BALANCING & FLOW CONTROL VALVES

FRESE
Quick Reference Introduction

3.1

FRESE VALVES
Alpha / S / SH+ / EVA / Optima / Circon+/Temcon+

3.12 3.47

OVENTROP
Necessity of Hydronic Balancing / Mode of Operation of Valves & Controls Specifying Engineers Calculation / Heating & Cooling Systems

OVENTROP VALVES
Hydrocontrol R/F/FS/FR / Hycocon V / Cocon Q / Flow Charts / Hydromat DP

3.55 3.89 3.92

OVENTROP FLOW MEASURING


Hydronic Balancing on Site / OV-DMC 2 Flow Meter

COMDRONIC AC6

ALPHA Cartridge type 50, 60 A Cartridge type Z, A & B ALPHA Cartridge type 10, 11, 20 ALPHA Cartridge type 30 & 40

BALANCING & FLOW CONTROL VALVES FRESE QUICK REFERENCE

UK INFO 00 02 J AN 05

June 2010
0.008 - 0.358 L/s 0.015 - 0.680 L/s 0.188 - 3.154 L/s 0.008 - 0.358 L/s 0.015 - 0.680 L/s 0.188 - 3.154 L/s

Fe ma Fe le/Fe ma le/ male Fe ma le

ALPHA BASIC

ALPHA DN15-25 ALPHA DN25L-50

Fix ed Fix end ed fem en d f ale/u em n ale ion /un ion

ALPHA UNION

ALPHA DN15-25 ALPHA DN25L-50

Fo r

un

ion sa n

dw ith

ac

tua

FRESE QUICK REFERENCE


QUICK REFERENCE

tor

EVA DN15/20/25

0.008 - 0.358 L/s 0.015 - 0.680 L/s

Fo r

un

ion sa n

dw ith

ac

tua

tor

EVA BASIC DN15

0.008 - 0.358 L/s 0.015 - 0.680 L/s

Fo r

un io

ns

an

COMBIN NG CARTR DGES AND HOUSINGS

dw i

th

ac

tua

Fo r

tor

Fo r

un

Klima DN15

0.008 - 0.358 L/s 0.015 - 0.680 L/s

un

ion

sa nd ion s a with on nd /of wi fa th c on /of tuato fa ctu r ato r

0.008 - 0.358 L/s 0.015 - 0.680 L/s 0.188 - 3.154 L/s

LUNA DN15-25 LUNA DN25L-50

ALPHA WAFER

Automatic Balancing Valves

Fo rf lan ge Fo s rf lan ge Fo s rf lan ge s

ALPHA DN50 ALPHA DN65

Fo rf lan ge Fo s rf lan ge Fo s rf lan g es Fo rf lan ge Fo s rf lan ge Fo s rf lan ge Fo s rf lan ge Fo s rf lan ge Fo s rf lan g Fo es rf lan ge Fo s rf lan Fo ge rf lan s ge s

ALPHA DN80

1.061 - 11.38 L/s 1.061 - 11.38 L/s 1.061 - 11.38 L/s 1.061 - 22.76 L/s 1.061 - 34.14 L/s 1.061 - 45.52 L/s 1.061 - 79.67 L/s 1.061 - 136.6 L/s 1.061 - 170.7 L/s 1.061 - 216.2 L/s 1.061 - 295.9 L/s 1.061 - 375.6 L/s 1.061 - 455.2 L/s 1.061 - 637.3 L/s 1.061 - 967.4 L/s

ALPHA DN100 ALPHA DN125 ALPHA DN150 ALPHA DN200 ALPHA DN250 ALPHA DN300 ALPHA DN350 ALPHA DN400 ALPHA DN450 ALPHA DN500 ALPHA DN600 ALPHA DN800

3.1

FRESE INTROdUCTION
BALANCING & FLOW CONTROL VALVES FRESE INTRODUCTION
SCOPE This section contains an account of why it is necessary to balance a water distribution system for the distribution of heating or cooling effects, the considerations that should be made before the system is designed, the result of balancing and the difference between a static and a dynamic balancing valve. WHAT Is A BALANCED SYsTEM? Denition: A distribution system is in balance when the ow in the whole system (through the component terminal lines, distributing lines and main distributing lines) corresponds to the ow rates that were specied for the design of the system. The dimensioned hydraulic condition of operation can be simulated by means of the opening of all the valves regulating the ow depending on the temperature (room temperature, outdoor temperature or medium temperature) either as manual radiator valves, self-regulating thermostatic valves or electrically actuated valves. In practice it is recommended that balance is established by means of a number of balancing valves that can be pre-set individually to an assessed orice dimension. Together with the rest of the system they will then establish the exact ow resistances to ensure a correct distribution of the owing medium.

Figure 2.1 A Balanced section with a distributing line for three terminals. Figure 2.1 Shows an outline of a minor section of a balanced water distribution system. Referring to the gure above the distribution system is in balance when the system contains a number of regulation valves that have been pre-set to be mutually dependent so that the ow through the component terminal lines, distributing lines and main distributing lines corresponds to the ow rates that were specied for the design of the system.

3.2

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE INTROdUCTION
In an analogue electric system the balancing valves are comparable with a variable resistance, and the resistance of the pipes with the corresponding wiring resistance, and the effective heating-/cooling surfaces with a load resistance (g. 2.2). The distribution of the electric power through the component load resistances, distributing lines and main distributing lines, depends on the distribution of the resistance in the circuit, similarly to a water distribution system. THE NEED fOR BALANCING If the correct balancing of the system has not been established, this will result in an unequal distribution of the ow, so that there will be a surplus effect in some of the terminals, whereas the effect will be inadequate in others. The result of this will be that the wanted heating/chilling will not be ensured in all parts of the installation.
Figure 2.2 An analogue electric system

BALANCING & FLOW CONTROL VALVES FRESE INTRODUCTION

In practice it is not possible to make a correctly balanced system by manipulation of the piping or alteration of the pipe dimensions only. Only a correct adjustment of the balancing valves shown in gure 2.1 will ensure the correct distribution of the ow in the system. DEsIGN CONsIDERATIONs The engineer in charge of the design and installation of a system should aim at: Substantial operating effectiveness  Achievement of the required comfort at the lowest operating costs possible Avoiding unnecessary waste of energy resources. For the design and selection of equipment for the balancing and control of a system the following should be taken into consideration: (A) Type of application (B) Type of the building in question (C) The required room temperature/comfort (D) Type of the hot domestic water supply (E) Acceptable deviations from the comfort parameters (F) Minimization of the primary energy (G) Application of heat recycling (H) Economic factors The result of (C), (E) and (F) is very much dependent on the correct distribution of the ow in the system. Therefore the quality of the balancing should meet the the required comfort and energy efciency. The quality of the balancing is partly dependent on the type of the required balancing valves (static versus dynamic valves, ref. the following section), compared with the required adjustment method, and partly the design of the required components for the verication of the ow in the system. The following quality parameters should be specied during the phase of design: Type of balancing valves Adjustment method Verification of flow, where and how? Acceptable deviations of the flow

June 2010

3.3

FRESE INTROdUCTION
BALANCING & FLOW CONTROL VALVES FRESE INTRODUCTION
THE REsULT Of BALANCING A satisfactorily balanced installation will show the following results: Correct flow in boilers and chillers.  Correct distribution of flow and effect in the whole system.  Compatibility between all flow rates in primary and secondary lines. These results will ensure the following benets:  The room temperature is adjustable within the specific deviations.  Energy saving as a result of the favourable conditions of the equipment that controls the energy transfer. Achievement of the required indoor climate. WHY ARE BALANCING VALvEs REQUIRED? We answer that question on the basis of gure 2.3 The gure shows a schematic outline of a simple installation that contains a boiler/chiller, three identical terminals with the same ow requirement, and a pump to make the heat transfer medium, i.e. water or water/glycol circulate in the system. The top half of the diagram represents the pressure distribution throughout the schematic layout shown in the lower half of the diagram. The branch nodes are indicated on both the distribution diagram and the schematic by the small lettering.
Figure 2.3 Simple installation and its pressure distribution.

qvn = p/(R . rn), in which qv = ow p = pressure drop R =  resistance of pipes, single resistances (ttings, terminals etc.) and valves n =  exponent r = density

In the piping there will be friction between the owing medium and the pipe wall. This frictional loss makes the pressure decrease along the pipe in the direction of the ow. This will be seen from the falling pressure line between the branching points. The ow rate between two points is determined by the pressure differential between the points and the resistance of pipes, valves and terminals against the ow. The arithmetic coherence can be expressed by the equation to the left. The resistance of value R can be read from tables, please see the respective product catalogues. The exponent n varies in relation to the pipe sizing.

3.4

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE INTROdUCTION
The pressure drop Delta p1 is referred to as the index circuit. The index circuit is the circuit that has the highest resistance to ow. It is normal for this to be the circuit most remote from the pump. This pressure drop can be found by means of the equation delta p1 = R1 x (qv x r)n, in which the resistance of the terminal R1 and the wanted ow q v are known values. The pressure drop across the three identical terminals will be the same, provided the same ow is required through all of them, i.e. Delta p1 = Delta P2 = Delta p3. In order to bring about this identical pressure drop across the terminals and associated piping it is necessary to connect another resistance in series with the resistances of the terminals, so that the residual pressure drop between branching points BF and CG can be absorbed. If the installation in question is not equipped with balancing valves after terminals (2) and (3), the ow through the three terminals will vary so that terminal (3) will be exposed to the major ow, terminal (2) to a smaller ow, and terminal (1) to the smallest ow. In that case the system will not be in the required state of balance. Figure 2.4 shows the distribution of the pressure drop between branching points BF. From this you will see that the adjustment of the regulating valve to the required resistance value has to be carried out with regard to not only the terminal but also the connecting pipes. The nal adjustment is usually carried out by indirect measurement of the ow through the regulating valve simultaneously with measurement of the ow through terminal (1). The regulating valve to terminal (2) is to be adjusted to ensure that the proportion of the measured ow rates through terminals (1) and (2) is the same as the one between the indexed ow rates between the two terminals. Hereafter the valve is adjusted to terminal (3) to ensure that the proportion between the measured ow rates through terminals (3) and (2) is the same as the one between the indexed ow rates between the two terminals. This adjustment method is called the proportional method.

BALANCING & FLOW CONTROL VALVES FRESE INTRODUCTION

Figure 2.4 Absorbing 'residual' pressure

June 2010

3.5

FRESE INTROdUCTION
BALANCING & FLOW CONTROL VALVES FRESE INTRODUCTION
THE DIffERENCE bETwEEN A STATIC & A DYNAMIC BALANCING VALvE Usually you will not nd an indication of the resistance value of a valve in valve catalogues and data sheets. On the other hand, the producer always states a ow coefcient referred to as kv or C v (American products). This is also called the ow coefcient of the valve. The ow coefcient of kv is dened to be the ow of water (density 1 kg/litre) through the valve, when the differential pressure across the valve is 1 bar. The designation of this ow is m3/hour. The ow coefcient of Cv is dened as the ow of water (density 1 kg/litre) through the valve, when the differential pressure across the valve is 1 psi (lb/inch2). The designation of this ow is GPM (US gallon/min.). Hereafter the mathematic coherence between the ow and the differential pressure of the valve can be expressed as follows:

qv = kv p/rr  qv in m3/hour when p is in bar (gauge) qv in GPM (US) when p is in psi qv = cv p/rr 

Figure 2.5 The valve features of a static circuit balancing valve and a dynamic circuit balancing valve respectively at a given pre-adjustment value.

