i.e., a setpoint event is either asserted or de-asserted, the following happens in your device:

The new setpoint status is logged to the setpoint status register that can be monitored through communications from the SCADA system or from a programmable controller in order to give an indication on the expected event. The operated setpoint status is latched to the setpoint alarm latch register that can be inspected through communications and via the display (see Status Display in Chapter 3). The register holds the last setpoint alarm status until it is explicitly cleared through communications or via the display. A programmable action is performed on setpoint status transition when a setpoint event is asserted.

Generally, setpoint actions are performed independently for each setpoint and can be repeated a number of times for the same target. The exceptions are relay operations that are shared for each separate target between all setpoints using an OR scheme. A relay output is operated when one of the setpoints linked to the relay is activated and stays in the operated state until all of these setpoints are released (except for latched relays that require a separate release command to be deactivated).

4.6.8.5 Using Time Counters


Each of the meter counters can be used to count the setpoint operation time. If you select the TIME CNT n action for a setpoint, the target counter measures the time while the setpoint is in the operated state. The counter resolution is 0.1 hour. See Status Display in Chapter 3 on how to examine the counters via the front display.

4.7 Configuring Summary Energy and TOU Registers


The TOU option is only available in the presence of the batterybattery-backed clock unit. The PM130EH provides 4 total (summary) energy and 4 concurrent tariff energy and maximum demand registers. The registers can be linked to any internal energy source or to any external pulse source that delivers pulses through the device digital inputs. The meter tariff structure supports 4 different tariffs using an arbitrary tariff schedule. A total of 4 types of days and 4 seasons are supported with up to eight tariff changes per day. By default, the billing registers in your meter and the tariff system are not operational.

90

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

To activate the summary/tariff registers or to change the profile for the first billing register: 1. Link the billing registers to the respective energy sources. 2. Configure the options for the registers to whether the only totalization or both total and tariff registers would be used, and whether daily profiling should be enabled for the energy usage and maximum demand registers. 2. Configure the daily tariff schedule using the TOU daily profiles for all types of days and seasons. 3. Configure the season tariff schedule using the TOU calendar.

4.7.1

Setting up Total and Tariff Registers


To configure the device total (summary) and TOU registers: 1. Select Energy/TOU from the Meter Setup menu. The Energy/TOU Setup dialog box appears.

Figure 4-16: Energy/TOU Setup Dialog Box 2. Configure the Energy/TOU options according to the valid parameters shown in Table 34.

PM130 PLUS Powermeters Series

91

Chapter 4PAS Application Software

Table 34: Energy/TOU Parameters


Parameter Options Default Summary/TOU Registers TOU Units Unchecked Checked Unchecked Links tariff registers to the selected energy source The register measurement units. When a register is linked to an internal energy source, it is set automatically. When an external pulse source is used, the user can select a measurement unit for the register. Description

kWh, kvarh, kVAh, None m3, CF (cubic foot), CCF (hundred cubic feet)

Register Source List Source Input None kWh Import kWh Export kvarh Import kvarh Export kVAh, DI1-DI4 0.001 to 100.000 None Links an energy source to the register

Multiplier

1.000

The multiplication factor for the energy source. Unchangeable for internal energy sources. Defines the target billing register for the energy source. It is set automatically.

Target

Reg#1- Reg#4

None

4.7.2

Configuring the Daily Tariff Schedule


To configure your daily tariff schedule: select Energy/TOU from the Meter Setup menu, and then click on the TOU Daily Profiles tab.

92

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

Figure 4-17: Energy/TOU Setup Dialog Box TOU Daily Profiles Tab The daily profile setup allows you to specify the daily tariff change points with a 15-minute resolution for 4 seasons using 4 different daily schedules for each season. To configure your daily profiles: 1. Select the required season and day type. 2. Select the start time for each tariff change point and the corresponding active tariff number. 3. Repeat the setup for all active profiles. The first tariff change point is fixed at 00:00 hours, and the last tariff change you specified will be in use until 00:00 hours on the next day. The energy daily profile log will be automatically configured for the number of active tariffs you defined in the meter TOU daily profile.

4.7.3

Configuring the Season Tariff Schedule


To configure your season tariff schedule, select Energy/TOU from the Meter Setup menu, and then click on the TOU Calendar tab.

PM130 PLUS Powermeters Series

93

Chapter 4PAS Application Software

Figure 4-18: Energy/TOU Setup Dialog Box TOU Calendar Tab The meters TOU calendar allows you to configure any tariff schedule based on any possible utility regulation. The calendar itself has 32 entries that allow you to specify profiles for working days and holidays through all seasons in any order that is convenient for you, based on simple intuitive rules. There are no limitations on how to define your schedule. The meter is able to automatically recognize your settings and to select a proper daily tariff schedule for any day within a year. The above picture gives you an example of a single-season tariff schedule configured for weekends and the designated U.S.A. holidays. To configure your season tariff schedule: 1. In the Season box, select the season, and in the Day Type box, select a day type for this calendar entry. 2. Select the time interval when this daily tariff schedule is effective, based on the start and the end weekdays and, for a multi-season schedule, on the start and the end month for the selected season. It does not matter which order of weekdays or months you select: the meter can recognize the correct order by itself. 3. For exception days like designated holidays, select a specific day either by specifying a day and month, or by selecting a month, a week and a weekday within the month.

4.8 Configuring Communication Protocols


This section describes how to customize protocol options for use with your application software.

94

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

4.8.1

Configuring Modbus

4.8.1.1 Modbus Point Mapping


The PM130 provides 120 user assignable registers in the address range of 0 to 119. You can re-map any register available in the meter to any assignable register so that Modbus registers that reside at different locations may be simply accessed using a single request by re-mapping them to adjacent addresses. Initially these registers are reserved and none of them points to an actual data register. To build your own Modbus register map: 1. From the Meter Setup menu, select Protocol Setup and click on the Modbus Registers tab. 2. Click on the Default button to cause the assignable registers to reference the actual default meter register 6656 (0 through 119 are not allowable register addresses for re-mapping). 3. Type in the actual addresses you want to read from or write to via the assignable registers. Refer to the PM130 Modbus Reference Guide for a list of the available registers. Note that 32-bit Modbus registers should always start at an even register address.

Figure 4-19: Protocol Setup Dialog Box Modbus Registers Tab 4. Click Send to download your setup to the meter.

4.8.1.2 Changing 32-bit Register Format


The PM130 allows you to read 32-bit Modbus analog registers, energy counters and binary counters either in integer format, or in IEEE single precision floating point format. Refer to the PM130 Modbus Reference Guide for more information.

