Prefco is a leading brand of Life-Safety Fire, Smoke, and Ceiling Radiation dampers. We are dedicated to providing the best service of any manufacturer serving the HVAC market today. Manufactured by Perfect Air Control, Inc., Prefco is an industry leader in the innovation and development of these important HVAC components. Our products are designed, manufactured, and tested in compliance with appropriate UL Standards for Safety as well as many state and international standards. The Prefco brand is sold throughout the United States as well as Canada, South America, the Far East, and Middle East through a broad network of representatives, distributors, and licensees, knowledgeable in all phases of HVAC design. In the interest of product development, Prefco reserves the right to make changes without notice.

Table of Contents
Mutliblade Fire Dampers
Series 5000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Model 5000 Model 5003 Series 5500 E6 / DE6 . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 5500 E6 LPB 5500 E6 BC 5500 E6 CR 5500 E6 CO 5500 E6 LPC 5500 E6 M 5500 E6 ML 5500 DE6 LPB 5500 DE6 BC 5500 DE6 CR 5500 DE6 CO 5500 DE6 LPC 5500 DE6 M 5500 DE6 ML Series 5500 E8 / DE8 . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 5500 E8 CR 5500 E8 CO 5500 E8 LPC 5500 E8 M 5500 E8 ML 5500 DE8 CR 5500 DE8 CO 5500 DE8 LPC 5500 DE8 M 5500 DE8 ML Series 5500 E2 / DE2 . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 5500 E2 A 5500 DE2 A Series 5500 SF / DSF . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 5500 SF M 5500 DSF LPB 5500 DSF 2 1/2 5500 SF1.5 A 5500 DSF1.5 A

Combination Fire + Smoke Dampers


Series 5050 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Model 5050-1 Model 5050-2 Model 5050-3 Series 5000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Model 5053-1 Model 5053-2 Model 5053-3 Series 5050 TC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Model 5050 TC-1 Model 5050 TC-2

Smoke Dampers
Series 5150 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Model 5150-1 Model 5150-2 Model 5150-3

Pressure Drop Information and Actuators . . . . . . . . .8 Curtain Dampers


Series 5500 E4 / DE4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 5500 E4 A 5500 E4 A3 5500 E4 BC 5500 E4 BC3 5500 E4 C 5500 E4 C3 5500 E4 CR 5500 E4 CR3 5500 E4 CO 5500 E4 CO3 5500 E4 ML 5500 E4 ML3 5500 DE4 A 5500 DE4 A3 5500 DE4 BC 5500 DE4 BC3 5500 DE4 C 5500 DE4 C3 5500 DE4 CR 5500 DE4 CR3 5500 DE4 CO 5500 DE4 CO3 5500 DE4 ML 5500 DE4 ML3

Radiation Dampers
Series 5600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 5600 / 5600EF 5610 / 5610EF 5650 / 5650EF 5673 / 5673EF 5660 / 5660EF 5680 / 5680EF

Butterfly / Single Blade Fire Dampers


Series 5600F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 5600F 5600F3 5630F 5650F 5650F3 5660F 5660F3

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Multiblade Fire Dampers


For Use in Static or Dynamic Systems
Application

Series 5000

Series 5000 multi-blade fire dampers are UL555 fire dampers that can be either static or dynamic rated. When applied in a dynamic (fans on) system, this damper has been evaluated with bi-directional airflow, and is rated to 3000 FPM and 4" static pressure in compliance with UL555 6th edition. Series 5000 meets or complies with the following as a fire damper: CA State Fire Marshall Fire listing #3225-1518:100
Available Models Model 5000 5003 Description 1 1/2 HR Fire 3 HR Fire

NFPA 90A & B All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code

UL Listings File #R6189 Model 5000 - UL555 1 1/2 Hour Fire Static or Dynamic Model 5003 - UL555 3 Hour Fire Static or Dynamic

Typical Pressure Drop Per Duct Velocity Pressure drop information is from a 24" x 24" damper. Pressure drop through a smaller damper will be higher. Duct Velocity (FPM) 500 Full Open
Pressure Drop / Inches of Water

600

700

800

900 1000 1250 1500 1750 2000 3000 4000

.010 .013 .015 .021 .030 .035 .040 .067 .080 .100 .250 .480

Model 5000 Standard Sizes Type Static Dynamic Fire Rating 1 1/2 HR Fire 1 1/2 HR Fire Min. Vertical or Horizontal 6" x 6" 6" x 6" Max. Vertical 120" x 84" 36" x 45" Max Horizontal 144" x 90" 36" x 45"

Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.