As regards the 2-position and balancing valves, the indicated ow coefcient of kv refers to the completely open valve. A feature of a static circuit balancing valve is that the open orice area (k value) can be changed manually and xed into a static value. The kv value can now be obtained by referring to the hand wheel position in relation to the calibration graph of the valve. The valve should be equipped with 2 pcs. isolation test plugs to which the measuring equipment for indirect ow measurement can be connected. The valve can be pre-adjusted on the basis of a calculated pressure distribution in the whole HVAC installation. Please note that the calculation of large, complex installations may involve a considerable inaccuracy. Further, the valve can be pre-adjusted on the basis of an adjustment after the installation, e.g. according to the proportional method. A dynamic circuit balancing valve is the next step in balancing valves that was introduced onto the market forty years ago. One of its features is that it can be pre-adjusted to a given ow and be locked to ensure this ow. The valve is an automatic regulator valve that with a reference to the differential pressure automatically adjusts to the kv value necessary to maintain the required ow. The kv value of the valve automatically compensates for any changes of the differential pressure, so that the ow will never exceed the pre-set ow.

These valves are available in types that have been calibrated in the factory to the rated ow, and in types the indexed ow of which can be pre-adjusted by the user before or after the installation of the valve in the system, or from the outside as the system is working. The valve can be used on the basis of the calculated ow without regard to the distribution of pressure in the system. Figure 2.5 illustrates the difference between the static and the dynamic application in the form of ow variation as a function of the differential pressure across the valves at a given pre-adjustment. As will be seen from the chart, the ow through the static valve will increase as the differential pressure increases, and decrease as the differential pressure falls, whereas the dynamic balancing valve will maintain a constant ow (within the regulation range) independently of the differential pressure within the dynamic balancing valve. Further, please note that the indexed ow (100%) through a static balancing valve will not be achieved unless the differential pressure across the valve is equal to the indexed differential pressure delta p.

3.6

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE INTROdUCTION
WHEN ARE FLOw MEAsUREMENT DEvICEs REQUIRED? Static Systems: During the adjustment it should be possible to measure the ow through each terminal (coil in air-condition, not radiators in heating systems), distributing line, main distributing line and supply line. The measurements will typically be carried out as an indirect measurement, i.e. measurement of the differential pressure converted into a ow value in relation to the kv value of the measured device. The measurements are carried out across each circuitbalancing valve with the kv value relative to the valve setting and the associated ow chart. The accuracy of the measured ow is not likely to be better than +/- 25% dependent on the hand wheel position. This inaccuracy should be taken into consideration in connection with the verication of the ow. Still, it is of no particular importance to the relative comparison between the ow through the individual terminals and distributing lines during the balancing procedure. Dynamic Systems: Dynamic valves will typically balance the system at an accuracy of +/- 5% of the rated ow. So, as direct measurements involve a degree of accuracy of +/- 25%, it will be inappropriate to verify the ow through the individual terminals. Instead, measurement/verication of the ow in the supply line is recommended. For verication of the ow in the supply line it is recommended that a xed orice device is used with a specied accuracy which is +/- 5% above that of the measured ow. WHERE ARE BALANCING VALvEs REQUIRED? Figures 2.6 and 2.7 show a section of the same system, in which gure 2.6 has been designed as a static system, and gure 2.7 as a dynamic system. The section contains one supply line for 3 main distributing lines, each of which has 3 distributing lines with 3 terminals each (totally 27 terminals). In the static system each terminal has to be balanced in 9 groups of 3 terminals each. Hereafter the 9 terminal sections have to be balanced in 3 groups of 3 distributing lines each. After that the 3 main distributing lines have to be balanced. And nally the distributing line is adjusted to ensure the total design ow. This balancing procedure requires one balancing valve per terminal, one balancing valve per distributing line, one balancing valve per main distributing line and one balancing valve in the supply line. In the dynamic system the individual terminals can be adjusted independently of each other. This simply requires one balancing valve per terminal.

BALANCING & FLOW CONTROL VALVES FRESE INTRODUCTION

Figure 2.6 Water distribution system, static balancing.

Figure 2.7 Water distribution system, dynamic balancing.

June 2010

3.7

FRESE INTROdUCTION
BALANCING & FLOW CONTROL VALVES FRESE INTRODUCTION
WHY UsE DYNAMIC BALANCING INsTEAD Of STATIC BALANCING? The adjustment of a dynamic system is quick and easy. All that is needed is the right pre-adjustment/balancing valve specied for the rated ow. There is no need for measurements for making comparisons between the ows of the individual balancing valves. When the features of an installation are to be calculated, the only uncertain factor will be any inaccuracy in the calculated ow rate. When a dynamic balancing valve is used the uncertainty regarding the distribution of pressure in the installation and consequently the calculated kv values of the balancing valves is eliminated. Balancing valves are only needed for the individual terminals. There is no need for balancing valves in the distribution lines, main distribution lines and supply lines. The individual terminals are 100% safe from overow without regard to the load distribution in the installation and independent of the dynamic load variation in the installation. In an properly balanced static system overow (up to 300-400%) may occur through some of the terminals. The rated ow can be changed in one or more sections of the installation without upsetting the balance in the rest of the system. If the dimensional basis of the whole system turns out to be wrong after the installation, a static system can only be re-adjusted if the whole installation is re- adjusted. The result of the adjustment is better when compared to static balancing, because the rated ow is controlled at an accuracy of +/- 5%. After the installation the system can be changed/extended/restored without regard to the changes of the balance in the existing part of the system. In a corresponding static system this would often involve a change of the total design of the system. From the foregoing, the following benets of dynamic balancing can be stated: Quick and easy adjustment  Independent of errors/ unreliabilities in the calculated distribution of pressure in the installation. Fewer balancing valves 100 % safe from overflow Unproblematic re-adjustments More effective adjustment  Great flexibility if the system is changed after the installation Due to these benets the features of the system design will typically be as follows: Cheaper installation Better comfort Greater flexibility More economical operation

3.8

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE ALphA CARTRIdGES


APPLICATION The Frese Alpha Cartridges are particularly designed and manufactured for the automatic balancing of heating and cooling circuits. They are integral part of the Frese Automatic Balancing Valves keeping the ow constant at the specied level even under uctuating pressure conditions. From small size valves (DN15) to big wafer types (DN800), from small heating units to sea-water district cooling applications, there is a Frese Alpha Cartridge that can guarantee the specied ow. The advanced patented design of the Frese Alpha Cartridges introduces the orice plate concept for higher performance and exibility. With the Frese Alpha Cartridges it is no longer needed to change the cartridge every time the design ow is modied. Each cartridge contains an orice plate specic for every ow that can be easily removed and replaced by another one. ADvANTAGEs O  nly one differential pressure operating range (up to 350 kPa for DN15 to DN50, up to 600 kPa for sizes DN50 and upwards) making the sizing of the cartridge very easy (depending only on the design ow).  Complete, broad and well-balanced distribution of flows for the full range of heating and cooling applications (from 0.015 l/s and 7 kPa min. differential pressure to 11.381 l/s, per cartridge).  Minimized friction and noise due to the patented cartridge design based on the metal-rubber diaphragm-metal contact.  Improved response to water hammer due to the shock absorption by the rubber diaphragm of the cartridge.  No impact of debris on the performance of the cartridge. The design of the inlet and the outlet areas makes the accumulation of particles inside the cartridge very difcult. BENEfITs Design L  ess time to define the necessary equipment for a hydraulic balanced system.  No impact if the calculated distribution of pressure in the installation is not accurate. Security that the specified flow is also the real one.  Flexibility if the system is modified after the initial installation. Installation C  artridge solution makes flushing procedure very easy.  Quick and easy installation of the cartridge in the valve.  Minimized commissioning time due to automatic balancing of the system. Operation U  nproblematic performance even with high concentration of debris.  Noiseless operation. High comfort for the end-users.

BALANCING & FLOW CONTROL VALVES FRESE ALPHA CARTRIDGES


3.9

June 2010

FRESE ALphA CARTRIdGES


BALANCING & FLOW CONTROL VALVES FRESE ALPHA CARTRIDGES
FLOw RATE GRAPH
[l/s]
1.94 1.67 1.39 1.11 0.83 0.56 0.28
0 0

[kPa]
100 200 300

Schematic view of the ow development for cartridge type 40, Frese number 50-44176. Nominal ow 1.388 l/s. The cartridge enters the pressure range at 22 kPa and maintains the ow at a constant level all the way till 350 kPa.

INDICATION Of FLOw RATE ON THE ORIfICE PLATE A four-digit number on the orice plate is identical with the last four digits in the Frese number. The cartridge can be identied by means of this number and the corresponding ow rate can be read from the above ow rate tables.

Frese no.

Flow [gpm]

Flow [l/s]

Min. DP

[kPa]

49-11735 49-11740 49-11745 49-11750

3.24 3.52 3.83 4.12

0.204 0.222 0.242 0.260

14 16 19 21

49 = HP High Pressure 50 = LP Low pressure

Tradelink stocks Low Pressure (50=LP) type cartridges, with a pressure range up to 350 kPa for Cartridge types 10, 11, 20, 30 and 40, for valve sizes DN15 to DN50.

CARTRIDGE OPERATION When the pressure increases the spring will be compressed and there by the piston will reduce the outlet area and viceversa. The result is a constant ow rate through the valve, independent of pressure uctuations.

3.10

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

SELECTING FLOW RATES FOR GLYCOL mIXTURES


FLOw 'CORRECTION FACTORs' WATER/GLYCOL MIXTUREs FORMULA GPM =
SG

BALANCING & FLOW CONTROL VALVES SELECTING FLOW RATES FOR GLYCOL MIXTURES

GPMV

SG

GPM = GPMV DEfINITION Q- Fluid Flow Q v - Flow through valve, at measured conditions - Viscosity correction SG - Specic gravity (to water) METHOD Of UsE fOR GRAPH 1. Select the curve appropriate for the known percentage glycol/ water mixture. 2. Identify the point on this curve corresponding to the system temperature during balancing. The graph indicates values of the specic gravity for specied percentage mixtures and operating temperatures CORRECTION FACTOR TAbLE
VISCOSITY CENTIPOISE SG 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 1.00 1.05 1.10 1.15 1.20 1.25 1.30 1.35 1.40 SG 0.775 0.806 0.837 0.866 0.894 0.922 0.949 0.975 1.000 1.025 1.049 1.072 1.096 1.118 1.140 1.162 1.183 1.29 1.24 1.20 1.16 1.12 1.08 1.05 1.03 1.00 0.98 0.95 0.93 0.91 0.89 0.88 0.86 0.85 1.23 1.18 1.14 1.10 1.06 1.03 1.00 0.97 0.95 0.93 0.91 0.89 0.87 0.85 0.84 0.82 0.80 1.16 1.12 1.08 1.04 1.01 0.98 0.95 0.92 0.90 0.88 0.86 0.84 0.82 0.81 0.79 0.78 0.76 1.10 1.05 1.02 0.98 0.95 0.92 0.90 0.87 0.85 0.83 0.81 0.79 0.78 0.76 0.75 0.73 0.72 1 1 10 0.95 15 0.90 25 0.85 35 0.80 60 0.75 0.97 0.93 0.90 0.87 0.84 0.81 0.79 0.77 0.75 0.73 0.72 0.70 0.68 0.67 0.66 0.65 0.63 100 0.70 0.90 0.87 0.84 0.81 0.78 0.76 0.74 0.72 0.70 0.68 0.67 0.65 0.64 0.63 0.62 0.60 0.59 200 0.65 0.84 0.81 0.78 0.75 0.73 0.71 0.69 0.67 0.65 0.63 0.62 0.61 0.59 0.58 0.57 0.56 0.55 500 0.60 0.78 0.75 0.72 0.69 0.67 0.65 0.63 0.62 0.60 0.59 0.57 0.56 0.54 0.54 0.53 0.52 0.51

3. Draw a horizontal line from this point to intersect the specic gravity scale.

1.03 0.99 0.96 0.92 0.89 0.87 0.84 0.82 0.80 0.78 0.76 0.75 0.73 0.72 0.70 0.69 0.68

June 2010

3.11

FRESE ALphA AUTOmATIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE ALPHA AUTOMATIC BALANCING vALvE
APPLICATION The Frese Alpha Valves are particularly designed and manufactured for the automatic balancing of heating and cooling circuits. The Frese Alpha Cartridges - the second generation cartridges - are an integral part of the Frese Alpha Valves limiting the ow at the specied level even under uctuating pressure conditions. The patented design of these cartridges introduces a replaceable orice plate for higher exibility and a resistant diaphragm for higher accuracy. From small size threaded valves (DN15) to big anged type valves (DN800), from small heating units to sea-water district cooling applications, Frese Alpha Valves guarantee the hydraulic balance of the system regardless pressure uctuations. BENEfITs Design N  o need to use balancing valves in the distribution lines, main distribution lines and supply lines  Less time to define the necessary equipment for a hydraulic balanced system  No impact if the calculated distribution of pressure in the installation is not accurate  Security that the specified flow is also the real one  No requirements on pipe lengths before and after the valve Installation M  inimized commissioning time due to automatic balancing of the system  Cartridge solution makes flushing procedure very easy  No need for oversized pumps and oversized control valves Operation Energy savings due to elimination of overflows  Higher comfort due to correct distribution of water in the system and to optimized function of the control valves Maintenance-free operation of the valve Advantages W  ide product range covering all applications - sizes from DN15 to DN800 - different end connections (female/female, union connections,anges), - dezincication resistant brass, ductile iron, naval bronze, - P/T plugs, drain, combi-drain, - kit solution with strainer and ball-valves, solution with integral ball-valve,  Balancing of the system takes place automatically even under uctuating pressure conditions  No more overflows in the system  Modifications & extensions of the system do not affect the hydraulic balance in the other parts of the system  Tamper resistant cartridge independent of ow regulation errors during commissioning and operation of the system  Self-cleaning cartridge not allowing dirt to compromise the accuracy of the valve  Resistant diaphragm between the moving parts of the cartridge eliminates friction, noise and impact from water-hammer.