PM130 PLUS Powermeters Series

95

Chapter 4PAS Application Software

The 32-bit Modbus registers are factory-set in the PM130 to integer format. To change the register format: 1. From the Meter Setup menu, select Protocol Setup and click on the Modbus Registers tab. 2. Change the 32-bit register format in the Modbus Options pane. 3. Click Send to download your setup to the meter.

4.8.2

Configuring DNP3
DNP Options can be changed both via DNP3 and Modbus. Refer to the PM130 DNP3 Reference guide for information on the protocol implementation and a list of the available data points.

4.8.2.1 DNP Options


To view or change the factory-set DNP options, select Protocol Setup from the Meter Setup menu and click on the DNP Options tab.

Figure 4-20: Protocol Setup Dialog Box DNP Options Tab The following table describes available DNP options. Refer to the DNP3 Data Object Library document available from the DNP Users Group on the DNP3 object types.

Table 35: Protocol Setup DNP Options Parameters


Parameter Binary Input Object Options Single-bit With Status Default Binary Inputs (BI) Single-bit The default BI object variation for requests with qualifier code 06 when no specific variation is requested Description

96

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

Parameter Analog Input Object

Options 32-bit 32-bit Flag 16-bit 16-bit Flag 32-bit 32-bit 16-bit 16-bit +Flag Flag +Flag Flag

Default Analog Inputs (AI) 16-bit -Flag

Description The default AI object variation for requests with qualifier code 06 when no specific variation is requested

Binary Counters (BC) Binary Counter Object 32-bit -Flag The default BC object variation for requests with qualifier code 06 when no specific variation is requested

DNP General Options 16-bit AI Scaling 16-bit BC Scaling SBO Timeout3 Disabled Enabled x1, x10, x100, x1000 2-30 sec Enabled x1 10 Allows scaling 16-bit analog input objects (see description below) Allows scaling 16-bit binary counter objects (see description below) Defines the Select Before Operate (SBO) timeout when using the ControlRelay-Output-Block object Defines the time interval between periodic time synchronization requests Defines the time interval between fragments of the response message when it is fragmented

Time Sync Period4 Multi Fragment Interval

0-86400 sec 50-500 ms

86400 50

Scaling 1616-bit AI objects Scaling 16-bit AI objects allows accommodating native 32-bit analog input readings to 16-bit object format; otherwise it may cause an over-range error if the full-range value exceeds a 16-bit point limit. Scaling is enabled by default. It is not related to points that are read using 32-bit AI objects. Refer to the PM130 DNP3 Reference Guide for information on the data point scales and a reverse conversion that should be applied to the received scaled values. Scaling 1616-bit Binary Counters Scaling 16-bit Binary Counters allows changing a counter unit in powers of 10 to accommodate a 32-bit counter value to 16-bit BC object format. If the scaling unit is greater than 1, the counter value is reported being divided by the selected scaling unit from 10 to 1000. To get the actual value, multiply the counter reading by the scaling unit.

4.8.2.2 Configuring DNP Class 0 Responses


The most common method of getting static object information from the meter via DNP is to issue a read Class 0 request. The PM130 allows you to

The Select Before Operate command causes the meter to start a timer. The following Operate command must be sent before the specified timeout value expires. The meter requests time synchronization by bit 4 in the first octet of the internal indication word being set to 1 when the time interval specified by the Time Sync Period elapses. The master should synchronize the time in the meter by sending the Time and Date object to clear this bit. The meter does not send time synchronization requests if the Time Sync Period is set to 0.

PM130 PLUS Powermeters Series

97

Chapter 4PAS Application Software

configure the Class 0 response by assigning ranges of points to be polled via Class 0 requests. To view the factoryfactory-set DNP Class 0 assignments, assignments, or build your own Class 0 response message: 1. From the Meter Setup menu select Protocol Setup and click on the DNP Class 0 Points tab. 2. Select the object and variation type for a point range. 3. Specify the start point index and the number of points in the range. Refer to the PM130 DNP3 Reference Guide for available data points. 4. Repeat these steps for all point ranges you want to be included into the Class 0 response. 5. Click Send to download your setup to the meter. The factory-set Class 0 point ranges are shown in the picture below.

Figure 4-21: Protocol Setup Dialog Box DNP Class 0 Points Tab

4.9 Remote Device Control


This section describes online operations on the meter you can perform through PAS. To access device control options you should have your device online.

4.9.1

Remote Relay Control


PAS allows you to send a command to any relay in your device or release a latched relay, except of the relays that are linked to an internal pulse source. These relays cannot be operated outside of the device.

98

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

To access the Remote Relay Control dialog, check the On-line button on the PAS toolbar, select Device Control from the Monitor menu, and then click on the Remote Relay Control tab. To send a remote command command to the relay: 1. From the Relay Command box for the relay, select the required command: OPERATE to operate a relay RELEASE - to remove your remote command, or to release a latched relay 2. Click on Send.

Figure 4-22: Device Control Dialog Box Remote Relay Control Tab

4.9.2

Device Diagnostics
PAS allows you to examine and clear the present device diagnostics events. To access the Device Diagnostics dialog, check the On-line button on the PAS toolbar, select Device Control from the Monitor menu, and then click on the Device Diagnostics tab. See Device Diagnostic Codes in Appendix F for the list of diagnostic codes and their meanings.

PM130 PLUS Powermeters Series

99

Chapter 4PAS Application Software

Figure 4-23: Device Control Dialog Box Device Diagnostics Tab To clear the device diagnostics events, click on Clear.

4.9.3

Resetting Accumulators
PAS allows you to remotely clear energy accumulators, maximum demands, Min/Max log registers and counters in your device. To open the dialog, check the On-line button, and then select Reset from the Monitor menu.

Figure 4-24: Reset Window

100

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

To reset the required accumulation registers: 1. Click on the corresponding button, and then confirm your command. 2. If a target has more than one component, you are allowed to select components to reset. 3. Check the corresponding boxes, and then click OK.

Figure 4-25: Reset Min/Max Demands Dialog Box

4.9.4

Updating the Clock


To update the Real-Time Clock (RTC) in your device, check the On-line button on the PAS toolbar, and then select RTC from the Monitor menu or click on the Real-Time Clock button on the PAS toolbar. The RTC dialog box displays the current PC time and the time in your device. To synchronize the device clock with the PC clock, click Set.

Figure 4-26: Real Time Clock Window

4.10 Administration
4.10.1 Changing a Password
PAS allows you to remotely change the password, and enable or disable the password security check in your meter. To change the password, check the On-line button, select Administration from the Monitor menu, and then select Change Password.