Model 5003 Standard Sizes

A dim. is always width of blades

Type Static Dynamic

Fire Rating 3 Hour Fire 3 Hour Fire

Min. Vertical 6" x 6" 6" x 6"

Max Vertical 30" x 30" 30" x 30"

Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.

5000

Standard Construction
Frame 4" Wrap around full channel frame 16 GA Galvanized Steel Blades 22 GA Galvanized Steel, Modified Triple-V Design Bearings Integral Curl in Frame Design Linkage 14 GA Galvanized, on Blade Type (in airstream) Heat Responsive Device Fusible Link 165F standard, 212, 250 or 350F optional

Options & Accessories


Dual Blade Position Indicator Switches (Switch#1) Factory Supplied Sleeves 18 or 14 Gauge, 18" or 24" deep (For other gauges and depths, contact your local rep) Factory supplied EZ Mount mounting angles Single or Dual Blade stiffeners - for strength & stability of wider units in high pressure systems

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Series 5050
Application

Combination Fire & Smoke Dampers 1 1/2 Hour Class I/II/III Leakage
For Use in Static or Dynamic Systems

Series 5050 is a combination fire & smoke damper with a 1 1/2 Hour UL555 fire rating available with your choice of Class I, II, or III UL555S Leakage rating. This damper utilizes a thermally responsive electric switch to allow for the return spring of the specified actuator to close the damper upon elevated temperature. The damper may be installed vertically or horizontally for use in barriers requiring both fire and leakage protection. This damper has been evaluated with bi-directional airflow, and is rated to 2000 FPM and 4" static pressure in compliance with UL555 6th edition and UL555S 4th edition.
Available Models Model Description 5050-1 / Class I 1 1/2 HR Fire 5050-2 / Class II 1 1/2 HR Fire 5050-3 / Class III 1 1/2 HR Fire

Series 5050 meets or complies with the following as a smoke, fire or combination fire & smoke damper: CA State Fire Marshall Fire listing #3225-1518:100
Leakage listing #3230-1518:106

NFPA 90A & B, 92A & B All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code Models 5050-1 / 5050-2 / 5050-3 UL Listings File #R6189 UL555 1 1/2 Hour Fire
Internally mounted actuator

UL555S Class I/II/III @ 250F or 350F

Series 5050 Standard Sizes See actuator section, pg. 8 for internal mount minimums and pressure drop information Fire Rating 1 1/2 Hour Fire 1 1/2 Hour Fire Leakage Rating Class I/II/III @ 250F Class I/II/III @ 350F Min. Vertical or Horizontal 6" x 6" 6" x 6" Max. Vertical 120" x 84" 120" x 84" Max Horizontal 144" x 90" 144" x 90"

Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.

A dim. is always width of blades

5050

Standard Construction
Frame 4" Wrap around full channel frame 16 GA Galvanized Steel Blades 22 GA Galvanized Steel , Modified Triple-V Design Bearings Integral Curl in Frame Design Linkage 14 GA Galvanized, on Blade Type (in airstream) Seals Compression type silicone seals (Class I/II ONLY) Heat Responsive Device Electric-Thermal Disc, 165F standard, 212, 250 or 350F optional Sealant UL Certified silicone caulk (sleeved units only)

Options & Accessories


Dual Blade Position Indicator Switches (Switch#1) Factory Supplied Sleeves 18 or 14 Gauge, 18" or 24" deep
(For other gauges and depths, contact your local rep. Dampers with external mounted actuators are available with a 18 gauge side plate, if no factory sleeve is desired)

Factory supplied EZ Mount mounting angles Single or Dual Blade stiffeners - for strength & stability of wider
units in high pressure systems

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Combination Fire & Smoke Dampers 3 Hour Class I/II/III Leakage