3.12

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE ALphA BASIC dYNAmIC BALANCING VALVE


SPECIfICATION Body Brass (DZR) CW602N O-Rings EPDM Seal PTFE Flow Cartridge Brass (DZR) CW602N Spring Stainless Steel Diaphragm HBNR Orice Plate Brass (DZR) CW602N Accuracy +/- 5% Pressure Class PN25 Max Differential Pressure 350 kPaD Media Temperature -20C to +120C Body Tappings 1/4 ISO Flow Rate Range 0.007 L/s to 3.154 L/s Size Range DN15 to DN50 Threads ISO 228 Female Parallel DEsIGN FEATUREs
L W

BALANCING & FLOW CONTROL VALVES FRESE ALPHA BASIC DYNAMIC BALANCING vALvE

1. Automatic balancing valve with two colour coded test points for differential pressure measurement. Red is for Flow and Blue is the return side of the valve. 2. The unit will automatically limit the ow rate to +/- 5% of the selected ow rate. 3. The ow cartridge is removable from the valve for change of ow rate or ushing without removing the valve from inline. 4. Only one differential pressure operating range (up to 350 kPaD) making the sizing of the cartridge very easy. (depending only on the design ow) 5. The cartridge design has minimized friction and noise due to the patented cartridge design based on the metal-rubber diaphragmmetal contact. 6. Improved response to water hammer due to the shock absorption by the rubber diaphragm of the cartridge. 7. No impact of debris on the performance of the cartridge. The design of the inlet and outlet areas makes the accumulation of particles inside the cartridge very difcult. 8. Valves are delivered assembled and tagged for easy identication.

DN 1

VALvE DIMENsIONs - mm
SIZE H L W kg 15 94 77 55 0.5 20 94 77 55 0.5 25 sml 94 77 55 0.5 25 lge 126 123 80 1.45 32 126 123 80 1.45 40 126 123 80 1.45 50 126 123 80 1.45

Dimensions shown with standard P/T points.

TRADELINK INDUsTRIAL ALPHA BAsIC CODEs


SIZE Code 15 020164 20 020170 25 sml 020177 25 lge 020185 32 020187 40 020193 50 020215

TRADELINK FREsE EXTENDED P/T POINT KIT CODEs


EXTENSION LENGTH Code 50mm 116157 100mm 116156

5/P N2 5
June 2010

3.13

FRESE ALphA BASIC dYNAmIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE ALPHA BASIC DYNAMIC BALANCING vALvE
FOR VALvEs DN15-DN25, 0.007 - 0.680 L/s
ID 1150 1170 1190 1210 1230 1260 1290 1300 1320 1350 1370 1400 1430 1460 1490 1510 1540 1570 1620 1725 1730 1735 1740 1745 1750 0700 0740 0770 0820 0860 0880 0920 0940 0990 1030 1060 1090 FLOW L/s MIN DP kPa CARTRIDGE Kv 0.09 0.14 0.16 0.21 0.27 0.28 0.33 0.36 0.39 0.46 0.51 0.59 0.70 0.81 0.89 0.97 1.11 1.27 1.46 1.64 1.79 1.97 2.00 2.00 2.04 2.17 2.30 2.55 2.78 3.09 3.30 3.62 3.74 4.16 4.41 4.46 4.63

FOR VALvE DN25L-DN50, 0.188 - 3.154 L/s


ID 3073 3082 3089 3094 3096 3098 3102 3107 3111 3112 3118 3124 3125 3129 3132 3135 3138 3142 3148 3156 3161 3163 4148 4152 4156 4164 4168 4173 4176 4182 4191 4194 4200 4205 4211 4217 4222 4229 4235 4241 4248 4250 4262 FLOW L/s MIN DP kPa CARTRIDGE Kv 1.95 2.49 2.94 3.28 3.44 3.53 3.74 4.12 4.19 4.36 4.85 5.17 5.11 5.43 5.51 5.77 5.89 6.22 6.59 6.96 7.26 7.43 8.13 8.03 8.92 9.42 9.68 10.17 10.42 11.12 11.81 12.82 13.11 13.73 14.10 14.68 15.02 15.58 15.90 16.20 16.51 16.82 17.12

CARTRIDGE/ORIFICE TYPE 10 0.007 7 0.010 7 0.012 7 0.015 7 0.021 8 0.024 9 0.029 10 0.032 10 0.036 11 0.043 11 0.049 12 0.057 12 0.067 12 0.078 12 0.089 13 0.097 13 0.111 13 0.132 14 0.151 14 CARTRIDGE/ORIFICE TYPE 11 0.171 14 0.186 14 0.204 14 0.222 16 0.242 19 0.260 21 CARTRIDGE/ORIFICE TYPE 20 0.283 22 0.300 22 0.332 22 0.371 23 0.412 23 0.439 23 0.493 24 0.509 24 0.578 25 0.625 26 0.644 27 0.680 28

SPECIfICATION TEXT The valve shall operate by means of an automatic balancing cartridge with replaceable orice plate and internal diaphragm. The pressure class of the valve shall be PN25. The valve housing shall be made of DR brass. The valve is Frese Alpha Basic. INsTALLATION No requirements on pipe lengths before and after the valve. The valve body has ow direction indicated. A strainer is recommended according to good piping practises. Standard practise for balancing valves is to install on the return side of the terminal. The pipe system should be properly ventilated to avoid the risk of air-pockets.

CARTRIDGE/ORIFICE TYPE 30 0.188 12 0.239 12 0.283 12 0.315 12 0.331 12 0.353 13 0.375 13 0.413 13 0.435 14 0.453 14 0.504 14 0.556 15 0.568 16 0.603 16 0.631 17 0.661 17 0.694 18 0.733 18 0.797 19 0.886 21 0.946 22 0.968 22 CARTRIDGE/ORIFICE TYPE 40 1.010 20 1.072 21 1.136 21 1.199 21 1.261 22 1.325 22 1.388 23 1.514 24 1.640 25 1.767 26 1.893 27 2.018 28 2.144 30 2.271 31 2.397 33 2.524 34 2.650 36 2.775 38 2.901 40 3.028 42 3.154 44

NOTE: The minimum required differential pressure is measured using the measurement outlets on the valve housing. This applies to all cartridge types. If measured pressure differential pressure is below minimum Dp, the ow can be found by using the Kv gures above. Glycol mixtures (both ethylene and propylene) up to 50% are applicable. See page 3.11. ID = four digit number on the orice plate.

3.14

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE ALphA UNION dYNAmIC BALANCING VALVE


SPECIfICATION Body Brass (DZR) CW602N O-Rings EPDM Seal PTFE Flow Cartridge Brass (DZR) CW602N Spring Stainless Steel Diaphragm HBNR Orice Plate Brass (DZR) CW602N Union Brass (DZR) CW602N Accuracy +/- 5% Pressure Class PN25 Max Differential Pressure 350 kPaD Media Temperature -20C to +120C Body Tappings 1/4 ISO Flow Rate Range 0.007 L/s to 3.154 L/s Size Range DN15 to DN40 Threads ISO 228 Female Parallel DEsIGN FEATUREs 1. Integrated ow limiter, isolation ball valve and inlet union. 2. Two colour coded test points for differential pressure measurement. Red is for Flow and Blue is the return side of the valve. 3. The unit will automatically limit the ow rate to +/- 5% of the selected ow rate. 4. The union tail piece is available in parallel threaded male, female and copper sweat end connections for ease of installation. 5. The integral ball valve has a full size external handle and an external mechanical stop to ensure a 90 turn. 6. The ow cartridge is removable from the valve for change of ow rate or ushing without removing the valve from inline. 7. Only one differential pressure operating range (up to 350 kPaD) making the sizing of the cartridge very easy. (depending only on the design ow) 8. The cartridge design has minimized friction and noise due to the patented cartridge design based on the metal-rubber diaphragmmetal contact. 9. Improved response to water hammer due to the shock absorption by the rubber diaphragm of the cartridge. 10. No impact of debris on the performance of the cartridge. The design of the inlet and outlet areas makes the accumulation of particles inside the cartridge very difcult. 11. Valves are delivered assembled and tagged for easy identication.
20 94 107 129 87 0.87 25 sml 94 107 146 87 0.87 25 lge 126 126 195 124 2.54 32 126 126 195 124 2.54 40 126 126 200 124 2.54
H

BALANCING & FLOW CONTROL VALVES FRESE ALPHA UNION DYNAMIC BALANCING vALvE

VALvE DIMENsIONs - mm
SIZE H L* L** W kg 15 94 107 129 87 0.87

* with no union end. ** with female union tail piece. Dimensions shown with standard P/T points.