PM130 PLUS Powermeters Series

101

Chapter 4PAS Application Software

Figure 4-27: Change Password Dialog Box To change the password: 1. Type in a new 4-digit password 2. Repeat the password in the Confirm box 3. Check the Enable network protection to enable password checking 4. Click Send.

4.11 Upgrading Device Firmware


Your meter has upgradeable firmware. If you need to upgrade your device, download a new firmware file to the meter through PAS. Firmware is downloaded through any communication port except the Profibus port. The meter may be connected to your PC through a serial interface or the Internet. Upgrading firmware is only supported through the Modbus RTU and Modbus/TCP protocols, so your serial port should be put into Modbus RTU mode. To download a new firmware file to your device: 1. Ensure that the communication port you are connected through to the meter operates in Modbus RTU mode. 2. If the port is configured for a different protocol, put it into Modbus RTU mode either from the front display, or remotely through PAS. If you are connected to the meter through a serial interface, it is recommended to set the port baud rate to 115,200 bps. See Configuring Communications in your Meter on how to remotely change the protocol and baud rate in your meter. 3. Check the On-line button on the PAS toolbar, select Flash Downloader from the Monitor menu, and then confirm changes. 4. Point to the firmware upgrade file for your meter, click Open, and then confirm upgrading the meter.

102

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

Figure 4-28: Open Dialog Box 5. You are asked for the password regardless of the password protection setting in your meter. Type the meter password, and click OK. If you did not change the password in the meter, enter the default password 0.

Figure 4-29: Authorization Required Dialog Box 6. Wait until PAS completes upgrading your device. It takes about 3-4 minutes at 115,200 bps to download the file to the meter.

Figure 4-30: Downloading File Progress Window 7. After upgrading firmware is completed, the meter restarts, so communications can be temporarily lost. You may need to wait a short duration until PAS restores a connection with your device.

Figure 4-31: Download Complete Message Window

PM130 PLUS Powermeters Series

103

Chapter 4PAS Application Software

4.12 Monitoring Your Meters


4.12.1 Viewing Real-time Data
Real-time data is continuously retrieved from your devices, updated on the screen at the rate you defined in the Instrument Setup, and can be recorded to a file. You can view acquired data in a tabular or in a graphical form as a data trend.

Figure 4-32: RT Data Monitor Set Window For information on the real-time data monitoring and recording options, see the PAS Getting Started Guide. Any data, energy and maximum demand registers in your meters can be read and recorded to files through the PAS Data Monitor. See Appendix D for a list of data available in your meter.

4.12.2 Viewing Min/Max Log


To retrieve the real-time Min/Max log data from your device, select the device site from the list box on the toolbar, select RT Min/Max Log from the Monitor menu, and then select a data set you want to view. For more information on the Min/Max data monitoring options, see the PAS Getting Started Guide.

104

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

4.12.3 Viewing Harmonic Spectrum and Synthesized Waveforms


To retrieve the real-time harmonic spectrum from the PM130E, select the device site from the list box, and then select RT Harmonic Monitor from the button on the PAS toolbar. Monitor menu or click on the PAS retrieves harmonic spectrum for V1-V3 and I1-I3 channels. Harmonics can be displayed as a spectrum chart for a selected channel or in a table. PAS can also synthesize waveforms based on the harmonic spectrum to let you view a shape of the voltage and current waveforms in your network

4.12.3.1

Viewing a Spectrum Chart


Click on the button to view a spectrum chart for the selected channel. To change a channel, click on the window with the right mouse button, select Channels..., check the channel you want displayed, and then click OK. PAS provides voltage, current, active power and reactive power spectrum charts.

Figure 4-33: RT Harmonic Monitor Window PAS can give you indication on whether harmonic levels in the sampled waveforms exceed compliance limits defined by the power quality standards or local regulations. To review or change change harmonic limits: 1. Click on the spectrum window with the right mouse button and select Limits.

PM130 PLUS Powermeters Series

105

Chapter 4PAS Application Software

2. Select a known harmonics standard, or select Custom and specify your own harmonic limits. 3. Check the Enabled box to visualize harmonic faults on the spectrum graph and in harmonic tables. Harmonics that exceed selected compliance levels are colored in red on the graph and in the tables.

Figure 4-34: Limits Window

4.12.3.2

Viewing a Spectrum Table


Click on the button on the local toolbar to display the harmonics spectrum in a tabular view for a selected phase or for all phases together. The spectrum table shows voltage, current, active power and reactive power harmonic components both in percent of the fundamental and in natural units, and harmonic phase angles.

106

PM130 PLUS Powermeters Series

Chapter 4PAS Application Software

Figure 4-35: RT Harmonic Monitor Spectrum Details Window To change a phase, click on the window with the right mouse button, select Options..., check the phase you want displayed, and then click OK.

4.12.3.3

Viewing Synthesized Waveforms


To view the synthesize waveforms based on the sampled harmonic spectrum, click on the button on the local toolbar to view nonbutton to overlapped voltage and current waveforms, or click on the view them overlapped.

PM130 PLUS Powermeters Series

107

Chapter 4PAS Application Software

Figure 4-36: RT Harmonic Monitor Window PAS shows a pair of 4-cycle voltage and current synthesized AC waveforms for a single phase. To select the channels you want to view, click with the right mouse button on the waveform window, select Channels..., check the channels for the phase you want displayed, and then click OK.

108

PM130 PLUS Powermeters Series

Appendix ATechnical Specifications

Appendix A Technical Specifications


A.1 Environmental Conditions
Operating temperature: -20C to 60C (-4F to 140F) Storage temperature: -40C to 85C (-40F to 185F) Humidity: 0 to 95% non-condensing

A.2 Construction
Dimensions see Figure 22-1 Weight: 1.23kg (2.7 lb.) Materials Case enclosure: plastic PC/ABS blend Display body: plastic PC/ABS blend Front panel: plastic PC PCB.: FR4 (UL94-V0) Terminals: PBT (UL94-V0) Connectors-Plug-in type: Polyamide PA6.6 (UL94-V0) Packaging case: Carton and Stratocell (Polyethylene Foam) brackets Labels: Polyester film (UL94-V0)

A.3 Power Supply


120/230 VAC-DC Option: Rated input 85-265VAC 50/60 Hz, 88-290VDC, Burden 9VA Isolation: Input to output: 3000 VAC Input to ground: 2500 VAC 12 VDC Option: Rated input 9.5-18 VDC 24/48 VDC Option: Rated input 18.5-72 VDC Wire size: up to 12 AWG (up to 3.5 mm2)