For Use in Static or Dynamic Systems
Application

Series 5053

Series 5053 is a combination fire & smoke damper with a 3 Hour UL555 fire rating available with your choice of Class I, II, or III UL555S Leakage rating. This damper utilizes a thermally responsive electric switch to allow for the return spring of the specified actuator to close the damper upon elevated temperature. The damper may be installed vertically for use in barriers requiring both fire and leakage protection. This damper has been evaluated with bi-directional airflow, and is rated to 2000 FPM and 4" static pressure in compliance with UL555 6th edition and UL555S 4th edition. Series 5053 meets or complies with the following as a smoke, fire or combination fire & smoke damper: CA State Fire Marshall Fire listing #3225-1518:100
Leakage listing #3230-1518:106

Available Models Model 5053-1 / Class I 5053-2 / Class II 5053-3 / Class III Description 3 HR Fire 3 HR Fire 3 HR Fire

NFPA 90A & B, 92A & B All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code

UL Listings File #R6189 UL555 3 Hour Fire UL555S Class I/II/III @ 250F or 350F

Series 5053 Standard Sizes See actuator section, pg. 8 for internal mount minimums and pressure drop information Fire Rating 3 Hour Fire 3 Hour Fire Leakage Rating Class I/II/III @ 250F Class I/II/III @ 350F Min. Vertical 6" x 6" 6" x 6" Max. Vertical 30" x 30" 30" x 30"

Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.

A dim. is always width of blades

Standard Construction
Frame 4" Wrap around full channel frame 16 GA Galvanized Steel Blades 22 GA Galvanized Steel , Modified Triple-V Design Bearings Integral Curl in Frame Design Linkage 14 GA Galvanized, on Blade Type (in airstream) Seals Compression type silicone seals (Class I/II ONLY) Heat Responsive Device Electric-Thermal Disc, 165F standard, 212, 250 or 350F optional Sealant UL Certified silicone caulk (sleeved units only)

Options & Accessories


Dual Blade Position Indicator Switches (Switch#1)

Factory Supplied Sleeves 18 or 14 Gauge, 18" or 24" deep (For other gauges and depths, contact your local rep. Dampers with external mounted actuators are available with a 18 gauge side plate, if no factory sleeve is desired) Factory supplied EZ Mount mounting angles Single or Dual Blade stiffeners - for strength & stability of wider units in high pressure systems

5053

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Series 5050 TC
Application

Combination Fire & Smoke Dampers


For Tunnel Corridor Applications For Use in Static or Dynamic Systems

Series 5050TC is a combination fire and smoke damper that is UL classified for interior tunnel corridor ceiling penetrations. When installed in a tunnel-type corridor ceiling, the damper assembly carries a 1 hour UL555 fire rating and a Class I/II UL555S leakage rating. This damper also can be applied as a standard fire and smoke damper. It may be mounted horizontally or vertically, is approved for bi-directional airflow, and is rated to 2000 FPM and 4" static pressure in compliance with UL555 6th edition and UL555S 4th edition. Series 5050TC meets or complies with the following as a corridor smoke, fire or combination fire & smoke damper: CA State Fire Marshall Fire listing #3225-1518:100
Leakage listing #3230-1518:106

Externally mounted actuator

Available Models Model 5050TC-1 / Class I Description 1 1/2 HR Fire

5050TC-2 / Class II 1 1/2 HR Fire

NFPA 90A & B, 92A & B All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code

UL Listings File #R6189 UL555 1 Hour Fire Corridor - 1 1/2 Hour Fire Wall / Floor
Internally mounted actuator

UL555S Class I/II @ 250F or 350F

5050 TC

Series 5050 TC Standard Sizes See actuator section, pg. 8 for internal mount minimums and pressure drop information Application Fire Rating Corridor Corridor 1 Hour 1 Hour Leakage Rating Class I / II @ 250F Class I / II @ 350F Min. Vert. or Horiz. Max Vert. Max Horiz. 6" x 6" 6" x 6" 6" x 6" 6" x 6" N/A N/A 24" x 24" 24" x 24" 24" x 24" 24" x 24" 24" x 24" 24" x 24"

Fire/Smoke 1 1/2 Hour Class I / II @ 250F Fire/Smoke 1 1/2 Hour Class I / II @ 350F

Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.