TRADELINK INDUsTRIAL ALPHA UNION CODEs


SIZE F&F Cu&F M&F 15 020222 019449 019456 20 020255 019451 019457 25 sml 020258 019452 019458 25 lge 020318 019453 019759 32 020319 019454 019761 40 020525 019455 019765

TRADELINK FREsE ALPHA ACCEssORY KIT CODEs


SIZE Ball valve spindle extension P/T Extension kit 50mm P/T Extension kit 100mm 15 116157 116156 20 116157 116156 25 sml 116157 116156 25 lge 116157 116156 32 116757 116156 40 116157 116156

June 2010

3.15

FRESE ALphA UNION dYNAmIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE ALPHA UNION DYNAMIC BALANCING vALvE
FOR VALvEs DN15-DN25, 0.007 - 0.680 L/s
ID 1150 1170 1190 1210 1230 1260 1290 1300 1320 1350 1370 1400 1430 1460 1490 1510 1540 1570 1620 1725 1730 1735 1740 1745 1750 0700 0740 0770 0820 0860 0880 0920 0940 0990 1030 1060 1090 FLOW L/s MIN DP kPa CARTRIDGE Kv 0.09 0.14 0.16 0.21 0.27 0.28 0.33 0.36 0.39 0.46 0.51 0.59 0.70 0.81 0.89 0.97 1.11 1.27 1.46 1.64 1.79 1.97 2.00 2.00 2.04 2.17 2.30 2.55 2.78 3.09 3.30 3.62 3.74 4.16 4.41 4.46 4.63

FOR VALvE DN25L-DN50, 0.188 - 3.154 L/s


ID 3073 3082 3089 3094 3096 3098 3102 3107 3111 3112 3118 3124 3125 3129 3132 3135 3138 3142 3148 3156 3161 3163 4148 4152 4156 4164 4168 4173 4176 4182 4191 4194 4200 4205 4211 4217 4222 4229 4235 4241 4248 4250 4262 FLOW L/s MIN DP kPa CARTRIDGE Kv 1.95 2.49 2.94 3.28 3.44 3.53 3.74 4.12 4.19 4.36 4.85 5.17 5.11 5.43 5.51 5.77 5.89 6.22 6.59 6.96 7.26 7.43 8.13 8.03 8.92 9.42 9.68 10.17 10.42 11.12 11.81 12.82 13.11 13.73 14.10 14.68 15.02 15.58 15.90 16.20 16.51 16.82 17.12

CARTRIDGE/ORIFICE TYPE 10 0.007 7 0.010 7 0.012 7 0.015 7 0.021 8 0.024 9 0.029 10 0.032 10 0.036 11 0.043 11 0.049 12 0.057 12 0.067 12 0.078 12 0.089 13 0.097 13 0.111 13 0.132 14 0.151 14 CARTRIDGE/ORIFICE TYPE 11 0.171 14 0.186 14 0.204 14 0.222 16 0.242 19 0.260 21 CARTRIDGE/ORIFICE TYPE 20 0.283 22 0.300 22 0.332 22 0.371 23 0.412 23 0.439 23 0.493 24 0.509 24 0.578 25 0.625 26 0.644 27 0.680 28

SPECIfICATION TEXT The valve shall operate by means of an automatic balancing cartridge with replaceable orice plate and internal diaphragm. The pressure class of the valve shall be PN25. The valve housing shall be made of DR brass. The housing shall have one xed threaded end and one union end. The valve includes and integral ball valve with handle. The valve is Frese Alpha Union. INsTALLATION No requirements on pipe lengths before and after the valve. The valve body has ow direction indicated. A strainer is recommended according to good piping practises. Standard practise for balancing valves is to install on the return side of the terminal. The pipe system should be properly ventilated to avoid the risk of air-pockets.

CARTRIDGE/ORIFICE TYPE 30 0.188 12 0.239 12 0.283 12 0.315 12 0.331 12 0.353 13 0.375 13 0.413 13 0.435 14 0.453 14 0.504 14 0.556 15 0.568 16 0.603 16 0.631 17 0.661 17 0.694 18 0.733 18 0.797 19 0.886 21 0.946 22 0.968 22 CARTRIDGE/ORIFICE TYPE 40 1.010 20 1.072 21 1.136 21 1.199 21 1.261 22 1.325 22 1.388 23 1.514 24 1.640 25 1.767 26 1.893 27 2.018 28 2.144 30 2.271 31 2.397 33 2.524 34 2.650 36 2.775 38 2.901 40 3.028 42 3.154 44

NOTE: The minimum required differential pressure is measured using the measurement outlets on the valve housing. This applies to all cartridge types. If measured pressure differential pressure is below minimum Dp, the ow can be found by using the Kv gures above. Glycol mixtures (both ethylene and propylene) up to 50% are applicable. See page 3.11. ID = four digit number on the orice plate.

3.16

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE ALphA WAFER dYNAmIC BALANCING VALVE


SPECIfICATION Body  Ductile Iron DIN 1693 GGG-40 O-Rings EPDM Flow Cartridge AISI 304 Spring Stainless Steel Diaphragm Reinforced EPDM Orice Plate AISI 316 Fasteners Stainless Steel AISI 306 Accuracy  +/- 5%, +/-10% over 400 kPaD Pressure Class  PN16 (DN50/65/80 are PN25) (other sizes on request) Max Differential Pressure 600 kPaD Dm Media Temperature -20C to +110C Body Tappings 1/4 ISO Size Range DN50 to DN800 Flange connections According to EN/ANSI Standards DEsIGN FEATUREs 1. Two 100mm colour coded test points for differential pressure measurement. Red is for Flow and Blue is the return side of the valve. 2. The unit will automatically limit the ow rate to +/- 5% of the selected ow rate, unless differential pressure across valve exceeds 400 kPaD. In differential pressure ranges up to 600 kPaD the ow rate becomes +/- 10%. 3. The ow cartridge shall offer possibility to change ow rate by means of an orice plate. 4. Only one differential pressure operating range (up to 600 kPaD) making the sizing of the cartridge very easy (depending only on the design ow). 5. The cartridge design has minimized friction and noise due to the patented cartridge design based on the metal-rubber diaphragmmetal contact. 6. Improved response to water hammer due to the shock absorption by the rubber diaphragm of the cartridge. 7. No impact of debris on the performance of the cartridge. The design of the inlet and outlet areas makes the accumulation of particles inside the cartridge very difcult. 8. Valves are delivered assembled and tagged for easy identication. 9. From DN100 the valves are delivered with eye bolt. 10. Valve housing in Naval Bronze RG6, DN100-800, PN16 available on request with AISI 316 cartridge and fasteners for sea water applications.

BALANCING & FLOW CONTROL VALVES FRESE ALPHA WAFER DYNAMIC BALANCING vALvE

L D H

Dim

TRADELINK INDUsTRIAL ALPHA WAfER CODEs


SIZE Ductile Iron Naval Bronze SIZE Ductile Iron Naval Bronze 300 020695 350 020696 400 020711 450 020712 500 020717 600 020721 800 020727 50 020532 65 020546 80 020586 100 020642 125 020646 150 020648 200 020659 250 020692

June 2010

3.17

FRESE ALphA WAFER dYNAmIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE ALPHA WAFER DYNAMIC BALANCING vALvE
VALvE DIMENsIONs - mm
SIZE 50 65 80 100 125 150 200 250 300 350 400 450 500 600 800 L 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 D 100 119 131 163 193 216 271 326 383 443 496 545 601 715 880 H 218 237 249 281 311 334 389 440 501 561 614 663 719 833 998 kg 3.41 4.91 4.79 6.90 9.00 11.73 18.75 23.44 33.41 44.21 51.63 57.47 67.75 88.90 127.30 CART / VLv 1 1 1 2 3 4 7 12 15 19 26 33 40 56 85 MAX L/s 11.38 11.38 11.38 22.76 34.14 45.52 79.67 136.6 170.7 216.2 295.9 375.6 455.2 637.3 967.4 RG6 kg

7.59 9.90 12.90 20.63 25.78 36.75 48.63 56.79 63.22 74.53 97.79 140.03

fOR VALvEs DN50-DN800, 1.061 - 12.5 L/s


ID 5179 5184 5189 5194 5200 5206 5213 5220 5227 5235 5243 5251 5260 5269 5279 5287 5292 5298 5303 5308 FLOW L/s MIN DP kPa CARTRIDGE Kv 10.6 10.9 11.2 11.7 12.2 12.4 13.2 14.2 15.2 16.6 17.4 18.9 20.4 22.3 23.9 24.2 26.1 27.4 28.4 29.7

fOR VALvEs DN50-DN800, 1.061 - 12.5 L/s


ID 6285 6292 6301 6305 6312 6319 6326 6332 6338 6344 6349 6356 6362 6367 6373 6379 6385 6391 6393 6398 6400 6407 6407H FLOW L/s MIN DP kPa CARTRIDGE Kv 29.2 31.1 31.8 32.9 34.6 35.9 37.4 39.1 40.3 41.6 43.0 44.9 47.3 48.0 49.6 51.0 53.0 55.3 56.1 57.5 58.2 60.4 64.3

CARTRIDGE/ORIFICE TYPE 50 1.061 13 1.092 13 1.125 13 1.167 13 1.222 13 1.289 14 1.375 14 1.475 14 1.583 14 1.725 14 1.808 14 1.967 14 2.194 15 2.472 16 2.889 19 3.154 22 3.470 23 3.722 24 4.100 27 4.444 29

SPECIfICATION TEXT The valve shall operate by means of an automatic balancing stainless steel cartridges with replaceable orice plates and internal EPDM diaphragms. The pressure class of the valve shall be PN16/PN25. The valve housing shall be made of ductile iron type GGG40. The valve shall comply with anges according to EN/ANSI standards. The valve is Frese Alpha Wafer. INsTALLATION No requirements on pipe lengths before and after the valve. The valve body has ow direction indicated. A strainer is recommended according to good piping practises. Standard practise for balancing valves is to install on the return side of the terminal. The pipe system should be properly ventilated to avoid the risk of air-pockets.

CARTRIDGE/ORIFICE TYPE 60 4.733 34 5.041 34 5.221 35 5.408 35 5.684 35 5.980 36 6.236 36 6.523 36 6.815 37 7.117 38 73.690 38 7.690 38 8.099 38 8.320 39 8.605 39 8.961 40 9.324 40 9.709 40 10.093 42 10.468 43 10.724 44 11.381 46 12.500 49

NOTE: The minimum required differential pressure is measured using the measurement outlets on the valve housing. This applies to all cartridge types. In pressure ranges from 0 to 400 kPaD the ow rate is +/- 5%. In pressure ranges up to 600 kPaD the ow rate is +/10%. If measured pressure differential pressure is below minimum Dp, the ow can be found by using the Kv gures listed. Glycol mixtures (both ethylene and propylene) up to 50% are applicable. See page 3.11. ID = four digit number on the orice plate.

3.18

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE S dYNAmIC BALANCING VALVE


APPLICATION The Frese S is an externally adjustable, tamper resistant, automatic balancing valve. Each valve can be set to deliver a range of ow rates via the handle without requiring a change of the internal cartridge. Frese S is used in heating and cooling systems for the distribution of ow in various sections of the system. The dynamic balancing valve ensures easy and reliable balancing of the system, regardless of any uctations in the differential pressure of the system. Frese S limits maximum ow in the system, and ensures the most economical operation. Can be used in both variable and constant ow systems. SPECIfICATION Housing DZR Brass DP Controller PPS 40% Glass Flow Setting PPO Spring Stainless Steel Diaghragm HNBR O-Rings EPDM Pressure Class PN25 Max. Differential Pressure 400 kPa (High Pressure) 250 kPa (Low Pressure) Temperature Range -10C to + 120C BENEfITs 1. Quick and easy selection as only ow data are required. 2. Security that the specied ow will not be exceeded. 3. Easy to install and adjust according to pre-dened ow. 4. Flexibility if the system is modied after the initial installation without changing internal cartridge. 5.  Minimized commissioning time due to automatic balancing of the system. 6.  High comfort for the end-users due to right balance of the hydraulic system. 7. The valves automatically nd the hydraulic balance regardless of pressure uctations in the system. 8. No main circuit or branch balancing valves needed in the system. 9. Systems with dynamic balancing are exible, as they do not require readjustment of the 'original' circuit in case the system is extended after installation. FEATUREs 1. Removable differential pressure cartridge solution simplies ushing procedure. 2. No minimum straight pipe lengths required before or after the valve. 3. Built-in optional P/T ports, with test points, for needle system. 4. Easy adjustment of the ow by the lockable handle without changing internal cartridge. 5. Flow rate tolerance +/-5%. 6. Differential pressure operating range up to 400 kPa or 250 kPa (DN15-DN25 Low pressure). 7. The handle is for the adjustment of ow. Use a partner isolation ball valve to shut off ow.

BALANCING & FLOW CONTROL VALVES FRESE S DYNAMIC BALANCING vALvE

TRADELINK FREsE EXTENDED P/T POINT KIT CODEs


EXTENSION LENGTH Code 50mm 116157 100mm 116156

TRADELINK INDUsTRIAL FREsE S CODEs


SIZE HP LP HP = High Pressure, LP = Low Pressure. 15 113589 20 113590 25 113591 32 113592 40 113593 50

113594

June 2010

3.19

FRESE S dYNAmIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE S DYNAMIC BALANCING vALvE
SPECIfICATION The valve should be a automatic balancing valve with the option of setting the ow without interference of operation. The valve should include P/T plugs for the verication of differential pressure. The valve should only be adjustable by means of a lockable handle. FUNCTION The operation of the Frese S can be simplied by breaking it down into its two main components, a pre-adjustment unit and a differential pressure control unit. The Frese S valves, react to pressure uctations so that the differential pressure across the pre-adjustment unit is kept constant. In that way a max. ow limit is ensured in accordance with the design. FLOw CHARACTERIsTIC The illustration shows how the ow in a Frese S valve reacts in accordance to the pump pressure. For comparison we have added the typical ow characteristic for a static balancing valve. The differential pressure unit of the valve will work as soon as the differential pressure provided by the pump is sufcient. Consequently, the rated ow is maintained regardless of any pressure uctuations in the system.