PM130 Powermeters Series

109

Appendix ATechnical Specifications

A.4 Input Ratings


Voltage Inputs Operating range: 690VAC line-to-line, 400VAC line-to-neutral Direct input and input via PT (up to 828VAC line-to-line, up to 480VAC lineto-neutral) Input impedance: 1000 k Burden for 400V: < 0.4 VA Burden for 120V: < 0.04 VA Over-voltage withstand: 1000 VAC continuous, 2000 VAC for 1 second Galvanic isolation: 3500 VAC Wire size: up to 12 AWG (up to 3.5mm2) Current Inputs Wire size: 12 AWG (up to 3.5 mm2) Galvanic isolation: 3500 VAC 5A secondary Operating range: continuous 10A RMS Burden: < 0.1 VA Overload withstand: 15A RMS continuous, 300A RMS for 1 second 1A secondary Operating range: continuous 2A RMS Burden: < 0.02 VA Overload withstand: 6A RMS continuous, 80A RMS for 1 second Sampling Rate measurement 128 samples/cycle

A.5 Optional Relay Outputs


DRY contact relay option (DI/DO Optional module) 2 relays rated at 3A/250 VAC; 3A/30 VDC, 1 contact (SPST Form A) Galvanic isolation: Between contacts and coil: 3000 VAC 1 min Between open contacts: 750 VAC Operate time: 10 ms max.

110

PM130 PLUS Powermeters Series

Appendix ATechnical Specifications

Release time: 5 ms max. Update time: 1 cycle Wire size: 14 AWG (up to 1.5 mm2) Solid State relay option 2 relays rated at 0.15A/250 VAC - 400 VDC, 1 contact (SPST Form A) Galvanic isolation: 3750 VAC 1 min Operate time: 1 ms max. Release time: 0.25 ms max. Update time: 1 cycle Wire size: 14 AWG (up to 1.5 mm2)

A.6 Optional Digital Inputs


4 Digital Inputs Dry Contacts, internally wetted @ 24VDC (DI/DO Optional module) Sensitivity: Open @ input resistance >100 k, Closed @ Input resistance < 100 Galvanic isolation: 3750 VAC 1 min Internal power supply: 24VDC Scan time: 1 ms Wire size: 14 AWG (up to 1.5 mm2)

A.7 Optional Analog Outputs


4 Analog Outputs optically isolated (AO Optional module) Ranges (upon order):
1 mA, maximum load 5 k (100% overload)

0-20 mA, maximum load 510 4-20 mA, maximum load 510 0-1 mA, maximum load 5 k (100% overload) Isolation: 2500 VAC 1 min Power supply: internal Accuracy: 0.5% FS Update time: 1 cycle Wire size: 14 AWG (up to 1.5 mm2)

PM130 Powermeters Series

111

Appendix ATechnical Specifications

A.8 Communication Ports


COM1 RS-485 optically isolated port Isolation: 3000 VAC 1 min Connector type: removable, 3 pins. Baud rate: up to 115.2 kbps. Supported protocols: Modbus RTU, DNP3, and SATEC ASCII. Wire size: up to 14 AWG (up to 1.5 mm2).

COM2 (ETH Optional module) Ethernet Port Transformer-isolated 10/100BaseT Ethernet port. Connector type: RJ45 modular. Supported protocols: Modbus/TCP (Port 502), DNP3/TCP (Port 20000). Number of simultaneous connections: 4 (2 Modbus/TCP + 2 DNP3/TCP).

A.9 Real-time Clock


Standard Meter Clock Non-backed clock Accuracy: typical error 15 seconds per month @ 25C Typical clock retention time: 30 seconds Battery-backed Clock Unit Battery-backed clock Accuracy: typical error 7 seconds per month @ 25C (2.5ppm) Typical clock retention time: 36 months

A.10 Display
High-brightness seven-segment digital LEDs, two 4-digit + one 5-digit windows Keypad: 6 push buttons

112

PM130 PLUS Powermeters Series

Appendix ATechnical Specifications

A.11 Standards Compliance


Accuracy: Per IEC62053-22, class 0.2 Per ANSI C12.20 1998, class 10 0.5% Electromagnetic Immunity: IEC 61000-6-2: IEC 61000-4-2 level 3: Electrostatic Discharge IEC 61000-4-3 level 3: Radiated Electromagnetic RF Fields IEC 61000-4-4 level 3: Electric Fast Transient IEC 61000-4-5 level 3: Surge IEC 61000-4-6 level 3: Conducted Radio Frequency IEC 61000-4-8: Power Frequency Magnetic Field ANSI/IEEE C37.90.1: Fast Transient SWC Electromagnetic Emission: IEC 61000-6-4: Radiated/Conducted class A IEC CISPR 22: Radiated/Conducted class A Safety/Construction: IEC 61010-1: 2006 AC and Impulse Insulation: IEC 62052-11: 2500 VAC during 1 minute 6KV/500 @ 1.2/50 s impulse

PM130 Powermeters Series

113

Appendix ATechnical Specifications

A.12 Measurement Specifications


Table 36: Measurement Specifications Parameters
Parameter Full Scale @ Input Range 120VxPT @ 120V 400VxPT @ 690V Line current Active power Reactive power Apparent power Power factor Frequency Total Harmonic Distortion, THD V (I), %Vf (%If) Total Demand Distortion, TDD, % Active energy Import & Export Reactive energy Import & Export Apparent energy 999.9 CT 0.36PTCT @ 120V 1.2PTCT @ 690V 0.36PTCT @ 120V 1.2PTCT @ 690V 0.36PTCT @ 120V 1.2PTCT @ 690V 1.000 0.02 1.5 0.1 THD 1%, V(I) 10% FSV (FSI) TDD 1%, I 10% FSI 0.2 |PF| 0.5, I 2% FSI -0.999 to +1.000 15 Hz to 480 Hz 0 to 999.9 0.2 0.02 |PF| 0.85 0.3 0.04 |PF| 0.95 0.2 0.2 0.02 0.02 10% to 120% FS |PF| 0.85 Accuracy % % FS Conditions Reading 0.2 0.01 10% to 120% FS Range

Voltage

0 to 1,150,000 V Starting voltage 1.5-5.0% FS (selectable) 0 to 50,000 A Starting current 0.1% FS -10,000,000 kW to +10,000,000 kW -10,000,000 kvar to +10,000,000 kvar 0 to 10,000,000 kVA

100

1.5

0 to 100

Class 0.2 Class 0.5 Class 0.2

0 to 999,999,999 kWh 0 to 999,999,999 kvarh 0 to 999,999,999 kVAh

PT - external potential transformer ratio CT - primary current rating of external current transformer FSV - voltage full scale FSI - current full scale Vf - fundamental voltage If - fundamental current Notes 1. Accuracy is expressed as (percentage of reading + percentage of full scale) 1 digit. This does not include inaccuracies introduced by the user's potential and current transformers. Accuracy calculated at 1second average.