A dim. is always width of blades

Standard Construction
Frame 4" Wrap around full channel frame 16 GA Galvanized Steel Blades 22 GA Galvanized Steel, Modified Triple-V Design Bearings Integral Curl in Frame Design Linkage 14 GA Galvanized, on Blade Type (in airstream) Seals Compression type silicone seals Heat Responsive Device Electric-Thermal Disc, 165F standard, 212, 250 or 350F optional Sealant UL Certified silicone caulk (sleeved units only)

Options & Accessories


Dual Blade Position Indicator Switches (Switch#1) Factory Supplied Sleeves 18 or 14 Gauge, 18" or 24" deep (For other gauges and depths, contact your local rep) Factory supplied EZ Mount mounting angles Single or Dual Blade stiffeners - for strength & stability of wider units in high pressure systems

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Smoke Dampers Class I/II/III Leakage


For Use in Static or Dynamic Systems
Application

Series 5150

Series 5150 is a UL555S approved Smoke damper available for Class I, II, or III. Series 5150 can utilize a variety of internally or externally mounted actuators. The damper may be installed vertically or horizontally in ducts penetrating barriers requiring leakage protection, within 24" of the barrier being protected. This damper has been evaluated with bi-directional airflow, and is rated to 2000 FPM and 4" static pressure in compliance UL555S 4th edition. Series 5150 meets or complies with the following as a smoke damper: CA State Fire Marshall Leakage listing #3230-1518:106
Available Models Model 5150-1 / Class I 5150-2 / Class II 5150-3 / Class III

NFPA 90A & B, 92A & B All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code

UL Listings File #R6189 UL555S Class I/II/III @ 250F or 350F

Series 5150 Standard Sizes See actuator section, pg. 8 for internal mount minimums and pressure drop information Leakage Rating Class I/II/III @ 250F Class I/II/III @ 350F Min. Vertical or Horizontal 6" x 6" 6" x 6" Max. Vertical or Horizontal 144" x 96" or 288" x 48" 144" x 96" or 288" x 48"

*Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.

A dim. is always width of blades

Standard Construction
Frame 4" Wrap around full channel frame 16 GA Galvanized Steel Blades 22 GA Galvanized Steel , Modified Triple-V Design Bearings Integral Curl in Frame Design Linkage 14 GA Galvanized, on Blade Type (in airstream) Seals Compression type silicone seals (Class I/II ONLY) Sealant UL Certified silicone caulk (sleeved units only)

Options & Accessories


Dual Blade Position Indicator Switches (Switch#1) Factory Supplied Sleeves 18 or 14 Gauge, 18" or 24" deep (For other gauges and depths, contact your local rep. Dampers with external mounted actuators are available with a 18 gauge side plate, if no factory sleeve is desired) Factory supplied EZ Mount mounting angles Single or Dual Blade stiffeners - for strength & stability of wider units in high pressure systems

5150

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Series 5050, 5053, 5050 TC and 5150 Pressure Drop


Typical Pressure Drop Per Duct Velocity
Pressure drop information is from a 24" x 24" damper. Pressure drop through a smaller damper will be higher.
Duct Velocity (FPM) Full Open 500 600 700 800 900 1000 1250 1500 1750 2000 3000 4000 .010 .013 .015 .021 .030 .035 .040 .067 .080 .100 .250 .480

Pressure Drop / Inches of Water

Series 5050, 5053, 5050 TC and 5150 Actuators


Specifications
Actuators will be mounted externally on the right side unless otherwise specified. Actuators available for internal or external mount (all must be factory mounted):
Actuator Model
Belimo FSNF120 Belimo FSNF24 Honeywell ML4115 Honeywell ML8115 Honeywell MS4209F, MS4309F Honeywell MS8209F, MS8309F Honeywell MS4120F Honeywell MS8120F

Voltage (AC)
120 24 120 24 120 24 120 24

Power Consumption Running


0.23A, 18W 24VA 0.18A, 18W 16VA 0.25A, 23W 23VA 0.35A, 35W 45VA

Holding
0.09A, 6W 24VA 0.11A, 9W 8VA 0.13A, 7W 7VA 0.15A, 10W 10VA

* Damper must be at least 13" in height for actuator to mount internally. * Unit must be 10" or greater in width for any internal actuator mounting orientation. * The factory will mount the actuator parallel to the damper, whenever height allows, unless otherwise specified.

Mounting Configurations
(140)
(140) (270)

(98)
(98)

(259)
(259)
Actuator Mounted perpendicular to the damper

*Damper height must be at least 18" for actuator to mount internally.