Frese S

Frese S valve

SETTING THE VALvE The valve is easily set and the pre-setting is read on the scale on the handle. See ow rate graphs attached for settings. NOTE: the scale is for the adjustment of ow. If you want to shut off ow you should use a partner isolation ball valve. The handle can be locked after adjustment. Remove the cap marked 'Frese' and tighten with 5mm hexagonal key. DIMENsIONs - mm
SIZE L H H1 15 96 148 96 20 97 151 98 25 103 155 102 32 132 188 115 40 144 206 119 50 155 219 126

FLOw RATEs - L/s


SIZE Range L/s Kvs 15 0.011-0.306 HP 0.007-0.223 LP 2.4 HP / 2.2 LP 20 0.018-0.512 HP 0.011-0.351 LP 3.6 HP / 3.3 LP 25 0.025-0.653 HP 0.017-0.462 LP 4.4 HP/ 4.1 LP 32 0.060-1.328 HP 8.8 HP 40 0.049-2.067 HP 13.2 HP 50 0.122-2.868 HP 16.7 HP

3.20

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE S dYNAmIC BALANCING VALVE


FLOw VERIfICATION The ow through the valve can be identied by measuring the differential pressure (p) across the valve: -  If the measured differential pressure is above the minimum p, the ow is the one stated on the graph for the valve. - If the measured differential pressure is below the minimum p, the ow can be found by using the formulas below. FLOw CALCULATION
Q = kV p Q = kV 100 p Q = m3/h p = Bar Q = L/h p = kPa

BALANCING & FLOW CONTROL VALVES FRESE S DYNAMIC BALANCING vALvE

Q = kV p 36

Q = L/s p = kPa

Measurement of the differential pressure across the valve.

FLOw RATE EXAMPLE FREsE S, DN15 Rated ow 500 L/h - 0,0139 L/s 1. The rated ow is used as the point of reference for the overall rating of dynamic systems. (See the graph) 2. The pre-setting for the valve is found by means of the ow rate graph. Setting = 5.2. 3. To the right in the graph you will see the minimum differential pressure required from the pump by each valve. Requires 18,3 kPa.

kPa

1 2
June 2010

3.21

FRESE S dYNAmIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE S DYNAMIC BALANCING vALvE
FLOw RATE GRAPH FREsE S, DN15 HIGH PREssURE
kV (m3/h)
0,1 0,3 0,6 0,8 1,1 1,3 1,6 1,9 2,2 2,4

p kPa

Pre-set

FLOw RATE GRAPH FREsE S, DN20 HIGH PREssURE


( kV (m3/h)
0,2 0,6 1,0 1,5 1,9 2,3 2,7 3,1 3,5 3,6

p kPa

Pre-set

3.22

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE S dYNAmIC BALANCING VALVE


FLOw RATE GRAPH FREsE S, DN25 HIGH PREssURE
kV ( k
00,3 3
08 8 0 1,5 5 2,2 2 2
3

BALANCING & FLOW CONTROL VALVES FRESE S DYNAMIC BALANCING vALvE

)
33 3 38 8 4 41 4 43 3 44

2,8 8

ppkPa kPa

Pre-set

FLOw RATE GRAPH FREsE S, DN32 HIGH PREssURE


kV (m3/h)
0,6 1,8 3,0 4,1 5,2 6,3 7,3 8,1 8,7 8,8

p kPa

Pre-set

June 2010

3.23

FRESE S dYNAmIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE S DYNAMIC BALANCING vALvE
FLOw RATE GRAPH FREsE S, DN40 HIGH PREssURE
( 3 kV (m /h) 7
7,6

p kPa
9,0 10,5 11,8 12,9 13,2

0,5

2,0

4,0

5,9

Pre-set

FLOw RATE GRAPH FREsE S, DN50 HIGH PREssURE


kV (m3/h)
1,1 3,6 6,2 8,6 10,6 12,4 14,0 15,4 16,2 16,7

p kPa

Pre-set

3.24

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE S dYNAmIC BALANCING VALVE


FLOw RATE GRAPH FREsE S, DN15 LOw PREssURE
Flow Flow(l/s) l/s Flow Flow(l/h) (l/h 0,222 0 222
33 kV (m /h) (m /h 1,1 1

BALANCING & FLOW CONTROL VALVES FRESE S DYNAMIC BALANCING vALvE

800 8

0,1

0,3 0,

0,6 06

0,8

1,3

1,6 16

1,8 1,8

2,1 2

min. mi p pkPa kPa

2,2 2,2 12,8 12

0,194 0,194

700 700

12,2 12,2

0,167 0,167

600 6

11,6 1 6

0,139 0,1 9

500 5

11 1

0,111 0,11

400 4

10,4 10 4

0,083 0,08

300 3

9,8 9

0,056 0,056

200 2

9,2 92

0,028 0,028

100 1

8,6 86

4 4

5 5 Pre-set Pre-se

6 6

7 7

9 9

10 1

8 8

FLOw RATE GRAPH FREsE S, DN20 LOw PREssURE


Flow (l/s) Flow (l/h) 0,361 0,333 0,306 0,278 0,250 0,222 0,194 0,167 0,139 0,111 0,083 0,056 0,028 0

1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 0

0,2

0,5

0,9

1,4

kV (m3/h) 1,8

2,2

2,5

2,9

3,2

min. p kPa

3,3 15

14,5 14 13,5 13 12,5 12 11,5 11 10,5 10 9,5 9 1 2 3 4 5 6 7 8 9 10 8,5

June 2010

3.25

FRESE S dYNAmIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE S DYNAMIC BALANCING vALvE
FLOw RATE GRAPH FREsE S, DN25 LOw PREssURE
Flow (l/s) Flow (l/h) 0,472 0,444 0,417 0,389 0,361 0,333 0,306 0,278 0,250 0,222 0,194 0,167 0,139 0,111 0,083 0,056 0,028 0 1700 1600 1500 1400

0,2

0,7

1,3

1,9

kV (m3/h) 2,5

3,0

3,4

3,7

4,0

min. p kPa

4,1 17

16,5 16 15,5 15 14,5 14 13,5 13 12,5 12 11,5 11 10,5 10 9,5 9 0 1 2 3 4 5 Pre-set 6 7 8 9 10 8,5

1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0

3.26

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE S dYNAmIC BALANCING VALVE


SETTING & FLOw - L/s
PRE-SETTING 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5 5.2 5.4 5.6 5.8 6 6.2 6.4 6.6 6.8 7 7.2 7.4 7.6 7.8 8 8.2 8.4 8.6 8.8 9 9.2 9.4 9.6 9.8 10 15 HP 0.011 0.015 0.020 0.025 0.030 0.036 0.042 0.048 0.054 0.060 0.066 0.072 0.078 0.084 0.091 0.097 0.103 0.109 0.115 0.122 0.128 0.134 0.141 0.147 0.154 0.161 0.168 0.175 0.183 0.190 0.198 0.206 0.214 0.222 0.230 0.238 0.246 0.254 0.262 0.270 0.278 0.284 0.291 0.296 0.301 0.306 15 LP 0.007 0.009 0.012 0.015 0.019 0.023 0.028 0.033 0.038 0.043 0.048 0.053 0.058 0.063 0.068 0.073 0.078 0.083 0.087 0.092 0.097 0.101 0.106 0.110 0.115 0.120 0.125 0.130 0.135 0.140 0.145 0.151 0.156 0.162 0.168 0.174 0.180 0.185 0.191 0.196 0.202 0.207 0.212 0.216 0.219 0.223 20 HP 0.018 0.024 0.031 0.039 0.048 0.057 0.067 0.078 0.089 0.100 0.111 0.122 0.133 0.145 0.156 0.168 0.179 0.190 0.202 0.213 0.225 0.237 0.248 0.260 0.273 0.285 0.297 0.310 0.323 0.336 0.349 0.363 0.376 0.390 0.403 0.417 0.430 0.443 0.456 0.467 0.479 0.488 0.497 0.503 0.508 0.512 20 LP 0.011 0.016 0.021 0.026 0.033 0.040 0.048 0.057 0.065 0.074 0.083 0.092 0.101 0.109 0.118 0.126 0.134 0.143 0.151 0.160 0.168 0.176 0.184 0.192 0.201 0.209 0.217 0.226 0.234 0.243 0.252 0.261 0.270 0.278 0.287 0.296 0.304 0.312 0.320 0.327 0.334 0.339 0.344 0.348 0.349 0.351 25 HP 0.025 0.035 0.044 0.056 0.069 0.082 0.098 0.114 0.130 0.147 0.164 0.182 0.200 0.218 0.236 0.254 0.272 0.290 0.308 0.325 0.343 0.361 0.378 0.395 0.412 0.429 0.445 0.461 0.477 0.492 0.508 0.522 0.537 0.551 0.564 0.578 0.590 0.601 0.612 0.621 0.631 0.637 0.644 0.648 0.651 0.653 25 LP 0.017 0.025 0.032 0.041 0.051 0.061 0.072 0.083 0.095 0.108 0.120 0.133 0.146 0.158 0.171 0.184 0.197 0.210 0.223 0.236 0.249 0.261 0.274 0.286 0.298 0.310 0.321 0.332 0.343 0.354 0.365 0.375 0.385 0.395 0.404 0.413 0.421 0.428 0.435 0.442 0.448 0.452 0.456 0.459 0.460 0.462 32 HP 0.060 0.085 0.110 0.137 0.166 0.194 0.224 0.255 0.286 0.317 0.349 0.381 0.413 0.445 0.478 0.510 0.542 0.575 0.607 0.640 0.672 0.705 0.738 0.771 0.804 0.837 0.870 0.903 0.936 0.969 1.002 1.034 1.067 1.098 1.129 1.159 1.186 1.213 1.238 1.261 1.283 1.297 1.312 1.321 1.324 1.328 40 HP 0.049 0.078 0.107 0.143 0.185 0.227 0.276 0.325 0.376 0.428 0.480 0.533 0.586 0.638 0.690 0.742 0.792 0.843 0.893 0.942 0.992 1.041 1.090 1.138 1.187 1.236 1.286 1.335 1.385 1.436 1.486 1.537 1.588 1.639 1.690 1.741 1.789 1.837 1.882 1.923 1.964 1.994 2.024 2.045 2.056 2.067 50 HP 0.122 0.182 0.241 0.304 0.371 0.438 0.509 0.580 0.651 0.724 0.797 0.870 0.943 1.015 1.088 1.161 1.233 1.304 1.375 1.446 1.517 1.587 1.656 1.726 1.795 1.864 1.932 2.000 2.067 2.134 2.200 2.264 2.328 2.390 2.451 2.511 2.565 2.620 2.670 2.715 2.760 2.791 2.822 2.844 2.856 2.868

June 2010

3.27

BALANCING & FLOW CONTROL VALVES FRESE S DYNAMIC BALANCING vALvE

FRESE Sh+ dYNAmIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE SH+ DYNAMIC BALANCING vALvE
SPECIfICATION Presure Class PN 25 (25 Bar) Temperature Range -20C to 110C Plastic Parts PSU, POM Diaphragm HBNR Body Material Brass CW617N End Connections Bronze Alloy ISO or NPT O-Rings EPDM 281 Springs Stainless Steel Body Tappings 1/4" ISO DEsIGN FEATUREs Externally adjustable to 60 different ow rate settings. Pressure/Temperature ports. Range of end connections available. Sizes: 15,20,25,32, and 40mm. Flow Rate Range: 0.075 - 1.949 L/s. An SH+ valve is not a shut-off valve. ACCEssORIEs Adjustment Key Pressure/Temperature Test Fittings 1/4 ISO Drain Valve

DIMENsIONs & WEIGHTs (NOMINAL)


SIZE 15mm 20mm 25mm 25mm 32mm 40mm
1

MODEL CODE

L LENGTH

H2 HEIGHT

H1 HEIGHT

END CONNECTIONS1 F ISO 22.4 22.4 N/A 35.1 MISO 25.4 25.4 33.5 40.1 40.1 41.2 SWT 9.5 9.5 9.5 9.5 9.5 9.5

WEIGHT (kg)

SHUT OFF LEAKAGE .3% of max ow rate .5% of max ow rate

kPaD RANGE

SH 1

108.0

89.9

58.9

1.8

23 - 300

SH 2

149.1

140.0

63.0

35.1 35.1

4.5

19 - 300

Add end connection length to body length. Measured in mm unless noted.