@ 80% to 120% of voltage FS, 10% to 120% of current FS, and frequency 50/60 Hz

114

PM130 PLUS Powermeters Series

Appendix ATechnical Specifications

2. Specifications assume: voltage and current waveforms with THD 5% for kvar, kVA and PF, and reference operating temperature 20C - 26C. 3. Measurement error is typically less than the maximum error indicated.

PM130 Powermeters Series

115

Appendix BAnalog Output Parameters

Appendix B Analog Output Parameters


The following table lists parameters that can be provided on the meters analog outputs.

Table 37: Analog Output Parameters


Display Code nonE rt.U1 rt.U2 rt.U3 rt.U12 rt.U23 rt.U31 rt.C1 rt.C2 rt.C3 rt. P rt. q rt. S rt. PF r.PF.LG r.PF.Ld r.nEU.C rt. Fr Ar.U1 Ar.U2 Ar.U3 Ar.U12 Ar.U23 Ar.U31 Ar.C1 Ar.C2 Ar.C3 Ar. P Ar. q Ar. S Ar. PF A.PF.LG A.PF.Ld A.nEU.C Ar. Fr Acd.P.i Designation NONE V1/12 RT6 V2/23 RT6 V3/31 RT6 V12 RT V23 RT V31 RT I1 RT I2 RT I3 RT kW RT kvar RT kVA RT PF RT PF LAG RT PF LEAD RT In RT FREQ RT V1/12 AVR6 V2/23 AVR6 V3/31 AVR6 V12 AVR V23 AVR V31 AVR I1 AVR I2 AVR I3 AVR kW AVR kvar AVR kVA AVR PF AVR PF LAG AVR PF LEAD AVR In AVR FREQ AVR kW IMP ACC DMD Description None (output disabled) 1-Cycle Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage V12 Voltage V23 Voltage V31 Voltage I1 Current I2 Current I3 Current 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Total PF Lag Total PF Lead 1-Cycle Auxiliary Values In Current Frequency 1-Sec Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage V12 Voltage V23 Voltage V31 Voltage I1 Current I2 Current I3 Current 1-Sec Total Values Total kW Total kvar Total kVA Total PF Total PF Lag Total PF Lead 1-Sec Auxiliary Values In Current Frequency Demands EH Accumulated kW import demand

In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages.

116

PM130 PLUS Powermeters Series

Appendix BAnalog Output Parameters

Display Code Acd.P.E Acd.q.i Acd.q.E Acd.S

Designation kW EXP ACC DMD kvar IMP ACC DMD kvar EXP ACC DMD kVA ACC DMD

Accumulated Accumulated Accumulated Accumulated

Description kW export demand kvar import demand kvar export demand kVA demand

PM130 Powermeters Series

117

Appendix CSetpoint Triggers and Actions

Appendix C

Setpoint Triggers and Actions


Designation NONE STAT STAT STAT STAT STAT STAT STAT STAT INP #1 ON INP #2 ON INP #3 ON INP #4 ON INP #1 OFF INP #2 OFF INP #3 OFF INP #4 OFF #1 #2 #1 #2 ON ON OFF OFF Description None (condition is not active) Status Inputs Status input #1 ON Status input #2 ON Status input #3 ON Status input #4 ON Status input #1 OFF Status input #2 OFF Status input #3 OFF Status input #4 OFF Relays Relay #1 ON Relay #2 ON Relay #1 OFF Relay #2 OFF Phase Reversal Positive phase rotation reversal Negative phase rotation reversal 1-Cycle Values on any Phase High voltage Low voltage High current Low current High voltage THD High current THD High K-Factor High current TDD 1-Cycle Auxiliary Values High frequency Low frequency High voltage unbalance High current unbalance 1-Sec Phase Values High I1 current High I2 current High I3 current Low I1 current Low I2 current Low I3 current 1-Sec Values on any Phase High voltage Low voltage High current Low current 1-Sec Total Values High total kW import High total kW export High total kvar import High total kvar export High total kVA Low total PF Lag Low total PF Lead 1-Sec Auxiliary Values High neutral current

Table 38: Setpoint Triggers Parameters


Display Code nonE S1.On S2.On S3.On S4.On S1.OFF S1.OFF S3.OFF S4.OFF r1.On r2.On r1.OFF r2.OFF POS.P.r nEG.P.r r.Hi. U r.Lo. U r.Hi. C r.Lo. C r.thd.U r.thd.C r.HFc.C r.tdd.C r.Hi.Fr r.Lo.Fr r.U.Unb r.C.Unb A.Hi.C1 A.Hi.C2 A.Hi.C3 A.Lo.C1 A.Lo.C2 A.Lo.C3 A.Hi. U A.Lo. U A.Hi. C A.Lo. C A.Hi.P.i A.Hi.P.E A.Hi.q.i A.Hi.q.E A.Hi. S A.PF.LG A.PF.Ld A.nEU.C

RELAY RELAY RELAY RELAY

POS PHASE REVERSAL NEG PHASE REVERSAL HI VOLT RT 1 LO VOLT RT 1 HI AMPS RT LO AMPS RT HI V THD 2 HI I THD 2 HI KF RT HI I TDD HI FREQ RT LO FREQ RT HI V UNB% RT 1 HI I UNB% RT HI I1 AVR HI I2 AVR HI I3 AVR LO I1 AVR LO I2 AVR LO I3 AVR HI VOLT AVR 1 LO VOLT AVR 1 HI AMPS AVR LO AMPS AVR HI HI HI HI HI HI HI kW IMP AVR kW EXP AVR kvar IMP AVR kvar EXP AVR kVA AVR PF LAG AVR PF LEAD AVR

HI In AVR

118

PM130 Powermeters Series

Appendix CSetpoint Triggers and Actions

Display Code A.Hi.Fr A.Lo.Fr Hi.d.U1 Hi.d.U2 Hi.d.U3 Hi.d.C1 Hi.d.C2 Hi.d.C3 Hi.d.P Hi.d.q Hi.d. S Hi.Sd.P Hi.Sd.q Hi.Sd. S Hi.Ad.P Hi.Ad.q Hi.Ad. S Hi.Pd.P Hi.Pd.q Hi.Pd. S