(102)

(110)
Actuator Mounted Parallel to the dampe
(102)
(140)

*Available Down To Min Height

(140)

(84)
(292) (84)

(272)

(272)

*Damper height must be at least 18" for actuator to mount internally.


(111) (102)
(140)

Actuator Mounted perpendicular to the damper *Available Down To Min Height


(102)

Actuator Mounted Parallel to the damp

(140) (233)
(57)

(130)
(191)

*Damper height must be at least 13" for actuator to mount internally.


(122)
Actuator Mounted Parallel to the damper

(191) (43)
Actuator Mounted perpendicular to the damper *Available Down To Min Height

(102)

(102)

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Curtain Fire Dampers (4 Frame)


Application

Series 5500 E4/ DE4

For Use in Static or Dynamic Systems


Series 5500 E4 or DE4 curtain fire dampers are UL Classified for installation in walls, floors, and partitions requiring a fire damper. Series 5500 E4 or DE4 is available with a UL555 Listing of either 1 1/2 or 3 hours. These dampers may be installed vertically or horizontally in static (5500 E4) or dynamic (5500 DE4) systems. Series 5500 E4 or DE4 meets or complies with the following as a fire damper: NFPA Standards All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code BS 476:Part 8; 20 & 22; ISO/DIS 834-1 & 10294-1 PREN 1366-2 Internationally Tested 4 hour CA State Fire Marshall - #3225-1518-101

UL Listing File #R6189 UL555 Listing 1 1/2 or 3 Hour Static (5500 E4)
UL555 1 1/2 Hour Fire - Static A V or H Type A - Frame and blades within airstream BC V or H Type B - Blades removed from airstream via cap CR V or H Type C - Frame blades removed from airstream sq. to round 5500 E4 CO V or H Type C - Frame and blades are removed from airstream sq. to oval C M V or H Type C - Frame and blades are removed from airstream V or H Flanged frame, oversized 2" from duct removes frame and partial blades from airstream

UL555 Listing 1 1/2 or 3 Hour Dynamic (5500 DE4)

Standard Construction
Frame Wrap-around frame 21 GA Galvanized Steel Blades - Low Profile Roll Formed 21 GA Galvanized Steel Closure Springs (Horizontal Models) Stainless Steel Constant Force Coil Fusible Link - UL-33 UL Listed 165 F (standard), 212 F (optional) McCabe Link (optional)

ML V or H Slip connection oversized 2" from duct removes frame and partial blades from airstream UL555 1 1/2 Hour Fire - Dynamic A V or H Type A - Frame and blades within airstream BC V or H Type B - Blades removed from airstream via cap 5500 DE4 CR V or H Type C - Frame blades removed from airstream sq. to round CO V or H Type C - Frame and blades are removed from airstream sq. to oval C M V or H Type C - Frame and blades are removed from airstream V or H Flanged frame, oversized 2" from duct removes frame and partial blades from airstream

E4/DE4

ML V or H Slip connection oversized 2" from duct removes frame and partial blades from airstream UL555 3 Hour Fire - Static A3 BC3 CR3 5500 E4 CO3 C3 M3 ML3 V V V V V V V Type A - Frame and blades within airstream Type B - Blades removed from airstream via cap Type C - Frame blades removed from airstream sq. to round Type C - Frame and blades are removed from airstream sq. to oval Type C - Frame and blades are removed from airstream Flanged frame, oversized 2" from duct removes frame and partial blades from airstream Slip connection oversized 2" from duct removes frame and partial blades from airstream

UL555 3 Hour Fire - Dynamic A3 BC3 5500 DE4 CR3 CO3 C3 M3 ML3 V V V V V V V Type A - Frame and blades within airstream Type B - Blades removed from airstream via cap Type C - Frame blades removed from airstream sq. to round Type C - Frame and blades are removed from airstream sq. to oval Type C - Frame and blades are removed from airstream Flanged frame, oversized 2" from duct removes frame and partial blades from airstream Slip connection oversized 2" from duct removes frame and partial blades from airstream

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Series 5500 E6/DE6


Application

Curtain Fire Dampers (6 Frame)


For Use in Static or Dynamic Systems

Series 5500 E6 or DE6 curtain fire dampers are UL Classified for installation in walls, floors, and partitions with a fire rating of less than 3 hours. These dampers may be installed vertically or horizontally in static (5500 E6) or dynamic (5500 DE6) systems. Series 5500 E6 or DE6 meets or complies with the following as a fire damper NFPA Standards All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code BS 476: Part 8; 20 & 22; ISO/DIS 834-1 & 10294-1 PREN 1366-2 Internationally Tested 4 hour CA State Fire Marshall - #3225-1518-101