TRADELINK INDUsTRIAL FREsE SH+ CODEs


SIZE Cu&Cu F&Cu F&F M&Cu M&F M&M 15 040274 040285 040227 040486 040268 040695 20 040280 040286 040228 040487 040269 040696 040229 040488 25 sml 040281 25 lge 040282 040288 040230 040489 040271 040699 32 040283 040289 040231 040490 040272 040701 40 040284 040290 040232 040491 040273 040702

3.28

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE Sh+ dYNAmIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE SH+ DYNAMIC BALANCING vALvE

DN 15/20/25 male/male for union programme.

DN 25L/32/40 male/male for union programme.

FLOw RATEs - L/s (+/- 5%)


DIAL SETTING 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.2
3

FLOW SH1 (15-25mm) 0.003 3 0.015 3 0.030 0.060 0.075 0.090 0.105 0.120 0.135 0.150 0.166 0.182 0.198 0.214 0.230 0.246 0.262 0.278 0.294 0.310 0.324 0.338 0.352 0.366 0.380 0.394 0.408
3

FLOW SH2 (25-40mm) 0.044 0.095 0.145 0.196 0.246 0.290 0.341 0.391 0.442 0.492 0.543 0.593 0.644 0.694 0.738 0.789 0.839 0.890 0.940 0.991 1.041 1.073 1.098 1.129 1.161 1.192 1.218 1.249

DIAL SETTING 3.3 3.4 3.5 3.6 3.7 3.8 3.9 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0

FLOW SH1 (15-25mm) 0.422 0.436 0.450 0.463 0.476 0.489 0.502 0.516 0.526 0.537 0.548 0.559 0.570 0.581 0.592 0.603 0.614 0.625 0.633 0.641 0.649 0.657 0.665 0.673 0.681 0.689 0.697 0.705

FLOW SH2 (25-40mm) 1.281 1.312 1.338 1.369 1.401 1.432 1.457 1.489 1.514 1.533 1.558 1.577 1.602 1.621 1.647 1.672 1.697 1.722 1.741 1.767 1.785 1.811 1.830 1.855 1.880 1.899 1.924 1.949

0.045 3
3

These Flow Rates are (+/- 15%)

June 2010

3.29

FRESE EVA TWO-WAY AUTOmATIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE EvA TWO-WAY AUTOMATIC BALANCING vALvE
APPLICATION Frese Eva is a valve particularly designed for the balancing of cooling and heating units. With its simple on/off control the valve can be used for many different applications, and at the same time advantage is derived from the dynamic control principle. By means of Frese Eva the optimum ow rate is ensured in each control area. This ow rate is maintained in spite of pressure uctuations in the system. (A control area may be two fan coil units for a hotel room or a calorier for a sports centre). SPECIfICATION Valve Housing Body Brass (DZR) CW602N O-Rings EPDM Pressure Class PN25 Temp. Range 0 to +95C Ambient Temp. Range 0 to +50C Max. Diff. Pressure 400 kPa Flow Range 0.007 L/s to 0.68 L/s Size Range DN15-DN25 End Connections Threaded Female Weight 0.7kg Length of Stroke 2.15mm Actuator Actuator Travel 4mm Actuator Types  24 V, on/off, normally closed 230 V, on/off, normally closed Power Consumption 1.8 Watt Closing and opening time Approx. 3min Force 100Nm Ambient Temperature 0 to +60C Protection IP54 Weight (without adaptor, inc 1m wire) 100g Connection Wire 2 x 0.75mm2 PVC Unit includes a valve adaptor and 1.0m of wire. DEsIGN FEATUREs 1. Two valves in one. Replaces both the normal static valve(DRV) and two way valve. 3. No requirement on pipe lengths before and after the valve. 2. Built-in on/off function for electrically operated actuator. (normally closed) 4. Time consuming adjustment of the system is eliminated. 5. The valve automatically ensures the hydraulic balance, regardless of changing pressure conditions in the system. 6. The valve can be easily tted into the system. 7. Integral optional P/T ports for needle system and/or drain. 8. Supplied with two colour coded P/T plugs as standard. 9. Small compact product.
20 25

2.

1.

3.

Extension piece for actuator

Spindle extension

TRADELINK INDUsTRIAL EvA CODEs


SIZE 24V, on/off, F&F 230V, on/off, F&F 15

TRADELINK FREsE EvA ACCEssORY CODEs


ACCESSORY Code P/T EXTENSION KIT 50mm 116157 P/T EXTENSION KIT 100mm 116156 EXTENSION PIECE FOR ACTUATOR SPINDLE EXTENSION DN15/20 SPINDLE EXTENSION DN25

3.30

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE EVA TWO-WAY AUTOmATIC BALANCING VALVE


DIMENsIONs - mm
SIZE L Height inc. actuator 15 102 135 20 110 135 25 119 135

BALANCING & FLOW CONTROL VALVES FRESE EvA TWO-WAY AUTOMATIC BALANCING vALvE

ELECTRIC DIAGRAM - EXAMPLE You may let the valve signal run the fan engine of the unit, so that the fan engine is not running when the valve is closed. APPLICATION EXAMPLE The system is easily balanced by adjusting the pump in accordance with the required minimum pump head across the critical valve. When this pump head is available the system will be automatically balanced. Min. required pump head is the lowest differential pressure at which the cartridge can operate plus the pressure drop of the EVA valve at design ow. See cartridge data on page 3.32.
L1 optional trafo to 24V

Actuator for Frese EVA

Relay N

It is recommendable to fit strainer and isolation ball valves.

P/T Plug Example: Frese no. 48-0012

2x

June 2010

3.31

FRESE EVA TWO-WAY AUTOmATIC BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE EvA TWO-WAY AUTOMATIC BALANCING vALvE
FOR VALvEs DN15-25, 0.007 - 0.680 L/s
ID FLOW L/s MIN DP kPa CARTRIDGE MIN DP kPa HOUSING MIN DP TOTAL kPa 7 7 7 7 8 9 10 10 11 11 12 12 13 13 14 14 15 17 17 18 19 20 23 27 31 34 35 38 43 47 51 59 61 73 82 87 95

SPECIfICATION Housing The valve housing shall be made of hot stamped Brass in DR quality. The valve shall regulate ow by means of a replaceable cartridge. Pressure rating of the valve housing shall be PN25. The Kv value of the valve housing inclusive of the on/off control unit shall be no less than 3.0. Control Unit The valve shall be NC (normally closed). The valve shall be able to close completely against a DP of 4 Bar. Flow Regulator The ow regulating cartridge shall be made of brass in DR quality. The cartridge shall offer the opportunity to change the ow by replacing an orice plate without changing the entire cartridge. The cartridge shall operate to one maximum pressure range only throughout the entire hydraulic system. INsTALLATION No requirements on pipe lengths before and after the valve. The valve body has ow direction indicated. A strainer is recommended according to good piping practises. Standard practise for balancing valves is to install on the return side of the terminal. The pipe system should be properly ventilated to avoid the risk of air-pockets. Glycol mixtures (both ethylene and propylene) up to 50% are applicable. See page 3.11.

1150 1170 1190 1210 1230 1260 1290 1300 1320 1350 1370 1400 1430 1460 1490 1510 1540 1570 1620 1725 1730 1735 1740 1745 1750 0700 0740 0770 0820 0860 0880 0920 0940 0990 1030 1060 1090

CARTRIDGE/ORIFICE TYPE 10 0.007 7 0 0.010 7 0 0.012 7 0 0.015 7 0 0.021 8 0 0.024 9 0 0.029 10 0 0.032 10 0 0.036 11 0 0.043 11 0 0.049 12 0 0.057 12 0 0.067 12 1 0.078 12 1 0.089 13 1 0.097 13 1 0.111 13 2 0.132 14 3 0.151 14 3 CARTRIDGE/ORIFICE TYPE 11 0.171 14 4 0.186 14 5 0.204 14 6 0.222 16 7 0.242 19 8 0.260 21 10 CARTRIDGE/ORIFICE TYPE 20 0.283 22 12 0.300 22 13 0.332 22 16 0.371 23 20 0.412 23 24 0.439 23 28 0.493 24 35 0.509 24 37 0.578 25 48 0.625 26 56 0.644 27 60 0.680 28 67

For the pressure drop across the entire EVA valve add the pressure drop across the valve housing (Kv = 1.9) to the min. required differential pressure of the cartridge selected above. ID = four digit number on the orice plate.

3.32

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE OpTImA pRESSURE INdEpENdENT CONTROL & BALANCING VALVE


APPLICATION Frese OPTIMA pressure independent control valve (PICV) is used in heating and cooling systems in applications with Fan Coil Units, Air Handling Units or other terminal unit applications. Frese OPTIMA provides modulating control with full authority regardless of any uctuations in the differential pressure of the system. Frese OPTIMA combines an externally adjustable automatic balancing valve, a differential pressure control valve and a full authority modulating control valve. Frese OPTIMA makes it simple to achieve 100% control of the water ow in the building, while creating high comfort and energy savings at the same time. An additional benet is that no balancing is required if further stages are added to the system, or if the dimensioned capacity is changed. DEsIGN FEATUREs 1. Less time to dene the necessary equipment for a hydraulic balanced system (only ow data are required). 2. No need to calculate valve authority. The constant differential pressure across the modulating control component guarantees 100% authority. 3. Flexibility if the system is modied after the initial installation. 4. No further regulating valves required in the distribution pipework when Frese OPTIMA is installed at terminals. 5. Total number of valves minimized due to the 3-in-1 design. 6.  Minimized commissioning time due to automatic balancing of the system. 7. Removable cartridge solution simplies ushing procedure. 8. No minimum straight pipe lengths required before or after the valve. 9.  High comfort for the end-users due to high precision temperature control. 10. Longer life due to less movements of the actuator. 11. Less energy consumption due to faster response and increased system stability. 12. The presetting function has no impact on the stroke; Full stroke modulation at all times, regardless the preset ow. 13. Automatic balancing eliminates overows, regardless of uctuating pressure conditions in the system. 14. Electrical actuator 0-10 V and 3 point control, normally closed. 15.  Differential pressure operating range up to 400 kPa. 16.  High ows with minimal required differential pressure due to advanced design of the valve. 17.  More accurate control due to long 5mm stroke. 18.  Higher presetting precision due to stepless analogue scale.

BALANCING & FLOW CONTROL VALVES FRESE OPTIMA PRESSURE INDEPENDENT CONTROL & BALANCING vALvE

A Frese strainer ball valve in the supply line combined with a Frese Optima (two way automatic balancing valve) in the return line of a cooling/heating unit.