Designation HI FREQ RT LO FREQ RT HI HI HI HI HI HI HI HI HI HI HI HI HI HI HI HI HI HI V1/12 DMD 1 V2/23 DMD 1 V3/31 DMD 1 I1 DMD I2 DMD I3 DMD kW IMP BD kvar IMP BD kVA BD kW IMP SD kvar IMP SD kVA SD kW IMP ACC DMD kvar IMP ACC DMD kVA ACC DMD kW IMP PRD DMD kvar IMP PRD DMD kVA PRD DMD

Description High frequency Low frequency Demands High V1/V12 Volt demand High V2/V23 Volt demand High V3/V31 Volt demand High I1 Ampere demand High I2 Ampere demand High I3 Ampere demand High block kW import demand High block kvar import demand High block kVA demand High sliding window kW import demand High sliding window kvar import demand High sliding window kVA demand High accumulated kW import demand High accumulated kvar import demand High accumulated kVA demand High predicted kW import demand High predicted kvar import demand High predicted kVA demand

1 In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltages will be lineto-neutral; for any other wiring mode, they will be line-to-line voltages.

Table 39: Setpoint Actions Parameters


Display Code none r1 On r2 On r1 OFF r2 OFF In.Cn.1 In.Cn.2 In.Cn.3 In.Cn.4 ti.Cn.1 ti.Cn.2 ti.Cn.3 ti.Cn.4 Designation NONE OPERATE RELAY #1 OPERATE RELAY #2 RELEASE RELAY #1 RELEASE RELAY #2 INC CNT #1 INC CNT #2 INC CNT #3 INC CNT #4 TIME CNT #1 TIME CNT #2 TIME CNT #3 TIME CNT #4 Description None (no action) Operate RO1 Operate RO2 Release latched RO1 Release latched RO2 Increment counter #1 Increment counter #2 Increment counter #3 Increment counter #4 Count operation time using Count operation time using Count operation time using Count operation time using

counter counter counter counter

#1 #2 #3 #4

PM130 Powermeters Series

119

Appendix DParameters for Data Monitoring

Appendix D Parameters for Data Monitoring


The following table lists parameters measured by the meter that are available for monitoring through communications. The left column shows data abbreviations used in PAS. Parameter groups are highlighted in bold.

Table 40: Data Monitoring Parameters


Designation NONE DIGITAL INPUTS DI1:16 RELAYS RO1:16 COUNTERS COUNTER 1 COUNTER 2 COUNTER 3 COUNTER 4 RT PHASE V1 V2 V3 I1 I2 I3 kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 PF L1 PF L2 PF L3 V1 THD V2 THD V3 THD I1 THD I2 THD I3 THD I1 KF I2 KF I3 KF I1 TDD I2 TDD I3 TDD V12 V23 V31 RT TOTAL kW kvar kVA PF PF LAG Description None (stub, read as zero) Digital Inputs Digital Inputs Status DI1:DI4 Relays Relay Status RO1:RO2 Pulse Counters Counter #1 Counter #2 Counter #3 Counter #4 1-Cycle Phase Values V1/V12 Voltage 1 V2/V23 Voltage 1 V3/V31 Voltage 1 I1 Current I2 Current I3 Current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1/V12 Voltage THD 1 V2/V23 Voltage THD 1 V3/V31 Voltage THD 1 I1 Current THD I2 Current THD I3 Current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 Current TDD I2 Current TDD I3 Current TDD V12 Voltage V23 Voltage V31 Voltage 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Total PF lag

120

PM130 Powermeters Series

Appendix DParameters for Data Monitoring

Designation PF LEAD kW IMP kW EXP kvar IMP kvar EXP V AVG V LL AVG I AVG RT AUX In FREQ V UNB% I UNB% AVR PHASE V1 V2 V3 I1 I2 I3 kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 PF L1 PF L2 PF L3 V1 THD V2 THD V3 THD I1 THD I2 THD I3 THD I1 KF I2 KF I3 KF I1 TDD I2 TDD I3 TDD V12 V23 V31 AVR TOTAL kW kvar kVA PF PF LAG PF LEAD kW IMP kW EXP kvar IMP kvar EXP V AVG V LL AVG I AVG AVR AUX In FREQ V UNB%

Description Total PF lead Total kW import Total kW export Total kvar import Total kvar export 3-phase average L-N/L-L voltage 3-phase average L-L voltage 3-phase average current 1-Cycle Auxiliary Values In (neutral) Current Frequency Voltage unbalance Current unbalance 1-Second Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1/V12 Voltage THD 1 V2/V23 Voltage THD 1 V3/V31 Voltage THD 1 I1 Current THD I2 Current THD I3 Current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 Current TDD I2 Current TDD I3 Current TDD V12 Voltage V23 Voltage V31 Voltage 1-Second Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Total kW import Total kW export Total kvar import Total kvar export 3-phase average L-N/L-L voltage 1 3-phase average L-L voltage 3-phase average current 1-Second Auxiliary Values In (neutral) Current Frequency Voltage unbalance

PM130 Powermeters Series

121

Appendix DParameters for Data Monitoring

Designation I UNB% PHASORS V1 Mag V2 Mag V3 Mag I1 Mag I2 Mag I3 Mag V1 Ang V2 Ang V3 Ang I1 Ang I2 Ang I3 Ang DEMANDS V1 DMD V2 DMD V3 DMD I1 DMD I2 DMD I3 DMD kW IMP BD kvar IMP BD kVA BD kW IMP SD kvar IMP SD kVA SD kW IMP ACC DMD kvar IMP ACC DMD kVA ACC DMD kW IMP PRD DMD kvar IMP PRD DMD kVA PRD DMD PF IMP@kVA MXDMD kW EXP BD kvar EXP BD kW EXP SD kvar EXP SD kW EXP ACC DMD kvar EXP ACC DMD kW EXP PRD DMD kvar EXP PRD DMD SUMM ACC DMD SUM REG1 ACC DMD SUM REG2 ACC DMD SUM REG3 ACC DMD SUM REG4 ACC DMD SUMM BLK DMD SUM REG1 BLK DMD SUM REG2 BLK DMD SUM REG3 BLK DMD SUM REG4 BLK DMD SUMM SW DMD SUM REG1 SW DMD SUM REG2 SW DMD SUM REG3 SW DMD SUM REG4 SW DMD ENERGY kWh IMPORT kWh EXPORT kvarh IMPORT kvarh EXPORT kVAh TOTAL