UL Listing File #R6189 UL555 Listing 1 1/2 Hour Static (5500 E6) UL555 Listing 1 1/2 Hour Dynamic (5500 DE6)

Standard Construction
Blades - Low Profile Roll Formed - 21 GA Galvanized Steel Closure Springs (Horizontal Models) Stainless Steel Constant Force Coil Fusible Link - UL-33 UL Listed 165 F (standard), 212 F (optional) McCabe Link (optional).

E6/DE6

UL555 1 1/2 Hour Fire - Static LPB BC CR 5500 E6 CO LPC M ML V or H V or H V or H V or H V or H V or H V or H Type A - Frame and blades within airstream Type B - Blades removed from airstream via cap Type C - Frame blades removed from airstream sq. to round Type C - Frame and blades are removed from airstream sq. to oval Oversized 2" from duct removes frame and partial blades from airstream Flanged frame, oversized 2" from duct removes frame and partial blades from airstream Slip connection oversized 2" from duct removes frame and partial blades from airstream

UL555 1 1/2 Hour Fire - Dynamic LPB BC CR 5500 DE6 CO LPC M ML V or H V or H V or H V or H V or H V or H V or H Type A - Frame and blades within airstream Type B - Blades removed from airstream via cap Type C - Frame blades removed from airstream sq. to round Type C - Frame and blades are removed from airstream sq. to oval Oversized 2" from duct removes frame and partial blades from airstream Flanged frame, oversized 2" from duct removes frame and partial blades from airstream Slip connection oversized 2" from duct removes frame and partial blades from airstream

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Curtain Fire Dampers (8 Frame)


For Use in Static or Dynamic Systems
Application

Series 5500 E8/DE8

Series 5500 E8 or DE8 curtain fire dampers are UL Classified for installation in walls, floors, and partitions with a fire rating of less than 3 hours. These dampers may be installed vertically or horizontally in static (5500 E8) or dynamic (5500 DE8) systems. The 8 frame allows for installation without the use of an addition sleeve. Series 5500 E8 or DE8 meets or complies with the following as a fire damper: NFPA Standards All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code BS 476:Part 8; 20 & 22; ISO/DIS 834-1 & 10294-1PREN 1366-2 Internationally Tested 4 hour CA State Fire Marshall - #3225-1518-101

UL Listing File #R6189 UL555 Listing 1 1/2 Hour Static (5500 E8) UL555 Listing 1 1/2 Hour Dynamic (5500 DE8)

Standard Construction
Blades - Low Profile Roll Formed - 21 GA Galvanized Steel Closure Springs (Horizontal Models) Stainless Steel Constant Force Coil Fusible Link - UL-33 UL Listed 165 F (standard), 212 F (optional) McCabe Link (optional)

UL555 1 1/2 Hour Fire - Static CR CO 5500 E8 LPC M ML V or H V or H V or H V or H V or H Type C - Frame blades removed from airstream sq. to round Type C - Frame and blades are removed from airstream sq. to oval Oversized 2" from duct removes frame and partial blades from airstream Flanged frame, oversized 2" from duct removes frame and partial blades from airstream Slip connection oversized 2" from duct removes frame and partial blades from airstream

E8/DE8

UL555 1 1/2 Hour Fire - Dynamic CR CO 5500 DE8 LPC M ML V or H V or H V or H V or H V or H Type C - Frame blades removed from airstream sq. to round Type C - Frame and blades are removed from airstream sq. to oval Oversized 2" from duct removes frame and partial blades from airstream Flanged frame, oversized 2" from duct removes frame and partial blades from airstream Slip connection oversized 2" from duct removes frame and partial blades from airstream

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Series 5500 E2/DE2


Application

Curtain Fire Dampers (2 Frame - Thin-Line)

For Use in Static Systems or Dynamic Systems


Series 5500 E2 or DE2 curtain fire dampers are UL Classified for installation in walls, floors, and partitions with a fire rating of less than 3 hours. These dampers may be installed vertically or horizontally in static (5500 E2) or dynamic (5500 DE2) systems. Series 5500 E2 or DE2 meets or complies with the following as a fire damper: NFPA Standards All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code BS 476:Part 8; 20 & 22; ISO/DIS 834-1 & 10294-1 PREN 1366-2 Internationally Tested 4 hour CA State Fire Marshall - #3225-1518-101