June 2010

3.33

FRESE OpTImA pRESSURE INdEpENdENT CONTROL & BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE OPTIMA PRESSURE INDEPENDENT CONTROL & BALANCING vALvE
SPECIfICATION Valve Valve Housing and Flow Setting DZR Brass, CW602N Dp Controller PPS 40% Glass Spring Stainless Steel Diaphragm HNBR O-Rings EPDM Pressure Class PN25 Max. Diff. Pressure 400 kPa Medium Temp. Range 0C to 120C The pipe system shall be properly ventilated to avoid risk of air pockets. Glycolic mixtures up to 50% are applicable (both ethylene and propylene). Frese A/S can accept no responsibility if another actuator is used instead of the Frese actuator
25 92 66 145 1.00 32 128 72 152 1.52 40 144 87 219 2.55 50 155 93 225 3.20
H1
L H1 H

DN15 - DN32

DN40 - DN50

DIMENsIONs - mm
SIZE L H H1 Kg 15 88 65 145 0.90 20 88 65 145 0.91

FLOw RATE RANGE - L/s


SIZE Low Flow High Flow 15 0.022 - 0.174 0.068 - 0.479 20 0.036 - 0.292 0.081 - 0.566 25 0.064 - 0.478 0.081 - 0.566 32 0.129 - 0.849 40 0.562 - 1.974 50 0.612 - 2.385

Example: for high ow DN15, the maximum ow can be set between 0.068 and 0.417 l/s, according to design specications.

MINIMUM DIffERENTIAL PREssURE RANGE - kPa


SIZE Low Flow High Flow 15 14.5 - 16 14 - 18 20 14.5 - 16 14 - 22 25 14 - 16 14 - 22 32 14.5 - 18 40 16 - 26 50 19 - 32

Minimum differential pressure depends on ow rate setting, refer to ow rate charts.

FLOw COEffICIENTs - m 3 /h
SIZE Kvs LF Kvs HF 15 1.6 4.1 20 2.6 4.3 25 4.3 4.3 32 7.2 40 13.9 50 15.2

TRADELINK INDUsTRIAL OPTIMA CODEs


SIZE 24V /0..10V 24V /3 pos. 230V /3 pos. LF HF LF HF LF HF 116158 116159 113616 113615 113617 116160 116161 116162 116163 15 113608 113611 20 113609 113612 25 113610 113613 32 113614 40 115945 50 115946

TRADELINK FREsE EXTENDED P/T POINT KIT CODEs


EXTENSION LENGTH Code 50mm 116157 100mm 116156

3.34

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE OpTImA pRESSURE INdEpENdENT CONTROL & BALANCING VALVE


TECHNICAL DATA Actuator DN15-DN32 Characteristics Electrical, modulating, normally closed Protection Class IP 40 to EN 60529 Frequency 50/60 Hz Control Signal 0-10V DC, or 3 position Actuating Force 250 N Stroke 5.5 mm Ambient Operating Conditions +1C to 50C Storage -5C to 50C Humidity 5 to 85% r.F. Manual Operation 3mm hexagonal key Cable Length 1,5m Weight 350g Input Impedance >100k Ohm (DC 0...10v) Actuator DN40-DN50w Characteristics Electrical, modulating, normally closed Protection Class IP 54 to EN 60529 Frequency 50 Hz Control Signal 0-10V DC, or 3 position Actuating Force 400 N Stroke 6.5mm Ambient Operating Conditions -5C to 50C Storage -5C to 50C Humidity 5 to 95% r.F. Manual Operation Manual adjusting handle Cable Not included Weight 600g Input Impedance >100k Ohm (DC 0...10v) MANUAL OPERATION Manual operation should be performed after disconnecting from the power supply. If the operation is performed manually without disconnecting from the power, the supply must be disconnected and then reconnected, whereby the actuator will start the calibration process and correctly adjust itself. Do not forget that a manually operated valve must go through the calibration process before commencing normal operation again. TYPEs & OPERATION DATA
VALvE DIM DN15-DN32 DN15-DN32 DN15-DN32 DN40-DN50 DN40-DN50 DN40-DN50 FUNCTION DC 0..10 V 3 - position 3 - position DC 0..10 V 3 - position 3 - position RUNNING TIME (50 HZ) 75s 150s/5.5mm 150s/5.5mm 43s/6,5mm 43s/6,5mm 170s/6,5mm SUPPLY VOLTAGE AC/DC 24 V +/- 25% AC 24 V +/- 20% AC 230 V +/- 15% AC 24 V +/- 20% AC 24 V +/- 20% AC 230 V +/- 15% POWER CONSUMPTION 2,5 VA 0,8 VA 6 VA 4,5 VA 2,0 VA 2,5 VA PARALLEL OPERATION NO. OF ACTUATOR Max. 10 Max. 24 Max. 6 Max. 10

June 2010

3.35

BALANCING & FLOW CONTROL VALVES FRESE OPTIMA PRESSURE INDEPENDENT CONTROL & BALANCING vALvE

FRESE OpTImA pRESSURE INdEpENdENT CONTROL & BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE OPTIMA PRESSURE INDEPENDENT CONTROL & BALANCING vALvE
4 5

F 4

DEsIGN The design of Frese OPTIMA combines high performance with small size and compact construction. The main components of the valve are: 1. The pressure control cartridge 2. The modulating control component 3. The presetting scale (not accessible when the actuator is mounted) 4. The P/T plugs (optional) 5. The electrical actuator COMMIssIONING The Frese Optima is delivered to Australian customers with a commissioning cap and the pressure control cartridge installed. The commissioning cap keeps the modulating component in a fully open position to aid the ushing process. For automatic balancing valves a backush is recommended as a forward ush with the pressure control cartridge installed will begin to operate and limit the ow to the valves maximum owrate. During ushing the valve must be in the fully open position. Tags, labels, and a presetting list can be supplied with each valve upon request. At this point the user can then adjust the presetting dial to the design ow. Once the ow is set, the actuator can be mounted (this also prevents tampering of the presetting) and the valve is ready to operate. Pre-settings can be checked simply via ow vs. presetting graphs page 3.38 to 3.42.

2 1

Actuator 5

SPECIfICATION TEXT The actuated valve shall operate by means of an automatic balancing cartridge that can be removed without dismantling the valve. The presetting of the valve shall not inuence the length of the stroke. The pressure class shall be PN25. The differential pressure operating range shall be up to 400kPa. The valve shall operate by means of an electrical modulating actuator.

Pre-setting scale 3

Modulating control component

Pressure control cartridge

4 P/T

plugs

3.36

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE OpTImA pRESSURE INdEpENdENT CONTROL & BALANCING VALVE


Flow Rate vs. Differential Pressure (Preset ow: 625 l/h, 300 l/h)
Flow (l/h)

OPERATION PRINCIPLE The innovative design of Frese OPTIMA introduces a modulating control component that retains 100% authority at all times. With the Frese OPTIMA, there are two independent movements for the presetting and the modulating function. During presetting, the inlet area moves radially without interfering with the length of the stroke. During modulating, the inlet area moves axial taking advantage of the full stroke. In the example, the ow is modulated throughout the full range from 10 to 0V regardless of the preset ow (i.e. 625 l/h or 300 l/h). Whilst the control component provides proportional modulation irrespective of the preset ow, the automatic balancing cartridge guarantees that the ow will never exceed the maximum preset ow. Regardless of pressure uctuation in the system, the maximum ow is kept constant up to a maximum differential pressure of 400kPa.

BALANCING & FLOW CONTROL VALVES FRESE OPTIMA PRESSURE INDEPENDENT CONTROL & BALANCING vALvE

(kPa)

Flow Rate vs. Voltage (Preset ow: 625 l/h, 300 l/h)
Voltage (V ) Pre-setting

Flow l/h

Flow Rate vs. Differential Pressure (Voltage: 10V, 6V, 3V)


Flow (l/h)

10V

6V

3V

(kPa)

June 2010

3.37

FRESE OpTImA pRESSURE INdEpENdENT CONTROL & BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE OPTIMA PRESSURE INDEPENDENT CONTROL & BALANCING vALvE
FREsE OPTIMA DN15, LOw FLOw
0.194

Flow l/s l l

Flow l/h l l
700

0.2

0.4

0.6

Kv (m3/h) K (m 0.8 )

1.0

1.2

1.4

1.6

min. p kPa i

16.0 0.167 600

0.139

500 15.7

0.111

400 15.1

0.083

300

0.056

200 14.5

0.028

100

0.5

1.5

Pre-set

2.5

3.5

FREsE OPTIMA DN15, HIGH FLOw

Flow l/s
0.500 0.444 0.389 0.333 0.278 0.222 0.167 0.111 0.056 0

Flow l/h
1800 1600 1400 1200 1000 800 600

0.7

1.3

2.0

Kv (m3/h)
2.5

3.1

3.5

3.8

4.1

min. p kPa

18.0

17.0

15.8

14.0 400 200 0

0.5

1.5

Pre-set

2.5

3.5

3.38

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE OpTImA pRESSURE INdEpENdENT CONTROL & BALANCING VALVE


FREsE OPTIMA DN20, LOw FLOw

BALANCING & FLOW CONTROL VALVES FRESE OPTIMA PRESSURE INDEPENDENT CONTROL & BALANCING vALvE

0.306 0.278 0.250 0 25

Flow l l/s l

1100 1000

Flow l/h F l

0.3 03

0.7 7

1.0 1

3 Kv (m (m /h) h)

1.4 1

1.7 17

2.0 20

2.3 23

2.6 26 16.0

min. p p kPa kP

900 900 800 800 700 700 600 600 500 500 400 00 300 300 200 200 100 100 0 00 0 0.5 5 1 1 1.5 15 2 2 2.5 25 3 3 3.5 35 4 14.5 1 5 15.1 15 1 15.7 15

0.222 0 222 0.194 0 19 0.167 0 16 0.139 0 13 0.111 0 111 0.083 0 083 0.056 0 05 0.028 0 02 0

Pre-set P

FREsE OPTIMA DN20, HIGH FLOw

Flow l/s
0.611 0.556 0.500 0.444 0.389 0.333 0.278 0.222 0.167 0.111 0.056 0

Flow l/h
2200 2000 1800

0.8

1.5

2.2

Kv (m3/h)
2.7

3.3

3.8

4.2

4.3

min. p kPa

22.0

20.0 1600 1400 1200 1000 800 600 400 200 0 0 0.5 1 1.5 2 2.5 3 3.5 4 14.0 18.0

Pre-set

June 2010

3.39

FRESE OpTImA pRESSURE INdEpENdENT CONTROL & BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE OPTIMA PRESSURE INDEPENDENT CONTROL & BALANCING vALvE
FREsE OPTIMA DN25 LOw FLOw r s O T T MA DN 2 ow
0.500 0 500 0.444 0 0.389 0 389 0.333 0.278 0 278 0.222 0 222 0.167 0.111 0.056 0 056 0

Flow Flo l/s l

1800 1800 1600 1600 1400 1 00 1200 1000 1000 800 800 600

Flow Flow l/h h

0.6 0

1.3 13

2.0 20

3 Kv Kv (m m3/h) h) 2.6

3.2 32

3.7 3

4.1 1

43 3 16 0

min. m p p kPa k a

15 5 5

14 8

14.0 400 200 200 0 0 0 0.5 1 1.5 2 2.5 3 3.5 4

Pre-set t

rese DN25 High FREsE OPTIMA DN25 HIGH FLOw r se O O T MA MA DN2 i h


Flow l/s
0.611 0.556 0.500 0.444 0.389 0.333 0.278 0.222 0.167 0.111 0.056 0

Flow l/h
2200 2000 1800

0.8

1.5

2.2

Kv (m3/h)
2.7

3.3

3.8

4.2

4.3

min. p kPa
22.0

20.2 1600 1400 1200 1000 800 600 400 200 0 0 0.5 1 1.5 2 2.5 3 3.5 4 14.0 18.0

Pre-set

3.40

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE OpTImA pRESSURE INdEpENdENT CONTROL & BALANCING VALVE


FREsE OPTIMA DN32

BALANCING & FLOW CONTROL VALVES FRESE OPTIMA PRESSURE INDEPENDENT CONTROL & BALANCING vALvE

ese OPTI

Flow l/s
0.903 0.833 0.764 0.694 0.625 0.556 0.486 0.417 0.347 0.278 0.208 0.139 0.069 0