Description Current unbalance Phasors V1/V12 Voltage magnitude 1 V2/V23 Voltage magnitude 1 V3/V31 Voltage magnitude 1 I1 Current magnitude I2 Current magnitude I3 Current magnitude V1/V12 Voltage angle 1 V2/V23 Voltage angle 1 V3/V31 Voltage angle 1 I1 Current angle I2 Current angle I3 Current angle Present Demands (Power Demands EH) V1/V12 Volt demand 1 V2/V23 Volt demand 1 V3/V31 Volt demand 1 I1 Ampere demand I2 Ampere demand I3 Ampere demand kW import block demand kvar import block demand kVA block demand kW import sliding window demand kvar import sliding window demand kVA sliding window demand kW import accumulated demand kvar import accumulated demand kVA accumulated demand kW import predicted sliding window demand kvar import predicted sliding window demand kVA predicted sliding window demand PF (import) at Maximum kVA sliding window demand kW export block demand kvar export block demand kW export sliding window demand kvar export sliding window demand kW export accumulated demand kvar export accumulated demand kW export predicted sliding window demand kvar export predicted sliding window demand Summary (TOU Total) Accumulated Demands EH Summary register #1 demand Summary register #2 demand Summary register #3 demand Summary register #4 demand Summary (TOU Total) Block Demands EH Summary register #1 demand Summary register #2 demand Summary register #3 demand Summary register #4 demand Summary (TOU Total) Sliding Demands EH Summary register #1 demand Summary register #2 demand Summary register #3 demand Summary register #4 demand Total Energy EH kWh import kWh export kvarh import kvarh export kVAh total

122

PM130 Powermeters Series

Appendix DParameters for Data Monitoring

Designation SUMMARY REGS SUM REG1 SUM REG2 SUM REG3 SUM REG4 PHASE ENERGY kWh IMP L1 kWh IMP L2 kWh IMP L3 kvarh IMP L1 kvarh IMP L2 kvarh IMP L3 kVAh L1 kVAh L2 kVAh L3 %HD V1 V1 %HD01 V1 %HD02 V1 %HD40 %HD V2 V2 %HD01 V2 %HD02 V2 %HD40 %HD V3 V3 %HD01 V3 %HD02 V3 %HD40 %HD I1 I1 %HD01 I1 %HD02 I1 %HD40 %HD I2 I2 %HD01 I2 %HD02 I2 %HD40 %HD I3 I3 %HD01 I3 %HD02 I3 %HD40 ANG V1 V1 H01 ANG V1 H02 ANG V1 H40 ANG ANG V2 V2 H01 ANG V2 H02 ANG V2 H40 ANG ANG V3 V3 H01 ANG V3 H02 ANG V3 H40 ANG ANG I1

Description Summary (TOU Total) Energy Registers EH Summary energy register #1 Summary energy register #2 Summary energy register #3 Summary energy register #4 Phase Energy EH kWh import L1 kWh import L2 kWh import L3 kvarh import L1 kvarh import L2 kvarh import L3 kVAh total L1 kVAh total L2 kVAh total L3 V1/V12 Harmonic Distortions EH 1 H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion V2/V23 Harmonic Distortions EH 1 H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion V3/V31 Harmonic Distortions EH 1 H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion I1 Harmonic Distortions EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion I2 Harmonic Distortions EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion I3 Harmonic Distortions EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion V1/V12 Harmonic Angles EH 1 H01 Harmonic angle H02 Harmonic angle ... H40 Harmonic angle V2/V23 Harmonic Angles EH 1 H01 Harmonic angle H02 Harmonic angle ... H40 Harmonic angle V3/V31 Harmonic Angles EH 1 H01 Harmonic angle H02 Harmonic angle ... H40 Harmonic angle I1 Harmonic Angles EH

PM130 Powermeters Series

123

Appendix DParameters for Data Monitoring

Designation I1 H01 ANG I1 H02 ANG I1 H40 ANG ANG I2 I2 H01 ANG I2 H02 ANG I2 H40 ANG ANG I3 I3 H01 ANG I3 H02 ANG I3 H40 ANG H1 PHASE V1 H01 V2 H01 V3 H01 I1 H01 I2 H01 I3 H01 kW L1 H01 kW L2 H01 kW L3 H01 kvar L1 H01 kvar L2 H01 kvar L3 H01 kVA L1 H01 kVA L2 H01 kVA L3 H01 PF L1 H01 PF L2 H01 PF L3 H01 HRM TOT POW kW H01 kvar H01 kVA H01 PF H01 MIN PHASE V1 MIN V2 MIN V3 MIN I1 MIN I2 MIN I3 MIN MIN TOTAL kW MIN kvar MIN kVA MIN PF MIN MIN AUX In MIN FREQ MIN MAX PHASE V1 MAX V2 MAX V3 MAX I1 MAX I2 MAX I3 MAX MAX TOTAL kW MAX kvar MAX

Description H01 Harmonic angle H02 Harmonic angle ... H40 Harmonic angle I2 Harmonic Angles EH H01 Harmonic angle H02 Harmonic angle ... H40 Harmonic angle I3 Harmonic Angles EH H01 Harmonic angle H02 Harmonic angle ... H40 Harmonic angle Fundamental (H01) Phase Values V1/V12 Voltage 1 V2/V23 Voltage 1 V3/V31 Voltage 1 I1 Current I2 Current I3 Current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 Fundamental and Harmonic Total Power Values Total fundamental kW Total fundamental kvar Total fundamental kVA Total fundamental PF Minimum 1-Cycle Phase Values V1/V12 Voltage 1 V2/V23 Voltage 1 V3/V31 Voltage 1 I1 Current I2 Current I3 Current Minimum 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Minimum 1-Cycle Auxiliary Values In Current Frequency Maximum 1-Cycle Phase Values V1/V12 Voltage 1 V2/V23 Voltage 1 V3/V31 Voltage 1 I1 Current I2 Current I3 Current Maximum 1-Cycle Total Values Total kW Total kvar