UL Listing File #R6189 UL555 Listing 1 1/2 Hour Static (5500 E2) UL555 Listing 1 1/2 Hour Dynamic (5500 DE2)

Standard Construction
Blades - Low Profile Roll Formed - 21 GA Galvanized Steel Closure Springs (Horizontal Models) Stainless Steel Constant Force Coil Fusible Link - UL-33 UL Listed 165 F (standard), 212 F (optional) McCabe Link (optional)

E2/DE2

UL555 1 1/2 Hour Fire - Static 5500 E2 A V or H Type A - Frame and blades within airstream

UL555 1 1/2 Hour Fire - Dynamic 5500 DE2 A V or H Type A - Frame and blades within airstream

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Curtain Fire Dampers (Sub Frame)


Application

Series 5500 SF/DSF

For Use in Static Systems or Dynamic Systems


Series 5500 SF or DSF curtain fire dampers are UL Classified for installation in walls, floors, and partitions with a fire rating of less than 3 hours. These dampers may be installed vertically or horizontally in static (5500 SF) or dynamic (5500 DSF) systems. Series 5500 SF or DSF meets or complies with the following as a fire damper: NFPA Standards All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code CA State Fire Marshall - #3225-1518-101 UL Listing File #R6189 UL555 Listing 1 1/2 Hour Static (5500 SF) UL555 Listing 1 1/2 Hour Dynamic (5500 DSF)

Standard Construction
Blades - Full Length Hinge 21 GA Galvanized Steel Closure Springs Stainless Steel Fusible Link - UL-33 UL Listed 212F (standard) 165 F (optional) McCabe Link (optional)

SF/DSF

4 1/2 Wide Blade - Sub Frame UL555 1 1/2 Hour Fire - Static 5500 SF LPB V or H Type A - Frame and blades within airstream

UL555 1 1/2 Hour Fire - Dynamic 5500 DSF LPB V or H Type A - Frame and blades within airstream 2 1/2 Wide Blade - Sub Frame UL555 1 1/2 Hour Fire - Static 5500 SF 2 1/2 V or H Type A - Frame and blades within airstream

UL555 1 1/2 Hour Fire - Dynamic 5500 DSF 2 1/2 V or H Type A - Frame and blades within airstream 1 1/2 Wide Blade - Sub Frame UL555 1 1/2 Hour Fire - Static 5500 SF 1 1/2 V or H Type A - Frame and blades within airstream

UL555 1 1/2 Hour Fire - Dynamic 5500 DSF 1 1/2 V or H Type A - Frame and blades within airstream

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

13

For more product information visit us at www.prefco-hvac.com

Series 5600
Application

Ceiling Radiation Dampers

Series 5600 provide fire and heat radiation protection of HVAC penetrations in floor/ceiling and roof/ceiling assemblies with restrained or unrestrained ratings of either 2 or 3 hours. Standard fire dampers (1 1/2 or 3 hr) do not provide the required heat protection for ceiling penetrations. Series 5600 meets or complies with the following as a ceiling radiation damper: NFPA Standards All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code CA State Fire Marshall - #3225-1518-103 UL Listing File #R7365 UL555C Listing 2 or 3 Hour

Standard Construction
Frame 21 GA Galvanized Steel Blades - Full Length Hinge 21 GA Galvanized Steel Closure Springs Stainless Steel Fusible Link - UL-33 UL Listed 212F (standard) 165 F (optional) McCabe Link (optional) Blade Insulation Ceramic fiber

Series 5600 Round Butterfly 5600 5600EF 5610 5610EF H Un-insulated - 2 Hours H Un-insulated - 2 Hours, w/extended flange H Insulated - 3 Hours H Insulated - 3 Hours, w/extended flange Square/Rectangular Butterfly 5660 5660EF 5680 5680EF H Un-insulated - 2 Hours H Un-insulated - 2 Hours, w/extended flange H Insulated - 3 Hours H Insulated - 3 Hours, w/extended flange Square/Rectangular Single Blade 5650 5650EF 5673 5673EF H Un-insulated - 2 Hours H Un-insulated - 2 Hours, w/extended flange H Insulated - 3 Hours H Insulated - 3 Hours, w/extended flange