Flow l/h
3250 3000 2750 2500 2250 2000 1750 1500 1250 1000 750 500 250 0 0

1.3

2.4

3.5

Kv (m3/h)
4.5

5.5

6.2

6.8

7.2

min. p kPa

18.0

17.0

16.0

14.5

0.5

1.5

Pre-set

2.5

3.5

FREsE OPTIMA DN40

Flow l/s
2.083 1.994 1.806 1.667 1.528 1.389 1.250 1.111 0.972 0.833 0.694 0.556 0.417 0.278 0.139 0

Flow l/h
7500 7000 6500 6000 5500 5000 4500 4000 3500 3000 2500 2000 1500 1000 500 0 0

5.1

8.7

11.2

Kv (m3/h)
12.8

13.6

13.8

13.8

13.9

min. p kPa
26 25 22.5 20

18

16.5

16

0.5

1.5

Pre-set

2.5

3.5

June 2010

3.41

FRESE OpTImA pRESSURE INdEpENdENT CONTROL & BALANCING VALVE


BALANCING & FLOW CONTROL VALVES FRESE OPTIMA PRESSURE INDEPENDENT CONTROL & BALANCING vALvE
FREsE OPTIMA DN50

Flow (l/s)
2,500 2,361 2,222 1,994 1,806 1,667 1,528 1,389 1,250 1,111 0,972 0,833 0,694 0,556 0,556 0,417 0,278 0,139 0

Flow (l/h)
9000 8500 8000 7500 7000 6500 6000 5500 5000 4500 4000 3500 3000 2500 2000 1500 1000 500 0 0

5,1

9,2

11,9

Kv (m3/h)
13,4

14,4

15,0

15,1

15,2

min. p kPa
32 30 29 28 25

22

19

0.5

1,5

Pre-set

2,5

3,5

SETTINGs & FLOw - L/s


PRE-SET 0.5 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 DN15 LF 0.022 0.026 0.035 0.043 0.052 0.061 0.069 0.078 0.087 0.096 0.105 0.113 0.121 0.130 0.139 0.148 0.156 0.165 0.174 DN15 HF 0.068 0.082 0.110 0.139 0.168 0.197 0.225 0.253 0.280 0.306 0.332 0.357 0.379 0.401 0.421 0.439 0.454 0.468 0.479 DN20 LF 0.036 0.044 0.059 0.073 0.087 0.102 0.117 0.132 0.146 0.160 0.175 0.190 0.205 0.219 0.233 0.248 0.262 0.277 0.292 DN20 HF 0.081 0.097 0.129 0.160 0.192 0.224 0.256 0.288 0.320 0.352 0.383 0.414 0.444 0.472 0.498 0.520 0.540 0.556 0.566 DN25 LF 0.064 0.078 0.106 0.135 0.164 0.193 0.222 0.251 0.279 0.306 0.333 0.358 0.381 0.403 0.423 0.441 0.456 0.468 0.478 DN25 HF 0.081 0.097 0.129 0.160 0.192 0.224 0.256 0.288 0.320 0.352 0.383 0.414 0.444 0.472 0.498 0.520 0.540 0.556 0.566 DN32 0.129 0.154 0.205 0.256 0.306 0.357 0.407 0.456 0.504 0.550 0.595 0.637 0.677 0.715 0.749 0.779 0.806 0.830 0.849 DN40 0.562 0.651 0.825 0.983 1.125 1.258 1.380 1.492 1.595 1.683 1.760 1.826 1.879 1.921 1.947 1.963 1.971 1.974 1.974 DN50 0.612 0.737 0.980 1.205 1.400 1.574 1.725 1.854 1.964 2.050 2.123 2.184 2.236 2.279 2.314 2.343 2.366 2.381 2.385

3.42

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

FRESE CIRCON+/TEmCON+ ThERmOSTATIC VALVE


APPLICATION CirCon+ and TemCon+ are control valves designed for domestic hot water installations with circulation. The valves automatically control the temperature of the water that circulates through the valves. Thus the thermal balance is ensured throughout the domestic hot water system. The valve is adjusted on a scale to a desired temperature in the interval between 37C and 65C. TemCon+ is equipped with a by-pass located outside the thermal part of the valve. So, TemCon+ is suited for hot water installations with bacterial problems, eg Legionella. Here a procedure of raising the temperature of the water to between 70C and 80C is carried out at certain intervals. SPECIfICATION Body DR Brass CW602N O-Rings EPDM Springs Stainless Steel Element Wax Plastic Parts POM, ABS, PC By-Pass TemCon+ Stainless Steel Surface Coating Tin/Nickel Temperature Range 37C - 65C Accuracy +/- 2C < 100 kPa Dp P-Band 10C (Xp = 10K) Max. Kv-Value 1.10 (m3/h) Recommended Differential Pressure 3-10 kPa Max. Diff. Pressure 100 kPa Max. Static Pressure 1000 kPa Pressure Class CirCon+: PN16, TemCon+: PN10 Connections Threaded Actuator Controlled By-pass, TemCon+ Kv-value, Open By-pass Running Time Power Consumption Supply Voltage DEsIGN FEATUREs 1. The thermostatic element is located out of contact with the circulating water, and its dry location prevents scale problems. 2. The setting of the valves is stepless between 37C and 65C at an accuracy of +/-2C. 3. Each valve is calibrated seperately. 4. The valves are coated with tin/nickel, which is an anticorrosive coating. 5. TemCon+ has a by-pass for high-temperature operation from 70C to 80C. 6. TemCon+ by-pass adjustment occurs by hand or actuator.
20

BALANCING & FLOW CONTROL VALVES FRESE CIRCON+/TEMCON+ THERMOSTATIC vALvE

0.3 (m3/h) 180 sec from closed to fully open 2W 24 V DC/AC or 230 V AC

TRADELINK INDUsTRIAL TEMCON+ CODEs


SIZE F&F F&F w/ball vlv M&M w/ball vlv With Actuated By-pass F&F F&F w/ball vlv M&M w/ball vlv 15

TRADELINK INDUsTRIAL CIRCON+ CODEs


SIZE F&F F&F w/ball vlv M&M w/ball vlv 15 20 088747

June 2010

3.43

FRESE CIRCON+/TEmCON+ ThERmOSTATIC VALVE


BALANCING & FLOW CONTROL VALVES FRESE CIRCON+/TEMCON+ THERMOSTATIC vALvE
H

Ball e valve

AllCirCon + valves have the approval of the Danish VA-Authorities.

DIMENsIONs - mm CIRCON+
SIZE Ends L B H kg * with integral ball valve. 15 F&F 63 32 96 0.5 20 F&F 63 32 96 0.5 20* F&F 79 37 96 0.6 20* M&M 79 37 96 0.6

OPERATION PRINCIPLE - CIRCON+ THERMAL CONTROL Circon+ controls on the basis of the temperature of the water that circulates through the valve. If the valve is set to a temperature of e.g. 50C, and the temperature of the circulating water is under 50C, the valve opens. If the temperature is over 50C, the valve closes. To Set The temperature setting is between 37C and 65C. Remove the cap, and the temperature is easily set by a screwdriver as shown here. APPLICATION EXAMPLE - CIRCON+
Draw-off taps Draw-off taps Draw-off taps

Hot-water tank

Cold water
C

Domestic hot water


CR

Cirkulating pump Distribution pipe

Frese no. 35-1138

It is recommendable to install pressure test points on both sides of the critical CirCon+ valve in the installation for the verification of differential pressure.

3.44

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

CR

FRESE CIRCON+/TEmCON+ ThERmOSTATIC VALVE


DIMENsIONING EXAMPLE The CirCon+ and TemCon+ is dimensioned on the basis of the thermal loss in the circuit, in which it is located. Example In an installation with 4 oors and basement a circulation line is dimensioned. The following parameters should be known for the calculation of the ow rate. Length of Pipe  30m, total length of pipe controlled by thermostatic valve. Thermal Loss  9 W/m of pipe, Thermal loss in an external 27mm pipe with 30mm insulation and a difference of 40C between room temperature and temperature of uid. Temp Differential  5C, temperature in hotwater tank is 55C. The CirCon+ was set to 50C on the scale. The ow rate can be found from the following formula: Q = (30m x 9W/m) x 0.86 = 46 l/h 5C DIMENsIONs - mm TEMCON+
SIZE Ends L B H kg * with integral ball valve. 15 F&F 63 58 99 0.6 20 F&F 63 58 99 0.6 20* F&F 79 58 99 0.6 20* M&M 79 58 99 0.6 79 86 120 0.75 WITH ACT.

BALANCING & FLOW CONTROL VALVES FRESE CIRCON+/TEMCON+ THERMOSTATIC vALvE

T mC o

5
0

So, the total quantity of water from 3 delivery pipes to the circulating pump is approx. 138 l/h (3 x 46) The Kv-value of the thermostatic valve at 46l/h and a differential pressure of 10 kPaD across the valve can be found from the following formula: Kv = Q SQRT(Dp) = (46/SQRT 10)/100 = 0.15

OPERATION PRINCIPLE - TEMCON+ CONTROL AT TwO OPERATING TEMPERATUREs TemCon+ was designed to control two sets of temperatures: Normal Operating Temperature Normal operation occurs at temperatures from approx. 50C to 60C. That is economic operation at low precise ow rates, which ensures a high level of comfort at all draw off taps and exact termperature in all circuits. High Operating Temperature High operating temperature is used at intervals for the pasteurization of domestic water at 70C to 80C. To Set The plastic cap is dismantled by means of a screwdriver that ts into the slot in the cap. Then the manually operated by-pass can be set steplessly to a Kv-value between 0.0 and 0.3.

June 2010

3.45

FRESE CIRCON+/TEmCON+ ThERmOSTATIC VALVE


BALANCING & FLOW CONTROL VALVES FRESE CIRCON+/TEMCON+ THERMOSTATIC vALvE
APPLICATION EXAMPLE - TEMCON+
Draw-off taps Draw-off taps Draw-off taps

Hot water tank

Cold water Hot water-/ circulation pipe

Circulating pump

BMS
The control during high temperature operation occurs as the actuator mounted on the by-pass opens to a fixed Kv-value of 0.3.

Frese no. 35-1138

It is recommendable to install pressure test points on both sides of the critical TemCon+ valve in the installaton for the verification of differential pressure.

DIMENsIONING EXAMPLE During normal operation the TemCon+ is dimensioned in the same way as the Circon+. TemCon+ - Actuated by-pass The automatic heater or BMS opens the by-pass to a xed Kv-value of 0.3, continuing with the above example: Length of Pipe 30m, same as above. Thermal Loss  14 W/m of pipe, same pipe as above except with temperature difference of 60C. Temp Differential  8C, temperature in hotwater tank is 80C and temperature after TemCon+ is 72C. The ow rate for TemCon+ by-pass: Q = (30m x 14W/m) x 0.86 = 45 l/h 8C The minimum differential pressure of the TemCon+ valve at Kv 0.3: Dp = [45 / (0.3 x 1000)]2 = 2 kPaD Hydraulic Balance: The application of a circulating pump with proportional control of the pump pressure is recommended if a xed Kv-value of 0.3 is too much for the installation so that the hydraulic balance is upset. The pump compensates for increased ow by increasing the differential pressure. TemCon+ - Adjustable by-pass On the basis of the example above: Q = (30m x 14W/m) x 0.86 = 45 l/h 8C

The differential pressure across the TemCon+ at the given location in the system should be known in order to nd the value of the adjustable by-pass. Here we use 35 kPaD across the valve and Kv can be found as follows: Kv = Q = (0.045/SQRT 0.35) = 0.08 SQRT(Dp) Normal Operation: During normal operation is tis recommended to close the adjustable by-pass to gain all the benets of the thermal control of the TemCon+ valve. WIRING DIAGRAM - TEMCON+

L
2 3 0 V DC/ 2 4 V

Actuator

Installation of actuator. The actuator must not be installed upside down.

3.46

The information provided in this catalogue is based on original manufacturers designs and specications and subject to change without notice. Crane Distribution accepts no liability for the accuracy of the information or the availability of products.

Vous aimerez peut-être aussi