124

PM130 Powermeters Series

Appendix DParameters for Data Monitoring

Designation kVA MAX PF MAX MAX AUX In MAX FREQ MAX MAX DMD V1 DMD MAX V2 DMD MAX V3 DMD MAX I1 DMD MAX I2 DMD MAX I3 DMD MAX kW IMP SD MAX kW EXP SD MAX kvar IMP SD MAX kvar EXP SD MAX kVA SD MAX MAX SUMMARY DMD SUM REG1 DMD MAX SUM REG2 DMD MAX SUM REG3 DMD MAX SUM REG4 DMD MAX AO RAW AO1 AO2 AO3 AO4 TOU PRMS ACTIVE TARIFF ACTIVE PROFILE TOU REG1 TOU REG1 TRF1 TOU REG1 TRF2 TOU REG1 TRF3 TOU REG1 TRF4 TOU REG2 TOU REG2 TRF1 TOU REG2 TRF2 TOU REG2 TRF3 TOU REG2 TRF4 TOU REG3 TOU REG3 TRF1 TOU REG3 TRF2 TOU REG3 TRF3 TOU REG3 TRF4 TOU REG4 TOU REG4 TRF1 TOU REG4 TRF2 TOU REG4 TRF3 TOU REG4 TRF4 TOU MAX DMD REG1 DMD1 TRF1 MAX DMD1 TRF2 MAX DMD1 TRF3 MAX DMD1 TRF4 MAX TOU MAX DMD REG2 DMD2 TRF1 MAX DMD2 TRF2 MAX DMD2 TRF3 MAX DMD2 TRF4 MAX TOU MAX DMD REG3 DMD3 TRF1 MAX

Description Total kVA Total PF Maximum 1-Cycle Auxiliary Values In Current Frequency Maximum Demands (Power Demands EH) V1/V12 Maximum volt demand 1 V2/V23 Maximum volt demand 1 V3/V31 Maximum volt demand 1 I1 Maximum ampere demand I2 Maximum ampere demand I3 Maximum ampere demand Maximum kW import sliding window demand Maximum kvar import sliding window demand Maximum kW export sliding window demand Maximum kvar export sliding window demand Maximum kVA sliding window demand Maximum Summary (TOU Total) Demands EH Summary register #1 maximum demand Summary register #2 maximum demand Summary register #3 maximum demand Summary register #4 maximum demand Raw Analog Outputs (A/D Units) Analog output AO1 Analog output AO2 Analog output AO3 Analog output AO4 TOU Parameters EH Active TOU tariff Active TOU profile TOU Energy Register #1 EH Tariff #1 register Tariff #2 register Tariff #3 register Tariff #4 register TOU Energy Register #2 EH Tariff #1 register Tariff #2 register Tariff #3 register Tariff #4 register TOU Energy Register #3 EH Tariff #1 register Tariff #2 register Tariff #3 register Tariff #4 register TOU Energy Register #4 EH Tariff #1 register Tariff #2 register Tariff #3 register Tariff #4 register TOU Maximum Demand Register #1 EH Tariff #1 register Tariff #2 register Tariff #3 register Tariff #4 register TOU Maximum Demand Register #2 EH Tariff #1 register Tariff #2 register Tariff #3 register Tariff #4 register TOU Maximum Demand Register #3 EH Tariff #1 register

PM130 Powermeters Series

125

Appendix DParameters for Data Monitoring

Designation DMD3 TRF2 MAX DMD3 TRF3 MAX DMD3 TRF4 MAX TOU MAX DMD REG4 DMD4 TRF1 MAX DMD4 TRF2 MAX DMD4 TRF3 MAX DMD4 TRF4 MAX

Description Tariff #2 register Tariff #3 register Tariff #4 register TOU Maximum Demand Register #4 EH Tariff #1 register Tariff #2 register Tariff #3 register Tariff #4 register

1 In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltages will be lineto-neutral; for any other wiring mode, they will be line-to-line voltages.

126

PM130 Powermeters Series

Appendix EData Scales

Appendix E Data Scales


The maximum values for volts, amps and power in the PM130 setup and in communications are limited by the voltage and current scale settings. See the Device Options setup in Chapter 3 or Device Options in Chapter 4 on how to change the voltage and current scales in your meter. The following table defines the meter data scales.

Table 41: Data Scales Values


Scale Conditions Maximum All configurations voltage (V max) Maximum current (I max) Maximum Power 4 All configurations Wiring 4LN3, 3LN3, 3BLN3 Range Voltage scale PT Ratio, V 1 Current scale CT Ratio, A 2, 3 V max I max 3, W

Wiring 4LL3, 3LL3, 3BLL3, V max I max 2, W 3OP2, 3OP3, 3DIR2 Maximum frequency
1

25, 50 or 60 Hz 400Hz

100 Hz 500 Hz

The default voltage scale is 144V. The recommended voltage scale is 120V+20% = 144V for using with external PTs, and 690V+20% = 828V for a direct connection to power line.
CT Ratio = CT primary current/CT secondary current

2 3

The default current scale is 2 CT secondary


(2.0A with 1A secondary and 10.0A with 5A secondary).

Maximum power is rounded to whole kilowatts. With PT=1.0, it is limited to 9,999,000 W.

PM130 Powermeters Series

127

Appendix FDevice Diagnostic Codes

Appendix F

Device Diagnostic Codes


Table 42: Device Diagnostic Codes Parameters
Diagnostic Message dAtA rSt CPU runt tout PWr.UP rStrt Description Memory/Data fault Hardware watchdog reset CPU exception Run-time software error Software watchdog timeout Power Down/Up Warm restart Reason Hardware failure Hardware failure Hardware failure Hardware failure Hardware failure Normal power-up sequence External restart via communications or by firmware upgrade Corrupted setup data has been replaced with the default configuration The clock time has been lost Battery replacement is required Hardware failure

Diagnostic Code 2 3 5 6 7 8 9

10

ConF

Configuration reset

11 13 15

rtc Lo.bAt EEPr

RTC fault Low battery (with a battery backup unit) EEPROM fault

See Diagnostics Display in Chapter 3 for more information on the PM130 built-in diagnostics.

128

PM130 Powermeters Series

Appendix FDevice Diagnostic Codes

Index
A accuracy, 101 active energy, 100 active power, 100 analog output, 8 B burden, 95 C CT, 28, 54, 100, 113 CT PRIMARY CURRENT, 100 current transformers, 100 D demand, 10, 32, 34, 35 diagnostic, 10 display, 27, 28, 29, 30, 54 display mode, 30 E energy, 100 F frequency, 100 terminals, 2 I inputs, 10 Wye, 65 W T open delta, 16, 65 P password, 30, 36 power, 2, 6, 8, 14, 15, 21, 24, 72, 100 power factor, 100 power source, 2, 14, 15, 21, 24 PT, 96, 100, 113 R reactive energy, 100 reactive power, 100 registers, 80 reset, 36 Load bar graph, 28 M measurement, 101 mounting, 13 O L