5600

2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Butterfly/ Single Blade Fire Dampers


Application

Series 5600F

Series 5600F fire damper is UL Classified for installation in walls, floors, and partitions available with a UL555 Listing of either 1 1/2 or 3 hours. This damper may be installed vertically or horizontally in static HVAC systems that automatically shut down in the event of fire Series 5600F meets or complies with the following as a fire damper: NFPA Standards
Series 5600 F Round Butterfly 5600F 5600F3 V or H V 1 1/2 hours 3 hours

All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code CA State Fire Marshall - #3225-1518-101 UL Listing File #R6189 UL555 Listing 1 1/2 or 3 Hour

Round Single Blade 5630F V 1 1/2 hours

Square/Rectangular Butterfly 5660F 5660F3 V or H V 1 1/2 hours 3 hours

Square/Rectangular Single Blade 5650F 5650F3 V or H V 1 1/2 hours 3 hours

Standard Construction
Frame 21 GA Galvanized Steel Blades - Full Length Hinge 21 GA Galvanized Steel Closure Springs Stainless Steel Fusible Link - UL-33 UL Listed 212F (standard) 165 F (optional) McCabe Link (optional)

5600F

15
For more product information visit us at www.prefco-hvac.com
2004 Perfect Air Control, Inc. All Rights Reserved 1310 N. Hercules Ave. Clearwater, FL 33765 (800) 437-6653 (727) 443-7167 Fax www.prefco-hvac.com

Perfect Air Control, Inc. manufactures Prefco products under one or more of the or following patents. Prefco-Johnson Tech Air Control Inc. manufactures Prefco products under one more of the following patents. 3 , 6 48, 3 28/ 3 , 7 2 5 , 97 2/ 3 , 7 2 7 , 663 / 3 , 796 ,248/ 3 , 796 ,24 9 / 3 ,8 1 4, 165 / 3 ,8 33 , 9 8 9 / 3 ,8 66 , 656 / 3 ,8 66 ,657/3,889,314 3,648,328/3,725,972/3,727,663/3,796,248/3,796,249/3,814,165/3,833,989/3,866,656/3,866,657/3,889,314 3 ,8 99 , 156 / 3 , 960 , 065 / 3 , 977 ,4 56 /4, 0 4 0 , 30 4/4, 0 4 1 , 570 /4, 07 4, 3 88/4, 0 8 0 , 97 8/4, 0 8 1 , 173 /4, 099 ,292/4,113,230 3,899,156/3,960,065/3,977,456/4,040,304/4,041,570/4,074,388/4,080,978/4,081,173/4,099,292/4,113,230 4, 133 ,2 3 2/4, 11 4, 656 /4, 1 4 6 , 0 48/4,24 1 , 7 48/4,2 63 , 930 /4,2 95 ,48 6 /4, 1 8 5 , 65 8/4,4 7 2, 999 /4,442,8 62/4,372,342 4,133,232/4,114,656/4,146,048/4,241,748/4,263,930/4,295,486/4,185,658/4,472,999/4,442,862/4,372,342 4, 33 8, 967 /4, 301 , 569 /4,2 19 , 1 8 5 /4,4 7 4, 167 /4, 37 2,48 5 /4, 195 , 3 84/4,2 00 , 95 4/4,2 13 ,22 7 /4,28 7 , 63 8/3,273,682 4,338,967/4,301,569/4,219,185/4,474,167/4,372,485/4,195,384/4,200,954/4,213,227/4,287,638/3,273,682 3 , 3 2 7 , 76 4/4,2 19 , 0 4 1 /4, 1 8 3 , 1 2 9 /4, 1 8 5 , 657 /4,2 77 ,8 70 /4, 30 4,42 7 /4,4 0 4, 990 /4, 390 , 1 2 3 /4,4 9 4,44 9 /RE 3 2362 3,327,764/4,219,041/4,183,129/4,185,657/4,277,870/4,304,427/4,404,990/4,390,123/4,494,449/RE 32362 3,401,734/3,580,160/3,605,603 Other Other Patents Also Patented in in other countries. 3,401,734/3,580,160/3,605,603 PatentsPending. Pending. Also Patented other countries.