Warranty and liability ............................................................................................... 2 1 2 3 4 5 Task................................................................................................................. 4 Creating a Full PH Database Backup............................................................. 5 Restore Historian Storage Database ........................................................... 13 Related literature .......................................................................................... 23 History .......................................................................................................... 23
Copyright
10/2013
1 Task
Task
The non-redundant Process Historian (PH) machine is because of some reason broken. The PC must be exchanged and new installed. The already existing database should be used for the new installation. Therefore one needs a full database backup. This full DB backup can be restored to a PH Database after exchanging the machine. This document offers a guideline for the following Scenarios. 1. New installation of PH software on the existing hardware 2. PH hardware exchange due to hardware defect In both scenarios an existing PH database shall be used without data loss. Data which is available on the OS revolving archive, but not in the PH database, can be recovered against the OS revolving archive. To make sure that the data are available inside of the OS archive, we recommend creating a full database backup file in half of the time range the OS archive is configured.
Introduction
Example
Siemens AG 2013 All rights reserved
The OS archive contains 4 Weeks of data. In this case one should generate a full database backup every 2 weeks. That means in the worst case the data of two weeks must be recovered against the OS archive. Prerequisite The computer name doesn't change The PH is non-redundant Additional reasons to create a full data backup of the Process Historian database All runtime database segments, which are visible inside of the Segmentation menu of the PH Management Console, must be backuped with a full database backup. Segment backups created with help of the PH Management Console menu Backup and Restore, can be restored in a Historian Storage database they are created from. It is not possible to restore a PH segment backup into an empty Historian Storage database.
Copyright
10/2013
Table 2-1 No. 1. Action Deactivate the PH with help of the PH Management Console. Use the drop down menu and choose shutdown and click on the Go button.
Copyright
2.
3.
10/2013
No. 4.
Action Close the Process Historian Management Console on the Process Historian. An open Process Historian Management Console can be the reason that a full database backup fails.
5.
Close the Process Historian Icon in the task bar. Execute a right mouse click on the PH Icon. Choose the function Exit.
6.
Open the SQL Server Management Studio as administrator. With help of the menu Start > All Programs > Microsoft SQL Server 2008 R2 > SQL Server Management Studio > Run as administrator
Copyright
10/2013
No. 7.
Action Connect to the Process Historian SQL Server. The server name is <PH computer name>\HISTORIAN.
8.
Create a full Database Backup. Expand the folder Databases > perform a right mouse click on the DB folder Historian Storage > click on the menu Tasks > click on the function Back Up.
Copyright
10/2013
No. 9.
10.
Copyright
10/2013
No. 11.
12.
Define the backup destination and the backup file name and click on the OK button.
Copyright
10/2013
Action
Result:
Copyright
10/2013
10
No. 14.
Action Choose the Option page and mark the radio button "Backup to new media set, and erase all existing backup sets.Click on the OK button to start the backup execution.
15.
Result:
Copyright
10/2013
11
Action
NOTE
A file of a full database backup could be huge, if the database is huge! Creating a huge backup file is also time consuming. There are different reasons because a full database backup fails, for instance concurrent database connections. If a full database backup on a running PH fails, the PH Services must be deactivated before creating a full database backup. The following table shows the steps which have to be executed if a full backup fails:
NOTE
Table 2-2 No. 17. Action Open the Microsoft Server Manager on the PH and deactivate the Process Historian Maintenance Service.
Copyright
18.
19. 20.
Close the Microsoft Server Manager. Start the full database backup procedure.
10/2013
12
Table 3-1 No
Siemens AG 2013 All rights reserved
Action Check if a full database backup file is available. Deactivate the PH with help of the PH Management Console. Use the drop down menu and choose shutdown and click on the Go button.
1. 2.
Copyright
3.
10/2013
13
Action
5. 6.
Close the PH Management Console. Close the Process Historian Icon in the task bar. Execute a right mouse click on the PH Icon. Choose the function Exit.
7.
Siemens AG 2013 All rights reserved
Open the Microsoft Server Manager on the Process Historian. Click on Start > Type Server Manager into the input box > Click on the Server Manager Program Icon.
Copyright
10/2013
14
No 8.
Action Deactivate the Process Historian Maintenance Service. Execute a right mouse click on the Process Historian Maintenance Service > Execute the Stop function > wait until the service is stopped.
9.
Deactivate the SIMATIC Process Historian Service. Execute a right mouse click on the SIMATIC Process Historian service > execute the Stop function > wait until the service is stopped.
Copyright
10.
10/2013
15
No 11.
Action Open the SQL Server Management Studio as administrator. With help of the menu Start > All Programs > Microsoft SQL Server 2008 R2 > SQL Server Management Studio > Run as administrator.
12.
Copyright
Connect to the Process Historian SQL Server. The server name is <PH computer name>\HISTORIAN.
10/2013
16
No 13.
Action Expand the folder Databases > execute a right mouse click on the database Historian Storage> click on the menu Tasks > execute the Detach function.
Copyright
14.
Choose the option Drop Connections and click on OK. Wait until the database is detached.
10/2013
17
Action
16.
Siemens AG 2013 All rights reserved
Rename the original storage location for the existing Historian Storage database with help of the Microsoft Explorer, to avoid overwriting. Create a new, empty folder structure with the original naming for restore purpose.
Copyright
17.
Use the SQL Server Management Studio and execute a right mouse click on the Database folder. Click on Restore Database function.
10/2013
18
No 18.
Action Choose the radio button From device and click on the button to choose a backup file.
Copyright
19.
10/2013
19
No 20.
Action Choose Files of type = All Files(*) and choose the database backup file. Click on the OK button.
Copyright
21.
Choose in the drop down menu To database = Historian Storage and select the backup set to restore via checkbox Restore. Click on the OK button.
10/2013
20
No 22.
Action The restore function will be executed. Wait until the restore process has finished. Click on the OK button
23.
Copyright
24.
Reboot the PH System. The PH will automatically change into state Active.
5)
10/2013
21
No 25.
Action Refresh the Information Server data source, as in the following steps. Open the Internet Explorer on the Information Server and connect to the Information Server. Open the Administration menu > click on the Process Historian project > Click on the Refresh button.
NOTE
1)
Copyright
In case the PH has been installed completely new, and the Process Historian database installation wizard wasnt executed, there is no Historian Storage database which must be detached.
2)
In case the PH has been installed completely new, and the Process Historian database installation wizard has been executed, the Historian Storage database is empty and can be deleted.
4)
In this example, just in case, the original Historian Storage database is also stored on the disc drive, but therefore enough disc capacity is needed.
5)
After a Process Historian system restart the Process Historian changes into the state active. After approximately 30 minutes the system will create a recovery against the OS archive to close the data gap. Therefore time synchronization between the Process Historian and the OS Systems is mandatory.
CAUTION
3)
If you delete an existing Historian Storage database which contains the process data, without having a healthy and complete full database backup file, you lose your process data.
10/2013
22
4 Related literature
4
Table 4-1
Related literature
Topic Title / Link
www.siemens.com/industry/onlinesupport/pcs7 http://support.automation.siemens.com/WW/view/en/66579062 http://support.automation.siemens.com/WW/view/en/68099510/0/en http://support.automation.siemens.com/WW/view/en/64906050
SIMATIC PCS 7 in Industry Online Support - Overview Page Download page of this entry Process Historian 2013 Administration Creating Report Templates for the Information Server on the Process Historian Database in the PCS 7 Environment
5
Siemens AG 2013 All rights reserved
History
Version V1.0 Date 10/2013 First version Modifications
Table 5-1
Copyright
10/2013